DEVI - an abbreviation of Dansk El-Varme Industri – was established in
Copenhagen, Denmark, in 1942. As from January 1st 2003 DEVI has become
a part of the Danfoss Group - Denmark’s largest industrial Group. Danfoss
is one of the world’s leading companies within heating, cooling and airconditioning. The Danfoss Group has more than 23.000 employees and
serves customers in more than 100 countries.
DEVI is Europe’s leading brand of electrical cable heating systems and electric
pipe heating systems with over 70 years of experience. The production of
heating cables takes place in France and Poland while the head office is
situated in Denmark.
The value of experience
We have installed literally thousands of systems across the globe, in every
conceivable setting. This experience means that we can offer you practical
advice about precisely which components you need to get the best results at
the lowest cost.
Asphalt application. Ice & Snow Melting
This design guide presents DEVI’s recommendations for design and
installation of ice and snow melting systems for asphalt application.
It provides guidance for heating cable positioning, electrical data and system
configurations.
Our quality management
Following DEVI’s recommendations will ensure energy efficient, reliable and
maintenance free solution for constant wattage heating cables with 20 year
warranty.
system
and compliances
ISO 9001TS 16949
ISO 14001PED
Along with full compliance with EU
directives and product approvals
1. Application
Briefing
Winter weather costs
In recent years there have been
plenty of new stories about human
and financial costs caused by
increasingly harsh winter weather.
Property damage, increased
maintenance expenses, lost
productivity, rising insurance
premiums, personal injuries and even
worse. Installation of DEVI Ice & Snow
Melting System ensures a steady
solution to address cold weather
related problems.
Asphalt Ground solution – with a
first class product range
The DEVIasphalt™ Snow Melting
System is a system installed directly
in asphalt ensuring instantaneous
relief from snow build up and ice
forming.
DEVIasphalt™ series introduces
completely new standards for highperformance cables used for ice
and snow melting in asphalt areas
outside.
DEVI recommends the DEVIasphalt™
cables and mats for asphalt
installations as they provide shortterm resistance to temperatures
of 240 °C. With this type of cables
and mats the sand bed over the
cable is not required. This reduces
Benefits
• Efficient snow removal
• Safe traffic and working areas for people
• Quick installation directly in asphalt, no need to
cover cables with a sand bed or concrete
• Up to 20% Energy saving comparing to heating
elements installation in a sand bed
• Cost saving for asphalt repair after winter
• Environment is protected against salting and
antifreeze related damages.
• Automatic ”Around the Clock” snow clearing service.
• Smart 2-zone control with low energy consumption
• PVC free, twin conductors heating cables and mats
(IEC 60800 and IEC 62395)
• A maintenance free system with 20 year full warranty on cables and heating
time and installation costs. To avoid
cable damage heavy machinery
(rollers or asphalt laying machines)
should not be used. Asphalt cover
should be at least 5 cm thick from
the top of the DEVIasphalt™ heating
cables. An electrician should ensure
of cable and insulation resistance
measurements both before and after
asphalt is applied.
By using DEVIasphalt™ heating cables
and mats controlled by electronic
thermostats with moisture sensors,
you can cost-effectively protect large
areas such as parking areas, ramps
or pedestrian accesses to buildings.
Giving you convenience and safety
while saving a lot of tiring and timeconsuming manual work.
One of the greatest advantages of
this system is a prompt response and
as a result, the most energy efficient
solution for the ground ice & snow
melting applications.
2. System Description
The most common DEVI ice and snow
melting applications on ground are
car parks, driveways, pavements,
outdoor steps, loading platforms and
bridges.
Main purpose of the application is to
melt snow or slippery ice on asphalt
surfaces.
Like for any other outdoor areas
during winter, snow and ice needs
to be removed from asphalt surfaces
to secure safe access to buildings.
It can be done manually or in a
smart way – by means of electrical
ice & snow melting system with
thermostat control and moisture and
temperature sensors that can control
2 zones simultaneously. Inactive
during cold but dry weather 2 zone
control saves energy and reduces
costs.
The automatic regulation of the snow
melting system keeps areas free of
snow and passable at all times –
night and day.
Another great advantage of the
system installed directly in asphalt is
a prompt response or warm up time
compared to other installations.
Two types of asphalt applications are
used most frequently: Mastic asphalt
and Road/concrete asphalt.
Important: if DEVIasphalt™ cable or
mat is embedded in asphalt
• 2 layers of asphalt must be always
ensured
• DEVIasphalt™ cable must be
installed in the first asphalt layer
(max. 8 mm stone fraction)
• If road asphalt is used, first layer
must be rolled by a hand drum
• First layer must be cooled down
to max 80 °C before laying the
second layer
• The second layer can be rolled
with up to 500 kg
Warm-up time for 2 applications, 300 W/m² in -3 °C air temperature
0,5
0
-0,5
-1
[°C]
-1,5
-2
-2,5
Surface temperature
-3
0 1 2 3 4 5
When installing ice and snow melting
systems on steep slopes it may be
necessary to provide some drainage
for melted water at the slope bottom.
The drain system should also be
protected against ice formations.
The diagram below shows the
warm-up time values for 2 different
driveways constructions. The heating
cable that is installed directly into
asphalt (red line) can warm up the
surface approx. 4 times quicker
comparing to the cable that is
installed in sand bed with pavement
blocks (blue line).
Driveway w ith sand bed &
80 mm pavement block s
Car park with 60 mm
mastic asphalt
Hours [hrs]
Fig. 1 - DEVIasphalt™ heating cable under the first layer of Road asphalt
rolled by a hand drum.
Fig. 2 - The cables are protected by concrete prior to further asphalt
arrangement.
Mastic asphalt is a dense mass
composed of suitably graded minerals
such as chippings, sand, limestone
The primary difference between
Mastic asphalt and Road/concrete
asphalt is the compound density.
powder and bitumen. When Mastic
asphalt is used along with heating
cables, it should be used as a filling
material with rounded stones of small
fraction (less than Ø8 mm) in such a
Mastic asphalt provides a perfect
impermeable mass. It is often used in
park decks, bridges and tunnels or as
a filler.
way as not to damage the heating
cables.
Impervious consistency of the Mastic
asphalt can be attributed to its high
content and concentration of bitumen
that is much higher than in Road/
concrete asphalt.
When Mastic asphalt is heated to high
temperatures, it is formed as a solid
liquid substance that can be poured or
spread over the surface by means of a
hand float or mechanical finishing.
2.2 Road/concrete asphalt application
Mastic asphalt does not need
any compaction/compression as
contrasted to Road asphalt.
The Mastic asphalt installation
temperature shall not exceed 240 °C
before pouring over the cables.
Mastic asphalt, 2nd layer
st
Mastic asphalt, 1
DEVIasphalt™ heating cable or mat
Sensor in a metal pipe
DEVIfast™ fitting or mesh for the cable
Lower support or crushed stone
Ground
layer
Road/concrete asphalt is typically
composed of 5% asphalt/bitumen
cement and 95% aggregates (stone,
First later of road asphalt must be
rolled by a hand drum. Second layer
may be rolled with up to 500 kg.
sand, and gravel).
The temperature required when
spreading can vary depending upon
characteristics of the asphalt or
bitumen and is usually 130...150 °C.
Considering sturdiness and ability
for quick repair, it is easy to maintain
asphalt pavements. Wear or
damaged surfaces can be milled,
removed and replaced by a new
layer. Road asphalt is often laid in
layers with compaction of each by
means of mechanical rollers.
2.3 Application with thermal protection layer
Heating cables or mats can be placed
in thermal protective layer – sand,
concrete, etc. It ensures the heating
cable protection against high
temperatures of the asphalt cover.
When concrete is used as a
protection it is possible to roll asphalt
with no weight restriction.
DEVIasphalt™ cables and
DEVIasphalt™ mats are extremely
high-quality products consisted of a
360° fully screened twin conductor
cable with highly robust outer sheath
(UV stable), designed especially for
embedding in mastic asphalt or road/
concrete asphalt.
The 10 m cold lead has solid
conductors ensuring quick installation
with a clearly visible connection.
To ensure long life-time and quality
all cables are thoroughly inspected
including tests for Ohmic resistance,
high voltage and material control.
DEVIasphalt™ 300T mat is a heating
mat with DEVIasphalt™ heating cable
fixed on a plastic mesh.
Mats are available for two power
supply options - 230 and 400 V.
Output is 300 W/m² (230 or 400 V).
Mat width - 0,5 m for 230 V and 0,5,
0,75 and 1 m for 400 V.
Available size: 1 - 12,4 m² for 230 V
and 1,7 - 21,15 m² for 400 V.
Note. The number at the end of the
cable’s and mat’s name refers to its
linear output – W/m or area output –
W/m², at 230 V or 400 V. Letter “T”
means twin conductor cable (Twin).
Fixing
The product range of controls is
designed for external systems
including the following:
• thermostats with a temperature
sensor - DEVIreg™ 330 (5…45 °C),
DEVIreg™ 610, DEVIreg™ 130;
• regulator with an integrated
temperature and moisture
sensor(s) - DEVIreg™ 850.
To control simple or low output
systems thermostat with a ground
temperature sensor is recommended.
DEVIreg™ 330 (5…45 °C) thermostat
with the DIN rail attachment is recommended as a standard solution. It can
be also used on wall/pipe mounted
DEVIreg™ 610, IP44. As an alternative
to control small areas near private
houses etc. DEVIreg™ 130 wall mounted room thermostat can be used.
All thermostats above are supplied
with a wire temperature sensor –
NTC 15 kOhm @25 °C, 3 m.
To control ice and snow melting systems especially with high output the
best solution is DEVIreg™ 850 regulator/
controller with integrated ground and
roof moisture and temperature sensors.
DEVIasphalt™ 30T cable is a twin
conductor heating cable for
installation in asphalt of 240 °C
maximum installation temperature.
Cables comply with EN62395-1:2006
and IEC 60800:2009 class M2 - for
applications with high risk of
mechanical damage.
It’s supplied in a readymade set
with a 10 m cold lead, hermetic
connections and end muffs.
Cable diameter – 7 mm.
Cables are available for 400 V power
supply.
Cable linear output is 30 W/m (400 V).
Available lengths: 8,5 - 215 m.
If heating cable is applied, it is
recommended to use a fitting band
to fix cable to the floor base. For
example, metal galvanized DEVIfast™
fitting band. It is attached to the
basement (nailed etc.) in parallel lines
usually in 50 cm or 2 meter intervals
of fitting band for each square meter
of the cable installation.
Control
Ice and snow melting systems
are different and require different
thermostats/regulators.
DEVIreg™ thermostats and regulators
are fitted with a complete set of
control functions for heating systems
for ice and snow melting of any
type and allow attaching external
measuring sensors for ground
temperature measuring as well as
control of moisture conditions.
DEVIreg™ 850 is a two-zone controller
with possibility of connection up to 4
sensors to provide maximum control
of the outdoor heating system. Comparing to installations with typical
ground temperature measuring this
regulator allows reduction of energy
consumption costs by up to 30-40%.
Products - general overview for ice and snow melting for Asphalt application
ProductOptionsDescription
DEVIasphalt™
Resistive heating cable
DEVIasphalt™
Resistive heating mat
Fixing DEVIfast™ Metal25 m pack; galvanized metal, fixings every 2,5 cm.
DEVIreg™
Regulator
Moisture & temperature
sensor
Accessories
DEVIreg™
Thermostat
DEVIreg™
Thermostat
DEVIreg™
Room thermostat
Temperature sensor10 m, PVCWire sensor, Ø8 mm, IP65, NTC 15 kOhm @25 °C
DEVIasphalt™ 30T
400 V program
DEVIasphalt™ 300T
230 & 400 V program
DEVIreg™ 850
Ground sensor
for DEVIreg™ 850
PSU 24 V
for DEVIreg™ 850
DEVIreg™ 330 (5…45 °C)
DEVIreg™ 610
DEVIreg™ 130
Twin conductor, 100% screen, UV stabilized, black,
short term contact with 240 °C allowed, 30 W/m (400 V).
DIN IEC 60800:2009 M2, EN 62395-1:2006
Twin conductor, 100% screen, UV stabilized, black,
short term contact with 240 °C allowed, 300 W/m² (230 V/400 V).
DIN IEC 60800:2009 M2, EN 62395-1:2006
Connection to Ground and Roof moisture and temp. sensor, max
4 sensors, 2 zones,
2x15 A, PSU 24 V, DIN rail
Ø93 x 98 mm, IP67, 15 m connection cable 4x1 mm²
Extra PSU for DEVIreg™ 850 with 3-4 sensors
5…45 °C, 16 A, IP20, with wire sensor, 3 m,
DIN rail
-30…+50 °C, 10 A, IP44, with wire sensor, 3 m,
on wall/pipe installation
5…45 °C, 16 A, IP30, with wire sensor, 3 m,
room on wall installation
For additional information please refer to the DEVI Catalogue.
• Project details (materials, foundation
type, dimensions, insulation);
• Electrical data (voltage, power,
control requirements);
• System performance expectations;
• Safety factor.
Evaluation of the specific output for
ice and snow melting systems can
be done based on the diagram and
other similar documents.
Installed output (in W/m²) for asphalt
areas is identical to other ice & snow
melting installations. For more
information about performance of
ice and snow melting systems, as well
as control, see Outdoor Application
manuals.
No back loss & area width 6 m & 50% cloud cover
Surface temp. - 3 °C & 70% relative humidity
700
600
500
Heatloss [W/m²]
400
300
200
100
0
-3-113579111315 17 19 2123 25
Temperature difference [K] between surface and ambience
Fig. 3. Wind and temperature dependent heat loss
When installing ice and snow melting
systems it may be necessary to
provide drainage for melted water
at the slope bottom, walkways, etc.
The drain system should also be
protected against ice formations.
0 m/s
2 m/s
4 m/s
6 m/s
8 m/s
10 m/s
15 m/s
20 m/s
25 m/s
30 m/s
For example, heat loss depending
on the wind speed and temperature
differences between the surface and the
ambient air is described in 2003 ASHRAE
Application Handbook (see fig. 3).
For example, for medium weather
conditions and 6 m/s wind speed, if
choosing ΔT = 10 K (from -3 K to +7 K)
the heat loss value is approx. 230 W/m²
(marked with the red dotted line in fig. 3).
In other words, surface heating up to
10 degrees requires 230 W/m² or
230 / 10 = 23 W/(m²·K).
All in all, for medium winter weather
conditions, heating of 1 m² outdoor
surface up to 1°С needs power of
approx. 23 Watts. Or the calculation
heat exchange coefficient for outdoor
surfaces is approx. 23 W/(m²·K)
(sometimes named αout – “alpha out”).
As an example IEC 62395-2 provides
another evaluation of typical snow
melting heat loads (see table 1).
Values in table 1 less than 250 W/m²
should be used in limited
circumstances, for example in
countries with warm climate or
with the technical justification. Low
output at the level of 150-200 W/m²
may lack for snow and ice melting.
Moderate, for example,
commercial walkw ays and
driveways
W/m²
Add 100 W/m²:
• for every 1000 m altitude;
• if the heated area isafree standing
construction without insulation;
• if the local average wind speed is
• >6 m/s;
• if the more efficient system is
Maxi mum, fo r example, tal l
plaz as, hos pita l emerg ency
entrances and helicopter
decks
required;
For ice and snow melting systems
should be recommended next outputs:
• if it snows at temperatures lower
than -10 °C.
• minimum– 250 W/m²,
• optimum – 350 W/m².
Note. It can be recommended to
design output for ice and snow
Output for ice and snow melting
systems should be designed to follow
The main task of ice and snow
melting systems is melting, i.e. to
maintain +3 °C on the surface. Any
output can be addressed to the
lowest temperature at which ice and
snow is still melting or the heating
system will cope with its main task.
Table 2 shows some heat outputs
(W/m²) and temperatures at which
system ensures ice & snow melting
or, in other words, supports +3 °С on
the surface.
4.2 Insulation
The benefit of thermal insulation
is significant for free standing
constructions as ramps or bridges,
steps, etc. Insulation of the free sides
of the construction must also be
considered.
In this example, a 6 m wide bridge
is exposed to snow at -3 °C air
temperature and 4,5 m/s crossing
wind. Calculated approx. downward
heat losses are presented in the table
below.
Output,
W/m²
Min air temperature
for +3 °C on surface
(α
= 23 W/(m²·K))
out
250-8 °C
300-10 °C
350-12 °C
400-14 °C
550-21 °C
Table 2. Minimum melting air temperatures
for some outputs. ΔT surface-air is calculated
as output divided by the heat exchange
coefficient 23 W/(m²·K).
For example, if 250 W/m² is installed,
then the heating system enables
ice and snow melting at the air
temperature not lower than -8 °C
(ΔT = 250/23 ≈ 11 °C).
But if the ambient/air temperature is
-12 °C for instance, then the surface
temperature will be -1 °C, with
ΔT = -11 °C for output of 250 W/m².
It means that the system consumes
power for surface heating, but
doesn’t melt ice and snow at all.
Asphalt, one or more layers
Sand or concrete protection layer
DEVIasphalt™ heating cable
DEVIfast™ fitting or mesh for the cable
Insulation
Free standing construction
Ambient/air temperature
Insulation
thickness
Downward
heat loss, %
No insulation36
20 mm23
50 mm15
100 mm9
4.3 C-C distance and corresponding output (W/m²)
The C-C distance is the centre- tocentre distance between the
adjacent cables (sometimes named
“installation step”).
С-С
С-С
Note! Heating cable bending
diameter must be at least 6 times
cable diameter.
TThe C-C distance and corresponding
output W/m² can be calculated by
the following formulas (see also
Application manual - Cable Floor
Heating Systems):
Area [m²]
C - C [cm] =
Cable length [m]
· 100 cm
or
Cable output [W/m]
C - C [cm] =
Heat density [W/m²]
· 100 cm
Output of the DEVIasphalt™ cable for
some C-C is presented in table:
Heating Cables embedded in a protection layer under Asphalt
Ground areas such as driveways, walkways and pavements
Asphalt concrete
Concrete or sand
DEVIasphalt™ cables
or DEVIasphalt™ mats
DEVIfast™ or fastening to
the mesh for cable
Lower support or crushed stone
4.4 Control
Ice and snow melting systems
are different and require different
thermostats. The control product
range is designed for external
systems including the following:
• thermostats with a temperature
sensor – DEVIreg™ 330 (5…45 °C),
DEVIreg™ 610, DEVIreg™ 130;
• regulator with integrated
temperature and moisture
sensors - DEVIreg™ 850.
To control simple or low output
systems (approx. up to 5 kW)
thermostat with a temperature sensor
is recommended. The sensor is usually
installed in a metal pipe nearby a
heating cable (“in the ground”).
DEVIreg™ 330 (5…45 °C) thermostat
with the DIN rail attachment is
recommended as a standard solution.
It can be also used a wall/pipe
mounted DEVIreg™ 610, IP44.
As an option, to control small areas
nearby private houses, etc., DEVIreg™
130 wall mounted room thermostat
can be used. Please pay attention to
the right place for the thermostat
installation, considering that this is a
class IP20 room thermostat .
All thermostats are supplied with a
wire temperature sensor –
NTC 15 kOhm @25 °C, 3 m.
The sensor cable must have
an appropriate length to allow
temperature measurement in a right
point – additional standard sensor
length should be used, e.g. 10 m, or
sensor cable can be adjusted to any
length by cable size of at least 0,5 mm².
To control ice and snow melting
systems DEVIreg™ 850 regulator/
controller with an integrated
temperature and moisture sensor is
recommended. We recommend this
type of regulator for installations with
output capacity exceeding 5 kW or
for any smaller installations where
optimum power use is a preference.
DEVIreg™ 850 is a two-zone (A and
B) controller with possibility to
connect 4 integrated ground and
roof moisture & temperature sensors
to provide maximum control of the
heating system.
A
B
B
The ground sensor is equipped
with 15 m cable for connection to
regulator.
Comparing to installations with
typical ground temperature
measuring this regulator allows
reducing energy consumption costs
of up to 30-40%.
• Cutting the heating element will
void the warranty.
• Cold leads can be shortened to
suit requirements.
Elements must always be installed
according to local building
regulations and wiring rules as well as
the guidelines in proper installation
instructions and this manual.
• Any other installation may hamper
element functionality or constitute
a safety risk, and will void the
warranty.
• Make sure that elements, cold
leads, connection boxes, and other
electrical components do not
come into contact with chemicals
or flammable materials during or
after installation.
Elements must always be connected
by an authorized electrician using a
fixed connection.
• De-energize all power circuits
before installation and service.
• The connection to the power
source must not be directly
accessible to the end user.
• Each heating cable screen must
be earthed in accordance with
local electricity regulations and
connected to a residual current
device (RCD).
• Recommended RCD trip rating is
30 mA, but may be up to 300 mA
where capacitive leakage may lead
to nuisance tripping.
• Heating elements must be
connected via a switch providing
all pole disconnection.
• The element must be equipped
with a correctly sized fuse or circuit
breaker, e.g. 10/13 A for a 1,5 mm²
cold lead and 16/20 A for a 2,5 mm²
cold lead.
The presence of a heating element
must
• be made evident by affixing
caution signs or markings at the
power connection fittings and/or
frequently along the circuit line
where clearly visible
• be stated in any electrical
documentation following the
installation.
Never exceed the maximum heat
density (W/m² or W/m) for the actual
application.
Prepare the installation site properly
by removing sharp objects, dirt, etc.
Heating elements may not touch or
cross themselves or other heating
elements and must be evenly
distributed on areas.
Regularly measure Ohm resistance
and insulation resistance, minimum:
before, during and after installation.
The elements and especially the
connection must be protected from
stress and strain.
Do not install heating elements
under walls and fixed obstacles. Min.
6 cm space is required.
Keep elements clear of insulation
material, other heating sources and
expansion joints.
The element should be temperature
controlled and not operate at
ambient temperature higher than
10 °C in outdoor applications.
5.1.2 Planning the installation
Draw a sketch of the installation
showing
• element layout
• cold leads and connections
• junction box/cable well (if
applicable)
• sensor
• connection box
• thermostat/regulator
Save the sketch
• Knowing the exact location
of these components makes
subsequent troubleshooting and
repair of faulty elements easier.
Please observe the following:
• Observe all safety guidelines.
• Observe correct cable C-C
distance and distance between
mats.
• Observe required installation
depth and possible mechanical
protection of cold leads
according to local regulations.
• When installing more than one
heating element, never wire
elements in series but route
all cold leads in parallel to the
connection box.
• For single conductor cables, both
cold leads must be connected to
the connection box.
Remove all traces of old installations,
if applicable.
• Ensure that the installation surface
is even, stable, smooth, dry and
clean.
• If necessary, fill out gaps around
pipes, drains and walls.
• There must be no sharp edges, dirt
or foreign objects.
5.2.2 Installing heating elements
• The ohmic resistance must be
within -5 to +10 % of the value
labeled.
• The insulation resistance should
read >20 MΩ after one minute at
min. 500 V DC.
Observe all instructions and
guidelines in section about general
safety and in proper installation
instructions.
Heating elements
• Position the heating element
so that it is at least half the C-C
distance from obstacles.
• Heating elements must always
be in good contact with the heat
distributor (e.g. concrete).
• When using heating mats secure
them to the ground, some mats
are mitted with a glue covered
surface, it attaches well to a
cleaned and primed surface.
5.2.3 Installation summary
Prepare installation surface with
DEVIflex™ fastening accessories and/
or mesh reinforcement.
Apply sensor conduit Ø 16-20 mm
made from heat resistant material,
e.g. metal. Fix conduit for sensor tube
for DEVIreg™ 850 ground sensor, if
any.
Place cold leads and connections
in a dry place. Seal all penetrations
through walls or similar structures.
Apply caution tape above cold leads.
It is not recommended to install
heating elements at temperatures
below -5 °C.
At low temperatures, heating cables
can become rigid. Connect the cable/
mat to the mains for a short time
(few minutes). The cable or mat must
be rolled out during this process!
Measuring resistance
Measure, verify and record element
resistance during installation.
• After unpacking
• After fastening the elements
• After the installation is finalized
If Ohm resistance and insulation
resistance are not as on label
attached to product and product
transportation box, the element must
be replaced.
Heating mats
• Always roll out heating mats with
the heating cables facing up.
• When the heating mat reaches the
area boundary, cut the liner/net
and turn the mat before rolling it
back.
Extending cold leads
• Avoid extending cold leads if
possible. Wire cold leads to e.g.
junction boxes or cable wells.
• Be aware of power loss in the
extending cold leads according to
local regulations and wiring rules.
After laying blocks or pouring
concrete/asphalt, install external
sensor(s), and extend sensor cable(s)
according to the sensor manual.
The DEVIreg™ thermostat/regulator
must be commissioned as prescribed
in the installation manual and
adjusted where local conditions vary
in relation to factory settings.
Before every season, check for faults
in the switchboard, thermostat and
sensors.
Ensure to clean the area properly for
stone and sharp edges.
Protect the heating cables against
excessive use of rakes, shovels,
vibrators and rollers.
Remember that the cable always shall
be fully embedded to avoid air gaps.
For second layer of asphalt should be
used drum/roller with the maximum
limited load of 500 kg.
It is not allowed to drive directly
on the cables with heavy trucks
or asphalt machinery, as the cable
construction only is developed for a
maximum mechanical load of 2000 N.
It will immediately lead to cable
damages.
5.3.1 Important
All electrical connections must
be done by authorized persons
according to local regulations.
Installation in Mastic Asphalt
Only use DEVIasphalt™ fully
embedded.
Mastic asphalt shall be cooled down
to max. 240 °C
Installation in Road/concrete
asphalt
First layer – 3 cm hand rolled asphalt
concrete (max. 8 mm stone size),
cooled down to max. 80 °C before
(no vibrator).
Apply second layer with a max. 500 kg
drum size (no vibrator).
When extending cold lead,
observe:
• That there is max. 5% loss of
potential power in the whole
length of the cold cable.
Do not tip the wheel barrow by
supporting it directly on the cables.
Fasten the cables to the sub
construction in short distances to
ensure that the cable remains in right
position.
It is recommended to connect a
buzzer or other alarm giving device
to the cables if an incident anyway
should occur during installation
despite all caution and a cable is
being damaged. Then there will be
the ability to quickly detect this and
get the problem solved at the lowest
possible cost and delay.
Ensure that all cables turn towards
the electrical cupboards where the
cables shall be connected.
Pour the asphalt at a moderate
delivery speed to avoid displacement
of the heating cable.
• That the leak current of the whole
installation is less than 1/3 of the
RCD trigger level.
Thermostat controlling ground
temperature is mandatory.