Installation guide
Contactors CI 6 - CI 30
Thermal overload relays TI 16C - TI 25C - TI 30C
Before installing the contactor, make sure that the control voltage supply corresponds with the specified voltage.
Wrong control voltage across the terminals (A1 and A2) can cause contactor chattering or coil overheating and damage.
037C0615
Control voltage must be applied within tolerances given below:
- Standard coil: from -15% to 10%
- Double frequency coil: ±10%
037C0615
circuits capable of delivering not more than 100 000 rms
symmetrical amperes, 600 V maximum when protected
by Class J fuses
© Danfoss | DCS (az) | 2017.10
TI 16C / TI 25C / TI 30CConditional Short Circuit Rating - Suitable for use on
IC.PI.C10.C2.00 | 520B7001 | 1
Contactors CI 32 - CI 50
Thermal overload relay TI 80
Before installing the contactor, make sure that the control voltage supply corresponds with the specified voltage.
Wrong control voltage across the terminals (A1 and A2) can cause contactor chattering or coil overheating and damage.
Control voltage must be applied within tolerances given below:
- Standard coil: from -15% to 10%
- Double frequency coil: ±10%
circuits capable of delivering not more than 100 000 rms
symmetrical amperes, 600 V maximum when protected
by Class J fuses
© Danfoss | DCS (az) | 2017.10
TI 80Conditional Short Circuit Rating - Suitable for use on
IC.PI.C10.C2.00 | 520B7001 | 2