Danfoss AVDO Data sheet

Data Sheet
Automatic Bypass Control AVDO
Application
AVDO is a self-acting constant flow control primarily used either to maintain minimum flow rates through e.g. a low-capacity gas boiler or to control the differential pressure in a central heating system.
AVDO:
has a setting range of 0.05 - 0.5 bar
Low-capacity gas boiler where maintenance of a min.
flow is required
is dimensioned for pressure stage PN 10,
max. 120 °C DN 15 and DN 20
operates without impulse tubes
On delivery valve housing is fit onto AVDO with one of the following fittings: internal socket thread, internal socket thread/nipple or external thread for compression fittings.
Differential pressure control
Danfoss Heating Solutions VD55K902 © Danfoss 02/2011 1
Q [m³/h]
∆P [bar]
Q [m³/h]
∆P [bar]
Data Sheet Automatic Bypass Control AVDO
Ordering
Type Setting range, Connection Code no.
bar Inlet Outlet
AVDO 15 AVDO 20 AVDO 25 AVDO 15 AVDO 20 AVDO 25 AVDO 15
AVDO 20 AVDO 25 AVDO 15
AVDO 20 AVDO 25
1)
According to ISO 7/1
2)
According to ISO 228/1
0.05 - 0.5
0.05 - 0.5
0.05 - 0.5
0.05 - 0.5
Rp ½ Rp ¾
Rp 1 Rp ½ Rp ¾
Rp 1
G ¾ A
G 1 A
G 1 ¼ A
Rp ½ Rp ¾
Rp 1
1)
1)
1)
1)
1)
1)
2)
2)
2)
1)
1)
1)
R ½ R ¾
1)
R 1 R ½ R ¾
1)
R 1
G ¾ A
G 1 A
G 1 ¼ A
R ½ R ¾
1)
R 1
1)
1)
1)
1)
1)
1)
2)
2)
2)
003L6002 003L6007 003L6012 003L6003 003L6008 003L6013 003L6020
003L6025 003L6030 003L6018
003L6023 003L6028
Accessories (supplied in boxes of 10)
Copper tube fittings Code no.
AVDO 15
AVDO 20
Ø 16 x 1 013U0131 Ø 18 x 1 013U0132 Ø 18 x 1 013U0134 Ø 22 x 1 013U0135
AVDO 25 Ø 28 x 1 013U0140
Technical Data
Capacities
Setting range: 0.05 - 0.5 bar Max. differential pressure 0.5 bar
Max. flow temperature 120 °C Max. leakage at closed valve 50 l/h
Operation pressure PN 10
AVDO 15 AVDO 25
2 VD55K902 © Danfoss 02/2011 Danfoss Heating Solutions
Q [m³/h]
∆P [bar]
Data Sheet Automatic Bypass Control AVDO
AVDO 20
A = set opening pressure
∆P = ∆p for valve
– - – = Upper limit graph for recommended application area with almost noiseless installation. Measurement conditions according to ISO 3743.
Design
Installation
Setting
Materials
Setting handle Pom-plast
1.
2. Base Ms 58
3. Spring guide PPS plastic
4. Spring Stainless steel
5. Valve cone PPS plastic
6. Valve body Ms 58, hot-pressed
7. Setting pin Stainless steel O-rings EPDM
The valve body must be mounted with flow in direction of the cast-in arrow.
The control is set by turning the setting dial. AVDO has a setting scale on which the opening pressure in bar or mwg can be directly read. The differential pressures stated for a given setting are indicative.
The scale gives the differential pressure across the AVDO when it just begins to open.
Danfoss Heating Solutions VD55K902 © Danfoss 02/2011 3
1
1
Data Sheet Automatic Bypass Control AVDO
Sizing
Fig. 1 Fig. 2
Example 1: Bypass control across heating system
Given:
System, see fig. 1.
Insignificant pressure loss in pipe from
boiler to bypass. Pump characteristic, see fig. 2.
0.15 bar system differential pressure at max.
system load.
Required:
Bypass circulation beginning at 0.15 bar
pump pressure. Min. 2.0 m³/h boiler circulation.
Seek:
A constant flow control that opens
concurrently with falling load across the system (closing radiator thermostats).
A constant flow control that ensures min. 2.0
m³/h boiler circulation at min. system load.
Solution:
A 2.0 m³/h flow corresponds to a 0.25 bar
pump pressure. On closing radiator thermostats AVDO is to ensure min. 2.0 m³/h circulation at 0.25 bar differential pressure across AVDO. Choose AVDO 25 that provides 2.75 m³/h at 0.25 bar differential pressure across valve. Set AVDO on 0.15 bar required opening pressure.
Example 2: Bypass control across circulation pump
Given:
System, see fig. 3.
-Pump characteristic, see fig. 4.
Required:
Bypass circulation beginning at 0.1 bar
pump pressure. Max. system differential pressure at closed
radiator thermostats must be limited to 0.25 bar.
Seek:
A constant flow control that opens
concurrently with falling load across the system (closing radiator thermostats).
A constant flow control that ensures max.
system differential pressure not exceeding
0.25 bar at min. system load.
Solution:
The max. permissible differential pressure
0.25 bar across system corresponds to a 1.8 m³/h water volume (fig. 4). At min. load AVDO must ensure 1.8 m³/h pump bypass circulation. In this example AVDO 20 must be used - see "Capacity".- As circulation is not to begin before differential pressure across system has exceeded 0.1 bar, AVDO is set on 0.1 bar - see "Setting.
Fig. 2
Fig. 4
1. Pump characteristic
4 VD55K902 © Danfoss 02/2011 Danfoss Heating Solutions
Data Sheet Automatic Bypass Control AVDO
Dimensions
Fig. 1 Fig. 2
Fig. 3 Fig. 4
Fig. 1
DN Type
1)
a
1)
b
L3 L4 L5 H1 S1 S2
min max
15 AVDO 15 RP ½ 40 69 33 83 112 28 30 20 AVDO 20 RP ¾ R ¾ 42 74 37 83 112 34 37 25 AVDO 25 RP 1 R 1 46 81 46 85 114 43 40
Fig.2
DN Type
1)
a
L3 L5 H1 S1
min max
15 AVDO 15 RP ½ 40 33 83 112 28 20 AVDO 20 RP ¾ 42 37 83 112 34 25 AVDO 25 RP 1 46 46 85 114 43
Danfoss Heating Solutions VD55K902 © Danfoss 02/2011 5
Data Sheet Automatic Bypass Control AVDO
Fig. 3
DN Type a, mm
2)
b
L1 L2 H1 S
min max 15 AVDO 15 15/16/18 G ¾ A 87 111 89 113 30 20 AVDO 20 18/22 G 1 A 93 120 90 114 37 25 AVDO 25 28 G 1¼ A 106 136 95 119 45
Fig. 4
DN Type
1)
a
1)
b
L1 L2 H1 S1 S2
min max
15 AVDO 15 RP ½ 87 116 89 113 28 30 20 AVDO 20 RP ¾ R ¾ 93 125 90 114 34 37 25 AVDO 25 RP 1 R 1 106 141 95 119 43 40
1)
According to ISO 7/1
2)
According to ISO 228/1
6 VD55K902 © Danfoss 02/2011 Danfoss Heating Solutions
Data Sheet Automatic Bypass Control AVDO
Danfoss Heating Solutions VD55K902 © Danfoss 02/2011 7
Data Sheet Automatic Bypass Control AVDO
Danfoss A/S Heating Solutions Haarupvaenget 11 8600 Silkeborg Denmark Phone:+45 7488 8000 Fax: +45 7488 8100 Email: heating.solutions@danfoss.com www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
8 VD55K902 © Danfoss 02/2011 Danfoss Heating Solutions
Loading...