Installation guide
Solenoid coil
Type AB, AM, AC, AK, AL, AP, BB, BA, BC and BD
A B
A - Coils B - Coils
042R9019
A2
IP00/PD3
Spade
A1 A2 B1 B3B2
1 2
Type of contro l 1
Class of pro tection Class I
Ambient temperature See T
Voltage variation
Voltage tolerances
Humidity
Ball pres sure test 200 °C (392 °F) i n accordance to IEC 60 695-10-2
Impulse withstand voltage
Overvoltage category
Degree o f protection IP xx
Pollution degree PDX
Installation
Suitable cable,
Conductor size for plug
Suitable cable for cable plug See datasheet when ordering the coil
Cable conductor size 3 x 0.75 mm² (3 x 0.001 in2)
Plugs can b e removed/mounte d 10 times
Surface temperature
- Only qual ified personn el is allowed to inst all or maintain this p roduct
- Disconnect the power when dismounting the coil
- Avoid direc t exposure to alk aline condition s, use in neutral con ditions is recomm ended
- Ensure that t he O-ring is in pl ace on the valve
- If the coil is u sed as independ ently mounted cont rol, the end-us er shall use a plast ic cable gland wit h strain relief
Імпортер:ТОВ з іі “Данфосс ТОВ” 04080, Київ 80, п/с 168, Україна
© Danfoss | Climate Solutions | 2021.12
A1
+ / = IP65/PD3
Cable plug
IP00/PD3
Spade
3 4
on coil
ambient
For volta ge variation, se e print on coil
For voltage tolerances see datasheet, when ordering the coil
Only non e-conduct ive pollution occ urs except that occ asionally a tempo rary conduc tivity caused b y
condensation is to be expected.
Spade
Plug
Plug
III
Enclosur e rating according to I EC standard 60529 (Se e illustration fo r details A-B)
Pollutio n degree accordin g to EN60664-1 (See i llustration fo r details A-B)
Integrated control
Incorporated control
Independently mounted control (IP65/IP67)
ø6.6 − ø11 mm (ø0.26 − ø0 .43 in)
0.75 − 1.5 mm ² (21 − 15 AWG flexible cord )
Indepe ndently mounted c ontrols must be ina ccessible in norm al use if the surfa ce temperature on t he control > 85°C
4.0 kV at alt itude <4000 m (13123 ft)
4.0 kV at alt itude <2000 m (6561 ft)
3.1 kV 2000 m<alt itude<4000 m (6561<altitude <13123 ft)
AN353730866505en-000301| 1
B2
B1
+ / = IP65/PD3
B3
+ = IP67/PD4
Cable plug
042R9019
Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
5
6
7 8
40 - 50 Ncm
(0.30 − 0.39 lb-ft)
90°
9
250 - 375 Ncm
(1.85 − 2.77 lb-ft)
A2
B2
10
11-A2
11-B2
50 - 60 Ncm
(0.39 − 0.44 lb-ft)
1.25 ± 0.15 Nm
(0.92 ± 0.11 Ib-ft)
1.0 ± 0,15 Nm
(0.74 ± 0.11 Ib-ft)
A1
B1
B3
11-A1
11-B1
11-B3
1.25 ± 0.15 Nm
(0.92 ± 0.11 Ib-ft)
0.7 ± 0.1 Nm
(0.52 ± 0.07 Ib-ft)
1.5 ± 0.15 Nm
(1.11 ± 0.11 Ib-ft)
Visit www.products.danfoss.com for fur ther technical data
Para más información, visite www.products.danfoss.es
Rendez-vous sur le site w ww.products.danfoss.fr pour plus de données techniques
© Danfoss | Climate Solutions | 2021.12