VLT® Advanced Active Filter AAF 006
A exible and adaptable solution for central or de-central harmonic mitigation.
E-frame
Danfoss Advanced Active Filters can
compensate for individual VLT® drives
or can be installed as a compact
stand-alone solution at a common
point of coupling, compensating for
several loads simultaneously.
Consequently the lter ensures optimal harmonic suppression independent of the number of loads and their
individual load prole. In addition the
active lter corrects the power factor
and balances the phase load providing an optimal energy utilization.
This improves the system eciency
and increases the grid robustness to
avoid downtime.
The extensive re-use of proven VLT®
components and the modular construction ensures a high reliability and
at the same time oers high energy
eciency, back-channel cooling and
high enclosure grades without size
encrease.
The VLT® Advanced Active Filter is
easily controlled via the user-friendly
LCP, sharing design and programming
structure with the VLT® drives series.
Without dismounting existing installation, the VLT® Advanced Active
Filters are easily retrotted to the
existing installation, where harmonics
are increased because of enlarged
employment of non-linear loads such
as variable speed drives.
Voltage range
380 – 480 V AC 50 – 60 Hz
Current range
190 A, 250 A, 310 A, 400 A.
Up to 4 units can be paralleled
for higher power.
Enclosure degree
IP 21/NEMA Type 1
IP 54/NEMA Type 12
Perfect
match for:
– Industrial
automation
– High dynamic
applications
– Safety installations
Feature Benet
Reliable Maximum uptime
– 100% factory tested
– Coated PCBs
– >90% components re-used from
proven VLT® FC series
– Innovative cooling concept – Prolonged lifetime of electronics
User-friendly and exible Saves commissioning and operating cost
– Innovative programming possibilities – Low running expenses
– Modular design – Easy serviceability
– Wide range of options
Energy saving Lower operation costs
– High eciency
– Sleep mode and progressive switching freq.
– Power factor correction
– Low failure rate
Low initial investment
–
– High degree of customisation
– Low running expenses
Facts about our products
Options
The following options are available:
n RFI lters
n Disconnect
n Fuses
n Mains shielding
PC software
VLT® MCT 10 Setup Software
VLT® MCT 10 oers advanced programming functionality for all
Danfoss drive products, greatly
reducing programming and set-up
time.
VLT® MCT 10 Basic (available free of
charge from www.danfoss.com)
allows access to a nite number of
drives with limited functionality.
The advanced edition, oering a
higher level of functionality, is
available from your Danfoss sales
partner.
Specications
THiD* at:
– 40% load
– 70% load
– 100% load
Eciency* at:
– 40% load
– 70% load
– 100% load
True power factor* at:
– 40% load
– 70% load
– 100% load
Ambient temperature 45° C
Cooling Back-channel air cooling
* Measured at balanced grid without pre-distor tion and with VLT® drive matching full load demand
Norms and recommendations Compliance
IEEE519 Application and load dependent
IEC61000-3-2 (up to 16 A) Out of scope
IEC61000-3-12 (between 16 and 75 A) Out of scope
IEC61000-3-4 (above 75 A) Out of scope
< 7%
< 5.5%
< 5%
> 95%
> 98%
> 98%
> 0.98
> 0.98
> 0.98
E1D14
VLT® MCT 31 Harmonics
Calculation Software
With VLT® MCT 31, you can determine
whether harmonics will be an issue in
your installation when drives are
added.
VLT® MCT 31 estimates the benets of
adding various harmonic mitigation
solutions from the Danfoss product
portfolio and calculates system
harmonic distortion. Furthermore the
software provides quick indication of
whether the installation complies
with the most recognised harmonic
norms and recommendations.
From www.danfoss.com you can
download the free tool VLT® Harmonic Calculation MCT 31 – the most
up-to-date version of the calculation
software.
400 V AC (380 – 480 V AC)
Total
Current
[A]
190 190 170 D14
250 250 225
310 310 280
400 400 360
Total
Current
[A]
190 119 85 55 48 34 31 27 24
250 158 113 72 63 45 40 36 32
310 196 140 90 78 56 50 45 40
400 252 180 115 100 72 65 58 50
Max.
Reactive
[A]
I
5
Max.
Harmonic
[A]
I
7
Frame
E1
Max. individual harmonic compensation
I
11
I
13
Dimensions
mm [Inches]
1740 x 600 x 380
[68.2 x 33.5 x 15.0]
2000 x 600 x 500
[78.7 x 33.5 x 19.4]
[A]
I
H x W x D
17
Weight
Kg [Lbs]
283
[623]
476
[1047]
498
[1096]
I
19
I
23
I
25
Danfoss VLT Drives, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80
www.danfoss.com/drives • E-mail: info@danfoss.com
DKDD.PFP.650.A2.02 VLT® is a trademark of Danfoss A/S Produced by PE-MMSC 2014.09