BD250GH.2 Direct current Compressor
R134a, 48V DC
General
Code number (without electronic units) |
|
|
101Z0405 |
|
||
Electronic unit - Telecom |
|
|
101N0732, 36 pcs: 101N0733 |
|||
Approvals |
|
|
|
|
UL |
|
Compressors on pallet |
|
|
|
150 |
|
|
Application |
|
|
|
|
|
|
Application |
|
|
|
LBP/MBP/HBP |
||
Evaporating temperature |
|
°C |
|
-25 to 15 |
|
|
Voltage range |
|
|
VDC |
|
32 - 60 |
|
Max. condensing temperature continuous (short) °C |
|
60 (70) |
|
|||
Max. winding temperature continuous (short) |
°C |
|
125 (135) |
|
||
Cooling requirements |
|
|
|
|
|
|
Application |
|
|
|
LBP |
MBP |
HBP |
32°C |
|
|
|
S |
S |
S |
38°C |
|
|
|
S |
S |
S |
43°C |
|
|
|
S |
S |
F1 |
Remarks on application: |
|
|
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
|
|
|
|
|
Motor type |
|
|
|
variable speed |
||
Resistance, all 3 windings (25°C) |
Ω |
|
1.03 |
|
||
Design |
|
|
|
|
|
|
Displacement |
|
|
cm3 |
|
2.50 |
|
Oil quantity (type) |
|
cm3 |
150 (polyolester) |
|||
Maximum refrigerant charge |
|
g |
|
300 |
|
|
Free gas volume in compressor |
cm3 |
|
870 |
|
||
Weight - Compressor/Electronic unit |
kg |
|
4.4/0.24 |
|
||
Battery protection settings |
|
|
|
|
|
|
Voltage |
|
|
|
Min. value |
Default |
Max. value |
Cut out |
(0.1 steps) |
|
VDC |
32 |
36 |
60 |
Cut in diff. |
(0.1 steps) |
|
VDC |
0.5 |
4.0 |
10.0 |
Dimensions |
|
|
|
|
|
|
Height |
|
|
mm |
A |
137 |
|
|
|
|
|
B |
135 |
|
|
|
|
|
B1 |
128 |
|
|
|
|
|
B2 |
73 |
|
Suction connector |
location/I.D. mm | angle |
C |
6.2 | 40° |
|
||
|
|
material | comment |
Cu-plated steel | Al cap |
|||
Process connector |
location/I.D. mm | angle |
D |
6.2 | 45° |
|
||
|
|
material | comment |
Cu-plated steel | Al cap |
|||
Discharge connector |
location/I.D. mm | angle |
E |
5.0 | 21° |
|
||
|
|
material | comment |
Cu-plated steel | Al cap |
|||
Connector tolerance |
|
I.D. mm |
±0.09, on 5.0 +0.12/+0.20 |
|||
Remarks: |
Clearance between electronic unit and baseplate |
|
|
|||
|
does not allow the snap-on option for mounting. |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S |
= Static cooling normally sufficient |
|
|||||||||||||||||||||||||||
O |
= Oil cooling |
|
|||||||||||||||||||||||||||
F1 |
= Fan cooling 1.5 m/s |
|
|||||||||||||||||||||||||||
|
|
|
|
(compressor compartment temperature |
|
||||||||||||||||||||||||
|
|
|
|
equal to ambient temperature) |
|
||||||||||||||||||||||||
F2 |
= Fan cooling 3.0 m/s necessary |
|
|||||||||||||||||||||||||||
SG |
= Suction gas cooling normally sufficent |
|
–= not applicable in this area
© Danfoss | DCS (CC) | 2017.06 |
DEHC.ED.200.F8.02 | 1 |
Capacity |
(EN |
12900 |
Household/CECOMAF) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
watt |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
|
|
53V DC, fan cooling F1 |
|
Operational errors |
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||
rpm \ °C |
-25 |
-23.3 |
|
-20 |
-15 |
-10 |
|
|
-6.7 |
|
-5 |
0 |
|
|
5 |
|
|
|
|
7.2 |
|
|
10 |
|
15 |
|
|
|
Error |
|
|
|
|
|
|
|
|
|
|
Error type |
|
|||||||||||||||||||||
2,500 |
31.4 |
36.6 |
|
47.2 |
65.5 |
87.0 |
|
103 |
|
112 |
143 |
178 |
|
195 |
|
219 |
|
267 |
|
|
|
code |
|
Can be read out in the software TOOL4COOL® |
||||||||||||||||||||||||||||||||||||||
3,100 |
42.9 |
49.1 |
|
62.1 |
84.8 |
112 |
|
132 |
|
144 |
181 |
224 |
|
246 |
|
275 |
|
333 |
|
|
|
6 |
|
Thermostat failure |
|
|
||||||||||||||||||||||||||||||||||||
3,800 |
55.0 |
62.4 |
|
78.3 |
106 |
139 |
|
165 |
|
179 |
224 |
277 |
|
303 |
|
337 |
|
408 |
|
|
|
|
|
|
|
(If the NTC thermistor is short-circuit or has no connection, |
||||||||||||||||||||||||||||||||||||
4,400 |
64.3 |
72.8 |
|
91.1 |
124 |
162 |
|
191 |
|
208 |
261 |
322 |
|
352 |
|
392 |
|
472 |
|
|
|
|
|
|
|
the electronic unit will enter manual mode). |
||||||||||||||||||||||||||||||||||||
Capacity |
(ASHRAE LBP) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
53V DC, fan cooling F1 |
|
watt |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 |
|
Thermal cut-out of electronic unit |
||||||||||||||||||||||||||||||||||||||||||||
rpm \ °C |
-25 |
-23.3 |
|
-20 |
-15 |
-10 |
|
|
-6.7 |
|
-5 |
0 |
|
|
5 |
|
|
|
|
7.2 |
|
|
10 |
|
15 |
|
|
|
|
|
|
|
(If the refrigeration system has been too heavily loaded, |
|||||||||||||||||||||||||||||
2,500 |
40.1 |
46.3 |
|
59.3 |
81.8 |
108 |
|
129 |
|
140 |
177 |
222 |
|
243 |
|
273 |
|
334 |
|
|
|
|
|
|
|
or if the ambient temperature is high, the electronic unit |
||||||||||||||||||||||||||||||||||||
3,100 |
54.0 |
61.6 |
|
77.6 |
106 |
139 |
|
164 |
|
178 |
225 |
279 |
|
306 |
|
342 |
|
416 |
|
|
|
|
|
|
|
will run too hot). |
|
|
|
|
||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
|
Minimum motor speed error |
|
|||||||||||
3,800 |
68.7 |
77.9 |
|
97.4 |
132 |
173 |
|
204 |
|
222 |
279 |
345 |
|
377 |
|
421 |
|
509 |
|
|
|
|
||||||||||||||||||||||||||||||||||||||||
4,400 |
80.0 |
90.5 |
|
113 |
153 |
201 |
|
237 |
|
257 |
323 |
400 |
|
437 |
|
488 |
|
589 |
|
|
|
|
|
|
|
(If the refrigeration system is too heavily loaded, the |
||||||||||||||||||||||||||||||||||||
Power |
consumption |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
53V DC, fan cooling F1 |
|
watt |
|
|
|
|
motor cannot maintain minimum speed at approximately |
|||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1,850 rpm). |
|
|
|
|
|||||||||||||||||||||||||||||||||||||
rpm \ °C |
-25 |
-23.3 |
|
-20 |
-15 |
-10 |
|
|
-6.7 |
|
-5 |
0 |
|
|
5 |
|
|
|
|
7.2 |
|
|
10 |
|
15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
|
3 |
|
Motor start error |
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||
2,500 |
40.8 |
44.1 |
|
50.1 |
58.5 |
66.0 |
|
70.4 |
72.5 |
78.5 |
83.9 |
|
86.1 |
|
88.7 |
|
93.1 |
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
(The rotor is blocked or the differential pressure in the |
|||||||||||||||||||||||||||||||||||||||||||||||||||
3,100 |
46.5 |
50.1 |
|
57.0 |
66.9 |
76.5 |
|
82.6 |
85.7 |
94.7 |
103 |
|
107 |
|
112 |
|
121 |
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
refrigeration system is too high). |
|
|||||||||||||||||||||||||||||||||||||||||||||||||
3,800 |
58.2 |
62.2 |
|
70.0 |
81.7 |
93.7 |
|
102 |
|
106 |
119 |
132 |
|
137 |
|
145 |
|
159 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||
|
|
|
|
|
2 |
|
Fan over-current cut-out |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||
4,400 |
72.4 |
76.7 |
|
85.3 |
98.8 |
113 |
|
122 |
|
128 |
143 |
160 |
|
167 |
|
177 |
|
196 |
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
Current |
consumption |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
53V DC, fan cooling F1 |
|
|
A |
|
|
|
|
(The fan loads |
the |
electronic unit with more than |
||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.8Apeak). |
|
|
|
|
||||||||||||||||||||||||||||||||||||
rpm \ °C |
-25 |
-23.3 |
|
-20 |
-15 |
-10 |
|
|
-6.7 |
|
-5 |
0 |
|
|
5 |
|
|
|
|
7.2 |
|
|
10 |
|
15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
|
1 |
|
Battery protection cut-out |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||
2,500 |
0.78 |
0.86 |
|
1.01 |
1.23 |
1.43 |
|
1.55 |
1.60 |
1.75 |
1.87 |
|
1.91 |
|
1.95 |
|
1.98 |
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
3,100 |
0.65 |
0.74 |
|
0.90 |
1.14 |
1.38 |
|
1.52 |
1.59 |
1.79 |
1.97 |
|
2.04 |
|
2.12 |
|
2.23 |
|
|
|
|
|
|
(The voltage is outside the cut-out setting). |
||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3,800 |
0.87 |
0.96 |
|
1.13 |
1.40 |
1.67 |
|
1.85 |
1.94 |
2.20 |
2.45 |
|
2.55 |
|
2.68 |
|
2.89 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
4,400 |
1.36 |
1.45 |
|
1.64 |
1.93 |
2.24 |
|
2.44 |
2.55 |
2.86 |
3.17 |
|
3.30 |
|
3.47 |
|
3.76 |
|
|
Accessories for BD250GH.2 |
|
|||||||||||||||||||||||||||||||||||||||||
COP (EN 12900 Household/CECOMAF) |
|
|
|
|
|
53V DC, fan cooling F1 |
|
W/W |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Mounting |
|
|
|
|
|
|
|
|
|
|
Code number |
||||
rpm \ °C |
-25 |
-23.3 |
|
-20 |
-15 |
-10 |
|
|
-6.7 |
|
-5 |
0 |
|
|
5 |
|
|
|
|
7.2 |
|
|
10 |
|
15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||
|
|
|
|
|
Bolt joint for one compressor |
Ø: 16 mm |
118-1917 |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
2,500 |
0.77 |
0.83 |
|
0.94 |
1.12 |
1.32 |
|
1.47 |
1.55 |
1.82 |
2.12 |
|
2.27 |
|
2.47 |
|
2.87 |
|
|
|||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
Bolt joint in quantities |
|
|
Ø: 16 mm |
118-1918 |
|||||||||||||||||||||||||||||||||||||||||||||||||||||
3,100 |
0.92 |
0.98 |
|
1.09 |
1.27 |
1.46 |
|
1.60 |
1.67 |
1.91 |
2.17 |
|
2.29 |
|
2.45 |
|
2.74 |
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||
3,800 |
0.94 |
1.00 |
|
1.12 |
1.30 |
1.49 |
|
1.62 |
1.68 |
1.89 |
2.11 |
|
2.21 |
|
2.33 |
|
2.57 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
|
|
|
|
|
Electrical |
|
|
|
|
|
|
|
|
|
Code number |
|||||||||||||||||||||||||||||||||||||||||||||||
4,400 |
0.89 |
0.95 |
|
1.07 |
1.25 |
1.44 |
|
1.56 |
1.63 |
1.82 |
2.01 |
|
2.10 |
|
2.21 |
|
2.41 |
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
(cables, sensors, etc.) |
|
Single pack |
I - Pack |
||||||||||||||||||||||||||||||||||||||||||||||||||||
COP (ASHRAE LBP) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
53V DC, fan cooling F1 |
|
W/W |
|
||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DC line cord, 900 mm |
|
|
105N9542 |
105N9543, 36 pcs. |
|||||||||||||||||||||||||||||||||||||||||
rpm \ °C |
-25 |
-23.3 |
|
-20 |
-15 |
-10 |
|
|
-6.7 |
|
-5 |
0 |
|
|
5 |
|
|
|
|
7.2 |
|
|
10 |
|
15 |
|
|
|
DC line cord, 2000 mm |
|
|
105N9540 |
105N9541, 36 pcs. |
|||||||||||||||||||||||||||||
2,500 |
0.98 |
1.05 |
|
1.19 |
1.41 |
1.66 |
|
1.84 |
1.95 |
2.28 |
2.67 |
|
2.86 |
|
3.12 |
|
3.63 |
|
|
DC line cord, 5000 mm |
|
|
105N9538 |
105N9539, 36 pcs. |
||||||||||||||||||||||||||||||||||||||
3,100 |
1.16 |
1.23 |
|
1.37 |
1.59 |
1.83 |
|
2.00 |
2.09 |
2.39 |
2.72 |
|
2.87 |
|
3.07 |
|
3.45 |
|
|
Temperature sensor 470 mm |
|
105N9612 |
105N9613, 200 pcs. |
|||||||||||||||||||||||||||||||||||||||
3,800 |
1.18 |
1.25 |
|
1.40 |
1.62 |
1.85 |
|
2.01 |
2.10 |
2.36 |
2.64 |
|
2.76 |
|
2.92 |
|
3.22 |
|
|
Temperature sensor 1000 mm |
|
105N9614 |
105N9615, 100 pcs. |
|||||||||||||||||||||||||||||||||||||||
4,400 |
1.10 |
1.18 |
|
1.33 |
1.55 |
1.79 |
|
1.94 |
2.02 |
2.27 |
2.51 |
|
2.62 |
|
2.76 |
|
3.02 |
|
|
Temperature sensor 1500 mm |
|
105N9616 |
105N9617, 100 pcs. |
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
One Wire/LIN gateway |
|
|
105N9501 |
– |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Comm. cable, 1500 mm |
|
|
– |
105N9545, 100 pcs. |
||||||||||
Test conditions |
|
|
EN 12900/CECOMAF |
|
|
|
|
|
|
ASHRAE LBP |
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Comm. cable, 3000 mm |
|
|
– |
105N9547, 50 pcs. |
||||||||||||||||||||||||||||||||||||||||||||
Condensing temperature |
|
|
|
|
|
|
|
|
55°C |
|
|
|
|
|
|
|
|
|
|
|
|
54.4°C |
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
Ambient temperature |
|
|
|
|
|
|
|
|
|
32°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
32°C |
|
|
|
|
|
|
Not deliverable from Secop |
|
|
|
|
|||||||||||||||||||||||||||
Suction gas temperature |
|
|
|
|
|
|
|
|
32°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
32°C |
|
|
|
|
|
|
Slow-blow fuse |
|
|
|
16A |
||||||||||||||||||||||||||||
Liquid temperature |
|
|
|
|
|
no subcooling |
|
|
|
|
|
|
|
|
|
|
|
|
|
32°C |
|
|
|
|
|
|
Main switch |
|
|
|
rated to min. 25A |
|||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed.