Danfoss AVPL Data sheet

Data sheet
Differential pressure controller (PN 16)
AVPL - return mounting, adjustable setting
Description
Ordering
Example: Differential pressure controller, return mounting, DN 15, kvs 1.0, PN 16, setting range 0.05 - 0.25 bar, t
120 °C, ext. thread
max
- 1× AVPL DN 15 controller Code No: 003L5030
Option:
- 1× Weld-on tailpieces Code No: 003H6908
It can be used on primary side of house substations for smaller systems such as one and two-family houses.
The controller could be used to control the differential pressure across radiator systems and similar systems to keep a constant differential pressure even with a variable system resistance kva and/or supply pressure ∆p0.
Main data:
• DN 15
• kvs 1.0, 1.6 m3/h
• PN 16
• Setting range: 0.05-0.25 bar
(factory setting 0.1 bar) AVPL is a self-acting differential pressure controller primarily for use in district heating systems. The controller closes on rising differential pressure.
• Temperature:
- Circulation water / glycolic water up to 30%: 2 … 120 °C
• Connections:
- Ext thread (weld-on and thread tailpieces)
The controller has a control valve and an actuator with one control diaphragm.
AVPL Controller
Picture
* Controller inc l. impulse tube set AH (1.5 m at kvs 1.0 and 2.5 m at kvs 1.6) and nipple G⁄ - R⁄ fo r impulse tube connecti on to pipe
DN
(mm)
15
kVS
(m3h)
1.0
1.6 003L5031
Ext. thread acc. to ISO 228/1 G ¾ A 0.05-0.25
Connection
∆p setting range
(bar)
Code No. *
003L5030
Accessories
Picture Type designation DN Connection Code No.
© Danfoss | 2020.03
Weld-on tailpieces
15
External thread tailpieces
Description:
Impulse tube set AH
Fitting for impulse tube connection to pipe
EPP insulation box
10 EPDM o-rings for impulse tube 003L8175
1)
The material fo r the insulation box is approve d according to the fire hazard classif ication B2, DIN 4102.
1)
- 1× copper tube Ø 3 × 1 mm
- 2× fitting for imp. tube connec tion to actuator and pipe G /
Conical ex t. thread acc. to
EN 10226-1
- 003H6908
AI180286474027en-000902 | 1
R / 003H6902
1.5 m 003L3561
2.5 m 003L5043 5 m 003L3562
G / - R / 003L5042
G / - R ¼ 003L8151
00 3L817 0
Data sheet Differential pressure controller AVPL (PN 16)
Technical data
Application principles
The controller AVPL could be installed in the return pipeline only.
Nominal diameter DN
k
value m3/h 1.0 1.6
vs
Cavitation factor z 0.5 Nominal pressure PN 16 Max. differential pressure bar 4.5 Medium Circulation water / glycolic water up to 30% Medium pH Min. 7, max. 10 Medium temperature
Connections
Materials
Valve body, etc. Dezincing free brass CuZn36Pb2As Cone, seat, spindle and spring Stainless steel Diaphragm and O-ring EPDM
Impulse tube
o
C 2 … 120
valve External thread
tailpieces Weld-on and external thread
Copper tube Ø 3 × 1 mm
Stainless steel tube Ø 0.8 × 0.2 × 800 mm
15
Installation positions
Direct-connected heating system Indirectly connected heating system
The controllers can be installed in any position.
2 | © Danfoss | 2020.03
AI180286474027en-000902
Data sheet Differential pressure controller AVPL (PN 16)
Sizing
Considering the correlation between the capacity of the system kva, the system flow Q and the differential pressure ∆pa, the controller setting ∆pi is determined by:
∆pi = ∆pa = (Q/kva)
2
Based on the stated differential pressure of the district heating ∆po and the calculated differential pressure of the system ∆pa, the differential pressure across the controller valve is expressed as:
∆pv = ∆po - ∆p
a
Finally, a check is required to ensure that the actual capacity of the controller k than its max. capacity k
kvv = Q / √∆pv ≤ k
vs
vs
is smaller
vv
Example:
A heating system with a number of parallel hot surfaces. Required flow: Q = 0.24 m3/h Total capacity of the system determined to be kva = 0.6 m3/h.
Calculation of the differential pressure across the system:
∆pa = (Q/ kva )2 = (0.24 /0.6)2 = 0.16 bar (16 kPa)
The differential pressure from the district heating is stated to be:
∆po = 0.5 bar (50 kPa) min
Calculation of the differential pressure across the controller valve:
∆pv = ∆po - ∆pa = 0.5 bar - 0.16 bar = 0.34 bar (34 kPa)
In this example the capacity of the controller valve is:
kvv = Q/√∆pv = 0.24/√0.34 = 0.412 m3/h
which is less that the max. capacity of the controller = kvs = 1.0 m3/h.
Design
1. Spindle for differential
pressure setting
2. Bushing
3. Actuator
4. Control diaphragm
5. Setting spring for diff.
pressure control
6. Connection for impulse tube
7. O-ring
8. Pressure relieved valve cone
9. Seat
10. Valve body
AI180286474027en-000902
© Danfoss | 2020.03 | 3
Data sheet Differential pressure controller AVPL (PN 16)
2
va
a
k
Q
p
⎟ ⎠
⎜ ⎝
=
2
vv
v
k
Q
p
⎟ ⎠
⎜ ⎝
=
()
( )
2
vv
2
va
o
k1k1
p+∆
=
()
()
2
vvs
2
va
o
max
k1k1
p
Q
max
min
+
=
Function AVPL is a proportional controller which operates
according to the following principle: The degree of opening of the control valve / kv value is proportional to the deviation between the controlled and set differential pressure, ∆pa – ∆ps. Thus the resistance/kv value is adjusted to the actual differential pressure ∆pv and accordingly, the flow Q is adjusted so that the desired differential pressure ∆pa is obtained across the actual resistance kva in the system.
Differential pressure across the system
Differential pressure across the controller
Differential pressure from the district heating
Settings
∆po = ∆pa + ∆p
AVPL can be set to any differential pressure
v
within the range 5 kPa to 25 kPa (0.05 bar to
0.25 bar). The factory pre-setting of the AVPL is 10 kPa (0.1 bar), 1 kPa for each turn.
Rewritten the flow can be expressed as
The max. flow is limited by the min. differential pressure of the district heating ∆p capacity of the system k capacity of the controller k
, and of the max.
va
max
.
v
vs
, the max.
o
min
Max. system flow:
The chosen deviation is large enough to ensure a stable control and small enough to keep the controlled differential pressure within acceptable limits.
As mentioned above, the proportional effect depends on the correlation between the controller valve’s degree of opening and the deviation between the controlled and set differential pressure. Furthermore, the deviation depends on the actual differential pressure across the control valve and the actual control setting.
The controller is designed in such a way that the controlled and the set differential pressures are equal when the flow is about 250 l/h for AVPL 1.0 and 400 l/h for AVPL 1.6 at nominal differential pressure 50 kPa (∆pv). At min. and max. flow the controlled differential pressure deviates from the set pressure with ±1…3 kPa, depending on the actual differential pressure and setting.
4 | © Danfoss | 2020.03
AI180286474027en-000902
Data sheet Differential pressure controller AVPL (PN 16)
Dimensions
DN
15 (kvs 1.0) 15 (kvs 1.6) 0.69
L1
(mm)L2(mm)L3(mm)H(mm)D(mm)aISO 228/1bIS O 7/1
65 120 139 10 4 63 G ¾ A R ½
Weight
(kg)
0.64
Fittings
AI180286474027en-000902
© Danfoss | 2020.03 | 5
Data sheet Differential pressure controller AVPL (PN 16)
6 | © Danfoss | 2020.03
AI180286474027en-000902
Data sheet Differential pressure controller AVPL (PN 16)
AI180286474027en-000902
© Danfoss | 2020.03 | 7
Data sheet Differential pressure controller AVPL (PN 16)
8 | © Danfoss | DHS-SRMT/SI | 2020.03
AI180286474027en-000902
Loading...