User guide
AST-g driver
The driver is powered by two 9V batteries or external DC
power supply.
Batteries may remain in the driver when external power
supply is used.
The batteries will not be charged or otherwise connected to
the circuit when the driver is connected to external power
supply. A switch in the power jack disconnects the batteries
when external power supply is connected.
Installation of batteries
To install batteries open the battery compartment on the
backside of the driver. Use Philips size 2 cross screwdriver to
open the lid
Connection to the external power supply
1. Connect the stepper motor to the terminals or to the
M12 connector. Do not connect two stepper motors at
the same time. Match the wire colour to the colour
indicated on the driver. The driver is intended to be use
with Danfoss ETS and KVS valve. Any bipolar stepper
motor accepting 100mA/coil and with max 75Ω/coil can
be tested with the driver. Phase 1 should be connected
to the L1+ and L1– terminals, Phase 2 should be
connected to the L2+ and L2– terminals.
2. Select speed
3. Push the ACTIVATE toggle in close direction to close the
valve
4. Push the ACTIVATE toggle in open direction to open the
valve
Note: KVS 15 - 35 opens and closes in the opposite
direction of all ETS sizes and KVS 42- 54.
5. Make sure that the POWER LED is lit. If not change the
batteries or make sure the external power supply is
connected and switches on.
6. Observe the terminal indicator LEDs
At Speed above 1 step/sec the LEDs will ash quickly.
At 1 step/sec the LEDs will indicate how the phases are
energized.
Only one LED per phase should lit at a time.
At higher speeds all LEDs seems to light up continuously.
Operating the valve at speed 1 step/sec will show how
the phases are energized.
The LEDs will light in the following sequence:
1
2
3
4
ETS
KVS 42 -54
open
Black
L1+
••
••
White
L1–
••
••
Green
L2+
Red
L2–
KVS 15 - 35
open
If only one LED is on, the other phase is disconnected or
broken.
If two LEDs lights but in a di erent sequence, the phases
have been mixed, e.g. green and white wire swapped.
Speci cation
Speed [step/sec]
1, 18, 37, 75, 150 and 300 can be selected
Motor Connector
Spring clamp connectors on front cover, and
M12 connector on back panel.
Power
2 x 9V batteries type 6L61 or 12V-18Volt external supply,
e.g. Mascot adaptor no.9883000047
Power connector
standard 5.5 mm adaptor connector, centre contact
positive.
Danfoss code no.: 034G0013
Take care not to mix up the polarity of the batteries.
© Danfoss A/S (AC-BNM / mr), 09 - 2007 RI4JY102 - 034R9514 → DKRCC.PI.VD1.C1.02/520H2411 1