Danfoss AB-QM DN 40-100 User Manual

Installation Guide
AB-QM DN 40-100
DN 40/50 DN 50 DN 65-100
Installation / Montering / Einbau / Installation /Installatie / Installation / Asennus / Montaż / Uzstādīšana / Beépítés / Montaj / Монтаж / Instalace / 安装 / Vgradnja / Instalación / Montavimas
AME 435 QM
IP 54
DN 40/50 DN 50 DN 65-100
AME 435 QM
Code No.: 003Z0695
Heating Solutions VI.A7.E2.3T SMT/SI
1
Installation Guide AB-QM DN 40-100
Shut off / Afspærring / Absperrung / Fermeture / Afsluiten / Avstängning / Sulkuventtiili / Funkcja odcięcia / Aizvēršana / Elzárás / KAPAMA / Отключение /Uzavření / 关闭 / Zapiranje pretoka / Corte / Uždarymas
DN 40, DN 50
Δp max = 16 bar
3 Nm
Setting / Indstilling / Einstellung / Réglage / Instelling / Inställning / Asettelu / Wykonywanie nastawy / Iestādījumi / Beállítás / Ayarlama / Настройка / Nastavení / 设定 / Nastavitev / Ajuste / Nustatymas
Note: best before applying pressure
DN 40/50
DN 65-100
Δp max = 16 bar
12 Nm
8 mm
DN 65-100
Resetting
DN 40-10 0
max 1 turn
3 mm
50 mm
Max. 25 Nm 1 turn = 10%
42 mm
Max. 25 Nm 1 turn = 10%
Max. 25 Nm 1 turn = 10%
3 mm
SMT/SI VI.A7.E2.3T Heating Solutions
2
Installation Guide AB-QM DN 40-100
Locking / Låsning / Blockierung / Verrouillage / Vergrendelen / Låsning / Lukitseminen / Blokowanie nastawy / Noslēgšana / Korlátozás / Kilitle / Блокировка / Uzamykání / 锁定 / Blokiranje / Bloqueo / Blokavimas
DN 40/50
3 mm
DN 65-100
3 mm
Measuring / Måling / Messung / Mesure / Meten / Mätning / Mittaaminen / Wykonywanie pomiarów / Mērīšana / Mérés / Ölçüm / Измерение / Měření / 测量 / Merjenje / Medida / Matavimas
P1 - P3
P1
P1-P3
DN 40/50
Q
Q ≠ const
P3P1
P3
DN 65-100
Pump optimization
30 kPa
Q = const
P1 - P3
Heating Solutions VI.A7.E2.3T SMT/SI
3
Installation Guide AB-QM DN 40-100
–10…120 °C
DN 40 L/h L/s GPM
20% 1500 0,416 6,6 25% 1875 0,520 8,3 30% 2250 0,625 9,9 35% 2625 0,729 11,6 40% 3000 0,833 13,2 45% 3375 0,937 14,9 50% 3750 1,041 16,5 55% 4125 1,145 18,2 60% 4500 1,250 19,8 65% 4875 1,354 21,5 70% 5250 1,458 23,1 75% 5625 1,562 24,8 80% 6000 1,666 26,4 85% 6375 1,770 28,1 90% 6750 1,875 29,7 95% 7125 1,979 31,4
100% 7500 2,083 33,0
Note: 1 turn = 10%
DN 80 L/h L/s GPM
40% 11200 3,11 49,3 45% 12600 3,50 55,5 50% 14000 3,89 61,6 55% 15400 4,23 67,8 60% 16800 4,67 74,0 65% 18200 5,10 80,1 70% 19600 5,44 86,3 75% 21000 5,83 92,5 80% 22400 6,22 98,6 85% 23800 6,61 104,8 90% 25200 7,00 111,0 95% 26600 7,39 117,1
100% 28000 7,78 123,3
Note: 1 turn = 10%
PN 16
DN 50 L/h L/s GPM
40% 5000 1,386 22,0 45% 5625 1,562 24,8 50% 6250 1,736 27,5 55% 6875 1,909 30,3 60% 7500 2,083 33,0 65% 8125 2,256 35,8 70% 8750 2,430 38,50 75% 9375 2,604 41,3 80% 10000 2,777 44,0 85% 10625 2,951 46,8 90% 11250 3,125 49,5 95% 11875 3,298 52,3
100% 12500 3,472 55,0
Note: 1 turn = 10%
DN 100 L/h L/s GPM
40% 15200 4,22 66,9 45% 17100 4,75 75,3 50% 19000 5,28 83,7 55% 20900 5,81 92,0 60% 22800 6,33 100,4 65% 24700 6,86 108,8 70% 26600 7,39 117,1 75% 28500 7,92 125,5 80% 30400 8,44 133,8 85% 32300 8,97 142,2 90% 34200 9,50 150,6 95% 36100 10,03 158,9
100% 38000 10,56 167,3
Note: 1 turn = 10%
Δp
= 400 kPa (4 bar)
max.
DN 65 L/h L/s GPM
40% 8000 2,22 35,2 45% 9000 2,50 39,6 50% 10000 2,78 44,0 55% 11000 3,06 48,4 60% 12000 3,33 52,8 65% 13000 3,61 57,2 70% 14000 3,89 61,6 75% 15000 4,17 66,0 80% 16000 4,44 70,4 85% 17000 4,72 74,9 90% 18000 5,00 79,3 95% 19000 5,28 83,7
100% 20000 5,56 88,1
Note: 1 turn = 10%
73693790/VI.A7.E2.3T
Produced by Danfoss A/S © 07/2013