Danfoss A377 Operating guide

OperatingGuide
ECLComfort310,applicationA377

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................13
2.4Placingthetemperaturesensors................................21
2.5Electricalconnections.............................................23
2.6InsertingtheECLApplicationKey..............................32
2.7Checklist............................................................39
2.8Navigation,ECLApplicationKeyA377.........................40
3.0Dailyuse.........................................................55
3.1Howtonavigate...................................................55
3.2Understandingthecontrollerdisplay..........................56
3.3Ageneraloverview:Whatdothesymbolsmean?...........60
3.4Monitoringtemperaturesandsystem
components........................................................61
3.5Influenceoverview................................................62
3.6Manualcontrol.....................................................63
3.7Schedule............................................................64
4.0Settingsoverview............................................65
5.0Settings...........................................................67
5.1IntroductiontoSettings..........................................67
5.2Flowtemperature..................................................68
5.3Roomlimit..........................................................72
5.5Flow/powerlimit.................................................81
5.6Optimization........................................................85
5.7Controlparameters................................................92
5.8Application.........................................................96
5.9Heatcut-out......................................................106
5.10Tanktemperature................................................109
5.11Alarm..............................................................114
5.12Alarmoverview..................................................118
5.13Anti-bacteria......................................................119
6.0Commoncontrollersettings............................121
6.1Introductionto‘Commoncontrollersettings’..............121
6.2Time&Date.......................................................122
6.3Holiday............................................................123
6.4Inputoverview...................................................125
6.5Log.................................................................126
6.6Outputoverride..................................................127
6.7Keyfunctions.....................................................128
6.8System.............................................................130
7.0Miscellaneous................................................137
7.1ECA30/31setupprocedures.................................137
7.2Overridefunction................................................145
7.3Severalcontrollersinthesamesystem......................148
7.4Frequentlyaskedquestions....................................151
7.5Definitions........................................................154
7.6Type(ID6001),overview.......................................158
7.7Automatic/manualupdateoffirmware.....................159
7.8ParameterIDoverview..........................................160
©Danfoss|2021.12AQ190786468664en-010802|1
OperatingGuideECLComfort310,applicationA377

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA377 (ordercodeno.087H3817).
TheECLApplicationKeyA377contains3subtypes,allapplicablein ECLComfort310:
A377.1:2xheatingand1xDHW
A377.2:2xheatingand1xadvancedDHW
A377.3:2xheatingand1xadvancedDHWwithDHW circulationtemperaturemonitoring
SeetheMountingGuide(deliveredwiththeapplicationkey)for applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310for advancedsolutions,forexampleM-bus,ModbusandEthernet (Internet)communication.
TheapplicationKeyA377complieswithECLComfort310 controllersasofsoftwareversion1.11(visibleatstart-upofthe controllerandin'Commoncontrollersettings'in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe connectedandthebuilt-inroomtemperaturesensorcanbe utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O moduleECA32(ordercodeno.087H3202)canbeusedforextra datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool". Navigation:Danfoss.com>Products&Solutions>DistrictHeating andCooling>T ools&Software>ECLTool. TheURLis:
https://www.danfoss.com/en/service-and-support/downloads/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL Comfort310.
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartforECLComfort310:
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort310,modulesand accessoriesisavailableonhttp://danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AQ190786468664en-010802
©Danfoss|2021.12|3
OperatingGuideECLComfort310,applicationA377
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310/311:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
4|©Danfoss|2021.12
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
2
Circuit2Parameterno.
174
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
AQ190786468664en-010802
©Danfoss|2021.12|5
OperatingGuideECLComfort310,applicationA377

2.0Installation

2.1Beforeyoustart

Theapplications(subtypes)intheA377applicationkeyarevery flexibleandalmostidentical. However,someapplicationshaveextrafunctionswhichare describedseparately. Thesearethebasicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1). Thelowertheoutdoortemperature,thehigherthedesiredflow temperature.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesforthedesiredroomtemperature). InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM2isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature.
TypicalA377.1application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperature(RemotecontrolunitECA30/
31)doesnotequalthedesiredroomtemperature,thedesiredflow temperaturecanbeadjusted.
Thecirculationpump(P2)isONatheatdemandoratfrost protection. TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit thefloworenergytoasetmaximumvalue.Furthermore,the limitationcanbeinrelationtotheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedflow/power.
Thedesiredflowtemperatureofheatingcircuit1can,viaS7,be controlledbymeansofanexternalvoltageintherange0-10volt.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C. Analarmcanbeactivatediftheactualflowtemperaturediffers fromthedesiredflowtemperature.
TheroomtemperaturesignalcanbeachievedfromtheRemote ControlUnitECA30/31,ifconnected.
A377.2: WhenbothDHWheating/chargingandheatingcircuit1are active,thecirculationpumpintheheatingcircuitcancontinue operating.Theheatingcircuittemperatureistypicallyincreased. Thisisparallelmode.Iftheincreaseoftheflowtemperature cannotbeaccepted,thecirculationpumpinheatingcircuitcanbe stopped.ThisisDHWprioritymode.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2Returntemperaturesensor,circuit2
S3
Flowtemperaturesensor,circuit1
S4
Flowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
(S7)
(Externaltemperaturecontrol,notillustrated)
S8
DHWtanktemperaturesensor,lower
S9
DHWflowtemperaturesensor,circuit3
S10Returntemperaturesensor,circuit3
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit3 Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
M3
Motorizedcontrolvalve(3-pointcontrolled),circuit2 Alternative:Thermoactuator(DanfosstypeABV)
P1
DHWheatingpump(notillustrated)
P2
Circulationpump,heating,circuit1
P3
DHWcirculationpump
P4
DHWchargingpump
P5
Circulationpump,heating,circuit2
A1
Alarm
A/B
Internal/externalconnectionsforDHWcirculation
6|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Heatingcircuit,ingeneral:
Exerciseofcirculationpumpandcontrolvalveinperiodswithout heatingdemandcanbearranged.
Heating(circuit2):
Thiscircuitworksaftersameprinciplesascircuit1.
TheflowtemperaturesensorS4isthemostimportantsensor.
ThemotorizedcontrolvalveM3controlsthecircuit.
Thereturntemperature(S2)enableslimitationasdescribed previously.
Heatingcircuit2canbeconnectedafterheatingcircuit1.Ifso,the desiredflowtemperatureatS3canbeinfluencedbythedesired flowtemperatureatS4.
A377.1examplea:
A377.1,exampled
AQ190786468664en-010802
©Danfoss|2021.12|7
OperatingGuideECLComfort310,applicationA377
DHW(circuit3):
TheDHWheatingcircuitisconnecteddirectlytotheheating source.ThetemperaturesensorS10measuresthereturn temperature.Ifthereturntemperaturelimitisexceeded,the desiredtemperatureatS9canbecorrected.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredDHWtemperature).
Chargingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthe charging-starttemperature,theDHWheatingpumpP1isswitched ON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain theheating/chargingtemperatureatS9.
TheDHWchargingpumpisswitchedONwhentheS9temperature isacceptable,whichmeansitmustbewithin3Kfromdesired heating/chargingtemperature.SeealsoapplicationA377.1,ex.d.
IfS9isplacedontheheat-exchanger'ssecondaryside,itmustbe placedintheheat-exchanger.
TheDHWchargingtemperatureisdeterminedbythedesiredDHW temperatureatS6plusthesetchargingdifference.Thecharging temperatureistypically5–10degreeshigherthanthedesired DHWtemperature.
A377.1,exampled
Charging-starttemperature:
DesiredDHWtemperature+Startdifference. Example: 50°C+(-3K)=47°C
A377.1,A377.3: S10canhaveoneoftwofunctions:
1.Actasreturntemperaturelimiter
2.MonitortheDHWheatingtemperatureinordertoavoid dischargingandenablereturntemperaturelimitation.
Function1:Thereturntemperature,whentheDHWheating/ chargingisactive,canbelimitedtoasetvalue.
Function2:TheDHWchargingpumpisswitchedONwhentheS10 temperatureishigherthantheDHWtemperature.After4minutes, thereturntemperaturelimitation(setvalue)isactivated.
A377.2: TheDHWheating/chargingcircuitisconnectedafterheating circuit1.TheDHWheatingcircuitcannotbeconnecteddirectlyto theheatingsource.ThetemperaturedemandatS9istransferredas desiredtemperatureatS3.
TheDHWheatingcircuithasapreheatingcircuit,wheretheDHW heatingtemperatureatS9isadaptedtothedesiredDHWcharging temperatureatS10.IftheDHWchargingtemperatureatS10 cannotbereached,theECLcontrollergraduallyincreasesthe desiredDHWheatingtemperatureatS9inordertoobtaintheDHW chargingtemperature.TheECLcontrollerrememberstheadapted S9temperature.Amaximumtemperaturevaluecanbeset.
Adelayedstart
ofchargingpumpcanbearranged.Also,itcan bearranged,thatthestartofthechargingpumpdependsonthe chargingtemperature.Inthiscase,S10mustbeplacedinthe heat-exchanger.
TheS10temperaturesensorcanalternativelybeusedasamonitoring temperaturesensortoenableDHWcharging.Ifusedasamonitoring temperaturesensor,theS10temperaturesensormustbeplacedin thesupplypipe.
8|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Chargingstop,DHWtankwith1temperaturesensor:
WhenthemeasuredDHWtemperatureS6getshigherthan thecharging-stoptemperature,theDHWchargingpumpP4is switchedOFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors:
WhenthemeasuredDHWtemperatureS6gets2Khigherthan thecharging-starttemperatureANDthelowertanktemperature S8getshigherthanthecharging-stoptemperature,theDHW chargingpumpP4isswitchedOFF.Apost-runtimecanbeset.
DHWcirculation:
InchargingapplicationstheDHWcirculationcanbethrough theDHWtank(connectionA)orthroughtheheat-exchanger (connectionB). ThesolutionwithconnectionAresultsinclosingofthemotorized controlvalveaftertheDHWtankchargingprocedure. ThesolutionwithconnectionBstopstheDHWchargingpump aftertheDHWtankchargingprocedure.Thetemperatureatthe chargingtemperaturesensorismaintainedaccordingtothevalue ofthedesiredDHWtemperatureinordertocompensateforthe heatlossintheDHWcirculationpipe.
Flow/powerlimitation
AconnectedfloworenergymeterbasedonM-bussignalcanlimit thefloworpowertoasetmaximumvalue.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
TheDHWcirculationpumpP3hasaweekscheduleforupto3 ON-periodsperday.
TypicalA377.2application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem. AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor S2Returntemperaturesensor,circuit2 S3
Flowtemperaturesensor,circuit1 S4
Flowtemperaturesensor,circuit2 S5Returntemperaturesensor,circuit1 S6
DHWtanktemperaturesensor,upper
(S7)
(Externaltemperaturecontrol,notillustrated) S8
DHWtanktemperaturesensor,lower S9
DHWheatingtemperaturesensor,circuit3
S10
DHWchargingtemperaturesensor,circuit3
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit3
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
M3
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV) P1
DHWheatingpump P2
Circulationpump,heating,circuit1 P3
DHWcirculationpump P4
DHWchargingpump P5
Circulationpump,heating,circuit2
A1
Alarm
A/B
Internal/externalconnectionsforDHWcirculation
Charging-stoptemperature:
DesiredDHWtemperature+Stopdifference. Example,S6only: 50°C+(3K)=53°C Example,S6andS8: 50°C+(-8K)=42°C
AQ190786468664en-010802
©Danfoss|2021.12|9
OperatingGuideECLComfort310,applicationA377
A377.2examplea:
A377.2exampleb:
10|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
A377.3,ex.a
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2Returntemperaturesensor,circuit2
S3
Flowtemperaturesensor,circuit1
S4
Flowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
(S7)
(Externaltemperaturecontrol,notillustrated)
S8
DHWcirculationtemperaturesensor
S9
DHWheating/chargingtemperaturesensor
S10DHWreturntemperaturesensor,circuit3
M1
Motorizedcontrolvalve(3-pointcontrolled),circuit3
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
M3
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
P1
DHWheatingpump
P2
Circulationpump,heating,circuit1
P3
DHWcirculationpump
P4
DHWchargingpump
P5
Circulationpump,heating,circuit2
A1
Alarm
A/B
Internal/externalconnectionsforDHWcirculation
AQ190786468664en-010802
©Danfoss|2021.12|11
OperatingGuideECLComfort310,applicationA377
A377,ingeneral
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto oneECLcontrollerinordertomeasuretheroomtemperatureand controltheECLcontrollerremotely.
WhentheDHWcircuitisactivefortheheating/charging procedure,heatingcircuits1and2canbeclosedinordertogive higherprioritytotheDHWheating/charging.
HolidayprogramsarepresentforHeatingandDHWcircuits. Besides,aholidayprogramispresentfortheentirecontroller.
Oneormoreconnectedfloworenergymeters(basedonM-bus signal)canlimitthefloworpowertoasetmaximum(DHWcircuit) andinrelationtotheoutdoortemperature(heatingcircuits).
InputS7canbeusedtocontrolthedesiredflowtemperatureof heatingcircuit1.Theappliedvoltageintherange0-10voltis convertedintheECLcontrollertothedesiredflowtemperature.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout heatingdemandcanbearranged.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL 485businordertoutilizecommonoutdoortemperaturesignal, timeanddatesignals.TheECLcontrollersintheECL485system canworkinmaster-slavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beused tooverridethescheduletoafixed'Comfort' ,'Saving','Frost protection'or'Constanttemperature'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished. TheM-busdatacanfurthermorebetransferredtotheModbus communication.
Alarm:
AlarmA1(=relay6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow temperature
ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview).
WhentheA377hasbeenuploaded,theECLComfortcontroller startsinManualmode.Thiscanbeusedforcheckingthecontrolled componentsforcorrectfunctionality.
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
12|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
AQ190786468664en-010802
©Danfoss|2021.12|13
OperatingGuideECLComfort310,applicationA377
Adviceforsettings:
Factorysettingsinthesubtypeswillrunthemostapplication examples.Someoftheapplicationexamplesneedchangeof dedicatedsettings.
Seethedocumentationforapplicationsandsubtypes,delivered withtheapplicationkey.
A377.1,ex.a A377.1,ex.d A377.3,ex.a A377.3,ex.b
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(3):
InternalDHWcirculation
DHWcircuit(3):
ExternalDHWcirculation
A377.1,ex.b A377.1,ex.c
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2.
Issue:
Heatingcircuit(1):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit2.
Circuit2mustbeabletosendtheheatdemandtocircuit1.
Issue:
Heatingcircuit(2):
Heatdemand
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
Navigation:
MENU\Settings\Application:'Demandoffset'
Navigation:
MENU\Settings\Application:'SenddesiredT'
IDno.:
13054
13054
IDno.:
11017
IDno.:
12500
Recommended setting:
OFF
ON
Recommended setting:
3K*
Recommended setting:
ON
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(3):
InternalDHWcirculation
DHWcircuit(3):
ExternalDHWcirculation
14|©Danfoss|2021.12
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
13054
13054
Recommended setting:
OFF
ON
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Adviceforsettings:
A377.2,ex.a
Circuit1mustbeabletoreceivetheDHW-heatingdemandfrom circuit3.
Issue:
Heatingcircuit(1):
Heatdemand
*ThisvalueisaddedtotheDHW-heatingdemandfromcircuit3.
Circuit3mustbeabletosendtheDHW-heatingdemandto circuit1.
Issue:
DHWcircuit(3):
Heatdemand
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(3):
InternalDHWcirculation
DHWcircuit(3):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application:'Demandoffset'
Navigation:
MENU\Settings\Application:'SenddesiredT'
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
11017
IDno.:
13500
IDno.:
13054
13054
Recommended setting:
3K*
Recommended setting:
ON
Recommended setting:
OFF
ON
AQ190786468664en-010802
©Danfoss|2021.12|15
OperatingGuideECLComfort310,applicationA377
Adviceforsettings:
A377.2,ex.b A377.2,ex.c
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2 andtheDHW-heatingdemandfromcircuit3.
Issue:
Heatingcircuit(1):
Heatdemand
*Thisvalueisaddedtotheheatingdemandvaluecircuit2and3.
Circuit2mustbeabletosendtheheatdemandtocircuit1.
Issue:
Heatingcircuit(2):
Heatdemand
Circuit3mustbeabletosendtheDHW-heatingdemandto circuit1.
Issue:
DHWcircuit(3):
Heatdemand
Navigation:
MENU\Settings\Application:'Demandoffset'
Navigation:
MENU\Settings\Application:'SenddesiredT'
Navigation:
MENU\Settings\Application:'SenddesiredT'
IDno.:
11017
IDno.:
12500
IDno.:
13500
Recommended setting:
3K*
Recommended setting:
ON
Recommended setting:
ON
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(3):
InternalDHWcirculation
DHWcircuit(3):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
13054
13054
Recommended setting:
OFF
ON
16|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ190786468664en-010802
©Danfoss|2021.12|17
OperatingGuideECLComfort310,applicationA377
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
18|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
AQ190786468664en-010802
©Danfoss|2021.12|19
OperatingGuideECLComfort310,applicationA377
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
20|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
AQ190786468664en-010802
©Danfoss|2021.12|21
OperatingGuideECLComfort310,applicationA377
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
22|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
AQ190786468664en-010802
©Danfoss|2021.12|23
OperatingGuideECLComfort310,applicationA377
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
24|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
AQ190786468664en-010802
©Danfoss|2021.12|25
OperatingGuideECLComfort310,applicationA377
2.5.3Electricalconnections,safetythermostats,ingeneral
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
26|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
SeetheInstallationGuide(deliveredwiththeapplicationkey)for sensorandinputconnections.
A377:
Sen­sor
S1 S2Returntemperaturesensor
S3
S4
S5Returntemperaturesensor
S6
S7
S8
S9
(S9)
S10
Description
Outdoortemperaturesensor*
Flowtemperaturesensor**
Flowtemperaturesensor**
DHWtanktemperaturesensor, upper***
Voltagesignal(0-10V)for externalcontrolofdesiredflow temperature,heatingcircuit1
A377.1,A377.2: DHWtanktemperaturesensor, lower
A377.3: DHWcirculationreturn
A377.1,A377.3 DHWheating/charging temperaturesensor**
A377.2 DHWheatingtemperaturesensor**
A377.1,A377.3: AlternativepositionforDHW heating/chargingtemperature sensor**
A377.1,A377.3: DHWreturntemperature sensor**** Alternative:Supplytemperature sensor
A377.2: DHWchargingtemperature sensor****
Type (recomm.)
ESMT
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESMB/ ESMU
ESMB/ ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
*
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
**
Thesensormustalwaysbeconnectedinordertohavethe desiredfunctionality.Ifthesensorisnotconnectedorthe cableisshort-circuited,themotorizedcontrolvalvecloses (safetyfunction).
***
Thissensorisusedifonlyonetanktemperaturesensoris required.
****
Thesensormustalwaysbeconnectedinordertohavethe desiredfunctionality.
AQ190786468664en-010802
©Danfoss|2021.12|27
OperatingGuideECLComfort310,applicationA377
Connectionofvoltagesignal(0–10V)forexternalcontrolof desiredflowtemperature
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus) Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
28|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
2.5.5Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
AQ190786468664en-010802
©Danfoss|2021.12|29
OperatingGuideECLComfort310,applicationA377
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
30|©Danfoss|2021.12
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
AQ190786468664en-010802
©Danfoss|2021.12|31
OperatingGuideECLComfort310,applicationA377

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
32|©Danfoss|2021.12
ECLComfort296
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ190786468664en-010802
©Danfoss|2021.12|33
OperatingGuideECLComfort310,applicationA377
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
34|©Danfoss|2021.12
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
AQ190786468664en-010802
©Danfoss|2021.12|35
OperatingGuideECLComfort310,applicationA377
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
36|©Danfoss|2021.12
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
AQ190786468664en-010802
©Danfoss|2021.12|37
OperatingGuideECLComfort310,applicationA377
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
38|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
AQ190786468664en-010802
©Danfoss|2021.12|39
OperatingGuideECLComfort310,applicationA377

2.8Navigation,ECLApplicationKeyA377

Navigation,A377.1,circuits1,2and3
Home
MENU
Schedule
Schedulecirc.P Settings
Flowtemperature
Tanktemperature
Roomlimit
Returnlimit
Flow/powerlimit
Optimization
Controlpar.
ApplicationA377.1
IDnos.
1117812178 11177
1100412004
1118212182Infl.-max.(( 1118312183
1101512015
1103112031 1103212032 1103312033 1103412034 110351203513035 110361203613036 110371203713037 1108512085 11029 1102812028
1111912119 11117 1111812118 1111612116 111121211213112 111131211313113 111091210913109 11115 1101112011 1101212012 1101312013 1101412014 1102612026 1102012020 1102112021 1117912179 11174 111841218413184 111851218513185 111861218613186 111871218713187 111891218913189 110241202413024
12177
13193 13195 13194 13152
13030
12117
1211513115
1217413174
FunctionCircuit1Circuit2Circuit3
(((
Heatcurve Temp.max. Temp.min. Ext.desiredT DesiredT Chargedifference Startdifference Stopdifference Max.chargeT
Infl.-min. Adapt.time Limit HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,ret.Tlim. Actual Actuallimit HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Motorpr. Xp Tn Mrun Nz Min.act.time Actuator
(( (( (( ( ((
(( ((
(( ((
(( ((
((( ((( (((
((
( (( ((( ((( (( (( (( (( ((( ((( ((( ((( (( (( (( (( (( (( (( (( ((( ((( ((( ((( ((( (( ((
(
( ( ( (
(
( (
40|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Navigation,A377.1,circuits1,2and3,continued
Home MENU Settings
Holiday
Alarm
Application
Heatcut-out
Anti-bacteria
Temp.monitor.
Alarmoverview
IDnos.
1101012010 11017 11050 1150012500 1102212022 1102312023 1105212052 1107712077 1107812078 1104012040
110931209313093 11141 111421214213142 11393 11392 1117912179 1139512395 11397 11396 1139812398 1139912399
11147 111481214813148 111491214913149 111501215013150
1214113141
1214713147
ApplicationA377.1
FunctionCircuit1Circuit2Circuit3
ECAaddr. Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority PfrostT PheatT
Ppost-run 13055 13054 13056 13042 13500 13076
Circ.Ppriority
Cont.Tcontrol
SupplyTmon.
Char.Ppost-run
SenddesiredT
Circ.PfrostT
Frostpr.T
Ext.input
Ext.mode
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Win.start,month
Winter,cut-out
Winter,filter
Upperdifference
Lowerdifference
Delay
Lowesttemp.
((
(
(
((
((
((
((
((
((
((
(
(
(
(
(
(
(((
(((
(((
(
(
((
((
(
(
((
((
(
(((
(((
(((
(((
(((
(((
AQ190786468664en-010802
©Danfoss|2021.12|41
OperatingGuideECLComfort310,applicationA377
Navigation,A377.1,circuits1,2and3,continued
Home
MENU
InfluenceoverviewDes.flowT
Des.DHWT
IDnos.
ApplicationA377.1
FunctionCircuit1Circuit2Circuit3
((
(
Returnlim. Roomlim. Flow/powerlim. Holiday Ext.override Anti-bacteria ECAoverride Boost Ramp
Slave,demand Heatingcut-out DHWpriority
SCADAoffset SCADAoverride Ext.desiredT
(((
((
(((
(((
(((
(
((
((
((
(
((
((
((
(
(
42|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Navigation,applicationA377.1,Commoncontrollersettings
Home
MENU
Time&Date HolidaySelectable
Inputoverview1
Inputoverview2
Inputoverview3
Log1(sensors)
Log2(sensors)
Log3(sensors)
Outputoverride
OutdoorTLogtoday Heatingflow&des. HeatreturnT&limitLog2days
OutdoorTLogtoday Heatingflow&des. HeatreturnT
DHWflow&des. DHWreturn TankTup.&des.Log2days TankTup.&low.Log4days
ApplicationsA377.1,Commoncontrollersettings
IDno.
Function
Selectable
OutdoorT Outdooracc.T RoomT HeatflowT HeatreturnT Ext.desiredT OutdoorT Outdooracc.T RoomT HeatflowT HeatreturnT ChargeT DHWreturn TankupperT TanklowerT
Logyesterday
Log4days
Logyesterday Log2days Log4days Logtoday Logyesterday
M1 P1 M2 P2 M3 P5 P3 P4 A1
A377.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
AQ190786468664en-010802
©Danfoss|2021.12|43
OperatingGuideECLComfort310,applicationA377
Navigation,applicationsA377.1,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
ApplicationA377.1,Commoncontrollersettings
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview Alarm Display
Communication
Language
60058 60059
38
39 2048 2150 2151 2050
Function
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. Productiondate
Backlight Contrast Modbusaddr. Baud ECL485addr. Servicepin Ext.reset Language
A377.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
44|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Navigation,A377.2,circuits1,2and3
Home
MENU
Schedule Schedulecirc.P Settings
Flowtemperature
Tanktemperature
Roomlimit
Returnlimit
Flow/powerlimit
Optimization
Controlpar.
ApplicationA377.2
IDnos.
1117812178 11177
1100412004
1118212182Infl.-max.(( 1118312183
1101512015
1103112031 1103212032 1103312033 1103412034 1103512035 1103612036 1103712037 1108512085 11029 1102812028
1111912119 11117 1111812118 1111612116 1111212112 1111312113 1110912109 11115 1101112011 1101212012 1101312013 1101412014 1102612026 1102012020 1102112021 1117912179 11043 11174 111841218413184 111851218513185 111861218613186 111871218713187 111891218913189 110241202413024
12177
13193 13195 13194 13152 13068
13030
13111
12117
12115
1217413174
FunctionCircuit1Circuit2Circuit3
((
Heatcurve Temp.max. Temp.min. Ext.desiredT DesiredT Chargedifference Startdifference Stopdifference Max.chargeT FlowTadapttime
Infl.-min. Adapt.time Limit HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,ret.Tlim. Actual Actuallimit Limit HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Paralleloperation Motorpr. Xp Tn Mrun Nz Min.act.time Actuator
(( (( (( ( ((
(( ((
(( (( (( (( (( (( (( ((
( (( ((( ((
(( (( (( (( (( (( (( (( (( (( (( (( (( (( (( (( ( ((( ((( ((( ((( ((( (( ((
(
(
( ( ( ( (
(
(
( (
AQ190786468664en-010802
©Danfoss|2021.12|45
OperatingGuideECLComfort310,applicationA377
Navigation,A377.2,circuits1,2and3,continued
Home
MENU Settings
Holiday
Alarm
Application
Heatcut-out
Anti-bacteria
Temp.monitor.
Alarmoverview
IDnos.
1101012010 11017 11050 1150012500 1102212022 1102312023 1105212052 1107712077 1107812078 1104012040
110931209313093 11141 111421214213142 11393 11392 1117912179 1139512395 11397 11396 1139812398 1139912399
11147 111481214813148
111491214913149 111501215013150
1214113141
1214713147
ApplicationA377.2
Function
ECAaddr. Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority PfrostT PheatT
Ppost-run 13055 13054 13042 13059 13500 13076
Circ.Ppriority
Cont.Tcontrol
Char.Ppost-run
Pchargedelay
SenddesiredT
Circ.PfrostT
Frostpr.T
Ext.input
Ext.mode
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Win.start,month
Winter,cut-out
Winter,filter
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Circuit1Circuit2Circuit3
((
(
(
((
((
((
((
((
((
((
(
(
(
(
(
(
(((
(((
(((
(
(
((
((
(
(
((
((
(
(((
(((
(((
(((
(((
(((
46|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Navigation,A377.2,circuits1,2and3,continued
Home
MENU
InfluenceoverviewDes.flowT
Des.DHWT
IDnos.
ApplicationA377.2
Function
Returnlim. Roomlim. Flow/powerlim. Holiday Ext.override Anti-bacteria ECAoverride Boost Ramp Slave,demand Heatingcut-out DHWpriority DHWinfluence SCADAoffset SCADAoverride Ext.desiredT
Circuit1Circuit2Circuit3
((
(
((
((
(((
(((
(((
(
((
((
((
(
((
((
(
((
(
(
AQ190786468664en-010802
©Danfoss|2021.12|47
OperatingGuideECLComfort310,applicationA377
Navigation,applicationA377.2,Commoncontrollersettings
Home
MENU
Time&Date HolidaySelectable
Inputoverview1
Inputoverview2
Inputoverview3
Log1(sensors)
Log2(sensors)
Log3(sensors)
Outputoverride
OutdoorTLogtoday Heatingflow&des. HeatreturnT&limitLog2days
OutdoorTLogtoday Heatingflow&des. HeatreturnT
DHWflow&des. ChargeTLogyesterday TankTup.&des.Log2days TankTup.&low.Log4days
ApplicationsA377.2,Commoncontrollersettings
IDno.
Function
Selectable
OutdoorT Outdooracc.T RoomT HeatflowT HeatreturnT Ext.desiredT OutdoorT Outdooracc.T RoomT HeatflowT HeatreturnT DHWflowT ChargeT TankupperT TanklowerT
Logyesterday
Log4days
Logyesterday Log2days Log4days Logtoday
M1 P1 M2 P2 M3 P5 P3 P4 A1
A377.2
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
48|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Navigation,applicationsA377.2,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
ApplicationA377.2,Commoncontrollersettings
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview Alarm Display
Communication
Language
60058 60059
38
39 2048 2150 2151 2050
Function
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. Productiondate
Backlight Contrast Modbusaddr. Baud ECL485addr. Servicepin Ext.reset Language
A377.2
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
AQ190786468664en-010802
©Danfoss|2021.12|49
OperatingGuideECLComfort310,applicationA377
Navigation,A377.3,circuits1,2and3
Home
MENU
Schedule
Schedulecirc.P Settings
Flowtemperature
Tanktemperature
Roomlimit
Returnlimit
Flow/powerlimit
Optimization
Controlpar.
ApplicationA377.3
IDnos.
1117812178 11177
1100412004
1118212182Infl.-max.(( 1118312183
1101512015
1103112031 1103212032 1103312033 1103412034 110351203513035 110361203613036 110371203713037 1108512085 11029 1102812028
1111912119 11117 1111812118 1111612116 111121211213112 111131211313113 111091210913109 11115 1101112011 1101212012 1101312013 1101412014 1102612026 1102012020 1102112021 1117912179 11174 111841218413184 111851218513185 111861218613186 111871218713187 111891218913189 110241202413024
12177
13193 13195 13194 13152
13030
12117
1211513115
1217413174
FunctionCircuit1Circuit2Circuit3
(((
Heatcurve Temp.max. Temp.min. Ext.desiredT DesiredT Chargedifference Startdifference Stopdifference Max.chargeT
Infl.-min. Adapt.time Limit HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,ret.Tlim. Actual Actuallimit HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Motorpr. Xp Tn Mrun Nz Min.act.time Actuator
(( (( (( ( ((
(( ((
(( ((
(( ((
((( ((( (((
((
( (( ((( ((( (( (( (( (( ((( ((( ((( ((( (( (( (( (( (( (( (( (( ((( ((( ((( ((( ((( (( ((
(
( ( ( (
(
( (
50|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Navigation,A377.3,circuits1,2and3,continued
Home MENU Settings
Holiday
Alarm
Application
Heatcut-out
Anti-bacteria
Temp.monitor.
Alarmoverview
IDnos.
1101012010 11017 11050 1150012500 1102212022 1102312023 1105212052 1107712077 1107812078 1104012040
110931209313093 11141 111421214213142 11393 11392 1117912179 1139512395 11397 11396 1139812398 1139912399
11147 111481214813148 111491214913149 111501215013150
1214113141
1214713147
ApplicationA377.3
FunctionCircuit1Circuit2Circuit3
ECAaddr. Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority PfrostT PheatT
Ppost-run 13055 13054 13056 13042 13500 13076
Circ.Ppriority
Cont.Tcontrol
SupplyTmon.
Char.Ppost-run
SenddesiredT
Circ.PfrostT
Frostpr.T
Ext.input
Ext.mode
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Win.start,month
Winter,cut-out
Winter,filter
Upperdifference
Lowerdifference
Delay
Lowesttemp.
((
(
(
((
((
((
((
((
((
((
(
(
(
(
(
(
(((
(((
(((
(
(
((
((
(
(
((
((
(
(((
(((
(((
(((
(((
(((
AQ190786468664en-010802
©Danfoss|2021.12|51
OperatingGuideECLComfort310,applicationA377
Navigation,A377.3,circuits1,2and3,continued
Home
MENU
InfluenceoverviewDes.flowT
Des.DHWT
IDnos.
ApplicationA377.3
FunctionCircuit1Circuit2Circuit3
((
(
Returnlim. Roomlim. Flow/powerlim. Holiday Ext.override Anti-bacteria ECAoverride Boost Ramp
Slave,demand Heatingcut-out DHWpriority
SCADAoffset SCADAoverride Ext.desiredT
(((
((
(((
(((
(((
(
((
((
((
(
((
((
((
(
(
52|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Navigation,applicationA377.3,Commoncontrollersettings
Home
MENU
Time&Date HolidaySelectable
Inputoverview1
Inputoverview2
Inputoverview3
Log1(sensors)
Log2(sensors)
Log3(sensors)
Outputoverride
OutdoorTLogtoday Heatingflow&des. HeatreturnT&limitLog2days
OutdoorTLogtoday Heatingflow&des. HeatreturnT
DHWflow&des. DHWreturn TankTup.&des.Log2days TankTup.&low.Log4days
ApplicationsA377.3,Commoncontrollersettings
IDno.
Function
Selectable
OutdoorT Outdooracc.T RoomT HeatflowT HeatreturnT Ext.desiredT OutdoorT Outdooracc.T RoomT HeatflowT HeatreturnT ChargeT DHWreturn TankupperT TanklowerT
Logyesterday
Log4days
Logyesterday Log2days Log4days Logtoday Logyesterday
M1 P1 M2 P2 M3 P5 P3 P4 A1
A377.3
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
AQ190786468664en-010802
©Danfoss|2021.12|53
OperatingGuideECLComfort310,applicationA377
Navigation,applicationsA377.3,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
ApplicationA377.3,Commoncontrollersettings
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview Alarm Display
Communication
Language
60058 60059
38
39 2048 2150 2151 2050
Function
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. Productiondate
Backlight Contrast Modbusaddr. Baud ECL485addr. Servicepin Ext.reset Language
A377.3
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
54|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ190786468664en-010802
©Danfoss|2021.12|55
OperatingGuideECLComfort310,applicationA377

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
56|©Danfoss|2021.12
)
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
DHWcircuit
Overviewdisplay1informsabout: actualDHWtemperature,controllermode,desiredDHW temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout: stateofthecontrolledcomponents,actualDHWtemperature, (desiredDHWtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith Influenceindication:
AQ190786468664en-010802
©Danfoss|2021.12|57
OperatingGuideECLComfort310,applicationA377
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Examples:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
58|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled operationandincomfortmode.
Examples:
50
55
AQ190786468664en-010802
©Danfoss|2021.12|59
OperatingGuideECLComfort310,applicationA377

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
60|©Danfoss|2021.12
DamperOFF
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview oftheactualand(desired)temperaturesaswellastheactualstate ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
(30)
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
Flowtemperature
Desiredflowtemperature
--
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
AQ190786468664en-010802
©Danfoss|2021.12|61
OperatingGuideECLComfort310,applicationA377
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
62|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
AQ190786468664en-010802
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
©Danfoss|2021.12|63
OperatingGuideECLComfort310,applicationA377

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
64|©Danfoss|2021.12
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Ext.desiredT—(ECLComfort310)
Actual(actualfloworpower)
Extendedheatcut-outsetting
Extendedwintercut-outsetting
Day
Starttime
Duration
DesiredT
DesiredT(Desiredflowtemperature)
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Adapt.time(adaptiontime)
Demandoffset
Basedon(optimizationbasedonroom/outdoortemp.)
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Actuator
Pre-stop(optimizedstoptime)
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
DHW,ret.Tlimit
Limit(returntemp.limitation)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Ppost-run
Char.Ppost-run(DHWchargingpump,post-run)
Paralleloperation
Pdemand
DHWpriority(closedvalve/normaloperation)
1x00469
1x01096
1x01185
1x01286
1x01387
1x01487
1x01572
1x01796
1x02088
1x02188
1x02297
1x02397
1x02493
1x02689
1x02876
1x029
1x030
1x031
1x03278
1x03378
1x03478
1x03578
1x03679
1x03780
1x04098
1x04298
1x04389
1x05098
1x05299
Factorysettingsincircuit(s)
1
68
70
82
107
107
119
119
120
120
77
77
77
23
AQ190786468664en-010802
©Danfoss|2021.12|65
OperatingGuideECLComfort310,applicationA377
SettingIDPage
Cont.Tcontrol
Circ.Ppriority
SupplyTmon.
Pchargedelay(Chargingpump,delayedstart)
FlowTadapttime(Flowtemperature,adaptationtime)
Circ.PfrostT
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Max.chargeT(maximumheating/chargingtemperature)
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Infl.-max.(roomtemp.limitation,max.)
Infl.-min.(roomtemp.limitation,min.)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Chargedifference
Stopdifference
Startdifference
SenddesiredT
1x05499
1x05599
1x056100
1x059100
1x068109
1x076100
1x077101
1x078101
1x08580
1x093101
1x10982
1x111
1x11283
1x11383
1x115
1x11683
1x117
1x11884
1x11984
1x141
1x142102
1x147115
1x148116
1x149116
1x150
1x152109
1x174
1x177
1x17870
1x17990
1x18272
1x18373
1x18494
1x18594
1x18694
1x18794
1x18995
1x193109
1x194110
1x195112
1x500104
Factorysettingsincircuit(s)
1
82
83
84
101
117
93
70
23
66|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
AQ190786468664en-010802
©Danfoss|2021.12|67
OperatingGuideECLComfort310,applicationA377

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
68|©Danfoss|2021.12
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
TheECLComfort210/296/310controlstheDHWtemperature accordingtothedesiredflowtemperatureforexampleunderthe influenceofthereturntemperature.
ActualDHWtemp.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DesiredDHW temp.
AQ190786468664en-010802
©Danfoss|2021.12|69
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Flowtemperature
DesiredT(Desiredflowtemperature)
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow temperaturecanbeset. A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU >Settings>Returnlimit>'Con.T,ret.Tlim. '
1x004
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan beappliedtoaninputinordertooverridetoComfort,Saving,Frost ProtectionorConstanttemperature.Aslongasthecontact(switch) signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
70|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Externalsignalfordesiredflowtemperature
Avoltage(0-10V)canbeappliedtotheinputterminalS7inorder todeterminethedesiredflowtemperature.
ThemeasuredvoltageoninputS7mustbeconvertedtoa temperaturevaluebythecontroller.Whenthevoltagegetshigher, thedesiredflowtemperatureincreases.
Thefollowingsettingssetupthescaling.
MENU>Settings>Flowtemperature
Ext.desiredT—(ECLComfort310)
CircuitSettingrange
1
Theactualdesiredflowtemperatureisindicatedbytheunit°C.
Read-outonly
Factorysetting
Read-out:
--:
°C:
Externalvoltagesignalisnotconnected.
Externalvoltagesignalconvertedtodesiredflow temperature.
Pushthedialtoseethegraphandenterthevaluesetsfortheinput voltage(1and10volt)anddisplayeddesiredflowtemperature.
Example:Relationshipbetweeninputvoltageanddisplayeddesiredflow temperature
Desiredflowtemp.(°C)
Volt
Thisexampleshowsthat1voltcorrespondsto10.0°Cand10volt correspondto100°C.
Desiredflowtemperature:
10...120°C
Fixedvoltagesettings:1Vand10V Factorysettings:
(1,10)and(10,100)
Thismeansthatthe‘Desiredflowtemperature’is10°Cat1.0V and100°Cat10V.
Typically,thehigherthevoltage,thehigherthedisplayeddesired flowtemperature.
Theexternalvoltagesignalmustbehigherthan1.0Vinorderto activatetheoverride.
AQ190786468664en-010802
©Danfoss|2021.12|71
OperatingGuideECLComfort310,applicationA377

5.3Roomlimit

ThefollowingsectionisageneraldescriptionforRoom temperaturelimitation. Thissectionisonlyrelevantifyouhaveinstalledaroom temperaturesensororaRemoteControlUnitforutilizingtheroom temperaturesignal. Inthefollowingdescriptionisreferredto"flowtemperature"in general.
Thecontrolleradjuststhedesiredflowtemperaturetocompensate forthedifferencebetweenthedesiredandtheactualroom temperature.
Iftheroomtemperatureishigherthanthedesiredvalue,the desiredflowtemperaturecanbereduced. The'Infl.-max.'(Influence,max.roomtemp.)determineshow muchthedesiredflowtemperatureshouldbereduced. Usethisinfluencetypetoavoidatoohighroomtemperature. Thecontrollerwillallowforfreeheatgains,i.e.solarradiationor heatfromafireplaceetc.
Iftheroomtemperatureislowerthanthedesiredvalue,thedesired flowtemperaturecanbeincreased. The'Infl.-min.'(Influence,min.roomtemperature)determines howmuchthedesiredflowtemperatureshouldbeincreased. Usethisinfluencetypetoavoidatoolowroomtemperature. Thiscouldforexamplebecausedbywindysurroundings.
Atypicalsettingwillbe-4.0for'Infl.-max.'and4.0for'Infl.-min. '
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Roomlimit
Adapt.time(adaptiontime)
Controlshowfasttheactualroomtemperatureadaptstothedesiredroom temperature(Icontrol).
1x015
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe'Adapt. time'.
Minor
Thedesiredroomtemperatureisadaptedquickly.
value: Major
Thedesiredroomtemperatureisadaptedslowly.
value:
Theadaptationfunctioncancorrectthedesiredroomtemperature withmax.8Kxheatcurveslopevalue.
72|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Roomlimit
Infl.-max.(roomtemp.limitation,max.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (decreased)iftheactualroomtemperatureishigherthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
0.0:
-2.0:
-5.0:
-9.9:
Noinfluence Minorinfluence Mediuminfluence Maximuminfluence
1x182
=
X
#1#
#2#
#3#
Roomtemperature
=
Desiredroomtemperature
=
Negativeinfluence(1x082)whenactualroomtemp.getshigher thandesiredroomtemp.
=
Positiveinfluence(1x083)whenactualroomtemp.getslowerthan desiredroomtemp.
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x-4.0x1.8) –14.4degrees.
MENU>Settings>Roomlimit
Infl.-min.(roomtemp.limitation,min.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (increased)iftheactualroomtemperatureislowerthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
9.9:
5.0:
2.0:
0.0:
Maximuminfluence Mediuminfluence Minorinfluence Noinfluence
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x-4.0x1): –8.0degrees.
Example
1x183
Theactualroomtemperatureis2degreestoolow. The‘Infl.-min.’issetto4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x4.0x1.8)
14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x4.0x1):
8.0degrees.
AQ190786468664en-010802
©Danfoss|2021.12|73
OperatingGuideECLComfort310,applicationA377

5.4Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant temperaturevalue. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthesetlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
74|©Danfoss|2021.12
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
AQ190786468664en-010802
©Danfoss|2021.12|75
OperatingGuideECLComfort310,applicationA377
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
ThereturntemperaturelimitationfortheDHWcircuitisbasedonthe settingin'Limit(returntemp.limitation)' .
Theinfluencefactorsaresetintheheatingcircuit.
Ifthereturntemperaturelimitationvalueintheheatingcircuitis higherthanthereturntemperaturelimitationvalueintheDHWcircuit, thehighestvalueisused.
76|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Returnlimit
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
The"Con.T ,ret.Tlimit"isthereturntemperaturelimitationvaluewhenthe circuitissettooverridemodetype"Const.T"(=Constanttemperature).
SeeAppendix“ParameterIDoverview”
Value:Setthereturntemperaturelimitation
MENU>Settings>Returnlimit
DHW,ret.Tlimit
WhenanaddressedslaveisactiveinDHW-tankheating/charging,the returntemperaturelimitationinthemastercanbeset. Notes:
Themastercircuitmustbesettoreactonthedesiredflowtemperature intheslave(s).See"Demandoffset"(ID11017).
Theslave(s)mustbesettosendits/theirdesiredflowtemperatureto themaster.See"SenddesiredT"(ID1x500).
SeeAppendix“ParameterIDoverview”
OFF:
Noinfluencefromslaves.Thereturntemperature limitationisrelatedtosettingsin"Returnlimit" .
Value:
Returntemperaturelimitationvaluewhenslaveisin DHWtankheating/chargingoperation.
1x028
1x029
#1#=Master,exampleA266,address15 #2#=Slave,exampleA237,address9 #3#=Slave,exampleA367,address6
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe setvalue,thecontrollerautomaticallychangesthedesiredflow/ ducttemperaturetoobtainanacceptablereturntemperature.The influenceissetin'Infl.-max. 'and'Infl.-min.' .
SomeexamplesofapplicationswithDHW-tankheating/chargingare:
•A217,A237,A247,A367,A377
A377.2only:
ThereturntemperaturelimitationfortheDHWcircuitisbasedonthe settingin'Limit(returntemp.limitation)' .
Theinfluencefactorsaresetinheatingcircuit1.
AQ190786468664en-010802
©Danfoss|2021.12|77
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
1x031
1x032
1x033
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
1x034
78|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
1x035
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Thereturnlimitisactiveabove50°C. Theinfluenceissetto-2.0. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby-2.0x2=-4.0degrees.
Normally,thissettingislowerthan0indistrictheatingsystemsto avoidatoohighreturntemperature.
Typically,thissettingis0inboilersystemsbecauseahigherreturn temperatureisacceptable(seealso'Infl.-min. ').
AQ190786468664en-010802
©Danfoss|2021.12|79
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
Example
1x036
1x037
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
80|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

5.5Flow/powerlimit

Heatingcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2# #Y1#
#Y2#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
=
X
Y
#1#
#2#
#3#
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
AQ190786468664en-010802
©Danfoss|2021.12|81
OperatingGuideECLComfort310,applicationA377
DHWcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower. Whentheflow/powergetshigherthanthesetlimit,thecontroller graduallyreducesthedesiredflowtemperaturetoobtainan acceptablemax.floworpowerconsumption.
=
X
Y
#1#
#2#
#3#
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Inputtype
ChoiceofM-bussignalfromenergymeternumber1...5.Onlypossible inECLComfort310.
SeeAppendix“ParameterIDoverview”
OFF:
EM1...EM5:
NoM-bussignalacquired. Energymeternumber.
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
1x109
FloworpowerlimitationisbasedonM-bussignal(ECLComfort310 controllersonly).
82|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
1x111
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Flowvaluesareexpressedasl/horm³/h PowervaluesareexpressedaskW,MWorGW.
1x113
1x115
Listforsettingrangeof'Units': l/h m³/h kW MW GW
AQ190786468664en-010802
©Danfoss|2021.12|83
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
1x116
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
1x118
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
1x119
84|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377

5.6Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost','Optimizer','Totalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
AQ190786468664en-010802
©Danfoss|2021.12|85
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
86|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
=
X Y #1#
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
AQ190786468664en-010802
©Danfoss|2021.12|87
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
MENU>Settings>Optimization
Basedon(optimizationbasedonroom/outdoortemp.)
Theoptimizedstartandstoptimecanbebasedoneitherroomoroutdoor temperature.
SeeAppendix“ParameterIDoverview”
OUT:
Optimizationbasedonoutdoortemperature.Usethis settingiftheroomtemperatureisnotmeasured.
ROOM:
Optimizationbasedonroomtemperature,ifmeasured.
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
1x020
-5°C
small
88|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost protectionisstillactive,see'PfrostT' .
Totalstop=OFF
Totalstop=ON
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
1x026
Example:OptimizationofComfortfrom07:00-22:00
=
X #1# #2# #3# #4# #5#
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
AQ190786468664en-010802
©Danfoss|2021.12|89
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Optimization
Paralleloperation
ChoosewhethertheheatingcircuitistooperateindependenceoftheDHW circuit.Thisfunctionmightbeusefulifaninstallationhaslimitedpower orflow.
SeeAppendix“ParameterIDoverview”
OFF:
Independentparalleloperation,i.e.theDHWand theheatingcircuitsoperateindependentlyofeach other.ItmakesnodifferencewhetherthedesiredDHW temperaturecanbereachedornot.
Value:Dependentparalleloperation,i.e.thedesiredheating
temperaturedependsontheDHWdemand.Choose howmuchtheDHWtemperaturecandropbeforethe desiredheatingtemperaturehastobedecreased.
1x043
=
X
Y1
Y2
#1#
#2#
#3#
#4#
#5#
#6#
#7#
Time
=
Temperature
=
Temperature
=
Acceptabledeviation(Paralleloperation,1x043)
=
DesiredDHWtemperature
=
ActualDHWtemperature
=
Desiredheatingtemperature
=
Reducedheatingtemperature
=
100%paralleloperation
=
Paralleloperationwithdecreasedheatingtemperature
IftheactualDHWtemperaturedeviatesmorethanthesetvalue,the gearmotorM2intheheatingcircuitwillgraduallyclosetosuchan extentthattheDHWtemperaturestabilizesatthelowestacceptable value.
A377.2:
Whenparalleloperationcannotbeobtained,thecirculationpump incircuit1willbeswitchedoff.
90|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
Summer,cut-out
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
AQ190786468664en-010802
©Danfoss|2021.12|91
OperatingGuideECLComfort310,applicationA377

5.7Controlparameters

Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point controlsignal.
Valvecontrol: Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
92|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
Thermo-hydraulicactuator,ABV
Danfossthermo-actuatortypeABVisaslowactingvalveactuator. InsidetheABVanelectricheatcoilwillheatathermostaticelement whenanelectricsignalisapplied.Whenheatingthethermostatic elementitexpandsinordertomanagethecontrolvalve.
Twobasictypesareavailable:ABVNC(NormalClosed)andABVNO (normalopen).Forexample,ABVNCkeepsa2-portcontrolvalve closedwhennoopen-signalsareapplied.
Electricopen-signalscomefromtheelectronicoutputoftheECL Comfortcontrollerinordertomanagethecontrolvalve.When open-signalsareappliedtotheABVNC,thevalvegraduallyopens.
Open-signalsareintheECLComfortcontrollerexpressedas "Arrow-up"(open)anddisplayedatthevalvesymbol.
Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,relativelylongopen-signalscomefrom theECLComfortcontrollerinordertoincreasetheflow.Bythis, theflowtemperaturewillovertimebealignedwiththedesired temperature.
Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,relativelyshortopen-signalscomefromtheECL Comfortcontrollerinordertoreducetheflow.Again,theflow temperaturealigns,overtime,withthedesiredtemperature.
ThecontroloftheDanfossthermo-actuatortypeABVusesaunique designedalgorithmandisbasedonthePWMprinciple(Pulse WidthModulation),wherethedurationofthepulsedetermines themanagementofthecontrolvalve.Thepulsesarerepeated each10sec.
Aslongastheflowtemperaturecorrespondstothedesired temperature,thedurationoftheopen-signalswillremainconstant.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Actuator
ABV/GEAR
1x024
GEAR
Selectionofvalveactuatortype.
Whenselecting"ABV",thecontrolparameters:
•Motorprotection(ID1x174)
ABV:
GEAR:
AQ190786468664en-010802
DanfosstypeABV(thermoactuator). Gearmotorbasedactuator.
•Xp(ID1x184)
•Tn(ID1x185)
•Mrun(ID1x186)
•Nz(ID1x187)
•Min.act.time(ID1x189)
arenotconsidered.
©Danfoss|2021.12|93
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
1x174
Recommendedforductsystemswithvariableload.
1x184
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
94|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Criticaltimeperiod
Time
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
AQ190786468664en-010802
©Danfoss|2021.12|95
OperatingGuideECLComfort310,applicationA377

5.8Application

Thesection"Application"describesspecificapplicationrelated issues. Someoftheparameterdescriptionsareuniversalfordifferent applicationkeys.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Application
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Decidestheroomtemperaturesignaltransferandcommunicationwiththe RemoteControlUnit.
SeeAppendix“ParameterIDoverview”
OFF:
NoRemoteControlUnit.Onlyroomtemperaturesensor, ifany.
A:
B:
RemoteControlUnitECA30/31withaddressA. RemoteControlUnitECA30/31withaddressB.
1x010
TheRemoteControlUnitmustbesetaccordingly(AorB).
96|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Application
Demandoffset
Thedesiredflowtemperatureinheatingcircuit1canbeinfluencedbythe demandforadesiredflowtemperaturefromanothercontroller(slave)or anothercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredflowtemperatureincircuit1isnot influencedbythedemandofanyothercontroller(slave orcircuit2).
Value:
Thedesiredflowtemperatureisincreasedbytheset valuein‘Demandoffset’ ,ifthedemandoftheslave/ circuit2ishigher.
Heatingapplication
1x017
=
X
Y
#1#
#2#
#3#
Time
=
Desiredflowtemperatures
=
Demandoffset
=
Desiredflowtemperature,master
=
Desiredflowtemperature,slave
MENU>Settings>Application
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
'Demandoffset'withavalueistobeusedintheMastercontrolleronly.
Thefunctionof‘Demandoffset’cancompensateforheatlosses betweenmasterandslavecontrolledsystems.
Whensetting"Demandoffset"toavalue,thereturntemperature limitationwillreactaccordingtothehighestlimitationvalue(Heating /DHW).
1x022
OFF:
ON:
AQ190786468664en-010802
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat noon(12:14hours).
©Danfoss|2021.12|97
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Application
Mexercise(valveexercise)
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thevalveexerciseisnotactive.
Thevalveopensfor7minutesandclosesfor7minutes everythirddayatnoon(12:00hours).
MENU>Settings>Application
Ppost-run
Heatingapplications:
ThecirculationpumpintheheatingcircuitcanbeONforanumberof minutes(m)afterheatingstop.Heatingstopiswhenthedesiredflow temperaturegetslowerthanthesettingin'PheatT'(IDno.1x078).
Coolingapplications:
ThecirculationpumpinthecoolingcircuitcanbeONforanumberof minutes(m)aftercoolingstop.Coolingstopiswhenthedesiredflow temperaturegetshigherthanthesettingin'PcoolT'(IDno.1x070). ThisPpost-runfunctioncanutilizetheremainingenergyinforexamplea heatexchanger.
SeeAppendix“ParameterIDoverview”
1x023
1x040
0:
Thecirculationpumpstopsimmediatelyafterheating orcoolingstop.
Value:
ThecirculationpumpisONforthesettimeafterheating orcoolingstop.
MENU>Settings>Application
Char.Ppost-run(DHWchargingpump,post-run)
SettheDHWchargingpumppost-runtime(minutes).TheDHWcharging pumpcancontinuetobeswitchedONaftertheDHWheatingprocedurein ordertoutilizetheremainingheatintheheatexchanger.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
1x042
98|©Danfoss|2021.12
AQ190786468664en-010802
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Application
Pdemand
Thecirculationpumpinthemastercircuitcanbecontrolledinrelationto themastercircuit'sdemandorslavecircuit'sdemand.
SeeAppendix“ParameterIDoverview”
Heatingapplications:
OFF:
ThecirculationpumpisONwhenthedesiredflow temperatureintheheatingcircuitishigherthanthe valuesetin'PheatT'.
ON:
ThecirculationpumpisONwhenthedesiredflow temperaturefromslavesishigherthanthevaluesetin 'PheatT'.
Coolingapplications:
OFF:
ThecirculationpumpisONwhenthedesiredflow temperatureinthecoolingcircuitislowerthanthevalue setin'PcoolT'.
ON:
ThecirculationpumpisONwhenthedesiredflow temperaturefromslavesislowerthanthevaluesetin 'PcoolT'.
MENU>Settings>Application
1x050
Thecirculationpumpisalwayscontrolledaccordingtofrostprotection conditions.
DHWpriority(closedvalve/normaloperation)
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen DHWheating/chargingisactiveinthemaster.
SeeAppendix“ParameterIDoverview”
OFF:
Theflowtemperaturecontrolremainsunchanged duringactiveDHWheating/charginginthemaster controller.
ON:
Thevalveintheheatingcircuitisclosed*duringactive DHWheating/charginginthemastercontroller.
*Thedesiredflowtemperatureissettothevaluesetin ‘Frostpr.T’
MENU>Settings>Application
Cont.Tcontrol
ThedesiredDHWheating/chargingtemperaturecanbeloweredwhenthe DHWheating/chargingprocedurehaselapsed.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredheating/chargingtemperatureislowered to10°C.Typically,theDHWiscirculatedthroughthe DHWtank.
ON:
Thedesiredheating/chargingtemperatureislowered tothedesiredDHWtemperature.Typically,theDHW iscirculatedthroughtheheatexchangerinorderto compensatefortheheatlossintheDHWcirculation pipe.
1x052
Thissettingmustbeconsideredifthiscontrollerisaslave.
1x054
AQ190786468664en-010802
©Danfoss|2021.12|99
OperatingGuideECLComfort310,applicationA377
MENU>Settings>Application
Circ.Ppriority
ChoosewhethertheDHWcirculationpumpshouldbeONduringDHW heating.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWcirculationpumpisswitchedOFFduringDHW heating.
ON:
TheDHWcirculationpumpisnotswitchedOFFduring DHWheating.
MENU>Settings>Application
SupplyTmon.
SelectionoffunctionsrelatedtotemperaturesensorS10.
SeeAppendix“ParameterIDoverview”
OFF:
S10actsasreturntemperaturesensor. LimitationvalueandInfluencefactorsaresetas describedinthesection'Returnlimit' .
ON:
S10actsassupplytemperaturesensorandreturn temperaturesensor. A: Thesupplytemperatureismonitoredandenablesthe DHWcharging. B: Returntemperaturelimitfunction:Limitationvalue andinfluencefactorsaresetasdescribedinthesection 'Returnlimit' . Thereturntemperaturelimitationisactivated4minutes afterstartofDHWcharging.
1x055
Whenthe'Circ.Ppriority'issettoOFF ,theschedulefortheDHW circulationpumpisoverruled.
1x056
IfONisselected,thetemperaturesensorS10canbeplacedinthe supplyline.
TheDHWchargingpumpP4willstartwhenthesupplytemperature (S10)becomeshigherthantheDHWtanktemperature(S6).
Ifnoinfluencefromreturntemperaturelimitisdesired,theinfluence factorssetinIDnos.13035/13036mustbesetto0.0.
MENU>Settings>Application
Pchargedelay(Chargingpump,delayedstart)
ConditionsforswitchingtheDHWheating/chargingpumpONatDHW heating/chargingdemand. Correctsettingcanavoiddischarging.
SeeAppendix“ParameterIDoverview”
OFF:
DHWheating/chargingpumpisswitchedONwhen DHWheating/chargingtemperatureisOK.
0:
Value:
DHWheating/chargingpumpisswitchedON.
DHWheating/chargingpumpisswitchedONafterthe setnumberofminutes.
1x059
Whenthesetting"OFF"isselected,thetemperaturesensorforDHW heating/chargingmustbeplacedintheheat-exchanger.
100|©Danfoss|2021.12