Danfoss A333 Operating guide

OperatingGuide
ECLComfort310,applicationA333

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................10
2.4Placingthetemperaturesensors................................18
2.5Electricalconnections.............................................20
2.6InsertingtheECLApplicationKey..............................51
2.7Checklist............................................................58
2.8Navigation,ECLApplicationKeyA333.........................59
3.0Dailyuse.........................................................64
3.1Howtonavigate...................................................64
3.2Understandingthecontrollerdisplay..........................65
3.3Ageneraloverview:Whatdothesymbolsmean?...........68
3.4Monitoringtemperaturesandsystem
components........................................................69
3.5Influenceoverview................................................70
3.6Manualcontrol.....................................................71
3.7Schedule............................................................72
4.0Settingsoverview............................................73
5.0Settings...........................................................76
5.1IntroductiontoSettings..........................................76
5.2Flowtemperature..................................................77
5.4Flow/powerlimit.................................................82
5.5Optimization........................................................85
5.6Controlparameters1..............................................90
5.7Controlparameters,refillpump(s)..............................95
5.8Controlparameters,circulationpump(s)....................100
5.9Pumpcontrol.....................................................103
5.10Refillwater........................................................106
5.11Refilltank..........................................................113
5.12Application.......................................................116
5.13Watermeter......................................................120
5.14Flowmeter........................................................121
5.15S7,S8,S9,S10pressure.........................................124
5.16Alarm..............................................................127
6.0Commoncontrollersettings............................132
6.1Introductionto‘Commoncontrollersettings’..............132
6.2Time&Date.......................................................133
6.3Holiday............................................................134
6.4Inputoverview...................................................136
6.5Log.................................................................137
6.6Outputoverride..................................................138
6.7Keyfunctions.....................................................139
6.8System.............................................................141
7.0Miscellaneous................................................148
7.1ECA30/31setupprocedures.................................148
7.2Overridefunction................................................156
7.3Severalcontrollersinthesamesystem......................159
7.4Frequentlyaskedquestions....................................162
7.5Definitions........................................................165
7.6Type(ID6001),overview.......................................169
7.7Automatic/manualupdateoffirmware.....................170
7.8ParameterIDoverview..........................................171
©Danfoss|2021.04AQ076586461441en-010401|1
OperatingGuideECLComfort310,applicationA333

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA333 (ordercodeno.087H3818).
ThefunctionsarerealizedinECLComfort310foradvanced solutions,e.g.M-bus,ModbusandEthernet(Internet) communication.
TheapplicationA333complieswithECLComfortcontrollers310as ofsoftwareversion1.11(visibleatstart-upofthecontrollerandin ‘Commoncontrollersettings’in‘System’).
TheapplicationA333workswiththeInternalI/OmoduleECA32 (ordercodeno.087H3202).
AdditionaldocumentationforECLComfort310,modulesand accessoriesisavailableonwww.ecl.doc.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
2|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
2
Circuit2Parameterno.
AQ076586461441en-010401
174
©Danfoss|2021.04|3
OperatingGuideECLComfort310,applicationA333
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
4|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

2.0Installation

2.1Beforeyoustart

TheA333applicationkeycontains3subtypes:A333.1,A333.2 andA333.3whicharealmostidentical.
Differentandextrafunctionsaredescribedadditionally.
TheapplicationA333.1isveryflexible.
Thesearethebasicprinciples:
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.
TheflowtemperaturesensorS3isthemostimportantsensor.The desiredflowtemperatureatS3iscalculatedintheECLcontroller, basedontheoutdoortemperature(S1)andthedesiredroom temperature.Thelowertheoutdoortemperature,thehigherthe desiredflowtemperature.
Bymeansofaweekschedule(upto3'Comfort'periods/day),the heatingcircuitcanbein'Comfort'or'Saving'mode(twodifferent temperaturevaluesforthedesiredroomtemperature).
InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM1isopenedgraduallywhentheflow temperatureS3islowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature. Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
AconnectedfloworenergymeterbasedonM-bussignalcan limitthefloworenergytoasetmaximumvalue.Furthermorethe limitationcanbeinrelationtotheoutdoortemperature.Typically, thelowertheoutdoortemperature,thehighertheacceptedflow/ power.
ThecirculationpumpsP1andP2areoperatedalternately.One circulationpumpisusedasworkingpumpandtheothercirculation pumpisusedassparepump.Thecirculationpumpinquestionis ONatheatdemandoratfrostprotection.Thealternationtime canbesetasanumberofdaysandasettimeontheshiftday.A solutionwithasinglecirculationpumpcanalsobeselected.
BymeansofthepressuredifferencebetweenS9andS10the ECLcontrollerverifiesthatthecirculationpumpinquestionis operating.
ApplicationA333.1:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
(Optional)Primarysupplytemperaturesensor.For monitoringpurpose
S3
Secondaryflowtemperaturesensor
S4
(Optional)Secondaryreturntemperaturesensor.For monitoringpurpose
S5
(Optional)Primaryreturntemperaturesensor
S7
(Optional)Primarysupplypressuresensor.Formonitoring purpose
S8
(Optional)Primaryreturnpressuresensor.Formonitoring purpose
S9
Secondaryflowpressuresensor
S10
Secondaryreturnpressuresensor
M1
Motorizedcontrolvalve(3-pointcontrolled)
P1/P2
Circulationpumps
P3/P4
Refillwaterpumps
V1
Refillwatervalve
V2
Pressurereleasevalve
A1
Alarm
Thepressuredifferenceonthesecondarysideisbasedonthestatic pressuresatS9andS10.Thepressuresaremeasuredas0-10volt signals(frompressuretransmitters)andconverted(scaled)inthe ECLcontrollertoappropriatepressurevalues.
AQ076586461441en-010401
©Danfoss|2021.04|5
OperatingGuideECLComfort310,applicationA333
Ifanacceptablepressuredifferenceisnotdetected,theECL controlleractivatesthealarmandshiftstheoperatingcommandto theoppositecirculationpump.
TheheatingcanbeswitchedOFFautomaticallywhentheoutdoor temperatureishigherthanaselectablevalue.
TheFrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
Incaseofatoolowpressure,measuredbyS10,therefillwater functionwillsupplementwithwaterfromawatersource.
ArefillpumpisswitchedONandtheON/OFFvalveV1opens.
TherefillpumpsP3andP4areoperatedalternately.Onepumpis usedasworkingpumpandtheotherpumpisusedassparepump. Thealternationtimecanbesetasanumberofdays.
Asolutionwithasinglerefillpumpcanalsobeselected.
Incaseofatoohighpressure,measuredbyS10,thereleasevalve V2(ON/OFF)willopeninordertoreducethepressure.
6|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
TheapplicationA333.2isveryflexibleandworkslikeA333.1, andwiththeseadditionalfeatures:
*
ThecirculationpumpsP1/P2can,asanalternativetoON-OFF control,bespeedcontrolledbymeansofa0-10voltsignal. ThedesiredpressuredifferencebetweenS9andS10issetfor thespeedcontrolprocedure. Aflow-meterF2(pulsesignal,analoguesignalS13orM-Bus) measuresthecirculationofwaterintheheatingcircuit.
*
Thelevelintherefillwaterstoragetankismeasuredby meansofthepressuresensorS12.Whenatoolowpressure ismeasured,theON/OFFvalveV3opens.Anacceptable pressurewillclosetheV3valve.
*
TherefillwaterpumpsP3/P4can,asanalternativetoON-OFF control,bespeedcontrolledbymeansofa0-10voltsignal. ThedesiredpressureatS10issetforthespeedcontrol procedure. Aflow-meterF1(pulsesignalorM-Bus)measurestheinjected refillwater.
ApplicationA333.2:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
ElectroniccontrollerECLComfort310
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Primarysupplytemperaturesensor.For monitoringpurpose
S3
Secondaryflowtemperaturesensor
S4
(Optional)Secondaryreturntemperaturesensor.For monitoringpurpose
S5
(Optional)Primaryreturntemperaturesensor
S7
(Optional)Primarysupplypressuresensor.Formonitoring purpose
S8
(Optional)Primaryreturnpressuresensor.Formonitoring purpose
S9
Secondaryflowpressuresensor
S10
Secondaryreturnpressuresensor
F1
(Optional)Flowmeter(pulseorM-bussignal)
F2
(Optional)Flowmeter(pulse,0-10voltorM-bussignal)
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Speedcontrol(0-10volt)ofP3/P4
M3
Speedcontrol(0-10volt)ofP1/P2
P1/P2
Circulationpumps
P3/P4
Refillwaterpumps
V1
Refillwatervalve
V2
Pressurereleasevalve
V3
Refillwatertankvalve
A1
Alarm
AQ076586461441en-010401
©Danfoss|2021.04|7
OperatingGuideECLComfort310,applicationA333
TheapplicationA333.3isveryflexibleandworkslikeA333.2, butwiththisfeature:
*
ThemotorizedcontrolvalveM1iscontrolledbymeansofa 0-10voltsignal.
ApplicationA333.2:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
ElectroniccontrollerECLComfort310
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Primarysupplytemperaturesensor.For monitoringpurpose
S3
Secondaryflowtemperaturesensor
S4
(Optional)Secondaryreturntemperaturesensor.For monitoringpurpose
S5
(Optional)Primaryreturntemperaturesensor
S7
(Optional)Primarysupplypressuresensor.Formonitoring purpose
S8
(Optional)Primaryreturnpressuresensor.Formonitoring purpose
S9
Secondaryflowpressuresensor
S10
Secondaryreturnpressuresensor
F1
(Optional)Flowmeter(pulseorM-bussignal)
F2
(Optional)Flowmeter(pulse,0-10voltorM-bussignal)
M1
Motorizedcontrolvalve(0-10voltcontrolled)
M2
Speedcontrol(0-10volt)ofP3/P4
M3
Speedcontrol(0-10volt)ofP1/P2
P1/P2
Circulationpumps
P3/P4
Refillwaterpumps
V1
Refillwatervalve
V2
Pressurereleasevalve
V3
Refillwatertankvalve
A1
Alarm
8|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
ApplicationA333ingeneral:
UptotwoRemoteControlUnits,theECA30canbeconnectedto oneECLcontrollerinordertocontroltheECLcontrollerremotely.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout heatingdemandcanbearranged.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL 485businordertoutilizecommonoutdoortemperaturesignal, timeanddatesignals.TheECLControllersintheECL485system canworkinmaster-slavesystem.
Aconnectedfloworenergymeter(basedonM-bussignal)can limitthefloworenergytoasetmaximumandinrelationtothe outdoortemperature.
Unusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished. TheM-busdatacanfurthermorebetransferredtotheModbus communication.
AlarmA1(=relay6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow temperature.
ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview).
ifthecirculationpump(s)do(es)notgenerateacceptable pressure.
iftherefillwaterpump(s)do(es)notgenerateacceptable pressure.
ifmeasuredpressuresarenotinsideanacceptablepressure range.
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
AQ076586461441en-010401
©Danfoss|2021.04|9
OperatingGuideECLComfort310,applicationA333

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
10|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
A333.1,ex.a
Heatingsystemwithcontrolofupto2circulationpumpsandupto2refillwaterpumps
A333.1,ex.b
Basicheatingsystem
AQ076586461441en-010401
©Danfoss|2021.04|11
OperatingGuideECLComfort310,applicationA333
A333.1,ex.c
Heatingsystemwithcirculationpumpfeedback
A333.1,ex.d
Heatingsystemwithrefillwatersystem
12|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
A333.1,ex.e
Heatingsystemwithrefillwaterandexcesspressuresystem
A333.2,ex.a
HeatingsystemwithON/OFFandspeedcontrolofupto2circulationpumpsandupto2refillwaterpumps.Refillwaterstoragecontrol.
AQ076586461441en-010401
©Danfoss|2021.04|13
OperatingGuideECLComfort310,applicationA333
A333.3,ex.a
HeatingsystemwithON/OFFandspeedcontrolofupto2circulationpumpsandupto2refillwaterpumps.Refillwaterstoragecontrol. ControlvalveM1iscontrolledby0-10voltsignal.
14|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ076586461441en-010401
©Danfoss|2021.04|15
OperatingGuideECLComfort310,applicationA333
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
16|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
AQ076586461441en-010401
©Danfoss|2021.04|17
OperatingGuideECLComfort310,applicationA333

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
18|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ076586461441en-010401
©Danfoss|2021.04|19
OperatingGuideECLComfort310,applicationA333

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
20|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
AQ076586461441en-010401
©Danfoss|2021.04|21
OperatingGuideECLComfort310,applicationA333
2.5.2Electricalconnections,230Va.c.,powersupply,pumps,dampers,motorizedcontrolvalvesetc.
ConnectionsforA333.1andA333.2,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.1/A333.2
Terminal
19 18
A1
17
V2 16 15
P4 14
13
P3 12
P2 11
P1 10
9 8 7
M1
6
M1
5 4
V1
3 2 1
*Relaycontacts:4Aforohmicload,2Aforinductiveload
Description
PhaseforON/OFFvalve/Alarm Alarm ON/OFFvalveforpressurerelease Phaseforrefillwaterpump Refillwaterpump
Phaseforcirculationpumps/refillwaterpump Refillwaterpump Circulationpump Circulationpump Supplyvoltage230Va.c.-neutral(N) Supplyvoltage230Va.c.-live(L)
PhaseformotorizedcontrolvalveM1 Motorizedcontrolvalve-opening Motorizedcontrolvalve-closing
PhaseforON/OFFvalveV1 ON/OFFvalveforrefillwater Nottobeused Nottobeused Nottobeused
Max.load
4(2)A/230Va.c.* 4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.* 4(2)A/230Va.c.* 4(2)A/230Va.c.*
0.2A/230Va.c.
0.2A/230Va.c.
0.2A/230Va.c.
Factoryestablishedjumpers: 5to8,9to14,Lto5andLto9,Nto10
22|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ076586461441en-010401
©Danfoss|2021.04|23
OperatingGuideECLComfort310,applicationA333
2.5.3Electricalconnections,230Va.c.,powersupply,pumps,dampers,motorizedcontrolvalvesetc.
ConnectionsforA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.3
Terminal
19 18
A1 17
V2 16 15
P4 14
13
P3 12
P2 11
P1 10
9 8 7
6 5 4
V1
3 2 1
*Relaycontacts:4Aforohmicload,2Aforinductiveload
Description
PhaseforON/OFFvalve/Alarm Alarm ON/OFFvalveforpressurerelease Phaseforrefillwaterpump Refillwaterpump
Phaseforcirculationpumps/refillwaterpump Refillwaterpump Circulationpump Circulationpump Supplyvoltage230Va.c.-neutral(N) Supplyvoltage230Va.c.-live(L) Nottobeused Nottobeused Nottobeused
PhaseforON/OFFvalveV1 ON/OFFvalveforrefillwater Nottobeused Nottobeused Nottobeused
Max.load
4(2)A/230Va.c.* 4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.* 4(2)A/230Va.c.* 4(2)A/230Va.c.*
0.2A/230Va.c.
0.2A/230Va.c.
0.2A/230Va.c.
0.2A/230Va.c.
Factoryestablishedjumpers: 5to8,9to14,Lto5andLto9,Nto10
24|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ076586461441en-010401
©Danfoss|2021.04|25
OperatingGuideECLComfort310,applicationA333
2.5.4Electricalconnections,ECA32
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Terminal
39
R10 40
R10 41
R9 42
R9 43
R8 44
R8 45
R8 46
R7 47
R7 48
R7
49 50
S11 51
S12 52
S13 53 54 55
Description
Relay10,notused
Relay9,notused
Relay8,notused
Relay7
V3,ON/OFFvalveforpressurerelease PhaseforON/OFFvalveV3
Commonterminalforinputsignals Input:PositionsignalfromM1,0-10volt Input:Refillwaterlevelinstoragetank,0-10volt Input:F2flowsignal,0-10volt Nottobeused Nottobeused Nottobeused
Max.load
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
56
57
F1 58
F2
59
M1 60
M2 61
M3 62
*Relaycontacts:4Aforohmicload,2Aforinductiveload **Min.resistance:5KΩ
ReferenceterminalforAnalogueout2(M2)and3(M3)
Input:Flow-meter,pulsetype Input:Flow-meter,pulsetype
Analogueout1:0-10voltforcontrolofmotorizedcontrolvalveM1(A333.3) Analogueout2:0-10voltforspeedcontrolofrefillwaterpumpsP3andP4(A333.2,A333.3) Analogueout3:0-10voltforspeedcontrolofcirculationpumpsP1andP2(A333.2,A333.3) ReferenceterminalforAnalogueout1(M1)
2mA** 2mA** 2mA**
26|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.5Electricalconnections,ON/OFFvalveV3controlledfromrelayoutputinECA32
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
2.5.6Electricalconnections,230Va.c.,powersupply,motorizedcontrolvalveM1controlledby0-10voltfromECA32
ConnectionsforA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.3
Thetransformerforsupplyingtheactuatormustbeadouble-isolatedversion.
AQ076586461441en-010401
©Danfoss|2021.04|27
OperatingGuideECLComfort310,applicationA333
2.5.7Electricalconnections,230Va.c.,powersupply,controlof2or3phasepoweredpumps
ConnectionsforA333.1,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.1
2.5.8Electricalconnections,230Va.c.,powersupply,ON/OFFcontrolandspeedcontrolof1phasepoweredpumps
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
28|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.9Electricalconnections,230Va.c.,powersupply,0-10voltforspeedcontrolof1phasepoweredpumps
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
2.5.10Electricalconnections,230Va.c.,powersupply ,ON/OFFcontrolandspeedcontrolof2or3phasepoweredpumps
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
AQ076586461441en-010401
©Danfoss|2021.04|29
OperatingGuideECLComfort310,applicationA333
2.5.11Electricalconnections,230Va.c.,powersupply,ON/OFFcontrolandspeedcontrol(viaFrequencyConverter)of1 phasepoweredpumps
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
FC=FrequencyConverter
2.5.12Electricalconnections,230Va.c.,powersupply,ON/OFFcontrolandspeedcontrol(viaFrequencyConverter)of2 or3phasepoweredpumps
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
FC=FrequencyConverter
30|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.13Electricalconnections,examplewithexternalStart/StopcontrolofaFrequencyConverterforcirculationpumpsP1/P2
ApplicationA333.2/A333.3
FC=FrequencyConverter
2.5.14Electricalconnections,examplewithexternalStart/StopcontrolofaFrequencyConverterforrefillwaterpumpsP3/P4
ApplicationA333.2/A333.3
FC=FrequencyConverter
AQ076586461441en-010401
©Danfoss|2021.04|31
OperatingGuideECLComfort310,applicationA333
2.5.15Electricalconnections,safetythermostats,230Va.c.or24Va.c.
Withsafetythermostat,1–stepclosing:
Motorizedcontrolvalvewithoutsafetyfunction
Withsafetythermostat,1–stepclosing:
Motorizedcontrolvalvewithsafetyfunction
Withsafetythermostat,2–stepclosing:
Motorizedcontrolvalvewithsafetyfunction
32|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ076586461441en-010401
©Danfoss|2021.04|33
OperatingGuideECLComfort310,applicationA333
2.5.16Electricalconnections,24Va.c.(ECL310only),powersupply,pumps,motorizedvalvesetc.
ConnectionsforA333.1andA333.2,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.1/A333.2
Terminal
19 18
A1 17
V2 16 15
P4 14
13
P3 12
P2 11
P1 10
9 8 7
M1
6
M1
5 4
V1
3 2 1
*Relaycontacts:4Aforohmicload,2Aforinductiveload
Description
Supplyvoltage(SP)forON/OFFvalve/Alarm Alarm ON/OFFvalveforpressurerelease Supplyvoltage(SP)forrefillwaterpump Refillwaterpump
Supplyvoltage(SP)forcirculationpumps/refillwaterpump Refillwaterpump Circulationpump Circulationpump Supplyvoltage24Va.c.-(SN) Supplyvoltage24Va.c.-(SP)
Supplyvoltage(SP)formotorizedcontrolvalveM1 Motorizedcontrolvalve-opening Motorizedcontrolvalve-closing
Supplyvoltage(SP)forON/OFFvalveV1 ON/OFFvalveforrefillwater Nottobeused Nottobeused Nottobeused
Max.load
4(2)A/24Va.c.* 4(2)A/24Va.c.*
4(2)A/24Va.c.*
4(2)A/24Va.c.* 4(2)A/24Va.c.* 4(2)A/24Va.c.*
1A/24Va.c. 1A/24Va.c.
1A/24Va.c.
Factoryestablishedjumpers: 5to8,9to14,Lto5andLto9,Nto10
34|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
AQ076586461441en-010401
©Danfoss|2021.04|35
OperatingGuideECLComfort310,applicationA333
2.5.17Electricalconnections,24Va.c.(ECL310only),powersupply,pumps,motorizedvalvesetc.
ConnectionsforA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.3
Terminal
19 18
A1 17
V2 16 15
P4 14
13
P3 12
P2 11
P1 10
9 8 7
6 5 4
V1
3 2 1
*Relaycontacts:4Aforohmicload,2Aforinductiveload
Description
Supplyvoltage(SP)forON/OFFvalve/Alarm Alarm ON/OFFvalveforpressurerelease Supplyvoltage(SP)forrefillwaterpump Refillwaterpump
Supplyvoltage(SP)forcirculationpumps/refillwaterpump Refillwaterpump Circulationpump Circulationpump Supplyvoltage24Va.c.-(SN) Supplyvoltage24Va.c.-(SP) Nottobeused Nottobeused Nottobeused
Supplyvoltage(SP)forON/OFFvalveV1 ON/OFFvalveforrefillwater Nottobeused Nottobeused Nottobeused
Max.load
4(2)A/24Va.c.* 4(2)A/24Va.c.*
4(2)A/24Va.c.*
4(2)A/24Va.c.* 4(2)A/24Va.c.* 4(2)A/24Va.c.*
1A/24Va.c.
Factoryestablishedjumpers: 5to8,9to14,Lto5andLto9,Nto10
36|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
AQ076586461441en-010401
©Danfoss|2021.04|37
OperatingGuideECLComfort310,applicationA333
2.5.18Electricalconnections,ECA32
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Terminal
39
R10
40
R10
41
R9
42
R9
43
R8
44
R8
45
R8
46
R7
47
R7
48
R7
49 50
S11
51
S12
52
S13 53 54 55
Description
Relay10,notused
Relay9,notused
Relay8,notused
Relay7
V3,ON/OFFvalveforpressurerelease PhaseforON/OFFvalveV3
Commonterminalforinputsignals Input:PositionsignalfromM1,0-10volt Input:Refillwaterlevelinstoragetank,0-10volt Input:F2flowsignal,0-10volt Input:notused Input:notused Input:notused
Max.load
4(2)A/24Va.c.*
4(2)A/24Va.c.*
4(2)A/24Va.c.*
4(2)A/24Va.c.*
56
57
F1 58
F2
59
M1 60
M2 61
M3
62
*Relaycontacts:4Aforohmicload,2Aforinductiveload **Min.resistance:5KΩ
ReferenceterminalforAnalogueout2(M2)and3(M3)
Input:Flow-meter,pulsetype Input:Flow-meter,pulsetype
Analogueout1:0-10voltforcontrolofmotorizedcontrolvalveM1(A333.3) Analogueout2:0-10voltforspeedcontrolofrefillwaterpumpsP3andP4(A333.2,A333.3) Analogueout3:0-10voltforspeedcontrolofcirculationpumpsP1andP2(A333.2,A333.3)
ReferenceterminalforAnalogueout1(M1)
2mA** 2mA** 2mA**
38|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.19Electricalconnections,24Va.c.,powersupply,ON/OFFvalveV3controlledfromrelayoutputinECA32
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
2.5.20Electricalconnections,24Va.c.,powersupply,motorizedcontrolvalveM1controlledby0-10voltfromECA32
ConnectionsforA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.3
Thetransformerforsupplyingtheactuatormustbeadouble-isolatedversion. TheECLComfort310andtheactuatorforthecontrolvalveM1musthaveseparatetransformers.
AQ076586461441en-010401
©Danfoss|2021.04|39
OperatingGuideECLComfort310,applicationA333
2.5.21Electricalconnections,24Va.c.,powersupply,controlof2or3phasepoweredpumps
ConnectionsforA333.1,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.1
2.5.22Electricalconnections,24Va.c.,powersupply,0-10voltforspeedcontrolof1,2or3phasepoweredpumps
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
40|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.23Electricalconnections,24Va.c.,powersupply,ON/OFFcontrolandspeedcontrol(viaFrequencyConverter)of1,2 or3phasepoweredpumps
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
ApplicationA333.2/A333.3
FC=FrequencyConverter
ElectricalconnectionsforexternalStart/StopcontrolofaFrequencyConverter: Seeexamplesin"Electricalconnections,230Va.c. ”
AQ076586461441en-010401
©Danfoss|2021.04|41
OperatingGuideECLComfort310,applicationA333
2.5.24Electricalconnections,Pt1000temperaturesensorsandsignals
ConnectionsforA333,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
TerminalSensor/description
29and30
28and30
27and30
26and30
25and30
24and30Notused 23and30 22and30 21and30 20and30
*
**
S1
Outdoortemperature sensor*
S2
Primarysupplytemperature sensor
S3
Secondaryflowtemperature sensor**
S4
Secondaryreturn temperaturesensor
S5Primaryreturntemperature
sensor
S7
Pressuresignal(0-10volt)
S8
Pressuresignal(0-10volt)
S9
Pressuresignal(0-10volt)
S10
Pressuresignal(0-10volt)
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
Thesensormustalwaysbeconnectedinordertohavethe desiredfunctionality.Ifthesensorisnotconnectedorthe cableisshort-circuited,themotorizedcontrolvalvecloses (safetyfunction).
Type (recomm.)
ESMT
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
42|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.25Electricalconnections,pressuretransmitters,0-10volttypes
S7,S8,S9,S10
2.5.26Electricalconnections,pressuretransmitters,4-20mAtypes
S7,S8,S9,S10
4-20mAthrougharesistorof500ohmgivesavoltageof2-10volt.
AQ076586461441en-010401
©Danfoss|2021.04|43
OperatingGuideECLComfort310,applicationA333
2.5.27Electricalconnections,ECA32
ConnectionsforA333.2andA333.3,ingeneral:
SeealsotheMountingGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
TerminalSensor/description
50and49 51and49 52and49 53and49Notused 54and49Notused 55and49Notused
S11
PositionsignalfromM1,0-10volt
S12
Refillwaterlevelinstoragetank,0-10volt
S13
F2flowsignal,0-10volt
56
57and49 58and49
Waterandflowmeters,possibilities:
WatermeterF1 (flowmeter)
FlowmeterF2 (flowmeter)
Usedforoutputsignal
F1
Watermeter(flowmeter),pulsetype
F2
Flowmeter,pulsetype
-pulsetype
-M-Bus
-pulsetype
-0-10volttype
-M-Bus
44|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.28Electricalconnections,ECA32,flowmeters,pulsetypes
A333.2/A333.3
F1andF2,pulseinput
2.5.29Electricalconnections,ECA32,flowmeter ,0-10volttype
A333.2/A333.3
F2toinputS13(0-10voltinput)
AQ076586461441en-010401
©Danfoss|2021.04|45
OperatingGuideECLComfort310,applicationA333
2.5.30Electricalconnections,ECA32,pressuretransmitter,0-10volttype
A333.2/A333.3
S12,levelinrefillwaterstoragetank
2.5.31Electricalconnections,ECA32,pressuretransmitter,4-20mAtype
A333.2/A333.3
S12,levelinrefillwaterstoragetank
4-20mAthrougharesistorof500ohmgivesavoltageof2-10volt
2.5.32Electricalconnections,ECA32,M1valveposition,0-10volttype
A333.2/A333.3
S11,valvepositionindication
46|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.33Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
AQ076586461441en-010401
©Danfoss|2021.04|47
OperatingGuideECLComfort310,applicationA333
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
48|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
2.5.34Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
AQ076586461441en-010401
©Danfoss|2021.04|49
OperatingGuideECLComfort310,applicationA333
2.5.35Electricalconnections,communication
Electricalconnections,Modbus
Electricalconnections,M-bus
Example,M-busconnections
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
50|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
AQ076586461441en-010401
ECLComfort296
©Danfoss|2021.04|51
OperatingGuideECLComfort310,applicationA333
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
52|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
AQ076586461441en-010401
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
©Danfoss|2021.04|53
OperatingGuideECLComfort310,applicationA333
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
54|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
AQ076586461441en-010401
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
©Danfoss|2021.04|55
OperatingGuideECLComfort310,applicationA333
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
56|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ076586461441en-010401
©Danfoss|2021.04|57
OperatingGuideECLComfort310,applicationA333

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
58|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

2.8Navigation,ECLApplicationKeyA333

Parameterlist,applicationA333,Heating
Home MENU
ScheduleSchedule
Settings
Sub-menu
Heating
Flow temperature
Returnlimit
Flow/Actual powerlimitActuallimit
Optimization
Controlpar.1
IDnos.
11178 11179 11031 11032 11033 11034 11035 11036 11037 11085
11119 11117 11118 11116 11112 11113 11109 11115 11011 11012 11013 11014 11026 11021 11179
15113 15607 15608 11174 11184 11185 11186 11187 11189
Function
Heatcurve Temp.max. Temp.min HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Pre-stop Totalstop Summer,cut-out Position Filterconstant LowX HighX Motorpr Xp Tn Mrun Nz Min.act.time
A333
A333.1A333.2A333.3
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
((
((
((
((
(((
(((
(((
((
(((
((
AQ076586461441en-010401
©Danfoss|2021.04|59
OperatingGuideECLComfort310,applicationA333
Parameterlist,applicationA333,Heating,continued
Home MENU
Settings
Sub-menu
Heating
Controlpar.,Prefill
Controlpar.,Pcirc.
Pumpcontrol
RefillwaterTimeleft
IDnos.
11321 13184 13185 13187 13197 13165 13167 11331 111332 11330 11333 12322 12184 12185 12187 12197 12165 12167 11322 11314 11310 11313 11311 11312 11022 11316
12311 11321 13322 11318 11319 11323 11320 11325 11326 12316
Function
Pressure,des. Xp Tn Nz Td V.out,max. V.out,min. Sleeplevel Sleepmodetime Wake-uplevel Boost Pressure,diff. Xp Tn Nz Td V.out,max. V.out,min. Pressurediff. Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise Alarmhandling
Changeduration Pressuredes. Pressurediff. Max.pressure Max.press.diff. Time-out Pexercise Valvedelay No.ofpumps Alarmhandling
A333
A333.1A333.2A333.3
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
60|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
Parameterlist,applicationA333,Heating,continued
Home MENU
Settings
Sub-menu
Heating
Refilltank
Application
Watermeter
FlowmeterActual
S7pressurePressure
S8pressurePressure
S9pressurePressure
S10pressurePressure
IDnos.
16113 16607 16608 16602 16194 16195 11017 11500 11023 11052 11077 11078 11093 11141 11142
13513 13514
17607 17608 17109 17114 17115
14113 14607 14608
13113 13607 13608
12113 12607 12608
11113 11607 11608
Function
Level Filterconstant LowX HighX Level,desired Stopdifference Startdifference Demandoffset SenddesiredT Mexercise DHWpriority PfrostT PheatT Frostpr.T Ext.input Ext.mode CWconsump. Pulsevalue Preset
LowX HighX Inputtype Pulse Units
Filterconstant LowX HighX
Filterconstant LowX HighX
Filterconstant LowX HighX
Filterconstant LowX HighX
A333
A333.1A333.2A333.3
((
((
((
((
((
((
((
(((
(((
(((
(((
(((
(((
(((
(((
(((
((
((
((
((
((
((
((
((
((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
AQ076586461441en-010401
©Danfoss|2021.04|61
OperatingGuideECLComfort310,applicationA333
Parameterlist,applicationA333,Heating,continued
Home MENU
HolidayHoliday
Alarm
Influenceoverview
Sub-menu
Heating
Temp.monitor
Refilltank
S7pressure
S8pressure
S9pressure
S10pressure
Lowpressure
Alarmoverview Des.flowTInfluencesource
IDnos.
11147 11148 11149 11150 16614 16615 16617 14614 14615 14617 13614 13615 13617 12614 12615 12617 11614 11615 11617 15615 15617
Function
Upperdiff Lowerdiff Delay Lowesttemp. Alarmhigh Alarmlow Alarmtime-out Alarmhigh Alarmlow Alarmtime-out Alarmhigh Alarmlow Alarmtime-out Alarmhigh Alarmlow Alarmtime-out Alarmhigh Alarmlow Alarmtime-out
Alarmlow Alarmtime-out
A333
A333.1A333.2A333.3
(((
(((
(((
(((
(((
((
((
((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
62|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
Parameterlist,applicationA333,Commoncontroller
Home
MENU
Sub-menu
Commoncontroller
Time&date Inputoverview Log Outputoverride Keyfunctions
System
IDnos.
Function
Newapplication Application Factorysetting Copy Keyoverview ECLversion Extension Ethernet Portalconfig. M-busconfig. Energymeters Rawinputoverview Alarm Display Communication Language
A333
A333.1A333.2A333.3
(((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
((
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
AQ076586461441en-010401
©Danfoss|2021.04|63
OperatingGuideECLComfort310,applicationA333

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
)willalwaysshowyouwhere
Examples:
Heatingcircuit():
Circuitselector
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
64|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
AQ076586461441en-010401
)
©Danfoss|2021.04|65
OperatingGuideECLComfort310,applicationA333
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Examples:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
20.5
21.0
66|©Danfoss|2021.04
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
AQ076586461441en-010401
©Danfoss|2021.04|67
OperatingGuideECLComfort310,applicationA333

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
68|©Danfoss|2021.04
DamperOFF
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
AQ076586461441en-010401
©Danfoss|2021.04|69
OperatingGuideECLComfort310,applicationA333
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
70|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
AQ076586461441en-010401
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
©Danfoss|2021.04|71
OperatingGuideECLComfort310,applicationA333

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
72|©Danfoss|2021.04
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Actual(actualfloworpower)
Pexercise(pumpexercise)
Pexercise(pumpexercise)
Frostpr.T(frostprotectiontemperature)
Inputtype
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Motorpr.(motorprotection)—onlyA333.1,A333.2
Nz(neutralzone)
Retrytime
Change,duration
Changetime
Stab.time(stabilizationtime)
Chan.-overtime(change-overtime)
Alarmhandling
Max.pressure
Max.pressurediff.
Pressuredes.(A333.2/A333.3)
Pressuredes.
Pressurediff.
Time-out
Valvedelay
No.ofpumps
Wakeuplevel(A333.2/A333.3)
Sleeplevel(A333.2/A333.3)
Sleepmodetime(A333.2/A333.3)
Boost(A333.2/A333.3)
Voutmax.(A333.2/A333.3)
Voutmin.(A333.2/A333.3)
Tn(integrationtime)(A333.2/A333.3)
Nz(neutralzone)(A333.2/A333.3)
Td(Timederivative)(A333.2/A333.3)
Changeduration
Alarmhandling
Pressurediff.(A333.2/A333.3)
Voutmax.(A333.2/A333.3)
Voutmin.(A333.2/A333.3)
Tn(integrationtime)(A333.2/A333.3)
11022105
11022110
11093
1110984
11141
11142118
11174
1118793
11310103
11311104
11312104
11313104
11314103
11316105
11318108
11319108
1132195
11321107
11322103
11323109
11325
11326
1133098
1133198
1133298
1133399
12165101
12167102
12185101
12187101
12197101
12311106
12316
12322100
1316597
1316797
1318596
Factorysettingsincircuit(s)
1
77
82
117
118
92
111
111
111
23
AQ076586461441en-010401
©Danfoss|2021.04|73
OperatingGuideECLComfort310,applicationA333
SettingIDPage
Nz(neutralzone)(A333.2/A333.3)
Td(Timederivative)(A333.2/A333.3)
Pressurediff.
Alarmlow
Alarmtime-out
Filterconstant
Stopdifference(A333.2/A333.3)
Startdifference(A333.2/A333.3)
Level,desired(A333.2/A333.3)
LowX(A333.2/A333.3)
HighX(A333.2/A333.3)
Alarmhigh(A333.2/A333.3)
Alarmlow(A333.2/A333.3)
Alarmtime-out(A333.2/A333.3)
Inputtype(A333.2/A333.3)
Pulse(A333.2/A333.3)
Units(A333.2/A333.3)
LowX(A333.2/A333.3)
HighX(A333.2/A333.3)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Demandoffset
Totalstop
Mexercise(valveexercise)
Pre-stop(optimizedstoptime)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
DHWpriority(closedvalve/normaloperation)
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
1318797
1319797
13322107
15615131
15617131
16113113
16194
16195
16602
16607
16608
16614128
16615129
16617129
17109122
17114
17115
17607121
17608122
1x01185
1x01285
1x01386
1x01486
1x017116
1x02188
1x023116
1x02687
1x03179
1x03279
1x03379
1x03479
1x03580
1x03680
1x03781
1x052116
1x077
1x078
1x08581
1x093
1x111
1x11283
1x11383
Factorysettingsincircuit(s)
1
115
115
114
114
114
122
123
117
117
117
82
23
74|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
SettingIDPage
Filterconstant
Filterconstant(S7,S8,S9,S10)
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Xp(proportionalband)
Xp(proportionalband)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Min.act.time(min.activationtimegearmotor)
SenddesiredT
Pulsevalue
Preset
LowX
LowX(S7,S8,S9,S10)
HighX
HighX(S7,S8,S9,S10)
Alarmhigh
Alarmlow
Alarmtime-out
Position(A333.2/A333.3)
TimeLeft
Level(A333.2/A333.3)
CWconsump.(A333.2/A333.3)
Actual(A333.2/A333.3)
Pressure(S7,S8,S9,S10)
1x11391
1x113125
1x115
1x11683
1x117
1x11883
1x11982
1x147
1x148127
1x149128
1x150128
1x174
1x177
1x17878
1x17988
1x18493
1x18496
1x184100
1x18593
1x18693
1x18994
1x500116
1x513120
1x514
1x60791
1x607125
1x60892
1x608126
1x614130
1x615130
1x617130
Read-
out
Read-
out
Read-
out
Read-
out
Read-
out
Read-
out
Factorysettingsincircuit(s)
1
84
83
127
92
78
120
90
106
113
120
121
124
23
AQ076586461441en-010401
©Danfoss|2021.04|75
OperatingGuideECLComfort310,applicationA333

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
76|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
AQ076586461441en-010401
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
©Danfoss|2021.04|77
OperatingGuideECLComfort310,applicationA333
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
MENU>Settings>Flowtemperature
Temp.min.
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow
1x177
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
MENU>Settings>Flowtemperature
Temp.max.
1x178
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
78|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

5.3Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' .
Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit.
ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
1x031
Returntemperaturelimitation
HighlimitY2
LowlimitY1
Outdoortemp.
LowToutX2
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
HighToutX1
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
1x032
1x033
ThecorrespondingYcoordinateissetin'HighlimitY2'.
AQ076586461441en-010401
©Danfoss|2021.04|79
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
1x034
1x035
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Thereturnlimitisactiveabove50°C. Theinfluenceissetto-2.0. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby-2.0x2=-4.0degrees.
Normally,thissettingislowerthan0indistrictheatingsystemsto avoidatoohighreturntemperature.
Typically,thissettingis0inboilersystemsbecauseahigherreturn temperatureisacceptable(seealso'Infl.-min. ').
80|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
Example
1x036
1x037
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
AQ076586461441en-010401
©Danfoss|2021.04|81
OperatingGuideECLComfort310,applicationA333

5.4Flow/powerlimit

Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
HighlimitY2
LowlimitY1
Flow/power limitation
Desiredflow temp.
Flow/powerlimitation
LowToutX2
Outdoortemp.
HighToutX1
Limit
Time
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
SeeAppendix“ParameterIDoverview”
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
1x111
82|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
1x119
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
1x118
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
1x116
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
OFF:
Minor value:
Major value:
AQ076586461441en-010401
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Thedesiredtemperatureisadaptedquickly.
Thedesiredtemperatureisadaptedslowly.
©Danfoss|2021.04|83
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Flow/powerlimit
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Inputtype
ChoiceofM-bussignalfromenergymeternumber1...5.Onlypossible inECLComfort310.
OFF:
EM1...EM5:
NoM-bussignalacquired. Energymeternumber.
MENU>Settings>Flow/powerlimit
1x113
11109
FloworpowerlimitationisbasedonM-bussignal(ECLComfort310 controllersonly).
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Unitstotheleft:pulsevalue. Unitstotheright:actualandlimitationvalues.
Thevaluefromtheflowmeterisexpressedasmlorl. ThevaluefromtheenergymeterisexpressedasWh,kWh,MWh orGWh.
Thevaluesfortheactualflowandtheflowlimitationareexpressed asl/horm³/h.
Thevaluesfortheactualpowerandthepowerlimitationare expressedaskW,MWorGW.
1x115
Listforsettingrangeof'Units': ml,l/h l,l/h ml,m³/h l,m³/h Wh,kW kWh,kW kWh,MW MWh,MW MWh,GW GWh,GW
Example1:
'Units'(11115):
'Pulse'(11114):
l,m³/h 10
Eachpulserepresents10litresandtheflowisexpressedascubic meters(m³)perhour.
Example2:
'Units'(11115):
'Pulse'(11114):
kWh,kW(=kiloWatthour,kiloWatt) 1
Eachpulserepresents1kiloWatthourandthepoweris expressedinkiloWatt.
84|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333

5.5Optimization

MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
AQ076586461441en-010401
©Danfoss|2021.04|85
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
X Y #1#
=
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
86|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
-5°C
small
AQ076586461441en-010401
©Danfoss|2021.04|87
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
1x026
Example:OptimizationofComfortfrom07:00-22:00
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost protectionisstillactive,see'PfrostT' .
X #1# #2# #3# #4# #5#
Totalstop=OFF
Totalstop=ON
=
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
88|©Danfoss|2021.04
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
Summer,cut-out
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
AQ076586461441en-010401
©Danfoss|2021.04|89
OperatingGuideECLComfort310,applicationA333

5.6Controlparameters1

TheapplicationsA333.1andA333.2controlthemotorizedcontrol valveM1bymeansof3-pointcontrol.
TheapplicationA333.3controlstheM1bymeansofa0-10volt controlsignal.
ThemotorizedcontrolvalveM1isopenedgraduallywhentheflow temperatureS3islowerthanthedesiredflowtemperatureand viceversa.
3-pointcontrolledM1(A333.1andA333.2):
"Open"and"close"commandscomefromtheelectronicoutputsof theECLComfortcontrollerandcontrolthepositionofM1.
Thecommandsareexpressedas"Arrow-up"(open)and "Arrow-down"(close)anddisplayedattheM1symbol.
WhenthetemperatureatS3islowerthanthedesiredtemperature, shortopen-commandscomefromtheECLComfortcontrollerin ordertoopenM1morethanthemomentbefore.Bythis,theS3 temperaturealignswiththedesiredtemperature.
Oppositely,whenthetemperatureatS3ishigherthanthedesired temperature,shortclose-commandscomefromtheECLComfort controllerinordertocloseM1morethanthemomentbefore. Again,theS3temperaturealignswiththedesiredtemperature.
Neitheropen-commandsnorclose-commandswillcomeaslongas theflowtemperaturecorrespondstothedesiredtemperature.
0-10voltcontrolledM1(A333.3):
Acontrolvoltagebetween0and10voltcomesfromtheextension moduleECA32andcontrolsthepositionofM1.Thevoltageis expressedasa%valueanddisplayedattheM1symbol.
WhenthetemperatureatS3islowerthanthedesiredtemperature, thecontrolvoltageisgraduallyincreasedinordertoopenM1more thanthemomentbefore.Bythis,theS3temperaturealignswith thedesiredtemperature.
Thecontrolvoltageremainsonafixedvalueaslongastheflow temperaturecorrespondstothedesiredtemperature.
Oppositely,whenthetemperatureatS3ishigherthanthedesired temperature,thecontrolvoltageisgraduallydecreasedinorderto closeM1morethanthemomentbefore.Again,theS3temperature alignswiththedesiredtemperature.
90|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Controlparameters1
Position(A333.2/A333.3)
CircuitSettingrange
1
PositionofthemotorizedcontrolvalveM1isindicatedasa%value. A0-10voltsignalcomesfromapositionmeasuringinM1andisappliedto inputS11(ECA32).Thisinputvoltageisconvertedtothedisplayed%value. Accesstoconversion(scale)settings.
*)
2.0volt=0%,10.0volt=100%
-
Read-out
Factorysetting
Thepositionismeasuredbymeansofa0-10voltsignal. Themeasuredvoltagemustbeconvertedtoapositionvalueby thecontroller.
Thefollowingproceduresetsuptheconversion: Pushthedialtoseethegraphandenterthevaluesetsforthe2 inputvoltagesandrelatedpositionvalues. Positionvaluerange:0…100%
Thefactorysetvoltagevalues(2.0voltand10.0volt)canbe changedinthefollowingtwoseparatemenus"LowX"and"HighX" .
Factorysettings:2.0,0(=2.0V/0%)and10.0,100(=10.0V/100%)
Thismeansthatthe"Position"is0%at2.0Vand100%at10.0V. Typically,thehigherthevoltage,thehigherthedisplayedposition.
*)
=
X
Volt
=
Y
Position
Thisscalingmenuisalwaysdisplayed,regardlessapositionsignal isapplied.
Thepositionisindicatedas0whenthepositionsignalisnotapplied.
MENU>Settings>Controlparameters1
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
1x113
AQ076586461441en-010401
©Danfoss|2021.04|91
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Controlparameters1
LowX
Definitionofwhichvoltagevaluecorrespondstowhichpositionvalue. Thevoltage(asa0-10voltsignal)comesfromapositionmeasuringin M1andisappliedtoinputS11(ECA32).Thisinputvoltageisconvertedto displaya%valueforthepositionofM1. Seealso"Position"and"HighX" .
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters1
HighX
Definitionofwhichvoltagevaluecorrespondstowhichpositionvalue. Thevoltage(asa0-10voltsignal)comesfromapositionmeasuringin M1andisappliedtoinputS11(ECA32).Thisinputvoltageisconvertedto displaya%valueforthepositionofM1. Seealso"Position"and"LowX" .
1x607
=
X Y #1#
1x608
Volt
=
Position
=
LowX
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters1
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
=
X Y #1#
1x174
Volt
=
Position
=
HighX
92|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Controlparameters1
Motorpr.(motorprotection)—onlyA333.1,A333.2
CircuitSettingrange
1
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
OFF:
10...59:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation
OFF/10...59mOFF
Factorysetting
delayinminutes.
MENU>Settings>Controlparameters1
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
MENU>Settings>Controlparameters1
Tn(integrationtimeconstant)
11174
Recommendedforheatingsystemswithvariableload.
1x184
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters1
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
AQ076586461441en-010401
©Danfoss|2021.04|93
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Controlparameters1
Nz(neutralzone)
CircuitSettingrange
1
1...9K3K
11187
Factorysetting
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.Whentheactualflowtemperature iswithintheneutralzone,thecontrollerdoesnotactivatethe motorizedcontrolvalve.
MENU>Settings>Controlparameters1
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
1x189
SeeAppendix“ParameterIDoverview”
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
SettingexampleValuex20ms
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
94|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
5.7Controlparameters,refillpump(s)
Controlparametersforrefillwaterpump(s),applications A333.2/A333.3
TherefillwaterpumpsP3/P4canbespeedcontrolledbymeansof a0-10voltsignal.Thespeedcontrolsignalcomesfromtheoutput M2(terminals60and56)ontheECA32module.
AdesiredpressureatS10issetforthespeedcontrolprocedure. Thecontrolvoltageisexpressedasa%valueanddisplayedatthe M2symbol.
WhenthepressureatS10getstoolow,arefillpump(P3orP4)is switchedON.
Thecontrolvoltageisgraduallyincreasedinordertoincreasethe speedoftherefillwaterpump.Bythis,thepressurealignswith thedesiredpressure.
Thecontrolvoltageremainsonafixedvalueaslongasthepressure correspondstothedesiredpressure.
Thecontrolvoltagecanbelimitedtoamaximumandaminimum %value.
Sleepfunction:
Inordertoprotectarefillpumpagainstatoolowspeed,the"Sleep function"canbeused.
WhenthespeedcontrolvoltageforM2getslowerthan"Sleep level",thecontrolvoltageiscommandedto0%afteraperiod ("Sleepmodetime").Therefillpumpstops.
Afterelapseofthe"Sleepmodetime"andacontinueddemandfor refill,thecontrolvoltageiscommandedto"Wake-uplevel"and startstherefillpump.A"Boost"canbeaddedtothe"Wake-up level".
AQ076586461441en-010401
©Danfoss|2021.04|95
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Controlparameters,refillpump(s)
Pressuredes.(A333.2/A333.3)
CircuitSettingrange
1
SettingofdesiredpressureatS10inordertospeedcontroltherefillpump(s) P3/P4.
0.2-25.0:
SetthedesiredpressureatS10(inbar)
0.2...25.0bar3.0bar
11321
Factorysetting
=
X Y #1#
#2# #3# #4# #5#
#6#
Time
=
Pressure
=
Pressuredesired
=
Actualpressure
=
Pressuredifference
=
Neutralzone,Nz
=
Refillwaterpump
=
Speedcontrolsignal(0-10V)
MENU>Settings>Controlparameters,refillpump(s)
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
Theparameter"Pressuredes. "isalsousedinapplicationA333.1for settingdesiredpressureforON/OFFcontrolofrefillpump(s)P3/P4.
1x184
96|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Controlparameters,refillpump(s)
Tn(integrationtime)(A333.2/A333.3)
CircuitSettingrange
1
SettheintegrationtimeforthecontrolofthepressureatS10.
Lowvalue:
Controllerreactsfast,butwithlessstability
1...999sec25sec
Factorysetting
Highvalue:Controllerreactsslowandwithhigherstability
MENU>Settings>Controlparameters,refillpump(s)
Nz(neutralzone)(A333.2/A333.3)
CircuitSettingrange
1
SettheacceptablepressuredeviationatS10. Whentheactualpressureiswithintheneutralzone,thecontrollerdoes notchangetherefillpumpspeed.
0.1...2.0bar0.4bar
Factorysetting
Lowvalue:Alowvariationinpressureisacceptable Highvalue:Ahighvariationinpressureisacceptable
13185
13187
Theneutralzoneissymmetricalaroundthedesiredpressurevalue,i.e. halfthevalueisaboveandhalfthevalueisbelowthispressure.
MENU>Settings>Controlparameters,refillpump(s)
Td(Timederivative)(A333.2/A333.3)
CircuitSettingrange
1
TheTdrelatedfunctioncanavoidatooaggressivereactioninthespeed controlprocedure.
0:
Lowvalue:
Highvalue:
Noinfluence Minorinfluence Majorinfluence
0...250sec0sec
Factorysetting
MENU>Settings>Controlparameters,refillpump(s)
Voutmax.(A333.2/A333.3)
CircuitSettingrange
1
Theoutputvoltageforcontrollingthespeedoftherefillpumpcanbelimited toamaximumvalue. Seealso"Voutmin" .
0-100:
Thevaluein%expressesthemaximumvoltage
0...100%100%
Factorysetting
forcontrollingtheanalogueoutputforthespeed controloftherefillpump.
13197
13165
Example:
Asettingof60%meansthattheoutputvoltagewillbe6voltasa maximum.
Thesettingof"V.outmin"haspriorityover"V.outmax" .
AQ076586461441en-010401
©Danfoss|2021.04|97
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Controlparameters,refillpump(s)
Voutmin.(A333.2/A333.3)
CircuitSettingrange
1
Theoutputvoltageforcontrollingthespeedoftherefillpumpcanbelimited toaminimumvalue. Seealso"Voutmax" .
0-100:
Thevaluein%expressesthemaximumvoltagefor
0...100%0%
Factorysetting
controllingtheanalogueoutputforthespeedcontrol oftherefillpump.
MENU>Settings>Controlparameters,refillpump(s)
Sleeplevel(A333.2/A333.3)
CircuitSettingrange
1
Whenthespeedcontrolsignalgetsbelowthe"Sleeplevel"value,thespeed willbesetto0(zero)%afterelapseof"Sleepmodetime". Therefillpumpstops(goesintosleepmode). Thesetvalueisalsothespeedlevelatanewrefillprocedure. Thisfunctionprotectstherefillpumpagainstlowspeed. Seealso:"Sleepmodetime"and"Wakeuplevel" .
OFF:
1-100:
Thesleepfunctionisdisabled Thesleepfunctionisenabled
OFF/1...100%
Factorysetting
13167
11331
20%
Example:
Asettingof15%meansthattheoutputvoltagewillbe1.5voltasa minimum.
Thesettingof"V.outmin"haspriorityover"V.outmax" .
MENU>Settings>Controlparameters,refillpump(s)
Sleepmodetime(A333.2/A333.3)
CircuitSettingrange
1
The"Sleepmodetime"determinesadelayedstopoftherefillpumpattoo lowspeed. Seealso:"Sleeplevel"and"Wakeuplevel" .
0-300:
Setthesleepmodetime(inseconds)
0...300sec10sec
Factorysetting
=
X Y #1#
#2# #3# #4#
11332
Time
=
Speedcontrolsignal(0-10V)(%))
=
Actualcontrolsignal
=
Sleeplevel
=
Wake-uplevel
=
Sleepmodetime
98|©Danfoss|2021.04
AQ076586461441en-010401
OperatingGuideECLComfort310,applicationA333
MENU>Settings>Controlparameters,refillpump(s)
Wakeuplevel(A333.2/A333.3)
CircuitSettingrange
1
Afterelapseofthe"Sleepmode"timeandacontinuedrefilldemand,the refillwaterpumprestartswithaspeedlevelasthesetvalue. Seealso:"Sleeplevel"and"Sleepmodetime" .
0-100:
Settherestartspeedlevel
0...100%40%
MENU>Settings>Controlparameters,refillpump(s)
Boost(A333.2/A333.3)
CircuitSettingrange
1
The"Wake-uplevel"canbeincreasedwitha%value.
0-100:
Settheboostlevel
0...100%5%
11330
Factorysetting
11333
Factorysetting
Example:
"Wake-uplevel"=40%
"Boost"=15%
Result:Theincreased"Wake-uplevel"=40x1.15=46%
AQ076586461441en-010401
©Danfoss|2021.04|99
OperatingGuideECLComfort310,applicationA333

5.8Controlparameters,circulationpump(s)

Controlparametersforcirculationpump(s),applications A333.2/A333.3
ThecirculationpumpsP1/P2canbespeedcontrolledbymeansof a0-10voltsignal.Thespeedcontrolsignalcomesfromtheoutput M3(terminals61and56)ontheECA32module.
AdesiredpressuredifferencebetweenS9andS10issetforthe speedcontrolprocedure.
Thecontrolvoltageisexpressedasa%valueanddisplayedatthe M3symbol.
Whenthepressuredifferencegetslowerthanthedesiredpressure difference,thecontrolvoltageisgraduallyincreasedinorderto increasethespeedofthecirculationpumpmorethanthemoment before.Bythis,thepressuredifferencealignswiththedesired pressuredifference.
Thecontrolvoltageremainsonafixedvalueaslongasthepressure differencecorrespondstothedesiredpressuredifference.
Thecontrolvoltagecanbelimitedtoamaximum.andaminimum %value.
MENU>Settings>Controlparameters,circulationpump(s)
Pressurediff.(A333.2/A333.3)
CircuitSettingrange
1
SettingofdesiredpressuredifferencebetweenS9andS10inordertospeed controlthecirculationpump(s)P1/P2.
0.1-5.0:
SetthedesiredpressuredifferencebetweenS9and
0.1...5.0bar1.5bar
S10(inbar)
12322
Factorysetting
=
X Y #1#
#2# #3# #4#
Time
=
Pressure
=
Pressurediff.,desired
=
Actualpressuredifference
=
Neutralzone,Nz
=
Speedcontrolsignal(0-10V)
100|©Danfoss|2021.04
AQ076586461441en-010401
Loading...