Danfoss A368 Operating guide

Page 1
OperatingGuide
ECLComfort310,applicationA368

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................15
2.4Placingthetemperaturesensors................................20
2.5Electricalconnections.............................................22
2.6InsertingtheECLApplicationKey..............................34
2.7Checklist............................................................41
2.8Navigation,ECLApplicationKeyA368.........................42
3.0Dailyuse.........................................................55
3.1Howtonavigate...................................................55
3.2Understandingthecontrollerdisplay..........................56
3.3Ageneraloverview:Whatdothesymbolsmean?...........60
3.4Monitoringtemperaturesandsystem
components........................................................61
3.5Influenceoverview................................................62
3.6Manualcontrol.....................................................63
3.7Schedule............................................................64
4.0Settingsoverview............................................65
5.0Settings...........................................................68
5.1IntroductiontoSettings..........................................68
5.2Flowtemperature..................................................69
5.4Flow/powerlimit.................................................79
5.5Optimization........................................................83
5.6Controlparameters................................................90
5.7Pumpcontrol.......................................................94
5.9Application.......................................................103
5.10Heatcut-out......................................................109
5.11Watermeter......................................................112
5.12Alarm..............................................................114
5.13Alarmoverview..................................................119
5.14Anti-bacteria......................................................120
6.0Commoncontrollersettings............................122
6.1Introductionto‘Commoncontrollersettings’..............122
6.2Time&Date.......................................................123
6.3Settings............................................................124
6.4Holiday............................................................125
6.5Inputoverview...................................................127
6.6Log.................................................................128
6.7Outputoverride..................................................129
6.8Alarm..............................................................130
6.9Keyfunctions.....................................................131
6.10System.............................................................133
7.0Miscellaneous................................................140
7.1ECA30/31setupprocedures.................................140
7.2Overridefunction................................................148
7.3Severalcontrollersinthesamesystem......................151
7.4Frequentlyaskedquestions....................................154
7.5Definitions........................................................157
7.6Type(ID6001),overview.......................................161
7.7Automatic/manualupdateoffirmware.....................162
7.8ParameterIDoverview..........................................163
©Danfoss|2021.12AQ189686468137en-010601|1
Page 2
OperatingGuideECLComfort310,applicationA368

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA368 (ordercodeno.087H3803).
TheECLApplicationKeyA368contains6subtypes,allapplicablein ECLComfort310:
A368.1:HeatingandDHWcontrol.Pumpforrefillwatercontrol
A368.2:HeatingandDHWcontrol.Supplytemperaturecan determinedesiredflowtemperature.Pumpforrefillwater control
A368.3:HeatingandDHWcontroland2pumpsforrefillwater control.Pressuremonitoring
A368.4:HeatingandDHWcontroland2pumpsforrefillwater control.Supplytemperaturecandeterminedesiredflow temperature.Pressuremonitoring
A368.5:HeatingandDHWcontrol.2pumpsandflowmeter forrefillwatercontrol.Pressureandsecondarytemperature monitoring
A368.6:HeatingandDHWcontrol.Pumpforrefillwatercontrol. Secondarytemperaturemonitoring
SeetheMountingGuide(deliveredwiththeapplicationkey)for applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310for advancedsolutions,e.g.M-bus,ModbusandEthernet(Internet) communication.
TheApplicationKeyA368complieswithECLComfort310 controllersasofsoftwareversion1.11(visibleatstart-upofthe controllerandin‘Commoncontrollersettings’in‘System’).
TheapplicationsA368.3,A368.4andA368.5workwiththeInternal I/OmoduleECA32(ordercodeno.087H3202). ECA32isplacedinthebasepartforECLComfort310. UptotwoRemoteControlUnits,ECA30orECA31,canbe connectedforremotemonitoringandsetting.
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
ThebasepartforECLComfort310,230voltand24volt:
087H3230
TheB-typeshavenodisplayanddial. TheB-typesareoperatedbymeansoftheremotecontrolunit ECA30/31:
ECA30(087H3200)
ECA31(087H3201)
AdditionaldocumentationforECLComfort310,modulesand accessoriesisavailableonhttp://danfoss.com/.
2|©Danfoss|2021.12
AQ189686468137en-010601
Page 3
OperatingGuideECLComfort310,applicationA368
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310/311:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
AQ189686468137en-010601
©Danfoss|2021.12|3
Page 4
OperatingGuideECLComfort310,applicationA368
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
1
-
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
2
Circuit2Parameterno.
174
4|©Danfoss|2021.12
AQ189686468137en-010601
Page 5
OperatingGuideECLComfort310,applicationA368

2.0Installation

2.1Beforeyoustart

TheECLapplicationkeyA368containsof6subtypes:A368.1, A368.2,A368.3,A368.4,A368.5andA368.6.
The6differentapplicationsareheatingandDHWapplicationsin variouscombinations.
Thebasicprinciplesforaheatingcircuit
(examplereferringtoA368.1)
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.Theflowtemperaturesensor(S3)isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein ‘Comfort’or‘Saving’mode.Theweekschedulecanhaveupto3 ‘Comfort’periods/day.Avalueforthedesiredroomtemperature canbesetineachofthemodes. InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
ThecirculationpumpsP3andP5areoperatedalternately.One circulationpumpisusedasworkingpumpandtheothercirculation pumpisusedassparepump.Thecirculationpumpinquestionis ONatheatdemandoratfrostprotection.Thealternationtime canbesetasanumberofdaysandasettimeontheshiftday.A solutionwithasinglecirculationpumpcanalsobeselected.
BymeansofthepressuredifferenceswitchS7theECLcontroller verifiesthatthecirculationpumpinquestionisoperating. Ifanacceptablepressuredifferenceisnotdetected,theECL controlleractivatesthealarmandshiftstheoperatingcommandto theoppositecirculationpump.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
TheFrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
TheheatingcircuitcanbegraduallyorfullclosedduringDHW heating
Thestaticpressureonthesecondaryside(consumerside)can1) bemeasuredasa0-10Vsignal(fromapressuretransmitter)or2) beaswitchsignalfromapressureswitch. Incaseofatoolowpressure,therefillwaterfunctionwill supplementwithwaterfromawatersourceorthesupplyside.The refillpumpP4isswitchedONandtheON/OFFvalveV1opens.
TypicalA368.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S3
S4
S5
S6
S7
S8
S9
S10
P1
P2
P3
P4
P5
M1
M2
V1
A1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|5
Page 6
OperatingGuideECLComfort310,applicationA368
A368.3,A368.4andA368.5only:
TherefillpumpsP4andP7areoperatedalternately.Thealternation timecanbesetasanumberofdays.
Asolutionwithasinglerefillpumpcanalsobeselected.
IncaseofnotreachedpressureatS10withinasettimeanalarm willbegenerated.
A368.2andA368.4only:
ThesupplytemperatureS2candeterminethedesiredflow temperature.
A368.3andA368only:
S11isusedformonitoringthepressureintheflowtotheheating circuit.
A368.5only:
AflowmeterF1(pulsesignal)measurestheinjectedrefillwater. S11isusedformonitoringthereturntemperaturefromtheheating circuit.
A368.6only:
S2isusedformonitoringthereturntemperaturefromtheheating circuit.
Heatingingeneral:
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout heatingdemandcanbearranged.
TypicalA368.1application:
ModbuscommunicationtoaSCADAsystemcanbeestablished.
AconnectedfloworenergymeterbasedonM-bussignalcan limitthefloworpowertoasetmaximumvalue.Furthermore,the limitationcanbeinrelationtotheoutdoortemperature.Typically, thelowertheoutdoortemperature,thehighertheacceptedflow/ power.
M-busdatacanbetransferredtotheModbuscommunication.
Overridefunction:
Bymeansofanexternalswitchorarelaycontactthescheduleof theheatingcircuitcanbeoverriddento
constantComfortmode
constantSavingmode
constantdesiredflowtemperature
constantFrostprotectionmode
6|©Danfoss|2021.12
AQ189686468137en-010601
Page 7
OperatingGuideECLComfort310,applicationA368
ThebasicprinciplesforaDHWcircuit(circuit2):
(examplereferringtoA368.1)
IfthemeasuredDHWtemperature(S4)islowerthanthedesired DHWtemperature,themotorizedcontrolvalve(M1)isopened graduallyandviceversa.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’ or‘Saving’mode.Theweekschedulecanhaveupto3‘Comfort’ periods/day. AvalueforthedesiredDHWtemperaturecanbesetineachof themodes.
Thereturntemperature(S6)canbelimitedtoasetvalue.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
IfthedesiredDHWtemperaturecannotbereached,theheating circuitcanbeclosedgraduallytoallowmoreenergytotheDHW circuit.
ThecirculationpumpsP1andP2areoperatedalternately.One circulationpumpisusedasworkingpumpandtheothercirculation pumpisusedassparepump.Thecirculationpumpinquestionis ONatDHWheatingdemandoratfrostprotection.Thealternation timecanbesetasanumberofdaysandasettimeontheshiftday. Asolutionwithasinglecirculationpumpcanalsobeselected.
BymeansofthepressuredifferenceS8(exceptA368.6)the ECLcontrollerverifiesthatthecirculationpumpinquestionis operating.
TheFrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit thefloworpowertoasetmaximumvalue.
A368.3,A368.4andA368.5only:
S13isusedformonitoringthepressureinthereturnfromtheDHW circulation. S14isusedformonitoringthepressureofthecoldwatersupply.
A368.6only:
S8isusedformonitoringthetemperatureinthereturnfromthe DHWcirculation.
Overridefunction:
Bymeansofanexternalswitchorarelaycontactthescheduleof theDHWcircuitcanbeoverriddento
constantComfortmode
constantSavingmode
constantFrostprotectionmode
TypicalA368.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S3
S4
S5
S6
S7
S8
S9
S10
P1
P2
P3
P4
P5
M1
M2
V1
A1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|7
Page 8
OperatingGuideECLComfort310,applicationA368
A368,ingeneral:
TheheatingcircuitcanbegraduallyorfullclosedduringDHW heating(slidingorfullDHWpriority).
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviathe ECL485businordertoutilizecommonoutdoortemperature signal,timeanddatesignals.
TheECLcontrollersintheECL485systemcanworkinmaster­slavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdatacanfurthermorebetransferredtotheModbus communication.
AlarmA1(=relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature
Theactivatedcirculationpumpdoesnotgenerateapressure difference
Therefillwaterfunctiondoesnotgenerateapressurewithin apresettime
Ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview)
Iftheuniversalalarminput(s)S9/S12areactivated.
8|©Danfoss|2021.12
AQ189686468137en-010601
Page 9
OperatingGuideECLComfort310,applicationA368
TypicalA368.2application:
(HeatingandDHW)
TypicalA368.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
P1
P2
P3
P4
P5
M1
M2
V1
A1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
Supplytemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|9
Page 10
OperatingGuideECLComfort310,applicationA368
TypicalA368.3application:
(HeatingandDHW)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA368.3application:
Listofcomponents:
ECL310
ECL32
S1
S3
S4
S5
S6
S7
S8
S9
S10
S11
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
(Optional)Secondarypressuresensor,circuit1.For monitoringpurpose
S12
S13
Alarminput
(Optional)DHWcirculationreturnpressuresensor.For monitoringpurpose
S14
(Optional)Coldwatersupplypressuresensor.For monitoringpurpose
S15
(Optional)Primarysupplypressuresensor.Formonitoring purpose
S16
(Optional)Primaryreturnpressuresensor.Formonitoring purpose
P1
P2
P3
P4
P5
P7
M1
M2
V1
A1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
10|©Danfoss|2021.12
AQ189686468137en-010601
Page 11
OperatingGuideECLComfort310,applicationA368
TypicalA368.4application:
(HeatingandDHW)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA368.4application:
Listofcomponents:
ECL310
ECL32
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
S11
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
Supplytemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
(Optional)Secondarypressuresensor,circuit1.For monitoringpurpose
S12
S13
Alarminput
(Optional)DHWcirculationreturnpressuresensor.For monitoringpurpose
S14
(Optional)Coldwatersupplypressuresensor.For monitoringpurpose
S15
(Optional)Primarysupplypressuresensor.Formonitoring purpose
S16
(Optional)Primaryreturnpressuresensor.Formonitoring purpose
P1
P2
P3
P4
P5
P7
M1
M2
V1
A1
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|11
Page 12
OperatingGuideECLComfort310,applicationA368
TypicalA368.5application:
(HeatingandDHW)
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA368.5application:
Listofcomponents:
ECL310
ECL32
S1
S3
S4
S5
S6
S7
S8
S9
S10
S11
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
Differentialpressureswitch,circuit2
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
(Optional)Secondaryreturntemperaturesensor, circuit1.Formonitoringpurpose
S12
S13
Alarminput
(Optional)DHWcirculationreturntemperaturesensor.For monitoringpurpose
S14
(Optional)Coldwatersupplypressuresensor.For monitoringpurpose
S15
(Optional)Primarysupplypressuresensor.Formonitoring purpose
S16
(Optional)Primaryreturnpressuresensor.Formonitoring purpose
F1
P1
P2
P3
P4
P5
P7
M1
M2
V1
A1
Refillwaterflowmeter
Circulationpump,DHW ,circuit2
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
12|©Danfoss|2021.12
AQ189686468137en-010601
Page 13
OperatingGuideECLComfort310,applicationA368
TypicalA368.6application:
(HeatingandDHW)
TypicalA368.6application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S2
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
(Optional)Secondaryreturntemperaturesensor, circuit1.Formonitoringpurpose
S3
S4
S5
S6
S7
S8
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
Differentialpressureswitch,circuit1
(Optional)DHWcirculationreturntemperaturesensor.For monitoringpurpose
S9
S10
P1
P3
P4
P5
M1
M2
V1
A1
Alarminput
(Optional)Pressuretransmitterorpressureswitch,circuit1
Circulationpump,DHW ,circuit2
Circulationpump,heating,circuit1
Refillwaterpump,circuit1
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
ON/OFFvalve,circuit1,refillwatervalve
Alarm
AQ189686468137en-010601
©Danfoss|2021.12|13
Page 14
OperatingGuideECLComfort310,applicationA368
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
14|©Danfoss|2021.12
AQ189686468137en-010601
Page 15
OperatingGuideECLComfort310,applicationA368

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Adviceforsettings:
Whencircuit1(heating)mustbeabletoreceiveatemperature demandfromaslave: MENU\Settings\Application: 'Demandoffset'(ID11017):3K*
WhenaheatingorDHWcircuitmustbeabletosendits temperaturedemandtocircuit1orthemaster: MENU\Settings\Application: 'SenddesiredT'(ID1x500):ON
WhenaheatingorDHWcircuitshouldnotsenditstemperature demandtocircuit1orthemaster: MENU\Settings\Application: 'SenddesiredT'(ID1x500):OFF
*Thisrecommendedvalueisaddedtothehighesttemperature demandvaluefromthesub-circuitoraslave.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
AQ189686468137en-010601
©Danfoss|2021.12|15
Page 16
OperatingGuideECLComfort310,applicationA368

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
16|©Danfoss|2021.12
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ189686468137en-010601
Page 17
OperatingGuideECLComfort310,applicationA368
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
AQ189686468137en-010601
©Danfoss|2021.12|17
Page 18
OperatingGuideECLComfort310,applicationA368
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
18|©Danfoss|2021.12
AQ189686468137en-010601
Page 19
OperatingGuideECLComfort310,applicationA368
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
AQ189686468137en-010601
©Danfoss|2021.12|19
Page 20
OperatingGuideECLComfort310,applicationA368

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
20|©Danfoss|2021.12
AQ189686468137en-010601
Page 21
OperatingGuideECLComfort310,applicationA368
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ189686468137en-010601
©Danfoss|2021.12|21
Page 22
OperatingGuideECLComfort310,applicationA368

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
22|©Danfoss|2021.12
AQ189686468137en-010601
Page 23
OperatingGuideECLComfort310,applicationA368
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ189686468137en-010601
©Danfoss|2021.12|23
Page 24
OperatingGuideECLComfort310,applicationA368
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
24|©Danfoss|2021.12
AQ189686468137en-010601
Page 25
OperatingGuideECLComfort310,applicationA368
2.5.3Electricalconnections,safetythermostats,ingeneral
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Theconnectiondiagramsshowvarioussolutions/examples:
Safetythermostat,1–stepclosing: Motorizedcontrolvalvewithoutsafetyfunction
Safetythermostat,1–stepclosing: Motorizedcontrolvalvewithsafetyfunction
Safetythermostat,2–stepclosing: Motorizedcontrolvalvewithsafetyfunction
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
AQ189686468137en-010601
©Danfoss|2021.12|25
Page 26
OperatingGuideECLComfort310,applicationA368
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
A368,Pt1000,ECL310
S1S2S3S4S5S6S7S8
A368.1
A368.2
A368.3
A368.4
A368.5
A368.6
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
Sensor
S1
Description
Outdoortemperature
Recommendedtype
ESMT
sensor*
S2
Supplyflowtemperature sensor
S3
Flowtemperaturesensor**, heating
S4
Flowtemperaturesensor**,
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESMB/ESMU
DHW
S5Returntemperaturesensor,
heating
S6Returntemperaturesensor,
DHW
S7
Differentialpressureswitch,
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
heating
S8
Differentialpressureswitch, DHW or Returntemperaturesensor, DHWcirculation
S9 S10
Alarmswitch Pressuretransmitter(0–10
ESM-11/ESMB/ ESMC/ESMU
Vor4–20mA)orpressure switch
*
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
**
Theflowtemperaturesensormustalwaysbeconnected inordertohavethedesiredfunctionality.Ifthesensoris notconnectedorthecableisshort-circuited,themotorized controlvalvecloses(safetyfunction).
26|©Danfoss|2021.12
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ189686468137en-010601
Page 27
OperatingGuideECLComfort310,applicationA368
Connectionofflowmeter
SeetheInstallationGuide(deliveredwiththeapplicationkey).
Connectionofflowswitchoralarmcontact/switch
ThealarmcontactactsasaNormallyClosed(NC)contact.The set-upcanbechangedtoreactonaNormallyOpen(NO)contact. SeeCircuit1>MENU>Alarm>Digital>Alarmvalue:
0=AlarmforNOcontact 1=AlarmforNCcontact
Connectionofpressuretransmitter
ScaleforconversionofvoltagetopressureissetintheECLComfort. Thepressuretransmitterispoweredwith12-24Vd.c. Outputtypes:0-10Vor4-20mA. 4-20mAsignalisconvertedtoa2-10Vsignalbymeansofa500 ohm(0,5W)resistor.
Connectionof2differentialpressureswitches
Connectionofalarmswitch,S9
Connectionofapressureswitch
AQ189686468137en-010601
©Danfoss|2021.12|27
Page 28
OperatingGuideECLComfort310,applicationA368
Connectionofpressuretransmitterwith0-10Voutput
Vd.c.:Thepressuretransmitterispoweredwith12-24Vd.c.
Connectionofpressuretransmitterwith4-20mAoutput
Vd.c.:Thepressuretransmitterispoweredwith12-24Vd.c. The4-20mAsignalisconvertedtoa2-10Vsignalbymeansofthe 500ohm(0,5W)resistor.
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus) Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
28|©Danfoss|2021.12
AQ189686468137en-010601
Page 29
OperatingGuideECLComfort310,applicationA368
Pt1000temperaturesensorsandsignals
A368,ECA32
S11S12S13S14S15S16
A368.1
A368.2
A368.3
A368.4
A368.5
A368.6
✔ ✔
✔ ✔
SeealsotheA368MountingGuide.
Sensor
S11
Description
Heating,secondaryside, returntemperaturesensor or Pressuretransmitter,0–10V or4–20mA
S12 S13
Alarmswitch DHWcirculation,return
temperaturesensor or Pressuretransmitter,0–10V or4–20mA
S14Pressuretransmitter,0–10V
or4–20mA
S15Pressuretransmitter,0–10V
or4–20mA
S16Pressuretransmitter,0–10V
or4–20mA
ConnectionofalarmswitchS12
Recommendedtype
Temp.sensor:ESM-11/ ESMB/ESMC/ESMU
Temp.sensor:ESM-11/ ESMB/ESMC/ESMU
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus) Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ189686468137en-010601
©Danfoss|2021.12|29
Page 30
OperatingGuideECLComfort310,applicationA368
Pressuretransmitters
A368,ECA32
S11S12S13S14S15S16
A368.1
A368.2
A368.3
A368.4
A368.5
A368.6
Connectionofpressuretransmitterwith0-10Voutput
Vd.c.:Thepressuretransmitterispoweredwith12-24Vd.c.
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
SeealsotheA368MountingGuide.
Connectionofpressuretransmitterwith4-20mAoutput
Vd.c.:Thepressuretransmitterispoweredwith12-24Vd.c. The4-20mAsignalisconvertedtoa2-10Vsignalbymeansofthe 500ohm(0,5W)resistor.
A368.5:
ECA32,connectionofwatermeter.Pulsetype,inputF1.
SeealsotheA368MountingGuide.
SeealsotheA368MountingGuide.
30|©Danfoss|2021.12
AQ189686468137en-010601
Page 31
OperatingGuideECLComfort310,applicationA368
2.5.5Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
AQ189686468137en-010601
©Danfoss|2021.12|31
Page 32
OperatingGuideECLComfort310,applicationA368
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
32|©Danfoss|2021.12
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
AQ189686468137en-010601
Page 33
OperatingGuideECLComfort310,applicationA368
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
AQ189686468137en-010601
©Danfoss|2021.12|33
Page 34
OperatingGuideECLComfort310,applicationA368

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
34|©Danfoss|2021.12
ECLComfort296
AQ189686468137en-010601
Page 35
OperatingGuideECLComfort310,applicationA368
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ189686468137en-010601
©Danfoss|2021.12|35
Page 36
OperatingGuideECLComfort310,applicationA368
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
36|©Danfoss|2021.12
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
AQ189686468137en-010601
Page 37
OperatingGuideECLComfort310,applicationA368
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
AQ189686468137en-010601
©Danfoss|2021.12|37
Page 38
OperatingGuideECLComfort310,applicationA368
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
38|©Danfoss|2021.12
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
AQ189686468137en-010601
Page 39
OperatingGuideECLComfort310,applicationA368
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
AQ189686468137en-010601
©Danfoss|2021.12|39
Page 40
OperatingGuideECLComfort310,applicationA368
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
40|©Danfoss|2021.12
AQ189686468137en-010601
Page 41
OperatingGuideECLComfort310,applicationA368

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
AQ189686468137en-010601
©Danfoss|2021.12|41
Page 42
OperatingGuideECLComfort310,applicationA368

2.8Navigation,ECLApplicationKeyA368

Navigation,applicationA368.1andA368.3,circuit1and2
Home
IDno.
MENU ScheduleSelectableSelectable
Settings
Flowtemperature
11178 11177 11004
Returnlimit
11031 11032 11033 11034 11035 11036 11037 11085 11029 11028
Flow/powerlimitActualActual
11119 11117 11118 11116 11112 11113 11109 11115
Optimization
Controlpar.
11011 11012 11013 11014 11026 11021 11179 11043
11174 11184 11185 11186 11187 11189
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve Temp.max. Temp.min. DesiredT
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,re.Tlim.
Limit HighToutX1 LowlimitY1 LowToutX2
HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Prestop Totalstop Summer,cut-out Paralleloperation
Motorpr. Xp Tn Mrun Nz Min.act.time
IDno.
12178 12177
12030
12035 12036 12037 12085
12111
12112 12113 12109 12115
12173 12174 12184 12185 12186 12187 12189
Function
Temp.max. Temp.min.
Limit
Infl.-max. Infl.-min. Adapt.time Priority
Limit
Adapt.time Filterconstant Inputtype Units
Autotuning Motorpr. Xp Tn Mrun Nz Min.act.time
42|©Danfoss|2021.12
AQ189686468137en-010601
Page 43
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.1andA368.3,circuit1andcircuit2continued
Home MENU
Settings
HolidaySelectableSelectable
Alarm
Pumpcontrol
Refillwater
Application
Heatcut-out
Anti-bacteria
Temp.monitor.
Clearalarm
AlarmoverviewSelectableSelectable
IDno.
11314 11310 11313 11311 11312 11022
11327 11323 11321 11322 11320 11325 11326 11316
11017 11500 11023 11052 11077 11078 11093 11141 11142
11393 11392 11179 11395 11397 11396 11398 11399
11147 11148 11149 11150
11315 11324
Circuit1,HeatingCircuit2,DHW
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise
Pressure Inputtype Time-out Pressure,des. Pressure,diff. Pexercise Valvedelay No.ofpumps Alarmhandling
Demandoffset SenddesiredT Mexercise DHWpriority PfrostT PheatT Frostpr.T Ext.input Ext.mode
Sum.start,day Sum.start,month Summer,cut-out Summer,filter Winterstart,day Win.start,month Winter,cut-out Winter,filter
Upperdifference Lowerdifference Delay Lowesttemp.
Circ.pumps Refillwater
IDno.
12314 12310 12313 12311 12312 12022
12500 12023
12077 12078 12093 12141 12142
12147 12148 12149 12150
12315
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise
SenddesiredT Mexercise
PfrostT PheatT Frostpr.T Ext.input Ext.mode
Day Starttime Duration DesiredT
Upperdifference Lowerdifference Delay Lowesttemp.
Circ.pumps
AQ189686468137en-010601
©Danfoss|2021.12|43
Page 44
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.1andA368.3,circuit1andcircuit2continued
Home MENU InfluenceoverviewDes.flowTReturnlim.Returnlim.
IDno.
Circuit1,HeatingCircuit2,DHW
Function
Parallelpriority Flow/powerlim.Flow/powerlim. HolidayHoliday Ext.overrideExt.override Boost Ramp Slave,demand Heatingcut-out DHWpriority
IDno.
Function
Anti-bacteria
44|©Danfoss|2021.12
AQ189686468137en-010601
Page 45
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.1andA368.3;Commoncontrollersettings(*A368.3only)
Home MENU Time&Date Settings* HolidaySelectable Inputoverview
Log(sensors)
Outputoverride
AlarmDigitalS9Alarmvalue
Keyfunctions
SystemECLversion
OutdoorTLogtoday Heatingflow&des. DHWflow&des. HeatreturnT&limitLog4days DHWreturnT&limit Staticpressure
DigitalS12*Alarmtime-out AlarmoverviewDigitalS9,digitalS12* NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview Alarm Display
Communication
Language
Commoncontrollersettings
IDno.
60058 60059
2048
38
39 2150 2151 2050
Function
Selectable S11,S13...S16press.sensor
OutdoorT HeatflowT DHWflowT HeatreturnT DHWreturnT Staticpressure S11,S13...S16pressure* S7,S8,S9,S12*status
Logyesterday Log2days
M1,P1,P2,M2,P3,P5,V1,P4, P7*,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
Selectable Selectable Selectable Selectable
Backlight Contrast ECL485addr. Modbusaddr. Baud Servicepin Ext.reset Language
AQ189686468137en-010601
©Danfoss|2021.12|45
Page 46
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.2andA368.4,circuit1and2
Home
IDno.
MENU ScheduleSelectableSelectable
Settings
Flowtemperature
11178 11177 11300 11301 11302 11303 11004
Returnlimit
11031 11032 11033 11034 11035 11036 11037 11085 11029 11028
Flow/powerlimitActualActual
11119 11117 11118 11116 11112 11113 11109 11115
Optimization
Controlpar.
11011 11012 11013 11014 11026 11021 11179 11043
11174 11184 11185 11186 11187 11189
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve Temp.max. Temp.min. Highsupp.TX2 HighTmaxY2 LowsupplyTX1 LowTmaxY1 DesiredT
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,re.Tlim.
Limit HighToutX1 LowlimitY1 LowToutX2
HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Prestop Totalstop Summer,cut-out Paralleloperation
Motorpr. Xp Tn Mrun Nz Min.act.time
IDno.
12178 12177
12030
12035 12036 12037 12085
12111
12112 12113 12109 12115
12173 12174 12184 12185 12186 12187 12189
Function
Temp.max. Temp.min.
Limit
Infl.-max. Infl.-min. Adapt.time Priority
Limit
Adapt.time Filterconstant Inputtype Units
Autotuning Motorpr. Xp Tn Mrun Nz Min.act.time
46|©Danfoss|2021.12
AQ189686468137en-010601
Page 47
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.2andA368.4,circuit1andcircuit2continued
Home MENU Settings
HolidaySelectableSelectable
Alarm
Pumpcontrol
Refillwater
Application
Heatcut-out
Anti-bacteria
Temp.monitor.
Clearalarm
AlarmoverviewSelectableSelectable
IDno.
11314 11310 11313 11311 11312 11022
11327 11323 11321 11322 11320 11325 11326 11316 11017 11500 11023 11052 11077 11078 11093 11141 11142
11393 11392 11179 11395 11397 11396 11398 11399
11147 11148 11149 11150 11315 11324
Circuit1,HeatingCircuit2,DHW
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise Pressure Inputtype Time-out Pressure,des. Pressure,diff. Pexercise Valvedelay No.ofpumps Alarmhandling Demandoffset SenddesiredT Mexercise DHWpriority PfrostT PheatT Frostpr.T Ext.input Ext.mode
Sum.start,day Sum.start,month Summer,cut-out Summer,filter Winterstart,day Win.start,month Winter,cut-out Winter,filter
Upperdifference Lowerdifference Delay Lowesttemp. Circ.pumps Refillwater
IDno.
12314 12310 12313 12311 12312 12022
12500 12023
12077 12078 12093 12141 12142
12147 12148 12149 12150 12315
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise
SenddesiredT Mexercise
PfrostT PheatT Frostpr.T Ext.input Ext.mode
Day Starttime Duration DesiredT
Upperdifference Lowerdifference Delay Lowesttemp. Circ.pumps
AQ189686468137en-010601
©Danfoss|2021.12|47
Page 48
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.2andA368.4,circuit1andcircuit2continued
Home MENU InfluenceoverviewDes.flowT
IDno.
Circuit1,HeatingCircuit2,DHW
Function
Returnlim.Returnlim. Parallelpriority Flow/powerlim.Flow/powerlim. HolidayHoliday Ext.overrideExt.override Boost Ramp Slave,demand Heatingcut-out DHWpriority
IDno.
Function
Anti-bacteria
48|©Danfoss|2021.12
AQ189686468137en-010601
Page 49
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.2andA368.4,Commoncontrollersettings(*A368.4only)
Home MENU Time&Date Settings* HolidaySelectable Inputoverview
Log(sensors)
Outputoverride
AlarmDigitalS9Alarmvalue
Keyfunctions
SystemECLversion
OutdoorTLogtoday SupplyTLogyesterday Heatingflow&des. DHWflow&des. HeatreturnT&limit DHWreturnT&limit Staticpressure
DigitalS12*Alarmtime-out AlarmoverviewDigitalS9,digitalS12* NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview Alarm Display
Communication
Language
Commoncontrollersettings
IDno.
60058 60059
2048
38
39 2150 2151 2050
Function
Selectable S11,S13...S16press.sensor
OutdoorT SupplyT HeatflowT DHWflowT HeatreturnT DHWreturnT Staticpressure S11,S13...S16pressure* S7,S8,S9,S12*status
Log2days Log4days
M1,P1,P2,M2,P3,P5,V1,P4, P7*,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware
Software Buildno. Serialno. MAC
Productionweek
Selectable Selectable Selectable Selectable
Backlight Contrast ECL485addr. Modbusaddr. Baud Servicepin Ext.reset Language
AQ189686468137en-010601
©Danfoss|2021.12|49
Page 50
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,circuit1and2
Home
IDno.
MENU ScheduleSelectableSelectable
Settings
Flowtemperature
11178 11177 11004
Returnlimit
11031 11032 11033 11034 11035 11036 11037 11085 11029 11028
Flow/powerlimitActualActual
11119 11117 11118 11116 11112 11113 11109 11115
Optimization
Controlpar.
11011 11012 11013 11014 11026 11021 11179 11043
11174 11184 11185 11186 11187 11189
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve Temp.max. Temp.min. DesiredT
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,re.Tlim.
Limit HighToutX1 LowlimitY1 LowToutX2
HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Prestop Totalstop Summer,cut-out Paralleloperation
Motorpr. Xp Tn Mrun Nz Min.act.time
IDno.
12178 12177
12030
12035 12036 12037 12085
12111
12112 12113 12109 12115
12173 12174 12184 12185 12186 12187 12189
Function
Temp.max. Temp.min.
Limit
Infl.-max. Infl.-min. Adapt.time Priority
Limit
Adapt.time Filterconstant Inputtype Units
Autotuning Motorpr. Xp Tn Mrun
Nz Min.act.time
50|©Danfoss|2021.12
AQ189686468137en-010601
Page 51
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,circuit1andcircuit2continued(*A368.5only)
Home MENU Settings
HolidaySelectableSelectable
Alarm
Pumpcontrol
Refillwater
Application
Heatcut-out
Watermeter*
Anti-bacteria
Temp.monitor.
Clearalarm*
AlarmoverviewSelectableSelectable
IDno.
11314 11310 11313 11311 11312 11022
11327 11323 11321 11322 11320 11325 11326 11316 11017 11500 11023 11052 11077 11078 11093 11141 11142
11393 11392 11179 11395 11397 11396 11398 11399
11513 11514
11147 11148 11149 11150 11315 11324
Circuit1,HeatingCircuit2,DHW
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise Pressure Inputtype Time-out Pressure,des. Pressure,diff. Pexercise Valvedelay No.ofpumps Alarmhandling Demandoffset SenddesiredT Mexercise DHWpriority PfrostT PheatT Frostpr.T Ext.input Ext.mode
Sum.start,day Sum.start,month Summer,cut-out Summer,filter Winterstart,day Win.start,month Winter,cut-out Winter,filter
Consump. Pulsevalue Preset
Upperdifference Lowerdifference Delay Lowesttemp. Circ.pumps* Refillwater*
IDno.
12314 12310 12313 12311 12312 12022
12500 12023
12077 12078 12093 12141 12142
12147 12148 12149 12150 12315
Function
Chan.-overtime* Retrytime* Stab.time* Change,duration* Changetime* Pexercise*
SenddesiredT Mexercise
PfrostT PheatT Frostpr.T Ext.input Ext.mode
Day Starttime Duration DesiredT
Upperdifference Lowerdifference Delay Lowesttemp. Circ.pumps*
AQ189686468137en-010601
©Danfoss|2021.12|51
Page 52
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,circuit1andcircuit2continued
Home MENU InfluenceoverviewDes.flowT
IDno.
Circuit1,HeatingCircuit2,DHW
Function
Returnlim.Returnlim. Parallelpriority Flow/powerlim.Flow/powerlim. HolidayHoliday Ext.overrideExt.override Boost Ramp Slave,demand Heatingcut-out DHWpriority
IDno.
Function
Anti-bacteria
52|©Danfoss|2021.12
AQ189686468137en-010601
Page 53
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,Commoncontrollersettings(*A368.5only)
Home MENU Time&Date Settings* HolidaySelectable Inputoverview
Log(sensors)
Outputoverride
AlarmDigitalS9Alarmvalue
Keyfunctions
OutdoorTLogtoday Heatingflow&des.
HeatreturnT&limitLog2days Heatsec.returnT DHWflow&des. DHWreturnT&lim. Circ.returnT Staticpressure
DigitalS12*Alarmtime-out AlarmoverviewDigitalS9,digitalS12* NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Commoncontrollersettings
IDno.
Function
Selectable S14,S15,S16press.sensor
OutdoorT HeatflowT HeatreturnT Heatsec.returnT DHWflowT DHWreturnT Circ.returnT Staticpressure S14,S15,S16pressure* S7,S8*,S9,S12*status Consump.*
Logyesterday
Log4days
M1,P1,P2,M2,P3,P5,V1,P4, P7*,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
AQ189686468137en-010601
©Danfoss|2021.12|53
Page 54
OperatingGuideECLComfort310,applicationA368
Navigation,applicationsA368.5andA368.6,Commoncontrollersettings(*A368.5only)
Home MENU SystemECLversion
Extension Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview Alarm Display
Communication
Language
Commoncontrollersettings
IDno.
60058 60059
2048
38
39 2150 2151 2050
Function
Codeno. Hardware Software Buildno. Serialno. MAC
Productionweek
Selectable Selectable Selectable Selectable
Backlight Contrast ECL485addr. Modbusaddr. Baud Servicepin Ext.reset Language
54|©Danfoss|2021.12
AQ189686468137en-010601
Page 55
OperatingGuideECLComfort310,applicationA368

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ189686468137en-010601
©Danfoss|2021.12|55
Page 56
OperatingGuideECLComfort310,applicationA368

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
56|©Danfoss|2021.12
)
AQ189686468137en-010601
Page 57
OperatingGuideECLComfort310,applicationA368
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
DHWcircuit
Overviewdisplay1informsabout: actualDHWtemperature,controllermode,desiredDHW temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout: stateofthecontrolledcomponents,actualDHWtemperature, (desiredDHWtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith Influenceindication:
AQ189686468137en-010601
©Danfoss|2021.12|57
Page 58
OperatingGuideECLComfort310,applicationA368
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
Examples:
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled operationandincomfortmode.
Examples:
50
55
58|©Danfoss|2021.12
AQ189686468137en-010601
Page 59
OperatingGuideECLComfort310,applicationA368
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
AQ189686468137en-010601
©Danfoss|2021.12|59
Page 60
OperatingGuideECLComfort310,applicationA368

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
60|©Danfoss|2021.12
DamperOFF
AQ189686468137en-010601
Page 61
OperatingGuideECLComfort310,applicationA368

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview oftheactualand(desired)temperaturesaswellastheactualstate ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
(30)
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
Flowtemperature
Desiredflowtemperature
--
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
AQ189686468137en-010601
©Danfoss|2021.12|61
Page 62
OperatingGuideECLComfort310,applicationA368
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
62|©Danfoss|2021.12
AQ189686468137en-010601
Page 63
OperatingGuideECLComfort310,applicationA368

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
AQ189686468137en-010601
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
©Danfoss|2021.12|63
Page 64
OperatingGuideECLComfort310,applicationA368

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
64|©Danfoss|2021.12
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ189686468137en-010601
Page 65
OperatingGuideECLComfort310,applicationA368

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Actual(actualfloworpower)
Pressure
Extendedheatcut-outsetting
Extendedwintercut-outsetting
Day
Starttime
Duration
DesiredT
S11,S13...S16press.sensor
DesiredT(Desiredflowtemperature)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Demandoffset
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Pre-stop(optimizedstoptime)
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
DHW,ret.Tlimit
Limit(returntemp.limitation)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Paralleloperation
DHWpriority(closedvalve/normaloperation)
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Inputtype
Limit(limitationvalue)
1x004
1x01183
1x01284
1x01385
1x01485
1x017103
1x02186
1x02294
1x023103
1x02687
1x028
1x029
1x03076
1x03176
1x03276
1x03376
1x034
1x035
1x036
1x037
1x04387
1x052104
1x077104
1x078104
1x08578
1x093104
1x10980
1x111
Factorysettingsincircuit(s)
1
69
80
97
110
110
120
120
121
121
124
71
75
75
77
77
77
77
80
2
AQ189686468137en-010601
©Danfoss|2021.12|65
Page 66
OperatingGuideECLComfort310,applicationA368
SettingIDPage
Adapt.time(adaptationtime)
Filterconstant
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Autotuning
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Highsupp.TX2(highvalueofsupplytemp.)
HighTmaxY2(highvalueofmaxlimitation)
LowsupplyTX1(lowvalueofsupplytemp.)
LowTmaxY1(lowvalueofmaxlimitation)
Retrytime
Change,duration
Changetime(changeovertime)
Stab.time(stabilizationtime)
Chan.-overtime(change-overtime)
Circ.pumps
Alarmhandling
Pexercise(pumpexercise)
Pressure,diff.(switchingdifference)
Time-out
Refillwater
Valvedelay
No.ofpumps
Inputtype
SenddesiredT
1x11281
1x11381
1x115
1x11681
1x117
1x11882
1x11982
1x141
1x142105
1x147115
1x148116
1x149116
1x150
1x17390
1x174
1x17771
1x178
1x17988
1x18491
1x18591
1x18692
1x18792
1x18992
1x30072
1x30172
1x30272
1x30372
1x31094
1x31194
1x31295
1x31395
1x31495
1x315
1x31698
1x32098
1x32299
1x32399
1x324
1x325100
1x326101
1x327101
1x500107
Factorysettingsincircuit(s)
1
81
82
105
117
91
71
117
117
2
66|©Danfoss|2021.12
AQ189686468137en-010601
Page 67
OperatingGuideECLComfort310,applicationA368
Pulsevalue
Preset
Pressure
Consump.(A368.5)
SettingIDPage
1x513112
1x514
Read-
out
Read-
out
Factorysettingsincircuit(s)
1
112
99
112
2
AQ189686468137en-010601
©Danfoss|2021.12|67
Page 68
OperatingGuideECLComfort310,applicationA368

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
68|©Danfoss|2021.12
AQ189686468137en-010601
Page 69
OperatingGuideECLComfort310,applicationA368

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
AQ189686468137en-010601
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
©Danfoss|2021.12|69
Page 70
OperatingGuideECLComfort310,applicationA368
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
Thedesiredflowtemperatureissetin'Des.Tcomfort'and'Des.T saving'.Setvaluesforcomfortmodecouldforexamplebe7.5°C andforsavingmode25°C.
Alternativelythedesiredflowtemperaturecanbesetbyapplying anexternalsignal.Thechoiceissetin'Ext.signal'.
TheECLComfort210/296/310controlstheDHWtemperature accordingtothedesiredflowtemperatureforexampleunderthe influenceofthereturntemperature.
ActualDHWtemp.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
DesiredDHW temp.
70|©Danfoss|2021.12
AQ189686468137en-010601
Page 71
OperatingGuideECLComfort310,applicationA368
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flowtemperature
DesiredT(Desiredflowtemperature)
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow temperaturecanbeset. A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU >Settings>Returnlimit>'Con.T,ret.Tlim. '
1x004
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan beappliedtoaninputinordertooverridetoComfort,Saving,Frost ProtectionorConstanttemperature.Aslongasthecontact(switch) signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
AQ189686468137en-010601
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
©Danfoss|2021.12|71
Page 72
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Flowtemperature
A368.2andA368.4:Themax.valueisnotadjustable,butdetermined bythesettings"Highsup.TX2"andrelated(ID:1x300,1x301,1x302 and1x303).
Highsupp.TX2(highvalueofsupplytemp.)
1x300
SeeAppendix“ParameterIDoverview”
Setthehighvalueforthesupplytemperatureinrelationtothe desiredmax.flowtemperature.Whenthesupplytemperatureis abovethesetvalue,themax.limitationoftheflowtemperatureis theY2value.Whenthesupplytemperatureisbelowthesetvalue, themax.limitationoftheflowtemperaturewillbelower.
MENU>Settings>Flowtemperature
HighTmaxY2(highvalueofmaxlimitation)
1x301
SeeAppendix“ParameterIDoverview”
Setthehighvalueforthemax.limitationofthedesiredflow temperature.
A368.2andA368.4offeralimitationofamax.desiredflow temperatureinrelationtothemeasuredtemperatureatS2.Bythis,the supplytemperaturecanalsodeterminethedesiredflowtemperature.
MENU>Settings>Flowtemperature
LowsupplyTX1(lowvalueofsupplytemp.)
1x302
SeeAppendix“ParameterIDoverview”
Setthelowvalueforthesupplytemperatureinrelationtothe desiredmax.flowtemperature.Whenthesupplytemperatureis belowthesetvalue,themax.limitationoftheflowtemperatureis theY1value.Whenthesupplytemperatureisabovethesetvalue, themax.limitationoftheflowtemperaturewillbehigher.
MENU>Settings>Flowtemperature
LowTmaxY1(lowvalueofmaxlimitation)
1x303
SeeAppendix“ParameterIDoverview”
Setthelowvalueforthemax.limitationofthedesiredflow temperature.
72|©Danfoss|2021.12
AQ189686468137en-010601
Page 73
OperatingGuideECLComfort310,applicationA368

5.3Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant temperaturevalue. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthesetlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
AQ189686468137en-010601
©Danfoss|2021.12|73
Page 74
OperatingGuideECLComfort310,applicationA368
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
74|©Danfoss|2021.12
AQ189686468137en-010601
Page 75
OperatingGuideECLComfort310,applicationA368
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
The"Con.T ,ret.Tlimit"isthereturntemperaturelimitationvaluewhenthe circuitissettooverridemodetype"Const.T"(=Constanttemperature).
SeeAppendix“ParameterIDoverview”
Value:Setthereturntemperaturelimitation
1x028
AQ189686468137en-010601
©Danfoss|2021.12|75
Page 76
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Returnlimit
DHW,ret.Tlimit
WhenanaddressedslaveisactiveinDHW-tankheating/charging,the returntemperaturelimitationinthemastercanbeset. Notes:
Themastercircuitmustbesettoreactonthedesiredflowtemperature intheslave(s).See"Demandoffset"(ID11017).
Theslave(s)mustbesettosendits/theirdesiredflowtemperatureto themaster.See"SenddesiredT"(ID1x500).
SeeAppendix“ParameterIDoverview”
OFF:
Noinfluencefromslaves.Thereturntemperature limitationisrelatedtosettingsin"Returnlimit" .
Value:Returntemperaturelimitationvaluewhenslaveisin
DHWtankheating/chargingoperation.
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x029
#1#=Master,exampleA266,address15 #2#=Slave,exampleA237,address9 #3#=Slave,exampleA367,address6
SomeexamplesofapplicationswithDHW-tankheating/chargingare:
•A217,A237,A247,A367,A377
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe setvalue,thecontrollerautomaticallychangesthedesiredflow/ ducttemperaturetoobtainanacceptablereturntemperature.The influenceissetin'Infl.-max. 'and'Infl.-min.' .
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
1x031
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
1x032
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
76|©Danfoss|2021.12
AQ189686468137en-010601
Page 77
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
1x033
1x034
Example
1x035
Thereturnlimitisactiveabove50°C. Theinfluenceissetto0.5. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby0.5x2=1.0degree.
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthesetlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthesetlimit.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Example
1x036
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
AQ189686468137en-010601
©Danfoss|2021.12|77
Page 78
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x037
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
78|©Danfoss|2021.12
AQ189686468137en-010601
Page 79
OperatingGuideECLComfort310,applicationA368

5.4Flow/powerlimit

Heatingcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2# #Y1#
#Y2#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
=
X
Y
#1#
#2#
#3#
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
AQ189686468137en-010601
©Danfoss|2021.12|79
Page 80
OperatingGuideECLComfort310,applicationA368
DHWcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower. Whentheflow/powergetshigherthanthesetlimit,thecontroller graduallyreducesthedesiredflowtemperaturetoobtainan acceptablemax.floworpowerconsumption.
=
X
Y
#1#
#2#
#3#
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Inputtype
ChoiceofM-bussignalfromenergymeternumber1...5.Onlypossible inECLComfort310.
SeeAppendix“ParameterIDoverview”
OFF:
EM1...EM5:
NoM-bussignalacquired. Energymeternumber.
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
1x109
FloworpowerlimitationisbasedonM-bussignal(ECLComfort310 controllersonly).
80|©Danfoss|2021.12
AQ189686468137en-010601
Page 81
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
1x111
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Flowvaluesareexpressedasl/horm³/h PowervaluesareexpressedaskW,MWorGW.
1x113
1x115
Listforsettingrangeof'Units': l/h m³/h kW MW GW
AQ189686468137en-010601
©Danfoss|2021.12|81
Page 82
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
1x116
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
1x118
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
1x119
82|©Danfoss|2021.12
AQ189686468137en-010601
Page 83
OperatingGuideECLComfort310,applicationA368

5.5Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost','Optimizer','Totalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
AQ189686468137en-010601
©Danfoss|2021.12|83
Page 84
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
84|©Danfoss|2021.12
AQ189686468137en-010601
Page 85
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
=
X Y #1#
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
AQ189686468137en-010601
©Danfoss|2021.12|85
Page 86
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
-5°C
small
86|©Danfoss|2021.12
AQ189686468137en-010601
Page 87
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost protectionisstillactive,see'PfrostT' .
Totalstop=OFF
Totalstop=ON
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
1x026
Example:OptimizationofComfortfrom07:00-22:00
=
X #1# #2# #3# #4# #5#
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
AQ189686468137en-010601
©Danfoss|2021.12|87
Page 88
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Paralleloperation
ChoosewhethertheheatingcircuitistooperateindependenceoftheDHW circuit.Thisfunctionmightbeusefulifaninstallationhaslimitedpower orflow.
SeeAppendix“ParameterIDoverview”
OFF:
Independentparalleloperation,i.e.theDHWand theheatingcircuitsoperateindependentlyofeach other.ItmakesnodifferencewhetherthedesiredDHW temperaturecanbereachedornot.
Value:Dependentparalleloperation,i.e.thedesiredheating
temperaturedependsontheDHWdemand.Choose howmuchtheDHWtemperaturecandropbeforethe desiredheatingtemperaturehastobedecreased.
1x043
=
X
Y1
Y2
#1#
#2#
#3#
#4#
#5#
#6#
#7#
Time
=
Temperature
=
Temperature
=
Acceptabledeviation(Paralleloperation,1x043)
=
DesiredDHWtemperature
=
ActualDHWtemperature
=
Desiredheatingtemperature
=
Reducedheatingtemperature
=
100%paralleloperation
=
Paralleloperationwithdecreasedheatingtemperature
IftheactualDHWtemperaturedeviatesmorethanthesetvalue,the gearmotorM2intheheatingcircuitwillgraduallyclosetosuchan extentthattheDHWtemperaturestabilizesatthelowestacceptable value.
IncasetheParalleloperationisactive(atoolowDHWtemperature andthereforeareducedheatingcircuittemperature),aslave's temperaturedemandwillnotchangethedesiredflowtemperaturein theheatingcircuit.
Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
88|©Danfoss|2021.12
AQ189686468137en-010601
Page 89
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
Summer,cut-out
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
AQ189686468137en-010601
©Danfoss|2021.12|89
Page 90
OperatingGuideECLComfort310,applicationA368

5.6Controlparameters

Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point controlsignal.
Valvecontrol: Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
90|©Danfoss|2021.12
AQ189686468137en-010601
Page 91
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Controlparameters
Autotuning
AutomaticallydeterminesthecontrolparametersfortheDHWcontrol.'Xp' 'Tn'and'Mrun'donotneedtobeset,whenusingautotuning.'Nz'must beset.
1x173
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Autotuningisnotactivated. Autotuningisactivated.
Theautotuningfunctionautomaticallydeterminesthecontrol parametersforDHWcontrol.Thusyoudonotneedtosetthe'Xp', 'Tn'and'Mrun',astheyareautomaticallysetwhentheautotuning functionissettoON.
Autotuningistypicallyusedinconnectionwiththeinstallationof thecontroller,butitcanbeactivatedwhenneeded,e.g.foran extracheckofthecontrolparameters.
Beforestartingtheautotuning,thetappingflowshouldbe adjustedtotherelevantvalue(seetable).
Ifpossible,anyadditionalDHWconsumptionshouldbeavoided duringtheautotuningprocess.Shouldthetappingloadvarytoo much,theautotuningandcontrollerwillreturntothedefault settings.
No.of apartments
Heat transfer
ConstantDHWdraw-off(l/min)
(kW)
1-230-493 3-950-796 10-4980-14912
50-129150-24918
130-210250-35024
Inordertomeetthesummer-/wintervariations,theECLclockmust besettothecorrectdateforansuccessfulautotuning.
Themotorprotectionfunction('Motorpr.')hastobedeactivated duringautotuning.Duringautotuningthecirculationpumpfortap watermustbeswitchedoff.Thisisdoneautomaticallyifthepumpis controlledbytheECLcontroller.
Autotuningisonlyapplicableinconnectionwithvalvesthatare approvedforautotuning,i.e.theDanfosstypesVB2andVM2with splitcharacteristicaswellaslogarithmicvalvessuchasVFandVFS.
(or1tap25%open) (or1tap50%open) (or1tap100%open)
(or1tap100%+1tap50% open)
(or2taps100%open)
AutotuningisactivatedbysettingthefunctiontoON.Whenthe autotuningisended,thefunctionisautomaticallyconvertedto OFF(defaultsetting).Thiswillbeindicatedinthedisplay.
Theautotuningprocesstakesupto25minutes.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
1x174
Recommendedforductsystemswithvariableload.
1x184
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
AQ189686468137en-010601
©Danfoss|2021.12|91
Page 92
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
MENU>Settings>Controlparameters
1x185
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
92|©Danfoss|2021.12
AQ189686468137en-010601
Page 93
OperatingGuideECLComfort310,applicationA368
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
Criticaltimeperiod
Time
AQ189686468137en-010601
©Danfoss|2021.12|93
Page 94
OperatingGuideECLComfort310,applicationA368

5.7Pumpcontrol

Thisapplicationcanoperatewithoneortwocirculationpumps. Whenoperatingwithtwocirculationpumps,thepumpsare controlledalternately,accordingtoatimeset-up.Whenapump isswitchedONthecontrolleriswaitingfordifferentialpressure S7tobuildup.Ifdifferentialpressureisnotachieved,analarmis generatedandtheECLComfortcontrollerswitchesONtheother pump.
Ifnoneofthepumpscancomeintooperation(detectedbymeans ofthedifferentialpressureswitch),thealarmisactivatedandthe motorizedcontrolvalvecloses(asafetyfunction).
TheapplicationsA368.1...A368.5canoperatewithoneor twocirculationpumps.Whenoperatingwithtwocirculation pumps,thepumpsarecontrolledalternately,accordingtoatime set-up.WhenapumpisswitchedONthecontrolleriswaitingfor differentialpressureS8tobuildup.Ifdifferentialpressureisnot achieved,analarmisgeneratedandtheECLComfortcontroller switchesONtheotherpump.
Ifnoneofthepumpscancomeintooperation(detectedbymeans ofthedifferentialpressureswitch),thealarmisactivatedandthe motorizedcontrolvalvecloses(asafetyfunction).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Pumpcontrol
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat noon(12:14hours).
MENU>Settings>Pumpcontrol
Retrytime
Ifanalarmhasbeengeneratedforthepumporalarmshavebeengenerated forbothpumps,thissettingwilldeterminethetimebetweenthetimeofthe alarmandtheretrytimeforrepeatedpumpstart.
SeeAppendix“ParameterIDoverview”
1x022
1x310
OFF:
1...99:
94|©Danfoss|2021.12
Noretrytimerequiredafteranalarm.Thepumpor pumpsinquestionwillnotberestarted.
Afteranalarm,thepumporpumpswillberestarted afterthesettime.
AQ189686468137en-010601
Page 95
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Pumpcontrol
Change,duration
Thenumberofdaysbetweenshiftofcirculationpumps.Theshifttakesplace atthetimesetin'Changetime' .
SeeAppendix“ParameterIDoverview”
MENU>Settings>Pumpcontrol
Changetime(changeovertime)
Theexacttimeoftheday,wheretheshiftmusttakeplace.Thedayisdivided into24hours.Thefactorysettinghereis12whichmeans12:00(noon).
1x311
=
X #1# #2# #3#
1x312
Time
=
PumpP3
=
PumpP5
=
Change,duration(days)
SeeAppendix“ParameterIDoverview”
MENU>Settings>Pumpcontrol
Stab.time(stabilizationtime)
Settingofmax.timetoelapsebetweenpumpstartcommandandfeedback fromdifferentialpressureswitch. Ifthedifferentialpressureswitchdoesnotgivefeedbackwithinthesettime, thealarmwillbeactivatedandtheotherpumpwillgetastartcommand.
SeeAppendix“ParameterIDoverview”
=
X #1# #2# #3#
1x313
Time
=
PumpP3
=
PumpP5
=
Changetime(clocktime)
Ifthechosenstabilizationtime(‘Stab.time’)istooshort,theactive pumpwillstopimmediatelyafterthestabilizationtimehaselapsed.
AQ189686468137en-010601
©Danfoss|2021.12|95
Page 96
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Pumpcontrol
Chan.-overtime(change-overtime)
Settingoftimetoelapsebetweenthepumpstopcommandforonepump andthestartcommandfortheotherpump. Thechange-overtimecanensurethatapumpisstoppedefficientlybefore theotherpumpstarts.
SeeAppendix“ParameterIDoverview”
OFF:
1...99:
Onecirculationpumpintheapplication.
Timeforchange-over.
1x314
=
X #1# #2# #3#
Time
=
PumpP3
=
PumpP5
=
Change-overtime(sec.)
‘Chan.-overtime’hastobechoseninsystemswithtwopumps.
Thestatusofthedifferentialpressureswitchisshownin'Input overview'.
(Navigation:MENU>Commoncontroller>Inputoverview).
Example:
S7status...OFF/ON
OFF:
Thedifferentialpressureswitchisclosed(differential pressureisOK)
ON:
Thedifferentialpressureswitchisopen(differential pressureisnotOK)
96|©Danfoss|2021.12
AQ189686468137en-010601
Page 97
OperatingGuideECLComfort310,applicationA368
5.8Refillwater
Leaksontheconsumerssidewillresultinfallingstaticpressureand therebyapoorsupplyofheating.Arefillwaterfunctioncaninject watertoincreasethestaticpressure.
Thisapplicationcanmonitorthestaticpressureandenablethe refillwaterfunctionwhenthepressureistoolow.
Thepressureismeasuredbymeansofapressuretransmitter (givinga0-10voltsignalinrelationtothemeasuredpressure)or apressureswitch.
Whenapressuretransmittersignalisused,twosettingsinthe controllerrepresentpressuresetpointanddifference.
Whenapressureswitchsignalisused,thesetpointand(maybe) theswitchingdifferenceissetonthepressureswitch.
Whenatoolowpressureisdetectedtherefillwaterpumpis switchedONand,afterasettime,theON-OFFvalveisactivated.
Ifthepressureisnotachievedwithinasettime,analarmis generated.TheECLComfortcontrollerswitchesOFFthecirculation pumpsafter60secondsandthecontrolvalvecloses(asafety function).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
Thealarmfunctionisdisabledifthe"Alarmhandling"(ID11316)is settoOFF.
AQ189686468137en-010601
©Danfoss|2021.12|97
Page 98
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Refillwater
Pressure
CircuitSettingrange
1
Read-outonly
Theread-outcanbeavalue(inbar):
Thepressureismeasuredbymeansofapressuretransmitter. Thetransmittersendsthemeasuredpressureasa0-10Vora 4-20mAsignal.Thevoltagesignalcanbeapplieddirectlyto inputS10.Acurrentsignalisconvertedbymeansofaresistor toavoltageandthenappliedtoinputS10.Themeasured voltageoninputS10mustbeconvertedtoapressurevalueby thecontroller.Thisproceduresetsupthescaling.
Pushthedialtoseethegraphandenterthevaluesetsforthe inputvoltage(2and10volt)anddisplayedpressure(inbar).
Pressurevaluerange:0.0...30.0bar
Fixedvoltagesettings:2Vand10V
Factorysettings:(2.0,0)and(10,20.0)
Thismeansthatthe‘Pressure'is0.0barat2Vand20.0barat 10V.
Typically,thehigherthevoltage,thehigherthedisplayed pressure.
Ortheread-outcanbeOFForON:
Thepressureismeasuredbymeansofapressureswitch.The pressureswitchhasanopencontactwhenmeasuringatoolow pressure(shownasOFF).WhenmeasuredpressureisOK,the contactisclosed(shownasON).
Thepressureswitchcontact(potentialfree)isconnected directlytoinputS10.
Factorysetting
=
X Y #1# #2#
Volt
=
Bar
=
0bar
=
30,0bar
Thisscalingmenuisalwaysshown,regardlesswhetherapressure transmitterorapressureswitchisused.
MENU>Settings>Refillwater
Alarmhandling
Choosewhetherthecontrollermustreactonanunacceptablepressure.
SeeAppendix“ParameterIDoverview”
OFF:
Alarmfunctionisdisabled.Circulationpumpisnot stoppedalthoughthepressureistoolow.
ON:
Alarmfunctionisenabled.Circulationpumpisstopped ifthepressureistoolow.
1x316
98|©Danfoss|2021.12
AQ189686468137en-010601
Page 99
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Refillwater
Pexercise(pumpexercise)
Thetimethepumpisactivatedduringexercise.Exercisetakesplaceevery day(at12:00).
SeeAppendix“ParameterIDoverview”
OFF:
1...200:
Nopumpexercise.
Activationtimeduringexercise.
MENU>Settings>Refillwater
Pressure
CircuitSettingrange
1
Thepressureisindicatedasavaluemeasuredinbar. A0-10voltsignalcomesdirectlyfromapressuretransmitter (voltageoutput)orconvertedbymeansofaresistorfromapressure transmitter(currentoutput). Thevoltagesignalisappliedtotheinputinquestionandisconverted tothedisplayedpressurevalue. Accesstoconversion(scale)settings.
*)
2.0volt=0.0bar,10.0volt=20.0bar
-
Read-out
Factorysetting
1x320
*)
Thepressureismeasuredbymeansofa0-10voltsignal. Themeasuredvoltagemustbeconvertedtoapressure valuebythecontroller.
Thefollowingproceduresetsuptheconversion: Pushthedialtoseethegraphandenterthevaluesets forthe2inputvoltagesandrelatedpressurevalues. Pressurevaluerange:0.0…30.0bar.
Factorysettings:2,0.0(=2V/0.0bar)and10,10.0 (=10V/10.0bar).
Thismeansthatthe"Pressure"is0.0barat2Vand10.0 barat10V.Typically,thehigherthevoltage,thehigher thedisplayedpressure.
MENU>Settings>Refillwater
Pressure,diff.(switchingdifference)
Settingoftheswitchingdifferenceformeasuredstaticpressure(pressure transmitter).Thedifferenceissymmetricalaroundthe'Pressuredes. 'See also'Pressuredes. '
SeeAppendix“ParameterIDoverview”
=
X Y
1x322
Volt
=
Pressure(bar)
Thisscalingmenuisalwaysdisplayed,regardlessapressuresignal isapplied. Thepressureisindicatedas0.0barwhenthepressuresignalisnot applied.
Thesettingsin'Pressure,des. 'and'Pressure,diff.'havenoinfluence whenapressureswitchisused.
AQ189686468137en-010601
©Danfoss|2021.12|99
Page 100
OperatingGuideECLComfort310,applicationA368
MENU>Settings>Refillwater
Time-out
Settingofthemax.timeforrefill.Thepressure,measuredbyS10,mustbe OKwithinthesettime.Ifnot,therefillwaterfunctionstopsandanalarm isactivated.
SeeAppendix“ParameterIDoverview”
1x323
=
X #1# #2# #3#
Time
=
PressureOK/notOK
=
Refillpump
=
Time-out
100|©Danfoss|2021.12
=
X #1# #2# #3# #4#
Time
=
PressureOK/notOK
=
Refillpump
=
Time-out
=
Alarm
AQ189686468137en-010601
Loading...