Danfoss A361 Operating guide

OperatingGuide
ECLComfort310,applicationA361

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype.......................................9
2.4Placingthetemperaturesensors................................14
2.5Electricalconnections.............................................16
2.6InsertingtheECLApplicationKey..............................25
2.7Checklist............................................................32
2.8Navigation,ECLApplicationKeyA361.........................33
3.0Dailyuse.........................................................36
3.1Howtonavigate...................................................36
3.2Understandingthecontrollerdisplay..........................37
3.3Ageneraloverview:Whatdothesymbolsmean?...........40
3.4Monitoringtemperaturesandsystem
components........................................................41
3.5Influenceoverview................................................42
3.6Manualcontrol.....................................................43
3.7Schedule............................................................44
4.0Settingsoverview............................................45
5.0Settings...........................................................47
5.1IntroductiontoSettings..........................................47
5.2Flowtemperature..................................................48
5.4Flow/powerlimit.................................................57
5.5Optimization........................................................61
5.6Controlparameters................................................67
5.7Pumpcontrol.......................................................71
5.9Application.........................................................79
5.10Alarm................................................................84
5.11Alarmoverview....................................................88
6.0Commoncontrollersettings..............................89
6.1Introductionto‘Commoncontrollersettings’................89
6.2Time&Date.........................................................90
6.3Holiday..............................................................91
6.4Inputoverview.....................................................93
6.5Log...................................................................94
6.6Outputoverride....................................................95
6.8System...............................................................98
7.0Miscellaneous................................................105
7.1ECA30/31setupprocedures.................................105
7.2Overridefunction................................................113
7.3Severalcontrollersinthesamesystem......................116
7.4Frequentlyaskedquestions....................................119
7.5Definitions........................................................122
7.6Type(ID6001),overview.......................................126
7.7Automatic/manualupdateoffirmware.....................127
7.8ParameterIDoverview..........................................128
©Danfoss|2021.02AQ000086455681en-010402|1
OperatingGuideECLComfort310,applicationA361

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA361 (ordercodeno.087H3804).
ThefunctionscanberealizedwithECLComfort310.
TheapplicationA361complieswithECLComfortcontroller310as ofsoftwareversion1.10(visibleatstart-upofthecontrollerandin ‘Commoncontrollersettings’in‘System’).
AdditionaldocumentationforECLComfort210and310,modules andaccessoriesisavailableonhttp://heating.danfoss.com/.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
2|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
2
Circuit2Parameterno.
AQ000086455681en-010402
174
©Danfoss|2021.02|3
OperatingGuideECLComfort310,applicationA361
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
4|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

2.0Installation

2.1Beforeyoustart

TheapplicationA361.1isveryflexible.Thesearethebasic principles:
Heating(circuit1and2):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3(circuit1)and S4(circuit2)arethemostimportantsensors.Thedesiredflow temperaturesatS3andS4arecalculatedintheECLcontroller, basedontheoutdoortemperature(S1).Thelowertheoutdoor temperature,thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein ‘Comfort’or‘Saving’mode(twodifferenttemperaturevaluesfor desiredroomtemperature).
ThemotorizedcontrolvalvesM1(circuit1)andM2(circuit2)are openedgraduallywhentheflowtemperatureislowerthanthe desiredflowtemperatureandviceversa.
ThereturntemperaturesS5(circuit1)andS6(circuit2)tothe districtheatingsupplyshouldnotbetoohigh.Ifso,thedesired flowtemperaturecanbeadjusted(typicallytoalowervalue),thus resultinginagradualclosingofthemotorizedcontrolvalves.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent oftheoutdoortemperature.Typically,thelowertheoutdoor temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1) bemeasuredasa0-10Vsignal(fromapressuretransmitter)or
2)beaswitchsignalfromapressureswitch.Incaseofatoolow pressure,therefillwaterfunctionwillsupplementwithwaterfrom thesupplyside.
TypicalA361.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor,circuit1
S4
Flowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6Returntemperaturesensor,circuit2
S7
Differentialpressureswitch,circuit1
S8
Differentialpressureswitch,circuit2
S9
Pressuretransmitterorpressureswitch,circuit2
S10
Pressuretransmitterorpressureswitch,circuit1
P1
Circulationpump,circuit1
P2
Circulationpump,circuit1
P3
Circulationpump,circuit2
P4
Refillwaterpump
P5
Circulationpump,circuit2
M1
Motorizedcontrolvalve,circuit1
M2
Motorizedcontrolvalve,circuit2
V1
Solenoidvalve,circuit1,refillwatervalve
V2
Solenoidvalve,circuit2,refillwatervalve
R6
Relayoutput,alarm
AQ000086455681en-010402
©Danfoss|2021.02|5
OperatingGuideECLComfort310,applicationA361
ApplicationA361.1ingeneral:
ThecirculationpumpsP1andP2(circuit1)/P3andP5(circuit2) workinshiftaccordingtoaschedule.Onepumpisusedasspare pumpandtheotherpumpisworking.Incaseofmalfunction (missingdifferentialpressure)ofonepump,theotherpumpwill takeover.Analarmwillbegeneratedandthedefectivepumpcan beinspected/repaired.
Alarm(relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin apresettime.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
M-buscommunicationenablesconnectiontofloworenergymeter. Thecontrollercanlimitthefloworenergytoasetmaximumbut alsoinrelationtotheoutdoortemperature.
Furthermore,theM-busdatacanbetransferredtotheModbus communication.
TypicalA361.1application:
6|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
TheapplicationA361.2isveryflexible.Thesearethebasic principles:
Heating(circuit1and2):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3(circuit1)and S4(circuit2)arethemostimportantsensors.Thedesiredflow temperaturesatS3andS4arecalculatedintheECLcontroller, basedontheoutdoortemperature(S1).Thelowertheoutdoor temperature,thehigherthedesiredflowtemperature.
Thesupplytemperature(S2)isusedto1)controltheS3andS4 temperaturesinrelationtotheS2temperatureor2)maximizethe limitofthedesiredflowtemperature.
Thefactorysetting,wherethesupplytemperature(S2)determines thedesiredflowtemperature,doesnotchangethedesiredflow temperatureaccordingto‘Comfort’or‘Saving’mode.
However,ifthesupplytemperature(S2)determinesamax. limitationofthedesiredflowtemperature,the‘Comfort’and ‘Saving’modewillhavetwodifferenttemperaturevaluesfor desiredroomtemperature.
ThemotorizedcontrolvalvesM1(circuit1)andM2(circuit2)are openedgraduallywhentheflowtemperatureislowerthanthe desiredflowtemperatureandviceversa.
ThereturntemperaturesS5(circuit1)andS6(circuit2)tothe districtheatingsupplyshouldnotbetoohigh.Ifso,thedesired flowtemperaturecanbeadjusted(typicallytoalowervalue),thus resultinginagradualclosingofthemotorizedcontrolvalves.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent oftheoutdoortemperature.Typically,thelowertheoutdoor temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1) bemeasuredasa0-10Vsignal(fromapressuretransmitter)or
2)beaswitchsignalfromapressureswitch.Incaseofatoolow pressure,therefillwaterfunctionwillsupplementwithwaterfrom thesupplyside.
TypicalA361.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplyflowtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S4
Flowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6Returntemperaturesensor,circuit2
S7
Differentialpressureswitch,circuit1
S8
Differentialpressureswitch,circuit2
S9
Pressuretransmitterorpressureswitch,circuit2
S10
Pressuretransmitterorpressureswitch,circuit1
P1
Circulationpump,circuit1
P2
Circulationpump,circuit1
P3
Circulationpump,circuit2
P4
Refillwaterpump
P5
Circulationpump,circuit2
M1
Motorizedcontrolvalve,circuit1
M2
Motorizedcontrolvalve,circuit2
V1
Solenoidvalve,circuit1,refillwatervalve
V2
Solenoidvalve,circuit2,refillwatervalve
R6
Relayoutput,alarm
AQ000086455681en-010402
©Danfoss|2021.02|7
OperatingGuideECLComfort310,applicationA361
ApplicationA361.2ingeneral:
ThecirculationpumpsP1andP2(circuit1)/P3andP5(circuit2) workinshiftaccordingtoaschedule.Onepumpisusedasspare pumpandtheotherpumpisworking.Incaseofmalfunction (missingdifferentialpressure)ofonepump,theotherpumpwill takeover.Analarmwillbegeneratedandthedefectivepumpcan beinspected/repaired.
Alarm(relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin apresettime.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
M-buscommunicationenablesconnectiontofloworenergymeter. Thecontrollercanlimitthefloworenergytoasetmaximumbut alsoinrelationtotheoutdoortemperature.
Furthermore,theM-busdatacanbetransferredtotheModbus communication.
TypicalA361.2application:
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
8|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
AQ000086455681en-010402
©Danfoss|2021.02|9
OperatingGuideECLComfort310,applicationA361

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
10|©Danfoss|2021.02
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
AQ000086455681en-010402
©Danfoss|2021.02|11
OperatingGuideECLComfort310,applicationA361
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
12|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
AQ000086455681en-010402
©Danfoss|2021.02|13
OperatingGuideECLComfort310,applicationA361

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
14|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ000086455681en-010402
©Danfoss|2021.02|15
OperatingGuideECLComfort310,applicationA361

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
16|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ000086455681en-010402
©Danfoss|2021.02|17
OperatingGuideECLComfort310,applicationA361
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
18|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
2.5.3Electricalconnections,safetythermostats,ingeneral
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
AQ000086455681en-010402
©Danfoss|2021.02|19
OperatingGuideECLComfort310,applicationA361
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
SeetheInstallationGuide(deliveredwiththeapplicationkey)for sensorandinputconnections.
A361.1/A361.2:
Sensor
S1
S2
S3
S4
S5Returntemperaturesensor,
S6Returntemperaturesensor,
S7
S8
S9
S10
*
** ***
Description
Outdoortemperature sensor*
Supplyflowtemperature sensor**
Flowtemperaturesensor***, circuit1
Flowtemperaturesensor***, circuit2
circuit1
circuit2 Differentialpressureswitch,
circuit1 Differentialpressureswitch,
circuit2 Pressuretransmitter(0–10
Vor4–20mA)orpressure switch,circuit2
Pressuretransmitter(0–10 Vor4–20mA)orpressure switch,circuit1
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
OnlyforapplicationA361.2. Theflowtemperaturesensormustalwaysbeconnected
inordertohavethedesiredfunctionality.Ifthesensoris notconnectedorthecableisshort-circuited,themotorized controlvalvecloses(safetyfunction).
Recommendedtype
ESMT
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
Connectionof2differentialpressureswitches
20|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Connectionofapressuretransmitterwith0-10Voutput
ExampleofapressuretransmitterconnectiontoS10.Pressure transmittercanbeconnectedinthesamewaytoS9.
Connectionofapressuretransmitterwith4-20mAoutput
The4-20mAsignalisconvertedtoa2-10Vsignalbymeansofthe 500ohmresistor.
ExampleofapressuretransmitterconnectiontoS10.Pressure transmittercanbeconnectedinthesamewaytoS9.
Connectionof2pressureswitches
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus) Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ000086455681en-010402
©Danfoss|2021.02|21
OperatingGuideECLComfort310,applicationA361
2.5.5Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
22|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
AQ000086455681en-010402
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
©Danfoss|2021.02|23
OperatingGuideECLComfort310,applicationA361
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
24|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
AQ000086455681en-010402
ECLComfort296
©Danfoss|2021.02|25
OperatingGuideECLComfort310,applicationA361
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
26|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
AQ000086455681en-010402
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
©Danfoss|2021.02|27
OperatingGuideECLComfort310,applicationA361
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
28|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
AQ000086455681en-010402
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
©Danfoss|2021.02|29
OperatingGuideECLComfort310,applicationA361
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
30|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ000086455681en-010402
©Danfoss|2021.02|31
OperatingGuideECLComfort310,applicationA361

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
32|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

2.8Navigation,ECLApplicationKeyA361

Navigation,applicationsA361,circuit1and2(*application361.2only)
Home
IDno.
MENU ScheduleSelectableSelectable
Settings
Flowtemperature
11178 11177 11300 11301 11302 11303
Returnlimit
Flow/powerlimitActualActual
Optimization
Controlpar.
11031 11032 11033 11034 11035 11036 11037 11085
11119 11117 11118 11116 11112 11113 11109 11115 11011 11012 11013 11014 11026 11021 11179 11174 11184 11185 11186 11187
Circuit1,HeatingCircuit2,Heating
Function
HeatcurveHeatcurve Temp.max. Temp.min. Highsupp.TX2* HighTmaxY2* LowsupplyTX1* LowTmaxY1* HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority
LimitLimit HighToutX1 LowlimitY1 LowToutX2
HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Prestop Totalstop Cut-out Motorpr. Xp Tn Mrun Nz
IDno.
11178 12177 12300 12301 12302 12303 12031 12032 12033 12034 12035 12036 12037 12085
12119 12117 12118 12116 12112 12113 12109 12115 12011 12012 12013 12014 12026 12021 12179 12174 12184 12185 12186 12187
Function
Temp.max. Temp.min. Highsupp.TX2* HighTmaxY2* LowsupplyTX1* LowTmaxY1* HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Prestop Totalstop Cut-out Motorpr. Xp Tn Mrun
Nz
AQ000086455681en-010402
©Danfoss|2021.02|33
OperatingGuideECLComfort310,applicationA361
Navigation,applicationA361,circuit1andcircuit2continued
Home
MENU
Settings
HolidaySelectableSelectable
Alarm
InfluenceoverviewDes.flowT
Pumpcontrol
Refillwater
Application
Temp.monitor.
Clearalarm
AlarmoverviewSelectableSelectable
IDno.
11314 11310 11313 11311 11312 11022
11327 11323 11321 11322 11320 11325 11326 11017 11023 11052 11077 11078 11093 11141 11142 11189
11147 11148 11149 11150 11315 11324
Circuit1,HeatingCircuit2,Heating
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise PressurePressure Inputtype Time-out Pressure,des. Pressure,diff. Pexercise Valvedelay No.ofpumps Demandoffset Mexercise DHWpriority PfrostT PheatT Frostpr.T Ext.input Ext.mode Min.act.time
Upperdifference Lowerdifference Delay Lowesttemp. Circ.pumps Refillwater
Returnlim.Returnlim. Flow/powerlim.Flow/powerlim.
HolidayHoliday Ext.overrideExt.override BoostBoost RampRamp Slave,demand Heatingcut-outHeatingcut-out DHWpriorityDHWpriority
IDno.
12314 12310 12313 12311 12312 12022
12327 12323 12321 12322 12320 12325 12326
12023 12052 12077 12078 12093 12141 12142 12189
12147 12148 12149 12150 12315 12324
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise
Inputtype Time-out Pressure,des. Pressure,diff. Pexercise Valvedelay No.ofpumps
Mexercise DHWpriority PfrostT PheatT Frostpr.T Ext.input Ext.mode Min.act.time
Upperdifference Lowerdifference Delay Lowesttemp. Circ.pumps Refillwater
34|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Navigation,applicationA361,Commoncontrollersettings(*applicationA361.2only)
Home MENU Time&Date HolidaySelectable Inputoverview1
Inputoverview2
Log1(sensors)
Log2(sensors)
Outputoverride
Keyfunctions
SystemECLversion
OutdoorTLogtoday SupplyT*Logyesterday Heatingflow&des. HeatreturnT&limitLog4days Staticpressure OutdoorTLogtoday SupplyT*Logyesterday Heatingflow&des. HeatreturnT&limitLog4days Staticpressure
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet M-busconfig EnergyMeters Display
Communication
Language
Commoncontrollersettings
IDno.
60058 60059
38 2048 2150 2151 2050
Function
Selectable
OutdoorT SupplyT* HeatflowT HeatreturnT Staticpressure S7status OutdoorT SupplyT* HeatflowT HeatreturnT Staticpressure S8status
Log2days
Log2days
M1,P1,P2,M2,P3,P5,V1,V2, P4,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
Selectable Selectable Backlight Contrast Modbusaddr. ECL485addr. Servicepin Ext.reset Language
AQ000086455681en-010402
©Danfoss|2021.02|35
OperatingGuideECLComfort310,applicationA361

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
36|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
AQ000086455681en-010402
)
©Danfoss|2021.02|37
OperatingGuideECLComfort310,applicationA361
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Examples:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
20.5
21.0
38|©Danfoss|2021.02
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
AQ000086455681en-010402
©Danfoss|2021.02|39
OperatingGuideECLComfort310,applicationA361

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
40|©Danfoss|2021.02
DamperOFF
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
AQ000086455681en-010402
©Danfoss|2021.02|41
OperatingGuideECLComfort310,applicationA361
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
42|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
AQ000086455681en-010402
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
©Danfoss|2021.02|43
OperatingGuideECLComfort310,applicationA361

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
44|©Danfoss|2021.02
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Heatcurve
Actual(actualfloworpower)
Pressure
Pressure,des.(desiredpressure)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Demandoffset
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Pre-stop(optimizedstoptime)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
DHWpriority(closedvalve/normaloperation)
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
1x01161
1x01262
1x01363
1x01463
1x01779
1x02164
1x022
1x02379
1x02665
1x031
1x032
1x033
1x034
1x035
1x036
1x037
1x05279
1x07780
1x07880
1x08556
1x09380
1x10958
1x111
1x11258
1x11359
1x115
1x11659
1x117
1x11860
1x11960
1x141
1x14281
1x147
Factorysettingsincircuit(s)
1
48
50
58
74
75
71
54
54
54
55
55
55
55
58
59
60
80
85
23
AQ000086455681en-010402
©Danfoss|2021.02|45
OperatingGuideECLComfort310,applicationA361
SettingIDPage
Lowerdifference
Delay,example
Lowesttemp.
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Highsupp.TX2(highvalueofsupplytemp.)
HighTmaxY2(highvalueofmaxlimitation)
LowsupplyTX1(lowvalueofsupplytemp.)
LowTmaxY1(lowvalueofmaxlimitation)
Retrytime
Change,duration
Changetime(changeovertime)
Stab.time(stabilizationtime)
Chan.-overtime(change-overtime)
Circ.pumps
Pexercise(pumpexercise)
Pressure,diff.(switchingdifference)
Time-out
Refillwater
Valvedelay
No.ofpumps
Inputtype
1x14885
1x14985
1x15086
1x174
1x17751
1x178
1x17966
1x18468
1x18569
1x18669
1x18769
1x18983
1x300
1x301
1x302
1x30352
1x310
1x311
1x31272
1x31372
1x31472
1x31586
1x320
1x322
1x323
1x32486
1x32576
1x326
1x327
Factorysettingsincircuit(s)
1
68
51
51
51
51
71
71
75
75
75
77
77
23
46|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
AQ000086455681en-010402
©Danfoss|2021.02|47
OperatingGuideECLComfort310,applicationA361

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
48|©Danfoss|2021.02
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
Max.limitationofthedesiredflowtemperature:
IntheapplicationA361.1themax.limitationvalueisselectable in‘Temp.max. ’ .
Max.limitationofthedesiredflowtemperature:
IntheapplicationA361.2thedesiredflowtemperatureormax. limitationvaluedependsonthesupplytemperature(S2).The relationshipissetinthefoursettings‘Highsupp.TX2’ ,‘HighTmax Y2’ ,‘LowsupplyTX1’and‘LowTmaxY1’ .
Whensettingtheheatcurvecoordinatesasdescribedinthe section'A361.1’ ,thedesiredflowtemperaturecanbelimitedtoa maximumaccordingtothesupplytemperature(S2).
AQ000086455681en-010402
©Danfoss|2021.02|49
OperatingGuideECLComfort310,applicationA361
5.2.1A361.2
TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtothesupplytemperature(S2).This relationshipissetinthecontroller.
Theheatcurveissetinallcoordinatepointstothemax.desired flowtemperature(150°C).Thedesiredflowtemperaturewill alwaysbeinrelationtothesupplytemperature(S2).
Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Outdoortemp.
FactorysettingY oursettings
-30°C150°C
-15°C150°C
-5°C150°C
0°C150°C
5°C150°C
15°C150°C
Adjustthedesiredflowtemperatureat-30,-15,-5,0,5,and15°C, ifrequired.
MENU>Settings>Flowtemperature
Desiredflowtemperature
Supplytemp.(S2)
Heatcurve
CircuitSettingrange
1
Read-outonly
Factorysetting
Thefactorysetting(ageneraldesiredflowtemperatureof150°C)is limitedtoamax.valuebasedonthesupplytemperature(S2)and thesettingsinparameters‘Highsupp.TX2’ ,‘HighTmaxY2’ ,‘Low supplyTX1’and‘LowTmaxY1’ .
Desiredflowtemperature
Supplytemp.(S2)
50|©Danfoss|2021.02
Theaboveheatcurveisanexampleofasupplytemperature(S2)of 85°C.Thedesiredflowtemperature(58°C)isbasedontheset-upof therelationshipbetweenthesupplytemperature(S2)andthedesired flowtemperature.
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
MENU>Settings>Flowtemperature
Highsupp.TX2(highvalueofsupplytemp.)
1x300
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
SeeAppendix“ParameterIDoverview”
Setthehighvalueforthesupplytemperatureinrelationtothe desiredmax.flowtemperature.Whenthesupplytemperatureis abovethesetvalue,themax.limitationoftheflowtemperatureis theY2value.Whenthesupplytemperatureisbelowthesetvalue, themax.limitationoftheflowtemperaturewillbelower.
MENU>Settings>Flowtemperature
HighTmaxY2(highvalueofmaxlimitation)
1x301
SeeAppendix“ParameterIDoverview”
Setthehighvalueforthemax.limitationofthedesiredflow temperature.
AQ000086455681en-010402
©Danfoss|2021.02|51
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Flowtemperature
LowsupplyTX1(lowvalueofsupplytemp.)
1x302
SeeAppendix“ParameterIDoverview”
Setthelowvalueforthesupplytemperatureinrelationtothe desiredmax.flowtemperature.Whenthesupplytemperatureis belowthesetvalue,themax.limitationoftheflowtemperatureis theY1value.Whenthesupplytemperatureisabovethesetvalue, themax.limitationoftheflowtemperaturewillbehigher.
MENU>Settings>Flowtemperature
LowTmaxY1(lowvalueofmaxlimitation)
1x303
SeeAppendix“ParameterIDoverview”
Setthelowvalueforthemax.limitationofthedesiredflow temperature.
52|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

5.3Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
AQ000086455681en-010402
©Danfoss|2021.02|53
OperatingGuideECLComfort310,applicationA361
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
1x031
1x032
54|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
1x033
1x034
Example
1x035
Thereturnlimitisactiveabove50°C. Theinfluenceissetto0.5. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby0.5x2=1.0degree.
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthesetlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthesetlimit.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Example
1x036
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
AQ000086455681en-010402
©Danfoss|2021.02|55
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x037
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
56|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

5.4Flow/powerlimit

Heatingcircuit
AfloworenergymetercanbeconnectedtotheECLcontrollerin ordertolimitthefloworconsumedpower.Thesignalfromthe floworenergymeterisapulsesignal.
WhentheapplicationrunsinanECLComfort296/310controller, theflow/powersignalcanbeobtainedfromaflow/energymeter viatheM-busconnection.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2#
#Y1#
#Y2#
X
Y
#1#
#2#
#3#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
=
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
Theparameter'Units'(ID1x115)hasareducedsettingrangewhen theflow/energysignalcomesviaM-bus.
AQ000086455681en-010402
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
©Danfoss|2021.02|57
OperatingGuideECLComfort310,applicationA361
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Pulsebasedsignalforflow/power ,appliedtoinputS7
Formonitoring: Frequencyrangeis0.01-200Hz
Forlimitation: Minimumfrequencyisrecommendedtobe1Hzinordertohavea
stablecontrol.Furthermore,thepulsesmustappearregularly.
Inputtype
Choiceofinputtypefromflow/energymeter
SeeAppendix“ParameterIDoverview”
OFF:
IM1-
Noinput
Flow/energymetersignalbasedonpulses.
IM5: EM1-
Flow/energymetersignalfromM-bus.
EM5:
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
1x109
ThesettingrangeforIMandEMdependsonchosensubtype.
1x111
SeeAppendix“ParameterIDoverview”
58|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
1x113
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Unitstotheleft:pulsevalue. Unitstotheright:actualandlimitationvalues.
Thevaluefromtheflowmeterisexpressedasmlorl. ThevaluefromtheenergymeterisexpressedasWh,kWh,MWh orGWh.
Thevaluesfortheactualflowandtheflowlimitationareexpressed asl/horm³/h.
Thevaluesfortheactualpowerandthepowerlimitationare expressedaskW,MWorGW.
1x115
Listforsettingrangeof'Units': ml,l/h l,l/h ml,m³/h l,m³/h Wh,kW kWh,kW kWh,MW MWh,MW MWh,GW GWh,GW
Example1:
'Units'(11115):
'Pulse'(11114):
l,m³/h 10
Eachpulserepresents10litresandtheflowisexpressedascubic meters(m³)perhour.
Example2:
'Units'(11115):
'Pulse'(11114):
kWh,kW(=kiloWatthour,kiloWatt) 1
Eachpulserepresents1kiloWatthourandthepoweris expressedinkiloWatt.
AQ000086455681en-010402
©Danfoss|2021.02|59
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
1x116
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
1x118
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
1x119
60|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

5.5Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost','Optimizer','Totalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
AQ000086455681en-010402
©Danfoss|2021.02|61
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
62|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
=
X Y #1#
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
AQ000086455681en-010402
©Danfoss|2021.02|63
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
-5°C
small
64|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Optimization
Totalstop
Settingthe'Totalstop'toOFForONgivesdifferentresults,dependingonthe actualapplication.Theconditionsare:
-Roomtemperaturecontrolledapplications
-Totalstopduringthesavingtemperatureperiod
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.
Heatingapplicationsingeneral: Savingmode:
Thedesiredflow/duct temperatureisreduced accordingtodesiredduct/ roomtemperature.
Comfortmode:Iftheroomtemperaturegets
higherthandesiredroom temperature,theheating switchesOFF .
Seealsotheheatingrelatedexamples.
Coolingapplications: Savingmode:
Themotorizedcontrolvalve closes.
ON:
Totalstop.
Heatingapplicationswithdesiredducttemperature: Savingmode:
Thedesiredflowtemperature issetto'Frostpr.T'(Frost protectiontemperature).
Heatingapplicationswithdesiredroomtemperature: Savingmode:
Theheatingisstoppedaslong astheroomtemperatureis higherthanthedesiredroom temperature.
Seealsotheheatingrelatedexamples.
Coolingapplications: Savingmode:
Themotorizedcontrolvalve closes.
Ingeneral,whentotalstopisON,theheatingorcooling closestotallywhenthecontrollergoesintosavingmode. However,when'Totalstop'isON,thecontrollerhasroom temperaturerelatedfunctionsalsoincomfortmode.
Theexamplesbelowarerelatedtoheatingapplications:
1x021
Desiredflowtemp.°C
Totalstop=ON
‘Frostpr. ’ Time
Desiredflowtemp.°C
Totalstop=OFF
‘Frostpr. ’ Time
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
AQ000086455681en-010402
©Danfoss|2021.02|65
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
1x026
Example:OptimizationofComfortfrom07:00-22:00
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
X #1# #2# #3# #4# #5#
Summer,cut-out
=
X
=
Y
=
#1#
=
#2#
=
#3#
=
#4#
=
#5#
=
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
Time
Temperature
Actualoutdoortemperature
Cut-outtemperature(1x179)
Accummulated(filtered)outdoortemperature
Heatingenabled
Heatingdisabled
66|©Danfoss|2021.02
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

5.6Controlparameters

Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point controlsignal.
Valvecontrol: Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
AQ000086455681en-010402
©Danfoss|2021.02|67
OperatingGuideECLComfort310,applicationA361
Thermo-hydraulicactuator,ABV
Danfossthermo-actuatortypeABVisaslowactingvalveactuator. InsidetheABVanelectricheatcoilwillheatathermostaticelement whenanelectricsignalisapplied.Whenheatingthethermostatic elementitexpandsinordertomanagethecontrolvalve.
Twobasictypesareavailable:ABVNC(NormalClosed)andABVNO (normalopen).Forexample,ABVNCkeepsa2-portcontrolvalve closedwhennoopen-signalsareapplied.
Electricopen-signalscomefromtheelectronicoutputoftheECL Comfortcontrollerinordertomanagethecontrolvalve.When open-signalsareappliedtotheABVNC,thevalvegraduallyopens.
Open-signalsareintheECLComfortcontrollerexpressedas "Arrow-up"(open)anddisplayedatthevalvesymbol.
Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,relativelylongopen-signalscomefrom theECLComfortcontrollerinordertoincreasetheflow.Bythis, theflowtemperaturewillovertimebealignedwiththedesired temperature.
Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,relativelyshortopen-signalscomefromtheECL Comfortcontrollerinordertoreducetheflow.Again,theflow temperaturealigns,overtime,withthedesiredtemperature.
ThecontroloftheDanfossthermo-actuatortypeABVusesaunique designedalgorithmandisbasedonthePWMprinciple(Pulse WidthModulation),wherethedurationofthepulsedetermines themanagementofthecontrolvalve.Thepulsesarerepeated each10sec.
Aslongastheflowtemperaturecorrespondstothedesired temperature,thedurationoftheopen-signalswillremainconstant.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
1x174
SeeAppendix“ParameterIDoverview”
Recommendedforductsystemswithvariableload.
OFF:
Value:
68|©Danfoss|2021.02
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
1x184
1x185
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
AQ000086455681en-010402
©Danfoss|2021.02|69
OperatingGuideECLComfort310,applicationA361
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
Criticaltimeperiod
Time
70|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

5.7Pumpcontrol

Thisapplicationcanoperatewithoneortwocirculationpumps. Whenoperatingwithtwocirculationpumps,thepumpsare controlledalternately,accordingtoatimeset-up.Whenapumpis switchedONthecontrolleriswaitingfordifferentialpressure(S7 forheatingcircuit,S8forDHWcircuit)tobuildup.Ifdifferential pressureisnotachieved,analarmisgeneratedandtheECL ComfortcontrollerswitchesONtheotherpump.
Ifnoneofthepumpscancomeintooperation(detectedbymeans ofthedifferentialpressureswitch),thealarmisactivatedandthe motorizedcontrolvalvecloses(asafetyfunction).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Pumpcontrol
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat noon(12:14hours).
MENU>Settings>Pumpcontrol
Retrytime
Ifanalarmhasbeengeneratedforthepumporalarmshavebeengenerated forbothpumps,thissettingwilldeterminethetimebetweenthetimeofthe alarmandtheretrytimeforrepeatedpumpstart.
SeeAppendix“ParameterIDoverview”
OFF:
Noretrytimerequiredafteranalarm.Thepumpor pumpsinquestionwillnotberestarted.
1...99:
Afteranalarm,thepumporpumpswillberestarted afterthesettime.
1x022
1x310
AQ000086455681en-010402
©Danfoss|2021.02|71
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Pumpcontrol
Change,duration
Thenumberofdaysbetweenshiftofcirculationpumps.Theshifttakesplace atthetimesetin'Changetime' .
SeeAppendix“ParameterIDoverview”
MENU>Settings>Pumpcontrol
Changetime(changeovertime)
Theexacttimeoftheday,wheretheshiftmusttakeplace.Thedayisdivided into24hours.Thefactorysettinghereis12whichmeans12:00(noon).
1x311
=
X #1# #2# #3#
1x312
Time
=
PumpP3
=
PumpP5
=
Change,duration(days)
SeeAppendix“ParameterIDoverview”
MENU>Settings>Pumpcontrol
Stab.time(stabilizationtime)
Settingofmax.timetoelapsebetweenpumpstartcommandandfeedback fromdifferentialpressureswitch. Ifthedifferentialpressureswitchdoesnotgivefeedbackwithinthesettime, thealarmwillbeactivatedandtheotherpumpwillgetastartcommand.
SeeAppendix“ParameterIDoverview”
=
X #1# #2# #3#
1x313
Time
=
PumpP3
=
PumpP5
=
Changetime(clocktime)
Ifthechosenstabilizationtime(‘Stab.time’)istooshort,theactive pumpwillstopimmediatelyafterthestabilizationtimehaselapsed.
72|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Pumpcontrol
Chan.-overtime(change-overtime)
Settingoftimetoelapsebetweenthepumpstopcommandforonepump andthestartcommandfortheotherpump. Thechange-overtimecanensurethatapumpisstoppedefficientlybefore theotherpumpstarts.
SeeAppendix“ParameterIDoverview”
OFF:
1...99:
Onecirculationpumpintheapplication.
Timeforchange-over.
1x314
=
X #1# #2# #3#
Time
=
PumpP3
=
PumpP5
=
Change-overtime(sec.)
‘Chan.-overtime’hastobechoseninsystemswithtwopumps.
Thestatusofthedifferentialpressureswitchisshownin'Input overview'.
(Navigation:MENU>Commoncontroller>Inputoverview).
Example:
S7status...OFF/ON
OFF:
Thedifferentialpressureswitchisclosed(differential pressureisOK)
ON:
Thedifferentialpressureswitchisopen(differential pressureisnotOK)
AQ000086455681en-010402
©Danfoss|2021.02|73
OperatingGuideECLComfort310,applicationA361
5.8Refillwater
Leaksontheconsumerssidewillresultinfallingstaticpressureand therebyapoorsupplyofheating.Arefillwaterfunctioncaninject watertoincreasethestaticpressure.
Thisapplicationcanmonitorthestaticpressureandenablethe refillwaterfunctionwhenthepressureistoolow.
Thepressureismeasuredbymeansofapressuretransmitter (givinga0-10voltsignalinrelationtothemeasuredpressure)or apressureswitch.
Whenapressuretransmittersignalisused,twosettingsinthe controllerrepresentpressuresetpointanddifference.
Whenapressureswitchsignalisused,thesetpointand(maybe) theswitchingdifferenceissetonthepressureswitch.
Whenatoolowpressureisdetectedtherefillwaterpumpis switchedONand,afterasettime,theON-OFFvalveisactivated.
Ifthepressureisnotachievedwithinasettime,analarmis generated.TheECLComfortcontrollerswitchesOFFthecirculation pumpsafter60secondsandthecontrolvalvecloses(asafety function).
MENU>Settings>Refillwater
Pressure
CircuitSettingrange
1
Read-outonly
Factorysetting
Theread-outcanbeavalue(inbar):
Thepressureismeasuredbymeansofapressuretransmitter. Thetransmittersendsthemeasuredpressureasa0-10Vora 4-20mAsignal.Thevoltagesignalcanbeapplieddirectlyto inputS10.Acurrentsignalisconvertedbymeansofaresistor toavoltageandthenappliedtoinputS10.Themeasured voltageoninputS10mustbeconvertedtoapressurevalueby thecontroller.Thisproceduresetsupthescaling.
Pushthedialtoseethegraphandenterthevaluesetsforthe inputvoltage(2and10volt)anddisplayedpressure(inbar).
Pressurevaluerange:0.0...30.0bar
Fixedvoltagesettings:2Vand10V
Factorysettings:(2.0,0)and(10,20.0)
Thismeansthatthe‘Pressure'is0.0barat2Vand20.0barat 10V.
Typically,thehigherthevoltage,thehigherthedisplayed pressure.
Ortheread-outcanbeOFForON:
Thepressureismeasuredbymeansofapressureswitch.The pressureswitchhasanopencontactwhenmeasuringatoolow pressure(shownasOFF).WhenmeasuredpressureisOK,the contactisclosed(shownasON).
Thepressureswitchcontact(potentialfree)isconnected directlytoinputS10.
=
X Y #1# #2#
Volt
=
Bar
=
0bar
=
30,0bar
Thisscalingmenuisalwaysshown,regardlesswhetherapressure transmitterorapressureswitchisused.
74|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Refillwater
Pexercise(pumpexercise)
Thetimethepumpisactivatedduringexercise.Exercisetakesplaceevery day(at12:00).
SeeAppendix“ParameterIDoverview”
OFF:
1...200:
Nopumpexercise.
Activationtimeduringexercise.
MENU>Settings>Refillwater
Pressure,des.(desiredpressure)
Readoutofthecalculateddesiredpressureattheinlet/outlet. Accesstoconversion(scale)settings:Pushdial.
SeeAppendix“ParameterIDoverview”
Settherelationshipbetweenoutdoortemperatureanddesired pressure.
1x320
MENU>Settings>Refillwater
Pressure,diff.(switchingdifference)
Settingoftheswitchingdifferenceformeasuredstaticpressure(pressure transmitter).Thedifferenceissymmetricalaroundthe'Pressuredes. 'See also'Pressuredes. '
SeeAppendix“ParameterIDoverview”
AQ000086455681en-010402
=
X
Y
1x322
Thesettingsin'Pressure,des. 'and'Pressure,diff.'havenoinfluence whenapressureswitchisused.
Outdoortemperature
=
Desiredpressure(Pascal)
©Danfoss|2021.02|75
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Refillwater
Time-out
Settingofthemax.timeforrefill.Thepressure,measuredbyS10,mustbe OKwithinthesettime.Ifnot,therefillwaterfunctionstopsandanalarm isactivated.
SeeAppendix“ParameterIDoverview”
1x323
=
X #1# #2# #3#
Time
=
PressureOK/notOK
=
Refillpump
=
Time-out
76|©Danfoss|2021.02
=
X #1# #2# #3# #4#
Time
=
PressureOK/notOK
=
Refillpump
=
Time-out
=
Alarm
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Refillwater
Valvedelay
SettingofthetimeforactivationoftheON/OFFvalveafterstartoftherefill waterpump.
SeeAppendix“ParameterIDoverview”
1x325
=
X Y #1# #2# #3# #4#
Time
=
Pressure
=
Pressuredesired
=
Actualpressure
=
Pressuredifference
=
Valvedelay
MENU>Settings>Refillwater
No.ofpumps
Settingofthenumberofpumpsintherefillwatercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Therefillwaterpumpfunctioniscontrolledbythe mastercontroller.
1...2:
Therefillwaterfunctionhasoneortwopumps.
1x326
Refillwater pump
WhenselectingOFFandademandforrefilloccurs,thecontroller fortheactualcircuitsendstherequirementviatheECL485 communicationbustothemastercontroller.
Themastermustberunninganapplicationwithrefillwaterfunction. Themasterstartstherefillwaterpumpandsends,viatheECL485 communicationbus,amessagethattherefillwaterpumpisstarted. Therefillwatervalvethenopens.
Theslavemusthaveanaddress1...9.
Refillwater valve
ECL485 communication bus
AQ000086455681en-010402
©Danfoss|2021.02|77
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Refillwater
Inputtype
Choiceofpressureinputsignal.
SeeAppendix“ParameterIDoverview”
OFF:
Pressuresignalisnotrequired.Therefillwaterfunction
isdisabled.
AI:
DI:
Theinputsignalisananalogsignal(0-10V).
Theinputsignalisadigitalsignal(switchOFForON).
1x327
Whenselecting‘OFF’ ,therefillwatersystemcouldbeself-acting.
Thestaticpressureisshownin'Inputoverview'asavalueinbaror OFF/ON.
Example:
OFF:
Thepressureswitchisopen(pressureisnotOK)
ON:
Thepressureswitchisclosed(pressureisOK)
78|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

5.9Application

Thesection"Application"describesspecificapplicationrelated issues. Someoftheparameterdescriptionsareuniversalfordifferent applicationkeys.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Application
Demandoffset
Thedesiredflowtemperatureinheatingcircuit1canbeinfluencedbythe demandforadesiredflowtemperaturefromanothercontroller(slave)or anothercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredflowtemperatureincircuit1isnot influencedbythedemandofanyothercontroller(slave orcircuit2).
Value:
Thedesiredflowtemperatureisincreasedbytheset valuein‘Demandoffset’ ,ifthedemandoftheslave/ circuit2ishigher.
MENU>Settings>Application
Mexercise(valveexercise)
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
Temp.
1x017
Thefunctionof‘Demandoffset’cancompensateforheatlosses betweenmasterandslavecontrolledsystems.
1x023
Settingin ‘Demandoffset’
Des.flowtemp., circuit1
Des.flowtemp., circuit2
Time
OFF:
ON:
AQ000086455681en-010402
Thevalveexerciseisnotactive.
Thevalveopensfor7minutesandclosesfor7minutes everythirddayatnoon(12:00hours).
©Danfoss|2021.02|79
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Application
DHWpriority(closedvalve/normaloperation)
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen DHWheating/chargingisactiveinthemaster.
SeeAppendix“ParameterIDoverview”
OFF:
Theflowtemperaturecontrolremainsunchanged duringactiveDHWheating/charginginthemaster controller.
ON:
Thevalveintheheatingcircuitisclosed*duringactive DHWheating/charginginthemastercontroller.
*Thedesiredflowtemperatureissettothevaluesetin ‘Frostpr.T’
MENU>Settings>Application
PfrostT(circulationpump,frostprotectiontemp.)
Frostprotection,basedontheoutdoortemperature. Whentheoutdoortemperaturegetsbelowthesettemperaturevaluein‘P frostT’ ,thecontrollerautomaticallyswitchesONthecirculationpump(for exampleP1orX3)toprotectthesystem.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Nofrostprotection. CirculationpumpisONwhentheoutdoortemperature
isbelowthesetvalue.
1x052
Thissettingmustbeconsideredifthiscontrollerisaslave.
1x077
Undernormalconditions,yoursystemisnotfrostprotectedifyour settingisbelow0°CorOFF.
Forwater-basedsystems,asettingof2°Cisrecommended.
Iftheoutdoortemperaturesensorisnotconnectedandthefactory settinghasnotbeenchangedto'OFF' ,thecirculationpumpisalways ON.
MENU>Settings>Application
PheatT(heatdemand)
Whenthedesiredflowtemperatureisabovethesettemperaturein‘PheatT’ , thecontrollerautomaticallyswitchesONthecirculationpump.
1x078
SeeAppendix“ParameterIDoverview”
Value:
ThecirculationpumpisswitchedONwhenthedesired flowtemperatureisabovethesetvalue.
MENU>Settings>Application
Frostpr .T(frostprotectiontemp.)
SetthedesiredflowtemperatureattemperaturesensorS3toprotectthe systemagainstfrost(atheatingcut-out,totalstopetc.). WhenthetemperatureatS3getslowerthanthesetting,themotorized controlvalveopensgradually.
1x093
SeeAppendix“ParameterIDoverview”
Thevalveisfullyclosedaslongasthepumpisnotswitchedon.
Thefrostprotectiontemperaturecanalsobesetinyourfavorite displaywhenthemodeselectorisinfrostprotectionmode.
80|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Overridemodefunctions:
ThefollowingsettingsdescribethefunctioningeneralfortheECL Comfort210/296/310series.Theexplainedmodesaretypical andnotapplicationrelated.Theymightdifferfromtheoverride modesinyourapplication.
MENU>Settings>Application
Ext.input(externaloverride)
Choosetheinputfor'Ext.input'(externaloverride).Bymeansofaswitch thecontrollercanbeoverriddento‘Comfort’,'Saving' ,'Frostprotection'or 'Constanttemperature'mode.
1x141
SeeAppendix“ParameterIDoverview”
OFF:
S1...S16:
Noinputshavebeenselectedforexternaloverride. Inputselectedforexternaloverride.
IfS1...S6ischosenasoverrideinput,theoverrideswitchmusthave gold-platedcontacts. IfS7...S16ischosenasoverrideinput,theoverrideswitchcanbea standardcontact.
Seethedrawingsforconnectionexamplesofoverrideswitchand overriderelaytoinputS8.
S7...S16arerecommendedforoverrideswitch.
Example:Connectionofanoverrideswitch
Example:Connectionofanoverriderelay
IfECA32ismounted,alsoS11...S16canbeused.
IfECA35ismounted,alsoS11orS12canbeused.
Chooseonlyanunusedinputforoverride.Ifanalreadyusedinputis appliedforoverride,thefunctionalityofthisinputisalsoneglected.
Seealso‘Ext.mode’.
AQ000086455681en-010402
©Danfoss|2021.02|81
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Application
Ext.mode(externaloverridemode)
ThemodeoverridecanbeactivatedforSaving,Comfort,Frostpr.or ConstantTmode. Foroverride,thecontrollermodemustbeinscheduledmode.
SeeAppendix“ParameterIDoverview”
Chooseanoverridemode:
SAVING:
Thecircuitinquestionisinsavingmodewhenthe overrideswitchisclosed.
COMFORT:
Thecircuitinquestionisincomfortmodewhenthe overrideswitchisclosed.
FROSTPR.:
TheheatingorDHWcircuitcloses,butisstillfrost protected.
CONSTANTT:
Thecircuitinquestioncontrolsaconstant temperature*)
*)
Seealso'DesiredT'(1x004),settingofdesiredflow temperature(MENU>Settings>Flowtemperature) Seealso'Con.T,ret.Tlim. '(1x028),settingofreturn temperaturelimitation(MENU>Settings>Return limit)
Theprocessdiagramsshowthefunctionality.
1x142
Seealso‘Ext.input’.
Example:OverridetoComfortmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Comfort) #3#=Time
Example:OverridetoSavingmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Saving) #3#=Time
Theresultofoverrideto'Saving'modedependsonthesettingin 'Totalstop'.
Totalstop=OFF:Heatingreduced Totalstop=ON:Heatingstopped
82|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
Example:OverridetoFrostprotectionmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Frostpr.) #3#=Time
Example:OverridetoConstanttemperaturemode
MENU>Settings>Application
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Const.T) #3#=Time
The"Const.T"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
AQ000086455681en-010402
©Danfoss|2021.02|83
OperatingGuideECLComfort310,applicationA361

5.10Alarm

Thesection"Alarm"describesspecificapplicationrelatedissues. ApplicationA231offerstwotypesofalarms:
Type:
1
1
2
2
Thealarmfunctionsactivatethealarmbellsymbol. ThealarmfunctionsactivateA1(Relay4).
Thealarmrelaycanactivatealamp,ahorn,aninputtoanalarm transmittingdeviceetc.
Thealarmsymbol/relayisactivated:
(type1)aslongasthealarmreasonispresent(automaticreset).
(type2)evenifthealarmreasondisappearsagain(manual reset).
Alarmtype1:
Iftheflowtemperaturedeviatesmorethanthesetdifferences fromthedesiredflowtemperature,thealarmsymbol/relay willbeactivated.
Iftheflowtemperaturebecomesacceptable,thealarmsymbol/ relaywillbede-activated.
Description:
Actualflowtemperaturediffersfromthedesired flowtemperature
A331.1,A331.2: TheuniversalalarminputS9isactivated
Anactivatedcirculationpumpdoesnotgenerate apressuredifference
Therefillwaterfunctiondoesnotgeneratea pressurewithinsettime
IftheuniversalalarminputS9isactivated.
IftheuniversalalarminputS9isde-activated,thealarmsymbol/ relaywillbede-activated.
Alarmtype2:
IfpumpdifferentialpressureS7isnotregistered,thealarm symbol/relaywillbeactivated.Furthermore,thecontrolvalve willclose.
Thisalarmmustbemanuallyreset.
IfRefillwaterfunctionhasnotgeneratedacceptablepressure, thealarmsymbol/relaywillbeactivated.
Thisalarmmustbemanuallyreset.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
84|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
5.10.1Temp.monitor.
MENU>Settings>Alarm
Upperdifference
Thealarmisactivatediftheactualflowtemperatureincreasesmorethan thesetdifference(acceptabletemperaturedifferenceabovethedesired flowtemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
1x147
Upperdifference
OFF:
Value:
Therelatedalarmfunctionisnotactive. Thealarmfunctionisactiveiftheactualtemperature
getsabovetheacceptabledifference.
MENU>Settings>Alarm
Lowerdifference
Thealarmisactivatediftheactualflowtemperaturedecreasesmorethan thesetdifference(acceptabletemperaturedifferencebelowthedesired flowtemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Therelatedalarmfunctionisnotactive. Thealarmfunctionisactiveiftheactualtemperature
getsbelowtheacceptabledifference.
=
X Y #1# #2#
1x148
Time
=
Temperature
=
Upperdifference
=
Desiredflowtemperature
Lowerdifference
=
X Y #1# #2#
AQ000086455681en-010402
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
©Danfoss|2021.02|85
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Alarm
Delay,example
Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'is presentforalongertimethanthesetdelay(inminutes),thealarmfunction isactivated.
SeeAppendix“ParameterIDoverview”
1x149
Delay,example
Value:
Thealarmfunctionwillbeactivatedifthealarm conditionremainsafterthesetdelay.
MENU>Settings>Alarm
Lowesttemp.
Thealarmfunctionwillnotbeactivatedifthedesiredflowtemperature islowerthanthesetvalue.
SeeAppendix“ParameterIDoverview”
5.10.2Clearalarm
=
X Y #1# #2# #3# #4#
1x150
Ifthecauseofthealarmdisappears,thealarmindicationandoutput alsodisappear.
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
=
Actualflowtemperature
=
Delay(ID1x149)
Clearalarm
Ifanalarmhasbeengenerated,abellisshowninoneof thefavoritedisplay(see‘Monitoringtemperaturesandsystem components’)orinanoverviewdisplay(see‘Understandingthe controllerdisplay’).Thefollowingmenusareusedtolocatethe alarmcauseandreset(clear)thealarmsignal.Evenwhenthecause ofthealarmhasdisappeared,theindicationwillstillbeactiveuntil theclearalarmprocedurehasbeencarriedout.
MENU>Settings>Alarm
Circ.pumps
Choosewhetherthealarmshouldbeclearedornot.
1x315
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thealarmhasnotbeenactivated. Thealarmhasbeenactivated.
Clearalarmprocedure:
Ifthestatusis‘ON’:Change‘ON’to‘OFF’ .
Ifthestatusis‘OFF’:Itisnotpossibletochangeitto‘ON’ .
86|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
MENU>Settings>Alarm
Refillwater
Choosewhetherthealarmshouldbeclearedornot.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thealarmhasnotbeenactivated. Thealarmhasbeenactivated.
Clearalarmprocedure:
Ifthestatusis‘ON’:Change‘ON’to‘OFF’ .
Ifthestatusis‘OFF’:Itisnotpossibletochangeitto‘ON’ .
1x324
AQ000086455681en-010402
©Danfoss|2021.02|87
OperatingGuideECLComfort310,applicationA361

5.11Alarmoverview

MENU>Alarm>Alarmoverview
Thismenushowsthealarmtypes,forexample:
"2:T emp.monitor"
"32:Tsensordefect"
Thealarmhasbeenactivatedifthealarmsymbol(abell)( presenttotherightofthealarmtype.
Resettinganalarm,ingeneral:
)is
MENU>Alarm>Alarmoverview: Lookforalarmsymbolinspecificline.
(Example:"2:Temp.monitor") Movecursortothelineinquestion. Pushdial.
Alarmoverview:
Alarmsourcesarelistedinthisoverviewmenu.
Someexamples: "2:Temp.monitor" "5:Pump1" "10:DigitalS12" "32:Tsensordefect"
Thealarmoverviewliststhecomponentsorfunctionsthatcould causeanalarm.
Thenumbertotheleft(i.e.1,5,6,7)relatestothealarmnumber whichissentbyModbuscommunicationtoaSCADAsystem.
Twoalarmtypescanbepresent,ie.thealarmsthatareloggedand thealarmsthatarenotlogged.
Example: Thealarmtypefor‘Refillwater’ ,‘Pump3’and‘Pump5’arelogged alarms.Thismeansthatthealarmsymbolwillremainuntil thealarmhasbeenclearedevenifthecauseofthealarmhas disappeared.
Thealarmtypefor‘Temp.monitor’e.g.isnotaloggedalarmwhich meansthatthealarmsymbolwillonlybepresentaslongasthe alarmcauseexists.
Relatedtotheexamples,thenumbers2,5and10areusedinthealarm communicationtotheBMS/SCADAsystem.
Relatedtotheexamples,"Temp.monitor" ,"Pump1"and"DigitalS12" arethealarmpoints.
Relatedtotheexamples,"32:Tsensordefect"indicatesthemonitoring ofconnectedsensors.
Alarmnumbersandalarmpointsmightdifferdependingonactual application.
Example:
’PumpP5’has causedanalarm.
Thealarmoverviewwillonlylistcomponentsorfunctionsthatcould causeanalarm.
88|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

6.0Commoncontrollersettings

6.1Introductionto‘Commoncontrollersettings’

Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ000086455681en-010402
©Danfoss|2021.02|89
OperatingGuideECLComfort310,applicationA361

6.2Time&Date

Itisonlynecessarytosetthecorrectdateandtimeinconnection withthefirstuseoftheECLComfortcontrollerorafterapower breakofmorethan72hours.
Thecontrollerhasa24hourclock.
Aut.daylight(Daylightsavingtimechangeover)
YES:
NO:
Thecontroller’sbuilt-inclockautomaticallychanges+/
-onehouronthestandardizeddaysfordaylightsaving timechangeoverforCentralEurope.
Youchangemanuallybetweensummerandwintertime bysettingtheclockbackwardorforward.
Howtosettimeanddate:
Action:
Purpose:
Choose‘MENU’
Confirm Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Time&Date’
Confirm Placethecursoratthepositiontobe
changed
Confirm
Enterthedesiredvalue
Confirm
Movethecursortothenextposition tobechanged.Continueuntil‘Time& Date’hasbeenset.
Finallymovethecursorto‘MENU’
Whencontrollersareconnectedasslavesinamaster/slavesystem
Examples:
(viaECL485communicationbus),theywillreceive‘Time&Date’from themaster.
90|©Danfoss|2021.02
Confirm
Movethecursorto‘HOME’
Confirm
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

6.3Holiday

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Thereisaholidayprogramforeachcircuitandaholidayprogram forthecommoncontroller.
Eachholidayprogramcontainsoneormoreschedules.Each schedulecanbesettoastartdateandanenddate.Thesetperiod startsonthestartdateat00.00andstopsontheenddateat00.00.
SelectablemodesareComfort,Saving,FrostprotectionorComfort 7-23(before7andafter23,themodeisscheduled).
Howtosetyourholidayschedule:
Action:
Purpose:
Examples:
Choose‘MENU’
Confirm Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm Chooseacircuitor'Commoncontroller
settings' Heating
DHW Commoncontrollersettings
Confirm
Goto‘Holiday’
Confirm
Theholidayprograminthe‘Commoncontrollersettings’isvalidfor allcircuits.Theholidayprogramcanalsobesetindividuallyinthe heatingorDHWcircuits.
Theenddatemustbeatleastbeonedaylaterthanthestartdate.
Chooseaschedule
Confirm
Confirmchoiceofmodeselector
Choosemode
Comfort
·Comfort7–23
Saving
·Frostprotection
Confirm Enterthestarttimefirstandthenthe
endtime Confirm
Goto‘Menu’
Confirm Choose‘Yes’or‘No’in‘Save’ .Choose
thenextschedule,ifrequired
AQ000086455681en-010402
©Danfoss|2021.02|91
OperatingGuideECLComfort310,applicationA361
Holiday,specificcircuit/CommonController
Whensettingoneholidayprograminspecificcircuitandanother holidayprograminCommonController,aprioritywillbetaken intoaccount:
1.Comfort
2.Comfort7-23
3.Saving
4.Frostprotection
Holiday,deletingasetperiod:
ChoosetheScheduleinquestion
Changethemodeto"Clock"
Confirm
Example1:
Circuit1: Holidaysetto"Saving"
CommonController: Holidaysetto"Comfort"
Result: Aslongas"Comfort"isactiveinCommonController,circuit1willbein
"Comfort".
Example2:
Circuit1: Holidaysetto"Comfort"
CommonController: Holidaysetto"Saving"
Result: Aslongas"Comfort"isactiveincircuit1,itwillbein"Comfort".
Example3:
Circuit1: Holidaysetto"Frostprotection"
TheECA30/31cannotoverridetheholidayscheduleofthe controllertemporarily.
However,itispossibletomakeuseofthefollowingoptionsfrom theECA30/31whenthecontrollerisinscheduledmode:
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
CommonController: Holidaysetto"Saving"
Result: Aslongas"Saving"isactiveinCommonController,circuit1willbe
in"Saving".
Energy-savingtrick: Use'Goingout'(theextendedsavingperiod)forairingpurposes(e.g. forventilatingtheroomsbymeansoffreshairfromopenwindows).
ConnectionsandsetupproceduresforECA30/31: Seesection'Miscellaneous'.
Quickguide"ECA30/31tooverridemode":
1.GotoECAMENU
2.Movecursorto"Clock"symbol
3.Selectthe"Clock"symbol
4.Chooseandselectoneof4overridefunctions
5.Belowtheoverridesymbol:Sethoursordate
6.Belowhours/date:Setdesiredroomtemperaturefortheoverride period
92|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

6.4Inputoverview

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Theinputoverviewislocatedinthecommoncontrollersettings.
Thisoverviewwillalwaysshowyoutheactualtemperaturesinthe system(read-only).
"Outdooracc.T"means"Accummulatedoutdoortemperature"andis acalculatedvalueintheECLComfortcontroller.
AQ000086455681en-010402
©Danfoss|2021.02|93
OperatingGuideECLComfort310,applicationA361

6.5Log

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Thelogfunction(temperaturehistory)allowsyoutomonitorthe logsoftoday,yesterday,thepast2daysaswellasthepast4days fortheconnectedsensors.
Thereisalogdisplayfortherelevantsensor,showingthemeasured temperature.
Thelogfunctionisonlyavailableinthe'Commoncontroller settings'.
Example1:
1daylogforyesterdayshowingthedevelopmentinoutdoor temperatureduringthepast24hours.
Example2:
Today’slogfortheactualheatingflowtemperatureaswellasthe desiredtemperature.
Example3:
Yesterday’slogfortheDHWflowtemperatureaswellasthedesired temperature.
94|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361

6.6Outputoverride

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Theoutputoverrideisusedtodisableoneormoreofthecontrolled components.Thiscouldamongothersbeusefulinaservice situation.
Action:Purpose:
Choose'MENU'inanyoftheoverview displays
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choosecommoncontrollersettings
Confirm
Choose'Outputoverride'
Confirm
Chooseacontrolledcomponent
Confirm
Adjustthestatusofthecontrolled component: Motorizedcontrolvalve:AUTO,STOP , CLOSE,OPEN Pump:AUTO,OFF ,ON
Confirmstatuschange
Examples:
M1,P1etc.
ControlledcomponentsCircuitselector
"Manualcontrol"hashigherprioritythan"Outputoverride".
Whentheselectedcontrolledcomponent(output)isnot‘AUTO’ ,the ECLComfortcontrollerdoesnotcontrolthecomponentinquestion (pumpormotorizedcontrolvalvee.g.).Frostprotectionisnotactive.
Remembertochangethestatusbackagainassoonasanoverride isnotrequiredanylonger.
AQ000086455681en-010402
Whenoutputoverrideofacontrolledcomponentisactivethesymbol ‘!’isshowntotherightofthemodeindicatorintheenduserdisplays.
©Danfoss|2021.02|95
OperatingGuideECLComfort310,applicationA361

6.7Keyfunctions

NewapplicationEraseapplication:
ApplicationGivesanoverviewovertheactual
FactorysettingSystemsettings:
Copy
Keyoverview
Removestheexistingapplication.As soonastheECLkeyisinserted,another applicationcanbechosen.
applicationintheECLcontroller.Push thedialagaintoexittheoverview.
Systemsettingsare,amongothers, communicationset-up,display brightnessetc.
Usersettings:
Usersettingsare,amongothers,desired roomtemperature,desiredDHW temperature,schedules,heatcurve, limitationvaluesetc.
Gotofactory:
Restoresthefactorysettings.
To:
Copydirection
Systemsettings
Usersettings
Startcopying
GivesanoverviewovertheinsertedECL key.(Example:A266Ver.2.30). Turnthedialtoseethesubtypes.Push thedialagaintoexittheoverview.
Amoredetaileddescriptionofhowtousetheindividual‘Key functions’canalsobeseenin‘InsertingtheECLapplicationkey’ .
96|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ000086455681en-010402
©Danfoss|2021.02|97
OperatingGuideECLComfort310,applicationA361

6.8System

6.8.1ECLversion
In‘ECLversion’youwillalwaysbeabletofindanoverviewofthe datarelatedtoyourelectroniccontroller.
Pleasehavethisinformationavailableifyouneedtocontactyour Danfosssalesorganizationconcerningthecontroller.
InformationaboutyourECLApplicationKeycanbefoundin‘Key functions’and‘Keyoverview’ .
Codeno.:
Hardware:
Software:Software(firmware)versionof
Serialno.:
Productionweek:Weekno.andyear(WW.YYYY)
6.8.2Extension
ECLComfort310/310B: ‘Extension’willofferyouinformationaboutadditionalmodules,if any.AnexamplecouldbetheECA32module.
TheDanfosssalesandorderno. forthecontroller
Hardwareversionofthe controller
thecontroller Uniquenumberforthe
individualcontroller
Example,ECLversion
6.8.3Ethernet
ECLComfort296/310/310BhaveaModbus/TCPcommunication interfacethatallowstheECLcontrollertobeconnectedtoan Ethernetnetwork.ThisallowsremoteaccesstotheECL296/310/ 310Bcontrollerbasedonstandardcommunicationinfrastructures.
In‘Ethernet’itispossibletosetuptherequiredIPaddresses.
6.8.4Portalconfig
ECLComfort296/310/310BhaveaModbus/TCPcommunication interfacethatallowstheECLcontrollertobemonitoredand controlledviatheECLPortal.
ECLPortalrelatedparametersaresethere.
DocumentationforECLPortal:Seehttps://ecl.portal.danfoss.com
6.8.5M-busconfig
ECLComfort296/310/310BhaveanM-buscommunication interfacethatallowsenergymeterstobeconnectedasslaves.
M-busrelatedparametersaresethere.
98|©Danfoss|2021.02
AQ000086455681en-010402
OperatingGuideECLComfort310,applicationA361
6.8.6EnergymeterandM-bus,generalinformation
ECLComfort296/310/310Bonly
WhenusingtheApplicationKeyintheECLComfort296/310 /310B,upto5energymeterscanbeconnectedtotheM-bus connections.
Connectionofenergymetercan:
limittheflow
limitthepower
transferenergymeterdatatotheECLPortal,viaEthernet,and/ oraSCADAsystem,viaModbus.
Manyapplicationswithcontrolofheating,DHWorcoolingcircuit havethepossibilitytoreactonenergymeterdata. Toverifyifactualapplicationkeycanbesettoreactonenergy meterdata: SeeCircuit>MENU>Settings>Flow/power.
TheECLComfort296/310/310Bcanalwaysbeusedfor monitoringpurposeofupto5energymeters.
TheECLComfort296/310/310BactasanM-busmasterandmust besettocommunicatewithconnectedenergymeter(s). SeeMENU>Commoncontroller>System>M-busconfig.
EnergymeterdataacquisitionfromECLPortalispossiblewithout settinguptheM-busconfiguration.
Technicalinfo:
TheM-busdataarebasedonstandardEN-1434.
DanfossrecommendsACsuppliedenergymetersinorderto avoidbatterydraining.
MENU>Commoncontroller>System>M-busconfig.
State
CircuitSettingrange
Read-out
Factorysetting
---
InformationaboutthecurrentM-busactivity.
IDLE:
INIT:
SCAN:
GATEW:
Normalstate
Thecommandforinitializationhasbeenactivated Thecommandforscanninghasbeenactivated ThecommandGatewayhasbeenactivated
MENU>Commoncontroller>System>M-busconfig.
TheECLComfort296/310/310BwillreturntoIDLEwhencommands havebeencompleted.
Gatewayisusedforread-outofenergymeterviaECLPortal.
Baud(bitspersecond)
CircuitSettingrange
-
300/600/1200/2400
ThecommunicationspeedbetweenECLComfort296/310/310B andtheconnectedenergymeter(s).
AQ000086455681en-010402
5997
Factorysetting
300
Typically,300or2400baudisused. IfECLComfort296/310/310BareconnectedtotheECLPortal,abaud
rateof2400isrecommendable,providedtheenergymeterallowsthis.
©Danfoss|2021.02|99
OperatingGuideECLComfort310,applicationA361
MENU>Commoncontroller>System>M-busconfig.
Command
CircuitSettingrange
-
NONE/INIT/SCAN/GA TEWNONE
Factorysetting
TheECLComfort296/310/310BareM-busmasters.Inordertoverify connectedenergymeters,differentcommandscanbeactivated.
NONE:
INIT:
SCAN:
Nocommandactivated Initializationisactivated
Scanningisactivatedinordertosearchforconnected energymeters.TheECLComfort296/310/310B detecttheM-busaddressesofupto5connected energymetersandplacetheseautomaticallyinthe "Energymeters"section.Theverifiedaddressisplaced after"Energymeter1(2,3,4,5)"
GATEW:
TheECLComfort296/310/310Bactasagateway betweenenergymetersandECLPortal.Usedonlyfor service.
MENU>Commoncontroller>System>M-busconfig.
M-busaddress Energymeter1(2,3,4,5)
CircuitSettingrange
-
0-255255
Factorysetting
Thesetorverifiedaddressofenergymeter1(2,3,4,5).
5998
Scantimecantakeupto12minutes. Whenallenergymetersarefound,thecommandcanbechanged
toINITorNONE.
6000
0:
1-250:
251-254:
Normallynotused ValidM-busaddresses
Specialfunctions.UseonlyM-busaddress254when oneenergymeterisconnected.
255:
Notused
MENU>Commoncontroller>System>M-busconfig.
Type Energymeter1(2,3,4,5)
CircuitSettingrange
-
0-40
Factorysetting
SelectingdatarangefromtheM-bustelegram..
0:
1:
2:
3:
4:
Smalldataset,smallunits Smalldataset,largeunits Largedataset,smallunits Largedataset,largeunits Volumeandenergydataonly
(example:HydroPortPulse)
6001
Dataexamples:
0: Flowtemp.,returntemp.,flow,power,acc.volume,acc.energy.
3: Flowtemp.,returntemp.,flow,power,acc.volume,acc.energy, tariff1,tariff2.
Seealsothe"Instructions,ECLComfort210/310,communication description"forfurtherdetails.
SeealsoAppendixfordetaileddescriptionof"Type".
100|©Danfoss|2021.02
AQ000086455681en-010402
Loading...