Flow and temperature controller with integrated control valve,
WE-version (PN 25)
AVQM-WE - f low controller with integrated control valve
AVQMT-WE - f low and temperature controller with integrated control valve
Description
AVQM-WE
DN 15-25
AVQM-WE is a self-acting flow controller with
integrated control valve primarily for use in
district heating systems. The controller closes
when set max. flow is exceeded.
AVQMT-WE is a self-acting flow and temperature
controller with integrated control valve primarily
for use in district heating systems. The controller
closes on rising temperature or when set max.
flow is exceeded.
All controllers have special designed (pressure
relieved) control valve insert.
AVQM-WE controller can be combined with
Danfoss electrical actuators AMV(E) (and
controlled by ECL electronic controllers).
AVQMT-WE controller can be combined with
Danfoss electrical actuators AMV(E) (and
controlled by ECL electronic controllers) and with
AVT or STM thermostatic actuators.
The controllers have a control valve with
adjustable flow restrictor, connection neck
for electrical actuator, connection neck for
thermostat (AVQMT-WE only), and an actuator
with one control diaphragm.
AVQM-WE and AVQMT-WE are used together
with Danfoss electrical actuators:
- AMV 150
- AMV(E) 10 1) / AMV(E) 20 / AMV(E) 30
- AMV(E) 13 1) / AMV(E) 23 / AMV(E) 33 with
spring return function
AMV 150 / AMV(E) 10 / AMV(E) 13 can be combined with D N 15
controller only.
1)
AVQM-WE
DN 32-50
AVQMT-WE
DN 15-25
AVQM(T)-WE combined with AMV(E) 13,
AMV(E) 23 (SL) or AMV(E) 33 (SL) has been
approved according to DIN 32730.
The controllers combined with AVT and STM
thermostats are type-tested acc. to EN 14597.
Controllers combined with STM thermostats
protect systems against exceeding temperatures.
Applications:
- District heating systems acc. to DIN 4747
- Heating systems acc. to EN 12828 (DIN 4751)
and EN 12953-6 (DIN 4752)
- Water heating systems for drinking and
industrial waters acc. to DIN 4753
Main data:
• DN 15-50
• kVS 2.5-25 m3/h
• PN 25
• Setting ranges:
- AVT thermostat:
−10 … 4 0 °C / 20 … 70 °C / 40 … 90 °C / 60 … 110 °C
Example 1 AVQM-WE controller:
Flow controller with integrated
control valve; DN 15; kVS 2.5;
PN 25;
flow restrictor Δp 0.2 bar;
T
150 °C
; ext. thread
max
- 1× AVQM-WE DN 15 controller
Code No: 003H7080
Option:
- 1× Weld-on tailpieces
Code No: 003H6908
The controller will be delivered
completely assembled, inclusive
impulse tube bet ween valve and
actuator. Electrical actuator AMV(E)
must be ordered separately.
Example 2 AVT (or STM) / AVQMT-WE
controller:
Flow and temperature controller
with integrated control valve,
DN 15; kVS 2.5; PN 25; setting range
40 … 90 °C; flow restrictor Δp 0.2 bar;
T
The controller AVQMT-WE will be
delivered completely assembled,
inclusive impulse tube between
valve and actuator. Thermostatic
actuator AVT will be delivered
separately. Electrical actuator
AMV(E) must be ordered separately.
In case of safety temp. monitoring
STM should be ordered instead of
AV T.
Example 3 STM / AVT / AVQMT-WE controller:
Flow and temperature controller
with safety temperature monitor
and integrated control valve,
DN 15, kVS 2.5; PN 25; setting range
40 … 90 °C; limit range 30 … 110 °C;
flow restrictor Δp 0.2 bar;
T
The controller AVQMT-WE will be
delivered completely assembled,
inclusive impulse tube between
valve and actuator. Combination
piece K2, thermostats AVT and STM
will be delivered separately.
Electrical actuator AMV(E) must be
ordered separately.
Accessories for thermostats
PictureType designationPN
Immersion pocket25
Combination piece K2003H6855
1)
Not for AVT the rmostatic actuator code numb ers: 065-0604, 065-0605, 065-0606, 065-0607
Strokemm5710
Control valve authority1 (100%) in the range of flow setting
Control characteristicLogarithmic
Cavitation factor z≥ 0.6≥ 0.55≥ 0.5
Leakage acc. to standard IEC 534% of k
Upper housing of actuatorStainless steel, mat. No.1.4301
Lower housing of actuatorDezincing free brass CuZn36Pb2As
DiaphragmEPDM
Impulse tubeCopper tube Ø 6 × 1 mm
2
54
AVT Thermostatic actuator
Setting range X
s
°C
Time constant T acc. to EN 14597smax. 50 (170 mm, max. 30 (255 mm)
Gain K
s
mm/°K
Max. adm. temperature at sensor50 °C above maximum setpoint
Max. amb. temperature at thermostat°C0 … 70
Nominal pressure sensor
Nominal pressure immerison pocket
Max. adm. temperature at sensor80 °C above maximum setpoint
Max. amb. temperature at thermostat°C0 … 70
Nominal pressure sensor
Nominal pressure immerison pocket
Capillary tube lengthm5
Flow and temperature controller with integrated
control valve (with AVT or STM)
Up to medium temperature of 100 °C the
controllers can be installed in any position.
Electrical actuator
Note!
Installation positions for electrical actuators AMV(E) have
to be observed as well. Please see relevant Data sheet.
Temperature sensor
The place of installation must be chosen in a way
that the temperature of the medium is directly
taken without any delay. Avoid overheating of
temperature sensor. The temperature sensor
must be immersed into the medium in its full length.
Temperature sensors 170 mm R½
- The temperature sensor may be installed in
any position.
For higher temperatures the controllers have
to be installed in horizontal pipes only, with a
pressure and temperature actuator oriented
downwards.
Temperature sensor 255 mm R¾
- The temperature sensor must be installed as
shown on the picture.
Pressure temperature
diagram
② EN-GJS -400-18-LT (GGG 40. 3) PN 25
① CuSn5ZnPb (Rg5) PN 25
Maximum allowed operating pressure as a function of medium temperature (according to EN 1092-3).
FunctionFlow and temperature controller with integrated
control valve (AVQM-WE, AVQMT-WE)
Flow volume causes pressure drop across
the adjustable flow restrictor. Resulting
pressures are being transferred through the
impulse tubes and/or control drain in the
actuator stem to the actuator chambers and
act on control diaphragm for flow control.
The flow restrictor diff. pressure is controlled
and limited by means of built-in spring for
flow control. Control valve closes on rising
differential pressure and opens on falling
differential pressure to control max flow.
Additionally the electrical actuator will
operate from zero to set max. flow according
to the load.
Safety Temperature Monitor (STM)
- Function
The safety temperature monitor is
proportional temperature controller which
controls temperature and protects the system
against exceeding temperatures. The valve
cone is soft sealed and pressure relieved.
In case the temperature at the temperature
sensor exceeds the adjusted set point, safety
temperature monitor interrupts energy
supply by closing the valve. As soon as the
temperature at the temperature sensor drops,
the valve opens automatically.
Handle for limit setting can be sealed.
- Extended safety function
If there is a leakage in the area of the
temperature sensor, the capillary tube, or the
thermostat, the valve closes by a safety spring
in the safety thermostat. In this case safety
temperature monitor (actuator) must be
replaced.
- Physical Function Principle
The safety temperature monitor operates
in accordance with the liquid expansion
principle. The temperature sensor, the
capillary tube and the bellows are filled with
liquid. As the temperature at the temperature
sensor rises, the liquid expands, the
thermostat stem moves out and closes the
valve.
Temperature Controller (AVT)
- Function
By increasing of medium temperature control
valve cone moves towards the seat (valve
closes), by decreasing of medium temperature
valve cone moves away from the seat (valve
opens).
Handle for temperature setting can be sealed.
- Physical Function Principle
Medium temperature changes cause pressure
changes in temperature sensor. Resulting
pressure is being transferred through the
capillary tube to the bellows. Bellows moves
thermostat stem and opens or closes the
valve.
Settings
Flow setting
Flow setting is being done by the adjustment of
the flow restrictor position. The adjustment can
be performed on the basis of flow adjustment
diagram (see relevant instructions) and/or by the
means of heat meter.
Temperature setting (AVT)
Temperature setting is being done by the
adjustment of the setting spring for temperature
control. The adjustment can be done by means
of handle for temperature setting and/or
temperature indicators.
Limit setting (STM)
Limit setting is being done by the adjustment of
the setting spring for temperature control. The
adjustment can be done by means of handle for
limit setting and/or temperature indicators.