Danfoss A390 Operating guide

OperatingGuide
ECLComfort310,applicationA390

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................14
2.4Placingthetemperaturesensors................................20
2.5Electricalconnections.............................................22
2.6InsertingtheECLApplicationKey..............................32
2.7Checklist............................................................39
2.8Navigation,ECLApplicationKeyA390.........................40
3.0Dailyuse.........................................................47
3.1Howtonavigate...................................................47
3.2Understandingthecontrollerdisplay..........................48
3.3Ageneraloverview:Whatdothesymbolsmean?...........51
3.4Monitoringtemperaturesandsystem
components........................................................52
3.5Influenceoverview................................................53
3.6Manualcontrol.....................................................54
3.7Schedule............................................................55
4.0Settingsoverview............................................56
5.0Settings...........................................................59
5.1IntroductiontoSettings..........................................59
5.2Flowtemperature..................................................60
5.3Roomlimit..........................................................64
5.5Compensation1...................................................74
5.6Compensation2...................................................76
5.7Flow/powerlimit.................................................78
5.8Optimization........................................................82
5.9Controlparameters................................................88
5.10Application.........................................................93
5.11Heatcut-out......................................................105
5.12Tanktemperature................................................108
5.13Anti-bacteria......................................................113
5.14Alarm..............................................................115
5.15Alarmoverview..................................................118
6.0Commoncontrollersettings............................119
6.1Introductionto‘Commoncontrollersettings’..............119
6.2Time&Date.......................................................120
6.3Holiday............................................................121
6.4Inputoverview...................................................123
6.5Log.................................................................124
6.6Outputoverride..................................................125
6.7Keyfunctions.....................................................126
6.8System.............................................................128
7.0Miscellaneous................................................135
7.1ECA30/31setupprocedures.................................135
7.2Overridefunction................................................144
7.3Severalcontrollersinthesamesystem......................147
7.4Frequentlyaskedquestions....................................151
7.5Definitions........................................................154
7.6Type(ID6001),overview.......................................158
7.7Automatic/manualupdateoffirmware.....................159
7.8ParameterIDoverview..........................................160
©Danfoss|2021.06AQ128686479024en-010601|1
OperatingGuideECLComfort310,applicationA390

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA390 (ordercodeno.087H3815).
TheECLApplicationkeyA390contains6subtypes,whichare:
A390.1:3heatingcircuits,3-pointcontrolofcontrolvalves
A390.2:3heatingcircuits,analogcontrolofcontrolvalves
A390.3:3coolingcircuits,3-point/analogcontrolofcontrol valves
A390.11:1xheating/DHWcircuit,2heatingcircuits;3-point/ analogcontrolofcontrolvalves
A390.12:1xheating/DHWchargingcircuit,2heatingcircuits; 3-point/analogcontrolofcontrolvalves
A390.13:1xDHWchargingcircuit,2heatingcircuits;3-point/ analogcontrolofcontrolvalves
TheA390applicationkeyalsocontainsaFloor(Screed)Drying Program.Seeseparatedocumentation(InEnglishandGerman languageonly).
SeetheInstallationGuideforelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310for advancedsolutions,e.g.M-bus,ModbusandEthernet(Internet) communication.
TheapplicationkeyA390complieswithECLComfortcontrollers 310asofsoftware(firmware)version1.11(visibleatstart-upofthe controllerandin‘Commoncontrollersettings’in‘System’).
UptotwoRemoteControlUnits,ECA30orECA31,canbe connectedandthebuilt-inroomtemperaturesensorcanbe utilized.
ThesubtypesA390.2,A390.3,A390.11,A390.12andA390.13can workwiththeInternalI/OmoduleECA32for0–10Voltcontrolof actuatorsandP7control. ECA32isplacedinthebasepartforECLComfort310.
TogetherwiththeECLComfort310theadditionalInternalI/O modulecanalsobeusedforextradatacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool". Navigation:Danfoss.com>Products&Solutions>Products> DistrictHeatingandCooling>Documentation>Tools&Software >ECLTool.
TheURLis: https://www.danfoss.com/en/service-and-support/downloads
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
TheB-typehasnodisplayanddial.TheB-typeisoperatedby meansoftheremotecontrolunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
InternalI/Omodule:
ECA32(087H3202)
ThebasepartforECLComfort310,230voltand24volt:
087H3230
AdditionaldocumentationforECLComfort310,modulesand accessoriesisavailableonhttp://danfoss.com/.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AQ128686479024en-010601
©Danfoss|2021.06|3
OperatingGuideECLComfort310,applicationA390
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
1
-
Circuit1Parameterno.
2
Circuit2Parameterno.
174
4|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
AQ128686479024en-010601
©Danfoss|2021.06|5
OperatingGuideECLComfort310,applicationA390

2.0Installation

2.1Beforeyoustart

TheECLapplicationkeyA390contains6subtypes:A390.1,A390.2, A390.3,A390.11,A390.12andA390.13.The6differentapplications areheating,coolingandDHWapplicationsinvariouscombinations.
TheheatingbasedapplicationsA390.1,A390.2,A390.11,
A390.12andA390.13areveryflexible.
Thebasicprinciplesforaheatingcircuit
(examplereferringtoA390.1,circuit1)
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.Theflowtemperaturesensor(S3)isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredroomtemperature). InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M1)isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperaturedoesnotequalthedesired roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Thecirculationpump,P1,isONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
AconnectedfloworenergymeterbasedonM-bussignalcan limitthefloworenergytoasetmaximumvalue.Furthermorethe limitationcanbeinrelationtotheoutdoortemperature.Typically, thelowertheoutdoortemperature,thehighertheacceptedflow/ power.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
TypicalA390.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
P1
P2
P3
M1
M2
M3
A1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
(Optional)Roomtemperaturesensor,circuit1
Flowtemperaturesensor,circuit1
Flowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)Returntemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit3
(Optional)Roomtemperaturesensor,circuit2
Flowtemperaturesensor,circuit3
(Optional)Roomtemperaturesensor,circuit3
Circulationpump,heating,circuit1
Circulationpump,heating,circuit2
Circulationpump,heating,circuit3
Motorizedcontrolvalve(3-pointcontrolled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
Motorizedcontrolvalve(3-pointcontrolled),circuit2 Alternative:Thermoactuator(DanfosstypeABV)
Motorizedcontrolvalve(3-pointcontrolled),circuit3 Alternative:Thermoactuator(DanfosstypeABV)
Alarm
6|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
A390.1,A390.2,A390.3,A390.11andA390.12:
Circuit1canactasmasterandtheremainingcircuitscanactas slaves.
A390.2:
ThemotorizedcontrolvalvesM1,M2andM3arecontrolledby meansof0-10voltsignals.Thecontrolsignalscomefromthe internalI/OextensionmoduleECA32.The3-pointoutputsinthe ECL310aredisabled.
A390.3,A390.11,A390.12,A390.13
ThemotorizedcontrolvalvesM1,M2andM3arecontrolledby meansofeither3-pointor0-10voltsignals.Bothtypesofoutputs areactive.The0–10VoltsignalscomefromtheinternalI/O extensionmoduleECA32.
A390.11andA390.13:
Eachoftheheatingcircuitscanbesettoutilizetheroom temperaturesensorS7. Ifthereisademandfortwoseparateroomtemperaturesensors, S7canbeusedforoneoftheheatingcircuitsandECA30forthe otherheatingcircuit.
A390.11,A390.12andA390.13:
TheheatingcircuitscanbeclosedduringDHWheating(priority).
A390.13:
DHWheatinghaspriority.
A390.1,A390.2,A390.11,A390.12andA390.13:
AlarmA1(=relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature.
Ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview).
Heatingrelatedcircuits,ingeneral:
Exerciseofcirculationpumpsandcontrolvalvesinperiodswithout heatingdemandcanbearranged.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
AconnectedfloworenergymeterbasedonM-bussignalcan limitthefloworpowertoasetmaximumvalue.Furthermore,the limitationcanbeinrelationtotheoutdoortemperature.Typically, thelowertheoutdoortemperature,thehighertheacceptedflow/ power. M-busdatacanbetransferredtotheModbuscommunication.
A390,ingeneral:
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL 485businordertoutilizecommonoutdoortemperaturesignal, timeanddatesignals. TheECLcontrollersintheECL485systemcanworkinmaster­slavesystem.
Unusedinputscan,bymeansofanoverrideswitchorrelaycontact, beusedforoverridingthescheduletoafixed'Comfort' ,'Saving', 'Frostprotection'or'Constanttemperature'mode.
TypicalA390.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
S1
S2
S3
S4
S5
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
(Optional)Roomtemperaturesensor,circuit1
Flowtemperaturesensor,circuit1
Flowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor, circuit1
S6
(Optional)Returntemperaturesensor, circuit2
S7
(Optional)Returntemperaturesensor, circuit3
S8
S9
S10
P1
P2
P3
M1
(Optional)Roomtemperaturesensor,circuit2
Flowtemperaturesensor,circuit3
(Optional)Roomtemperaturesensor,circuit3
Circulationpump,circuit1
Circulationpump,circuit2
Circulationpump,circuit3
Motorizedcontrolvalve(0-10voltcontrolled), circuit1
M2
Motorizedcontrolvalve(0-10voltcontrolled), circuit2
M3
Motorizedcontrolvalve(0-10voltcontrolled), circuit3
AQ128686479024en-010601
©Danfoss|2021.06|7
OperatingGuideECLComfort310,applicationA390
ThecoolingapplicationA390.3isveryflexible.
Thebasicprinciplesforacoolingcircuit
(examplereferringtoA390.3,circuit1)
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3issetin theECLcontroller.Furthermore,theoutdoortemperatureS1can influencethedesiredflowtemperature.Thehighertheoutdoor temperature,thelowerthedesiredflowtemperature.
Bymeansoftheweekschedule,thecoolingcircuitcanbein ‘Comfort’or‘Saving’mode(twovaluesforthedesiredflow temperature).
Theweekschedulealsocontrolstwovalues(‘Comfort’and ‘Saving’)forthedesiredroomtemperature.Ifthemeasuredroom temperaturedoesnotequalthedesiredroomtemperature,the desiredflowtemperaturecanbeadjusted.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe flowtemperatureishigherthanthedesiredflowtemperatureand viceversa. ThereturntemperatureS5tothecoolingsupplyshouldnotbetoo low.Ifso,thedesiredflowtemperaturecanbeadjusted(typicallyto ahighervalue),thusresultinginagradualclosingofthemotorized controlvalve.
ThecirculationpumpP1isONatcoolingdemand.
Aconnectedfloworenergymeter(M-bus)canlimittheflowor energytoasetmaximumvalue.
Thestandbymodemaintainsaselectableflowtemperature,for example30°C.
TypicalA390.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310 ECA32 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 P1 P2 P3 M1
ElectroniccontrollerECLComfort310 (notillustrated)*) Outdoortemperaturesensor (Optional)Roomtemperaturesensor,circuit1 Flowtemperaturesensor,circuit1 Flowtemperaturesensor,circuit2 (Optional)Returntemperaturesensor,circuit1 (Optional)Returntemperaturesensor,circuit2 (Optional)Returntemperaturesensor,circuit3 (Optional)Roomtemperaturesensor,circuit2 Flowtemperaturesensor,circuit3 (Optional)Roomtemperaturesensor,circuit3 Circulationpump,circuit1 Circulationpump,circuit2 Circulationpump,circuit3 Motorizedcontrolvalve(3-pointand/or0-10Volt
controlled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointand/or0-10Volt controlled),circuit2 Alternative:Thermoactuator(DanfosstypeABV)
M3
Motorizedcontrolvalve(3-pointand/or0-10Volt controlled),circuit3 Alternative:Thermoactuator(DanfosstypeABV)
X4
*)
Extraoutput(Schedule4) Usedfor0-10Voltcontrolofmotorizedcontrolvalve.
8|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
ThebasicprinciplesforaDomesticHotWatercircuit(DHW)
(examplereferringtoA390.11,circuit4)
Bymeansofaweekschedule(upto3'Comfort'periods/day),the DHWcircuitcanbein'Comfort'or'Saving'mode(twodifferent temperaturevaluesforthedesiredDHWtemperatureatS6).
TheDHWheatingtemperaturesensorS3isthemostimportant sensor.IfthemeasuredDHWtemperature(S6)getslowerthanthe desiredDHWtemperature,theDHWheatingpump(P4)isswitched ONandtheheatingcirculationpumpP1isswitchedOFF.
ThemotorizedcontrolvalveM1iscontrolledinordertomaintain theDHWheatingtemperatureatS3.
TheDHWheatingtemperatureisdeterminedbythedesiredDHW temperatureatS6plusthechargingdifference.
TheDHWchargingpumpP7canbeswitchedONdependingon1) theDHWheatingtemperatureisreached,or2)adelay.
TheDHWheatingtemperatureatS3istypically5–10degrees higherthanthedesiredDHWtemperature.
DHWtankwith1temperaturesensor(S6):
WhenthemeasuredDHWtemperature(S6)getshigherthanthe desiredDHWtemperature,theDHWheatingpump(P4)andthe DHWchargingpump(P7)areswitchedOFF.Thepost-runtimecan besetindividually.
TypicalA390.11application:(upto3xheating,1xDHW)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem. AllnamedcomponentsareconnectedtotheECLComfortcontroller.
DHWtankwith2temperaturesensors(S6,upperandS8, lower):
WhenthemeasuredDHWtemperature(S6)getshigherthanthe desiredDHWtemperatureandthetemperatureatS8getshigher thanthecut-outtemperature,theDHWheatingpump(P4)and theDHWchargingpump(P7)areswitchedOFF.Thepost-runtime canbesetindividually.
Thereturntemperature(S5)canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingofthe motorizedcontrolvalve. Aflow/powerlimitationcanbearrangedbyusinganM-busbased signalfromaflow/heatmeter.
A390.12:
TheDHWheatingcircuithasapreheatingcircuit,wheretheDHW heatingtemperatureatS9isadaptedtothedesiredDHWcharging temperatureatS7.IftheDHWchargingtemperatureatS7cannot bereached,theECLcontrollergraduallyincreasesthedesiredDHW heatingtemperatureatS9inordertoobtaintheDHWcharging temperature.Amaximumtemperaturevaluecanbeset.
A390.12:
TheDHWcirculationcanbethroughtheDHWtank(connectionA) orthroughtheheat-exchanger(connectionB).Thesolutionwith connectionAresultsinclosingofthemotorizedcontrolvalveafter theDHWtankchargingprocedure.Thesolutionwithconnection BisusedtocompensatefortheheatlossintheDHWcirculation pipe.Furthermore,afterDHWtankcharging,theDHWheating temperature(atS7)iscontrolledaccordingtothedesiredDHW temperature.
Listofcomponents:
ECL310 ECA32 S1 S2 S3 S4 S5 S6 S7 S8
ElectroniccontrollerECLComfort310 Built-inextensionmodule*) Outdoortemperaturesensor (Optional)Returntemperaturesensor,circuit2 Flowtemperaturesensor,circuit1 Flowtemperaturesensor,circuit2 (Optional)Returntemperaturesensor,circuit1 DHWtanktemperaturesensor,upper,circuit4 (Optional)Roomtemperaturesensor,circuit1/2/3 (Optional)DHWtanktemperaturesensor,lower,
circuit4 S9 S10 P1 P2 P3 P4 P5 P7 M1
Flowtemperaturesensor,circuit3
(Optional)Returntemperaturesensor,circuit3
Circulationpump,circuit1
Circulationpump,circuit2
DHWcirculationpump,circuit4
DHWheatingpump,circuit4
Circulationpump,circuit3
DHWchargingpump,circuit4
Motorizedcontrolvalve(3-pointand/or0-10Volt
controlled),circuit1
Alternative:Thermoactuator(DanfosstypeABV) M2
Motorizedcontrolvalve(3-pointand/or0-10Volt
controlled),circuit2
Alternative:Thermoactuator(DanfosstypeABV) M3
Motorizedcontrolvalve(3-pointand/or0-10Volt
controlled),circuit3
Alternative:Thermoactuator(DanfosstypeABV) A1 *)
Alarm
Alsousedfor0-10Voltcontrolofmotorizedcontrol
valve.
AQ128686479024en-010601
©Danfoss|2021.06|9
OperatingGuideECLComfort310,applicationA390
A390.13:
TheDHWheatinghaspriorityovertheheatingcircuits. TheDHWcircuitisconsideredasthemastercircuitwhilethe heatingcircuitsareslaves. TemperaturesensorS9isthemostimportantsensor. TheDHWcirculationcanbethroughtheDHWtank(connectionA) orthroughtheheat-exchanger(connectionB).
Generalinformation:
The‘Frostprotection’modemaintainsaselectabletemperature, forexample10°C. Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek. Theoutdoortemperature(S1)isusedtoprotectthecirculation circuitagainstfrost. TheDHWcirculationpump(P3)hasaweekscheduleforupto3 ONperiodsperday.
Ameasuredtemperaturecanbeoffsetadjusted,ifneeded.
WhenanA390subtypehasbeenuploaded,theECLComfort controllerstartsinmanualmode.Thiscanbeusedforcheckingthe controlledcomponentsforcorrectfunctionality.
Theapplicationkeymustbeinsertedinordertochangesettings.
10|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
TypicalA390.12application:
(upto2xheating,1xDHW)
TypicalA390.12application:(upto2xheating,1xDHW)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem. AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
S1
S2
S3
S4
S5
S6
S7
S8
ElectroniccontrollerECLComfort310
(notillustrated)*)
Outdoortemperaturesensor
(Optional)Returntemperaturesensor,circuit2
Flowtemperaturesensor,circuit1
Flowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
DHWtanktemperaturesensor,upper,circuit3
DHWchargingtemperaturesensor,circuit3
(Optional)DHWtanktemperaturesensor,lower,
circuit3 S9
S10
P1
P2
P3
P4
P5
M1
DHWheatingtemperaturesensor,circuit3
(Optional)Returntemperaturesensor,circuit3
DHWheatingpump,circuit3
Circulationpump,circuit1
DHWcirculationpump,circuit3
DHWchargingpump,circuit3
Circulationpump,circuit2
Motorizedcontrolvalve(3-pointand/or0-10Volt
controlled),circuit3 M2
Motorizedcontrolvalve(3-pointand/or0-10Volt
controlled),circuit1
Alternative:Thermoactuator(DanfosstypeABV) M3
Motorizedcontrolvalve(3-pointand/or0-10Volt
controlled),circuit2
Alternative:Thermoactuator(DanfosstypeABV) A1
A/B
*)
Alarm
Internal/externalconnectionsforDHWcirculation
Usedfor0-10Voltcontrolofmotorizedcontrolvalve.
AQ128686479024en-010601
©Danfoss|2021.06|11
OperatingGuideECLComfort310,applicationA390
TypicalA390.13application:
(1xDHW,upto2xheating)
TypicalA390.13application:(1xDHW,upto2xheating)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem. AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
S1
S2
S3
S4
S5
S6
S7
S8
ElectroniccontrollerECLComfort310
(notillustrated)*)
Outdoortemperaturesensor
(Optional)Returntemperaturesensor,circuit2
Flowtemperaturesensor,circuit1
Flowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
DHWtanktemperaturesensor,upper,circuit3
(Optional)Roomtemperaturesensor,circuit1/2
(Optional)DHWtanktemperaturesensor,lower, circuit3
S9
S10
P1
P2
P3
P4
P5
M1
DHWheatingtemperaturesensor,circuit3
(Optional)Returntemperaturesensor,circuit3
DHWheatingpump,circuit3
Circulationpump,circuit1
DHWcirculationpump,circuit3
DHWchargingpump,circuit3
Circulationpump,circuit2
Motorizedcontrolvalve(3-pointand/or0-10Volt controlled),circuit3
M2
Motorizedcontrolvalve(3-pointand/or0-10Volt controlled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
M3
Motorizedcontrolvalve(3-pointand/or0-10Volt controlled),circuit2 Alternative:Thermoactuator(DanfosstypeABV)
A1
A/B
*)
Alarm
Internal/externalconnectionsforDHWcirculation
Usedfor0-10Voltcontrolofmotorizedcontrolvalve.
12|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
AQ128686479024en-010601
©Danfoss|2021.06|13
OperatingGuideECLComfort310,applicationA390

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
14|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Adviceforsettings:
Factorysettingsinthesubtypeswillrunthemostapplication examples.Someoftheapplicationexamplesneedchangeof dedicatedsettings.
SeetheInstallationGuideforapplicationsandsubtypes,delivered withtheapplicationkey.
A390.1,ex.c A390.11,ex.d
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2 and/or3.
Issue:
Heatingcircuit(1):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit2and/ or3.
Circuit2and/or3mustbeabletosendtheheatdemandtocircuit
1.
Issue:
Heatingcircuit(2/3):
Heatdemand
A390.3,ex.b
Circuit1mustbeabletoreceivethecooldemandfromcircuit2 and/or3.
Issue:
Coolingcircuit(1):
Cooldemand
Navigation:
MENU\Settings\Application: 'Demandoffset'
Navigation:
MENU\Settings\Application: 'SenddesiredT'
Navigation:
MENU\Settings\Application: 'Demandoffset'
IDno.:
11017
IDno.:
12500 13500
IDno.:
11017
Recommended setting:
3K*
Recommended setting:
ON ON
Recommended setting:
-3K*
Thisvalueisaddedtothecooldemandvaluefromcircuit2and/ or3.
Circuit2and/or3mustbeabletosendthecooldemandtocircuit
1.
Issue:
Coolingcircuit(2/3):
Cooldemand
AQ128686479024en-010601
Navigation:
MENU\Settings\Application: 'SenddesiredT'
IDno.:
12500 13500
Recommended setting:
ON ON
©Danfoss|2021.06|15
OperatingGuideECLComfort310,applicationA390
Adviceforsettings:
A390.11,ex.c
Onepumpandchange-overvalvesystem:
Issue:
DHWcircuit(4):
Change-overvalve
A390.11,ex.e
DHWheatingconnectedprimarily:
Issue:
DHWcircuit(4):
Change-overvalve
DHWcircuit(4):
Tankprimarily
A390.12,ex.a A390.12,ex.b A390.13,ex.a
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(3):
InternalDHWcirculation
DHWcircuit(3):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application: 'Ch.-o.valve/P'
Navigation:
MENU\Settings\Application: 'Ch.-o.valve/P'
MENU\Settings\Application: 'Tank,sec./prim'
Navigation:
MENU\Settings\Application: 'Cont.Tcontrol'
MENU\Settings\Application: 'Cont.Tcontrol'
IDno.:
14051
IDno.:
14051
14053
IDno.:
13054
13054
Recommended setting:
OFF
Recommended setting:
OFF
ON
Recommended setting:
OFF
ON
A390.12,ex.b
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2.
Issue:
Heatingcircuit(1):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit2.
Circuit2mustbeabletosendtheheatdemandtocircuit1.
Issue:
Heatingcircuit(2):
Heatdemand
16|©Danfoss|2021.06
Navigation:
MENU\Settings\Application: 'Demandoffset'
Navigation:
MENU\Settings\Application: 'SenddesiredT'
IDno.:
11017
IDno.:
12500
Recommended setting:
3K*
Recommended setting:
ON
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390

2.3Mounting

2.3.1MountingtheECLComfortcontroller
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.Selectoneofthefollowingmethodsusingthesame basepart(codeno.087H3230):
Mountingonawall
MountingonaDINrail(35mm)
TheECLComfort310canonlybemountedintheECLComfort 310basepart.
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
AQ128686479024en-010601
©Danfoss|2021.06|17
OperatingGuideECLComfort310,applicationA390
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
18|©Danfoss|2021.06
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
AQ128686479024en-010601
©Danfoss|2021.06|19
OperatingGuideECLComfort310,applicationA390

2.4Placingthetemperaturesensors

Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
20|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ128686479024en-010601
©Danfoss|2021.06|21
OperatingGuideECLComfort310,applicationA390

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
ECL210/310
22|©Danfoss|2021.06
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
0,2A/230Va.c.
AQ128686479024en-010601
©Danfoss|2021.06|23
OperatingGuideECLComfort310,applicationA390
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
Maximumloadrating,ECA32
Max.voltage,relayoutputs
Max.loadonrelayoutputs
Max.loadonanalogue outputs
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
1A/24Va.c.
250Va.c.
4Aforohmicload,2Afor inductiveload
2mAeach(min.resistance 5KΩ)
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
24|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
2.5.3Electricalconnections,safetythermostats,ingeneral
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
AQ128686479024en-010601
©Danfoss|2021.06|25
OperatingGuideECLComfort310,applicationA390
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
2.5.5Electricalconnections,Pt1000temperaturesensors
SeetheInstallationGuide(deliveredwiththeapplicationkey)for sensorandinputconnections.
26|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
A390:
Sensor
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
Description
Outdoortemp.sensor*
A390.1/2/3:Roomtemp. sensor**
A390.11/12/13:Return temp.sensor
Flowtemp.sensor***
Flowtemp.sensor***
Returntemp.sensor****ESM-11/ESMB/ESMC
A390.1/2/3:Returntemp. sensor****
A390.11/12/13:DHWtank temp.sensor,upper****
A390.1/2/3:Returntemp. sensor****
A390.11/13:Roomtemp. sensor**
A390.12:DHWcharging temp.sensor****
A390.1/2/3:Roomtemp. sensor**
A390.11/12/13:DHWtank temp.sensor,lower****
A390.1/2/3/11/13:Flow temp.sensor***
A390.12:DHWcharging temp.sensor****
A390.1/2/3:Roomtemp. sensor**
A390.11/12/13:Return temp.sensor****
Type (recomm.)
ESMT
ESM-10
ESM-11/ESMB/ESMC /ESMU
ESM-11/ESMB/ESMC /ESMU
ESM-11/ESMB/ESMC /ESMU
/ESMU
ESM-11/ESMB/ESMC /ESMU
ESMB/ESMU
ESM-11/ESMB/ESMC /ESMU
ESM-10
ESM-11/ESMB/ESMC /ESMU
ESM-10
ESMB/ESMU
ESM-11/ESMB/ESMC /ESMU
ESM-11/ESMB/ESMC /ESMU
ESM-10
ESM-11/ESMB/ESMC /ESMU
*
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
**
Onlyforroomtemperaturesensorconnection.Theroom temperaturesignalcanalsobeavailablefromaRemote ControlUnit(ECA30/31).See'Electricalconnections,ECA 30/31'.
***
Theflowtemperaturesensormustalwaysbeconnected inordertohavethedesiredfunctionality.Ifthesensoris notconnectedorthecableisshort-circuited,themotorized controlvalvecloses(safetyfunction).
****
Thetemperaturesensormustbeconnectedinordertohave thedesiredfunctionality.
AQ128686479024en-010601
©Danfoss|2021.06|27
OperatingGuideECLComfort310,applicationA390
2.5.6Electricalconnections,ECA30/31
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus) Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
28|©Danfoss|2021.06
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ128686479024en-010601
©Danfoss|2021.06|29
OperatingGuideECLComfort310,applicationA390
2.5.7Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.8Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
30|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
2.5.9Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
AQ128686479024en-010601
©Danfoss|2021.06|31
OperatingGuideECLComfort310,applicationA390

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
32|©Danfoss|2021.06
ECLComfort296
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ128686479024en-010601
©Danfoss|2021.06|33
OperatingGuideECLComfort310,applicationA390
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
34|©Danfoss|2021.06
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
AQ128686479024en-010601
©Danfoss|2021.06|35
OperatingGuideECLComfort310,applicationA390
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
36|©Danfoss|2021.06
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
AQ128686479024en-010601
©Danfoss|2021.06|37
OperatingGuideECLComfort310,applicationA390
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
38|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
AQ128686479024en-010601
©Danfoss|2021.06|39
OperatingGuideECLComfort310,applicationA390

2.8Navigation,ECLApplicationKeyA390

Parameterlist,applicationA390,Heating
Home MENU
ScheduleSchedule
Settings
Sub-menu
IDnos.
Flow temperature
Roomlimit
Returnlimit
Flow/Actual powerlimitActuallimit
Optimization
1x178 1x177 1x004 1x182 1x183 1x015 1x031 1x032 1x033 1x034 1x035 1x036 1x037 1x085 11029 1x028
1x119 1x117 1x118 1x116 1x112 1x113 1x109 1x115 1x011 1x012 1x013 1x014 1x026 1x020 1x021 1x179 11043
Function
Heatcurve Temp.max. Temp.min. DesiredT Infl.-max. Infl.-min. Adapt.time HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,ret.Tlim.
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Paralleloperation
A390
A390.1A390.2A390.11A390.12A390.13
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(
40|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Parameterlist,applicationA390,Heating,continued
Home MENU
Settings
HolidayHoliday
Alarm
Influence overview
Sub-menu
IDnos.
Controlpar.
Application
Heatcut-out
Temp.monitor
Alarmoverview
Des.flowTInfluencesource
1x174 1x184 1x185 1x186 1x187 1x189 1x024 1x010 11017 11050 1x500 1x022 1x023 1x052 1x077 1x078 1x040 1x093 1x141 1x142 11393 11392 1x179 1x395 11397 11396 1x398 1x399
1x147 1x148 1x149 1x150
Function
Motorpr Xp Tn Mrun Nz Min.act.time Actuator ECAaddr. Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority PfrostT PheatT Ppost-run Frostpr.T Ext.input Ext.mode Sum.start,day Sum.start,month Summer,cut-out Summer,filter Winterstart,day Win.start,month Winter,cut-out Winter,filter
Upperdifference Lowerdifference Delay Lowesttemp.
A390
A390.1A390.2A390.11A390.12A390.13
(((((
(((((
(((((
((((
(((((
((((
((((
(((((
((((
((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
AQ128686479024en-010601
©Danfoss|2021.06|41
OperatingGuideECLComfort310,applicationA390
Parameterlist,applicationA390,Cooling
Home MENU
ScheduleSchedule
Settings
Sub-menu
IDnos.
Flow temperature
Roomlimit
Returnlimit
Compensation1
Compensation2
Flow/Actual powerlimit
Controlpar.
1x018 1x019 1x178 1x177 1x015 1x182 1x183 1x030 1x037 1x035 1x036 1x160 1x061 1x062 1x063 1x164 1x065 1x066 1x067
1x111 1x112 1x113 1x109 1x115 1x114 1x174 1x184 1x185 1x186 1x187 1x189 1x024
Function
Des.Tcomfort Des.Tsaving Temp.max. Temp.min Adapt.time Infl.-max. Infl.-min. Limit Adapt.time Infl.-max. Infl.-min. Limit Adapt.time Infl.-max. Infl.-min. Limit Adapt.time Infl.-max. Infl.-min.
Limit Adapt.time Filterconstant Inputtype Units Pulse Motorpr Xp Tn Mrun Nz Min.act.time Actuator
A390
A390.3
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
42|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Parameterlist,applicationA390,Cooling,continued
Home MENU
Settings
HolidayHoliday InfluenceoverviewDes.flowTInfluencesource
Sub-menu
Application
IDnos.
1x010 11017 11050 1x500 1x022 1x023 1x070 1x092 1x040 1x141 1x142
Function
ECAaddr. Demandoffset Pdemand SenddesiredT Pexercise Mexercise PcoolT StandbyT Ppost-run Ext.input Ext.mode
A390
A390.3
(
(
(
(
(
(
(
(
(
(
(
(
(
AQ128686479024en-010601
©Danfoss|2021.06|43
OperatingGuideECLComfort310,applicationA390
Parameterlist,applicationA390,DHW
Home
MENU
ScheduleSchedule Schedulecirc.PSchedulecirc.P
Settings
Sub-menu
IDnos.
Tank temperature
Returnlimit
Flow/powerlimitActual
Contr.par.
Application
13178 13177 1x193 1x195 1x194 1x152 13068 1x030 1x035 1x036 1x037
1x111 13112 13113 13109 13115 1x174 1x184 1x185 1x186 1x187 1x189 13017 13050 14051 14053 1x055 1x054 1x044 1x045 1x041 1x059 1x042 1x500 1x076 1x093 1x141 1x142
Function
Temp.max. Temp.min. Chargedifference Startdifference Stopdifference Max.chargeT FlowTadapt.time Limit Infl.-max. Infl.-min. Adapt.time
Limit Adapt.time Filterconstant Inputtype Units Motorpr Xp Tn Mrun Nz Min.act.time Demandoffset Pdemand Ch.-o.valve/P Tank,sec./prim. Circ.Ppriority Contr.Tcontrol Max.DHWtime DHWdeact.time DHWPpost-run Pchargedelay Char.Ppost-run SenddesiredT Circ.PfrostT Frostpr.T Ext.input Ext.mode
A390
A390.11A390.12A390.13
(((
(((
(
(
(((
(((
(((
((
(
(((
((
((
((
(((
(((
((
((
((
((
((
((
((
((
((
((
(
(
(
(
(((
((
((
((
(((
(((
(((
(((
(((
(((
(((
(((
44|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Parameterlist,applicationA390,DHW,continued
Home MENU
Settings
HolidayHoliday
Alarm
InfluenceoverviewDes.flowTInfluencesource
Sub-menu
IDnos.
Anti-bacteriaDay,days
Temp.monitor
Alarmoverview
1x147 1x148 1x149 1x150
Function
Starttime Duration DesiredT
Upperdifference Lowerdifference Delay Lowesttemp.
A390
A390.11A390.12A390.13
(((
(((
(((
(((
(((
((
((
((
((
((
(((
AQ128686479024en-010601
©Danfoss|2021.06|45
OperatingGuideECLComfort310,applicationA390
Parameterlist,applicationA390,Commoncontroller
Home MENU
Sub-menu
Time&date Schedule Holiday Inputoverview1 Inputoverview2 Inputoverview3 Inputoverview4 Log1 Log2 Log3 Log4 Outputoverride Keyfunctions
System
IDnos.
Function
Newapplication Application Factorysetting Copy Keyoverview ECLversion Extension Ethernet Portalconfig. M-busconfig. Energymeters
Rawinput overview Alarm
Display Communication Language
A390.1A390.2A390.3A390.11A390.12A390.13
((((((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
A390
(
((((
((((
((((
((((
(
((((
((((
((((
(
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
46|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ128686479024en-010601
©Danfoss|2021.06|47
OperatingGuideECLComfort310,applicationA390

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
48|©Danfoss|2021.06
)
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Examples:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
AQ128686479024en-010601
©Danfoss|2021.06|49
OperatingGuideECLComfort310,applicationA390
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Examples:
50
Confirm
AdjustthedesiredDHWtemperature
55
Confirm
InadditiontotheinformationaboutdesiredandactualDHW temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled operationandincomfortmode.
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
50|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
DamperOFF
AQ128686479024en-010601
©Danfoss|2021.06|51
OperatingGuideECLComfort310,applicationA390

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview oftheactualand(desired)temperaturesaswellastheactualstate ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
(30)
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
Flowtemperature
Desiredflowtemperature
--
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
52|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
AQ128686479024en-010601
©Danfoss|2021.06|53
OperatingGuideECLComfort310,applicationA390

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
54|©Danfoss|2021.06
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
Manualcontrolof0–10voltcontrolledactuator:
Theactuatorsymbolhasavalue(in%)whichcanbechanged.The% valueiscorrespondingtoavoltageintherange0–10volt.
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
AQ128686479024en-010601
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
©Danfoss|2021.06|55
OperatingGuideECLComfort310,applicationA390

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Actual(actualfloworpower)
Extendedheatcut-outsetting
Extendedwintercut-outsetting
Day
Starttime
Duration
DesiredT
DesiredT(Desiredflowtemperature)
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Adapt.time(adaptiontime)
Demandoffset
Des.TComfort
Des.TSaving
Basedon(optimizationbasedonroom/outdoortemp.)
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Actuator
Pre-stop(optimizedstoptime)
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
DHW,ret.Tlimit
Limit(returntemp.limitation)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Ppost-run
DHWPpost-run(DHWpump,post-run)
Char.Ppost-run(DHWchargingpump,post-run)
Paralleloperation
1x00461
1x01093
1x01182
1x01283
1x01384
1x01484
1x01564
1x01793
1x01862
1x01962
1x02085
1x02185
1x02295
1x02395
1x02490
1x02686
1x02869
1x02970
1x03070
1x031
1x032
1x033
1x034
1x035
1x03672
1x03773
1x04095
1x04195
1x04296
1x04386
Factorysettingsincircuit(s)
1
60
79
106
106
113
113
114
114
71
71
71
71
71
23
56|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
SettingIDPage
Max.DHWtime
DHWdeact.time(DHWdeactivationtime)
Pdemand
Ch.-o.valve/P(changeovervalve/pump)
DHWpriority(closedvalve/normaloperation)
Tank,sec./prim.(Tanksecondarilyorprimarilyconnected)
Cont.Tcontrol
Circ.Ppriority
Pchargedelay(Chargingpump,delayedstart)
Limit(compensationtemp.,1.point)
Adapt.time(adaptationtime)
Infl.-max.(compensationtemp.,1.point)
Infl.-min.(compensationtemp.,1.point)
Limit(compensationtemp.,2.point)
Adapt.time(adaptationtime)
Infl.-max.(compensationtemp.,2.point)
Infl.-min.(compensationtemp.,2.point)
FlowTadapttime(Flowtemperature,adaptationtime)
PcoolT(coolingdemand)
Circ.PfrostT
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
StandbyT
Frostpr.T(frostprotectiontemp.)
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Max.chargeT(maximumheating/chargingtemperature)
Motorpr.(motorprotection)
1x04496
1x04596
1x05096
1x05197
1x05297
1x05397
1x05498
1x05598
1x05998
1x060
1x061
1x062
1x063
1x06476
1x06576
1x06676
1x06776
1x068108
1x07099
1x07699
1x07799
1x07899
1x08573
1x092100
1x093100
1x10979
1x111
1x11280
1x11380
1x115
1x11680
1x117
1x11881
1x11981
1x141
1x142101
1x147
1x148116
1x149
1x150
1x152108
1x174
Factorysettingsincircuit(s)
1
74
74
74
75
79
80
81
100
116
117
117
90
23
AQ128686479024en-010601
©Danfoss|2021.06|57
OperatingGuideECLComfort310,applicationA390
SettingIDPage
Temp.min.
Temp.min.
Temp.max.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Infl.-max.(roomtemp.limitation,max.)
Infl.-min.(roomtemp.limitation,min.)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Chargedifference
Stopdifference
Startdifference
SenddesiredT
1x177
1x177
1x17862
1x178109
1x17987
1x18265
1x18365
1x18491
1x18591
1x18691
1x18791
1x18992
1x193109
1x194109
1x195
1x500103
Factorysettingsincircuit(s)
1
62
108
111
23
58|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
SomeparameterdescriptionsrefertoDuctorFloworInlet temperaturebecausetheparametersinquestionareusedinother applicationstoo.
AQ128686479024en-010601
©Danfoss|2021.06|59
OperatingGuideECLComfort310,applicationA390

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
60|©Danfoss|2021.06
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
TheECLComfort210/296/310controlstheDHWtemperature accordingtothedesiredflowtemperatureforexampleunderthe influenceofthereturntemperature.
ActualDHWtemp.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DesiredDHW temp.
AQ128686479024en-010601
©Danfoss|2021.06|61
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Flowtemperature
DesiredT(Desiredflowtemperature)
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow temperaturecanbeset. A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU >Settings>Returnlimit>'Con.T,ret.Tlim. '
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Des.TComfort
SettingofdesiredflowtemperaturewhentheECLcontrollerisincomfort mode.
1x004
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan beappliedtoaninputinordertooverridetoComfort,Saving,Frost ProtectionorConstanttemperature.Aslongasthecontact(switch) signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
1x018
Thissettinghasnoinfluenceifthecontrollerreceivesanexternalvalue forthedesiredflowtemperature.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Des.TSaving
SettingofdesiredflowtemperaturewhentheECLcontrollerisinsaving mode.
1x019
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
Thissettinghasnoinfluenceifthecontrollerreceivesanexternalvalue forthedesiredflowtemperature.
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
62|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
AQ128686479024en-010601
©Danfoss|2021.06|63
OperatingGuideECLComfort310,applicationA390

5.3Roomlimit

Thissectionisonlyrelevantifyouhaveinstalledaroom temperaturesensororaRemoteControlUnit. Thecontrolleradjuststhedesiredflowtemperaturetocompensate forthedifferencebetweenthedesiredandtheactualroom temperature. Iftheroomtemperatureishigherthanthedesiredvalue,the desiredflowtemperaturecanbereduced. The'Infl.-max.'(Influence,max.roomtemp.)determineshow muchthedesiredflowtemperatureshouldbereduced. Usethisinfluencetypetoavoidatoohighroomtemperature.The controllerwillallowforfreeheatgains,i.e.solarradiationetc. Iftheroomtemperatureislowerthanthedesiredvalue,thedesired flowtemperaturecanbeincreased. The'Infl.-min.'(Influence,min.roomtemperature)determines howmuchthedesiredflowtemperatureshouldbeincreased. Usethisinfluencetoavoidatoolowroomtemperature. Atypicalsettingwillbe-4.0for'Infl.-max.'and4.0for'Infl.-min. '
Influence
‘Infl.-min.’(min.limitation)
Desiredroomtemperature Actualroomtemperature
‘Infl.-max. ’(max.limitation)
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
Example1:
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. The‘Infl.-min.’issetto3.0. Result: Thedesiredflowtemperatureisdecreasedby2x-4.0=8.0degrees.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
Example2:
Theactualroomtemperatureis3degreestoolow. The‘Infl.-max.’issetto-4.0. The‘Infl.-min.’issetto3.0. Result: Thedesiredflowtemperatureisincreasedby3x3.0=9.0degrees.
64|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Roomlimit
Adapt.time(adaptiontime)
Controlshowfasttheactualroomtemperatureadaptstothedesiredroom temperature(Icontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe'Adapt. time'.
Minor
Thedesiredroomtemperatureisadaptedquickly.
value: Major
Thedesiredroomtemperatureisadaptedslowly.
value:
MENU>Settings>Roomlimit
Infl.-max.(roomtemp.limitation,max.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (decreased)iftheactualroomtemperatureishigherthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
0.0:
-2.0:
-5.0:
-9.9:
Noinfluence Minorinfluence Mediuminfluence Maximuminfluence
1x015
Theadaptationfunctioncancorrectthedesiredroomtemperature withmax.8Kxheatcurveslopevalue.
1x182
=
X
#1#
#2#
#3#
Roomtemperature
=
Desiredroomtemperature
=
Negativeinfluence(1x082)whenactualroomtemp.getshigher thandesiredroomtemp.
=
Positiveinfluence(1x083)whenactualroomtemp.getslowerthan desiredroomtemp.
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x-4.0x1.8) –14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x-4.0x1): –8.0degrees.
AQ128686479024en-010601
©Danfoss|2021.06|65
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Roomlimit
Infl.-min.(roomtemp.limitation,min.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (increased)iftheactualroomtemperatureislowerthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
9.9:
5.0:
2.0:
0.0:
Maximuminfluence Mediuminfluence Minorinfluence Noinfluence
Example
1x183
Theactualroomtemperatureis2degreestoolow. The‘Infl.-min.’issetto4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x4.0x1.8)
14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x4.0x1):
8.0degrees.
66|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390

5.4Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant temperaturevalue. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthesetlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
AQ128686479024en-010601
©Danfoss|2021.06|67
OperatingGuideECLComfort310,applicationA390
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
68|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
ThereturntemperaturelimitationfortheDHWcircuitisbasedonthe settingin'Limit(returntemp.limitation)' .
Theinfluencefactorsaresetintheheatingcircuit.
Ifthereturntemperaturelimitationvalueintheheatingcircuitis higherthanthereturntemperaturelimitationvalueintheDHWcircuit, thehighestvalueisused.
AQ128686479024en-010601
©Danfoss|2021.06|69
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Returnlimit
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
The"Con.T ,ret.Tlimit"isthereturntemperaturelimitationvaluewhenthe circuitissettooverridemodetype"Const.T"(=Constanttemperature).
SeeAppendix“ParameterIDoverview”
Value:Setthereturntemperaturelimitation
MENU>Settings>Returnlimit
DHW,ret.Tlimit
WhenanaddressedslaveisactiveinDHW-tankheating/charging,the returntemperaturelimitationinthemastercanbeset. Notes:
Themastercircuitmustbesettoreactonthedesiredflowtemperature intheslave(s).See"Demandoffset"(ID11017).
Theslave(s)mustbesettosendits/theirdesiredflowtemperatureto themaster.See"SenddesiredT"(ID1x500).
SeeAppendix“ParameterIDoverview”
OFF:
Noinfluencefromslaves.Thereturntemperature limitationisrelatedtosettingsin"Returnlimit" .
Value:
Returntemperaturelimitationvaluewhenslaveisin DHWtankheating/chargingoperation.
1x028
1x029
#1#=Master,exampleA266,address15 #2#=Slave,exampleA237,address9 #3#=Slave,exampleA367,address6
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe setvalue,thecontrollerautomaticallychangesthedesiredflow/ ducttemperaturetoobtainanacceptablereturntemperature.The influenceissetin'Infl.-max. 'and'Infl.-min.' .
SomeexamplesofapplicationswithDHW-tankheating/chargingare:
•A217,A237,A247,A367,A377
ThereturntemperaturelimitationfortheDHWcircuitisbasedonthe settingin'Limit(returntemp.limitation)' .
Theinfluencefactorsaresetinheatingcircuit1.
70|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Returnlimit
Ifthereturntemperaturelimitationvalueinheatingcircuit1ishigher thanthereturntemperaturelimitationvalueintheDHWcircuit,the highestvalueisused.
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
1x031
1x032
1x033
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
AQ128686479024en-010601
1x034
©Danfoss|2021.06|71
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
1x035
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Thereturnlimitisactiveabove50°C. Theinfluenceissetto-2.0. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby-2.0x2=-4.0degrees.
Normally,thissettingislowerthan0indistrictheatingsystemsto avoidatoohighreturntemperature.
Typically,thissettingis0inboilersystemsbecauseahigherreturn temperatureisacceptable(seealso'Infl.-min. ').
72|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
Example
1x036
1x037
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
AQ128686479024en-010601
©Danfoss|2021.06|73
OperatingGuideECLComfort310,applicationA390

5.5Compensation1

Alimitvalueforthecompensationtemperaturemakesitpossible tochangethedesiredflow/ducttemperature. Theinfluencefromthecompensationtemperaturecanresultin anincreaseoradecreasedesiredflow/ducttemperature.The compensationtemperatureisoftentheoutdoortemperaturebut couldforexamplebearoomtemperature. Thisapplicationcontains2compensationtemperaturelimits: Compensation1(Comp.1)andCompensation2(Comp.2). Intheparameterdescriptions"Sx"isusedforthecompensation temperature.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Compensation1
Limit(compensationtemp.,1.point)
Setthecompensationtemperaturelimitpoint1.
1x060
SeeAppendix“ParameterIDoverview”
WhenthecompensationtemperaturemeasuredbySxfallsbelow orgetshigherthanthesetvalue,thecontrollerautomatically changesthedesiredflow/ducttemperature.Theinfluenceisset in'Infl.-max. 'and'Infl.-min.' .
MENU>Settings>Compensation1
Adapt.time(adaptationtime)
Controlshowfastthecompensation/surfacetemperatureinfluencesthe desiredflow/ducttemperature.
1x061
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredflow/ducttemperatureisadaptedquickly.
value: Major
Thedesiredflow/ducttemperatureisadaptedslowly.
value: Value:Settheadaptationtime
Influence
Temp.Sx
Compensation1
Theadaptationfunctioncancorrectthedesiredflow/duct temperaturewithmax.8K.
74|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Compensation1
Infl.-max.(compensationtemp.,1.point)
Determineshowmuchthedesiredflow/ducttemperaturewillbeinfluenced ifthecompensationtemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflow/ducttemperatureisincreased,whenthe compensationtemperaturegetsabovethesetlimit.
Influencelowerthan0:
Thedesiredflow/ducttemperatureisdecreased,whenthe compensationtemperaturegetsabovethesetlimit.
MENU>Settings>Compensation1
Infl.-min.(compensationtemp.,1.point)
Determineshowmuchthedesiredflow/ducttemperaturewillbeinfluenced ifthecompensationtemperatureislowerthanthesetlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflow/ducttemperatureisincreased,whenthe compensationtemperaturegetsbelowthesetlimit.
Example
1x062
1x063
Thelimitvalueissetto5°C. ‘Infl.max.’issetto-1.5. Theactualcompensationtemperatureis7°C(2degreesabovethe
limitvalue). Result: Thedesiredflow/ducttemperatureischangedby-1.5x2=-3.0
degrees.
Example
Thelimitvalueissetto5°C. ‘Infl.min.’issetto2.5. Theactualcompensationtemperatureis2°C(3degreesbelowthe
limitvalue). Result: Thedesiredflow/ducttemperatureischangedby2.5x3=7.5
degrees.
Influencelowerthan0:
Thedesiredflow/ducttemperatureisdecreased,whenthe compensationtemperaturegetsbelowthesetlimit.
AQ128686479024en-010601
©Danfoss|2021.06|75
OperatingGuideECLComfort310,applicationA390

5.6Compensation2

Thisextracompensationtemperaturelimitsettingmakesitpossible tochangethedesiredflow/ducttemperatureinrelationtoa secondtemperaturelimitationpoint.Themeasuredcompensation temperatureisthesameasinsection"Compensation1". Intheparameterdescriptions"Sx"isusedforthecompensation temperature.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Compensation2
Limit(compensationtemp.,2.point)
Setthecompensationtemperaturelimitpoint2.
1x064
SeeAppendix“ParameterIDoverview”
WhenthecompensationtemperaturemeasuredbySxfallsbelow orgetshigherthanthesetvalue,thecontrollerautomatically changesthedesiredflow/ducttemperature.Theinfluenceisset in'Infl.-max. 'and'Infl.-min.' .
MENU>Settings>Compensation2
Adapt.time(adaptationtime)
Controlshowfastthecompensationtemperatureinfluencesthedesired flow/ducttemperature.
1x065
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredflow/ducttemperatureisadaptedquickly.
value: Major
Thedesiredflow/ducttemperatureisadaptedslowly.
value:
Influence
Temp.Sx
Compensation2
Theadaptationfunctioncancorrectthedesiredflow/duct temperaturewithmax.8K.
MENU>Settings>Compensation2
Infl.-max.(compensationtemp.,2.point)
Determineshowmuchthedesiredflow/ducttemperaturewillbeinfluenced ifthecompensationtemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflow/ducttemperatureisincreased,whenthe compensationtemperaturegetsabovethesetlimit.
Influencelowerthan0:
Thedesiredflow/ducttemperatureisdecreased,whenthe compensationtemperaturegetsabovethesetlimit.
76|©Danfoss|2021.06
Example
1x066
Thelimitvalueissetto25°C. ‘Infl.max.'issetto2.5. Theactualcompensationtemperatureis28°C(3degreesabovelimit
value). Thedesiredflow/ducttemperatureischangedby2.5x3=7.5
degrees.
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Compensation2
Infl.-min.(compensationtemp.,2.point)
CircuitSettingrange
Determineshowmuchthedesiredflow/ducttemperaturewillbeinfluenced ifthecompensationtemperatureislowerthanthesetlimit.
Factorysetting
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflow/ducttemperatureisincreased,whenthe compensationtemperaturegetsbelowthesetlimit.
Influencelowerthan0:
Thedesiredflow/ducttemperatureisdecreased,whenthe compensationtemperaturegetsbelowthesetlimit.
Example
1x067
Thelimitvalueissetto25°C. ‘Infl.min.’issetto0.5. Theactualcompensationtemperatureis23°C(2degreesbelowthe
limitvalue). Result: Thedesiredflow/ducttemperatureischangedby0.5x2=1.0degree.
AQ128686479024en-010601
©Danfoss|2021.06|77
OperatingGuideECLComfort310,applicationA390

5.7Flow/powerlimit

Heatingcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2# #Y1#
#Y2#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
=
X
Y
#1#
#2#
#3#
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
78|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
DHWcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower. Whentheflow/powergetshigherthanthesetlimit,thecontroller graduallyreducesthedesiredflowtemperaturetoobtainan acceptablemax.floworpowerconsumption.
=
X
Y
#1#
#2#
#3#
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Inputtype
Choiceofinputtypefromflow/energymeter
SeeAppendix“ParameterIDoverview”
OFF:
EM1-
Noinput
Flow/energymetersignalfromM-bus.
EM5:
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
1x109
AQ128686479024en-010601
©Danfoss|2021.06|79
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
1x111
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Flowvaluesareexpressedasl/horm³/h PowervaluesareexpressedaskW,MWorGW.
1x113
1x115
Listforsettingrangeof'Units': l/h m³/h kW MW GW
80|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
1x116
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
1x118
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
1x119
AQ128686479024en-010601
©Danfoss|2021.06|81
OperatingGuideECLComfort310,applicationA390

5.8Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost','Optimizer','Totalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
82|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
AQ128686479024en-010601
©Danfoss|2021.06|83
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
=
X Y #1#
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
84|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
MENU>Settings>Optimization
Basedon(optimizationbasedonroom/outdoortemp.)
Theoptimizedstartandstoptimecanbebasedoneitherroomoroutdoor temperature.
SeeAppendix“ParameterIDoverview”
OUT:
Optimizationbasedonoutdoortemperature.Usethis settingiftheroomtemperatureisnotmeasured.
ROOM:
Optimizationbasedonroomtemperature,ifmeasured.
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
1x020
-5°C
small
AQ128686479024en-010601
©Danfoss|2021.06|85
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost protectionisstillactive,see'PfrostT' .
Totalstop=OFF
Totalstop=ON
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
1x026
Example:OptimizationofComfortfrom07:00-22:00
=
X #1# #2# #3# #4# #5#
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
86|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Optimization
Paralleloperation
ChoosewhethertheheatingcircuitistooperateparalleltotheDHWcircuit.
SeeAppendix“ParameterIDoverview”
OFF:
DHWheatinghas100%priority.Theheatingcircuit circulationpumpisOFFduringDHWheating.
1...99K:
Dependentparalleloperation.Theheatingcircuit circulationpumpisONifthedifferencebetweenDHW heatingtemperature(chargingtemperature)and desiredflowtemperatureislessthanthesetvalue.
ON:
Paralleloperation.Theheatingcircuitcirculationpump isONduringDHWheating.
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
SeeAppendix“ParameterIDoverview”
1x043
=
X
Y
#1#
#2#
#3#
#4#
#5#
Summer,cut-out
1x179
Time
=
Temperature
=
Acceptabledeviation(Paralleloperation,1x043)
=
DesiredDHWheatingtemperature
=
ActualDHWheatingtemperature
=
100%paralleloperation
=
100%DHWpriority
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
AQ128686479024en-010601
©Danfoss|2021.06|87
OperatingGuideECLComfort310,applicationA390

5.9Controlparameters

Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansofeither 3-pointcontrolora0-10voltcontrolsignaloramixofthese. Valvecontrol(heating): Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Valvecontrol(cooling): Themotorizedcontrolvalveisoperatedoppositelyinrelationto heatingapplication. Thefollowingexplanationsforactuatortypesarerelatedtoheating applications. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
88|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
0-10voltcontrolledactuator Thiselectricactuatorcontainsareversiblegear-motor.Acontrol voltagebetween0and10voltcomesfromtheextensionmodule ECA32inordertomanagethecontrolvalve.ThevoltageintheECL Comfortcontrollerisexpressedasa%valueanddisplayedatthe valvesymbol.Example:45%correspondsto4.5volt. Whentheflowtemperature(forexampleatS3)islowerthan thedesiredflowtemperature,thecontrolvoltageisgradually increasedinordertograduallyincreasetheflow.Bythis,theflow temperaturewillalignwiththedesiredtemperature. Thecontrolvoltageremainsonaconstantvalueaslongastheflow temperaturecorrespondstothedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,thecontrolvoltageisgraduallyreducedinorder toreducetheflow.Again,theflowtemperaturealignswiththe desiredtemperature.
Thermo-actuator,DanfosstypeABV
Danfossthermo-actuatortypeABVisaslowactingvalveactuator. InsidetheABVanelectricheatcoilwillheatathermostaticelement whenanelectricsignalisapplied.Whenheatingthethermostatic elementitexpandsinordertomanagethecontrolvalve. Twobasictypesareavailable:ABVNC(NormalClosed)andABVNO (normalopen).Forexample,ABVNCkeepsa2-portcontrolvalve closedwhennoopen-signalsareapplied. Electricopen-signalscomefromtheelectronicoutputoftheECL Comfortcontrollerinordertomanagethecontrolvalve.When open-signalsareappliedtotheABVNC,thevalvegraduallyopens. Open-signalsareintheECLComfortcontrollerexpressedas "Arrow-up"(open)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,relativelylongopen-signalscomefrom theECLComfortcontrollerinordertoincreasetheflow.Bythis, theflowtemperaturewillovertimebealignedwiththedesired temperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,relativelyshortopen-signalscomefromtheECL Comfortcontrollerinordertoreducetheflow.Again,theflow temperaturealigns,overtime,withthedesiredtemperature. ThecontroloftheDanfossthermo-actuatortypeABVusesaunique designedalgorithmandisbasedonthePWMprinciple(Pulse WidthModulation),wherethedurationofthepulsedetermines themanagementofthecontrolvalve.Thepulsesarerepeated each10sec. Aslongastheflowtemperaturecorrespondstothedesired temperature,thedurationoftheopen-signalswillremainconstant.
AQ128686479024en-010601
©Danfoss|2021.06|89
OperatingGuideECLComfort310,applicationA390
TheapplicationA390.1controlsthemotorizedcontrolvalvesby meansof3-pointcontrol.
TheapplicationA390.2controlsthemotorizedcontrolvalvesby meansofa0-10voltcontrolsignal.
TheapplicationsA390.3,A390.11,A390.12andA390.13cancontrol themotorizedcontrolvalvesbymeansof3-pointcontroland0– 10Volt.Bothoutputtypesareactive.
Pleasesee‘Settingsinallheatingcircuits’section‘Control parameters’ .
Applicationexample,A390.1
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Actuator
ABV/GEAR
Selectionofvalveactuatortype.
ABV:
GEAR:
DanfosstypeABV(thermoactuator). Gearmotorbasedactuator.
1x024
GEAR
Whenselecting"ABV",thecontrolparameters:
•Motorprotection(ID1x174)
•Xp(ID1x184)
•Tn(ID1x185)
•Mrun(ID1x186)
•Nz(ID1x187)
•Min.act.time(ID1x189)
arenotconsidered.
90|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
1x174
Recommendedforductsystemswithvariableload.
1x184
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
Thesetting"Mrun"isnotpresentwhenthevalveiscontrolledby meansofa0-10voltsignal.
AQ128686479024en-010601
©Danfoss|2021.06|91
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Criticaltimeperiod
Time
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
92|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390

5.10Application

Thesection"Application"describesspecificapplicationrelated issues. Someoftheparameterdescriptionsareuniversalfordifferent applicationkeys.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Application
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Decidestheroomtemperaturesignaltransferandcommunicationwiththe RemoteControlUnit.
SeeAppendix“ParameterIDoverview”
OFF:
NoRemoteControlUnit.Onlyroomtemperaturesensor, ifany.
A:
B:
RemoteControlUnitECA30/31withaddressA. RemoteControlUnitECA30/31withaddressB.
1x010
TheRemoteControlUnitmustbesetaccordingly(AorB).
AQ128686479024en-010601
©Danfoss|2021.06|93
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Application
Demandoffset
Thedesiredflowtemperatureinthemastercircuitcanbeinfluencedbythe demandforadesiredflowtemperatureinanothercontroller(slave)or anothercircuit. The‘Demandoffset’cancompensateforheatingorcoolinglossesbetween masterandslavecontrolledsystems. Circuit1isthemastercircuitinmostapplications.
SeeAppendix“ParameterIDoverview”
1x017
Heatingapplication
*
**
OFF:
Value:
heatingapplications:OFF/1...20K coolingapplications:-20...-1K/OFF
heatingapplications:OFF coolingapplications:OFF
Thedesiredflowtemperatureisnotinfluencedbythe demandofanyothercontroller(slave)orcircuit.
Thedesiredflowtemperatureisincreased(heating)or decreased(cooling)bythesetvaluein‘Demandoffset’ .
X
Y
#1#
#2#
#3#
Coolingapplication
=
Time
=
Desiredflowtemperatures
=
Demandoffset
=
Desiredflowtemperature,master
=
Desiredflowtemperature,slave
94|©Danfoss|2021.06
=
X
Y
#1#
#2#
#3#
Heatingapplications:
Whensetting"Demandoffset"toavalue,thereturntemperature limitationwillreactaccordingtothehighestheating/DHWlimitation value.
Time
=
Desiredflowtemperatures
=
Demandoffset
=
Desiredflowtemperature,slave
=
Desiredflowtemperature,master
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Application
Whensetting"Demandoffset"toavalue,thereturntemperature limitationwillreactaccordingtothehighestlimitationvalue(Heating /DHW).
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheating/cooling demand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat noon(12:14hours).
MENU>Settings>Application
Mexercise(valveexercise)
Exercisesthevalvetoavoidblockinginperiodswithoutheating/cooling demand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thevalveexerciseisnotactive.
Thevalveopensfor7minutesandclosesfor7minutes everythirddayatnoon(12:00hours).
1x022
1x023
MENU>Settings>Application
Ppost-run
Heatingapplications:
ThecirculationpumpintheheatingcircuitcanbeONforanumberof minutes(m)afterheatingstop.Heatingstopiswhenthedesiredflow temperaturegetslowerthanthesettingin'PheatT'(IDno.1x078).
Coolingapplications:
ThecirculationpumpinthecoolingcircuitcanbeONforanumberof minutes(m)aftercoolingstop.Coolingstopiswhenthedesiredflow temperaturegetshigherthanthesettingin'PcoolT'(IDno.1x070). ThisPpost-runfunctioncanutilizetheremainingenergyinforexamplea heatexchanger.
SeeAppendix“ParameterIDoverview”
0:
Thecirculationpumpstopsimmediatelyafterheating orcoolingstop.
Value:
ThecirculationpumpisONforthesettimeafterheating orcoolingstop.
AQ128686479024en-010601
1x040
©Danfoss|2021.06|95
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Application
DHWPpost-run(DHWpump,post-run)
SettheDHWpumppost-runtime(minutes).TheDHWpumpcancontinue tobeswitchedONaftertheDHWheatingprocedureinordertoutilizethe remainingheatintheheatexchanger/boiler.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
MENU>Settings>Application
Char.Ppost-run(DHWchargingpump,post-run)
SettheDHWchargingpumppost-runtime(minutes).TheDHWcharging pumpcancontinuetobeswitchedONaftertheDHWheatingprocedurein ordertoutilizetheremainingheatintheheatexchanger.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
MENU>Settings>Application
1x041
1x042
Max.DHWtime
SetthemaxDHWheatingtime(minutes).WhenDHWheatingisactiveand theset'Max.DHWtime'expires,DHWheatingisdeactivated.
1x044
SeeAppendix“ParameterIDoverview”
OFF:
IftheDHWtemperatureislowerthantheDHWcharging cut-intemperature,theDHWchargingremainsactive forunlimitedperiodoftime.IftheDHWtemperatureis higherthantheDHWchargingcut-intemperature,the chargingisdeactivatedafter35minutes.
Value:
TheDHWheating/chargingisdeactivatedwhentheset 'Max.DHWtime'(inminutes)expires.
MENU>Settings>Application
DHWdeact.time(DHWdeactivationtime)
Setthetime(minutes)thatmustelapseafteraDHWheatingperiodbeforea newDHWheatingperiodcanbestarted.
1x045
SeeAppendix“ParameterIDoverview”
Value:WhentheDHWheating/chargingtimehasreachedits
maximum,DHWcanonlybeheated/chargedagain afterthesetdeactivationtime(inminutes)hasexpired.
96|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Application
Pdemand
Thecirculationpumpinthemastercircuitcanbecontrolledinrelationto themastercircuit'sdemandorslavecircuit'sdemand.
SeeAppendix“ParameterIDoverview”
Heatingapplications:
OFF:
ThecirculationpumpisONwhenthedesiredflow temperatureintheheatingcircuitishigherthanthe valuesetin'PheatT'.
ON:
ThecirculationpumpisONwhenthedesiredflow temperaturefromslavesishigherthanthevaluesetin 'PheatT'.
Coolingapplications:
OFF:
ThecirculationpumpisONwhenthedesiredflow temperatureinthecoolingcircuitislowerthanthevalue setin'PcoolT'.
ON:
ThecirculationpumpisONwhenthedesiredflow temperaturefromslavesislowerthanthevaluesetin 'PcoolT'.
MENU>Settings>Application
1x050
Thecirculationpumpisalwayscontrolledaccordingtofrostprotection conditions.
Ch.-o.valve/P(changeovervalve/pump)
ChoosewhethertheDHWheatingcontrolisbasedonachangeovervalve orapump.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Changeovervalve Pump
MENU>Settings>Application
DHWpriority(closedvalve/normaloperation)
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen DHWheating/chargingisactiveinthemaster.
SeeAppendix“ParameterIDoverview”
OFF:
Theflowtemperaturecontrolremainsunchanged duringactiveDHWheating/charginginthemaster controller.
ON:
Thevalveintheheatingcircuitisclosed*duringactive DHWheating/charginginthemastercontroller.
*Thedesiredflowtemperatureissettothevaluesetin ‘Frostpr.T’
1x051
Whenthechangeovervalveischosen,pumpP1isONatheatingas wellasatDHWheatingdemand.
Whenthepumpischosen,pumpP1isONatheatingandOFFatDHW heatingdemand.
Aparalleloption(heatingandDHWheatinginparallel)exists,based onthesetting‘Paralleloperation’ .
1x052
Thissettingmustbeconsideredifthiscontrollerisaslave.
AQ128686479024en-010601
©Danfoss|2021.06|97
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Application
Tank,sec./prim.(Tanksecondarilyorprimarily connected)
ChoosewhethertheheatingoftheDHWtankisdependentontheflow temperatureatS3.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWtankisplacedonthesecondarysideofthe heatexchangerandtheS3temperaturedetermines theDHWheating.
ON:
TheDHWtankisplacedontheprimarysideoftheheat exchangerandtheS3temperaturehasnoinfluence ontheDHWheating.
MENU>Settings>Application
Cont.Tcontrol
ThedesiredDHWheating/chargingtemperaturecanbeloweredwhenthe DHWheating/chargingprocedurehaselapsed.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredheating/chargingtemperatureislowered to10°C.Typically,theDHWiscirculatedthroughthe DHWtank.
ON:
Thedesiredheating/chargingtemperatureislowered tothedesiredDHWtemperature.Typically,theDHW iscirculatedthroughtheheatexchangerinorderto compensatefortheheatlossintheDHWcirculation pipe.
1x053
1x054
MENU>Settings>Application
Circ.Ppriority
ChoosewhethertheDHWcirculationpumpshouldbeONduringDHW heating.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWcirculationpumpisswitchedOFFduringDHW heating.
ON:
TheDHWcirculationpumpisnotswitchedOFFduring DHWheating.
1x055
Whenthe'Circ.Ppriority'issettoOFF ,theschedulefortheDHW circulationpumpisoverruled.
98|©Danfoss|2021.06
AQ128686479024en-010601
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Application
Pchargedelay(Chargingpump,delayedstart)
ConditionsforswitchingtheDHWheating/chargingpumpONatDHW heating/chargingdemand. Correctsettingcanavoiddischarging.
SeeAppendix“ParameterIDoverview”
OFF:
DHWheating/chargingpumpisswitchedONwhen DHWheating/chargingtemperatureisOK.
0:
Value:
DHWheating/chargingpumpisswitchedON.
DHWheating/chargingpumpisswitchedONafterthe setnumberofminutes.
MENU>Settings>Application
PcoolT(coolingdemand)
Whenthedesiredflowtemperatureisbelowthesettemperaturein‘PcoolT’ , thecontrollerautomaticallyswitchesONthecirculationpump.
SeeAppendix“ParameterIDoverview”
Value:
ThecirculationpumpisswitchedONwhenthedesired flowtemperatureisbelowthesetvalue.
1x059
Whenthesetting"OFF"isselected,thetemperaturesensorforDHW heating/chargingmustbeplacedintheheat-exchanger.
1x070
Thevalveisfullyclosedaslongasthepumpisnotswitchedon.
MENU>Settings>Application
Circ.PfrostT
SettheoutdoortemperaturevalueatwhichtheDHWcirculationpumpisto beactivetoprotecttheDHWcircuitagainstfrost.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
TheDHWcirculationpumpisnotactive. TheDHWcirculationpumpisactivewhentheoutdoor
temperatureislowerthanthesetvalue.
MENU>Settings>Application
PfrostT(circulationpump,frostprotectiontemp.)
Frostprotection,basedontheoutdoortemperature. Whentheoutdoortemperaturegetsbelowthesettemperaturevaluein‘P frostT’ ,thecontrollerautomaticallyswitchesONthecirculationpump(for exampleP1orX3)toprotectthesystem.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Nofrostprotection. CirculationpumpisONwhentheoutdoortemperature
isbelowthesetvalue.
1x076
1x077
Undernormalconditions,yoursystemisnotfrostprotectedifyour settingisbelow0°CorOFF.
Forwater-basedsystems,asettingof2°Cisrecommended.
Iftheoutdoortemperaturesensorisnotconnectedandthefactory settinghasnotbeenchangedto'OFF' ,thecirculationpumpisalways ON.
AQ128686479024en-010601
©Danfoss|2021.06|99
OperatingGuideECLComfort310,applicationA390
MENU>Settings>Application
PheatT(heatdemand)
Whenthedesiredflowtemperatureisabovethesettemperaturein‘PheatT’ , thecontrollerautomaticallyswitchesONthecirculationpump.
1x078
SeeAppendix“ParameterIDoverview”
Value:ThecirculationpumpisswitchedONwhenthedesired
flowtemperatureisabovethesetvalue.
MENU>Settings>Application
StandbyT
Setthedesiredflowtemperatureforthecontrollerwhenitisinstandby mode.
1x092
SeeAppendix“ParameterIDoverview”
Value:
Desiredflowtemperatureatstandby.
MENU>Settings>Application
Frostpr .T(frostprotectiontemp.)
SetthedesiredflowtemperatureattheflowtemperaturesensorS3to protectthesystemagainstfrost(atheatingcut-out,totalstopetc.). Whentheflowtemperaturegetslowerthanthesetting,themotorized controlvalveopensgradually.
1x093
Thevalveisfullyclosedaslongasthepumpisnotswitchedon.
Thefrostprotectiontemperaturecanalsobesetinyourfavorite displaywhenthemodeselectorisinfrostprotectionmode.
SeeAppendix“ParameterIDoverview”
100|©Danfoss|2021.06
AQ128686479024en-010601
Loading...