Danfoss AB-PM Installation guide

Installation Guide/Guide d’installation
AB-PM Rack set / AB-PM kit CIC (DN15-20)
Manual Shut-off-plastic / Fermeture vanne
∆p max = 1 bar
0%
Application / ApplicationConfiguration / Configuration
Filter / Filtre
Clockwise: Close Sens horaire : Fermeture Counter-Clockwise: Open Sens anti-horaire : Ouverture
Setting / Réglage
DN 15 L/h
20% 60 30% 90 40% 120 50% 150 60% 180 70% 210 80% 240 90% 270
100% 300
DN 20 L/h
20% 120 30% 180 40% 240 50% 300 60% 360 70% 420 80% 480 90% 540
100% 600
© Danfoss | 2016.12
VIHRB102 | 1
Danf already on order pro All trademarks in this material are property of the respec
AB-PM Rack set/AB-PM kit CIC (DN15-20)
Mounting actuator / Montage de l'actionneur
Mounting heatmeter / Montage du compteur d’énergie
TWA-Z
IP 41
TWA-Z
Remove the red tab.
Red tab serves to keep the valve open during filling.
Enlever la languette rouge.
Cette languette sert a maintenir la vanne ouverte lors du remplissage.
Temperature sensor Sonde température
Electrical connection / Raccordement électrique
TP5001 M TPOne TWA-Z / ABN A5
N L 1 2 3 N L COM NC1 NO1
230 V AC
50/60 Hz
RA-N flow setting / RA-N réglage débit
OK
230 V AC
50/60 Hz
Setting / Réglage Flow / Débit Heat W / Puissance W
DN 15 L/h ΔT 15 K ΔT 20 K
1 9 150 200 2 18 310 420 3 27 470 620 4 44 770 1000 5 67 1150 1550 6 89 1550 2050 7 115 2000 2650 N 165 2900 3800
230 V NC
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessary eady agreed.
2 | © Danfoss | DHS-SRMT/SI | 2016.12
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
/ VIHRB102