Danfoss CI 5 Data sheet

Data sheet
Minicontactors CI 5-
CI 5- minicontactors cover the power range up to
5.5 kW and are available for AC and DC coil voltages enabling reliable working with extremely low and high voltage uctuations.
Characteristic of the minicontactors is that they are compact and suitable for applications where space is at a premium. With add-on auxiliary contact blocks, timers and other additional accessories they oer high exibility.
One of the most important features is status feedback provided by mechanically linked and mirror contact performance in conrmity with IEC 60947-4-1 and 60947-5-1.
Additionally the CI 5- ensures safety against electric shock by extra protective distance between housing surfaces and live parts.
The CI 5- programme includes dedicated bimetallic overload protection relay with a dierential mechanism for sensitivity to phase­loss conditions.
Features • Compact design
• High exibility
• Power range up to 5.5 kw
• For ac and dc coil voltages
© Danfoss | DCS (im) | 2017.07
IC.PD.C10.F4.02 | 520B8097 | 1
Data sheet | Minicontactors, Type CI 5-
Ordering
Minicontactors CI 5-, for AC and DC coil voltage
Type
U
e
230 – 240
V kW
AC-3 load
U
e
400 – 690
V kW
Main circuit
I
e
A
Ith 2)
(AC-1)
Open
A
Ithe 3)
(AC-1)
Encl.
A
Main
contacts
number
Built-in auxiliary contacts Number/ Function
Code no.1)
CI 5-2 40E4) 104) 64) 4 NO 037H3500
CI 5-2 22Z4) 104) 64) 2 NO, 2 NC 037H3501
CI 5-5 10 1.5 2.2 4.9 20 16 3 1 NO 037H3502
CI 5-5 01 1.5 2.2 4.9 20 16 3 1 NC 037H3503
CI 5-9 10 3.0 4.0 8.5 20 16 3 1 NO 037H3504
CI 5-9 01 3.0 4.0 8.5 20 16 3 1 NC 037H3505
CI 5-9 M40 3.0 4.0 8.5 20 16 4 037H3506
CI 5-12 10 3.0 5.5 11.5 20 16 3 1 NO 037H3507
CI 5-12 01 3.0 5.5 11.5 20 16 3 1 NC 037H3508
1
) Coil voltage/frequency or Sux no. (see table below) must be added to the Danfoss code no.
2
) The thermal current value lth gives the maximum load at 40 °C, which corresponds to installing the contactor in air (open).
3
) The thermal current value l
4
) Control relay , rating according to AC-12 category
AC coil voltages for CI 5-
Coil voltage 1) Sux no.
24 V, 50/60 Hz 13
110 V, 50 Hz 120 V, 60 Hz
gives the maximum load at 60 °C, corresponding installing the contactor inside an enclosure.
the
Correct ordering of contactors Example: CI 5-5 with NC auxiliary contact and
24 V, 50/60 Hz coil voltage.
Select the following form of ordering:
23
1. Danfoss code no. + Sux no.: 037H350313
230 V, 50/60 Hz 32
240 V, 50/60 Hz 33
400 V, 50/60 Hz 37
1
) Standard coil voltage tolerance -15%, +10%
DC coil voltages for CI 5-
Coil voltage 1) Sux no.
*12 V DC 01
24 V DC 02
1
) Standard coil voltage tolerance -30%, + 25%
* Code no. 037H3504 only
2 | 520B8097 | IC.PD.C10.F4.02
© Danfoss | DCS (im) | 2017.07
Data sheet | Minicontactors, Type CI 5-
Auxiliary contact blocks CI 5-
Type Contact function
CBN 40 4 make (NO) 2 10 6 500 037H3511
CBN 02 2 break (NC) 2 10 6 500 037H3513
Auxiliary contact CBN
CBN 11 1 make (NO) + 1 break (NC) 2 10 6 500 037H3514
CBN 22 2 make (NO) + 2 break (NC) 2 10 6 500 037H3515
CBN 04 4 break (NC) 2 10 6 500 037H3512
*) Ith and I
(AC-15)
are dened and specied under Technical data
the
Load
I
e
A
Ith *)
(AC-1)
A
I
*)
the
(AC-1)
A
U
e
Code no.
V
Mechanical interlock
RC element RCN
CBN mirror contact block ensures reliable monitoring of the status of the CI 5 contactor according to IEC 60947-4-1.
Bifurcurated, H-shaped CBN contacts provide out­standing contact reliability for low energy switching down to 15V/2mA.
Accessories for minicotators CI 5-
Description Comments Code no.
Mech. interlock
Diode element
RC element
For interlocking of two adjacent
contactors (Applies to versions with
AC/DC coils)
Reduce over voltage on the
de-energization of coils
Type DCN 250 (12 – 250 V DC)
Reduce over voltage on de-energization of coils
Type RCN 48 (24 – 48 V AC)
RCN 280 (110 – 280 V AC) 037H3519
037H3520
037H3510
037H3518
© Danfoss | DCS (im) | 2017.07
IC.PD.C10.F4.02 | 520B8097 | 3
Data sheet | Minicontactors, Type CI 5-
Thermal overload relay TI 9C-5
Ordering
Introduction
Thermal overload relay TI 9C-5 is used with minicontactor CI 5- for protection of squirrel cage motors where compactness is required. The relay have single – phase protection, i.e. accelerated release if phase drop-out occurs.
This is particularly important for motors with delta connected windings.
Other features of TI 9C-5 :
• Stop / reset button
• Manual / automatic reset
• Test button
• Double scale for direct start or Y/D start
• Galvanically isolated signal contact
1
Range Max. fuse
Type
Motor
starter
[A]
Y/D-
starter
[A]
0.27 – 0.42
0.4 – 0.62
0.6 – 0.92
0.85 – 1.3
TI 9C-5
1.2 – 1.9
1.8 – 2.8 3.2 – 4.8
2.7 – 4.2 4.7 – 7.3
4.0 – 6.2 6.9 – 10.7
6.0 – 9.2 10 – 16
1
) To IEC 947-4 coordination types 1 and 2:
Coordination type 1: Any type of damage to the motor starter is permissible. If the motor starter is in an enclosure, no external
damage to the enclosure is permissible. After a short- circuit the thermal overload relay shall be partially or wholly replaced.
Coordination type 2: No damage to the motor starter is permissible, but slight contact burning and welding is permissible.
2
) In accordance with HRC form II, TI 9C and TI 12C is suitable for operation in Canada and the USA.
8.0 – 12 13 – 20.8
gl, gL, gG BS 88, type T
Type 1
[A]
Type 2
[A]
25 2 32 2 1 047H3132
25 2 32 4 1 047H3133
25 4 32 6 3 047H3134
25 4 32 6 3 047H3135
25 6 32 10 6 047H3136
25 6 32 10 15 047H3137
25 16 32 20 15 047H3138
35 20 40 25 15 047H3139
50 20 50 25 35 047H3140
63 25 63 32 35 047H3141
)
Type 1
[A]
Type 2
[A]
HRC
Form
II
2
)
Code no.
4 | 520B8097 | IC.PD.C10.F4.02
Selection of thermal overload relay:
The selection of a thermal overload relay must be based on the motor full load current and the method of starting:
- With direct start range for motor starter is used
- With star – delta start the range for Y/D starter is used
Example: Full load current: 12A
- With direct start the suitable motor starter range is 8.0 – 12A, i.e. thermal overload relay 047H3141
- With Y/D – start, the suitable motor starter range is 10 – 16A, i.e. thermal overload relay 047H3140
© Danfoss | DCS (im) | 2017.07
Data sheet | Minicontactors, Type CI 5-
Construction standards
Contactors, thermal overload relays and accessories are
CI 5- General data
designed and tested in accordance with IEC 60974 / EN 60947 and 60068.
Max. installation height: 2000 m NN, in accordance with IEC 60947
Mechanically linked contacts
IEC 60947-5-1, Annex L
Mirror contacts
IEC 60947-4-1, Annex F
CI 5-5, -9, -12
CI 5-5, -9, -12 and CBN
Rated impulse voltage
withstand
U
imp
[kV] IEC [V] UL, CSA [V]
6 690 600
Rated isolation
voltage
U
i
Ambient temperature
Type
Operation Storage / Transport
Ambient temperature
CI 5- -25 °C – 60 °C -55 °C – 80 °C
Vibration and shock
Tested and passed in accordance with IEC 68-2 / EN 60068
Type Vibration1) Shock2)
CI 5- 5g, 5 – 500 Hz 5g, 30ms
1
) Operating conditions: All directions with de-energized coil.
2
) Operating conditions: Parallel with armature and with de-energized coil
Environment
Type
Temperature
compensated
Ambient
temperature
Vibration
Shock
perpendicular to
contact system
Max.
operations
per hour
TI 9C-5 -5 °C – 40 °C -50 °C – 60 °C 2 g at 200 Hz 9 g for 7.5 ms 30
Mounting direction
Rated life
Approvals and standards
Type
CI 5-2 15 x 10
CI 5-5 CI 5-9
Mechanical life
6
6
15 x 10
CI 5-12
UL approvals : CI 5-: TI 9C-5:
Standards UL 508, CSA C22.2 No. 14
cULus
Standards UL 508, CSA C22.2 No. 14 M91
cULus
CE IEC/EN 60947-1, -4-1, -5-1, -5-4 EAC approved LLC CDC TYSK approved
Electrical life
AC-3 load
Operations
0.7 x 10
6
0.7 x 10
Electrical life
AC-15 load
Operations
6
600
Switching per hour
AC-3 load
Operations
© Danfoss | DCS (im) | 2017.07
IC.PD.C10.F4.02 | 520B8097 | 5
Data sheet | Minicontactors, Type CI 5-
Electrical life curves
Electrical life; Ue = 400 – 460V AC
AC-3: Switching of squirrel-cage motors while starting. AC-1: Non- or slightly inductive loads, resistance
furnaces.
Electrical life; Ue = 400 – 460V AC AC-4: Stepping of squirrel-cage motors.
6 | 520B8097 | IC.PD.C10.F4.02
© Danfoss | DCS (im) | 2017.07
Data sheet | Minicontactors, Type CI 5-
Tripping graph
TI 9C-5
3-phase overload
1
) Measure overload current
2
) Find the overload factor (x) by dividing the
measured value by the set value of the thermal overload relay (motor full load current)
3
) Find (x) on the horizontal axis and follow a line
vertically up until it intersects the upper curve
4
) From the intersection point, follow a horizontal line to
the left and read o on the vertical axis the time that will elapse before the thermal overload relay cuts out the motor
Explanation of graphs
Mean value curves Upper curve: 3-phase tripping and asymmetric load
tripping at min. setting. Lower curve: Asymmetric load tripping at max. setting.
When tripping from the operationally warm condition, the tripping times are approx. 30% of the values shown. These values apply at an ambient temperature = 20 °C.
3-phase tripping: x = rated motor current
Asymmetric load tripping: x = max. scale value on
overload relay
measured current
measured current
Tripping time 2 < Tp ≤ 10 s at 7.2 x Ie class 10 A Note: In general, the thermal overload relay is always set
on motor full load current.
Asymmetric load tripping
1
) Measure the current the motor draws from one of the
intact phases
2
) Find the overload factor (x) by dividing the measured
value by the maximum scale value of the thermal overload relay
3
) Find (x) on the horizontal axis and follow a line
vertically up until it intersects the lower curve
4
) From the intersection point, follow a horizontal line to
the left and read o on the vertical axis the time that will elapse before the thermal overload relay switch o the motor
© Danfoss | DCS (im) | 2017.07
IC.PD.C10.F4.02 | 520B8097 | 7
Data sheet | Minicontactors, Type CI 5-
Contact symbols and control relays terminal markings
Auxiliary contacts
Control relay (4 NO) CI 5-2 40e
Auxiliary contact (4 NO) CBN-40
Auxiliary contact (2 NC) CBN-02
Control relay (2 NO + 2 NC) CI 5-2 22z
Auxiliary contact (2 NO + 2 NC) CBN-22
Auxiliary contact (1 NO + 1 NC) CBN-11
Auxiliary contact (4 NC) CBN-04
Contactors
Contactor CI 5-5 10, CI 5-9 10, CI 5-12 10
Contactors CI 5-9 M40
Thermal overload relay
Contactor CI 5-5 01, CI 5-9 01, CI 5-12 01
8 | 520B8097 | IC.PD.C10.F4.02
Thermal overload relay TI 9C-5
© Danfoss | DCS (im) | 2017.07
Data sheet | Minicontactors, Type CI 5-
Main circuit
Connections, main contacts
Type Connection method
Single
core
[mm2] / [AWG] [mm2] [mm2] [Nm] / [lb-in]
terminal sleeve
without
Multi core
with
terminal sleeve
Recommended
Tightening
torque
CI 5- Screw1) and clamp washer 1 – 4 / 18 – 12 0.75 – 2.5 1.2 / 10.6
TI 9C-5 Screw2) and clamp washer 0.75 – 4 0.75 – 4 1 – 4 0.8 – 2
1
) Pozidrive No. 2 / Blade No. 3 screw
) H2 screw
Direct start, load categories AC-2, AC-3, AC-4
Type
CI 5-5
CI 5-9
CI 5-12
230 – 240 V 400 – 415 V 500 V 690 V
A 6.3 4.9 3.9 2.8
kW 1.5 2.2 2.2 2.2
A 11.3 8.5 6.8 4.9
kW 3 4 4 4
A 11.3 11.5 9.2 6.7
kW 3 5.5 5.5 5.5
Rated loads at 50Hz, 60 °C
Load category AC-4 at approximately 200,000 operations
Type
CI 5-5
CI 5-9
CI 5-12
230 – 240 V 400 – 415 V 500 V
A 2.3 2 1.9
kW 0.37 0.75 0.75
A 3.9 3.6 3.2
kW 0.75 1.5 1.5
A 3.9 3.6 3.2
kW 0.75 1.5 1.5
Rated loads
Star-delta starting
Type
CI 5-5
230 – 240 V 400 – 415 V 500 V 690 V
A 11.3 8.5 6.8 4.9
kW 3 4 4 4
Rated loads at 50 Hz
CI 5-9 A 20 15.5 12.4 8.9
CI 5-12 kW 5.5 7.5 7.5 7.5
Three phase ohmic load, load category AC-1
Type
CI 5-5 CI 5-9 CI 5-12
A 20 20 20 20 20
kW 8 8.3 14 17 24
Operating temperature max. 40 °C (Open condition)
230 V 240 V 400 – 415 V 500 V 600 V
Three phase ohmic load, load category AC-1
Type
CI 5-5 CI 5-9 CI 5-12
A 16 16 16 16 16 16
kW 6.4 6.7 11 12 14 19
Operating temperature max. 60 °C (Enclosed condition)
230 V 240 V 400 V 415 V 500 V 690 V
Rated thermal current AC-12
Rated thermal current Ith [A]
Type
Ambient temperature 40 °C Ambient temperature 60 °C
24 – 240 V 230 – 500 V 230 – 690 V 24 – 240 V 230 – 500 V 230 – 690 V
CI 5-2 10 10 10 6 6 6
© Danfoss | DCS (im) | 2017.07
IC.PD.C10.F4.02 | 520B8097 | 9
Data sheet | Minicontactors, Type CI 5-
Load categories AC-15/B600
Type
CI 5-2 3 2 1.2 1 0.6
Switching of power transformers, AC-6a (50 Hz)
Type
CI 5-5
CI 5-9
CI 5-12
Load categories AC-7a, AC-7b, AC-8a
Type
CI 5-5 20 20 6 6 11 10
CI 5-9 20 20 11 11 18 15
CI 5-12 20 20 11 11 18 15
24 V / 48 V / 120 V 230 V / 240 V 400 V 480 V / 500 V 600 V / 690 V
Transformer load, (factor n = 30, inrush current = n × rated transformer current)
230 – 240 V 400 V / 415 V 500 V 600 V
A 2.9 2.4 1.8
kV A 1.7 1.7 1.7 2
A 5.4 4.1 3.2
kV A 2 2.8 2.8 4
A 5.4 5.4 3.2
kV A 2 3.4 3.4 5
AC-7a AC-7b AC-8a
230 V 400 V 230 V 400 V 400 V 500 V
Rated current [A]
Max. operating current [A]
Switching lighting
Incandescent lamps Fluorescent lamps AC-5a 220 – 240 V AC
Type
CI 5-5 5 18 14.5 750 400
CI 5-9 9 18 14.5 750 400
CI 5-12 9 18 14.5 750 400
Switching direct current load Load categories DC-3 and DC-5, contacts connected in series
Type
CI 5-5 5 4 2 0.8 0.15 5 2 0.6 0.1
CI 5-9 9 6 3 1.2 0.2 9 3 1 0.1
CI 5-12 9 6 3 1.2 0.2 9 3 1 0.1
Switching direct current load Load categories DC-1 at 60 °C, contact connected in series
Type
CI 5-5 6 6 6 4 / 1 6 6 0.6 4 6 0.2 0.8 3 0.08 0.2 0.4
CI 5-9 9 9 9 6 / 1.5 8 9 1 6 9 0.3 1.2 4 0.1 0.3 0.6
CI 5-12 9 9 9 6 / 1.5 8 9 1 6 9 0.3 1.2 4 0.1 0.3 0.6
Max. operating current at
230 / 240 V
[A]
DC-3, 3 poles in series, 60 °C DC-5, 3 poles in series, 60 °C
24 V 48 / 60 V 110 V 220 V 440 V 24 V 48 / 60 V 110 V 220 V 440 V
24 V 48 /60 V 110 V 220 V 440 V
1-pole 2-poles 3-poles 1-pole 2-poles 3-poles 1-pole 2-poles 3-poles 1-pole 2-poles 3-poles 1-pole 2-poles 3-poles
Max. operating current at 40 °C
[A]
open closed 10 kA 20 kA
Max. operating current [A]
Max. operating current [A]
Max capacitance [μF] at expected short-circuit
current Icc =
Continuous current
Type
CI 5-2 5 10 2.3 1 0.55 0.27 0.15 0.1
10 | 520B8097 | IC.PD.C10.F4.02
General purpose [A] DC-13/Q600 [A], 1-pole
300 V AC 600 V AC 24 V AC 48 V AC 110 V / 125 V 220 V / 250 V 400 V / 440 V 600 V
© Danfoss | DCS (im) | 2017.07
Data sheet | Minicontactors, Type CI 5-
Power loss
Short circuit coordination
Contact resistance and power losses
Type
CI 5-2 6.5 2.6 1)
CI 5-5 2.2 0.3
CI 5-9 2.2 0.9
CI 5-12 2.2 0.9
1
) Power loses 4 main poles
Type
TI 9C-5 Typically 2.15 W Typically 4.87 W
Type
CI 5-5
CI 5-9 35 20
CI 5-12 35 20
Typical impedance per pole Power loses 3 main poles AC-3/400 V
[mΩ] [W]
Average power
Min. setting Max. setting
Short circuit coordination (Max. fuse or circuit breaker rating)
DIN fuses - gG [A] Type “1” Type “2”
50 kA
Available
Fault current
35 16
© Danfoss | DCS (im) | 2017.07
IC.PD.C10.F4.02 | 520B8097 | 11
Data sheet | Minicontactors, Type CI 5-
Control circuit
Connections
Auxiliary contacts
Type/ Application
Connection method
Single core Multi core
[mm2] / [AWG]
without terminal sleeve
[mm2]
with terminal sleeve
[mm2]
Recommended
Tightening
torque
[Nm] / [lb-in]
CI 5- built in Screw and clamp washer 1 – 4 / 18 – 12 0.75 – 2.5 1.2 / 10.6
CBN for CI 5- Screw and clamp washer 1 – 4 / 18 – 12 0.75 – 2.5 1.2 / 10.6
TI 9C-5 Screw and clamp washer 0.75 – 2.5 0.75 – 1.5 0.75 – 1.5 0.78 – 1
Auxiliary contacts, load categories AC-15 and AC-12
Max. operating current [A]
Type Comments
AC-15 AC-12
24 V – 120 V 240 V 400 V 480 V 500 V 600 V 690 V 40 °C 60 °C
CI 5-
CBN
Built into
contact
For contact
CI 5-
6 3 1.8 1.5 1.4 1.2 1 10 6
3 2 1.2 1 1 0.6 0.6 10 6
Auxiliary contacts, load categories DC-12, DC-13, DC-14
Max. operating current [A]
Type Comments
CI 5-
CBN
Built into
contact
For contact
CI 5-
12 V 48 V
6 4 0.6 0.2 0.08 4 2.5 0.4 0.12 0.05 2.8 1.2 0.55 0.27 0.15
2.3 1 0.55 0.27 0.15
DC-12 DC-13 DC-14
110 –
220 –
125 V
250 V
400 – 440 V
12 V 48 V
110 – 125 V
220 – 250 V
400 – 440 V
12 V 48 V
110 – 125 V
220 –
250 V
400 – 440 V
Coil consumption
Inrush power Holding power Pull-in voltage Drop-out voltage
Type
AC DC AC DC AC DC AC DC
VA W W VA W W V V V V
CI 5- 35 32 3 1) 2.6 2) 5 1.8 3 1) 2.6 2) (0.85 – 1.1) × U
1
) cold
S
(0.8 – 1.1) × U
S
(0.2 – 0.75) × U
S
(0.1 – 0.75) × U
2) warm
Coil operating times
Make time Break time
Type
AC DC AC AC+RC module DC
DC+integrated
diode
DC+external
diode
[ms] [ms] [ms] [ms] [ms] [ms] [ms]
CI 5- 15 – 40 18 – 40 15 – 33 15 – 28 6 – 12 8 – 12 35 – 50
RC element (charge suppressor)
Type Comments
overvoltage factor
n = U
/ U
max
n
RCN Suitable for contactors CI 5- 1 – 2.5
Max. load control circuit (contact system)
Type
TI 9C-5
AC-15 DC-13 , gL, gG Bs 88 type T
500 V
2 A
200 VA
Load Max. fuse
250 V
2A
4A 6A
20 W
S
12 | 520B8097 | IC.PD.C10.F4.02
© Danfoss | DCS (im) | 2017.07
UL/ CSA specication
General
purpose
Type
CI 5-5 12 9.8 0.5 8 1 6.9 1.5 6 1.5 4.8 3 3.9 3
CI 5-9 15 9.8 0.5 10 1.5 7.8 2 6.8 2 7.6 5 6.1 5
CI 5-12 18 13.8 0.75 12 2 11 3 9.6 3 11 7.5 9 7.5
Star-delta (60 Hz)
Type
CI 5-5 2.5 2.5 5 5
CI 5-9 3.3 3.3 8.5 8.5
CI 5-12 5 5 12 12
Auxiliary contacts, UL/CSA approved loads
Type Comments
CI 5-2 Built into contact max. 600 B600 max. 600 Q600
CI 5, 9, 12 Built into contact max. 600 A600 max. 600 Q600
CBN For contact CI 5- max. 600 B600 max. 600 Q600
current
(enclosed)
[A] [A] [HP] [A] [HP] [A] [HP] [A] [HP] [A] [HP] [A] [HP]
UL/CSA approved loads
Rated power (enclosed)
1-phase 3-phase
115 V 230 V 200 V 230 V 460 V 575 V
Rated power [HP]
200 V 230 V 460 V 575 V
AC DC
Rated voltage Switching capacity Rated voltage [V] Switching capacity
[V] [A] [V] [A]
Dimensions [mm]
Contactor CI 5- Motor starter
CI 5- +TI 9C-5
© Danfoss | DCS (im) | 2017.07
IC.PD.C10.F4.02 | 520B8097 | 13