Danfoss BFPW Installation guide

Installation Guide
Fuel unit BFPW
071R9857
Fig. 1 Fig. 2
071R9857
Fig. 3 Fig. 4
Technical Data Connections
See fig. 2
Oil types Used oil, No 4 & lighter fuels
Speed Max. 3450 rpm.
Pressure 80-210 psi
Factory setting 60 psi
Maximum pressure on suction port 30 psi
Transfer ow rating 3 GPH
Operating vacuum
Used oil and no. 4 fuel 20 in. HG
No. 2 and lighter fuel 10 in. HG
P1
R
Pressure adjustment See fig. 3
Air bleeding See fig. 4
The pump can be bleeded through the pressure gauge port in the front or through the return port R.
Pressure
Suction line
Return line
Nozzle connection left
regulation
1
/4 NPTF
1
/4 NPTF
1
/4 NPTF
Pressure gauge connection G and bleeding
Vacuum gauge connection
1
/8 NPTF
1
/8
© Danfoss | 2019.05
VI.DK.A1.12| 1
Danfos produc Al
Danfoss A/S
Heating Segment • heating
Installation Guide, Fuel unit BFPW
Installation
The fuel unit type BFPW should be installed in accordance with the National Board of Fire Underwriters requirements and local ordinances where applicable.
The pump does not have internal strainer. A filter in the supply line is always required.
Suction line length
Line size 1/2 inch ID 3/4 inch ID
Total length horizontal and vertical 35 feet 45 feet
Calculation basis 460 SSU (100 cSt) corresponding to no. 4 fuel at 40°F
s can accept no responsibility for possible errors in catalogues, brochures and o ther printed material. Danfoss reserves the right to alter its products w ithout notice. This also applies to ts already on order provided that such alterations can be m ade without subsequential changes being necessary in specications already agreed.