Danfoss A266 Operating guide

OperatingGuide
ECLComfort210/296/310,applicationA266

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................14
2.4Placingthetemperaturesensors................................19
2.5Electricalconnections.............................................21
2.6InsertingtheECLApplicationKey..............................30
2.7Checklist............................................................37
2.8Navigation,ECLApplicationKeyA266.........................38
3.0Dailyuse.........................................................58
3.1Howtonavigate...................................................58
3.2Understandingthecontrollerdisplay..........................59
3.3Ageneraloverview:Whatdothesymbolsmean?...........63
3.4Monitoringtemperaturesandsystem
components........................................................64
3.5Influenceoverview................................................65
3.6Manualcontrol.....................................................66
3.7Schedule............................................................67
4.0Settingsoverview............................................68
5.0Settings...........................................................71
5.1IntroductiontoSettings..........................................71
5.2Flowtemperature..................................................72
5.3Roomlimit..........................................................75
5.5Flow/powerlimit.................................................83
5.6Optimization........................................................88
5.7Controlparameters................................................95
5.8Application.......................................................102
5.9Heatcut-out......................................................110
5.10Alarm..............................................................113
5.11Alarmoverview..................................................119
5.12Anti-bacteria......................................................120
6.0Commoncontrollersettings............................122
6.1Introductionto‘Commoncontrollersettings’..............122
6.2Time&Date.......................................................123
6.3Holiday............................................................124
6.4Inputoverview...................................................126
6.5Log.................................................................127
6.6Outputoverride..................................................128
6.7Keyfunctions.....................................................129
6.8System.............................................................131
7.0Miscellaneous................................................138
7.1ECA30/31setupprocedures.................................138
7.2Overridefunction................................................146
7.3Severalcontrollersinthesamesystem......................149
7.4Frequentlyaskedquestions....................................152
7.5Definitions........................................................155
7.6Type(ID6001),overview.......................................159
7.7Automatic/manualupdateoffirmware.....................160
7.8ParameterIDoverview..........................................161
©Danfoss|2021.06AQ156586461753en-010601|1
OperatingGuideECLComfort210/296/310,applicationA266

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA266 (ordercodeno.087H3800).
TheECLApplicationKeyA266contains4subtypes,allapplicablein ECLComfort210,296and310:
A266.1:HeatingandDHW
A266.2:HeatingandadvancedDHW
A266.9:HeatinginclusivepressuremonitoringandDHW. Returntemperaturemonitoringonheatingside.
A266.10:HeatingandDHW.Returntemperaturemonitoringon heatingside.
TheA266applicationkeyalsocontainsaFloor(Screed)Drying Program.Seeseparatedocumentation.(InEnglishandGerman languageonly).
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort210for basicsolutionsandinECLComfort296and310foradvanced solutions,forexampleM-bus,ModbusandEthernet(Internet) communication.
TheapplicationKeyA266complieswithECLComfort210,ECL Comfort296andECLComfort310controllersasofsoftware version1.11(visibleatstart-upofthecontrollerandin'Common controllersettings'in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe connectedandthebuilt-inroomtemperaturesensorcanbe utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O moduleECA32(ordercodeno.087H3202)canbeusedforextra datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool". Navigation:Danfoss.com>Serviceandsupport>Downloads> Tools>ECLTool.TheURLis:
https://www.danfoss.com/en/service-and-support/downloads
TheInternalI/OmoduleECA32isplacedinthebasepartforECL Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volta.c.(087H3220)
forECLComfort296,230volta.c.(087H3240)
forECLComfort310,230volta.c.and24volta.c(087H3230)
AdditionaldocumentationforECLComfort210,296and310, modulesandaccessoriesisavailableonhttp://danfoss.com/.
DocumentationforECLPortal:Seehttps://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AQ156586461753en-010601
©Danfoss|2021.06|3
OperatingGuideECLComfort210/296/310,applicationA266
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
4|©Danfoss|2021.06
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
2
Circuit2Parameterno.
174
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
AQ156586461753en-010601
©Danfoss|2021.06|5
OperatingGuideECLComfort210/296/310,applicationA266

2.0Installation

2.1Beforeyoustart

TheECLApplicationkeyA266contains4subtypes,A266.1, A266.2,A266.9andA266.10whicharealmostidentical.
TheapplicationA266.1isveryflexible.Thesearethebasic principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.Theflowtemperaturesensor(S3)isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredroomtemperature). InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperaturedoesnotequalthedesired roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Thecirculationpump,P2,isONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit thefloworenergytoasetmaximumvalue.Furthermorethe limitationcanbeinrelationtotheoutdoortemperature.Typically, thelowertheoutdoortemperature,thehighertheacceptedflow/ power.WhentheA266.1isusedinanECLComfort310theflow/ energysignalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
DHW(circuit2):
IfthemeasuredDHWtemperature(S4)islowerthanthedesired DHWtemperature,themotorizedcontrolvalve(M1)isopened graduallyandviceversa.
Thereturntemperature(S6)canbelimitedtoafixedvalue.
TypicalA266.1application:
M1,M2=3–point/0–10V
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296 /310
S1
S2
S3
S4
S5
S6
S7
P1
P2
M1
M2
A1
V1
V2
ElectroniccontrollerECLComfort210,296or310
Outdoortemperaturesensor
(Optional)Roomtemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)DHWreturntemperaturesensor,circuit2
(Optional)Flow/energymeter(pulsesignal)
Circulationpump,DHW,circuit2
Circulationpump,heating,circuit1
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
Alarm
Motorizedcontrolvalve(0–10V) (ECLComfort310+ECA32only)
Motorizedcontrolvalve(0–10V) (ECLComfort310+ECA32only)
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredDHWtemperature).
6|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
IfthedesiredDHWtemperaturecannotbereached,theheating circuitcanbeclosedgraduallytoallowmoreenergytotheDHW circuit.
A266.1,ingeneral:
AlarmA1(=relay4)canbeactivatediftheactualflowtemperature differsfromthedesiredflowtemperature.
HolidayprogramsarepresentforHeatingandDHW.Besides,a holidayprogramispresentfortheentirecontroller.
WhenthesubtypeA266.1hasbeenuploaded,theECLComfort controllerstartsinmanualmode.Thiscanbeusedforcheckingthe controlledcomponentsforcorrectfunctionality.
AQ156586461753en-010601
©Danfoss|2021.06|7
OperatingGuideECLComfort210/296/310,applicationA266
TheapplicationA266.2isveryflexible.Thesearethebasic principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.Theflowtemperaturesensor(S3)isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredroomtemperature). InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
TypicalA266.2application:
M2=3–point/0–10V
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Ifthemeasuredroomtemperaturedoesnotequalthedesired roomtemperature,thedesiredflowtemperaturecanbeadjusted. Thecirculationpump,P2,isONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit thefloworenergytoasetmaximumvalue.Furthermorethe limitationcanbeinrelationtotheoutdoortemperature.Typically, thelowertheoutdoortemperature,thehighertheacceptedflow/ power.WhentheA266.2isusedinanECLComfort310theflow/ energysignalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
DHW(circuit2):
TheDHWtemperatureatS4ismaintainedat‘Comfort’levelata DHWdraw-off(DHWtapping)(theflowswitch(S8)isactivated). IfthemeasuredDHWtemperature(S4)islowerthanthedesired DHWtemperature,themotorizedcontrolvalve(M1)isopened graduallyandviceversa.
TheDHWtemperaturecontrolisinrelationtoactualsupply temperature(S6).Inordertocompensateforthereactiontime,the motorizedcontrolvalvecanbepre-activatedatthestartofaDHW draw-off(DHWtapping).Anidletemperaturecanbemaintainedat eitherS6orS4whenthereisnodraw-off(DHWtapping).
Listofcomponents:
ECL210/296 /310
S1
S2
S3
S4
S5
S6
S7
S8
P1
P2
M1
M2
A1
V2
ElectroniccontrollerECLComfort210,296or310
Outdoortemperaturesensor
(Optional)Roomtemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1,circuit 2orbothcircuits
(Optional)Supplytemperaturesensor,circuit2
(Optional)Flow/energymeter(pulsesignal)
Flowswitch,DHWdraw-off,circuit2
Circulationpump,DHW,circuit2
Circulationpump,heating,circuit1
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit1 Alternative:Thermoactuator(DanfosstypeABV
Alarm
Motorizedcontrolvalve(0–10V) (ECLComfort310+ECA32only)
Thereturntemperature(S5)canbelimitedtoafixedvalue.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredDHWtemperature).
8|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
IfthedesiredDHWtemperaturecannotbereached,theheating circuitcanbeclosedgraduallytoallowmoreenergytotheDHW circuit.
A266.2,ingeneral:
AlarmA1(=relay4)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow temperature
ifthetemperatureatS3exceedsanalarmvalue
HolidayprogramsarepresentforHeatingandDHW.Besides,a holidayprogramispresentfortheentirecontroller.
IfthetemperatureatS3exceedsthealarmvalue'Max.flowT',the circulationpumpP2isswitchedOFFafterelapseofthe'Delay' . P2isswitchedONagainwhenthetemperatureatS3getsbelow alarmvalue.
WhenthesubtypeA266.2hasbeenuploaded,theECLComfort controllerstartsinmanualmode.Thiscanbeusedforcheckingthe controlledcomponentsforcorrectfunctionality.
AQ156586461753en-010601
©Danfoss|2021.06|9
OperatingGuideECLComfort210/296/310,applicationA266
TheapplicationA266.9isveryflexible.Thesearethebasic principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.Theflowtemperaturesensor(S3)isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredroomtemperature). InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Thecirculationpump,P2,isONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Thesecondaryreturntemperature(S2)isusedformonitoring.The pressuremeasuring(S7)isusedtoactivateanalarmiftheactual pressureishigherorlowerthanthechosensettings.
WhentheA266.9isusedinanECLComfort310,aconnected floworenergymeterbasedonM-bussignalcanlimittheflowor energytoasetmaximumvalue.Furthermorethelimitationcanbe inrelationtotheoutdoortemperature.Typically,thelowerthe outdoortemperature,thehighertheacceptedflow/power.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
DHW(circuit2):
IfthemeasuredDHWtemperature(S4)islowerthanthedesired DHWtemperature,themotorizedcontrolvalve(M1)isopened graduallyandviceversa.IfthedesiredDHWtemperaturecannot bereached,theheatingcircuitcanbeclosedgraduallytoallow moreenergytotheDHWcircuit.
ThereturntemperatureS6canmeasure,formonitoringpurpose, thereturntemperatureonthesecondaryside.Analternative positionforS6canbeinthereturnontheprimarysideinorderto limitthereturntemperaturetoafixedvalue.
TypicalA266.9application:
M1,M2=3–point/0–10V
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296
ElectroniccontrollerECLComfort210,296or310
/310 S1
S2
Outdoortemperaturesensor
(Optional)Returntemperaturesensor,circuit1,for monitoring
S3
S4
S5
S6
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)Returntemperaturesensor,secondaryside, circuit2.Alternativeposition:Return,primaryside
S7
S8
P1
P2
M1
M2
A1
V1
(Optional)Pressuretransmitter,circuit1
(Optional)Alarminput
Circulationpump,DHW,circuit2
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
Alarm
Motorizedcontrolvalve(0–10V) (ECLComfort310+ECA32only)
V2
Motorizedcontrolvalve(0–10V) (ECLComfort310+ECA32only)
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredDHWtemperature).
IfthedesiredDHWtemperaturecannotbereached,theheating circuitcanbeclosedgraduallytoallowmoreenergytotheDHW circuit.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
10|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
A266.9,ingeneral:
AlarmA1(=relay4)canbeactivated:
ifthetemperatureatS3exceedsanalarmvalue
ifthepressureatS7isnotinsideanacceptablepressurerange
ifthealarminputS8isactivated
IfthetemperatureatS3exceedsthealarmvalue'Max.flowT',the circulationpumpP2isswitchedOFFafterelapseofthe'Delay' . P2isswitchedONagainwhenthetemperatureatS3getsbelow alarmvalue.
WhenthesubtypeA266.9hasbeenuploaded,theECLComfort controllerstartsinscheduledmode.
AQ156586461753en-010601
©Danfoss|2021.06|11
OperatingGuideECLComfort210/296/310,applicationA266
TheapplicationA266.10isveryflexible.Thesearethebasic principles:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.Theflowtemperaturesensor(S3)isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredroomtemperature). InSavingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Thecirculationpump,P2,isONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Thesecondaryreturntemperature(S2)isusedformonitoring. Aconnectedfloworenergymeterbasedonpulses(S7)canlimitthe floworenergytoasetmaximumvalue.Furthermorethelimitation canbeinrelationtotheoutdoortemperature.Typically,thelower theoutdoortemperature,thehighertheacceptedflow/power.
WhentheA266.10isusedinanECLComfort310theflow/energy signalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
DHW(circuit2):
IfthemeasuredDHWtemperature(S4)islowerthanthedesired DHWtemperature,themotorizedcontrolvalve(M1)isopened graduallyandviceversa.IfthedesiredDHWtemperaturecannot bereached,theheatingcircuitcanbeclosedgraduallytoallow moreenergytotheDHWcircuit.
ThereturntemperatureS6canmeasure,formonitoringpurpose, thereturntemperatureonthesecondaryside.Analternative positionforS6canbeinthereturnontheprimarysideinorderto limitthereturntemperaturetoafixedvalue.
TypicalA266.10application:
M1,M2=3–point/0–10V
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296
ElectroniccontrollerECLComfort210,296or310
/310 S1
S2
Outdoortemperaturesensor
(Optional)Returntemperaturesensor,circuit1,for monitoring
S3
S4
S5
S6
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
(Optional)Returntemperaturesensor,circuit1
(Optional)Returntemperaturesensor,secondaryside, circuit2.Alternativeposition:Return,primaryside
S7
S8
P1
P2
M1
M2
A1
V1
(Optional)Flow/energymeter(pulsesignal)
(Optional)Alarminput
Circulationpump,DHW,circuit2
Circulationpump,heating,circuit1
Motorizedcontrolvalve,circuit2
Motorizedcontrolvalve,circuit1
Alarm
Motorizedcontrolvalve(0–10V) (ECLComfort310+ECA32only)
V2
Motorizedcontrolvalve(0–10V) (ECLComfort310+ECA32only)
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredDHWtemperature).
IfthedesiredDHWtemperaturecannotbereached,theheating circuitcanbeclosedgraduallytoallowmoreenergytotheDHW circuit.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
12|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
A266.10,ingeneral:
AlarmA1(=relay4)canbeactivated:
ifthetemperatureatS3exceedsanalarmvalue
ifthealarminputS8isactivated
IfthetemperatureatS3exceedsthealarmvalue'Max.flowT',the circulationpumpP2isswitchedOFFafterelapseofthe'Delay' . P2isswitchedONagainwhenthetemperatureatS3getsbelow alarmvalue.
WhenthesubtypeA266.10hasbeenuploaded,theECLComfort controllerstartsinscheduledmode.
A266,ingeneral:
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto oneECLcontrollerinordertocontroltheECLcontrollerremotely.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout heatingdemandcanbearranged.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL 485businordertoutilizecommonoutdoortemperaturesignal, timeanddatesignals.TheECLcontrollersintheECL485system canworkinmaster-slavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdata(ECLComfort310)canfurthermorebetransferred totheModbuscommunication.
AlarmA1(=relay4)canbeactivated:
ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview).
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
AQ156586461753en-010601
©Danfoss|2021.06|13
OperatingGuideECLComfort210/296/310,applicationA266

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
14|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ156586461753en-010601
©Danfoss|2021.06|15
OperatingGuideECLComfort210/296/310,applicationA266
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
16|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
AQ156586461753en-010601
©Danfoss|2021.06|17
OperatingGuideECLComfort210/296/310,applicationA266
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
18|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
AQ156586461753en-010601
©Danfoss|2021.06|19
OperatingGuideECLComfort210/296/310,applicationA266
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
20|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
AQ156586461753en-010601
©Danfoss|2021.06|21
OperatingGuideECLComfort210/296/310,applicationA266
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
22|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
AQ156586461753en-010601
©Danfoss|2021.06|23
OperatingGuideECLComfort210/296/310,applicationA266
2.5.3Electricalconnections,safetythermostats,ingeneral
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
24|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
SeetheInstallationGuide(deliveredwiththeapplicationkey)for sensorandinputconnections.
Sensor
S1
S2
S3
S4
S5Returntemperaturesensor
(S5)
S6
(S6)
S7
S8
Description
Outdoortemperaturesensor*
A266.1,A266.2: Roomtemperaturesensor** Alternative:ECA30/31
A266.9,A266.10: Returntemperaturesensor (heating,secondaryside)
Flowtemperaturesensor*** (heating)
Flowtemperaturesensor*** (DHW)
(heating)
A266.2: Returntemperaturesensor, alternativepositions
A266.1,A266.9,A266.10: Returntemperaturesensor (DHW)
A266.2: Supplytemperaturesensor
A266.9,A266.10: Returntemperaturesensor, alternativeposition
A266.1,A266.2,A266.10: Flow/heatmeter(pulsesignal)
A266.9: Pressuretransmitter,0-10Vor 4-20mA
A266.2: Flowswitch
A266.9,A266.10: Alarmcontact/switch
Recommended type
ESMT
A266.1,A266.2: ESM-10
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
*
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
**
Onlyforroomtemperaturesensorconnection.Theroom temperaturesignalcanalsobeavailablefromaRemote ControlUnit(ECA30/31).SeetheInstallationGuide (deliveredwiththeapplicationkey)forspecificconnections.
***
Theflowtemperaturesensormustalwaysbeconnected inordertohavethedesiredfunctionality.Ifthesensoris notconnectedorthecableisshort-circuited,themotorized controlvalvecloses(safetyfunction).
AQ156586461753en-010601
©Danfoss|2021.06|25
OperatingGuideECLComfort210/296/310,applicationA266
Connectionofflowmeter
SeetheInstallationGuide(deliveredwiththeapplicationkey).
Connectionofflowswitchoralarmcontact/switch
ThealarmcontactactsasaNormallyClosed(NC)contact.The set-upcanbechangedtoreactonaNormallyOpen(NO)contact. SeeCircuit1>MENU>Alarm>Digital>Alarmvalue:
0=AlarmforNOcontact 1=AlarmforNCcontact
Connectionofpressuretransmitter
ScaleforconversionofvoltagetopressureissetintheECLComfort. Thepressuretransmitterispoweredwith12-24Vd.c. Outputtypes:0-10Vor4-20mA. 4-20mAsignalisconvertedtoa2-10Vsignalbymeansofa500 ohm(0,5W)resistor.
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
26|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
2.5.5Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
AQ156586461753en-010601
©Danfoss|2021.06|27
OperatingGuideECLComfort210/296/310,applicationA266
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
28|©Danfoss|2021.06
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
AQ156586461753en-010601
©Danfoss|2021.06|29
OperatingGuideECLComfort210/296/310,applicationA266

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
30|©Danfoss|2021.06
ECLComfort296
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ156586461753en-010601
©Danfoss|2021.06|31
OperatingGuideECLComfort210/296/310,applicationA266
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
32|©Danfoss|2021.06
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
AQ156586461753en-010601
©Danfoss|2021.06|33
OperatingGuideECLComfort210/296/310,applicationA266
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
34|©Danfoss|2021.06
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
AQ156586461753en-010601
©Danfoss|2021.06|35
OperatingGuideECLComfort210/296/310,applicationA266
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
36|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
AQ156586461753en-010601
©Danfoss|2021.06|37
OperatingGuideECLComfort210/296/310,applicationA266

2.8Navigation,ECLApplicationKeyA266

Navigation,A266.1,circuit1and2
Home
IDno.
MENU
ScheduleSelectableSelectable
Settings
Flowtemperature
11178 11177 11004
Roomlimit
Returnlimit
Flow/powerlimitActualActual
Optimization
11015 11182 11183
11031 11032 11033 11034 11035 11036 11037 11085 11029 11028
11119
11117
11118
11116
11112
11113
11109
11115
11114
11011
11012
11013
11014
11026
11020
11021
11179
11043
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve Temp.max. Temp.min. DesiredT
Adapt.time Infl.-max. Infl.-min.
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Adapt.time
Filterconstant
Inputtype
Units
Pulse
Autosaving
Boost
Ramp
Optimizer
Pre-stop
Basedon
Totalstop
Summer,cut-out
Paralleloperation
IDno.
12178 12177
12030
12035 12036 12037 12085
12111
12112
12113
12109
12115
12114
Function
Temp.max. Temp.min.
Limit
Infl.-max. Infl.-min. Adapt.time Priority
Limit
Adapt.time
Filterconstant
Inputtype
Units
Pulse
38|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.1,circuit1andcircuit2continued
Home
MENU
Settings
HolidaySelectableSelectable
Alarm
Controlpar.
Application
Heatcut-out
Anti-bacteria
Temp.monitoring
AlarmoverviewSelectableSelectable
IDno.
11174 11184 11185 11186 11187 11189 11024 11010 11017 11050 11500 11022 11023 11052 11077 11078 11040 11093 11141
11142 11393 11392 11179 11395 11397 11396 11398 11399
11147
11148 11149 11150
Circuit1,HeatingCircuit2,DHW
Function
Motorpr. Xp Tn Mrun Nz Min.act.time Actuator ECAaddr.
Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority
PfrostT PheatT Ppost-run Frostpr.T
Ext.input
Ext.mode Sum.start,day Sum.start,month Summer,cut-out
Summer,filter Winterstart,day Win.start,month Winter,cut-out
Winter,filter
Upperdifference Lowerdifference Delay Lowesttemp.
IDno.
12173 12174 12184 12185 12186 12187 12189 12024
12500 12022 12023
12077 12078 12040 12093 12141 12142
12147 12148 12149 12150
Function
Autotuning Motorpr. Xp Tn Mrun Nz Min.act.time Actuator
SenddesiredT Pexercise Mexercise
PfrostT PheatT Ppost-run Frostpr.T
Ext.input
Ext.mode
Day Starttime Duration
DesiredT
Upperdifference Lowerdifference Delay Lowesttemp.
AQ156586461753en-010601
©Danfoss|2021.06|39
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.1,circuit1andcircuit2continued
Home
MENU
InfluenceoverviewDes.flowTReturnlim.Returnlim.
IDno.
Circuit1,HeatingCircuit2,DHW
Function
Roomlim. Parallelpriority Flow/powerlim.Flow/powerlim. HolidayHoliday Ext.overrideExt.override ECAoverrideAnti-bacteria Boost Ramp
Slave,demand Heatingcut-out DHWpriority
SCADAoffsetSCADAoffset Floordry.,active
IDno.
Function
40|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.1,Commoncontrollersettings
Home
MENU
Time&Date
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
FloordryingFunctionalheating
OutdoorTLogtoday RoomT&desiredLogyesterday
HeatingflowT&des. DHWflowT&des. HeatreturnT&limit DHWreturnT&limit
Curingheating
IDno.
Commoncontrollersettings
Function
Selectable
OutdoorT Outdooracc.T RoomT
HeatflowT DHWflowT HeatreturnT
DHWreturnT
Log2days Log4days
M1
P1 V1 M2
P2 V2 A1
DesiredflowT X1 X2 X3 X4
DesiredflowT X5 X6 X7 X8
RampX5–X6 RampX7–X8
Max.pwr.failure Afterpowerfail. Prog.execution
Appl.continue
AQ156586461753en-010601
©Danfoss|2021.06|41
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.1,Commoncontrollersettingscontinued
Home
MENU
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet(ECLComfort296and310 only)
Portalconfig (ECLComfort296and310only)
Function
Usersettings
Gotofactory To
Systemsettings Usersettings Startcopying
Codeno. Hardware
Software Buildno. Serialno. Productiondate
Addresstype
ECLportal Portalstatus
M-busconfig (ECLComfort296and310only)
EnergyMeters (ECLComfort296and310only)
Rawinputoverview
Sensoroffset Alarm Display
Communication
Language
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210) S1-S10(ECLComfort310) S1-S18(ECLComfort310withECA32)
S1...S10offset
32:
Tsensordefect
60058
Backlight
60059
Contrast
38
Modbusaddr.
2048
ECL485addr.
39
Baud
2150
Servicepin
2151
Ext.reset
2050
Language
42|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.2,circuit1and2
Home
IDno.
MENU
ScheduleSelectableSelectable
Settings
Flowtemperature
11178 11177 11004
Roomlimit
Returnlimit
Flow/powerlimitActualActual
Optimization
11015 11182 11183
11031 11032 11033 11034 11035 11036 11037 11085 11029 11028
11119
11117
11118
11116
11112
11113
11109
11115
11114
11011
11012
11013
11014
11026
11020
11021
11179
11043
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve Temp.max. Temp.min. DesiredT
Adapt.time Infl.-max. Infl.-min.
HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority DHW,ret.Tlimit Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Adapt.time
Filterconstant
Inputtype
Units
Pulse
Autosaving
Boost
Ramp
Optimizer
Pre-stop
Basedon
Totalstop
Summer,cut-out
Paralleloperation
IDno.
12178 12177
12030
12035 12036 12037 12085
12111
12112
12113
12109
12115
12114
Function
Temp.max. Temp.min.
Limit
Infl.-max. Infl.-min. Adapt.time Priority
Limit
Adapt.time
Filterconstant
Inputtype
Units
Pulse
AQ156586461753en-010601
©Danfoss|2021.06|43
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.2,circuit1andcircuit2continued
Home
MENU
Settings
HolidaySelectableSelectable
Controlpar.
Application
Heatcut-out
Anti-bacteria
IDno.
11174
11184 11185 11186 11187
11189 11024 11010 11017 11050 11500 11022 11023 11052 11077 11078 11040 11093 11141
11142 11393 11392 11179 11395 11397 11396 11398 11399
Circuit1,HeatingCircuit2,DHW
Function
Motorpr. Xp Tn Mrun Nz
Min.act.time Actuator
ECAaddr.
Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority
PfrostT PheatT Ppost-run Frostpr.T
Ext.input
Ext.mode Sum.start,day Sum.start,month Summer,cut-out
Summer,filter Winterstart,day Win.start,month Winter,cut-out
Winter,filter
IDno.
12173 12174
12185 12186 12187 12097 12096 12094 12095 12189 12024
12500 12022 12023
12077 12078 12040 12093 12141 12142
Function
Autotuning Motorpr.
Xpactual Tn Mrun Nz
SupplyT(idle) Tn(idle) Opentime
Closetime Min.act.time Actuator
SenddesiredT Pexercise Mexercise
PfrostT PheatT Ppost-run Frostpr.T
Ext.input
Ext.mode
Day Starttime Duration
DesiredT
44|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.2,circuit1andcircuit2continued
Home
MENU
Alarm
InfluenceoverviewDes.flowT
Temp.monitoring
Max.temperature
AlarmoverviewSelectableSelectable
IDno.
11147
11148 11149 11150
11079 11080
Circuit1,HeatingCircuit2,DHW
Function
Upperdifference Lowerdifference Delay Lowesttemp.
Max.flowT Delay
Returnlim.Returnlim. Roomlim. Parallelpriority Flow/powerlim.Flow/powerlim. HolidayHoliday Ext.overrideExt.override ECAoverrideAnti-bacteria Boost Ramp
Slave,demand Heatingcut-out DHWpriority
SCADAoffsetSCADAoffset Floordry.,active
IDno.
12147 12148 12149 12150
Function
Upperdifference Lowerdifference Delay Lowesttemp.
AQ156586461753en-010601
©Danfoss|2021.06|45
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.2,Commoncontrollersettings
Home
MENU
Time&Date
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
FloordryingFunctionalheating
OutdoorTLogtoday RoomT&desiredLogyesterday
Heatingflow&des. DHWflow&des. HeatreturnT&limit DHWreturnT&limit
SupplyT
Curingheating
IDno.
Commoncontrollersettings
Function
Selectable
OutdoorT Outdooracc.T RoomT
HeatflowT DHWflowT ReturnT
SupplyT Flowswitch
Log2days Log4days
M1
P1 M2
P2 V2 A1
DesiredflowT X1 X2 X3 X4
DesiredflowT X5 X6 X7 X8
RampX5–X6 RampX7–X8
Max.pwr.failure Afterpowerfail. Prog.execution
Appl.continue
46|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.2,Commoncontrollersettingscontinued
Home
MENU
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet(ECLComfort296and310 only)
Portalconfig (ECLComfort296and310only)
Function
Usersettings
Gotofactory To
Systemsettings Usersettings Startcopying
Codeno. Hardware
Software Buildno. Serialno. Productiondate
Addresstype
ECLportal Portalstatus
M-busconfig (ECLComfort296and310only)
EnergyMeters (ECLComfort296and310only)
Rawinputoverview
Sensoroffset Alarm Display
Communication
Language
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210) S1-S10(ECLComfort310) S1-S18(ECLComfort310withECA32)
S1...S10offset
32:
Tsensordefect
60058
Backlight
60059
Contrast
38
Modbusaddr.
2048
ECL485addr.
39
Baud
2150
Servicepin
2151
Ext.reset
2050
Language
AQ156586461753en-010601
©Danfoss|2021.06|47
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.9,circuit1and2
Home
IDno.
MENU
ScheduleSelectableSelectable
Settings
Flowtemperature
11178
11177
11004
Returnlimit
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
Flow/powerlimitActualActual
11119
11117
11118
11116
11112
11113
11109
11115
Optimization
11011
11012
11013
11014
11026
11021
11179
11043
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve
Temp.max.
Temp.min.
DesiredT
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time
Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Adapt.time
Filterconstant
Inputtype
Units
Autosaving
Boost
Ramp
Optimizer
Pre-stop
Totalstop
Summer,cut-out
Paralleloperation
IDno.
12178
12177
12030
12035
12036
12037
12111
12112
12113
12109
12115
Function
Temp.max.
Temp.min.
Limit
Infl.-max.
Infl.-min.
Adapt.time
Limit
Adapt.time
Filterconstant
Inputtype
Units
48|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.9,circuit1andcircuit2continued
Home
MENU
Settings
Alarm
Controlpar.
Application
Heatcut-out
Anti-bacteria
Pressure
Digital
Max.temperature
AlarmoverviewSelectable
IDno.
11174 11184 11185 11186 11187 11189 11024
11017 11050
11500 11022 11023 11052 11077 11078 11040 11093 11141 11142
11393 11392
11179 11395 11397 11396 11398 11399
11614 11615
11617 11607 11608 11609 11610
11636 11637 11079 11080
Circuit1,HeatingCircuit2,DHW
Function
Motorpr. Xp Tn Mrun Nz Min.act.time Actuator
Demandoffset Pdemand
SenddesiredT Pexercise Mexercise DHWpriority PfrostT PheatT Ppost-run Frostpr.T Ext.input Ext.mode
Sum.start,day Sum.start,month
Summer,cut-out Summer,filter Winterstart,day Win.start,month Winter,cut-out Winter,filter
Alarmhigh Alarmlow
Alarmtime-out LowX HighX LowY HighY
Alarmvalue Alarmtime-out
Max.flowT Delay
IDno.
12173 12174
12184 12185 12186 12187 12189 12024
12500 12022 12023
12077 12078 12040 12093 12141 12142
Function
Autotuning Motorpr.
Xp Tn Mrun Nz Min.act.time Actuator
SenddesiredT Pexercise Mexercise
PfrostT PheatT Ppost-run Frostpr.T Ext.input Ext.mode
Day Starttime
Duration DesiredT
AQ156586461753en-010601
©Danfoss|2021.06|49
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.9,circuit1andcircuit2continued
Home
MENU
InfluenceoverviewDes.flowTReturnlim.Returnlim.
IDno.
Circuit1,HeatingCircuit2,DHW
Function
ParallelpriorityFlow/powerlimit Flow/powerlimitExt.override Ext.overrideAnti-bacteria Boost Ramp
Slave,demand Heatingcut-out DHWpriority
SCADAoffsetSCADAoffset Floordry.,active
IDno.
Function
50|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.9,Commoncontrollersettings
Home
MENU
Time&Date
Inputoverview
Log(sensors)
Outputoverride
FloordryingFunctionalheating
Heatingflow&des. Heatingreturn
DHWflow&des. DHWreturn
OutdoorT Heatingpressure
Curingheating
IDno.
Commoncontrollersettings
Function
Selectable OutdoorT Outdooracc.T HeatreturnT
HeatflowT DHWflowT Prim.returnT DHWreturnT Pressure
Digital Logtoday Logyesterday Log2days Log4days
M1
P1 M2 V1
P2 V2 A1
DesiredflowT X1 X2 X3 X4
DesiredflowT X5 X6 X7 X8
RampX5–X6 RampX7–X8
Max.pwr.failure Afterpowerfail. Prog.execution
Appl.continue
AQ156586461753en-010601
©Danfoss|2021.06|51
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.9,Commoncontrollersettingscontinued
Home
MENU
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet(ECLComfort296and310 only)
Portalconfig (ECLComfort296and310only)
Function
Usersettings
Gotofactory To
Systemsettings Usersettings Startcopying
Codeno. Hardware
Software Buildno. Serialno. Productiondate
Addresstype
ECLportal Portalstatus
M-busconfig (ECLComfort296and310only)
EnergyMeters (ECLComfort296and310only)
Rawinputoverview
Sensoroffset Alarm Display
Communication
Language
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210) S1-S10(ECLComfort310) S1-S18(ECLComfort310withECA32)
S1...S10offset
32:
Tsensordefect
60058
Backlight
60059
Contrast
38
Modbusaddr.
2048
ECL485addr.
39
Baud
2150
Servicepin
2151
Ext.reset
2050
Language
52|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.10,circuit1and2
Home
IDno.
MENU
ScheduleSelectableSelectable
Settings
Flowtemperature
11178
11177
11004
Returnlimit
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
Flow/powerlimitActualActual
11119
11117
11118
11116
11112
11113
11109
11115
11114
Optimization
11011
11012
11013
11014
11026
11021
11179
11043
Circuit1,HeatingCircuit2,DHW
Function
Heatcurve
Temp.max.
Temp.min.
DesiredT
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time
Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1
LowToutX2
HighlimitY2
Adapt.time
Filterconstant
Inputtype
Units
Pulse
Autosaving
Boost
Ramp
Optimizer
Pre-stop
Totalstop
Summer,cut-out
Paralleloperation
IDno.
12178
12177
12030
12035
12036
12037
12111
12112
12113
12109
12115
12114
Function
Temp.max.
Temp.min.
Limit
Infl.-max.
Infl.-min.
Adapt.time
Limit
Adapt.time
Filterconstant
Inputtype
Units
Pulse
AQ156586461753en-010601
©Danfoss|2021.06|53
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.10,circuit1andcircuit2continued
Home
MENU
Settings
AlarmDigital
IDno.
Controlpar.
11174 11184 11185 11186 11187 11189 11024
Application
Heatcut-out
Anti-bacteria
Max.temperature
AlarmoverviewSelectable
11017 11050 11500 11022 11023 11052 11077 11078 11040 11093 11141
11142 11393 11392 11179 11395 11397 11396 11398 11399
11636 11637 11079 11080
Circuit1,HeatingCircuit2,DHW
Function
Motorpr. Xp Tn Mrun Nz Min.act.time Actuator Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority
PfrostT PheatT Ppost-run Frostpr.T
Ext.input
Ext.mode Sum.start,day Sum.start,month Summer,cut-out
Summer,filter Winterstart,day Win.start,month Winter,cut-out
Winter,filter
Alarmvalue Alarmtime-out
Max.flowT Delay
IDno.
12173 12174 12184 12185 12186 12187 12189 12024
12500 12022 12023
12077 12078 12040 12093 12141 12142
Function
Autotuning Motorpr. Xp Tn Mrun Nz Min.act.time Actuator
SenddesiredT Pexercise Mexercise
PfrostT PheatT Ppost-run Frostpr.T
Ext.input
Ext.mode
Day Starttime Duration
DesiredT
54|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.10,circuit1andcircuit2continued
Home
MENU
InfluenceoverviewDes.flowTReturnlim.Returnlim.
IDno.
Circuit1,HeatingCircuit2,DHW
Function
ParallelperiorityFlow/powerlimit Flow/powerlimitExt.override Ext.overrideAnti-bacteria Boost Ramp
Slave,demand Heatingcut-out DHWpriority
SCADAoffsetSCADAoffset Floordry.,active
IDno.
Function
AQ156586461753en-010601
©Danfoss|2021.06|55
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.10,Commoncontrollersettings
Home
MENU
Time&Date
Inputoverview
Log(sensors)
Outputoverride
FloordryingFunctionalheating
Heatingflow&des. Heatingreturn
DHWflow&des. DHWreturn
OutdoorT
Curingheating
IDno.
Commoncontrollersettings
Function
Selectable OutdoorT Outdooracc.T HeatreturnT
HeatflowT DHWflowT Prim.returnT DHWreturnT
Digital Logtoday Logyesterday Log2days Log4days
M1
P1 M2 V1
P2 V2 A1
DesiredflowT X1 X2 X3 X4
DesiredflowT X5 X6 X7 X8
RampX5–X6 RampX7–X8
Max.pwr.failure Afterpowerfail. Prog.execution
Appl.continue
56|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Navigation,A266.10,Commoncontrollersettingscontinued
Home
MENU
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet(ECLComfort296and310 only)
Portalconfig (ECLComfort296and310only)
Function
Usersettings
Gotofactory To
Systemsettings Usersettings Startcopying
Codeno. Hardware
Software Buildno. Serialno. Productiondate
Addresstype
ECLportal Portalstatus
M-busconfig (ECLComfort296and310only)
EnergyMeters (ECLComfort296and310only)
Rawinputoverview
Sensoroffset Alarm Display
Communication
Language
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210) S1-S10(ECLComfort310) S1-S18(ECLComfort310withECA32)
S1...S10offset
32:
Tsensordefect
60058
Backlight
60059
Contrast
38
Modbusaddr.
2048
ECL485addr.
39
Baud
2150
Servicepin
2151
Ext.reset
2050
Language
AQ156586461753en-010601
©Danfoss|2021.06|57
OperatingGuideECLComfort210/296/310,applicationA266

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
58|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
AQ156586461753en-010601
)
©Danfoss|2021.06|59
OperatingGuideECLComfort210/296/310,applicationA266
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
DHWcircuit
Overviewdisplay1informsabout: actualDHWtemperature,controllermode,desiredDHW temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout: stateofthecontrolledcomponents,actualDHWtemperature, (desiredDHWtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith Influenceindication:
60|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Examples:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
AQ156586461753en-010601
©Danfoss|2021.06|61
OperatingGuideECLComfort210/296/310,applicationA266
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled operationandincomfortmode.
Examples:
50
55
62|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
DamperOFF
AQ156586461753en-010601
©Danfoss|2021.06|63
OperatingGuideECLComfort210/296/310,applicationA266

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview oftheactualand(desired)temperaturesaswellastheactualstate ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
(30)
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
Flowtemperature
Desiredflowtemperature
--
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
64|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
AQ156586461753en-010601
©Danfoss|2021.06|65
OperatingGuideECLComfort210/296/310,applicationA266

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
66|©Danfoss|2021.06
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
AQ156586461753en-010601
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
©Danfoss|2021.06|67
OperatingGuideECLComfort210/296/310,applicationA266

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Actual(actualfloworpower)
Xpactual
Extendedheatcut-outsetting
Extendedwintercut-outsetting
Day
Starttime
Duration
DesiredT
DesiredT(Desiredflowtemperature)
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Adapt.time(adaptiontime)
Demandoffset
Basedon(optimizationbasedonroom/outdoortemp.)
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Actuator
Pre-stop(optimizedstoptime)
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
DHW,ret.Tlimit
Limit(returntemp.limitation)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Ppost-run
Paralleloperation
Pdemand
DHWpriority(closedvalve/normaloperation)
PfrostT(circulationpump,frostprotectiontemp.)
1x00473
1x010102
1x01188
1x01289
1x01390
1x01490
1x015
1x017102
1x02091
1x02191
1x022102
1x023103
1x02496
1x02692
1x02879
1x02979
1x03080
1x03180
1x03280
1x03380
1x03481
1x03581
1x03681
1x03781
1x040103
1x04392
1x050103
1x052104
1x077104
Factorysettingsincircuit(s)
1
72
84
98
111
111
120
120
121
121
75
2
68|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
SettingIDPage
PheatT(heatdemand)
Max.flowT(Maximumflowtemperature)
Delay
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Opentime
Closetime
Tn(idle)
SupplyT(idle)
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Pulse
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Autotuning
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Infl.-max.(roomtemp.limitation,max.)
Infl.-min.(roomtemp.limitation,min.)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
SenddesiredT
LowX
HighX
LowY
HighY
1x078104
1x079
1x080
1x08582
1x093105
1x09496
1x09597
1x09697
1x09797
1x10984
1x111
1x11284
1x11385
1x114
1x115
1x11686
1x117
1x11886
1x11987
1x141
1x142106
1x147114
1x148
1x149
1x150116
1x17397
1x174
1x17774
1x178
1x17993
1x182
1x18376
1x18498
1x18599
1x18699
1x18799
1x18999
1x500108
1x607116
1x608116
1x609116
1x610
Factorysettingsincircuit(s)
1
114
114
84
85
85
86
105
115
115
98
74
75
117
2
AQ156586461753en-010601
©Danfoss|2021.06|69
OperatingGuideECLComfort210/296/310,applicationA266
Alarmhigh
Alarmlow
Alarmtime-out
Alarmvalue
Alarmtime-out
SettingIDPage
1x614
1x615
1x617
1x636
1x637118
Factorysettingsincircuit(s)
1
117
117
117
117
2
70|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
AQ156586461753en-010601
©Danfoss|2021.06|71
OperatingGuideECLComfort210/296/310,applicationA266

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
72|©Danfoss|2021.06
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
TheECLComfort210/296/310controlstheDHWtemperature accordingtothedesiredflowtemperatureforexampleunderthe influenceofthereturntemperature.
ActualDHWtemp.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DesiredDHW temp.
AQ156586461753en-010601
©Danfoss|2021.06|73
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Flowtemperature
DesiredT(Desiredflowtemperature)
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow temperaturecanbeset. A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU >Settings>Returnlimit>'Con.T,ret.Tlim. '
1x004
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan beappliedtoaninputinordertooverridetoComfort,Saving,Frost ProtectionorConstanttemperature.Aslongasthecontact(switch) signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
74|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

5.3Roomlimit

ThefollowingsectionisageneraldescriptionforRoom temperaturelimitation. Theactualapplicationmightnothavebothlimitationtypes.
Thissectionisonlyrelevantifyouhaveinstalledaroom temperaturesensororaRemoteControlUnitforutilizingtheroom temperaturesignal.
Inthefollowingdescriptionisreferredto"flowtemperature"in general.
Thecontrolleradjuststhedesiredflowtemperaturetocompensate forthedifferencebetweenthedesiredandtheactualroom temperature.
Iftheroomtemperatureishigherthanthedesiredvalue,the desiredflowtemperaturecanbereduced.
The'Infl.-max.'(Influence,max.roomtemp.)determineshow muchthedesiredflowtemperatureshouldbereduced.
Usethisinfluencetypetoavoidatoohighroomtemperature.The controllerwillallowforfreeheatgains,i.e.solarradiationorheat fromafireplaceetc.
Iftheroomtemperatureislowerthanthedesiredvalue,thedesired flowtemperaturecanbeincreased.
The'Infl.-min.'(Influence,min.roomtemperature)determines howmuchthedesiredflowtemperatureshouldbeincreased.
Usethisinfluencetypetoavoidatoolowroomtemperature.This coulde.g.becausedbywindysurroundings.
Atypicalsettingwillbe-4.0for'Infl.-max.'and4.0for'Infl.-min. '
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Roomlimit
Adapt.time(adaptiontime)
Controlshowfasttheactualroomtemperatureadaptstothedesiredroom temperature(Icontrol).
1x015
Theadaptationfunctioncancorrectthedesiredroomtemperature withmax.8Kxheatcurveslopevalue.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe'Adapt. time'.
Minor
Thedesiredroomtemperatureisadaptedquickly.
value: Major
Thedesiredroomtemperatureisadaptedslowly.
value:
AQ156586461753en-010601
©Danfoss|2021.06|75
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Roomlimit
Infl.-max.(roomtemp.limitation,max.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (decreased)iftheactualroomtemperatureishigherthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
0.0:
-2.0:
-5.0:
-9.9:
Noinfluence Minorinfluence Mediuminfluence Maximuminfluence
1x182
=
X
#1#
#2#
#3#
Roomtemperature
=
Desiredroomtemperature
=
Negativeinfluence(1x082)whenactualroomtemp.getshigher thandesiredroomtemp.
=
Positiveinfluence(1x083)whenactualroomtemp.getslowerthan desiredroomtemp.
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x-4.0x1.8) –14.4degrees.
MENU>Settings>Roomlimit
Infl.-min.(roomtemp.limitation,min.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (increased)iftheactualroomtemperatureislowerthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
9.9:
5.0:
2.0:
0.0:
Maximuminfluence Mediuminfluence Minorinfluence Noinfluence
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x-4.0x1): –8.0degrees.
Example
1x183
Theactualroomtemperatureis2degreestoolow. The‘Infl.-min.’issetto4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x4.0x1.8)
14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x4.0x1):
8.0degrees.
76|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

5.4Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant temperaturevalue. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthesetlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
AQ156586461753en-010601
©Danfoss|2021.06|77
OperatingGuideECLComfort210/296/310,applicationA266
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
T
Y
X
#1#
#2#
#3#
#4#
=
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
78|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
T
Y
X
#1#
#2#
#3#
#4#
=
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
The"Con.T ,ret.Tlimit"isthereturntemperaturelimitationvaluewhenthe circuitissettooverridemodetype"Const.T"(=Constanttemperature).
SeeAppendix“ParameterIDoverview”
Value:Setthereturntemperaturelimitation
1x028
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan beappliedtoaninputinordertooverridetoComfort,Saving,Frost ProtectionorConstanttemperature.Aslongasthecontact(switch) signalisapplied,theoverrideisactive.
AQ156586461753en-010601
©Danfoss|2021.06|79
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Returnlimit
DHW,ret.Tlimit
WhenanaddressedslaveisactiveinDHW-tankheating/charging,the returntemperaturelimitationinthemastercanbeset. Notes:
Themastercircuitmustbesettoreactonthedesiredflowtemperature intheslave(s).See"Demandoffset"(ID11017).
Theslave(s)mustbesettosendits/theirdesiredflowtemperatureto themaster.See"SenddesiredT"(ID1x500).
SeeAppendix“ParameterIDoverview”
OFF:
Noinfluencefromslaves.Thereturntemperature limitationisrelatedtosettingsin"Returnlimit" .
Value:Returntemperaturelimitationvaluewhenslaveisin
DHWtankheating/chargingoperation.
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x029
#1#=Master,exampleA266,address15 #2#=Slave,exampleA237,address9 #3#=Slave,exampleA367,address6
SomeexamplesofapplicationswithDHW-tankheating/chargingare:
•A217,A237,A247,A367,A377
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe setvalue,thecontrollerautomaticallychangesthedesiredflow/ ducttemperaturetoobtainanacceptablereturntemperature.The influenceissetin'Infl.-max. 'and'Infl.-min.' .
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
1x031
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
1x032
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
80|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
1x033
1x034
Example
1x035
Thereturnlimitisactiveabove50°C. Theinfluenceissetto0.5. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby0.5x2=1.0degree.
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthesetlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthesetlimit.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Example
1x036
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
AQ156586461753en-010601
©Danfoss|2021.06|81
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x037
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
82|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

5.5Flow/powerlimit

Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
HighlimitY2
LowlimitY1
Flow/power limitation
Desiredflow temp.
Flow/powerlimitation
LowToutX2
Outdoortemp.
HighToutX1
Limit
Time
DHWcircuit
AfloworheatmetercanbeconnectedtotheECLcontrollerin ordertolimitthefloworconsumedpower.Thesignalfromthe floworheatmeterisapulsesignal.
WhentheapplicationrunsinanECLComfort296/310controller, theflow/powersignalcanbeobtainedfromaflow/heatmeter viatheM-busconnection.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
=
X
Y
#1#
#2#
#3#
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
Theparameter'Units'(ID1x115)hasareducedsettingrangewhen theflow/energysignalcomesviaM-bus.
AQ156586461753en-010601
©Danfoss|2021.06|83
OperatingGuideECLComfort210/296/310,applicationA266
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Pulsebasedsignalforflow/power ,appliedtoinputS7
Formonitoring: Frequencyrangeis0.01-200Hz
Forlimitation: Minimumfrequencyisrecommendedtobe1Hzinordertohavea
stablecontrol.Furthermore,thepulsesmustappearregularly.
Inputtype
Choiceofinputtypefromflow/energymeter
SeeAppendix“ParameterIDoverview”
OFF:
IM1-
Noinput
Flow/energymetersignalbasedonpulses.
IM5: EM1-
Flow/energymetersignalfromM-bus.
EM5:
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
1x109
ThesettingrangeforIMandEMdependsonchosensubtype.
1x111
SeeAppendix“ParameterIDoverview”
84|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
1x113
MENU>Settings>Flow/powerlimit
Pulse
Setthevalueofthepulsesfromtheflow/energymeter.
SeeAppendix“ParameterIDoverview”
OFF:
1...9999:
Noinput.
Pulsevalue.
Example:
1x114
Onepulsecanrepresentanumberoflitres(fromaflowmeter) oranumberofkWh(fromaenergymeter).
Pulsebasedsignalforflow/power ,appliedtoinputS7
Formonitoring: Frequencyrangeis0.01-200Hz
Forlimitation: Minimumfrequencyisrecommendedtobe1Hzinordertohavea
stablecontrol.Furthermore,thepulsesmustappearregularly.
AQ156586461753en-010601
©Danfoss|2021.06|85
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Unitstotheleft:pulsevalue. Unitstotheright:actualandlimitationvalues.
Thevaluefromtheflowmeterisexpressedasmlorl. ThevaluefromtheenergymeterisexpressedasWh,kWh,MWh orGWh.
Thevaluesfortheactualflowandtheflowlimitationareexpressed asl/horm³/h.
Thevaluesfortheactualpowerandthepowerlimitationare expressedaskW,MWorGW.
1x115
Listforsettingrangeof'Units': ml,l/h l,l/h ml,m³/h l,m³/h Wh,kW kWh,kW kWh,MW MWh,MW MWh,GW GWh,GW
Example1:
'Units'(11115):
'Pulse'(11114):
l,m³/h 10
Eachpulserepresents10litresandtheflowisexpressedascubic meters(m³)perhour.
Example2:
'Units'(11115):
'Pulse'(11114):
kWh,kW(=kiloWatthour,kiloWatt) 1
Eachpulserepresents1kiloWatthourandthepoweris expressedinkiloWatt.
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
1x116
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
86|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
1x118
1x119
AQ156586461753en-010601
©Danfoss|2021.06|87
OperatingGuideECLComfort210/296/310,applicationA266

5.6Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost','Optimizer','Totalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
88|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
AQ156586461753en-010601
©Danfoss|2021.06|89
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
=
X Y #1#
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
90|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
MENU>Settings>Optimization
Basedon(optimizationbasedonroom/outdoortemp.)
Theoptimizedstartandstoptimecanbebasedoneitherroomoroutdoor temperature.
SeeAppendix“ParameterIDoverview”
OUT:
Optimizationbasedonoutdoortemperature.Usethis settingiftheroomtemperatureisnotmeasured.
ROOM:
Optimizationbasedonroomtemperature,ifmeasured.
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
1x020
-5°C
small
AQ156586461753en-010601
©Danfoss|2021.06|91
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost protectionisstillactive,see'PfrostT' .
Totalstop=OFF
Totalstop=ON
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
1x026
Example:OptimizationofComfortfrom07:00-22:00
=
X #1# #2# #3# #4# #5#
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
92|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Optimization
Paralleloperation
ChoosewhethertheheatingcircuitistooperateindependenceoftheDHW circuit.Thisfunctionmightbeusefulifaninstallationhaslimitedpower orflow.
SeeAppendix“ParameterIDoverview”
OFF:
Independentparalleloperation,i.e.theDHWand theheatingcircuitsoperateindependentlyofeach other.ItmakesnodifferencewhetherthedesiredDHW temperaturecanbereachedornot.
Value:Dependentparalleloperation,i.e.thedesiredheating
temperaturedependsontheDHWdemand.Choose howmuchtheDHWtemperaturecandropbeforethe desiredheatingtemperaturehastobedecreased.
1x043
=
X
Y1
Y2
#1#
#2#
#3#
#4#
#5#
#6#
#7#
Time
=
Temperature
=
Temperature
=
Acceptabledeviation(Paralleloperation,1x043)
=
DesiredDHWtemperature
=
ActualDHWtemperature
=
Desiredheatingtemperature
=
Reducedheatingtemperature
=
100%paralleloperation
=
Paralleloperationwithdecreasedheatingtemperature
IftheactualDHWtemperaturedeviatesmorethanthesetvalue,the gearmotorM2intheheatingcircuitwillgraduallyclosetosuchan extentthattheDHWtemperaturestabilizesatthelowestacceptable value.
IncasetheParalleloperationisactive(atoolowDHWtemperature andthereforeareducedheatingcircuittemperature),aslave's temperaturedemandwillnotchangethedesiredflowtemperaturein theheatingcircuit.
Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
AQ156586461753en-010601
©Danfoss|2021.06|93
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
Summer,cut-out
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
94|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266

5.7Controlparameters

Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point controlsignal.
Valvecontrol: Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
0-10voltcontrolledactuator Thiselectricactuatorcontainsareversiblegear-motor.Acontrol voltagebetween0and10voltcomesfromtheextensionmodule ECA32inordertomanagethecontrolvalve.ThevoltageintheECL Comfortcontrollerisexpressedasa%valueanddisplayedatthe valvesymbol.Example:45%correspondsto4.5volt. Whentheflowtemperature(forexampleatS3)islowerthan thedesiredflowtemperature,thecontrolvoltageisgradually increasedinordertograduallyincreasetheflow.Bythis,theflow temperaturewillalignwiththedesiredtemperature. Thecontrolvoltageremainsonaconstantvalueaslongastheflow temperaturecorrespondstothedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,thecontrolvoltageisgraduallyreducedinorder toreducetheflow.Again,theflowtemperaturealignswiththe desiredtemperature.
AQ156586461753en-010601
©Danfoss|2021.06|95
OperatingGuideECLComfort210/296/310,applicationA266
Thermo-hydraulicactuator,ABV
Danfossthermo-actuatortypeABVisaslowactingvalveactuator. InsidetheABVanelectricheatcoilwillheatathermostaticelement whenanelectricsignalisapplied.Whenheatingthethermostatic elementitexpandsinordertomanagethecontrolvalve.
Twobasictypesareavailable:ABVNC(NormalClosed)andABVNO (normalopen).Forexample,ABVNCkeepsa2-portcontrolvalve closedwhennoopen-signalsareapplied.
Electricopen-signalscomefromtheelectronicoutputoftheECL Comfortcontrollerinordertomanagethecontrolvalve.When open-signalsareappliedtotheABVNC,thevalvegraduallyopens.
Open-signalsareintheECLComfortcontrollerexpressedas "Arrow-up"(open)anddisplayedatthevalvesymbol.
Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,relativelylongopen-signalscomefrom theECLComfortcontrollerinordertoincreasetheflow.Bythis, theflowtemperaturewillovertimebealignedwiththedesired temperature.
Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,relativelyshortopen-signalscomefromtheECL Comfortcontrollerinordertoreducetheflow.Again,theflow temperaturealigns,overtime,withthedesiredtemperature.
ThecontroloftheDanfossthermo-actuatortypeABVusesaunique designedalgorithmandisbasedonthePWMprinciple(Pulse WidthModulation),wherethedurationofthepulsedetermines themanagementofthecontrolvalve.Thepulsesarerepeated each10sec.
Aslongastheflowtemperaturecorrespondstothedesired temperature,thedurationoftheopen-signalswillremainconstant.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Actuator
ABV/GEAR
1x024
GEAR
Selectionofvalveactuatortype.
Whenselecting"ABV",thecontrolparameters:
•Motorprotection(ID1x174)
ABV:
GEAR:
96|©Danfoss|2021.06
DanfosstypeABV(thermoactuator). Gearmotorbasedactuator.
•Xp(ID1x184)
•Tn(ID1x185)
•Mrun(ID1x186)
•Nz(ID1x187)
•Min.act.time(ID1x189)
arenotconsidered.
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Controlparameters
Opentime
The‘Opentime’istheforcedtime(inseconds)thatittakestoopenthe motorizedcontrolvalvewhenaDHWdraw-off(tapping)isdetected(the flowswitchisactivated).Thisfunctioncompensatesforthedelaybeforethe flowtemperaturesensormeasuresachangeintemperature.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
Closetime
The‘Closetime’istheforcedtime(inseconds)thatittakestoclosethe motorizedcontrolvalvewhenaDHWdraw-off(tapping)isstopped(the flowswitchisdeactivated).Thisfunctioncompensatesforthedelaybefore theflowtemperaturesensormeasuresachangeintemperature.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
Tn(idle)
WhennoDHWdraw-off(tapping)isdetected(theflowswitchisdeactivated), thetemperatureismaintainedatalowlevel(savingtemperature).The integrationtime‘Tn(idle)’canbesettoobtainaslowbutstablecontrol.
1x094
1x095
1x096
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
SupplyT(idle)
The‘supplyT(idle)’isthesupplytemperaturewhenthereisnoDHW draw-off(tapping).WhenDHWdraw-offisnotdetected(theflowswitch isdeactivated),thetemperatureismaintainedatalowerlevel(saving temperature).Choosewhichtemperaturesensoristomaintainthesaving temperature.
SeeAppendix“ParameterIDoverview”
OFF:
ThesavingtemperatureismaintainedattheDHWflow temperaturesensor.
ON:
Thesavingtemperatureismaintainedatthesupply temperaturesensor.
1x097
Ifthesupplytemperaturesensorisnotconnected,theidlesupply temperaturewillbemaintainedattheDHWflowtemperaturesensor.
AQ156586461753en-010601
©Danfoss|2021.06|97
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Controlparameters
Autotuning
AutomaticallydeterminesthecontrolparametersfortheDHWcontrol.'Xp' 'Tn'and'Mrun'donotneedtobeset,whenusingautotuning.'Nz'must beset.
1x173
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Autotuningisnotactivated. Autotuningisactivated.
Theautotuningfunctionautomaticallydeterminesthecontrol parametersforDHWcontrol.Thusyoudonotneedtosetthe'Xp', 'Tn'and'Mrun',astheyareautomaticallysetwhentheautotuning functionissettoON.
Autotuningistypicallyusedinconnectionwiththeinstallationof thecontroller,butitcanbeactivatedwhenneeded,e.g.foran extracheckofthecontrolparameters.
Beforestartingtheautotuning,thetappingflowshouldbe adjustedtotherelevantvalue(seetable).
Ifpossible,anyadditionalDHWconsumptionshouldbeavoided duringtheautotuningprocess.Shouldthetappingloadvarytoo much,theautotuningandcontrollerwillreturntothedefault settings.
No.of apartments
Heat transfer
ConstantDHWdraw-off(l/min)
(kW)
1-230-493 3-950-796 10-4980-14912
50-129150-24918
130-210250-35024
Inordertomeetthesummer-/wintervariations,theECLclockmust besettothecorrectdateforansuccessfulautotuning.
Themotorprotectionfunction('Motorpr.')hastobedeactivated duringautotuning.Duringautotuningthecirculationpumpfortap watermustbeswitchedoff.Thisisdoneautomaticallyifthepumpis controlledbytheECLcontroller.
Autotuningisonlyapplicableinconnectionwithvalvesthatare approvedforautotuning,i.e.theDanfosstypesVB2andVM2with splitcharacteristicaswellaslogarithmicvalvessuchasVFandVFS.
(or1tap25%open) (or1tap50%open) (or1tap100%open)
(or1tap100%+1tap50% open)
(or2taps100%open)
AutotuningisactivatedbysettingthefunctiontoON.Whenthe autotuningisended,thefunctionisautomaticallyconvertedto OFF(defaultsetting).Thiswillbeindicatedinthedisplay.
Theautotuningprocesstakesupto25minutes.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
1x174
Recommendedforductsystemswithvariableload.
1x184
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
98|©Danfoss|2021.06
AQ156586461753en-010601
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Controlparameters
Xpactual
‘Xpactual’istheread-outoftheactualXp(proportionalband)basedon thesupplytemperature.Xpisdeterminedbysettingsrelatedtothesupply temperature.Typically,thehigherthesupplytemperature,thehighertheXp mustbeinordertoachieveastabletemperaturecontrol.
Xpsettingrange:
5...250K
Fixedsupplytemperaturesettings:65°Cand90°C Factorysettings:
(65,40)and(90,120)
Thismeansthatthe‘Xp’is40Kat65°Csupplytemperature,and ‘Xp’is120Kat90°C.
SetthedesiredXpvaluesatthetwofixedsupplytemperatures.
Ifthesupplytemperatureisnotmeasured(thesupplytemperature sensorisnotconnected),theXpvalueatthesetting65°Cisused.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
1x186
1x187
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
AQ156586461753en-010601
©Danfoss|2021.06|99
OperatingGuideECLComfort210/296/310,applicationA266
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
100|©Danfoss|2021.06
AQ156586461753en-010601
Loading...