Capacity (EN 12900 Household/CECOMAF) 12V DC, static cooling watt
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50
2,000 95 126 142 201 273 308 359 458 571 583 632* 697*
2,500 119 157 176 247 335 375 442 570 723* 740 809*
3,000 142 189 211 297 402 450 529 682* 863*
3,500 167 220 245 343 464 518* 612* 790*
Capacity (ASHRAE LBP) 12V DC, static cooling watt
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50
2,000 22.6 30.0 33.6 47.7 64.9 72.6 85.2 109 135 138* 150* 165*
2,500 28.2 37.3 41.7 58.5 79.3 88.9 105 135 171* 175* 191*
3,000 33.7 44.8 50.1 70.4 95.2 107 125 161* 204*
3,500 39.8 52.2 58.2 81.3 110 123* 145* 187*
Power consumption 12V DC, static cooling watt
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50
2,000 27.4 32.5 34.6 41.7 49.0 52.6 56.8 65.4 75.1 76.9* 80.4* 86.2*
2,500 34.3 41.4 44.3 54.0 63.4 67.7 73.0 82.8 93.1* 94.9* 98.6*
3,000 41.4 50.1 53.7 65.2 76.2 81.3 87.4 98.9* 111*
3,500 49.6 58.8 62.6 75.5 88.7 95.0* 103* 119*
Current consumption
(for 24V applications the following must be halfed) A
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50
2,000 2.28 2.69 2.87 3.50 4.18 4.49 4.90 5.65 6.45 6.58* 6.87* 7.29*
2,500 2.86 3.41 3.65 4.45 5.26 5.61 6.10 6.94 7.81* 7.94* 8.25*
3,000 3.52 4.16 4.43 5.37 6.33 6.75 7.31 8.32 9.34*
3,500 4.20 4.88 5.18 6.24 7.39 7.90* 8.61* 9.91*
COP (ASHRAE LBP) 12V DC, static cooling W/W
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50
2,000 3.49 3.89 4.09 4.81 5.57 5.83 6.32 7.00 7.60 7.63* 7.86* 8.09*
2,500 3.47 3.81 3.97 4.58 5.28 5.52 6.05 6.89 7.76* 7.77* 8.21*
3,000 3.43 3.77 3.93 4.55 5.27 5.52 6.05 6.89 7.76*
3,500 3.37 3.74 3.91 4.54 5.23 5.46* 5.94* 6.66*
COP (EN 12900 Household/CECOMAF) 12V DC, static cooling W/W
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50
2,000 0.82 0.92 0.96 1.13 1.31 1.38 1.48 1.64 1.78 1.79* 1.84* 1.90*
2,500 0.82 0.90 0.94 1.08 1.24 1.31 1.42 1.62 1.82 1.89* 1.93*
3,000 0.81 0.89 0.93 1.07 1.24 1.31 1.42 1.62 1.82*
3,500 0.80 0.88 0.92 1.07 1.23 1.30* 1.40* 1.56*
power consumption is limited to 100W with 101N0500 * fan cooling of electronic unit compulsory
Test conditions EN 12900/CECOMAF ASHRAE LBP
Condensing temperature 131°F 130°F
Ambient temperature 90°F 90°F
Suction gas temperature 90°F 90°F
Liquid temperature no subcooling 90°F
Accessories for BD50F Code number
Bolt joint for one comp. Ø: 5/ 8 in. 118-1917
Bolt joint in quantities Ø: 5 /8 in . 118-1918
Snap-on in quantities Ø: 5/ 8 in. 118-1919
Remote kit (without cable) 105N9210
AC line cord UL approved 105N9520
AC line cord VDE approved 105N9530
DC usage:
Automoblie fuse
DIN 7258
12V: 15A
Not
deliverable
from Secop
24V: 7.5 A
Main switch
min. 20A
AC usage:
Fuse, 100-240V min. 4A
Main switch
min. 6A
Operational errors shown by LED (optional)
Error
code
Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly
loaded, or if the ambient tem pe ra ture is high, the
electronic unit will run too hot).
4
Minimum motor speed error
(If the refrigeration system is too heavily loaded,
the motor cannot maintain minimum speed at
approximately 1,850 rpm).
3
Motor start error
(The rotor is blocked or the differential pres-sure in
the refrigeration system is too high (>5 bar)).
2
Fan over-current cut-out
(The fan loads the electronic unit with more than
1A
peak
).
1
Battery protection cut-out
(The voltage is outside the cut-out setting).
Compressor speed
Electronit unit Resistor
(R1) [Ω]
Motor
speed
Control
circuit
Code number
calculated
values [rpm]
current
[mA]
101N0210
101N0220
101N0230
101N0500
0 2,000 5
277 2,500 4
692 3,000 3
1523 3,500 2
101N0320
101N0400
with AEO
0 AEO 6
173 2,000 5
450 2,500 4
865 3,000 3
1696 3,500 2
In AEO (Adaptive Energy Optimizing) speed mode the BD comressor will always adapt its speed to the actual cooling demand.
Wire Dimensions DC
Size Max. length* Max. length*
Cross AWG 12V operation 24V operation
section
[mm
2
] [Gauge] [m] [ft.] [m] [ft.]
2.5 12 2.5 8 5 16
4 12 4 13 8 26
6 10 6 20 12 39
10 8 10 33 20 66
*Length between battery an electronic unit
Wire Dimensions AC
Cross section min. 0.75 mm
2
or AWG 18