BD50F Direct Current Compressor R134a, 12-24V DC & 100-240V AC 50/60Hz
S = Static cooling normally suffi cient O = Oil cooling F
= Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F
= Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally suffi cent – = not applicable in this area
General
Code number (without electronic units) 101Z0203
Electronic unit - standard 101N0210, 30 pcs: 101N0211
Electronic unit 12-24V DC - with metal shielding 101N0220, 30 pcs: 101N0221
Electronic unit 12-24V DC - high start performance 101N0230, 30 pcs: 101N0231
Electronic unit 12-24V DC - AEO & metal shielding 101N0320, 30 pcs: 101N0321
Electronic unit 12-24V DC & 100-240V AC 50/60Hz 101N0500, 36 pcs: 101N0501
Approved compressor - electronic unit combinations refer to Instructions for 101N0xxx
Additional approvals e4, C-Tick
Compressors on pallet 150
Application
Application LBP/MBP/HBP
Evaporating temperature °F -20 to 50
Voltage range (DC& AC)
12-24V DC & 100-240V AC 50/60Hz
Max. condensing temperature continuous (short)
°F 140 (158)
Max. winding temperature continuous (short) °F 257 (275)
Cooling requirements
Application LBP MBP HBP
32°C S S F
38°C S S F
43°C S S F
Remarks on application: Fan cooling F
1
depending on application and speed.
Motor
Motor type Variable speed
Resistance, all 3 windings (25°C) 1.8
Design
Displacement cu.in. 0.15
Oil quantity (type) fl .oz. 5.1 (polyolester)
Maximum refrigerant charge oz. 10.5
Free gas volume in compressor fl .oz. 29.6
Weight - Compressor/Electronic unit lbs. 9.5/0.55
Standard battery protection settings
(refer to 101N0xxx Instructions for optional settings)
Voltage 12V 24V
Cut out VDC 10.4 22.8
Cut in VDC 11.7 24.2
Dimensions
Height inch A 5.39
B 5.32
B1 5.04
B2 2.87
Suction connector location/I.D. mm | angle C 0.252-0259 | 41.5°
material | comment Cu-plated steel | Al cap
Process connector location/I.D. mm | angle D 0.252-0259 | 45°
material | comment Cu-plated steel | Al cap
Discharge connector location/I.D. mm | angle E 0.202-0.205 | 21°
material | comment Cu-plated steel | Al cap
Remarks: inch connectors
2/2 Manufactured by Secop for DANFOSS - DEHC.ED.100.M6.22 / 520N0953 June 2011
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Capacity (EN 12900 Household/CECOMAF) 12V DC, static cooling watt
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50 2,000 95 126 142 201 273 308 359 458 571 583 632* 697* 2,500 119 157 176 247 335 375 442 570 723* 740 809* 3,000 142 189 211 297 402 450 529 682* 863* 3,500 167 220 245 343 464 518* 612* 790*
Capacity (ASHRAE LBP) 12V DC, static cooling watt
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50 2,000 22.6 30.0 33.6 47.7 64.9 72.6 85.2 109 135 138* 150* 165* 2,500 28.2 37.3 41.7 58.5 79.3 88.9 105 135 171* 175* 191* 3,000 33.7 44.8 50.1 70.4 95.2 107 125 161* 204* 3,500 39.8 52.2 58.2 81.3 110 123* 145* 187*
Power consumption 12V DC, static cooling watt
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50 2,000 27.4 32.5 34.6 41.7 49.0 52.6 56.8 65.4 75.1 76.9* 80.4* 86.2* 2,500 34.3 41.4 44.3 54.0 63.4 67.7 73.0 82.8 93.1* 94.9* 98.6* 3,000 41.4 50.1 53.7 65.2 76.2 81.3 87.4 98.9* 111* 3,500 49.6 58.8 62.6 75.5 88.7 95.0* 103* 119*
Current consumption
(for 24V applications the following must be halfed) A
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50 2,000 2.28 2.69 2.87 3.50 4.18 4.49 4.90 5.65 6.45 6.58* 6.87* 7.29* 2,500 2.86 3.41 3.65 4.45 5.26 5.61 6.10 6.94 7.81* 7.94* 8.25* 3,000 3.52 4.16 4.43 5.37 6.33 6.75 7.31 8.32 9.34* 3,500 4.20 4.88 5.18 6.24 7.39 7.90* 8.61* 9.91*
COP (ASHRAE LBP) 12V DC, static cooling W/W
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50 2,000 3.49 3.89 4.09 4.81 5.57 5.83 6.32 7.00 7.60 7.63* 7.86* 8.09* 2,500 3.47 3.81 3.97 4.58 5.28 5.52 6.05 6.89 7.76* 7.77* 8.21* 3,000 3.43 3.77 3.93 4.55 5.27 5.52 6.05 6.89 7.76* 3,500 3.37 3.74 3.91 4.54 5.23 5.46* 5.94* 6.66*
COP (EN 12900 Household/CECOMAF) 12V DC, static cooling W/W
rpm \ °F -20 -13 -10 0 10 14 20 30 40 41 45 50 2,000 0.82 0.92 0.96 1.13 1.31 1.38 1.48 1.64 1.78 1.79* 1.84* 1.90* 2,500 0.82 0.90 0.94 1.08 1.24 1.31 1.42 1.62 1.82 1.89* 1.93* 3,000 0.81 0.89 0.93 1.07 1.24 1.31 1.42 1.62 1.82* 3,500 0.80 0.88 0.92 1.07 1.23 1.30* 1.40* 1.56*
power consumption is limited to 100W with 101N0500 * fan cooling of electronic unit compulsory
Test conditions EN 12900/CECOMAF ASHRAE LBP
Condensing temperature 131°F 130°F Ambient temperature 90°F 90°F Suction gas temperature 90°F 90°F Liquid temperature no subcooling 90°F
Accessories for BD50F Code number
Bolt joint for one comp. Ø: 5/ 8 in. 118-1917 Bolt joint in quantities Ø: 5 /8 in . 118-1918 Snap-on in quantities Ø: 5/ 8 in. 118-1919 Remote kit (without cable) 105N9210
AC line cord UL approved 105N9520 AC line cord VDE approved 105N9530
DC usage:
Automoblie fuse DIN 7258
12V: 15A
Not
deliverable
from Secop
24V: 7.5 A
Main switch
min. 20A
AC usage:
Fuse, 100-240V min. 4A Main switch
min. 6A
Operational errors shown by LED (optional)
Error code
Error type
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 1,850 rpm).
Motor start error
(The rotor is blocked or the differential pres-sure in the refrigeration system is too high (>5 bar)).
Fan over-current cut-out
(The fan loads the electronic unit with more than 1A
peak
).
Battery protection cut-out
(The voltage is outside the cut-out setting).
Compressor speed
Electronit unit Resistor
(R1) [Ω]
Motor speed
Control
circuit
Code number
calculated
values [rpm]
current
[mA]
101N0210 101N0220 101N0230 101N0500
0 2,000 5
277 2,500 4
692 3,000 3
1523 3,500 2
101N0320 101N0400 with AEO
0 AEO 6
173 2,000 5
450 2,500 4
865 3,000 3
1696 3,500 2
In AEO (Adaptive Energy Optimizing) speed mode the BD com­ressor will always adapt its speed to the actual cooling demand.
Wire Dimensions DC
Size Max. length* Max. length*
Cross AWG 12V operation 24V operation
section
[mm
2
] [Gauge] [m] [ft.] [m] [ft.]
2.5 12 2.5 8 5 16 4 12 4 13 8 26 6 10 6 20 12 39
10 8 10 33 20 66
*Length between battery an electronic unit
Wire Dimensions AC
Cross section min. 0.75 mm
2
or AWG 18