Danfoss Chiller and reversable chiller User guide

Danfoss Chiller and reversable chiller User guide

User Guide

Chiller and reversable chiller

Reciprocating, scroll and screw compressors

Software Version 4.40.00

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Contents

User Interface...............................................................................

4

High water temperature alarm in cooling mode.....................

34

LED Display, LCD Display, Keyboard, Unit status, Login, Start,

Parameter: Ats, Atd

 

Parameter, Input/Output, I/O Display, I/O Config, I/O Prb

 

Boiler water temperature alarm...............................................

34

Calibration, I/O Commissioning, Alarm, EEV, VSH Monitor, VSH

Parameter: AbS, Abd

 

Control, Clock, Language, Service, Hours Counters, Variable

 

Fault of the regulation probe of the external coil...................

35

speed pump

 

Parameter: ACM, ACS, ACd

 

Parameters..................................................................................

12

Preventions.................................................................................

35

Display........................................................................................

12

Parameter: TMx, THo, TLo, HPE, HPo, HPh, LPE, LPo, LPh, PPt,

Parameter: dSA, dSb, dsc, Log, Par

 

PPp, HFo

 

Password.....................................................................................

13

Superheat alarms.......................................................................

37

Parameter: L01, L02, L03

 

Parameter: SHh, AHI, Ahi, AHd

 

SetUp...........................................................................................

13

Oil temperature alarms..............................................................

37

Parameter: y01, y02, y03, y04, y05, y06, y08, y09

 

Parameter: OTm, OTi, OTd

 

Serial setting...............................................................................

14

Screw compressors.....................................................................

38

Parameter: Cid, Ser, bAU, COM

 

Parameter: C01, C02, CSO, CSb, T1, T2,T3, T4, C07, C08, T5, T6,

Evaporator..................................................................................

15

T21, T22, T24, T24, T25, T26, T27, T28, T29

 

Parameter: H1, H2, H3, H4, H5, H12

 

Starting type of the compressor...............................................

42

Compressor.................................................................................

16

Parameter: Sty, Sti, SSt, Stm, Sdd

 

Parameter: H6, H7

 

Economizer.................................................................................

43

Condenser...................................................................................

17

Parameter: E01, EO2, EO3, EO4

 

Parameter: H9, H10, H11

 

Liquid injection..........................................................................

44

Heat Pump..................................................................................

18

Parameter: T41, T42, T43, T44, T45

 

Parameter: H40, H41, H42

 

Compressor with unloaders......................................................

44

Maintenance...............................................................................

19

Parameter: C04, C05, C06, C08

 

Parameter: H43

 

Maximum number of compressor starts per hour...................

45

Network settings........................................................................

20

Parameter: CT0, CT1, CT2, CT3, CT4, CT5, CT6, CT7

 

Parameter: n01,…n17

 

Valve in the liquid line...............................................................

46

Configuration.............................................................................

22

Parameter: Pd1, Pd2, Pd3, Pd4

 

Parameter: rEG, rET, rT1, rT2, o30, Er1

 

Maximum compressor running hours......................................

47

Main Setpoint.............................................................................

24

Parameter: C50

 

Parameter: SC1, SCL, SCH, SH1, SHL, SHH, SRE

 

Inverter compressor...................................................................

48

Economic Setpoint.....................................................................

25

Parameter: IV0, IV1, IV2, IV3, IV4, IV5

 

Parameter: SdS, SdM, SdC, SdH, SdO

 

Compressor enabling.................................................................

50

Setpoint compensation in based on the outside temperature.. 26

Parameter: CT1, CT2, CT3, CT4, CT5, CT6, CT7, CT8

 

Parameter: CC1, CC2, CC3, CC4, CH2, CH3, CH4

 

Heaters........................................................................................

50

PI regulation...............................................................................

27

Parameter: HE1, HE2, HE3, HE4, HE5, HE6, HE7

 

Parameter: CrC1, rH1, Rin, rC2, rC3

 

Pump of the internal coil...........................................................

51

Dead zone regulation................................................................

28

Parameter: P01, P02, P03, P04

 

Parameter: ddC, ddH, dd1, dd2, dd3, dd4, dd5, dd6, dd7, dd8...

28

Modulating Pump......................................................................

52

Digital output lock.....................................................................

29

Parameter: ERT, ECS, ECd, ECi, EHS, EHd, EHi, EDB, EI1, EI2, EI3

Parameter: DOn, Ain, Dos, DOd

 

Fan for the internal coil..............................................................

53

Buzzer and relay.........................................................................

29

Parameter: P21, P22, P50

 

Parameter: BUZ, Adl, AOF

 

Free cooling................................................................................

54

Flow alarm..................................................................................

30

Parameter: FrA, Fr1, Fr2, Fr3, Fr4, Fr5, Fr6, Fr7, Fr8, Fr9, FI1,

 

Parameter: AFr, AF1, AF2, AF3

 

FI2, FI3

 

ICE alarm.....................................................................................

31

Valve in the water line................................................................

56

Parameter: AIS, AID, Air, AI1, AI2, AI3, AIT, AIo

 

Parameter: EF1, EF2

 

Compressor oil delta pressure alarm........................................

32

External coil................................................................................

56

Parameter: OPR, OdP, GdP

 

Parameter: F01

 

Circuit high temperature alarm................................................

32

Fan requests................................................................................

57

Parameter: HTs, HTd

 

Parameter: F02, F03, FC, FCD, FCI, FCd, FHS, FHD, FHI, FHd

 

Pressure alarms from analogue input......................................

33

Fan regulation with a variable proportional part...................

59

Parameter: AHE, AHS, AHd, Alr, AL1, AL2, ALE, ALS, ALd, LPt,

Parameter: F31, F32, F33, F34, F35, F36, F37, F24, F25

 

AVO, VCt, SHS, SHb

 

 

 

2 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Economic setpoint for fan regulation.......................................

60

Parameter: SS1, SS2, SS3, SS4

 

Stepless regulation of the fan...................................................

60

Parameter: F10, F11, F12, F13, F14, F20, F21, F22, F23

 

Hot gas bypass valve..................................................................

61

Parameter: Bp0, Bp1

 

Cooling towers............................................................................

62

Parameter: WFs, WFd

 

Reversing cycle valve (4 ways valve).........................................

63

Parameter: rE2, rE1, rE3, rE4

 

Defrost........................................................................................

64

Parameter: d01, d02, d03, d04, d05, d06, d07, d09, d10, d11,

d12, d13, d14, d15, d16, d20, d22, d23, d25, d26

 

Heat recovery.............................................................................

66

Parameter: HRs, HRm, HRc, HRn, HRt, HRo

 

Superheat...................................................................................

67

Parameter: V10, V20, bAt, ex1, ex2, ex3, N19, N04, N05, N20,

N22, N10, N09, N11, N32, N18, N17, N15, N21, SHO

 

Input output expansion module...............................................

69

Parameter: XCn

 

Auxiliary alarms.........................................................................

69

Parameter: a11, a21, a31, a41, a12, a22, a32, a42, a13, a23,

a33, a43, a 14, a24, a34, a44

 

Oil Alarm Tandem ......................................................................

70

Parameter: BME, BST, TD1, TD2, TD3, TD4, ADO, BOF, BFR

 

Compressor Oil Pump................................................................

72

Parameter: OPE, OPO, OT1, OT2

 

Temperature delta of the oil......................................................

73

Parameter: OTD, OD1, OD2

 

How to set the power request remotely ..................................

73

Parameter: RPE, RPS

 

How to log data on an SD card .................................................

74

Parameter: ENL

 

Commissioning...........................................................................

77

Parameter: Ort

 

Graphic diagrams of some of the managed unit types...........

80

Status variables..........................................................................

91

Software status...........................................................................

91

Parameter: A01, …, A19, C01, …, C04, E01, …, E08

 

Software info..............................................................................

92

Parameter: F01, …, F07

 

Superheat info............................................................................

93

Parameter: H01, …, H13

 

Preparatory: link to MCXShape manual

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 3

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

User Interface

LED Display, LCD Display, Keyboard, Unit status, Login, Start, Parameter, Input/Output, I/O Display, I/O Config, I/O Prb Calibration, I/O Commissioning, Alarm, EEV, VSH Monitor, VSH Control, Clock, Language, Service, Hours Counters, Variable speed pump

Functionalities: Enable screen saver for LCD

Functionalities: Enable LED display

Enable support for MMILDS

Functionalities: Enable schema view

Functionalities: Enable I/O probe calibration

Functionalities: Enable override of input and output

Functionalities: Enable commissioning form

Functionalities: Enable EEV using EKE 1C

Enable MMI navigation

Functionalities: Enable EEV using EXD 316

Functionalities: Enable EEV using MCX driver

Functionalities: Enable VSH Modbus control

Functionalities: Enable Scheduler

Functionalities: Enable Evaporator variable capacity pump

Note: playing with MCXShape, it is very easy to customize the structure and the visibility of the menu: so the following indication cannot match with all the compiled software

Main screen: LED Display

Functionalities: Enable LED display

Note: check parameters dsA, dSb and dSC.

Main screen: LCD Display

Note: check parameters dsA, dSb and dSC.

Keyboard

: Scroll UP, increment a value

: 3s when in main screen: toggle ON/OFF : Scroll down, decrement a value

: 3s when in main screen: toggle Heat/Cool mode : exit and save,

: when in main screen: access the active alarm list : 3s when in Alarm screen: manual reset

The LEFT and RIGHT keys, if present, allow you to move the cursor to the desired option

4 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Menu: Unit Status

Functionalities: Enable schema view

Schema:

View EEV Cx (for valve which is driven by EXD or MCX):

The alarms bit pattern is:

Note: by pressing “OK” key you manually tune the position of the valve

View EEV Cx (for valve which is driven by EKE):

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 5

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Menu: Login

Parameters and Menu are organized into 4 access levels. Levels from 1 to 3 are linked to a password.

 

Elements cannot be accessed when they are on a higher level than the entering level. The level of

 

each parameter and menu is defined with MCXShape

 

• Level 0 is accessible without password

 

• Levels 1-3 are linked to a password (Check parameters L01, L02 and L03)

 

• Level 4 is not linked to a password, it can be used to make menu or parameters never reachable.

 

You can log in from the menu:

 

if the password provided is not correct you remain on the login screen. Otherwise you get back to

 

the main menu.

 

 

Menu: Start

 

 

Network menu: used to switch all the machines on or off in the Master and Slave network

 

Default param. menu: used to load the default value of the parameters which have been defined in

 

the .mcxs file

 

 

Menu: Parameter

This menu contains all the parameters.

 

The meanings of the parameters are explained in the last part of this manual

 

 

Menu: I/O Display

Display input and output values

 

LED display

 

Shows you (using the UP and DOWN keys) all the input and output values in sequence, showing the

 

I/O code on display A (“AI” for analogue input; “AO” for analogue output; “dI” for digital input and “dO”

 

for digital output) and its value on display B (analogue inputs that are not present or in alarm are

 

shown with “----”).

 

LCD display

 

You have access to three screens showing all the input and output values; each screen shows a group

 

of 8 I/O. Use UP and DOWN keys to scroll. The second and third screens are used with MCX15 and

 

MCX20 only.

 

The example below shows the first screen.

 

 

Menu: I/O Config

This menu is prepared for future use

 

Note: it is under the 4th level of password

 

 

Menu: I/O Prb Calibration

Functionalities: Enable I/O probe calibration

 

inside the “Reset All” menu, you can reset all the offsets to zero

 

Note: the screens calibration are not translated

 

 

 

 

6 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Menu: I/O Commissioning

Functionalities: Enable override of input and output

 

Functionalities: Enable commissioning form

 

Note: the logic will not affect the override. The override is stopped for power off, "Reset all" command

 

and timeout that is defined into the menu "Setup"

 

 

Menu: Alarm

Each alarm is described through an alarm description (for LCD display only), an alarm code and the

 

time since its activated in the format hours:minutes:seconds (seconds for LCD display only).

 

Note: You can also access alarm visualization by pressing the ESC key from the main screen.

 

The alarm is only reset if the alarm has ended and it will send you back to the main screen.

 

Note: Alarms can also be reset by holding ESC for 3 seconds on the alarm screens

 

 

Menu: EEV

Functionalities: Enable EEV using EKE 1C

 

Functionalities: Enable EEV using EXD 316

 

The parameters inside the external drivers can be checked and changed in the Config EEVx menu.

 

The available parameters for the EXD are: r05, r09, r10, r12, A34, n04, n05, n06, n09, n10, n11, n15,

 

n17, n18, n19, n20, n21, n22, n32, n37, n38, n39, n40, n42, n43, n44, n45, n50, o10, o18, o20, o21,

 

o30, o45, o56, o61, n03

 

The available parameters for the EKE are: R012, R009, r105, r107, O030, N102, N015, N104, N017,

 

N021, N107, N009, N010, N116, N005, N019, N004, N020, N117, N119, N130, N011, N140, N141,

 

A034, A103, A104, A110, A102, I020, I022, I040, I042, I043, O020, O021, I067, R005, B101, O002,

 

O022, G003, N108, N109

 

The Load Factory menu overwrite the EXD parameters with the default ones

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 7

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Menu: VSH Monitor

Functionalities: Enable VSH Modbus control

VSH Status:

VSH Alarms:

The STW bit-map is:

VSH inverter details:

8 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Menu: VSH Control

These commands are linked with the control word of the inverter

Menu: Clock

Functionalities: Enable Scheduler

Note: with the number beside to the function "Enable scheduler" you set the maximum amount of records, before to change it consider that it also affects the EEPROM.

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 9

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Menu: Language

Menu: Service

Software info: Check variables status F01-F07

Device info:

Show rolling text:

Enabling rolling text will add additional information in the main screen

-P: Power demand

-CxAlarm: Compressor X is in alarm

-CxCTy: Compressor X is waiting for the parameter with the label CTy

-P-Down: Compressor is waiting for pump down to be switched off

-CxPrev: Circuit X is being reducing by prevention

Network reset: it restarts from zero the managing of the master slave network

Stepper valves info:

10 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Menu: Hours Counters

Note: The Reset Counters menu resets to zero all the counters, compressors and both pumps.

 

For resetting the single compressor or pump push "Enter" button into the screen where are reported

 

the hours of the device.

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 11

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Parameters

Display

Parameter: dSA, dSb, dsc, Log, Par

How to customize the main screen.

dSA-Display A value

0= OFF : Display A is not used

 

1= IdOF : Display A shows the state of the digital input ON/OFF

 

2

=SEt : Display A shows the set point of the compressors regulation

 

3

=rEg : Display A shows the probe used for regulation

 

4=AI1 : Display A shows the value of the analogue input 1

 

……

 

19 =AI16 : Display A shows the value of the analogue input 16

 

 

 

dSb-Display B value

0

=OFF : Display B is not used

 

1=IdOF : Display B shows the state of the digital input ON/OFF

 

2=SEt : Display B shows the set point of the compressors regulation

 

3

=rEg : Display B shows the probe used for regulation

 

4

=AI1 : Display B shows the value of the analogue input 1

 

 

19 =AI16 : Display B shows the value of the analogue input 16

 

20 =TcP1 : Display B shows the temperature calculated from the dP1 sensor

 

 

23 =TcP4 : Display B shows the temperature calculated from the dP4 sensor

 

 

 

dsc-Icone for cooling mode

 

 

 

 

Log- Logo

Log=0 is combined with the image StartLogoDX in Chiller/BIN/Graph folder

 

Log=1 is combined with the image StartLogoDX_1 in Chiller/BIN/Graph folder

 

Note: the logo is shown just after the power on, pay attention to the size of the image because it is fit

 

in this screen

 

 

Par- Parameters version

It is not used in the software, can be used to recognize different set of parameters

 

Note: this number is reported into the software information

 

 

 

12 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Password

Parameter: L01, L02, L03

How to change the passwords.

L01, L02, L03-

Typing the parameter L0X, in the login screen, you will be able to see all the parameters and menu

Level x password

with level <= of X;

 

The level of access is highlighted in the yellow square;

 

after 10 minutes of inactivity the display is set to an access level of zero

 

 

SetUp

Parameter: y01, y02, y03, y04, y05, y06, y08, y09

How to switch ON-OFF and change the application mode from parameters.

Functionalities: Enable scheduler

Functionalities: Enable show compressor status

Digital input: ONO

Digital output: UNT

y01- System ON/OFF

0=Machine OFF

 

1=Machine status depends on the DI _ONO

 

Defines whether the chiller is in the ON or OFF state, it can be changed from the menu, remotely by

 

Modbus or CANBUS and from start screen by holding the up arrow key.

 

Note1: The software is in ON status only if y02=ON and DI_ONO=ON

 

Note2: The chiller status is also reported in the digital output UNT_Unit Status

 

 

y02- Restart mode after

0=OFF means that after power on, the chiller gets up in OFF state

power OFF

1=ON means that after power on, the chiller gets up in ON state

 

2=EQUA means that after power on, the chiller keeps the same state as before power off

 

 

y03- System heat/cool

It works only with H40> 0 and rE2=UI;

 

This defines whether the machine should be in chiller mode or heat pump mode.

 

This parameter can also be changed from the “Start” menu

 

 

y04- Actuators delay from

It is in seconds and sets the delay when powered ON (not when the unit status changes to ON) before

power ON

activating any outputs. Its purpose is to distribute the drawn current and protect the elements and

 

particularly the compressor against repeated starts in the event of frequent power failures. When the

 

timer has elapsed, the controller starts to manage the outputs based on the other times and the other

 

normal functions.

 

 

y05- Temperature

0=C means that the user interface will show values in Celsius and bar

measurement unit

1=F means that the user interface will show values in Fahrenheit and PSI

 

 

y06- Keyboard lock

0=No

 

1=Yes means that the user interface is locked

 

Note: This parameter can be adjusted in order to be set remotely because it is not enabled for the menu

 

 

y08- Scheduler enable

0=No means that the scheduler is disabled

 

1=Yes means that the scheduler is enabled

 

Note: the “Enable scheduler” functionality is required

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 13

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

y09- Show rolling test

0=No

 

1=Yes

 

Provides information about what is going on in relation to the cutting in/out of the compressors

Note: If the functionalities “Enable show compressor status” is enabled in the UI, a small icon is added for each compressor

Serial setting

Parameter: Cid, Ser, bAU, COM

How to configure the communication port.

Functionalities: Enable Modbus address different from CANBUS address

Cid – Serial address (CAN)

Defines the ID in the CANBUS communication

 

Note: the baud rate and the settings of the CANBUS communication is tuned through the bios menu

 

or though the MYK

 

 

SEr – Serial address (MODBUS)

Defines the ID in the Modbus communication

 

Note: the functionalities “Enable Modbus address different from CANBUS address” is required

 

 

bAU – Serial baud rate (Mod-

Defines the baud rate in the Modbus communication

bus)

0 means Reserved: do not use

 

1 means 1200 bits/sec

 

2 means 4200 bits/sec

 

3 means 4800 bits/sec

 

4 means 9600 bits/sec

 

5 means 14400 bits/sec

 

6 means 19200 bits/sec

 

5 means 28800 bits/sec

 

8 means 38400 bits/sec

 

9 means 57600 bits/sec

 

8 means 115200 bits/sec

 

 

COM – Serial settings

Defines the serial settings of the Modbus communication

(Modbus)

0 means 8N1

 

1 means 8E2

 

2 means 8N2

 

 

14 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Evaporator

Parameter: H1, H2, H3, H4, H5, H12

How to configure the internal coils.

Digital input: OPE, OPE1, OPE2

Digital output: PE1, PE2, …, PE8, H1, …, H4

Analogue input: TIN, TOM, TO1, …, TO4

Analogue output: E1, …, E4

Alarms: AE1, AO7, AP0, AP1, …, AP9

H1 – Number of evaporators

Defines the number of internal coils;

 

The supply temperature (TIN) is the same for all the coils.

 

Each coil has a “leaving temperature” (T01-T04) ; there is also a common “leaving temperature” sensor

 

for all the coils ( TOM)

 

 

H2 – Number of circuits per

Defines the number of circuits for each internal coil;

evaporator

Configuration accepted:

 

1 circuit per internal coil -> 0<H1<5

 

2 circuits per internal coil ->0<H1<3

 

3 circuits per internal coil H1=1

 

4 circuits per internal coil H1=1

 

 

H3 – Air or water cooling

Defines whether the evaporation process is managed by a pump (H3=H2O) or a fan (H3=Air):

 

• WATER evaporators (H3=H2O). For each evaporator, the H1,...,H4 digital outputs which are

 

necessary to manage the antifreeze heaters on the basis of the leaving water temperature TO1,...,TO4

 

are controlled. The number of heaters per evaporator is defined by H5.

 

• AIR evaporators (H3=Air). Only the “TO1_Tout Evaporator 1” input is used to measure the supply air

 

temperature even when more than one evaporator is present. The ice alarm AE1 is replaced with the

 

Low air temperature warning A07 which is set to the same parameters as the ice alarm.

 

 

H4 – Number of pump/fan per

Defines the pumps (or fan) per evaporator:

evaporator

• WATER evaporators (H3=H2O): The PE1 and PE2 digital outputs are managed to control one pump

 

or two twin pumps.

 

• AIR evaporators (H3=Air): “PE1 and PE2” outputs are used to manage fans on the evaporator.

 

Note: check "Fun for internal coil"

 

 

H5 – Number of heaters per

Defines the number of heaters for each internal coil;

evaporator

Configuration accepted:

 

1 heater per internal coil -> 0<H1<5

 

2 heaters per internal coil ->0<H1<3

 

3 heaters per internal coil ->H1=1

 

4 heaters per internal coil ->H1=1

 

 

H12 –Fan in common for each

0=NO means that each fan (AO ECx) works in relation to the evaporator pressure

evaporator

1=Yes means that only the fan EC1 will work in relation to worst pressure in the evaporators

 

Note: the fan speed is managed with PI logic (check parameters ECS,….,Hi)

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 15

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Compressor

Parameter: H6, H7

How to configure the compressors number.

H6 – Number of compressor

Defines the number of compressor per circuit;

per circuit

It’s not possible have circuits with different number of compressors

 

Configuration accepted:

 

• 1 compressor per circuit -> 0<H1*H2<5

 

• 2 compressors per circuit ->0<H1*H2<5

 

• 3 compressors per circuit ->0<H1*H2<3

 

• 4 compressors per circuit ->0<H1*H2<3

 

• >4 compressors per circuit ->0<H1*H2<2

 

 

H7 – Number of unloader per

Defines the number of compressor partialisation;

compressor

The number of regulation steps is equal to H6*H2*H1*(H7+1)

 

Activation and deactivation of the compressor’s unloader is defined by the parameters

 

C04-Unloaders activation mode” and “ C05-Unloaders deactivation mode”

 

 

16 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Condenser

Parameter: H9, H10, H11

How to configure the external coil.

Digital input: OFC, FCL1, …, FCL4, OFC1, …, OFC12

Digital output: FC1, …, FC12

Analogue output: Fc1, …, Fc4

Alarm: AF1, …, AF12

H9 – Air or water cooler

Defines whether the fans or the pump regulate condensing.

condenser

0=AIR : Controls defrosting in heating mode.

 

1=H2O : The configuration managed is H10=1 and H11=Yes

 

Note: the pump or fan behaviour is defined by parameters F01, F02 and F03

 

 

H10 – Number of pump/fans

Defines the necessary digital output to control the pumps or fans on the condenser.

per condenser

• Water-cooled units (H9=H2O).The single “Cond Fan1/Pump1” digital output is controlled to drive

 

a pump.

 

• Air-cooled units (H9=AIR). Contributes to defining the total number of managed ventilation steps and

 

thus of the corresponding ”Condenser Fan1”, ..., ”Condenser Fan8”digital outputs used to drive them.

 

 

H11 –Fan in common to all

On multi-circuits units, fans can be in common to all condensers.

condenser

If fans are not in common to all condensers (H11=0=NO), the following output are controlled:

 

• as many analogue inputs as the condensers (H1*H2)

 

• as many digital outputs as the condensers (H1*H2), multiplied by the number of fans per condenser

 

(H10); digital outputs for fans are assigned to condensers in a sequential and balanced way,

 

assuming that all condensers have the same number of fans; e.g. in a system made of 2 condensers

 

and 6 fans, “Cond Fan1/Pump1”, “Condenser Fan2” and “Condenser Fan3” outputs are assigned to

 

control fans belonging to the first condenser; “Condenser Fan4”, “Condenser Fan5” and “Condenser

 

Fan6” to the second condenser.

 

• as many analogue output s “InverterFanCond1”,...,”InverterFanCond4” for condensing control as for

 

the condensers (H1*H2).

 

If fans are common to all condensers (H11=1=YES) the following outputs are used:

 

• as before, as many analogue inputs for condensing controls as there are circuits per condenser

 

(H1*H2), but the one requiring the higher response from the control is used for regulation. Each

 

analogue input is then used for defrost control in heating mode;

 

• as many digital outputs as fans per condenser (H10);

 

• one analogue output “InverterFanCond1” for fan speed regulation.

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 17

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Heat Pump

Parameter: H40, H41, H42

How to configure the heat pump mode

Functionalities: Enable Heat Pump Control

Digital output: HC1, …, HC4, BO1, …, BO4

Analogue input: SP1, …, SP4, dP1, …, dP4

H40 Heat pump type

0=No means that the software does not perform heating mode

 

1=GAS means that the software performs the heating mode, the internal coil is the evaporator in

 

cooling mode and the condenser in heating mode

 

1=H2O means that the software performs the heating mode, the coils keep the same meaning in

 

both heating and cooling mode both

 

Note: one digital output “Reverse Valve C1”, ..., “Reverse Valve C4” per each circuit is reserved for

 

controlling the reverse flow valve

 

 

H41- Boiler number of heaters

Boiler heaters “Boiler1”, ..., “Boiler4” are turned ON when the temperature measured by the regulation

 

probe enters in the area defined by the active regulation setpoint in heating (SH1) and differential rH1.

 

They are an alternative to the heat pump, not in addition.

 

Boiler heaters can be activated only if the temperature measured by the “BoilerSafety” probe is

 

under a specific safety limit AbS. If it is over the limit, alarm A14 is generated.

 

To reset the alarm there is a constant differential Abd to be considered.

 

 

H42- Probe change in HP

0=No means that the probe is before the 4-way valve (close to the compressor):

 

• the sensor SPx – Suction pressure Cx measures low pressure

 

• the sensor dPx – Discharge pressure Cx measures high pressure

 

1=Yes means that the probe is after the 4-way valve (close to the coils):

 

• the sensor SPx – Suction pressure Cx measures low pressure in cooling mode and high pressure in

 

heating mode

 

• the sensor dPx – Discharge pressure Cx measures high pressure in cooling mode and low pressure

 

in heating mode

 

Note: if ex2=yes the variable used from H42 (pink line below) is always about low pressure, in

 

this case pay attention to set H42=No because in heating mode the discharge pressure will not

 

be available

 

 

18 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Maintenance

Parameter: H43

How to manually set the compressor power request.

Functionalities: Enable commissioning for power request

Digital output: MPR

H43- Manual chiller power

The power request provided to the compressors is about H43 %

 

H43< zero means that the function is disabled

 

Note: if H43 >=0 the digital output MPR is closed

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 19

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Network settings

Parameter: n01,…n17

The Master and Slave is a functionality that allow a group of machines to be managed like one machine (Master) decides which and how many units (Slaves) should run.

The max number of units is 8 (7 slaves + 1 master), the network is CANBUS. The Master and Slave function optimizes:

-ageing of machines

-distribution of the load in order to improve the performance of the plant

-The backup units

Functionalities: Enable Master/Slave

Alarms: N01, N02, N03, N04, N05,N06, N07, N08

n01 MCX network disable

0=NO means that the Master slave function is enabled

 

1=Yes means that the Master slave function is disabled

 

 

n02 –Number of slave nodes

It has to be set equal to (“number of chillers in the network” -1)

 

 

n03- Auto master select

0=NO means that the master in the master slave network can be only the chiller with the CANBUS ID

 

equal to n15: if the master is not more available in the network, the other chillers will start to work in

 

standalone mode

 

1=Yes means that the master in the master slave network is the chiller with lowest CANBUS ID

 

 

n04- Distribution algo

0= PWR The master, using its own sensors, decides how many chillers are working and the chillers’

 

power supply;

 

The maximum number of units that can work is related to the gap between setpoint and

 

temperature: practically the regulation band is divided for the number of machines (n02+1-n09):

 

1= CAP the master manages only the start order (following the ageing of the machines), chillers

 

manage their power as standalone machines.

 

If all the units which are running have capacity above n12 %, the master will switch on another chiller (the

 

youngest one).

 

If all the units which are running have capacity below n13 %, the master will switch off the oldest chiller

 

running

 

The minimum time between two actions of the master is n14 seconds

 

 

n05- Power Smart power

1=Yes means that the master is allowed to cut-in the first chiller available without considering the

distribution enable

start order related to the ageing of the machines

 

 

n06- Node rotation enable

0=No means that the start sequence of the machines is fixed; the order depends on the addressing,

 

the first to start is the machine with the smallest CANBUS ID, the first to stop is the chiller with the

 

highest CANBUS ID

 

1=Yes means that the start/stop sequence of the machines depends on the ageing of the chillers,

 

always starting with the youngest of the set and the oldest one is always the first to stop. In the case

 

that one machine works n17 hours more than another chiller that is switched off, the master will

 

exchange the unit in order to align the ageing.

 

 

20 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

n07- Backup node offset

When the gap between setpoint and temperature is above (n07+regulation band), the first backup

 

unit is allowed to work as a support, also considering parameter n08 .

 

Note: the offset to enable the other backup units is (n07*m+ regulation band):

 

m = 2 for the second backup unit

 

m = 3 for the third backup unit

 

 

Note: the backup units will work running normally after the set point. It will be switched off when the

 

gap between setpoint and temperature is below the regulation band

 

Note: the pump behaviour is defined through the parameter P01

 

 

n08- Time to enable n07

It’s the time to stay far away from the setpoint in order to cut in the backup unit

 

Note: check parameter n07

 

 

n09-Number of back-up unit

n09 defines the number of backup units inside the master slave network

 

A backup unit is never enabled (so does not provide cooling capacity) unless one of the following

 

situations occurs:

 

• one of the other units becomes unavailable

 

• Support (see parameter n07 and n08)

 

Note: The master chooses the backup unit (among all nodes present in the network) by looking at

 

the working time of every unit: the one which has worked the longest will be the backup unit.

 

 

n10 – Evaporator in common

0=No each chiller consider its own evaporator flow alarm

 

1=yes the master will read its “FPE” digital input (Flow Evaporator) and will send the information to

 

other slaves

 

 

n11 – Pump alarm in common

0=No each chiller considers its own pump alarm

 

1=yes the master will read its “AP1” digital input (Evap pump/fan overload alarm) and will send the

 

information to other slaves

 

 

n12 – Capacity upper

See parameter n04

threshold

 

 

 

 

n13 – Capacity lower

See parameter n04

threshold

 

 

 

 

n14 – Capacity step min time

See parameter n04

 

 

n15 – Master node CAN ID

It has to be set equal to the lowest ID in the CANBUS network

 

 

n16 – Slaves node CAN ID offset

The slaves have to take the CAN ID in relation to the n15 just adding n16.

 

E.G. for n02 =3

 

Master ID= n15

 

Slave1 ID= n15+n16

 

Slave2 ID= n15+n16+n16

 

Slave3 ID= n15+n16+n16+n16

 

 

n17 – Maximum gap time for

It is in hours

unit rotation

If a running unit becomes older than a switched-off unit by more than n17 hours, the logic will

 

switch off the oldest unit running it will cause the other unit to be switched on.

 

 

n18 – Backup unit pump

0=OFF: the backup chillers in standby have the pump switched-off

status

1=ON: the backup chillers in standby have the pump switched-on

 

Note:during support or backup, the pump of the chiller follow P01 setting

 

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 21

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Configuration

Parameter: rEG, rET, rT1, rT2, o30, Er1

rEG – Analogue input for

0= Tin : reference sensor is Tin_Tin Evaporator

temperature regulation

1= ToM: reference sensor is TOM_Tout Evap Mix

 

2 =AI1: reference sensor is the analogue input 1

 

……

 

17 =AI16 : reference sensor is the analogue input 16

 

18 =SPT1: reference is the temperature calculated from the sensor SP1_Suction Press C1, the gas

 

type is set using parameter o31

 

 

rET – Regulation Type

Defines the relation between the temperature gap and the power request to the circuits.

 

0=P : Power request to the circuits increases in proportional way with the regulation error, i.e., it is

 

100% when the regulation error (the gap between setpoint and the reference sensor ) is equal to rC1

 

( rH1)

1=PI: the power request is the sum of P regulation (rET=0) plus a component (Integral part) that increases in relation to the regulation error; the speed of the integral part depends on the parameter rin_Ti.

For PI regulation, the balance is reached only when the regulation sensor gets the setpoint.

2=dZ : The delay between compressors activations varies between a maximum value dd5 and minimum value dd6 proportional to the temperature position inside the regulation band defined by the activation differential dd1.

Above setpoint + dead zone + activation differential, the delay among activations is equal to the minimum.

Similarly the action for the delay among compressors deactivations, which can vary between a maximum value dd7 and a minimum value dd8, is proportional to the temperature position inside the regulation band defined by the deactivation differential dd2.

Below a setpoint differential, the delay among activations is equal to the minimum value, dd8, up to a limit threshold, dd3. Below that, all the compressors are immediately switched OFF to avoid the unit ice alarm.

rT1- Minimum limit for

The analogue output rtr linearly replays the regulation probe (check parameter rET)

TReg TX

It gets to 0% when the regulation probe reaches a value of rT1

 

Note: if the regulation probe is in error the AO_rtr gets to 100%

 

 

rT2- Maximum limit for

The analogue output rtr linearly replays the regulation probe (check parameter rET)

TReg TX

It gets to 100% when the regulation probe reachs rT2 value

 

Note: if regulation probe is in error the the AO_rtr gets to 100%

22 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

o30 – Gas type

0=---

 

1=R12

 

2=R22

 

3=R134a

 

4=R502

 

5=R717

 

6=R13

 

7=R131b1

 

8=R23

 

9=R500

 

10=R503

 

11=R114

 

12=R142b

 

13=--

 

14=R32

 

15=R227

 

16=R401a

 

17=R507

 

18=R402a

 

19=R404a

 

20= R407c

 

21= R407a

 

22= R407b

 

23= R410a

 

24= R170

 

25= R290

 

26=R600

 

27= R600a

 

28= R744

 

29= R1270

 

30=R417a

 

31=R422a

 

32=R413A

 

33=R422D

 

34=R427A

 

35=R438A

 

36=R513A

 

37=R407F

 

38=R1234ze

 

39=R1234yf

 

40=R448A

 

41=R449A

 

42=R452A

 

43=R450A

 

44=R452B

 

45=R454B

 

46=R1233zdE

 

47=R1234zeZ

 

48=R449B

 

49=R407H

 

Note: the gas definition is used when the translation of the pressure in temperature is required;

 

ReG=SPT1 and for the “internal” super heat control

 

 

o31 – Dew/Bubble Conversion

0=Dew

mode

1=Bubble used for the gas that require the "Glide" approximation

 

 

Er1 – Emergency mode

Er1 = -1 the function is disabled

max power

Er1 >= 0 when the digital input EEr is closed the power request is limited to Er1 instead of 100%

 

Note: the functionality “Enable emergency mode from DI” is required

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 23

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Main Setpoint

Parameter: SC1, SCL, SCH, SH1, SHL, SHH, SRE

Analogue input: TRM

SC1 – Cooling temperature set

Defines the setpoint in cooling mode

point

 

 

 

SCL – Minimum limit

Defines the minimum limit of the setpoint in cooling mode

 

Note: This limit is not respected when adjusted through Modbus

 

 

SCH – Maximum limit

Defines the maximum limit of the setpoint in cooling mode

 

Note: This limit is not respected when adjusted through Modbus

 

 

SH1 – heating temperature set

Defines the setpoint in heating mode

point

 

 

 

SHL – Minimum limit

Defines the minimum limit of the setpoint in heating mode

 

Note: This limit is not respected when adjusted through Modbus

 

 

SHH – Maximum limit

Defines the maximum limit of the setpoint in heating mode

 

Note: This limit is not respected when adjusted through Modbus

 

 

SRE- Remote set enable

The regulation setpoint is defined through the analogue input TRM_Remote Set

 

0=NO means that the function is not enabled

 

1=rEL means that

 

set point = main setpoint + offset from analogue input (TRM_Remote set)

2=Abs means that set point is linearly defined through AI_TREM, between SCL - SCH in cooling and SHL - SHH in heating

24 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Economic Setpoint

Parameter: SdS, SdM, SdC, SdH, SdO

SdS- Setpoint selection

0=DI means that the digital input SET2_Reg offset from DI defines if use comfort setpoint (SC1 or

 

SH1) or the economic setpoint (SC1+SdC or SH1-SdH); in economic mode the proportional band in

 

the PI control is increased by SdO

 

1=PAR meaning that the parameter SdM_Setpoint mode defines whether comfort setpoint

 

(SC1 or SH1) or the economic setpoint (SC1+SdC or SH1-SdH) is to be used; in economic mode the

 

proportional band in the PI control is increased by SdO

 

 

SdM- Setpoint mode

It works only for SdS=PAR

 

0=COMF meaning that chiller uses comfort setpoint ( SC1 or SH1)

 

1=ECO meaning that the chiller uses economic setpoint (SC1+SdC or SH1-SdH)

 

In economic mode the proportional band in the PI control is increased of SdO.

 

 

SdC-Offset for setpoint in cool-

In economic status and cooling mode the regulation setpoint is shifted to SdC.

ing

Note: see parameter SdS

 

 

SdH-Offset for setpoint

In economic status and heating mode the regulation setpoint is shifted to SdH.

in heating

Note: Take a look to parameter SdS

 

 

SdO-Offset for differential

In economic mode the proportional band of regulation becomes rC1+SdO or rH1+SdO.

 

Note: look at parameter SdS

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 25

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Setpoint compensation in based on the outside temperature

Parameter: CC1, CC2, CC3, CC4, CH2, CH3, CH4

Analogue input: OUt

CC1-Compensation enable

0=NO means compensation disable

 

1=YES means compensation enable

 

Note: this function adapts the setpoint to the outside temperature “Tout”

 

 

CC2-Outside temperature to

It’s in °C

start cool comp.

 

 

 

CC3-Outside temperature to

It’s in °C

stop cool comp.

 

 

 

CC4-Maximum cooling

It’s in °C

compensation

 

 

 

CH2-Outside temperature to

It’s in °C

start heat comp.

Like CC2 but used in heating mode

 

 

CH3-Outside temperature to

It’s in °C

stop heat comp.

Like CC3 but used in heating mode

 

 

CH4-Maximum heating

It’s in °C

compensation.

Like CC4 but used in heating mode

 

 

26 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

PI regulation

Parameter: CrC1, rH1, Rin, rC2, rC3

Note: the PI regulation is enabled when the parameter rET is equal to P or PI

rC1-Cooling temperature

See parameter rET

differential.

 

 

 

rH1-Heating temperature

See parameter rET

differential.

 

 

 

Rin- Ti

It is the integral time of the PI regulation, the bigger the value of Rin the slower the action of the

 

Integral part.

 

See parameter rET

 

 

rC2-Cut Off enable

It enables the gradual reduction of the integral error once reached and exceeded the setpoint. The

 

error integral in fact tends to keep the compressors turned on even if the proportional part of the

 

error would require a shutdown. The amount of reduction is proportional to the distance from the

 

setpoint considering the rC3 band. For example, in cooling, the reduction is zero when the control

 

temperature is equal to the setpoint; the reduction is greatest when it is equal to setpoint-rC3.

 

 

rC3- Cut off offset

 

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 27

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Dead zone regulation

Parameter: ddC, ddH, dd1, dd2, dd3, dd4, dd5, dd6, dd7, dd8

Functionalities: Enable Dead Zone Regulation

The dead zone regulation is enable when the parameter rET is equal to DZ It is a variable time regulation mainly used when the regulated value is the temperature of the fluid leaving the evaporator.

In the dead zone ddC no regulating action is taken.

Close to the dead zone the decision to cut the compressor in or out will take a maximum time of (dd5 or dd7), a time that will decrease linearly outside the dead zone. This variable time logic is described below.

ddC-Cooling dead zone

In dead zone ddC no regulation action is taken.

 

This is above the setpoint and used in cooling mode

 

 

ddH-Heating dead zone

In dead zone ddH no regulation action is taken.

 

This is below the setpoint used in heating mode

 

 

dd1-Comp activation

Defines the maximum temperature gap to have a minimum delay (dd6) in the compressor’s activation

differential

Note: see picture in the parameter ddC and ddH

 

 

dd2-Comp deactivation

Defines the maximum temperature gap to have a minimum delay (dd6) in the compressor’s

differential

deactivation

 

Note: see picture in the parameter ddC and ddH

 

 

dd3-Min temp for OFF comp

Defines the minimum temperature below which the compressors are switched off

in cooling

Note: see picture in the parameter ddC

 

 

dd4-Max temp for OFF comp

Defines the maximum temperature above which the compressors are switched off

in heating

Note: see picture in the parameter ddH

 

 

dd5-Max delay of comp activa-

Defines the maximum delay before a compressor cuts in

tion

Note: see picture in the parameter ddC and ddH

 

 

dd6-Min delay of comp

Defines the minimum delay before a compressor cuts in

activation

Note: see picture in the parameter ddC and ddH

 

 

dd7-Max delay of comp

Defines the maximum delay before a compressor cuts off

deactivation

Note: see picture in the parameter ddC and ddH

 

 

dd8-Min delay of comp

Defines the minimum delay before a compressor cuts off

deactivation

Note: see picture in the parameter ddC and ddH

 

 

28 | BC295150867120en-000201

© Danfoss | DCS (vt) | 2019.08

User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors

Digital output lock

Parameter: DOn, Ain, Dos, DOd

It is possible to lock a digital output in open position in relation to an analogue input.

The lock condition is reported in the rolling text

Functionalities: Enable DO Locking from AI

DOn-Digital output number

This is the number of the digital output to lock in open position;

 

The conditions to lock it are defined by AIn, DOs and DOd

 

 

AIn-Analogue input number

This is the number of the analogue input to refer to lock the digital output DOn

 

 

DOs-Set point for locking

This is the setpoint to compare with the value of the analogue input AIn for locking the digital output

 

DOn;

 

Note: set parameter DOd to lock the digital output DOn above or below the setpoint DOs

 

 

DOd-Differential to unlock

 

 

 

Buzzer and relay

Parameter: BUZ, Adl, AOF

BUZ-Buzzer activation time

It's in minutes.

number

Defines the maximum time that the buzzer can work;

 

BUZ=15 means that there is no limit in the active time of buzzer

 

 

Adl-Alarm relay activation

It's in seconds.

delay

Defines the delay of the alarm relay when there is an alarm

 

 

AOF-Alarm relay active if unit

Defines whether the alarm relay works in the OFF state of the chiller

in off

 

 

 

© Danfoss | DCS (vt) | 2019.08

BC295150867120en-000201 | 29

Loading...
+ 65 hidden pages