Danfoss CI 61, CI 73, CI 86 Installation guide [ar]

Instructions
037C3012
Contactors CI 61, CI 73, CI 86
CBD-, CBD S-, RCD-
1 x 2.5 ... 35mm² 2 x 2.5 ... 25 mm² No. 14 ... 2 AWG 75°C Cu wire
1 x 2.5 ... 50 mm² 2 x 2.5 ... 35 mm² No 14 ... 2 AWG
037C3012
3.5 ... 6 Nm 31 ... 52 lb-in
1 x 1 ... 2.5 mm² 2 x 1 ... 2.5 mm² No. 16 ... 12 AWG
1 ... 1.5 Nm
8.9 ... 13 lb-in
75°C Cu wire
1 x 1 ... 4 mm²
No. 3 2 x 1 ... 4 mm² No 16... 12 AWG
Pozidrive No. 2
USA/ CND
Suitable for use on a circuit capable of delivering not more than xxx rms symmetrical amperes
IEC 6094-4-1 EN 60947-4-1 Ue 690 V
CI 61 CI 73 CI 86
Min. distance lateral to grounded parts or walls = 6mm
Type 1 Type 2
250 A 250 A 250 A
160 A 160 A 160 A
Type 2
Size Standard Fault Currents High Available Fault Currents
Max. fuse Max. Circuit breaker Max. Class J Fuse Max. Circuit Breaker
600 V max. 600 V max. 480 V max.
XXX = 5.000 XXX = 100.000 XXX = 65.000
CI 61 200 A 200 A 80 A 100 A
XXX = 10.000 CI 73 250 A 250 A 100 A 100 A CI 86 300 A 250 A 150 A 100 A
CI 61, CI 73 + TI 80
CI 86 + TI 86
IC.PI.C10.A2.00 - 520B3342
Instructions
037C3012
CBD S-
037C3012
RCD
1... 1,5 Nm 8,9... 13 lb-in
Coil
©Danfoss A/S 09-2008 (AC-BNM/mr) IC.PI.C10.A2.00 - 520B3342