Functionalities: Enable screen saver for LCD
Functionalities: Enable LED display
Enable support for MMILDS
Functionalities: Enable schema view
Functionalities: Enable I/O probe calibration
Functionalities: Enable override of input and output
Functionalities: Enable commissioning form
Functionalities: Enable EEV using EKE 1C
Enable MMI navigation
Functionalities: Enable EEV using EXD 316
Functionalities: Enable EEV using MCX driver
Functionalities: Enable VSH Modbus control
Functionalities: Enable Scheduler
Functionalities: Enable Evaporator variable capacity pump
Note: playing with MCXShape, it is very easy to customize the
structure and the visibility of the menu: so the following indication
cannot match with all the compiled software
Main screen: LED DisplayFunctionalities: Enable LED display
Note: check parameters dsA, dSb and dSC.
Main screen: LCD Display
Note: check parameters dsA, dSb and dSC.
Keyboard
: Scroll UP, increment a value
: 3s when in main screen: toggle ON/OFF
: Scroll down, decrement a value
: 3s when in main screen: toggle Heat/Cool mode
: exit and save,
: when in main screen: access the active alarm list
: 3s when in Alarm screen: manual reset
The LEFT and RIGHT keys, if present, allow you to move the cursor to the desired option
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: LoginParameters and Menu are organized into 4 access levels. Levels from 1 to 3 are linked to a password.
Elements cannot be accessed when they are on a higher level than the entering level. The level of
each parameter and menu is defined with MCXShape
• Level 0 is accessible without password
• Levels 1-3 are linked to a password (Check parameters L01, L02 and L03)
• Level 4 is not linked to a password, it can be used to make menu or parameters never reachable.
You can log in from the menu:
if the password provided is not correct you remain on the login screen. Otherwise you get back to
the main menu.
Menu: Start
Network menu: used to switch all the machines on or off in the Master and Slave network
Default param. menu: used to load the default value of the parameters which have been defined in
the .mcxs file
Menu: ParameterThis menu contains all the parameters.
The meanings of the parameters are explained in the last part of this manual
Menu: I/O DisplayDisplay input and output values
LED display
Shows you (using the UP and DOWN keys) all the input and output values in sequence, showing the
I/O code on display A (“AI” for analogue input; “AO” for analogue output; “dI” for digital input and “dO”
for digital output) and its value on display B (analogue inputs that are not present or in alarm are
shown with “----”).
LCD display
You have access to three screens showing all the input and output values; each screen shows a group
of 8 I/O. Use UP and DOWN keys to scroll. The second and third screens are used with MCX15 and
MCX20 only.
The example below shows the first screen.
Menu: I/O ConfigThis menu is prepared for future use
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: I/O CommissioningFunctionalities: Enable override of input and output
Functionalities: Enable commissioning form
Note: the logic will not affect the override. The override is stopped for power off, "Reset all" command
and timeout that is defined into the menu "Setup"
Menu: AlarmEach alarm is described through analarm description (for LCD display only), an alarm code and the
time since its activated in the format hours:minutes:seconds (seconds for LCD display only).
Note: You can also access alarm visualization by pressing the ESC key from the main screen.
The alarm is only reset if the alarm has ended and it will send you back to the main screen.
Note: Alarms can also be reset by holding ESC for 3 seconds on the alarm screens
Menu: EEVFunctionalities: Enable EEV using EKE 1C
Functionalities: Enable EEV using EXD 316
The parameters inside the external drivers can be checked and changed in the Config EEVx menu.
The available parameters for the EXD are: r05, r09, r10, r12, A34, n04, n05, n06, n09, n10, n11, n15,
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: VSH Control
These commands are linked with the control word of the inverter
Menu: Clock
Functionalities: Enable Scheduler
Note: with the number beside to the function "Enable scheduler" you set the maximum amount of
records, before to change it consider that it also affects the EEPROM.
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Parameters
Display
Parameter: dSA, dSb, dsc, Log, Par
How to customize the main screen.
dSA-Display A value0= OFF : Display A is not used
1= IdOF : Display A shows the state of the digital input ON/OFF
2 =SEt : Display A shows the set point of the compressors regulation
3 =rEg : Display A shows the probe used for regulation
4=AI1 : Display A shows the value of the analogue input 1
……
19 =AI16 : Display A shows the value of the analogue input 16
dSb-Display B value0 =OFF : Display B is not used
1=IdOF : Display B shows the state of the digital input ON/OFF
2=SEt : Display B shows the set point of the compressors regulation
3 =rEg : Display B shows the probe used for regulation
4 =AI1 : Display B shows the value of the analogue input 1
…
19 =AI16 : Display B shows the value of the analogue input 16
20 =TcP1 : Display B shows the temperature calculated from the dP1 sensor
…
23 =TcP4 : Display B shows the temperature calculated from the dP4 sensor
dsc-Icone for cooling mode
Log- LogoLog=0 is combined with the image StartLogoDX in Chiller/BIN/Graph folder
Log=1 is combined with the image StartLogoDX_1 in Chiller/BIN/Graph folder
Note: the logo is shown just after the power on, pay attention to the size of the image because it is fit
in this screen
Par- Parameters versionIt is not used in the software, can be used to recognize different set of parameters
Note: this number is reported into the software information
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Password
Parameter: L01, L02, L03
How to change the passwords.
L01, L02, L03-
Level x password
Typing the parameter L0X, in the login screen, you will be able to see all the parameters and menu
with level <= of X;
The level of access is highlighted in the yellow square;
after 10 minutes of inactivity the display is set to an access level of zero
SetUp
Parameter: y01, y02, y03, y04, y05, y06, y08, y09
How to switch ON-OFF and change the application mode from parameters.
Functionalities: Enable scheduler
Functionalities: Enable show compressor status
Digital input: ONO
Digital output: UNT
y01- System ON/OFF0=Machine OFF
1=Machine status depends on the DI _ONO
Defines whether the chiller is in the ON or OFF state, it can be changed from the menu, remotely by
Modbus or CANBUS and from start screen by holding the up arrow key.
Note1: The software is in ON status only if y02=ON and DI_ONO=ON
Note2: The chiller status is also reported in the digital output UNT_Unit Status
y02- Restart mode after
power OFF
y03- System heat/coolIt works only with H40> 0 and rE2=UI;
0=OFF means that after power on, the chiller gets up in OFF state
1=ON means that after power on, the chiller gets up in ON state
2=EQUA means that after power on, the chiller keeps the same state as before power off
This defines whether the machine should be in chiller mode or heat pump mode.
This parameter can also be changed from the “Start” menu
y04- Actuators delay from
power ON
y05- Temperature
measurement unit
y06- Keyboard lock0=No
y08- Scheduler enable0=No means that the scheduler is disabled
It is in seconds and sets the delay when powered ON (not when the unit status changes to ON) before
activating any outputs. Its purpose is to distribute the drawn current and protect the elements and
particularly the compressor against repeated starts in the event of frequent power failures. When the
timer has elapsed, the controller starts to manage the outputs based on the other times and the other
normal functions.
0=C means that the user interface will show values in Celsius and bar
1=F means that the user interface will show values in Fahrenheit and PSI
1=Yes means that the user interface is locked
Note: This parameter can be adjusted in order to be set remotely because it is not enabled for the menu
1=Yes means that the scheduler is enabled
Note: the “Enable scheduler” functionality is required
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
y09- Show rolling test0=No
1=Yes
Provides information about what is going on in relation to the cutting in/out of the compressors
Note: If the functionalities “Enable show compressor status” is enabled in the UI, a small icon is
added for each compressor
Serial setting
Parameter: Cid, Ser, bAU, COM
How to configure the communication port.
Functionalities: Enable Modbus address different from CANBUS address
Cid – Serial address (CAN)Defines the ID in the CANBUS communication
Note: the baud rate and the settings of the CANBUS communication is tuned through the bios menu
or though the MYK
SEr – Serial address (MODBUS) Defines the ID in the Modbus communication
Note: the functionalities “Enable Modbus address different from CANBUS address” is required
bAU – Serial baud rate (Modbus)
COM – Serial settings
(Modbus)
Defines the baud rate in the Modbus communication
0 means Reserved: do not use
1 means 1200 bits/sec
2 means 4200 bits/sec
3 means 4800 bits/sec
4 means 9600 bits/sec
5 means 14400 bits/sec
6 means 19200 bits/sec
5 means 28800 bits/sec
8 means 38400 bits/sec
9 means 57600 bits/sec
8 means 115200 bits/sec
Defines the serial settings of the Modbus communication
H1 – Number of evaporatorsDefines the number of internal coils;
The supply temperature (TIN) is the same for all the coils.
Each coil has a “leaving temperature” (T01-T04) ; there is also a common “leaving temperature” sensor
for all the coils ( TOM)
H2 – Number of circuits per
evaporator
H3 – Air or water coolingDefines whether the evaporation process is managed by a pump (H3=H2O) or a fan (H3=Air):
H4 – Number of pump/fan per
evaporator
H5 – Number of heaters per
evaporator
H12 –Fan in common for each
evaporator
Defines the number of circuits for each internal coil;
Configuration accepted:
• 1 circuit per internal coil -> 0<H1<5
• 2 circuits per internal coil ->0<H1<3
• 3 circuits per internal coil H1=1
• 4 circuits per internal coil H1=1
• WATER evaporators (H3=H2O). For each evaporator, the H1,...,H4 digital outputs which are
necessary to manage the antifreeze heaters on the basis of the leaving water temperature TO1,...,TO4
are controlled. The number of heaters per evaporator is defined by H5.
• AIR evaporators (H3=Air). Only the “TO1_Tout Evaporator 1” input is used to measure the supply air
temperature even when more than one evaporator is present. The ice alarm AE1 is replaced with the
Low air temperature warning A07 which is set to the same parameters as the ice alarm.
Defines the pumps (or fan) per evaporator:
• WATER evaporators (H3=H2O): The PE1 and PE2 digital outputs are managed to control one pump
or two twin pumps.
• AIR evaporators (H3=Air): “PE1 and PE2” outputs are used to manage fans on the evaporator.
Note: check "Fun for internal coil"
Defines the number of heaters for each internal coil;
Configuration accepted:
• 1 heater per internal coil -> 0<H1<5
• 2 heaters per internal coil ->0<H1<3
• 3 heaters per internal coil ->H1=1
• 4 heaters per internal coil ->H1=1
0=NO means that each fan (AO ECx) works in relation to the evaporator pressure
1=Yes means that only the fan EC1 will work in relation to worst pressure in the evaporators
Note: the fan speed is managed with PI logic (check parameters ECS,….,Hi)
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Compressor
Parameter: H6, H7
How to configure the compressors number.
H6 – Number of compressor
per circuit
H7 – Number of unloader per
compressor
Defines the number of compressor per circuit;
It’s not possible have circuits with different number of compressors
Configuration accepted:
• 1 compressor per circuit -> 0<H1*H2<5
• 2 compressors per circuit ->0<H1*H2<5
• 3 compressors per circuit ->0<H1*H2<3
• 4 compressors per circuit ->0<H1*H2<3
• >4 compressors per circuit ->0<H1*H2<2
Defines the number of compressor partialisation;
The number of regulation steps is equal to H6*H2*H1*(H7+1)
Activation and deactivation of the compressor’s unloader is defined by the parameters
“C04-Unloaders activation mode” and “ C05-Unloaders deactivation mode”
Defines whether the fans or the pump regulate condensing.
0=AIR : Controls defrosting in heating mode.
1=HO : The configuration managed is H10=1 and H11=Yes
Note: the pump or fan behaviour is defined by parameters F01, F02 and F03
Defines the necessary digital output to control the pumps or fans on the condenser.
• Water-cooled units (H9=H2O).The single “Cond Fan1/Pump1” digital output is controlled to drive
a pump.
• Air-cooled units (H9=AIR). Contributes to defining the total number of managed ventilation steps and
thus of the corresponding ”Condenser Fan1”, ..., ”Condenser Fan8” digital outputs used to drive them.
On multi-circuits units, fans can be in common to all condensers.
If fans are not in common to all condensers (H11=0=NO), the following output are controlled:
• as many analogue inputs as the condensers (H1*H2)
• as many digital outputs as the condensers (H1*H2), multiplied by the number of fans per condenser
(H10); digital outputs for fans are assigned to condensers in a sequential and balanced way,
assuming that all condensers have the same number of fans; e.g. in a system made of 2 condensers
and 6 fans, “Cond Fan1/Pump1”, “Condenser Fan2” and “Condenser Fan3” outputs are assigned to
control fans belonging to the first condenser; “Condenser Fan4”, “Condenser Fan5” and “Condenser Fan6” to the second condenser.
• as many analogue output s “InverterFanCond1”,...,”InverterFanCond4” for condensing control as for
the condensers (H1*H2).
If fans are common to all condensers (H11=1=YES) the following outputs are used:
• as before, as many analogue inputs for condensing controls as there are circuits per condenser
(H1*H2), but the one requiring the higher response from the control is used for regulation. Each
analogue input is then used for defrost control in heating mode;
• as many digital outputs as fans per condenser (H10);
• one analogue output “InverterFanCond1” for fan speed regulation.
H40 –Heat pump type0=No means that the software does not perform heating mode
1=GAS means that the software performs the heating mode, the internal coil is the evaporator in
cooling mode and the condenser in heating mode
1=H2O means that the software performs the heating mode, the coils keep the same meaning in
both heating and cooling mode both
Note: one digital output “Reverse Valve C1”, ..., “Reverse Valve C4” per each circuit is reserved for
controlling the reverse flow valve
H41- Boiler number of heatersBoiler heaters “Boiler1”, ..., “Boiler4” are turned ON when the temperature measured by the regulation
probe enters in the area defined by the active regulation setpoint in heating (SH1) and differential rH1.
They are an alternative to the heat pump, not in addition.
Boiler heaters can be activated only if the temperature measured by the “BoilerSafety” probe is
under a specific safety limit AbS. If it is over the limit, alarm A14 is generated.
To reset the alarm there is a constant differential Abd to be considered.
H42- Probe change in HP0=No means that the probe is before the 4-way valve (close to the compressor):
• the sensor dPx – Discharge pressure Cx measures high pressure
1=Yes means that the probe is after the 4-way valve (close to the coils):
• the sensor SPx – Suction pressure Cx measures low pressure in cooling mode and high pressure in
heating mode
• the sensor dPx – Discharge pressure Cx measures high pressure in cooling mode and low pressure
in heating mode
Note: if ex2=yes the variable used from H42 (pink line below) is always about low pressure, in
this case pay attention to set H42=No because in heating mode the discharge pressure will not
be available
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Network settings
Parameter: n01,…n17
The Master and Slave is a functionality that allow a group of machines to be
managed like one machine (Master) decides which and how many units (Slaves)
should run.
The max number of units is 8 (7 slaves + 1 master), the network is CANBUS.
The Master and Slave function optimizes:
- ageing of machines
- distribution of the load in order to improve the performance of the plant
n01 –MCX network disable0=NO means that the Master slave function is enabled
1=Yes means that the Master slave function is disabled
n02 –Number of slave nodesIt has to be set equal to (“number of chillers in the network” -1)
n03- Auto master select0=NO means that the master in the master slave network can be only the chiller with the CANBUS ID
equal to n15: if the master is not more available in the network, the other chillers will start to work in
standalone mode
1=Yes means that the master in the master slave network is the chiller with lowest CANBUS ID
n04- Distribution algo0= PWR The master, using its own sensors, decides how many chillers are working and the chillers’
power supply;
The maximum number of units that can work is related to the gap between setpoint and
temperature: practically the regulation band is divided for the number of machines (n02+1-n09):
1= CAP the master manages only the start order (following the ageing of the machines), chillers
manage their power as standalone machines.
If all the units which are running have capacity above n12 %, the master will switch on another chiller (the
youngest one).
If all the units which are running have capacity below n13 %, the master will switch off the oldest chiller
running
The minimum time between two actions of the master is n14 seconds
n05- Power Smart power
distribution enable
n06- Node rotation enable0=No means that the start sequence of the machines is fixed; the order depends on the addressing,
1=Yes means that the master is allowed to cut-in the first chiller available without considering the
start order related to the ageing of the machines
the first to start is the machine with the smallest CANBUS ID, the first to stop is the chiller with the
highest CANBUS ID
1=Yes means that the start/stop sequence of the machines depends on the ageing of the chillers,
always starting with the youngest of the set and the oldest one is always the first to stop. In the case
that one machine works n17 hours more than another chiller that is switched off, the master will
exchange the unit in order to align the ageing.
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
n07- Backup node offsetWhen the gap between setpoint and temperature is above (n07+regulation band), the first backup
unit is allowed to work as a support, also considering parameter n08 .
Note: the offset to enable the other backup units is (n07*m+ regulation band):
• m = 2 for the second backup unit
• m = 3 for the third backup unit
• …
Note: the backup units will work running normally after the set point. It will be switched off when the
gap between setpoint and temperature is below the regulation band
Note: the pump behaviour is defined through the parameter P01
n08- Time to enable n07It’s the time to stay far away from the setpoint in order to cut in the backup unit
Note: check parameter n07
n09-Number of back-up unitn09 defines the number of backup units inside the master slave network
A backup unit is never enabled (so does not provide cooling capacity) unless one of the following
situations occurs:
• one of the other units becomes unavailable
• Support (see parameter n07 and n08)
Note: The master chooses the backup unit (among all nodes present in the network) by looking at
the working time of every unit: the one which has worked the longest will be the backup unit.
n10 – Evaporator in common0=No each chiller consider its own evaporator flow alarm
1=yes the master will read its “FPE” digital input (Flow Evaporator) and will send the information to
other slaves
n11 – Pump alarm in common 0=No each chiller considers its own pump alarm
1=yes the master will read its “AP1” digital input (Evap pump/fan overload alarm) and will send the
information to other slaves
n12 – Capacity upper
threshold
n13 – Capacity lower
threshold
n14 – Capacity step min timeSee parameter n04
See parameter n04
See parameter n04
n15 – Master node CAN ID It has to be set equal to the lowest ID in the CANBUS network
n16 – Slaves node CAN ID offset The slaves have to take the CAN ID in relation to the n15 just adding n16.
It is in hours
If a running unit becomes older than a switched-off unit by more than n17 hours, the logic will
switch off the oldest unit running it will cause the other unit to be switched on.
0=OFF: the backup chillers in standby have the pump switched-off
1=ON: the backup chillers in standby have the pump switched-onNote:during support or backup, the pump of the chiller follow P01 setting
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Configuration
Parameter: rEG, rET, rT1, rT2, o30, Er1
rEG – Analogue input for
temperature regulation
rET – Regulation TypeDefines the relation between the temperature gap and the power request to the circuits.
0= Tin : reference sensor is Tin_Tin Evaporator
1= ToM: reference sensor is TOM_Tout Evap Mix
2 =AI1: reference sensor is the analogue input 1
……
17 =AI16 : reference sensor is the analogue input 16
18 =SPT1: reference is the temperature calculated from the sensor SP1_Suction Press C1, the gas type is set using parameter o31
0=P : Power request to the circuits increases in proportional way with the regulation error, i.e., it is 100% when the regulation error (the gap between setpoint and the reference sensor ) is equal to rC1
( rH1)
1=PI: the power request is the sum of P regulation (rET=0) plus a component (Integral part)
that increases in relation to the regulation error; the speed of the integral part depends on the
parameter rin_Ti.
For PI regulation, the balance is reached only when the regulation sensor gets the setpoint.
2=dZ : The delay between compressors activations varies between a maximum value dd5 and
minimum value dd6 proportional to the temperature position inside the regulation band defined by
the activation differential dd1.
Above setpoint + dead zone + activation differential, the delay among activations is equal to the minimum.
rT1- Minimum limit for
TReg TX
rT2- Maximum limit for
TReg TX
Similarly the action for the delay among compressors deactivations, which can vary between a
maximum value dd7 and a minimum value dd8, is proportional to the temperature position inside
the regulation band defined by the deactivation differential dd2.
Below a setpoint differential, the delay among activations is equal to the minimum value, dd8, up
to a limit threshold, dd3. Below that, all the compressors are immediately switched OFF to avoid the
unit ice alarm.
The analogue output rtr linearly replays the regulation probe (check parameter rET)
It gets to 0% when the regulation probe reaches a value of rT1
Note: if the regulation probe is in error the AO_rtr gets to 100%
The analogue output rtr linearly replays the regulation probe (check parameter rET)
It gets to 100% when the regulation probe reachs rT2 value
Note: if regulation probe is in error the the AO_rtr gets to 100%
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Economic Setpoint
Parameter: SdS, SdM, SdC, SdH, SdO
SdS- Setpoint selection0=DI means that the digital input SET2_Reg offset from DI defines if use comfort setpoint (SC1 or
SH1) or the economic setpoint (SC1+SdC or SH1-SdH); in economic mode the proportional band in the PI control is increased by SdO
1=PAR meaning that the parameter SdM_Setpoint mode defines whether comfort setpoint
(SC1 or SH1) or the economic setpoint (SC1+SdC or SH1-SdH) is to be used; in economic mode the
proportional band in the PI control is increased by SdO
SdM- Setpoint modeIt works only for SdS=PAR
0=COMF meaning that chiller uses comfort setpoint ( SC1 or SH1)
1=ECO meaning that the chiller uses economic setpoint (SC1+SdC or SH1-SdH)
In economic mode the proportional band in the PI control is increased of SdO.
SdC-Offset for setpoint in cool-
ing
In economic status and cooling mode the regulation setpoint is shifted to SdC.
Note: see parameter SdS
SdH-Offset for setpoint
in heating
SdO-Offset for differentialIn economic mode the proportional band of regulation becomes rC1+SdO or rH1+SdO.
In economic status and heating mode the regulation setpoint is shifted to SdH.
Note: Take a look to parameter SdS
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
PI regulation
Parameter: CrC1, rH1, Rin, rC2, rC3
Note: the PI regulation is enabled when the parameter rET is equal to P or PI
rC1-Cooling temperature
differential.
rH1-Heating temperature
differential.
Rin- TiIt is the integral time of the PI regulation, the bigger the value of Rin the slower the action of the
rC2-Cut Off enableIt enables the gradual reduction of the integral error once reached and exceeded the setpoint. The
rC3- Cut off offset
See parameter rET
See parameter rET
Integral part.
See parameter rET
error integral in fact tends to keep the compressors turned on even if the proportional part of the
error would require a shutdown. The amount of reduction is proportional to the distance from the
setpoint considering the rC3 band. For example, in cooling, the reduction is zero when the control
temperature is equal to the setpoint; the reduction is greatest when it is equal to setpoint-rC3.
The dead zone regulation is enable when the parameter rET is equal to DZ
It is a variable time regulation mainly used when the regulated value is the
temperature of the fluid leaving the evaporator.
In the dead zone ddC no regulating action is taken.
Close to the dead zone the decision to cut the compressor in or out will
take a maximum time of (dd5 or dd7), a time that will decrease linearly
outside the dead zone. This variable time logic is described below.
ddC-Cooling dead zoneIn dead zone ddC no regulation action is taken.
This is above the setpoint and used in cooling mode
ddH-Heating dead zoneIn dead zone ddH no regulation action is taken.
This is below the setpoint used in heating mode
dd1-Comp activation
differential
dd2-Comp deactivation
differential
dd3-Min temp for OFF comp
in cooling
dd4-Max temp for OFF comp
in heating
dd5-Max delay of comp activation
dd6-Min delay of comp
activation
dd7-Max delay of comp
deactivation
dd8-Min delay of comp
deactivation
Defines the maximum temperature gap to have a minimum delay (dd6) in the compressor’s activation
Note: see picture in the parameter ddC and ddH
Defines the maximum temperature gap to have a minimum delay (dd6) in the compressor’s
deactivation
Note: see picture in the parameter ddC and ddH
Defines the minimum temperature below which the compressors are switched off
Note: see picture in the parameter ddC
Defines the maximum temperature above which the compressors are switched off
Note: see picture in the parameter ddH
Defines the maximum delay before a compressor cuts in
Note: see picture in the parameter ddC and ddH
Defines the minimum delay before a compressor cuts in
Note: see picture in the parameter ddC and ddH
Defines the maximum delay before a compressor cuts off
Note: see picture in the parameter ddC and ddH
Defines the minimum delay before a compressor cuts off
Note: see picture in the parameter ddC and ddH