Fact sheet
Termix BVX RO T/E
Indirect substation for single-family houses or apartments
Application
The Termix BVX RO T/E substation is
a complete solution for hot water and
space heating with optimal safety, efficient energy transfer, servicefriendly construction and a compact design. The substation is used if a heat
exchanger is required or on a conversion to district heating where the
existing equipment is unsuitable for
direct connection.
District heating (DH)
The substation is prefabricated with
a differential pressure controller, fitting
piece and sensor pockets for insertion
of a heat meter as well as strainers and
ball valves.
Heating (HE)
The heating circuit consists of a plate
heat exchanger, safety valves, manometer, thermometers, ball valves,
drain valve, air valves, expansion vessel and circulation pump. The temperature of the heating is controlled
by an electronic controller with an
outdoor temperature sensor.
Domestic hot water (DHW)
The domestic hot water circuit consists
of a hot water tank with coil and selfacting thermostatic control valve. The DHW
tank and coil are enamelled and the tank
contains a magnesium anode.
Options
The Termix BVX RO can be supplied
with a thermostatic circulation valve
or a built-in non-return valve and
safety valve mounted in the cold water supply. Both options delivered
loose with the unit.
Construction
All pipes are made of stainless steel. The
connections are made with nuts and
gaskets. The Termix BVX RO T/E is completed by a white steel cover in modern
design with door and including external
thermometers.
FEATURES AND BENEFITS
• Substation for apartment buildings
• Direct heating with mixing loop
• Thermostatic or electronic controls
• Capacity: 100-150 kW DHW, 100 kW HE
• DHW in sufficient quantity
• Operates independently
of differential pressure
and flow temperature
• Minimum space required
for installation
• Pipes and plate heat exchanger
made of stainless steel
• Minimized risk of lime scale
and bacteria formation
www.danfoss.com

CIRCUIT DIAGRAM EXAMPLE
DHW
DCW
DCW
DH
Supply
DH
Return
Technical parameters:
Nominal pressure: PN 10 (16)
Max. supply temperature: T
Brazing material (HEX): Copper
= 120 °C
max
Weight incl. cover: 120 – 150 k g
Cover: White-lacquered
steel sheet
Dimensions (mm):
With cover:
H 1580 × W 540 × D 640 (type BVX 1-x)
H 1890 × W 540 × D 640 (type BVX 2-x)
The connections are at the
top of the station
A Plate heat exchanger, HE
E DHW tank with coil
F Electronic controller
1 Ball valve
1A Ball valve, DVGW
4 Safet y valve
7 Thermostatic valve
9 Strainer
10 Circulation pump, HE
14 Sensor pocket, heat meter
16 Outdoor sensor
18 Thermometer
HE
Supply
HE
Return
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Heating (HE) supply
4. Heating (HE) return
5. Domestic cold water (DCW)
6. Domestic hot water (DHW)
7. DHW Circulation (Circ.)
Connections sizes:
DH + HE + DCW + DHW + Circ.: ¾“ G (int. thread)
Options:
• Thermostatic circulation set
• Ball valves set
• Thermometer
• Manometer
• Safety valve / non-return valve
• Pipe insulation
19 Surface sensor
20 Filling / drain valve
22 Test connection
24 Delivered loose with unit
26 Manometer
27 Actuator
29 2 - way motorized valve
38 Expansion tank
41 Fitting piece, heat meter
48 Air escape, manual
50 Differential pressure
controller w /o flow limiter
DHW: CAPACITY EXAMPLES, 10 °C / 50 °C
Substation
type
Tan k
volume
[l]
Coil
supply/return
temp.
[°C]
80/40 486 546 22,6
BVX 1-x 100
70/30 245 305 11,4
60/30 172 232 8,0
80/40 486 576 22,6
BVX 2-x 150
70/30 245 335 11,4
60/30 172 262 8,0
* Output first hour = constant output + 60% of tank volume
DHW
constant
capacity
[l/h]
DHW
capacity
first hour*
[l/h]
DHW
constant
capacity
[kW]
HEATING: CAPACITY EXAMPLES
Substa-
tion type
BVX x-1
BVX x-2
BVX x-3
BVX x-4
* Heat meter not included
70 / 40 – 35 / 60 °C 80 / 45 – 40 / 70 °C 90 / 45 – 40 / 70 °C
p
[kPa]*
Capacity Flow Capacity Flow Capacity Flow
30 15 518 17 476 23 673
35 16 555 18 510 25 724
30 19 671 21 619 30 865
35 21 718 23 662 32 929
30 22 773 25 715 34 990
35 24 828 27 765 37 1073
30 30 1018 33 941 45 1306
35 32 1089 35 1006 49 1404
Gemina Termix A/S · Member of the Danfoss Group · Navervej 15-17 · DK-7451 Sunds · Denmark
Tel.: +45 9714 1444 · Fax: +45 9714 1159 · mail@termix.dk · www.heating.danfoss.com
© Danfoss | DHS-SRMT/ PL | 2016 . 05
Temperature
VC.IQ.U2.02