Page 1

OperatingGuide
ECLComfort310,applicationA368
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................15
2.3Mounting...........................................................16
2.4Placingthetemperaturesensors................................20
2.5Electricalconnections.............................................22
2.6InsertingtheECLApplicationKey..............................34
2.7Checklist............................................................41
2.8Navigation,ECLApplicationKeyA368.........................42
3.0Dailyuse.........................................................55
3.1Howtonavigate...................................................55
3.2Understandingthecontrollerdisplay..........................56
3.3Ageneraloverview:Whatdothesymbolsmean?...........60
3.4Monitoringtemperaturesandsystem
components........................................................61
3.5Influenceoverview................................................62
3.6Manualcontrol.....................................................63
3.7Schedule............................................................64
4.0Settingsoverview............................................65
5.0Settings...........................................................68
5.1IntroductiontoSettings..........................................68
5.2Flowtemperature..................................................69
5.3Returnlimit.........................................................73
5.4Flow/powerlimit.................................................79
5.5Optimization........................................................83
5.6Controlparameters................................................90
5.7Pumpcontrol.......................................................94
5.8Refillwater..........................................................97
5.9Application.......................................................103
5.10Heatcut-out......................................................109
5.11Watermeter......................................................112
5.12Alarm..............................................................114
5.13Alarmoverview..................................................119
5.14Anti-bacteria......................................................120
6.0Commoncontrollersettings............................122
6.1Introductionto‘Commoncontrollersettings’..............122
6.2Time&Date.......................................................123
6.3Settings............................................................124
6.4Holiday............................................................125
6.5Inputoverview...................................................127
6.6Log.................................................................128
6.7Outputoverride..................................................129
6.8Alarm..............................................................130
6.9Keyfunctions.....................................................131
6.10System.............................................................133
7.0Miscellaneous................................................140
7.1ECA30/31setupprocedures.................................140
7.2Overridefunction................................................148
7.3Severalcontrollersinthesamesystem......................151
7.4Frequentlyaskedquestions....................................154
7.5Definitions........................................................157
7.6Type(ID6001),overview.......................................161
7.7Automatic/manualupdateoffirmware.....................162
7.8ParameterIDoverview..........................................163
©Danfoss|2021.12AQ189686468137en-010601|1
Page 2

OperatingGuideECLComfort310,applicationA368
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA368
(ordercodeno.087H3803).
TheECLApplicationKeyA368contains6subtypes,allapplicablein
ECLComfort310:
•A368.1:HeatingandDHWcontrol.Pumpforrefillwatercontrol
•A368.2:HeatingandDHWcontrol.Supplytemperaturecan
determinedesiredflowtemperature.Pumpforrefillwater
control
•A368.3:HeatingandDHWcontroland2pumpsforrefillwater
control.Pressuremonitoring
•A368.4:HeatingandDHWcontroland2pumpsforrefillwater
control.Supplytemperaturecandeterminedesiredflow
temperature.Pressuremonitoring
•A368.5:HeatingandDHWcontrol.2pumpsandflowmeter
forrefillwatercontrol.Pressureandsecondarytemperature
monitoring
•A368.6:HeatingandDHWcontrol.Pumpforrefillwatercontrol.
Secondarytemperaturemonitoring
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310for
advancedsolutions,e.g.M-bus,ModbusandEthernet(Internet)
communication.
TheApplicationKeyA368complieswithECLComfort310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin‘Commoncontrollersettings’in‘System’).
TheapplicationsA368.3,A368.4andA368.5workwiththeInternal
I/OmoduleECA32(ordercodeno.087H3202).
ECA32isplacedinthebasepartforECLComfort310.
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedforremotemonitoringandsetting.
ECLComfort310isavailableas:
•ECLComfort310,230volta.c.(087H3040)
•ECLComfort310B,230volta.c.(087H3050)
•ECLComfort310,24volta.c.(087H3044)
ThebasepartforECLComfort310,230voltand24volt:
•087H3230
TheB-typeshavenodisplayanddial.
TheB-typesareoperatedbymeansoftheremotecontrolunit
ECA30/31:
•ECA30(087H3200)
•ECA31(087H3201)
AdditionaldocumentationforECLComfort310,modulesand
accessoriesisavailableonhttp://danfoss.com/.
2|©Danfoss|2021.12
AQ189686468137en-010601
Page 3

OperatingGuideECLComfort310,applicationA368
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310/311:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
•Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AQ189686468137en-010601
©Danfoss|2021.12|3
Page 4

OperatingGuideECLComfort310,applicationA368
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
1
-
DisposalNote
Thissymbolontheproductindicatesthatitmaynot
bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back
schemefortherecyclingofelectricalandelectronic
equipment.
•Disposeoftheproductthroughchannelsprovided
forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws
andregulations.
2
Circuit2Parameterno.
174
4|©Danfoss|2021.12
AQ189686468137en-010601
Page 5

OperatingGuideECLComfort310,applicationA368
2.0Installation
2.1Beforeyoustart
TheECLapplicationkeyA368containsof6subtypes:A368.1,
A368.2,A368.3,A368.4,A368.5andA368.6.
The6differentapplicationsareheatingandDHWapplicationsin
variouscombinations.
Thebasicprinciplesforaheatingcircuit
(examplereferringtoA368.1)
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein
‘Comfort’or‘Saving’mode.Theweekschedulecanhaveupto3
‘Comfort’periods/day.Avalueforthedesiredroomtemperature
canbesetineachofthemodes.
InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
ThecirculationpumpsP3andP5areoperatedalternately.One
circulationpumpisusedasworkingpumpandtheothercirculation
pumpisusedassparepump.Thecirculationpumpinquestionis
ONatheatdemandoratfrostprotection.Thealternationtime
canbesetasanumberofdaysandasettimeontheshiftday.A
solutionwithasinglecirculationpumpcanalsobeselected.
BymeansofthepressuredifferenceswitchS7theECLcontroller
verifiesthatthecirculationpumpinquestionisoperating.
Ifanacceptablepressuredifferenceisnotdetected,theECL
controlleractivatesthealarmandshiftstheoperatingcommandto
theoppositecirculationpump.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
TheFrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
TheheatingcircuitcanbegraduallyorfullclosedduringDHW
heating
Thestaticpressureonthesecondaryside(consumerside)can1)
bemeasuredasa0-10Vsignal(fromapressuretransmitter)or2)
beaswitchsignalfromapressureswitch.
Incaseofatoolowpressure,therefillwaterfunctionwill
supplementwithwaterfromawatersourceorthesupplyside.The
refillpumpP4isswitchedONandtheON/OFFvalveV1opens.
TypicalA368.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S3
S4
S5
S6
S7
S8
S9
S10
P1
P2
P3
P4
P5
M1
M2
V1
A1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|5
Page 6

OperatingGuideECLComfort310,applicationA368
A368.3,A368.4andA368.5only:
TherefillpumpsP4andP7areoperatedalternately.Thealternation
timecanbesetasanumberofdays.
Asolutionwithasinglerefillpumpcanalsobeselected.
IncaseofnotreachedpressureatS10withinasettimeanalarm
willbegenerated.
A368.2andA368.4only:
ThesupplytemperatureS2candeterminethedesiredflow
temperature.
A368.3andA368only:
S11isusedformonitoringthepressureintheflowtotheheating
circuit.
A368.5only:
AflowmeterF1(pulsesignal)measurestheinjectedrefillwater.
S11isusedformonitoringthereturntemperaturefromtheheating
circuit.
A368.6only:
S2isusedformonitoringthereturntemperaturefromtheheating
circuit.
Heatingingeneral:
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
TypicalA368.1application:
ModbuscommunicationtoaSCADAsystemcanbeestablished.
AconnectedfloworenergymeterbasedonM-bussignalcan
limitthefloworpowertoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.
M-busdatacanbetransferredtotheModbuscommunication.
Overridefunction:
Bymeansofanexternalswitchorarelaycontactthescheduleof
theheatingcircuitcanbeoverriddento
•constantComfortmode
•constantSavingmode
•constantdesiredflowtemperature
•constantFrostprotectionmode
6|©Danfoss|2021.12
AQ189686468137en-010601
Page 7

OperatingGuideECLComfort310,applicationA368
ThebasicprinciplesforaDHWcircuit(circuit2):
(examplereferringtoA368.1)
IfthemeasuredDHWtemperature(S4)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’
or‘Saving’mode.Theweekschedulecanhaveupto3‘Comfort’
periods/day.
AvalueforthedesiredDHWtemperaturecanbesetineachof
themodes.
Thereturntemperature(S6)canbelimitedtoasetvalue.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
IfthedesiredDHWtemperaturecannotbereached,theheating
circuitcanbeclosedgraduallytoallowmoreenergytotheDHW
circuit.
ThecirculationpumpsP1andP2areoperatedalternately.One
circulationpumpisusedasworkingpumpandtheothercirculation
pumpisusedassparepump.Thecirculationpumpinquestionis
ONatDHWheatingdemandoratfrostprotection.Thealternation
timecanbesetasanumberofdaysandasettimeontheshiftday.
Asolutionwithasinglecirculationpumpcanalsobeselected.
BymeansofthepressuredifferenceS8(exceptA368.6)the
ECLcontrollerverifiesthatthecirculationpumpinquestionis
operating.
TheFrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworpowertoasetmaximumvalue.
A368.3,A368.4andA368.5only:
S13isusedformonitoringthepressureinthereturnfromtheDHW
circulation.
S14isusedformonitoringthepressureofthecoldwatersupply.
A368.6only:
S8isusedformonitoringthetemperatureinthereturnfromthe
DHWcirculation.
Overridefunction:
Bymeansofanexternalswitchorarelaycontactthescheduleof
theDHWcircuitcanbeoverriddento
•constantComfortmode
•constantSavingmode
•constantFrostprotectionmode
TypicalA368.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S3
S4
S5
S6
S7
S8
S9
S10
P1
P2
P3
P4
P5
M1
M2
V1
A1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|7
Page 8

OperatingGuideECLComfort310,applicationA368
A368,ingeneral:
TheheatingcircuitcanbegraduallyorfullclosedduringDHW
heating(slidingorfullDHWpriority).
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviathe
ECL485businordertoutilizecommonoutdoortemperature
signal,timeanddatesignals.
TheECLcontrollersintheECL485systemcanworkinmasterslavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdatacanfurthermorebetransferredtotheModbus
communication.
AlarmA1(=relay6)canbeactivatedif:
•Theactualflowtemperaturediffersfromthedesiredflow
temperature
•Theactivatedcirculationpumpdoesnotgenerateapressure
difference
•Therefillwaterfunctiondoesnotgenerateapressurewithin
apresettime
•Ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
•Iftheuniversalalarminput(s)S9/S12areactivated.
8|©Danfoss|2021.12
AQ189686468137en-010601
Page 9

OperatingGuideECLComfort310,applicationA368
TypicalA368.2application:
(HeatingandDHW)
TypicalA368.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
P1
P2
P3
P4
P5
M1
M2
V1
A1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
Supplytemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|9
Page 10

OperatingGuideECLComfort310,applicationA368
TypicalA368.3application:
(HeatingandDHW)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA368.3application:
Listofcomponents:
ECL310
ECL32
S1
S3
S4
S5
S6
S7
S8
S9
S10
S11
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
(Optional)Secondarypressuresensor,circuit1.For
monitoringpurpose
S12
S13
Alarminput
(Optional)DHWcirculationreturnpressuresensor.For
monitoringpurpose
S14
(Optional)Coldwatersupplypressuresensor.For
monitoringpurpose
S15
(Optional)Primarysupplypressuresensor.Formonitoring
purpose
S16
(Optional)Primaryreturnpressuresensor.Formonitoring
purpose
P1
P2
P3
P4
P5
P7
M1
M2
V1
A1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
10|©Danfoss|2021.12
AQ189686468137en-010601
Page 11

OperatingGuideECLComfort310,applicationA368
TypicalA368.4application:
(HeatingandDHW)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA368.4application:
Listofcomponents:
ECL310
ECL32
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
S11
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
Supplytemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
(Optional)Secondarypressuresensor,circuit1.For
monitoringpurpose
S12
S13
Alarminput
(Optional)DHWcirculationreturnpressuresensor.For
monitoringpurpose
S14
(Optional)Coldwatersupplypressuresensor.For
monitoringpurpose
S15
(Optional)Primarysupplypressuresensor.Formonitoring
purpose
S16
(Optional)Primaryreturnpressuresensor.Formonitoring
purpose
P1
P2
P3
P4
P5
P7
M1
M2
V1
A1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|11
Page 12

OperatingGuideECLComfort310,applicationA368
TypicalA368.5application:
(HeatingandDHW)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA368.5application:
Listofcomponents:
ECL310
ECL32
S1
S3
S4
S5
S6
S7
S8
S9
S10
S11
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
(Optional)Secondaryreturntemperaturesensor,
circuit1.Formonitoringpurpose
S12
S13
Alarminput
(Optional)DHWcirculationreturntemperaturesensor.For
monitoringpurpose
S14
(Optional)Coldwatersupplypressuresensor.For
monitoringpurpose
S15
(Optional)Primarysupplypressuresensor.Formonitoring
purpose
S16
(Optional)Primaryreturnpressuresensor.Formonitoring
purpose
F1
P1
P2
P3
P4
P5
P7
M1
M2
V1
A1
Refillwaterflowmeter
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
12|©Danfoss|2021.12
AQ189686468137en-010601
Page 13

OperatingGuideECLComfort310,applicationA368
TypicalA368.6application:
(HeatingandDHW)
TypicalA368.6application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S2
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
(Optional)Secondaryreturntemperaturesensor,
circuit1.Formonitoringpurpose
S3
S4
S5
S6
S7
S8
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
(Optional)DHWcirculationreturntemperaturesensor.For
monitoringpurpose
S9
S10
P1
P3
P4
P5
M1
M2
V1
A1
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|13
Page 14

OperatingGuideECLComfort310,applicationA368
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
14|©Danfoss|2021.12
AQ189686468137en-010601
Page 15

OperatingGuideECLComfort310,applicationA368
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Adviceforsettings:
Whencircuit1(heating)mustbeabletoreceiveatemperature
demandfromaslave:
MENU\Settings\Application:
'Demandoffset'(ID11017):3K*
WhenaheatingorDHWcircuitmustbeabletosendits
temperaturedemandtocircuit1orthemaster:
MENU\Settings\Application:
'SenddesiredT'(ID1x500):ON
WhenaheatingorDHWcircuitshouldnotsenditstemperature
demandtocircuit1orthemaster:
MENU\Settings\Application:
'SenddesiredT'(ID1x500):OFF
*Thisrecommendedvalueisaddedtothehighesttemperature
demandvaluefromthesub-circuitoraslave.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
AQ189686468137en-010601
©Danfoss|2021.12|15
Page 16

OperatingGuideECLComfort310,applicationA368
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
•onawall
•onaDINrail(35mm)
ECLComfort296canbemounted
•inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
16|©Danfoss|2021.12
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
AQ189686468137en-010601
Page 17

OperatingGuideECLComfort310,applicationA368
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
AQ189686468137en-010601
©Danfoss|2021.12|17
Page 18

OperatingGuideECLComfort310,applicationA368
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
•Mountingonawall,ECA30/31
•Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
18|©Danfoss|2021.12
AQ189686468137en-010601
Page 19

OperatingGuideECLComfort310,applicationA368
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
AQ189686468137en-010601
©Danfoss|2021.12|19
Page 20

OperatingGuideECLComfort310,applicationA368
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
20|©Danfoss|2021.12
AQ189686468137en-010601
Page 21

OperatingGuideECLComfort310,applicationA368
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ189686468137en-010601
©Danfoss|2021.12|21
Page 22

OperatingGuideECLComfort310,applicationA368
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage,
relaycontactsandtriacoutputsdonothavemutualsafetydistanceof
minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic
separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis
recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby
meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
22|©Danfoss|2021.12
AQ189686468137en-010601
Page 23

OperatingGuideECLComfort310,applicationA368
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ189686468137en-010601
©Danfoss|2021.12|23
Page 24

OperatingGuideECLComfort310,applicationA368
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic
relay)terminals
4(2)A/24Va.c.
(4Aforohmicload,2Afor
inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power
suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230
Va.c.from24Va.c.
24|©Danfoss|2021.12
AQ189686468137en-010601
Page 25

OperatingGuideECLComfort310,applicationA368
2.5.3Electricalconnections,safetythermostats,ingeneral
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Theconnectiondiagramsshowvarioussolutions/examples:
Safetythermostat,1–stepclosing:
Motorizedcontrolvalvewithoutsafetyfunction
Safetythermostat,1–stepclosing:
Motorizedcontrolvalvewithsafetyfunction
Safetythermostat,2–stepclosing:
Motorizedcontrolvalvewithsafetyfunction
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe
motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the
motorizedcontrolvalveisclosedgradually.Atahighertemperature
(theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve
closesthevalveimmediately.
AQ189686468137en-010601
©Danfoss|2021.12|25
Page 26

OperatingGuideECLComfort310,applicationA368
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
A368,Pt1000,ECL310
S1S2S3S4S5S6S7S8
A368.1
A368.2
A368.3
A368.4
A368.5
A368.6
✔
✔ ✔
✔
✔ ✔
✔
✔ ✔
✔
✔ ✔
✔
✔ ✔
✔
✔ ✔
✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔
✔ ✔
✔
✔ ✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔ ✔
Sensor
S1
Description
Outdoortemperature
Recommendedtype
ESMT
sensor*
S2
Supplyflowtemperature
sensor
S3
Flowtemperaturesensor**,
heating
S4
Flowtemperaturesensor**,
ESM-11/ESMB/
ESMC/ESMU
ESM-11/ESMB/
ESMC/ESMU
ESMB/ESMU
DHW
S5Returntemperaturesensor,
heating
S6Returntemperaturesensor,
DHW
S7
Differentialpressureswitch,
ESM-11/ESMB/
ESMC/ESMU
ESM-11/ESMB/
ESMC/ESMU
heating
S8
Differentialpressureswitch,
DHW
or
Returntemperaturesensor,
DHWcirculation
S9
S10
Alarmswitch
Pressuretransmitter(0–10
ESM-11/ESMB/
ESMC/ESMU
Vor4–20mA)orpressure
switch
*
Iftheoutdoortemperaturesensorisnotconnectedorthe
cableisshort-circuited,thecontrollerassumesthatthe
outdoortemperatureis0(zero)°C.
**
Theflowtemperaturesensormustalwaysbeconnected
inordertohavethedesiredfunctionality.Ifthesensoris
notconnectedorthecableisshort-circuited,themotorized
controlvalvecloses(safetyfunction).
26|©Danfoss|2021.12
Wirecrosssectionforsensorconnections:Min.0.4mm².
Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ189686468137en-010601
Page 27

OperatingGuideECLComfort310,applicationA368
Connectionofflowmeter
SeetheInstallationGuide(deliveredwiththeapplicationkey).
Connectionofflowswitchoralarmcontact/switch
ThealarmcontactactsasaNormallyClosed(NC)contact.The
set-upcanbechangedtoreactonaNormallyOpen(NO)contact.
SeeCircuit1>MENU>Alarm>Digital>Alarmvalue:
0=AlarmforNOcontact
1=AlarmforNCcontact
Connectionofpressuretransmitter
ScaleforconversionofvoltagetopressureissetintheECLComfort.
Thepressuretransmitterispoweredwith12-24Vd.c.
Outputtypes:0-10Vor4-20mA.
4-20mAsignalisconvertedtoa2-10Vsignalbymeansofa500
ohm(0,5W)resistor.
Connectionof2differentialpressureswitches
Connectionofalarmswitch,S9
Connectionofapressureswitch
AQ189686468137en-010601
©Danfoss|2021.12|27
Page 28

OperatingGuideECLComfort310,applicationA368
Connectionofpressuretransmitterwith0-10Voutput
Vd.c.:Thepressuretransmitterispoweredwith12-24Vd.c.
Connectionofpressuretransmitterwith4-20mAoutput
Vd.c.:Thepressuretransmitterispoweredwith12-24Vd.c.
The4-20mAsignalisconvertedtoa2-10Vsignalbymeansofthe
500ohm(0,5W)resistor.
Wirecrosssectionforsensorconnections:Min.0.4mm².
Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus)
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
28|©Danfoss|2021.12
AQ189686468137en-010601
Page 29

OperatingGuideECLComfort310,applicationA368
Pt1000temperaturesensorsandsignals
A368,ECA32
S11S12S13S14S15S16
A368.1
A368.2
A368.3
A368.4
A368.5
A368.6
✔
✔ ✔
✔
✔ ✔
SeealsotheA368MountingGuide.
Sensor
S11
Description
Heating,secondaryside,
returntemperaturesensor
or
Pressuretransmitter,0–10V
or4–20mA
S12
S13
Alarmswitch
DHWcirculation,return
temperaturesensor
or
Pressuretransmitter,0–10V
or4–20mA
S14Pressuretransmitter,0–10V
or4–20mA
S15Pressuretransmitter,0–10V
or4–20mA
S16Pressuretransmitter,0–10V
or4–20mA
ConnectionofalarmswitchS12
Recommendedtype
Temp.sensor:ESM-11/
ESMB/ESMC/ESMU
Temp.sensor:ESM-11/
ESMB/ESMC/ESMU
Wirecrosssectionforsensorconnections:Min.0.4mm².
Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus)
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ189686468137en-010601
©Danfoss|2021.12|29
Page 30

OperatingGuideECLComfort310,applicationA368
Pressuretransmitters
A368,ECA32
S11S12S13S14S15S16
A368.1
A368.2
A368.3
A368.4
A368.5
A368.6
Connectionofpressuretransmitterwith0-10Voutput
Vd.c.:Thepressuretransmitterispoweredwith12-24Vd.c.
✔
✔ ✔
✔
✔ ✔
✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔ ✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
✔
✔
✔ ✔
✔ ✔
SeealsotheA368MountingGuide.
Connectionofpressuretransmitterwith4-20mAoutput
Vd.c.:Thepressuretransmitterispoweredwith12-24Vd.c.
The4-20mAsignalisconvertedtoa2-10Vsignalbymeansofthe
500ohm(0,5W)resistor.
A368.5:
ECA32,connectionofwatermeter.Pulsetype,inputF1.
SeealsotheA368MountingGuide.
SeealsotheA368MountingGuide.
30|©Danfoss|2021.12
AQ189686468137en-010601
Page 31

OperatingGuideECLComfort310,applicationA368
2.5.5Electricalconnections,ECA30/31
Terminal
ECL
Terminal
ECA30/31
30
31
4
1
322
333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature
sensor*
Type
(recomm.)
Cable2x
twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL
Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A
progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible
toconnectanECA30/31toeachcircuit.Theelectricalconnections
aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller
ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage:
‘Applicationreq.newerECA’:
Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact
yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom
temperature.TheconnectedECA30/31willonlyfunctionasremote
control.
AQ189686468137en-010601
©Danfoss|2021.12|31
Page 32

OperatingGuideECLComfort310,applicationA368
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave
systemsviatheinternalECL485communicationbus(2xtwisted
paircable).
TheECL485communicationbusisnotcompatiblewiththeECL
businECLComfort110,200,300and301!
Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
Terminal
Description
Type
(recomm.)
30
Commonterminal
+12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/
slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x
twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike
this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe
master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections
ECLComfort296:GalvanicisolatedModbusconnections
ECLComfort310:GalvanicisolatedModbusconnections
32|©Danfoss|2021.12
MaximumrecommendedlengthoftheECL485bus:
200-81m=119m
AQ189686468137en-010601
Page 33

OperatingGuideECLComfort310,applicationA368
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented
ECLComfort296:Onboard,non-galvanicisolated.Max.cable
length50m.
ECLComfort310:Onboard,non-galvanicisolated.Max.cable
length50m.
AQ189686468137en-010601
©Danfoss|2021.12|33
Page 34

OperatingGuideECLComfort310,applicationA368
2.6InsertingtheECLApplicationKey
2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
•theapplicationanditssubtypes,
•currentlyavailablelanguages,
•factorysettings:e.g.schedules,desiredtemperatures,
limitationvaluesetc.Itisalwayspossibletorecoverthefactory
settings,
•memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight
beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired
DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display
brightnessetc.
34|©Danfoss|2021.12
ECLComfort296
AQ189686468137en-010601
Page 35

OperatingGuideECLComfort310,applicationA368
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
•Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about
thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;for20minutes
settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
AQ189686468137en-010601
©Danfoss|2021.12|35
Page 36

OperatingGuideECLComfort310,applicationA368
ApplicationKey:Situation1
Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed.
InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266
Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross"
isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm
Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date'
Turnandpushthedialtoselectand
change'Hours' ,'Minutes','Date',
'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’
Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer
andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure
AorBistakingplace:
A
TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey
toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B
TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot
containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
36|©Danfoss|2021.12
OnlyfactorysettingsfromtheECLApplicationKeywill
becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory
settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill
becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings)
willbecopiedtothecontroller.
AQ189686468137en-010601
Page 37

OperatingGuideECLComfort310,applicationA368
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory
settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2
Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the
currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
AQ189686468137en-010601
©Danfoss|2021.12|37
Page 38

OperatingGuideECLComfort310,applicationA368
ApplicationKey:Situation3
Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
•forsaving(backup)ofspecialuserandsystemsettings
•whenanotherECLComfortcontrollerofthesametype(210,
296or310)mustbeconfiguredwiththesameapplicationbut
user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ .
‘ECL’or‘KEY’willbeindicated.Choose
’ECL’orKEY’
Pushthedialrepeatedlytochoose
copydirection
Choose‘Systemsettings’or‘User
settings’
Pushthedialrepeatedlytochoose
‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’
TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser
settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
*
‘ECL’:
‘KEY’:
**
‘NO’:
‘YES’:
38|©Danfoss|2021.12
DatawillbecopiedfromtheApplicationKeytothe
ECLController.
DatawillbecopiedfromtheECLControllertothe
ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied
totheApplicationKeyortotheECLComfortcontroller.
Specialsettings(differingfromthefactorysettings)will
becopiedtotheApplicationKeyortotheECLComfort
controller.IfYEScannotbechosen,therearenospecial
settingstobecopied.
AQ189686468137en-010601
Page 39

OperatingGuideECLComfort310,applicationA368
Language
Atapplicationupload,alanguagemustbeselected.*
IfanotherlanguagethanEnglishisselected,theselectedlanguage
ANDEnglishwillbeuploadedintotheECLcontroller.
ThismakesserviceeasyforEnglishspeakingservicepeople,just
becausetheEnglishlanguagemenuscanbevisiblebychanging
theactualsetlanguageintoEnglish.
(Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe
erased.UserandSystemsettingscanbesavedontheapplication
keybeforeerasing.
Afternewuploadwithpreferredlanguage,theexistingUserand
Systemsettingscanbeuploaded.
*)
(ECLComfort310,24Volt)Iflanguagecannotbeselected,the
powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck
andadjustallorsomeofthebasicsettings.Thenewsettingscan
bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave
beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe
ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation
1:Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3:
Acopyofthecontrollerssettingsisneededforconfiguringanother
controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin
thecontroller.IftheKeyisremoved,itisnotpossibletochange
settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon
theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto
anothercontrollerprovidedthatthetwocontrollersarefromthesame
series(210or310).
Furthermore,whentheECLComfortcontrollerhasbeenuploaded
withanapplicationkey,minimumversion2.44,itispossibletoupload
personalsettingsfromapplicationkeys,minimumversion2.14.
AQ189686468137en-010601
©Danfoss|2021.12|39
Page 40

OperatingGuideECLComfort310,applicationA368
The“Keyoverview”doesnotinform—throughECA30/31—about
thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;for20minutes
settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
40|©Danfoss|2021.12
AQ189686468137en-010601
Page 41

OperatingGuideECLComfort310,applicationA368
2.7Checklist
IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected:
230V:Live=terminal9andNeutral=terminal10
24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour
requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled
components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
AQ189686468137en-010601
©Danfoss|2021.12|41
Page 42

OperatingGuideECLComfort310,applicationA368
2.8Navigation,ECLApplicationKeyA368
Navigation,applicationA368.1andA368.3,circuit1and2
Home
IDno.
MENU
ScheduleSelectableSelectable
Settings
Flowtemperature
11178
11177
11004
Returnlimit
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
Flow/powerlimitActualActual
11119
11117
11118
11116
11112
11113
11109
11115
Optimization
Controlpar.
11011
11012
11013
11014
11026
11021
11179
11043
11174
11184
11185
11186
11187
11189
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve
Temp.max.
Temp.min.
DesiredT
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time
Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Adapt.time
Filterconstant
Inputtype
Units
Autosaving
Boost
Ramp
Optimizer
Prestop
Totalstop
Summer,cut-out
Paralleloperation
Motorpr.
Xp
Tn
Mrun
Nz
Min.act.time
IDno.
12178
12177
12030
12035
12036
12037
12085
12111
12112
12113
12109
12115
12173
12174
12184
12185
12186
12187
12189
Function
Temp.max.
Temp.min.
Limit
Infl.-max.
Infl.-min.
Adapt.time
Priority
Limit
Adapt.time
Filterconstant
Inputtype
Units
Autotuning
Motorpr.
Xp
Tn
Mrun
Nz
Min.act.time
42|©Danfoss|2021.12
AQ189686468137en-010601
Page 43

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.1andA368.3,circuit1andcircuit2continued
Home
MENU
Settings
HolidaySelectableSelectable
Alarm
Pumpcontrol
Refillwater
Application
Heatcut-out
Anti-bacteria
Temp.monitor.
Clearalarm
AlarmoverviewSelectableSelectable
IDno.
11314
11310
11313
11311
11312
11022
11327
11323
11321
11322
11320
11325
11326
11316
11017
11500
11023
11052
11077
11078
11093
11141
11142
11393
11392
11179
11395
11397
11396
11398
11399
11147
11148
11149
11150
11315
11324
Circuit1,HeatingCircuit2,DHW
Function
Chan.-overtime
Retrytime
Stab.time
Change,duration
Changetime
Pexercise
Pressure
Inputtype
Time-out
Pressure,des.
Pressure,diff.
Pexercise
Valvedelay
No.ofpumps
Alarmhandling
Demandoffset
SenddesiredT
Mexercise
DHWpriority
PfrostT
PheatT
Frostpr.T
Ext.input
Ext.mode
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Win.start,month
Winter,cut-out
Winter,filter
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Circ.pumps
Refillwater
IDno.
12314
12310
12313
12311
12312
12022
12500
12023
12077
12078
12093
12141
12142
12147
12148
12149
12150
12315
Function
Chan.-overtime
Retrytime
Stab.time
Change,duration
Changetime
Pexercise
SenddesiredT
Mexercise
PfrostT
PheatT
Frostpr.T
Ext.input
Ext.mode
Day
Starttime
Duration
DesiredT
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Circ.pumps
AQ189686468137en-010601
©Danfoss|2021.12|43
Page 44

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.1andA368.3,circuit1andcircuit2continued
Home
MENU
InfluenceoverviewDes.flowTReturnlim.Returnlim.
IDno.
Circuit1,HeatingCircuit2,DHW
Function
Parallelpriority
Flow/powerlim.Flow/powerlim.
HolidayHoliday
Ext.overrideExt.override
Boost
Ramp
Slave,demand
Heatingcut-out
DHWpriority
IDno.
Function
Anti-bacteria
44|©Danfoss|2021.12
AQ189686468137en-010601
Page 45

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.1andA368.3;Commoncontrollersettings(*A368.3only)
Home
MENU
Time&Date
Settings*
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
AlarmDigitalS9Alarmvalue
Keyfunctions
SystemECLversion
OutdoorTLogtoday
Heatingflow&des.
DHWflow&des.
HeatreturnT&limitLog4days
DHWreturnT&limit
Staticpressure
DigitalS12*Alarmtime-out
AlarmoverviewDigitalS9,digitalS12*
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet
Portalconfig
M-busconfig
EnergyMeters
Rawinputoverview
Alarm
Display
Communication
Language
Commoncontrollersettings
IDno.
60058
60059
2048
38
39
2150
2151
2050
Function
Selectable
S11,S13...S16press.sensor
OutdoorT
HeatflowT
DHWflowT
HeatreturnT
DHWreturnT
Staticpressure
S11,S13...S16pressure*
S7,S8,S9,S12*status
Logyesterday
Log2days
M1,P1,P2,M2,P3,P5,V1,P4,
P7*,A1
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Buildno.
Serialno.
MAC
Productionweek
Selectable
Selectable
Selectable
Selectable
Backlight
Contrast
ECL485addr.
Modbusaddr.
Baud
Servicepin
Ext.reset
Language
AQ189686468137en-010601
©Danfoss|2021.12|45
Page 46

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.2andA368.4,circuit1and2
Home
IDno.
MENU
ScheduleSelectableSelectable
Settings
Flowtemperature
11178
11177
11300
11301
11302
11303
11004
Returnlimit
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
Flow/powerlimitActualActual
11119
11117
11118
11116
11112
11113
11109
11115
Optimization
Controlpar.
11011
11012
11013
11014
11026
11021
11179
11043
11174
11184
11185
11186
11187
11189
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve
Temp.max.
Temp.min.
Highsupp.TX2
HighTmaxY2
LowsupplyTX1
LowTmaxY1
DesiredT
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time
Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Adapt.time
Filterconstant
Inputtype
Units
Autosaving
Boost
Ramp
Optimizer
Prestop
Totalstop
Summer,cut-out
Paralleloperation
Motorpr.
Xp
Tn
Mrun
Nz
Min.act.time
IDno.
12178
12177
12030
12035
12036
12037
12085
12111
12112
12113
12109
12115
12173
12174
12184
12185
12186
12187
12189
Function
Temp.max.
Temp.min.
Limit
Infl.-max.
Infl.-min.
Adapt.time
Priority
Limit
Adapt.time
Filterconstant
Inputtype
Units
Autotuning
Motorpr.
Xp
Tn
Mrun
Nz
Min.act.time
46|©Danfoss|2021.12
AQ189686468137en-010601
Page 47

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.2andA368.4,circuit1andcircuit2continued
Home
MENU
Settings
HolidaySelectableSelectable
Alarm
Pumpcontrol
Refillwater
Application
Heatcut-out
Anti-bacteria
Temp.monitor.
Clearalarm
AlarmoverviewSelectableSelectable
IDno.
11314
11310
11313
11311
11312
11022
11327
11323
11321
11322
11320
11325
11326
11316
11017
11500
11023
11052
11077
11078
11093
11141
11142
11393
11392
11179
11395
11397
11396
11398
11399
11147
11148
11149
11150
11315
11324
Circuit1,HeatingCircuit2,DHW
Function
Chan.-overtime
Retrytime
Stab.time
Change,duration
Changetime
Pexercise
Pressure
Inputtype
Time-out
Pressure,des.
Pressure,diff.
Pexercise
Valvedelay
No.ofpumps
Alarmhandling
Demandoffset
SenddesiredT
Mexercise
DHWpriority
PfrostT
PheatT
Frostpr.T
Ext.input
Ext.mode
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Win.start,month
Winter,cut-out
Winter,filter
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Circ.pumps
Refillwater
IDno.
12314
12310
12313
12311
12312
12022
12500
12023
12077
12078
12093
12141
12142
12147
12148
12149
12150
12315
Function
Chan.-overtime
Retrytime
Stab.time
Change,duration
Changetime
Pexercise
SenddesiredT
Mexercise
PfrostT
PheatT
Frostpr.T
Ext.input
Ext.mode
Day
Starttime
Duration
DesiredT
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Circ.pumps
AQ189686468137en-010601
©Danfoss|2021.12|47
Page 48

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.2andA368.4,circuit1andcircuit2continued
Home
MENU
InfluenceoverviewDes.flowT
IDno.
Circuit1,HeatingCircuit2,DHW
Function
Returnlim.Returnlim.
Parallelpriority
Flow/powerlim.Flow/powerlim.
HolidayHoliday
Ext.overrideExt.override
Boost
Ramp
Slave,demand
Heatingcut-out
DHWpriority
IDno.
Function
Anti-bacteria
48|©Danfoss|2021.12
AQ189686468137en-010601
Page 49

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.2andA368.4,Commoncontrollersettings(*A368.4only)
Home
MENU
Time&Date
Settings*
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
AlarmDigitalS9Alarmvalue
Keyfunctions
SystemECLversion
OutdoorTLogtoday
SupplyTLogyesterday
Heatingflow&des.
DHWflow&des.
HeatreturnT&limit
DHWreturnT&limit
Staticpressure
DigitalS12*Alarmtime-out
AlarmoverviewDigitalS9,digitalS12*
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet
Portalconfig
M-busconfig
EnergyMeters
Rawinputoverview
Alarm
Display
Communication
Language
Commoncontrollersettings
IDno.
60058
60059
2048
38
39
2150
2151
2050
Function
Selectable
S11,S13...S16press.sensor
OutdoorT
SupplyT
HeatflowT
DHWflowT
HeatreturnT
DHWreturnT
Staticpressure
S11,S13...S16pressure*
S7,S8,S9,S12*status
Log2days
Log4days
M1,P1,P2,M2,P3,P5,V1,P4,
P7*,A1
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Buildno.
Serialno.
MAC
Productionweek
Selectable
Selectable
Selectable
Selectable
Backlight
Contrast
ECL485addr.
Modbusaddr.
Baud
Servicepin
Ext.reset
Language
AQ189686468137en-010601
©Danfoss|2021.12|49
Page 50

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,circuit1and2
Home
IDno.
MENU
ScheduleSelectableSelectable
Settings
Flowtemperature
11178
11177
11004
Returnlimit
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
Flow/powerlimitActualActual
11119
11117
11118
11116
11112
11113
11109
11115
Optimization
Controlpar.
11011
11012
11013
11014
11026
11021
11179
11043
11174
11184
11185
11186
11187
11189
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve
Temp.max.
Temp.min.
DesiredT
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time
Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Adapt.time
Filterconstant
Inputtype
Units
Autosaving
Boost
Ramp
Optimizer
Prestop
Totalstop
Summer,cut-out
Paralleloperation
Motorpr.
Xp
Tn
Mrun
Nz
Min.act.time
IDno.
12178
12177
12030
12035
12036
12037
12085
12111
12112
12113
12109
12115
12173
12174
12184
12185
12186
12187
12189
Function
Temp.max.
Temp.min.
Limit
Infl.-max.
Infl.-min.
Adapt.time
Priority
Limit
Adapt.time
Filterconstant
Inputtype
Units
Autotuning
Motorpr.
Xp
Tn
Mrun
Nz
Min.act.time
50|©Danfoss|2021.12
AQ189686468137en-010601
Page 51

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,circuit1andcircuit2continued(*A368.5only)
Home
MENU
Settings
HolidaySelectableSelectable
Alarm
Pumpcontrol
Refillwater
Application
Heatcut-out
Watermeter*
Anti-bacteria
Temp.monitor.
Clearalarm*
AlarmoverviewSelectableSelectable
IDno.
11314
11310
11313
11311
11312
11022
11327
11323
11321
11322
11320
11325
11326
11316
11017
11500
11023
11052
11077
11078
11093
11141
11142
11393
11392
11179
11395
11397
11396
11398
11399
11513
11514
11147
11148
11149
11150
11315
11324
Circuit1,HeatingCircuit2,DHW
Function
Chan.-overtime
Retrytime
Stab.time
Change,duration
Changetime
Pexercise
Pressure
Inputtype
Time-out
Pressure,des.
Pressure,diff.
Pexercise
Valvedelay
No.ofpumps
Alarmhandling
Demandoffset
SenddesiredT
Mexercise
DHWpriority
PfrostT
PheatT
Frostpr.T
Ext.input
Ext.mode
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Win.start,month
Winter,cut-out
Winter,filter
Consump.
Pulsevalue
Preset
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Circ.pumps*
Refillwater*
IDno.
12314
12310
12313
12311
12312
12022
12500
12023
12077
12078
12093
12141
12142
12147
12148
12149
12150
12315
Function
Chan.-overtime*
Retrytime*
Stab.time*
Change,duration*
Changetime*
Pexercise*
SenddesiredT
Mexercise
PfrostT
PheatT
Frostpr.T
Ext.input
Ext.mode
Day
Starttime
Duration
DesiredT
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Circ.pumps*
AQ189686468137en-010601
©Danfoss|2021.12|51
Page 52

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,circuit1andcircuit2continued
Home
MENU
InfluenceoverviewDes.flowT
IDno.
Circuit1,HeatingCircuit2,DHW
Function
Returnlim.Returnlim.
Parallelpriority
Flow/powerlim.Flow/powerlim.
HolidayHoliday
Ext.overrideExt.override
Boost
Ramp
Slave,demand
Heatingcut-out
DHWpriority
IDno.
Function
Anti-bacteria
52|©Danfoss|2021.12
AQ189686468137en-010601
Page 53

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,Commoncontrollersettings(*A368.5only)
Home
MENU
Time&Date
Settings*
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
AlarmDigitalS9Alarmvalue
Keyfunctions
OutdoorTLogtoday
Heatingflow&des.
HeatreturnT&limitLog2days
Heatsec.returnT
DHWflow&des.
DHWreturnT&lim.
Circ.returnT
Staticpressure
DigitalS12*Alarmtime-out
AlarmoverviewDigitalS9,digitalS12*
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Commoncontrollersettings
IDno.
Function
Selectable
S14,S15,S16press.sensor
OutdoorT
HeatflowT
HeatreturnT
Heatsec.returnT
DHWflowT
DHWreturnT
Circ.returnT
Staticpressure
S14,S15,S16pressure*
S7,S8*,S9,S12*status
Consump.*
Logyesterday
Log4days
M1,P1,P2,M2,P3,P5,V1,P4,
P7*,A1
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
AQ189686468137en-010601
©Danfoss|2021.12|53
Page 54

OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,Commoncontrollersettings(*A368.5only)
Home
MENU
SystemECLversion
Extension
Ethernet
Portalconfig
M-busconfig
EnergyMeters
Rawinputoverview
Alarm
Display
Communication
Language
Commoncontrollersettings
IDno.
60058
60059
2048
38
39
2150
2151
2050
Function
Codeno.
Hardware
Software
Buildno.
Serialno.
MAC
Productionweek
Selectable
Selectable
Selectable
Selectable
Backlight
Contrast
ECL485addr.
Modbusaddr.
Baud
Servicepin
Ext.reset
Language
54|©Danfoss|2021.12
AQ189686468137en-010601
Page 55

OperatingGuideECLComfort310,applicationA368
3.0Dailyuse
3.1Howtonavigate
Younavigateinthecontrollerbyturningthedialleftorrightto
thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the
fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay(
youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One
heatingcircuit()andonedomestichot-water(DHW)circuit().
Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare
locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ189686468137en-010601
©Danfoss|2021.12|55
Page 56

OperatingGuideECLComfort310,applicationA368
3.2Understandingthecontrollerdisplay
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault
display.Thefavoritedisplaywillgiveyouaquickoverviewofthe
temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill
reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay
selector(
turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout:
actualoutdoortemperature,controllermode,
actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout:
actualoutdoortemperature,trendinoutdoortemperature,
controllermode,max.andmin.outdoortemperaturessince
midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout:
date,actualoutdoortemperature,controllermode,time,desired
roomtemperatureaswellasshowsthecomfortscheduleofthe
currentday.
Overviewdisplay4informsabout:
stateofthecontrolledcomponents,actualflowtemperature,
(desiredflowtemperature),controllermode,returntemperature
(limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue
signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe
circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith
Influenceindication:
Example,favoritedisplay1in
A230.3,wheremin.desiredroom
temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe
heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
56|©Danfoss|2021.12
)
AQ189686468137en-010601
Page 57

OperatingGuideECLComfort310,applicationA368
Thesettingofthedesiredroomtemperatureisimportantevenifa
roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
DHWcircuit
Overviewdisplay1informsabout:
actualDHWtemperature,controllermode,desiredDHW
temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout:
stateofthecontrolledcomponents,actualDHWtemperature,
(desiredDHWtemperature),controllermode,returntemperature
(limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW
circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter
alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe
nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith
Influenceindication:
AQ189686468137en-010601
©Danfoss|2021.12|57
Page 58

OperatingGuideECLComfort310,applicationA368
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe
overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual
roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange
thedesiredroomtemperatureforsavingmode,choosethemode
selectorandselectsaving.
Examples:
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa
roomtemperaturesensor/RemoteControlUnitisnotconnected.
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe
overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW
temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled
operationandincomfortmode.
Examples:
50
55
58|©Danfoss|2021.12
AQ189686468137en-010601
Page 59

OperatingGuideECLComfort310,applicationA368
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe
controller.However,othersymbolscanbepresentinthedisplay
(pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom
temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
AQ189686468137en-010601
©Danfoss|2021.12|59
Page 60

OperatingGuideECLComfort310,applicationA368
3.3Ageneraloverview:Whatdothesymbolsmean?
Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor
connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+)
Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses
Actuator,analoguecontrol
signal
Pump/fanspeed
DamperON
Circuit
Controlled
component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin
thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
60|©Danfoss|2021.12
DamperOFF
AQ189686468137en-010601
Page 61

OperatingGuideECLComfort310,applicationA368
3.4Monitoringtemperaturesandsystemcomponents
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick
overviewoftheactualand(desired)temperaturesaswellasthe
actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview
oftheactualand(desired)temperaturesaswellastheactualstate
ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
(30)
Flowtemperature
Desiredflowtemperature
Returntemperature
Returntemperaturelimitation
Flowtemperature
Desiredflowtemperature
--
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures
isthe'Inputoverview'whichisvisibleinthecommoncontroller
settings(howtoenterthecommoncontrollersettings,see
‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured
actualtemperatures,itisread-only.
AQ189686468137en-010601
©Danfoss|2021.12|61
Page 62

OperatingGuideECLComfort310,applicationA368
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Themenugivesanoverviewoftheinfluencesonthedesired
flowtemperature.Itdiffersfromapplicationtoapplicationwhich
parametersarelisted.Itcanbehelpfulinaservicesituationto
explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor
moreparameters,itisindicatedbyasmalllinewitharrow-down,
arrow-upordouble-arrow:
Arrow-down:
Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up:
Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow:
Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline:
Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor
'Roomlim. ' .Thismeansthattheactualroomtemperatureis
higherthanthedesiredroomtemperaturewhichagainresultsina
decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
62|©Danfoss|2021.12
AQ189686468137en-010601
Page 63

OperatingGuideECLComfort310,applicationA368
3.6Manualcontrol
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich
thesymbolsforthecontrolledcomponents(valve,pumpetc.)are
visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe
desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe
installation.Thecontrolledcomponents,valve,pumpetc.,canbe
controlledforcorrectfunction.
AQ189686468137en-010601
Whenmanualcontrolisselectedforonecircuit,itisautomatically
selectedforallcircuits!
©Danfoss|2021.12|63
Page 64

OperatingGuideECLComfort310,applicationA368
3.7Schedule
3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.Insomeapplications,however,theremightbemore
thanoneschedule.Additionalschedulescanbefoundin‘Common
controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof
yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose:
Choose'MENU'inanyoftheoverview
displays
Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays
(inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort
periodbysettingstartandstoptimestothesamevalue.
64|©Danfoss|2021.12
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto
'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ189686468137en-010601
Page 65

OperatingGuideECLComfort310,applicationA368
4.0Settingsoverview
Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” .
ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Actual(actualfloworpower)
Pressure
Extendedheatcut-outsetting
Extendedwintercut-outsetting
Day
Starttime
Duration
DesiredT
S11,S13...S16press.sensor
DesiredT(Desiredflowtemperature)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Demandoffset
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Pre-stop(optimizedstoptime)
Con.T,re.Tlim.(Constanttemperaturemode,return
temperaturelimitation)
DHW,ret.Tlimit
Limit(returntemp.limitation)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Paralleloperation
DHWpriority(closedvalve/normaloperation)
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Inputtype
Limit(limitationvalue)
1x004
1x01183
1x01284
1x01385
1x01485
1x017103
1x02186
1x02294
1x023103
1x02687
1x028
1x029
1x03076
1x03176
1x03276
1x03376
1x034
1x035
1x036
1x037
1x04387
1x052104
1x077104
1x078104
1x08578
1x093104
1x10980
1x111
Factorysettingsincircuit(s)
1
69
80
97
110
110
120
120
121
121
124
71
75
75
77
77
77
77
80
2
AQ189686468137en-010601
©Danfoss|2021.12|65
Page 66

OperatingGuideECLComfort310,applicationA368
SettingIDPage
Adapt.time(adaptationtime)
Filterconstant
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Autotuning
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Highsupp.TX2(highvalueofsupplytemp.)
HighTmaxY2(highvalueofmaxlimitation)
LowsupplyTX1(lowvalueofsupplytemp.)
LowTmaxY1(lowvalueofmaxlimitation)
Retrytime
Change,duration
Changetime(changeovertime)
Stab.time(stabilizationtime)
Chan.-overtime(change-overtime)
Circ.pumps
Alarmhandling
Pexercise(pumpexercise)
Pressure,diff.(switchingdifference)
Time-out
Refillwater
Valvedelay
No.ofpumps
Inputtype
SenddesiredT
1x11281
1x11381
1x115
1x11681
1x117
1x11882
1x11982
1x141
1x142105
1x147115
1x148116
1x149116
1x150
1x17390
1x174
1x17771
1x178
1x17988
1x18491
1x18591
1x18692
1x18792
1x18992
1x30072
1x30172
1x30272
1x30372
1x31094
1x31194
1x31295
1x31395
1x31495
1x315
1x31698
1x32098
1x32299
1x32399
1x324
1x325100
1x326101
1x327101
1x500107
Factorysettingsincircuit(s)
1
81
82
105
117
91
71
117
117
2
66|©Danfoss|2021.12
AQ189686468137en-010601
Page 67

OperatingGuideECLComfort310,applicationA368
Pulsevalue
Preset
Pressure
Consump.(A368.5)
SettingIDPage
1x513112
1x514
Read-
out
Read-
out
Factorysettingsincircuit(s)
1
112
99
112
2
AQ189686468137en-010601
©Danfoss|2021.12|67
Page 68

OperatingGuideECLComfort310,applicationA368
5.0Settings
5.1IntroductiontoSettings
Descriptionsofsettings(parameter'sfunctions)aredividedinto
groupsasusedintheECLComfort210/296/310controller's
menustructure.Examples:"Flowtemperature" ,"Roomlimit"and
soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto
theparameter'sIDnumbers.Youmightcomeacrossdifferences
betweentheorderinthisOperatingGuideandtheECLComfort
210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication
subtypes.Thismeansthatyoumightnotseetherelatedparameter
intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof
thisOperatingGuide,whereparameter'ssettingrangesandfactory
settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit
…)covermultiplesubtypes.
68|©Danfoss|2021.12
AQ189686468137en-010601
Page 69

OperatingGuideECLComfort310,applicationA368
5.2Flowtemperature
TheECLComfortcontrollerdeterminesandcontrolstheflow
temperaturerelatedtotheoutdoortemperature.Thisrelationship
iscalledtheheatcurve.
Theheatcurveissetbymeansof6coordinatepoints.Thedesired
flowtemperatureissetat6pre-definedoutdoortemperature
values.
Theshownvaluefortheheatcurveisanaveragevalue(slope),
basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C
0°C32°C45°C70°C
5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating
B:Factorysettings
C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples
onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve
(example:1.0).
Whentheslopeoftheheatcurveischangedbymeansoftheslope
value,thecommonpointforallheatcurveswillbeadesiredflow
temperature=24.6°Catanoutdoortemperature=20°Canda
desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve
(example:-30,75).
Theheatcurverepresentsthedesiredflowtemperaturesat
differentoutdoortemperaturesandatadesiredroomtemperature
of20°C.
Ifthedesiredroomtemperatureischanged,thedesiredflow
temperaturealsochanges:
(DesiredroomT-20)×HC×2.5
where"HC"istheHeatCurveslopeand"2.5"isaconstant.
AQ189686468137en-010601
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and
‘Ramp’functionsetc.
Example:
Heatcurve:
Desiredflowtemp.:
Desiredroomtemp.:
Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0
50°C
22°C
5
©Danfoss|2021.12|69
Page 70

OperatingGuideECLComfort310,applicationA368
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
Thedesiredflowtemperatureissetin'Des.Tcomfort'and'Des.T
saving'.Setvaluesforcomfortmodecouldforexamplebe7.5°C
andforsavingmode25°C.
Alternativelythedesiredflowtemperaturecanbesetbyapplying
anexternalsignal.Thechoiceissetin'Ext.signal'.
TheECLComfort210/296/310controlstheDHWtemperature
accordingtothedesiredflowtemperatureforexampleunderthe
influenceofthereturntemperature.
ActualDHWtemp.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
DesiredDHW
temp.
70|©Danfoss|2021.12
AQ189686468137en-010601
Page 71

OperatingGuideECLComfort310,applicationA368
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flowtemperature
DesiredT(Desiredflowtemperature)
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow
temperaturecanbeset.
A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU
>Settings>Returnlimit>'Con.T,ret.Tlim. '
1x004
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow
temperaturewillnotbelowerthanthissetting.Adjustthefactory
setting,ifrequired.
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan
beappliedtoaninputinordertooverridetoComfort,Saving,Frost
ProtectionorConstanttemperature.Aslongasthecontact(switch)
signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor
'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn
temperaturelimitation(see'Priority').
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired
temperaturewillnotbehigherthanthissetting.Adjustthefactory
setting,ifrequired.
AQ189686468137en-010601
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
©Danfoss|2021.12|71
Page 72

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Flowtemperature
A368.2andA368.4:Themax.valueisnotadjustable,butdetermined
bythesettings"Highsup.TX2"andrelated(ID:1x300,1x301,1x302
and1x303).
Highsupp.TX2(highvalueofsupplytemp.)
1x300
SeeAppendix“ParameterIDoverview”
Setthehighvalueforthesupplytemperatureinrelationtothe
desiredmax.flowtemperature.Whenthesupplytemperatureis
abovethesetvalue,themax.limitationoftheflowtemperatureis
theY2value.Whenthesupplytemperatureisbelowthesetvalue,
themax.limitationoftheflowtemperaturewillbelower.
MENU>Settings>Flowtemperature
HighTmaxY2(highvalueofmaxlimitation)
1x301
SeeAppendix“ParameterIDoverview”
Setthehighvalueforthemax.limitationofthedesiredflow
temperature.
A368.2andA368.4offeralimitationofamax.desiredflow
temperatureinrelationtothemeasuredtemperatureatS2.Bythis,the
supplytemperaturecanalsodeterminethedesiredflowtemperature.
MENU>Settings>Flowtemperature
LowsupplyTX1(lowvalueofsupplytemp.)
1x302
SeeAppendix“ParameterIDoverview”
Setthelowvalueforthesupplytemperatureinrelationtothe
desiredmax.flowtemperature.Whenthesupplytemperatureis
belowthesetvalue,themax.limitationoftheflowtemperatureis
theY1value.Whenthesupplytemperatureisabovethesetvalue,
themax.limitationoftheflowtemperaturewillbehigher.
MENU>Settings>Flowtemperature
LowTmaxY1(lowvalueofmaxlimitation)
1x303
SeeAppendix“ParameterIDoverview”
Setthelowvalueforthemax.limitationofthedesiredflow
temperature.
72|©Danfoss|2021.12
AQ189686468137en-010601
Page 73

OperatingGuideECLComfort310,applicationA368
5.3Returnlimit
Thereturntemperaturelimitationisbasedontheoutdoor
temperature.Typicallyindistrictheatingsystemsahigherreturn
temperatureisacceptedatadecreaseinoutdoortemperature.The
relationshipbetweenthereturntemperaturelimitsandoutdoor
temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1'
and'LowToutX2' .Thereturntemperaturecoordinatesaresetin
'HighlimitY2'and'LowlimitY1' .
Thecontrollerautomaticallychangesthedesiredflowtemperature
toobtainanacceptablereturntemperaturewhenthereturn
temperaturefallsbeloworgetshigherthanthecalculatedlimit.
ThislimitationisbasedonaPIregulationwhereP('Infl.'factor)
respondsquicklytodeviationsandI('Adapt.time')responds
slowerandovertimeremovesthesmalloffsetsbetweenthe
desiredandactualvalues.Thisisdonebychangingthedesired
flowtemperature.
X
Y
#X1#
#X2#
#Y1#
#Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant
temperaturevalue.
Thecontrollerautomaticallychangesthedesiredflowtemperature
toobtainanacceptablereturntemperaturewhenthereturn
temperaturefallsbeloworgetshigherthanthesetlimit.
ThislimitationisbasedonaPIregulationwhereP('Infl.'factor)
respondsquicklytodeviationsandI('Adapt.time')responds
slowerandovertimeremovesthesmalloffsetsbetweenthe
desiredandactualvalues.Thisisdonebychangingthedesired
flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay.
Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X
#1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp.
Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp.
Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis
ariskofunstablecontrol.
AQ189686468137en-010601
©Danfoss|2021.12|73
Page 74

OperatingGuideECLComfort310,applicationA368
Example,maximumreturntemperaturelimitation;
returntemperaturegetshigherthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
74|©Danfoss|2021.12
AQ189686468137en-010601
Page 75

OperatingGuideECLComfort310,applicationA368
Example,minimumreturntemperaturelimitation;
returntemperaturegetslowerthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
Con.T,re.Tlim.(Constanttemperaturemode,return
temperaturelimitation)
The"Con.T ,ret.Tlimit"isthereturntemperaturelimitationvaluewhenthe
circuitissettooverridemodetype"Const.T"(=Constanttemperature).
SeeAppendix“ParameterIDoverview”
Value:Setthereturntemperaturelimitation
1x028
AQ189686468137en-010601
©Danfoss|2021.12|75
Page 76

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Returnlimit
DHW,ret.Tlimit
WhenanaddressedslaveisactiveinDHW-tankheating/charging,the
returntemperaturelimitationinthemastercanbeset.
Notes:
•Themastercircuitmustbesettoreactonthedesiredflowtemperature
intheslave(s).See"Demandoffset"(ID11017).
•Theslave(s)mustbesettosendits/theirdesiredflowtemperatureto
themaster.See"SenddesiredT"(ID1x500).
SeeAppendix“ParameterIDoverview”
OFF:
Noinfluencefromslaves.Thereturntemperature
limitationisrelatedtosettingsin"Returnlimit" .
Value:Returntemperaturelimitationvaluewhenslaveisin
DHWtankheating/chargingoperation.
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x029
#1#=Master,exampleA266,address15
#2#=Slave,exampleA237,address9
#3#=Slave,exampleA367,address6
SomeexamplesofapplicationswithDHW-tankheating/chargingare:
•A217,A237,A247,A367,A377
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe
setvalue,thecontrollerautomaticallychangesthedesiredflow/
ducttemperaturetoobtainanacceptablereturntemperature.The
influenceissetin'Infl.-max. 'and'Infl.-min.' .
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
1x031
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature
valuesetin'HighToutX1' .
1x032
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
76|©Danfoss|2021.12
AQ189686468137en-010601
Page 77

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature
limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature
valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe
returntemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
1x033
1x034
Example
1x035
Thereturnlimitisactiveabove50°C.
Theinfluenceissetto0.5.
Theactualreturntemperatureis2degreestoohigh.
Result:
Thedesiredflowtemperatureischangedby0.5x2=1.0degree.
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn
temperaturegetshigherthanthesetlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn
temperaturegetshigherthanthesetlimit.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe
returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn
temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn
temperaturegetsbelowthecalculatedlimit.
Example
1x036
Thereturnlimitisactivebelow50°C.
Theinfluenceissetto-3.0.
Theactualreturntemperatureis2degreestoolow.
Result:
Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower
returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo
lowreturntemperature(seealso'Infl.-max.').
AQ189686468137en-010601
©Danfoss|2021.12|77
Page 78

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn
temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt.
time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value:
Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset
min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled.
Themin.flowtemperaturelimitisoverruled.
1x037
Theadaptationfunctioncancorrectthedesiredflowtemperature
withmax.8K.
1x085
IfyouhaveaDHWapplication:
Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication:
Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum
limited,when"Priorityforreturntemperature"(ID1x085)isset
toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe
minimumlimited,when"Priorityforreturntemperature"
(ID1x085)issettoON.
78|©Danfoss|2021.12
AQ189686468137en-010601
Page 79

OperatingGuideECLComfort310,applicationA368
5.4Flow/powerlimit
Heatingcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL
controllerinordertolimitthefloworconsumedpower.
Theflow/powerlimitationcanbebasedontheoutdoor
temperature.Typically,indistrictheatingsystemsahigherflowor
powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor
temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1'
and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High
limitY2' .Basedonthesesettings,thecontrollercalculatesthe
limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the
controllergraduallyreducesthedesiredflowtemperaturetoobtain
anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2#
#Y1#
#Y2#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
=
X
Y
#1#
#2#
#3#
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
AQ189686468137en-010601
©Danfoss|2021.12|79
Page 80

OperatingGuideECLComfort310,applicationA368
DHWcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL
controllerinordertolimitthefloworconsumedpower.
Whentheflow/powergetshigherthanthesetlimit,thecontroller
graduallyreducesthedesiredflowtemperaturetoobtainan
acceptablemax.floworpowerconsumption.
=
X
Y
#1#
#2#
#3#
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Inputtype
ChoiceofM-bussignalfromenergymeternumber1...5.Onlypossible
inECLComfort310.
SeeAppendix“ParameterIDoverview”
OFF:
EM1...EM5:
NoM-bussignalacquired.
Energymeternumber.
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy
meter.
1x109
FloworpowerlimitationisbasedonM-bussignal(ECLComfort310
controllersonly).
80|©Danfoss|2021.12
AQ189686468137en-010601
Page 81

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe
actualoutdoortemperature.
Inotherapplicationsthevalueisaselectablelimitationvalue.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired
limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt.
time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value:
Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
1x111
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured
value.
Thehigherthevalue,themoredampening.
Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value:
Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Flowvaluesareexpressedasl/horm³/h
PowervaluesareexpressedaskW,MWorGW.
1x113
1x115
Listforsettingrangeof'Units':
l/h
m³/h
kW
MW
GW
AQ189686468137en-010601
©Danfoss|2021.12|81
Page 82

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset
in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin
'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
1x116
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired
flowtemperature.
1x118
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
1x119
82|©Danfoss|2021.12
AQ189686468137en-010601
Page 83

OperatingGuideECLComfort310,applicationA368
5.5Optimization
Thesection"Optimization"describesspecificapplicationrelated
issues.
Theparameters'Autosaving' ,'Boost','Optimizer','Totalstop'areall
relatedtoheatingmodeonly.
'Summer,cut-out'determine,atrisingoutdoortemperature,the
stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
AQ189686468137en-010601
©Danfoss|2021.12|83
Page 84

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature
settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature,
thesavingtemperaturerelatestotheactualoutdoortemperature.The
functionisrelevantindistrictheatinginstallationsinordertoavoidabig
changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe
outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove
10°C,thereductionis100%.Thelowertheoutdoor
temperature,thelessthetemperaturereduction.
Belowthesetvalue,thesavingtemperaturesetting
hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein
Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving
mode
ThedesiredroomtemperaturesforComfortandSavingmodes
aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)=
(10-(-5))/(10-(-15))=
15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode:
T.room.ref.Saving+(T.out.influencex(T.room.ref.ComfortT.room.ref.Saving))
16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
84|©Danfoss|2021.12
AQ189686468137en-010601
Page 85

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature
bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive.
Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving
temperatureperiod,thedesiredflowtemperaturecanbeincreased
temporarily(max.1hour).Atoptimizingtheboostisactiveinthe
optimizationperiod('Optimizer').
IfaroomtemperaturesensororanECA30/31isconnected,the
booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases
graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive.
Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow
temperaturecanbesettoincreasegraduallyafteraperiodwith
savingtemperature.Thiscausesthevalvetoopengradually.
=
X
Y
#1#
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
AQ189686468137en-010601
©Danfoss|2021.12|85
Page 86

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto
obtainthebestcomfortatthelowestenergyconsumption.
Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower
theoutdoortemperature,thelatertheheatingcut-out.
Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The
calculatedstartandstoptimesarebasedonthesettingoftheoptimizing
timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe
followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe
timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge
-1
-45°C
-5
-25°C
normal
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem
designerinconnectionwiththedesignoftheheatingsystem)atwhich
theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding
ismedium.
Theleftdigitis2.
Thedimensioningtemperatureis-25°C,andthecapacityisnormal.
Therightdigitis5.
Result:
Thesettingistobechangedto25.
-5°C
small
86|©Danfoss|2021.12
AQ189686468137en-010601
Page 87

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced
accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue
in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost
protectionisstillactive,see'PfrostT' .
Totalstop=OFF
Totalstop=ON
X
Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Theoptimizedstoptimeisdisabled.
Theoptimizedstoptimeisenabled.
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen
'Totalstop'isON.
1x026
Example:OptimizationofComfortfrom07:00-22:00
=
X
#1#
#2#
#3#
#4#
#5#
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
AQ189686468137en-010601
©Danfoss|2021.12|87
Page 88

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Paralleloperation
ChoosewhethertheheatingcircuitistooperateindependenceoftheDHW
circuit.Thisfunctionmightbeusefulifaninstallationhaslimitedpower
orflow.
SeeAppendix“ParameterIDoverview”
OFF:
Independentparalleloperation,i.e.theDHWand
theheatingcircuitsoperateindependentlyofeach
other.ItmakesnodifferencewhetherthedesiredDHW
temperaturecanbereachedornot.
Value:Dependentparalleloperation,i.e.thedesiredheating
temperaturedependsontheDHWdemand.Choose
howmuchtheDHWtemperaturecandropbeforethe
desiredheatingtemperaturehastobedecreased.
1x043
=
X
Y1
Y2
#1#
#2#
#3#
#4#
#5#
#6#
#7#
Time
=
Temperature
=
Temperature
=
Acceptabledeviation(Paralleloperation,1x043)
=
DesiredDHWtemperature
=
ActualDHWtemperature
=
Desiredheatingtemperature
=
Reducedheatingtemperature
=
100%paralleloperation
=
Paralleloperationwithdecreasedheatingtemperature
IftheactualDHWtemperaturedeviatesmorethanthesetvalue,the
gearmotorM2intheheatingcircuitwillgraduallyclosetosuchan
extentthattheDHWtemperaturestabilizesatthelowestacceptable
value.
IncasetheParalleloperationisactive(atoolowDHWtemperature
andthereforeareducedheatingcircuittemperature),aslave's
temperaturedemandwillnotchangethedesiredflowtemperaturein
theheatingcircuit.
Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum
limited,when"Priorityforreturntemperature"(ID1x085)isset
toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe
minimumlimited,when"Priorityforreturntemperature"
(ID1x085)issettoON.
88|©Danfoss|2021.12
AQ189686468137en-010601
Page 89

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanthesetvalue.Thevalveclosesandafterthepost-run
time,theheatingcirculationpumpstops.‘Temp.min.’willbe
overruled.
TheheatingsystemswitchesONagainwhentheoutdoor
temperatureandtheaccumulated(filtered)outdoortemperature
becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe
heatingsystemtoswitchOFF .
Summer,cut-out
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin
scheduledoperation.Whenthecut-outvalueissettoOFF,thereis
noheatingcut-out.
AQ189686468137en-010601
©Danfoss|2021.12|89
Page 90

OperatingGuideECLComfort310,applicationA368
5.6Controlparameters
Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point
controlsignal.
Valvecontrol:
Themotorizedcontrolvalveisopenedgraduallywhentheflow
temperatureislowerthanthedesiredflowtemperatureandvice
versa.
Thewaterflowthroughthecontrolvalveismanagedbymeans
ofanelectricactuator.Thecombination"actuator"and"control
valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin
thiswaygraduallyincreaseordecreasetheflowinordertochange
thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator:
Theelectricactuatorcontainsareversiblegear-motor.Electric
"open"and"close"signalscomefromtheelectronicoutputsofthe
ECLComfortcontrollerinordertomanagethecontrolvalve.The
signalsareintheECLComfortcontrollerexpressedas"Arrow-up"
(open)and"Arrow-down"(close)anddisplayedatthevalvesymbol.
Whentheflowtemperature(forexampleatS3)islowerthanthe
desiredflowtemperature,shortopen-signalscomefromtheECL
Comfortcontrollerinordertograduallyincreasetheflow.Bythis,
theflowtemperaturewillalignwiththedesiredtemperature.
Oppositely,whentheflowtemperatureishigherthanthedesired
flowtemperature,shortclose-signalscomefromtheECLComfort
controllerinordertograduallyreducetheflow.Again,theflow
temperaturealignswiththedesiredtemperature.
Neitheropen-signalsnorclose-signalswillcomeaslongastheflow
temperaturecorrespondstothedesiredtemperature.
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
90|©Danfoss|2021.12
AQ189686468137en-010601
Page 91

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Controlparameters
Autotuning
AutomaticallydeterminesthecontrolparametersfortheDHWcontrol.'Xp'
'Tn'and'Mrun'donotneedtobeset,whenusingautotuning.'Nz'must
beset.
1x173
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Autotuningisnotactivated.
Autotuningisactivated.
Theautotuningfunctionautomaticallydeterminesthecontrol
parametersforDHWcontrol.Thusyoudonotneedtosetthe'Xp',
'Tn'and'Mrun',astheyareautomaticallysetwhentheautotuning
functionissettoON.
Autotuningistypicallyusedinconnectionwiththeinstallationof
thecontroller,butitcanbeactivatedwhenneeded,e.g.foran
extracheckofthecontrolparameters.
Beforestartingtheautotuning,thetappingflowshouldbe
adjustedtotherelevantvalue(seetable).
Ifpossible,anyadditionalDHWconsumptionshouldbeavoided
duringtheautotuningprocess.Shouldthetappingloadvarytoo
much,theautotuningandcontrollerwillreturntothedefault
settings.
No.of
apartments
Heat
transfer
ConstantDHWdraw-off(l/min)
(kW)
1-230-493
3-950-796
10-4980-14912
50-129150-24918
130-210250-35024
Inordertomeetthesummer-/wintervariations,theECLclockmust
besettothecorrectdateforansuccessfulautotuning.
Themotorprotectionfunction('Motorpr.')hastobedeactivated
duringautotuning.Duringautotuningthecirculationpumpfortap
watermustbeswitchedoff.Thisisdoneautomaticallyifthepumpis
controlledbytheECLcontroller.
Autotuningisonlyapplicableinconnectionwithvalvesthatare
approvedforautotuning,i.e.theDanfosstypesVB2andVM2with
splitcharacteristicaswellaslogarithmicvalvessuchasVFandVFS.
(or1tap25%open)
(or1tap50%open)
(or1tap100%open)
(or1tap100%+1tap50%
open)
(or2taps100%open)
AutotuningisactivatedbysettingthefunctiontoON.Whenthe
autotuningisended,thefunctionisautomaticallyconvertedto
OFF(defaultsetting).Thiswillbeindicatedinthedisplay.
Theautotuningprocesstakesupto25minutes.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting
actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection
increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation
delayinminutes.
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
1x174
Recommendedforductsystemswithvariableload.
1x184
Settheproportionalband.Ahighervaluewillresultinastablebut
slowcontroloftheflowtemperature.
AQ189686468137en-010601
©Danfoss|2021.12|91
Page 92

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow
butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast
butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove
fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning
timebymeansofastopwatch.
MENU>Settings>Controlparameters
1x185
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing
thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller
doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh
variationinflowtemperature.
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear
motor.
SeeAppendix“ParameterIDoverview”
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature
value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis
temperature.
SettingexampleValuex20ms
1x189
240ms
10200ms
501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe
lifetimeoftheactuator(gearmotor).
92|©Danfoss|2021.12
AQ189686468137en-010601
Page 93

OperatingGuideECLComfort310,applicationA368
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
•Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
•Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it
mightbenecessarytoforcethesystembysettinganextremelowvalue).
•Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod.
‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption
whenyousettheparameters.
Criticaltimeperiod
Time
AQ189686468137en-010601
©Danfoss|2021.12|93
Page 94

OperatingGuideECLComfort310,applicationA368
5.7Pumpcontrol
Thisapplicationcanoperatewithoneortwocirculationpumps.
Whenoperatingwithtwocirculationpumps,thepumpsare
controlledalternately,accordingtoatimeset-up.Whenapump
isswitchedONthecontrolleriswaitingfordifferentialpressure
S7tobuildup.Ifdifferentialpressureisnotachieved,analarmis
generatedandtheECLComfortcontrollerswitchesONtheother
pump.
Ifnoneofthepumpscancomeintooperation(detectedbymeans
ofthedifferentialpressureswitch),thealarmisactivatedandthe
motorizedcontrolvalvecloses(asafetyfunction).
TheapplicationsA368.1...A368.5canoperatewithoneor
twocirculationpumps.Whenoperatingwithtwocirculation
pumps,thepumpsarecontrolledalternately,accordingtoatime
set-up.WhenapumpisswitchedONthecontrolleriswaitingfor
differentialpressureS8tobuildup.Ifdifferentialpressureisnot
achieved,analarmisgeneratedandtheECLComfortcontroller
switchesONtheotherpump.
Ifnoneofthepumpscancomeintooperation(detectedbymeans
ofthedifferentialpressureswitch),thealarmisactivatedandthe
motorizedcontrolvalvecloses(asafetyfunction).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Pumpcontrol
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat
noon(12:14hours).
MENU>Settings>Pumpcontrol
Retrytime
Ifanalarmhasbeengeneratedforthepumporalarmshavebeengenerated
forbothpumps,thissettingwilldeterminethetimebetweenthetimeofthe
alarmandtheretrytimeforrepeatedpumpstart.
SeeAppendix“ParameterIDoverview”
1x022
1x310
OFF:
1...99:
94|©Danfoss|2021.12
Noretrytimerequiredafteranalarm.Thepumpor
pumpsinquestionwillnotberestarted.
Afteranalarm,thepumporpumpswillberestarted
afterthesettime.
AQ189686468137en-010601
Page 95

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Pumpcontrol
Change,duration
Thenumberofdaysbetweenshiftofcirculationpumps.Theshifttakesplace
atthetimesetin'Changetime' .
SeeAppendix“ParameterIDoverview”
MENU>Settings>Pumpcontrol
Changetime(changeovertime)
Theexacttimeoftheday,wheretheshiftmusttakeplace.Thedayisdivided
into24hours.Thefactorysettinghereis12whichmeans12:00(noon).
1x311
=
X
#1#
#2#
#3#
1x312
Time
=
PumpP3
=
PumpP5
=
Change,duration(days)
SeeAppendix“ParameterIDoverview”
MENU>Settings>Pumpcontrol
Stab.time(stabilizationtime)
Settingofmax.timetoelapsebetweenpumpstartcommandandfeedback
fromdifferentialpressureswitch.
Ifthedifferentialpressureswitchdoesnotgivefeedbackwithinthesettime,
thealarmwillbeactivatedandtheotherpumpwillgetastartcommand.
SeeAppendix“ParameterIDoverview”
=
X
#1#
#2#
#3#
1x313
Time
=
PumpP3
=
PumpP5
=
Changetime(clocktime)
Ifthechosenstabilizationtime(‘Stab.time’)istooshort,theactive
pumpwillstopimmediatelyafterthestabilizationtimehaselapsed.
AQ189686468137en-010601
©Danfoss|2021.12|95
Page 96

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Pumpcontrol
Chan.-overtime(change-overtime)
Settingoftimetoelapsebetweenthepumpstopcommandforonepump
andthestartcommandfortheotherpump.
Thechange-overtimecanensurethatapumpisstoppedefficientlybefore
theotherpumpstarts.
SeeAppendix“ParameterIDoverview”
OFF:
1...99:
Onecirculationpumpintheapplication.
Timeforchange-over.
1x314
=
X
#1#
#2#
#3#
Time
=
PumpP3
=
PumpP5
=
Change-overtime(sec.)
‘Chan.-overtime’hastobechoseninsystemswithtwopumps.
Thestatusofthedifferentialpressureswitchisshownin'Input
overview'.
(Navigation:MENU>Commoncontroller>Inputoverview).
Example:
S7status...OFF/ON
OFF:
Thedifferentialpressureswitchisclosed(differential
pressureisOK)
ON:
Thedifferentialpressureswitchisopen(differential
pressureisnotOK)
96|©Danfoss|2021.12
AQ189686468137en-010601
Page 97

OperatingGuideECLComfort310,applicationA368
5.8Refillwater
Leaksontheconsumerssidewillresultinfallingstaticpressureand
therebyapoorsupplyofheating.Arefillwaterfunctioncaninject
watertoincreasethestaticpressure.
Thisapplicationcanmonitorthestaticpressureandenablethe
refillwaterfunctionwhenthepressureistoolow.
Thepressureismeasuredbymeansofapressuretransmitter
(givinga0-10voltsignalinrelationtothemeasuredpressure)or
apressureswitch.
Whenapressuretransmittersignalisused,twosettingsinthe
controllerrepresentpressuresetpointanddifference.
Whenapressureswitchsignalisused,thesetpointand(maybe)
theswitchingdifferenceissetonthepressureswitch.
Whenatoolowpressureisdetectedtherefillwaterpumpis
switchedONand,afterasettime,theON-OFFvalveisactivated.
Ifthepressureisnotachievedwithinasettime,analarmis
generated.TheECLComfortcontrollerswitchesOFFthecirculation
pumpsafter60secondsandthecontrolvalvecloses(asafety
function).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
Thealarmfunctionisdisabledifthe"Alarmhandling"(ID11316)is
settoOFF.
AQ189686468137en-010601
©Danfoss|2021.12|97
Page 98

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Refillwater
Pressure
CircuitSettingrange
1
Read-outonly
Theread-outcanbeavalue(inbar):
•Thepressureismeasuredbymeansofapressuretransmitter.
Thetransmittersendsthemeasuredpressureasa0-10Vora
4-20mAsignal.Thevoltagesignalcanbeapplieddirectlyto
inputS10.Acurrentsignalisconvertedbymeansofaresistor
toavoltageandthenappliedtoinputS10.Themeasured
voltageoninputS10mustbeconvertedtoapressurevalueby
thecontroller.Thisproceduresetsupthescaling.
Pushthedialtoseethegraphandenterthevaluesetsforthe
inputvoltage(2and10volt)anddisplayedpressure(inbar).
Pressurevaluerange:0.0...30.0bar
Fixedvoltagesettings:2Vand10V
Factorysettings:(2.0,0)and(10,20.0)
Thismeansthatthe‘Pressure'is0.0barat2Vand20.0barat
10V.
Typically,thehigherthevoltage,thehigherthedisplayed
pressure.
Ortheread-outcanbeOFForON:
•Thepressureismeasuredbymeansofapressureswitch.The
pressureswitchhasanopencontactwhenmeasuringatoolow
pressure(shownasOFF).WhenmeasuredpressureisOK,the
contactisclosed(shownasON).
Thepressureswitchcontact(potentialfree)isconnected
directlytoinputS10.
Factorysetting
=
X
Y
#1#
#2#
Volt
=
Bar
=
0bar
=
30,0bar
Thisscalingmenuisalwaysshown,regardlesswhetherapressure
transmitterorapressureswitchisused.
MENU>Settings>Refillwater
Alarmhandling
Choosewhetherthecontrollermustreactonanunacceptablepressure.
SeeAppendix“ParameterIDoverview”
OFF:
Alarmfunctionisdisabled.Circulationpumpisnot
stoppedalthoughthepressureistoolow.
ON:
Alarmfunctionisenabled.Circulationpumpisstopped
ifthepressureistoolow.
1x316
98|©Danfoss|2021.12
AQ189686468137en-010601
Page 99

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Refillwater
Pexercise(pumpexercise)
Thetimethepumpisactivatedduringexercise.Exercisetakesplaceevery
day(at12:00).
SeeAppendix“ParameterIDoverview”
OFF:
1...200:
Nopumpexercise.
Activationtimeduringexercise.
MENU>Settings>Refillwater
Pressure
CircuitSettingrange
1
Thepressureisindicatedasavaluemeasuredinbar.
A0-10voltsignalcomesdirectlyfromapressuretransmitter
(voltageoutput)orconvertedbymeansofaresistorfromapressure
transmitter(currentoutput).
Thevoltagesignalisappliedtotheinputinquestionandisconverted
tothedisplayedpressurevalue.
Accesstoconversion(scale)settings.
*)
2.0volt=0.0bar,10.0volt=20.0bar
-
Read-out
Factorysetting
1x320
*)
Thepressureismeasuredbymeansofa0-10voltsignal.
Themeasuredvoltagemustbeconvertedtoapressure
valuebythecontroller.
Thefollowingproceduresetsuptheconversion:
Pushthedialtoseethegraphandenterthevaluesets
forthe2inputvoltagesandrelatedpressurevalues.
Pressurevaluerange:0.0…30.0bar.
Factorysettings:2,0.0(=2V/0.0bar)and10,10.0
(=10V/10.0bar).
Thismeansthatthe"Pressure"is0.0barat2Vand10.0
barat10V.Typically,thehigherthevoltage,thehigher
thedisplayedpressure.
MENU>Settings>Refillwater
Pressure,diff.(switchingdifference)
Settingoftheswitchingdifferenceformeasuredstaticpressure(pressure
transmitter).Thedifferenceissymmetricalaroundthe'Pressuredes. 'See
also'Pressuredes. '
SeeAppendix“ParameterIDoverview”
=
X
Y
1x322
Volt
=
Pressure(bar)
Thisscalingmenuisalwaysdisplayed,regardlessapressuresignal
isapplied.
Thepressureisindicatedas0.0barwhenthepressuresignalisnot
applied.
Thesettingsin'Pressure,des. 'and'Pressure,diff.'havenoinfluence
whenapressureswitchisused.
AQ189686468137en-010601
©Danfoss|2021.12|99
Page 100

OperatingGuideECLComfort310,applicationA368
MENU>Settings>Refillwater
Time-out
Settingofthemax.timeforrefill.Thepressure,measuredbyS10,mustbe
OKwithinthesettime.Ifnot,therefillwaterfunctionstopsandanalarm
isactivated.
SeeAppendix“ParameterIDoverview”
1x323
=
X
#1#
#2#
#3#
Time
=
PressureOK/notOK
=
Refillpump
=
Time-out
100|©Danfoss|2021.12
=
X
#1#
#2#
#3#
#4#
Time
=
PressureOK/notOK
=
Refillpump
=
Time-out
=
Alarm
AQ189686468137en-010601