Instructions
037C3012
18mm
Contactors CI 61, CI 73, CI 86
CBD-, CBD S-, RCD-
1 x 2.5 ... 35mm²
2 x 2.5 ... 25 mm²
No. 14 ... 2 AWG
75°C Cu wire
1 x 2.5 ... 50 mm²
2 x 2.5 ... 35 mm²
No 14 ... 2 AWG
037C3012
3.5 ... 6 Nm
31 ... 52 lb-in
1 x 1 ... 2.5 mm²
2 x 1 ... 2.5 mm²
No. 16 ... 12 AWG
1 ... 1.5 Nm
8.9 ... 13 lb-in
75°C Cu wire
1 x 1 ... 4 mm²
No. 3
2 x 1 ... 4 mm²
No 16... 12 AWG
Pozidrive No. 2
USA/ CND
Suitable for use on a circuit capable of delivering not more than xxx rms symmetrical
amperes
IEC 6094-4-1
EN 60947-4-1
Ue ≤ 690 V
CI 61
CI 73
CI 86
Min. distance lateral
to grounded parts
or walls = 6mm
Type 1 Type 2
250 A
250 A
250 A
160 A
160 A
160 A
Type 2
Size Standard Fault Currents High Available Fault Currents
Max. fuse Max. Circuit breaker Max. Class J Fuse Max. Circuit Breaker
600 V max. 600 V max. 480 V max.
XXX = 5.000 XXX = 100.000 XXX = 65.000
CI 61 200 A 200 A 80 A 100 A
XXX = 10.000
CI 73 250 A 250 A 100 A 100 A
CI 86 300 A 250 A 150 A 100 A
CI 61, CI 73 + TI 80
CI 86 + TI 86
IC.PI.C10.A2.00 - 520B3342
Instructions
037C3012
CBD S-
037C3012
RCD
1... 1,5 Nm
8,9... 13 lb-in
Coil
©Danfoss A/S 09-2008 (AC-BNM/mr) IC.PI.C10.A2.00 - 520B3342