User Guide
Chiller and reversable chiller
Reciprocating, scroll and screw compressors
Software Version 4.40.00
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Contents
User Interface............................................................................... |
4 |
High water temperature alarm in cooling mode..................... |
34 |
LED Display, LCD Display, Keyboard, Unit status, Login, Start, |
Parameter: Ats, Atd |
|
|
Parameter, Input/Output, I/O Display, I/O Config, I/O Prb |
|
Boiler water temperature alarm............................................... |
34 |
Calibration, I/O Commissioning, Alarm, EEV, VSH Monitor, VSH |
Parameter: AbS, Abd |
|
|
Control, Clock, Language, Service, Hours Counters, Variable |
|
Fault of the regulation probe of the external coil................... |
35 |
speed pump |
|
Parameter: ACM, ACS, ACd |
|
Parameters.................................................................................. |
12 |
Preventions................................................................................. |
35 |
Display........................................................................................ |
12 |
Parameter: TMx, THo, TLo, HPE, HPo, HPh, LPE, LPo, LPh, PPt, |
|
Parameter: dSA, dSb, dsc, Log, Par |
|
PPp, HFo |
|
Password..................................................................................... |
13 |
Superheat alarms....................................................................... |
37 |
Parameter: L01, L02, L03 |
|
Parameter: SHh, AHI, Ahi, AHd |
|
SetUp........................................................................................... |
13 |
Oil temperature alarms.............................................................. |
37 |
Parameter: y01, y02, y03, y04, y05, y06, y08, y09 |
|
Parameter: OTm, OTi, OTd |
|
Serial setting............................................................................... |
14 |
Screw compressors..................................................................... |
38 |
Parameter: Cid, Ser, bAU, COM |
|
Parameter: C01, C02, CSO, CSb, T1, T2,T3, T4, C07, C08, T5, T6, |
|
Evaporator.................................................................................. |
15 |
T21, T22, T24, T24, T25, T26, T27, T28, T29 |
|
Parameter: H1, H2, H3, H4, H5, H12 |
|
Starting type of the compressor............................................... |
42 |
Compressor................................................................................. |
16 |
Parameter: Sty, Sti, SSt, Stm, Sdd |
|
Parameter: H6, H7 |
|
Economizer................................................................................. |
43 |
Condenser................................................................................... |
17 |
Parameter: E01, EO2, EO3, EO4 |
|
Parameter: H9, H10, H11 |
|
Liquid injection.......................................................................... |
44 |
Heat Pump.................................................................................. |
18 |
Parameter: T41, T42, T43, T44, T45 |
|
Parameter: H40, H41, H42 |
|
Compressor with unloaders...................................................... |
44 |
Maintenance............................................................................... |
19 |
Parameter: C04, C05, C06, C08 |
|
Parameter: H43 |
|
Maximum number of compressor starts per hour................... |
45 |
Network settings........................................................................ |
20 |
Parameter: CT0, CT1, CT2, CT3, CT4, CT5, CT6, CT7 |
|
Parameter: n01,…n17 |
|
Valve in the liquid line............................................................... |
46 |
Configuration............................................................................. |
22 |
Parameter: Pd1, Pd2, Pd3, Pd4 |
|
Parameter: rEG, rET, rT1, rT2, o30, Er1 |
|
Maximum compressor running hours...................................... |
47 |
Main Setpoint............................................................................. |
24 |
Parameter: C50 |
|
Parameter: SC1, SCL, SCH, SH1, SHL, SHH, SRE |
|
Inverter compressor................................................................... |
48 |
Economic Setpoint..................................................................... |
25 |
Parameter: IV0, IV1, IV2, IV3, IV4, IV5 |
|
Parameter: SdS, SdM, SdC, SdH, SdO |
|
Compressor enabling................................................................. |
50 |
Setpoint compensation in based on the outside temperature.. 26 |
Parameter: CT1, CT2, CT3, CT4, CT5, CT6, CT7, CT8 |
|
|
Parameter: CC1, CC2, CC3, CC4, CH2, CH3, CH4 |
|
Heaters........................................................................................ |
50 |
PI regulation............................................................................... |
27 |
Parameter: HE1, HE2, HE3, HE4, HE5, HE6, HE7 |
|
Parameter: CrC1, rH1, Rin, rC2, rC3 |
|
Pump of the internal coil........................................................... |
51 |
Dead zone regulation................................................................ |
28 |
Parameter: P01, P02, P03, P04 |
|
Parameter: ddC, ddH, dd1, dd2, dd3, dd4, dd5, dd6, dd7, dd8... |
28 |
Modulating Pump...................................................................... |
52 |
Digital output lock..................................................................... |
29 |
Parameter: ERT, ECS, ECd, ECi, EHS, EHd, EHi, EDB, EI1, EI2, EI3 |
|
Parameter: DOn, Ain, Dos, DOd |
|
Fan for the internal coil.............................................................. |
53 |
Buzzer and relay......................................................................... |
29 |
Parameter: P21, P22, P50 |
|
Parameter: BUZ, Adl, AOF |
|
Free cooling................................................................................ |
54 |
Flow alarm.................................................................................. |
30 |
Parameter: FrA, Fr1, Fr2, Fr3, Fr4, Fr5, Fr6, Fr7, Fr8, Fr9, FI1, |
|
Parameter: AFr, AF1, AF2, AF3 |
|
FI2, FI3 |
|
ICE alarm..................................................................................... |
31 |
Valve in the water line................................................................ |
56 |
Parameter: AIS, AID, Air, AI1, AI2, AI3, AIT, AIo |
|
Parameter: EF1, EF2 |
|
Compressor oil delta pressure alarm........................................ |
32 |
External coil................................................................................ |
56 |
Parameter: OPR, OdP, GdP |
|
Parameter: F01 |
|
Circuit high temperature alarm................................................ |
32 |
Fan requests................................................................................ |
57 |
Parameter: HTs, HTd |
|
Parameter: F02, F03, FC, FCD, FCI, FCd, FHS, FHD, FHI, FHd |
|
Pressure alarms from analogue input...................................... |
33 |
Fan regulation with a variable proportional part................... |
59 |
Parameter: AHE, AHS, AHd, Alr, AL1, AL2, ALE, ALS, ALd, LPt, |
Parameter: F31, F32, F33, F34, F35, F36, F37, F24, F25 |
|
|
AVO, VCt, SHS, SHb |
|
|
|
2 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Economic setpoint for fan regulation....................................... |
60 |
Parameter: SS1, SS2, SS3, SS4 |
|
Stepless regulation of the fan................................................... |
60 |
Parameter: F10, F11, F12, F13, F14, F20, F21, F22, F23 |
|
Hot gas bypass valve.................................................................. |
61 |
Parameter: Bp0, Bp1 |
|
Cooling towers............................................................................ |
62 |
Parameter: WFs, WFd |
|
Reversing cycle valve (4 ways valve)......................................... |
63 |
Parameter: rE2, rE1, rE3, rE4 |
|
Defrost........................................................................................ |
64 |
Parameter: d01, d02, d03, d04, d05, d06, d07, d09, d10, d11, |
|
d12, d13, d14, d15, d16, d20, d22, d23, d25, d26 |
|
Heat recovery............................................................................. |
66 |
Parameter: HRs, HRm, HRc, HRn, HRt, HRo |
|
Superheat................................................................................... |
67 |
Parameter: V10, V20, bAt, ex1, ex2, ex3, N19, N04, N05, N20, |
|
N22, N10, N09, N11, N32, N18, N17, N15, N21, SHO |
|
Input output expansion module............................................... |
69 |
Parameter: XCn |
|
Auxiliary alarms......................................................................... |
69 |
Parameter: a11, a21, a31, a41, a12, a22, a32, a42, a13, a23, |
|
a33, a43, a 14, a24, a34, a44 |
|
Oil Alarm Tandem ...................................................................... |
70 |
Parameter: BME, BST, TD1, TD2, TD3, TD4, ADO, BOF, BFR |
|
Compressor Oil Pump................................................................ |
72 |
Parameter: OPE, OPO, OT1, OT2 |
|
Temperature delta of the oil...................................................... |
73 |
Parameter: OTD, OD1, OD2 |
|
How to set the power request remotely .................................. |
73 |
Parameter: RPE, RPS |
|
How to log data on an SD card ................................................. |
74 |
Parameter: ENL |
|
Commissioning........................................................................... |
77 |
Parameter: Ort |
|
Graphic diagrams of some of the managed unit types........... |
80 |
Status variables.......................................................................... |
91 |
Software status........................................................................... |
91 |
Parameter: A01, …, A19, C01, …, C04, E01, …, E08 |
|
Software info.............................................................................. |
92 |
Parameter: F01, …, F07 |
|
Superheat info............................................................................ |
93 |
Parameter: H01, …, H13 |
|
Preparatory: link to MCXShape manual
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 3 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
LED Display, LCD Display, Keyboard, Unit status, Login, Start, Parameter, Input/Output, I/O Display, I/O Config, I/O Prb Calibration, I/O Commissioning, Alarm, EEV, VSH Monitor, VSH Control, Clock, Language, Service, Hours Counters, Variable speed pump
Functionalities: Enable screen saver for LCD
Functionalities: Enable LED display
Enable support for MMILDS
Functionalities: Enable schema view
Functionalities: Enable I/O probe calibration
Functionalities: Enable override of input and output
Functionalities: Enable commissioning form
Functionalities: Enable EEV using EKE 1C
Enable MMI navigation
Functionalities: Enable EEV using EXD 316
Functionalities: Enable EEV using MCX driver
Functionalities: Enable VSH Modbus control
Functionalities: Enable Scheduler
Functionalities: Enable Evaporator variable capacity pump
Note: playing with MCXShape, it is very easy to customize the structure and the visibility of the menu: so the following indication cannot match with all the compiled software
Main screen: LED Display |
Functionalities: Enable LED display |
Note: check parameters dsA, dSb and dSC.
Main screen: LCD Display
Note: check parameters dsA, dSb and dSC.
Keyboard
: Scroll UP, increment a value
: 3s when in main screen: toggle ON/OFF : Scroll down, decrement a value
: 3s when in main screen: toggle Heat/Cool mode : exit and save,
: when in main screen: access the active alarm list : 3s when in Alarm screen: manual reset
The LEFT and RIGHT keys, if present, allow you to move the cursor to the desired option
4 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: Unit Status |
Functionalities: Enable schema view |
Schema:
View EEV Cx (for valve which is driven by EXD or MCX):
The alarms bit pattern is:
Note: by pressing “OK” key you manually tune the position of the valve
View EEV Cx (for valve which is driven by EKE):
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 5 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: Login |
Parameters and Menu are organized into 4 access levels. Levels from 1 to 3 are linked to a password. |
|
Elements cannot be accessed when they are on a higher level than the entering level. The level of |
|
each parameter and menu is defined with MCXShape |
|
• Level 0 is accessible without password |
|
• Levels 1-3 are linked to a password (Check parameters L01, L02 and L03) |
|
• Level 4 is not linked to a password, it can be used to make menu or parameters never reachable. |
|
You can log in from the menu: |
|
if the password provided is not correct you remain on the login screen. Otherwise you get back to |
|
the main menu. |
|
|
Menu: Start |
|
|
Network menu: used to switch all the machines on or off in the Master and Slave network |
|
Default param. menu: used to load the default value of the parameters which have been defined in |
|
the .mcxs file |
|
|
Menu: Parameter |
This menu contains all the parameters. |
|
The meanings of the parameters are explained in the last part of this manual |
|
|
Menu: I/O Display |
Display input and output values |
|
LED display |
|
Shows you (using the UP and DOWN keys) all the input and output values in sequence, showing the |
|
I/O code on display A (“AI” for analogue input; “AO” for analogue output; “dI” for digital input and “dO” |
|
for digital output) and its value on display B (analogue inputs that are not present or in alarm are |
|
shown with “----”). |
|
LCD display |
|
You have access to three screens showing all the input and output values; each screen shows a group |
|
of 8 I/O. Use UP and DOWN keys to scroll. The second and third screens are used with MCX15 and |
|
MCX20 only. |
|
The example below shows the first screen. |
|
|
Menu: I/O Config |
This menu is prepared for future use |
|
Note: it is under the 4th level of password |
|
|
Menu: I/O Prb Calibration |
Functionalities: Enable I/O probe calibration |
|
inside the “Reset All” menu, you can reset all the offsets to zero |
|
Note: the screens calibration are not translated |
|
|
|
|
6 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: I/O Commissioning |
Functionalities: Enable override of input and output |
|
Functionalities: Enable commissioning form |
|
Note: the logic will not affect the override. The override is stopped for power off, "Reset all" command |
|
and timeout that is defined into the menu "Setup" |
|
|
Menu: Alarm |
Each alarm is described through an alarm description (for LCD display only), an alarm code and the |
|
time since its activated in the format hours:minutes:seconds (seconds for LCD display only). |
|
Note: You can also access alarm visualization by pressing the ESC key from the main screen. |
|
The alarm is only reset if the alarm has ended and it will send you back to the main screen. |
|
Note: Alarms can also be reset by holding ESC for 3 seconds on the alarm screens |
|
|
Menu: EEV |
Functionalities: Enable EEV using EKE 1C |
|
Functionalities: Enable EEV using EXD 316 |
|
The parameters inside the external drivers can be checked and changed in the Config EEVx menu. |
|
The available parameters for the EXD are: r05, r09, r10, r12, A34, n04, n05, n06, n09, n10, n11, n15, |
|
n17, n18, n19, n20, n21, n22, n32, n37, n38, n39, n40, n42, n43, n44, n45, n50, o10, o18, o20, o21, |
|
o30, o45, o56, o61, n03 |
|
The available parameters for the EKE are: R012, R009, r105, r107, O030, N102, N015, N104, N017, |
|
N021, N107, N009, N010, N116, N005, N019, N004, N020, N117, N119, N130, N011, N140, N141, |
|
A034, A103, A104, A110, A102, I020, I022, I040, I042, I043, O020, O021, I067, R005, B101, O002, |
|
O022, G003, N108, N109 |
|
The Load Factory menu overwrite the EXD parameters with the default ones |
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 7 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: VSH Monitor |
Functionalities: Enable VSH Modbus control |
VSH Status:
VSH Alarms:
The STW bit-map is:
VSH inverter details:
8 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: VSH Control
These commands are linked with the control word of the inverter
Menu: Clock
Functionalities: Enable Scheduler
Note: with the number beside to the function "Enable scheduler" you set the maximum amount of records, before to change it consider that it also affects the EEPROM.
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 9 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: Language
Menu: Service
Software info: Check variables status F01-F07
Device info:
Show rolling text:
Enabling rolling text will add additional information in the main screen
-P: Power demand
-CxAlarm: Compressor X is in alarm
-CxCTy: Compressor X is waiting for the parameter with the label CTy
-P-Down: Compressor is waiting for pump down to be switched off
-CxPrev: Circuit X is being reducing by prevention
Network reset: it restarts from zero the managing of the master slave network
Stepper valves info:
10 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Menu: Hours Counters |
Note: The Reset Counters menu resets to zero all the counters, compressors and both pumps. |
|
For resetting the single compressor or pump push "Enter" button into the screen where are reported |
|
the hours of the device. |
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 11 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
How to customize the main screen.
dSA-Display A value |
0= OFF : Display A is not used |
|
|
1= IdOF : Display A shows the state of the digital input ON/OFF |
|
|
2 |
=SEt : Display A shows the set point of the compressors regulation |
|
3 |
=rEg : Display A shows the probe used for regulation |
|
4=AI1 : Display A shows the value of the analogue input 1 |
|
|
…… |
|
|
19 =AI16 : Display A shows the value of the analogue input 16 |
|
|
|
|
dSb-Display B value |
0 |
=OFF : Display B is not used |
|
1=IdOF : Display B shows the state of the digital input ON/OFF |
|
|
2=SEt : Display B shows the set point of the compressors regulation |
|
|
3 |
=rEg : Display B shows the probe used for regulation |
|
4 |
=AI1 : Display B shows the value of the analogue input 1 |
|
… |
|
|
19 =AI16 : Display B shows the value of the analogue input 16 |
|
|
20 =TcP1 : Display B shows the temperature calculated from the dP1 sensor |
|
|
… |
|
|
23 =TcP4 : Display B shows the temperature calculated from the dP4 sensor |
|
|
|
|
dsc-Icone for cooling mode |
|
|
|
|
|
Log- Logo |
Log=0 is combined with the image StartLogoDX in Chiller/BIN/Graph folder |
|
|
Log=1 is combined with the image StartLogoDX_1 in Chiller/BIN/Graph folder |
|
|
Note: the logo is shown just after the power on, pay attention to the size of the image because it is fit |
|
|
in this screen |
|
|
|
|
Par- Parameters version |
It is not used in the software, can be used to recognize different set of parameters |
|
|
Note: this number is reported into the software information |
|
|
|
|
12 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
How to change the passwords.
L01, L02, L03- |
Typing the parameter L0X, in the login screen, you will be able to see all the parameters and menu |
Level x password |
with level <= of X; |
|
The level of access is highlighted in the yellow square; |
|
after 10 minutes of inactivity the display is set to an access level of zero |
|
|
How to switch ON-OFF and change the application mode from parameters.
Functionalities: Enable scheduler
Functionalities: Enable show compressor status
Digital input: ONO
Digital output: UNT
y01- System ON/OFF |
0=Machine OFF |
|
1=Machine status depends on the DI _ONO |
|
Defines whether the chiller is in the ON or OFF state, it can be changed from the menu, remotely by |
|
Modbus or CANBUS and from start screen by holding the up arrow key. |
|
Note1: The software is in ON status only if y02=ON and DI_ONO=ON |
|
Note2: The chiller status is also reported in the digital output UNT_Unit Status |
|
|
y02- Restart mode after |
0=OFF means that after power on, the chiller gets up in OFF state |
power OFF |
1=ON means that after power on, the chiller gets up in ON state |
|
2=EQUA means that after power on, the chiller keeps the same state as before power off |
|
|
y03- System heat/cool |
It works only with H40> 0 and rE2=UI; |
|
This defines whether the machine should be in chiller mode or heat pump mode. |
|
This parameter can also be changed from the “Start” menu |
|
|
y04- Actuators delay from |
It is in seconds and sets the delay when powered ON (not when the unit status changes to ON) before |
power ON |
activating any outputs. Its purpose is to distribute the drawn current and protect the elements and |
|
particularly the compressor against repeated starts in the event of frequent power failures. When the |
|
timer has elapsed, the controller starts to manage the outputs based on the other times and the other |
|
normal functions. |
|
|
y05- Temperature |
0=C means that the user interface will show values in Celsius and bar |
measurement unit |
1=F means that the user interface will show values in Fahrenheit and PSI |
|
|
y06- Keyboard lock |
0=No |
|
1=Yes means that the user interface is locked |
|
Note: This parameter can be adjusted in order to be set remotely because it is not enabled for the menu |
|
|
y08- Scheduler enable |
0=No means that the scheduler is disabled |
|
1=Yes means that the scheduler is enabled |
|
Note: the “Enable scheduler” functionality is required |
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 13 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
y09- Show rolling test |
0=No |
|
1=Yes |
|
Provides information about what is going on in relation to the cutting in/out of the compressors |
Note: If the functionalities “Enable show compressor status” is enabled in the UI, a small icon is added for each compressor
How to configure the communication port.
Functionalities: Enable Modbus address different from CANBUS address
Cid – Serial address (CAN) |
Defines the ID in the CANBUS communication |
|
Note: the baud rate and the settings of the CANBUS communication is tuned through the bios menu |
|
or though the MYK |
|
|
SEr – Serial address (MODBUS) |
Defines the ID in the Modbus communication |
|
Note: the functionalities “Enable Modbus address different from CANBUS address” is required |
|
|
bAU – Serial baud rate (Mod- |
Defines the baud rate in the Modbus communication |
bus) |
0 means Reserved: do not use |
|
1 means 1200 bits/sec |
|
2 means 4200 bits/sec |
|
3 means 4800 bits/sec |
|
4 means 9600 bits/sec |
|
5 means 14400 bits/sec |
|
6 means 19200 bits/sec |
|
5 means 28800 bits/sec |
|
8 means 38400 bits/sec |
|
9 means 57600 bits/sec |
|
8 means 115200 bits/sec |
|
|
COM – Serial settings |
Defines the serial settings of the Modbus communication |
(Modbus) |
0 means 8N1 |
|
1 means 8E2 |
|
2 means 8N2 |
|
|
14 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
How to configure the internal coils.
Digital input: OPE, OPE1, OPE2
Digital output: PE1, PE2, …, PE8, H1, …, H4
Analogue input: TIN, TOM, TO1, …, TO4
Analogue output: E1, …, E4
Alarms: AE1, AO7, AP0, AP1, …, AP9
H1 – Number of evaporators |
Defines the number of internal coils; |
|
The supply temperature (TIN) is the same for all the coils. |
|
Each coil has a “leaving temperature” (T01-T04) ; there is also a common “leaving temperature” sensor |
|
for all the coils ( TOM) |
|
|
H2 – Number of circuits per |
Defines the number of circuits for each internal coil; |
evaporator |
Configuration accepted: |
|
• 1 circuit per internal coil -> 0<H1<5 |
|
• 2 circuits per internal coil ->0<H1<3 |
|
• 3 circuits per internal coil H1=1 |
|
• 4 circuits per internal coil H1=1 |
|
|
H3 – Air or water cooling |
Defines whether the evaporation process is managed by a pump (H3=H2O) or a fan (H3=Air): |
|
• WATER evaporators (H3=H2O). For each evaporator, the H1,...,H4 digital outputs which are |
|
necessary to manage the antifreeze heaters on the basis of the leaving water temperature TO1,...,TO4 |
|
are controlled. The number of heaters per evaporator is defined by H5. |
|
• AIR evaporators (H3=Air). Only the “TO1_Tout Evaporator 1” input is used to measure the supply air |
|
temperature even when more than one evaporator is present. The ice alarm AE1 is replaced with the |
|
Low air temperature warning A07 which is set to the same parameters as the ice alarm. |
|
|
H4 – Number of pump/fan per |
Defines the pumps (or fan) per evaporator: |
evaporator |
• WATER evaporators (H3=H2O): The PE1 and PE2 digital outputs are managed to control one pump |
|
or two twin pumps. |
|
• AIR evaporators (H3=Air): “PE1 and PE2” outputs are used to manage fans on the evaporator. |
|
Note: check "Fun for internal coil" |
|
|
H5 – Number of heaters per |
Defines the number of heaters for each internal coil; |
evaporator |
Configuration accepted: |
|
• 1 heater per internal coil -> 0<H1<5 |
|
• 2 heaters per internal coil ->0<H1<3 |
|
• 3 heaters per internal coil ->H1=1 |
|
• 4 heaters per internal coil ->H1=1 |
|
|
H12 –Fan in common for each |
0=NO means that each fan (AO ECx) works in relation to the evaporator pressure |
evaporator |
1=Yes means that only the fan EC1 will work in relation to worst pressure in the evaporators |
|
Note: the fan speed is managed with PI logic (check parameters ECS,….,Hi) |
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 15 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
How to configure the compressors number.
H6 – Number of compressor |
Defines the number of compressor per circuit; |
per circuit |
It’s not possible have circuits with different number of compressors |
|
Configuration accepted: |
|
• 1 compressor per circuit -> 0<H1*H2<5 |
|
• 2 compressors per circuit ->0<H1*H2<5 |
|
• 3 compressors per circuit ->0<H1*H2<3 |
|
• 4 compressors per circuit ->0<H1*H2<3 |
|
• >4 compressors per circuit ->0<H1*H2<2 |
|
|
H7 – Number of unloader per |
Defines the number of compressor partialisation; |
compressor |
The number of regulation steps is equal to H6*H2*H1*(H7+1) |
|
Activation and deactivation of the compressor’s unloader is defined by the parameters |
|
“C04-Unloaders activation mode” and “ C05-Unloaders deactivation mode” |
|
|
16 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
How to configure the external coil.
Digital input: OFC, FCL1, …, FCL4, OFC1, …, OFC12
Digital output: FC1, …, FC12
Analogue output: Fc1, …, Fc4
Alarm: AF1, …, AF12
H9 – Air or water cooler |
Defines whether the fans or the pump regulate condensing. |
condenser |
0=AIR : Controls defrosting in heating mode. |
|
1=H2O : The configuration managed is H10=1 and H11=Yes |
|
Note: the pump or fan behaviour is defined by parameters F01, F02 and F03 |
|
|
H10 – Number of pump/fans |
Defines the necessary digital output to control the pumps or fans on the condenser. |
per condenser |
• Water-cooled units (H9=H2O).The single “Cond Fan1/Pump1” digital output is controlled to drive |
|
a pump. |
|
• Air-cooled units (H9=AIR). Contributes to defining the total number of managed ventilation steps and |
|
thus of the corresponding ”Condenser Fan1”, ..., ”Condenser Fan8”digital outputs used to drive them. |
|
|
H11 –Fan in common to all |
On multi-circuits units, fans can be in common to all condensers. |
condenser |
If fans are not in common to all condensers (H11=0=NO), the following output are controlled: |
|
• as many analogue inputs as the condensers (H1*H2) |
|
• as many digital outputs as the condensers (H1*H2), multiplied by the number of fans per condenser |
|
(H10); digital outputs for fans are assigned to condensers in a sequential and balanced way, |
|
assuming that all condensers have the same number of fans; e.g. in a system made of 2 condensers |
|
and 6 fans, “Cond Fan1/Pump1”, “Condenser Fan2” and “Condenser Fan3” outputs are assigned to |
|
control fans belonging to the first condenser; “Condenser Fan4”, “Condenser Fan5” and “Condenser |
|
Fan6” to the second condenser. |
|
• as many analogue output s “InverterFanCond1”,...,”InverterFanCond4” for condensing control as for |
|
the condensers (H1*H2). |
|
If fans are common to all condensers (H11=1=YES) the following outputs are used: |
|
• as before, as many analogue inputs for condensing controls as there are circuits per condenser |
|
(H1*H2), but the one requiring the higher response from the control is used for regulation. Each |
|
analogue input is then used for defrost control in heating mode; |
|
• as many digital outputs as fans per condenser (H10); |
|
• one analogue output “InverterFanCond1” for fan speed regulation. |
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 17 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
How to configure the heat pump mode
Functionalities: Enable Heat Pump Control
Digital output: HC1, …, HC4, BO1, …, BO4
Analogue input: SP1, …, SP4, dP1, …, dP4
H40 –Heat pump type |
0=No means that the software does not perform heating mode |
|
1=GAS means that the software performs the heating mode, the internal coil is the evaporator in |
|
cooling mode and the condenser in heating mode |
|
1=H2O means that the software performs the heating mode, the coils keep the same meaning in |
|
both heating and cooling mode both |
|
Note: one digital output “Reverse Valve C1”, ..., “Reverse Valve C4” per each circuit is reserved for |
|
controlling the reverse flow valve |
|
|
H41- Boiler number of heaters |
Boiler heaters “Boiler1”, ..., “Boiler4” are turned ON when the temperature measured by the regulation |
|
probe enters in the area defined by the active regulation setpoint in heating (SH1) and differential rH1. |
|
They are an alternative to the heat pump, not in addition. |
|
Boiler heaters can be activated only if the temperature measured by the “BoilerSafety” probe is |
|
under a specific safety limit AbS. If it is over the limit, alarm A14 is generated. |
|
To reset the alarm there is a constant differential Abd to be considered. |
|
|
H42- Probe change in HP |
0=No means that the probe is before the 4-way valve (close to the compressor): |
|
• the sensor SPx – Suction pressure Cx measures low pressure |
|
• the sensor dPx – Discharge pressure Cx measures high pressure |
|
1=Yes means that the probe is after the 4-way valve (close to the coils): |
|
• the sensor SPx – Suction pressure Cx measures low pressure in cooling mode and high pressure in |
|
heating mode |
|
• the sensor dPx – Discharge pressure Cx measures high pressure in cooling mode and low pressure |
|
in heating mode |
|
Note: if ex2=yes the variable used from H42 (pink line below) is always about low pressure, in |
|
this case pay attention to set H42=No because in heating mode the discharge pressure will not |
|
be available |
|
|
18 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
How to manually set the compressor power request.
Functionalities: Enable commissioning for power request
Digital output: MPR
H43- Manual chiller power |
The power request provided to the compressors is about H43 % |
|
H43< zero means that the function is disabled |
|
Note: if H43 >=0 the digital output MPR is closed |
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 19 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
The Master and Slave is a functionality that allow a group of machines to be managed like one machine (Master) decides which and how many units (Slaves) should run.
The max number of units is 8 (7 slaves + 1 master), the network is CANBUS. The Master and Slave function optimizes:
-ageing of machines
-distribution of the load in order to improve the performance of the plant
-The backup units
Functionalities: Enable Master/Slave
Alarms: N01, N02, N03, N04, N05,N06, N07, N08
n01 –MCX network disable |
0=NO means that the Master slave function is enabled |
|
1=Yes means that the Master slave function is disabled |
|
|
n02 –Number of slave nodes |
It has to be set equal to (“number of chillers in the network” -1) |
|
|
n03- Auto master select |
0=NO means that the master in the master slave network can be only the chiller with the CANBUS ID |
|
equal to n15: if the master is not more available in the network, the other chillers will start to work in |
|
standalone mode |
|
1=Yes means that the master in the master slave network is the chiller with lowest CANBUS ID |
|
|
n04- Distribution algo |
0= PWR The master, using its own sensors, decides how many chillers are working and the chillers’ |
|
power supply; |
|
The maximum number of units that can work is related to the gap between setpoint and |
|
temperature: practically the regulation band is divided for the number of machines (n02+1-n09): |
|
1= CAP the master manages only the start order (following the ageing of the machines), chillers |
|
manage their power as standalone machines. |
|
If all the units which are running have capacity above n12 %, the master will switch on another chiller (the |
|
youngest one). |
|
If all the units which are running have capacity below n13 %, the master will switch off the oldest chiller |
|
running |
|
The minimum time between two actions of the master is n14 seconds |
|
|
n05- Power Smart power |
1=Yes means that the master is allowed to cut-in the first chiller available without considering the |
distribution enable |
start order related to the ageing of the machines |
|
|
n06- Node rotation enable |
0=No means that the start sequence of the machines is fixed; the order depends on the addressing, |
|
the first to start is the machine with the smallest CANBUS ID, the first to stop is the chiller with the |
|
highest CANBUS ID |
|
1=Yes means that the start/stop sequence of the machines depends on the ageing of the chillers, |
|
always starting with the youngest of the set and the oldest one is always the first to stop. In the case |
|
that one machine works n17 hours more than another chiller that is switched off, the master will |
|
exchange the unit in order to align the ageing. |
|
|
20 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
n07- Backup node offset |
When the gap between setpoint and temperature is above (n07+regulation band), the first backup |
|
|
unit is allowed to work as a support, also considering parameter n08 . |
|
|
Note: the offset to enable the other backup units is (n07*m+ regulation band): |
|
|
• m = 2 for the second backup unit |
|
|
• m = 3 for the third backup unit |
|
|
• |
… |
|
Note: the backup units will work running normally after the set point. It will be switched off when the |
|
|
gap between setpoint and temperature is below the regulation band |
|
|
Note: the pump behaviour is defined through the parameter P01 |
|
|
|
|
n08- Time to enable n07 |
It’s the time to stay far away from the setpoint in order to cut in the backup unit |
|
|
Note: check parameter n07 |
|
|
|
|
n09-Number of back-up unit |
n09 defines the number of backup units inside the master slave network |
|
|
A backup unit is never enabled (so does not provide cooling capacity) unless one of the following |
|
|
situations occurs: |
|
|
• one of the other units becomes unavailable |
|
|
• Support (see parameter n07 and n08) |
|
|
Note: The master chooses the backup unit (among all nodes present in the network) by looking at |
|
|
the working time of every unit: the one which has worked the longest will be the backup unit. |
|
|
|
|
n10 – Evaporator in common |
0=No each chiller consider its own evaporator flow alarm |
|
|
1=yes the master will read its “FPE” digital input (Flow Evaporator) and will send the information to |
|
|
other slaves |
|
|
|
|
n11 – Pump alarm in common |
0=No each chiller considers its own pump alarm |
|
|
1=yes the master will read its “AP1” digital input (Evap pump/fan overload alarm) and will send the |
|
|
information to other slaves |
|
|
|
|
n12 – Capacity upper |
See parameter n04 |
|
threshold |
|
|
|
|
|
n13 – Capacity lower |
See parameter n04 |
|
threshold |
|
|
|
|
|
n14 – Capacity step min time |
See parameter n04 |
|
|
|
|
n15 – Master node CAN ID |
It has to be set equal to the lowest ID in the CANBUS network |
|
|
|
|
n16 – Slaves node CAN ID offset |
The slaves have to take the CAN ID in relation to the n15 just adding n16. |
|
|
E.G. for n02 =3 |
|
|
• |
Master ID= n15 |
|
• |
Slave1 ID= n15+n16 |
|
• |
Slave2 ID= n15+n16+n16 |
|
• |
Slave3 ID= n15+n16+n16+n16 |
|
|
|
n17 – Maximum gap time for |
It is in hours |
|
unit rotation |
If a running unit becomes older than a switched-off unit by more than n17 hours, the logic will |
|
|
switch off the oldest unit running it will cause the other unit to be switched on. |
|
|
|
|
n18 – Backup unit pump |
0=OFF: the backup chillers in standby have the pump switched-off |
|
status |
1=ON: the backup chillers in standby have the pump switched-on |
|
|
Note:during support or backup, the pump of the chiller follow P01 setting |
|
|
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 21 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
rEG – Analogue input for |
0= Tin : reference sensor is Tin_Tin Evaporator |
temperature regulation |
1= ToM: reference sensor is TOM_Tout Evap Mix |
|
2 =AI1: reference sensor is the analogue input 1 |
|
…… |
|
17 =AI16 : reference sensor is the analogue input 16 |
|
18 =SPT1: reference is the temperature calculated from the sensor SP1_Suction Press C1, the gas |
|
type is set using parameter o31 |
|
|
rET – Regulation Type |
Defines the relation between the temperature gap and the power request to the circuits. |
|
0=P : Power request to the circuits increases in proportional way with the regulation error, i.e., it is |
|
100% when the regulation error (the gap between setpoint and the reference sensor ) is equal to rC1 |
|
( rH1) |
1=PI: the power request is the sum of P regulation (rET=0) plus a component (Integral part) that increases in relation to the regulation error; the speed of the integral part depends on the parameter rin_Ti.
For PI regulation, the balance is reached only when the regulation sensor gets the setpoint.
2=dZ : The delay between compressors activations varies between a maximum value dd5 and minimum value dd6 proportional to the temperature position inside the regulation band defined by the activation differential dd1.
Above setpoint + dead zone + activation differential, the delay among activations is equal to the minimum.
Similarly the action for the delay among compressors deactivations, which can vary between a maximum value dd7 and a minimum value dd8, is proportional to the temperature position inside the regulation band defined by the deactivation differential dd2.
Below a setpoint differential, the delay among activations is equal to the minimum value, dd8, up to a limit threshold, dd3. Below that, all the compressors are immediately switched OFF to avoid the unit ice alarm.
rT1- Minimum limit for |
The analogue output rtr linearly replays the regulation probe (check parameter rET) |
TReg TX |
It gets to 0% when the regulation probe reaches a value of rT1 |
|
Note: if the regulation probe is in error the AO_rtr gets to 100% |
|
|
rT2- Maximum limit for |
The analogue output rtr linearly replays the regulation probe (check parameter rET) |
TReg TX |
It gets to 100% when the regulation probe reachs rT2 value |
|
Note: if regulation probe is in error the the AO_rtr gets to 100% |
22 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
o30 – Gas type |
0=--- |
|
1=R12 |
|
2=R22 |
|
3=R134a |
|
4=R502 |
|
5=R717 |
|
6=R13 |
|
7=R131b1 |
|
8=R23 |
|
9=R500 |
|
10=R503 |
|
11=R114 |
|
12=R142b |
|
13=-- |
|
14=R32 |
|
15=R227 |
|
16=R401a |
|
17=R507 |
|
18=R402a |
|
19=R404a |
|
20= R407c |
|
21= R407a |
|
22= R407b |
|
23= R410a |
|
24= R170 |
|
25= R290 |
|
26=R600 |
|
27= R600a |
|
28= R744 |
|
29= R1270 |
|
30=R417a |
|
31=R422a |
|
32=R413A |
|
33=R422D |
|
34=R427A |
|
35=R438A |
|
36=R513A |
|
37=R407F |
|
38=R1234ze |
|
39=R1234yf |
|
40=R448A |
|
41=R449A |
|
42=R452A |
|
43=R450A |
|
44=R452B |
|
45=R454B |
|
46=R1233zdE |
|
47=R1234zeZ |
|
48=R449B |
|
49=R407H |
|
Note: the gas definition is used when the translation of the pressure in temperature is required; |
|
ReG=SPT1 and for the “internal” super heat control |
|
|
o31 – Dew/Bubble Conversion |
0=Dew |
mode |
1=Bubble used for the gas that require the "Glide" approximation |
|
|
Er1 – Emergency mode |
Er1 = -1 the function is disabled |
max power |
Er1 >= 0 when the digital input EEr is closed the power request is limited to Er1 instead of 100% |
|
Note: the functionality “Enable emergency mode from DI” is required |
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 23 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Analogue input: TRM
SC1 – Cooling temperature set |
Defines the setpoint in cooling mode |
point |
|
|
|
SCL – Minimum limit |
Defines the minimum limit of the setpoint in cooling mode |
|
Note: This limit is not respected when adjusted through Modbus |
|
|
SCH – Maximum limit |
Defines the maximum limit of the setpoint in cooling mode |
|
Note: This limit is not respected when adjusted through Modbus |
|
|
SH1 – heating temperature set |
Defines the setpoint in heating mode |
point |
|
|
|
SHL – Minimum limit |
Defines the minimum limit of the setpoint in heating mode |
|
Note: This limit is not respected when adjusted through Modbus |
|
|
SHH – Maximum limit |
Defines the maximum limit of the setpoint in heating mode |
|
Note: This limit is not respected when adjusted through Modbus |
|
|
SRE- Remote set enable |
The regulation setpoint is defined through the analogue input TRM_Remote Set |
|
0=NO means that the function is not enabled |
|
1=rEL means that |
|
set point = main setpoint + offset from analogue input (TRM_Remote set) |
2=Abs means that set point is linearly defined through AI_TREM, between SCL - SCH in cooling and SHL - SHH in heating
24 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
SdS- Setpoint selection |
0=DI means that the digital input SET2_Reg offset from DI defines if use comfort setpoint (SC1 or |
|
SH1) or the economic setpoint (SC1+SdC or SH1-SdH); in economic mode the proportional band in |
|
the PI control is increased by SdO |
|
1=PAR meaning that the parameter SdM_Setpoint mode defines whether comfort setpoint |
|
(SC1 or SH1) or the economic setpoint (SC1+SdC or SH1-SdH) is to be used; in economic mode the |
|
proportional band in the PI control is increased by SdO |
|
|
SdM- Setpoint mode |
It works only for SdS=PAR |
|
0=COMF meaning that chiller uses comfort setpoint ( SC1 or SH1) |
|
1=ECO meaning that the chiller uses economic setpoint (SC1+SdC or SH1-SdH) |
|
In economic mode the proportional band in the PI control is increased of SdO. |
|
|
SdC-Offset for setpoint in cool- |
In economic status and cooling mode the regulation setpoint is shifted to SdC. |
ing |
Note: see parameter SdS |
|
|
SdH-Offset for setpoint |
In economic status and heating mode the regulation setpoint is shifted to SdH. |
in heating |
Note: Take a look to parameter SdS |
|
|
SdO-Offset for differential |
In economic mode the proportional band of regulation becomes rC1+SdO or rH1+SdO. |
|
Note: look at parameter SdS |
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 25 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Analogue input: OUt
CC1-Compensation enable |
0=NO means compensation disable |
|
1=YES means compensation enable |
|
Note: this function adapts the setpoint to the outside temperature “Tout” |
|
|
CC2-Outside temperature to |
It’s in °C |
start cool comp. |
|
|
|
CC3-Outside temperature to |
It’s in °C |
stop cool comp. |
|
|
|
CC4-Maximum cooling |
It’s in °C |
compensation |
|
|
|
CH2-Outside temperature to |
It’s in °C |
start heat comp. |
Like CC2 but used in heating mode |
|
|
CH3-Outside temperature to |
It’s in °C |
stop heat comp. |
Like CC3 but used in heating mode |
|
|
CH4-Maximum heating |
It’s in °C |
compensation. |
Like CC4 but used in heating mode |
|
|
26 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
PI regulation
Note: the PI regulation is enabled when the parameter rET is equal to P or PI
rC1-Cooling temperature |
See parameter rET |
differential. |
|
|
|
rH1-Heating temperature |
See parameter rET |
differential. |
|
|
|
Rin- Ti |
It is the integral time of the PI regulation, the bigger the value of Rin the slower the action of the |
|
Integral part. |
|
See parameter rET |
|
|
rC2-Cut Off enable |
It enables the gradual reduction of the integral error once reached and exceeded the setpoint. The |
|
error integral in fact tends to keep the compressors turned on even if the proportional part of the |
|
error would require a shutdown. The amount of reduction is proportional to the distance from the |
|
setpoint considering the rC3 band. For example, in cooling, the reduction is zero when the control |
|
temperature is equal to the setpoint; the reduction is greatest when it is equal to setpoint-rC3. |
|
|
rC3- Cut off offset |
|
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 27 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Dead zone regulation
Functionalities: Enable Dead Zone Regulation
The dead zone regulation is enable when the parameter rET is equal to DZ It is a variable time regulation mainly used when the regulated value is the temperature of the fluid leaving the evaporator.
In the dead zone ddC no regulating action is taken.
Close to the dead zone the decision to cut the compressor in or out will take a maximum time of (dd5 or dd7), a time that will decrease linearly outside the dead zone. This variable time logic is described below.
ddC-Cooling dead zone |
In dead zone ddC no regulation action is taken. |
|
This is above the setpoint and used in cooling mode |
|
|
ddH-Heating dead zone |
In dead zone ddH no regulation action is taken. |
|
This is below the setpoint used in heating mode |
|
|
dd1-Comp activation |
Defines the maximum temperature gap to have a minimum delay (dd6) in the compressor’s activation |
differential |
Note: see picture in the parameter ddC and ddH |
|
|
dd2-Comp deactivation |
Defines the maximum temperature gap to have a minimum delay (dd6) in the compressor’s |
differential |
deactivation |
|
Note: see picture in the parameter ddC and ddH |
|
|
dd3-Min temp for OFF comp |
Defines the minimum temperature below which the compressors are switched off |
in cooling |
Note: see picture in the parameter ddC |
|
|
dd4-Max temp for OFF comp |
Defines the maximum temperature above which the compressors are switched off |
in heating |
Note: see picture in the parameter ddH |
|
|
dd5-Max delay of comp activa- |
Defines the maximum delay before a compressor cuts in |
tion |
Note: see picture in the parameter ddC and ddH |
|
|
dd6-Min delay of comp |
Defines the minimum delay before a compressor cuts in |
activation |
Note: see picture in the parameter ddC and ddH |
|
|
dd7-Max delay of comp |
Defines the maximum delay before a compressor cuts off |
deactivation |
Note: see picture in the parameter ddC and ddH |
|
|
dd8-Min delay of comp |
Defines the minimum delay before a compressor cuts off |
deactivation |
Note: see picture in the parameter ddC and ddH |
|
|
28 | BC295150867120en-000201 |
© Danfoss | DCS (vt) | 2019.08 |
User Guide | Chiller and reversable chiller, reciprocating, scroll and screw compressors
Digital output lock
It is possible to lock a digital output in open position in relation to an analogue input.
The lock condition is reported in the rolling text
Functionalities: Enable DO Locking from AI
DOn-Digital output number |
This is the number of the digital output to lock in open position; |
|
The conditions to lock it are defined by AIn, DOs and DOd |
|
|
AIn-Analogue input number |
This is the number of the analogue input to refer to lock the digital output DOn |
|
|
DOs-Set point for locking |
This is the setpoint to compare with the value of the analogue input AIn for locking the digital output |
|
DOn; |
|
Note: set parameter DOd to lock the digital output DOn above or below the setpoint DOs |
|
|
DOd-Differential to unlock |
|
|
|
Buzzer and relay
BUZ-Buzzer activation time |
It's in minutes. |
number |
Defines the maximum time that the buzzer can work; |
|
BUZ=15 means that there is no limit in the active time of buzzer |
|
|
Adl-Alarm relay activation |
It's in seconds. |
delay |
Defines the delay of the alarm relay when there is an alarm |
|
|
AOF-Alarm relay active if unit |
Defines whether the alarm relay works in the OFF state of the chiller |
in off |
|
|
|
© Danfoss | DCS (vt) | 2019.08 |
BC295150867120en-000201 | 29 |