OperatingGuide
ECLComfort210/296/310,applicationA247/A347
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................15
2.3Mounting...........................................................21
2.4Placingthetemperaturesensors................................25
2.5Electricalconnections.............................................27
2.6InsertingtheECLApplicationKey..............................36
2.7Checklist............................................................43
2.8Navigation,ECLApplicationKeyA247/A347................44
3.0Dailyuse.........................................................50
3.1Howtonavigate...................................................50
3.2Understandingthecontrollerdisplay..........................51
3.3Ageneraloverview:Whatdothesymbolsmean?...........55
3.4Monitoringtemperaturesandsystem
components........................................................56
3.5Influenceoverview................................................57
3.6Manualcontrol.....................................................58
3.7Schedule............................................................59
4.0Settingsoverview............................................60
5.0Settings...........................................................63
5.1IntroductiontoSettings..........................................63
5.2Flowtemperature..................................................64
5.3Roomlimit..........................................................68
5.4Returnlimit.........................................................70
5.5Flow/powerlimit.................................................76
5.6Optimization........................................................81
5.7Controlparameters................................................88
5.8Application.........................................................93
5.9Heatcut-out......................................................104
5.10Tanktemperature................................................107
5.11Alarm..............................................................112
5.12Alarmoverview..................................................115
5.13Anti-bacteria......................................................116
6.0Commoncontrollersettings............................118
6.1Introductionto‘Commoncontrollersettings’..............118
6.2Time&Date.......................................................119
6.3Holiday............................................................120
6.4Inputoverview...................................................122
6.5Log.................................................................123
6.6Outputoverride..................................................124
6.7Keyfunctions.....................................................125
6.8System.............................................................127
7.0Miscellaneous................................................134
7.1ECA30/31setupprocedures.................................134
7.2Overridefunction................................................142
7.3Severalcontrollersinthesamesystem......................145
7.4Frequentlyaskedquestions....................................148
7.5Definitions........................................................151
7.6Type(ID6001),overview.......................................155
7.7Automatic/manualupdateoffirmware.....................156
7.8ParameterIDoverview..........................................157
©Danfoss|2021.12AQ192386469094en-010802|1
OperatingGuideECLComfort210/296/310,applicationA247/A347
1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA247
(ordercodeno.087H3808).
TheA247Keycontains6subtypes:
A247.1…A247.3(applicableinECLComfort210and310)
A347.1…A347.3(applicableinECLComfort310)
•A247.1:HeatingandDHWcharging/heating
•A247.2:HeatingandDHWcharging
•A247.3:HeatingandadvancedDHWcharging
•A347.1:HeatingandDHWcharging/heating.M-busoptional
•A347.2:HeatingandDHWcharging.M-busoptional
•A347.3:HeatingandDHWcharging.MonitoringofDHW
circulationreturn.M-busoptional
TheA247applicationkeyalsocontainsaFloor(Screed)Drying
Program.Seeseparatedocumentation.
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort210forbasic
solutionsandinECLComfort310foradvancedsolutions,for
exampleM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA247complieswithECLComfort210and
ECLComfort310controllersasofsoftwareversion1.11(visible
atstart-upofthecontrollerandin'Commoncontrollersettings'
in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedandthebuilt-inroomtemperaturesensorcanbe
utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
•Temperature,Pt1000(default)
•0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>T ools&Software>ECLTool.
TheURLis:
https://www.danfoss.com/en/service-and-support/downloads/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort210isavailableas:
•ECLComfort210,230volta.c.(087H3020)
•ECLComfort210B,230volta.c.(087H3030)
ECLComfort310isavailableas:
•ECLComfort310,230volta.c.(087H3040)
•ECLComfort310B,230volta.c.(087H3050)
•ECLComfort310,24volta.c.(087H3044)
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://danfoss.com/.
2|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
•ECA30(087H3200)
•ECA31(087H3201)
BasepartsforECLComfort:
•forECLComfort210,230volta.c.(087H3220)
•forECLComfort296,230volta.c.(087H3240)
•forECLComfort310,230volta.c.and24volta.c(087H3230)
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://danfoss.com/.
DocumentationforECLPortal:Seehttps://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
•Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
AQ192386469094en-010802
©Danfoss|2021.12|3
OperatingGuideECLComfort210/296/310,applicationA247/A347
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310/311:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
4|©Danfoss|2021.12
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
2
Circuit2Parameterno.
174
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot
bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back
schemefortherecyclingofelectricalandelectronic
equipment.
•Disposeoftheproductthroughchannelsprovided
forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws
andregulations.
AQ192386469094en-010802
©Danfoss|2021.12|5
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.0Installation
2.1Beforeyoustart
Theapplications(subtypes)intheA247applicationkeyarevery
flexibleandalmostidentical.However,someapplicationshave
extrafunctionswhicharedescribedseparately.
Thesearethebasicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperatureS1andthe
desiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent
temperaturevaluesfordesiredroomtemperature).
InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM2isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent
oftheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
Ifthemeasuredroomtemperature(RemotecontrolunitECA30/
31)doesnotequalthedesiredroomtemperature,thedesiredflow
temperaturecanbeadjusted.
Thecirculationpump(P1)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
A247.1,A247.2:
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedflow/power.
WhenthesubtypesA347.1-A347.3areused(onlyinECLComfort
310),theflow/powersignalcancomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
TypicalA247.1application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
S2DHWreturntemperaturesensor,circuit2
S3
S4
S5Returntemperaturesensor,circuit1
S6
S7
S8
P1
P2
P3
M1
M2
A1
A/B
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
DHWtanktemperaturesensor,upper
Flow/energymeter(pulsesignal)
DHWtanktemperaturesensor,lower
Circulationpump,heating,circuit1
Chargingpump,DHW,circuit2
Circulationpump,DHW,circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
Alarm
Internal/externalconnectionsforDHWcirculation
Analarmcanbeactivatediftheactualflowtemperaturediffers
fromthedesiredflowtemperature.
6|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
A247.1,A247.2,A247.3:
TheroomtemperaturesignalcanbeachievedfromtheRemote
ControlUnitECA30/31,ifconnected.
A347.1,A347.2,A347.3:
Theroomtemperaturesignalcanbeachievedfromtheroom
temperaturesensorS7ortheRemoteControlUnitECA30/31,if
connected.
A347.1,A347.2,A347.3:
Thedesiredflowtemperatureofheatingcircuit1can,viaS10,be
controlledbymeansofanexternalvoltageintherange0-10volt.
Heatingcircuit,ingeneral:
Exerciseofcirculationpumpandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
AQ192386469094en-010802
©Danfoss|2021.12|7
OperatingGuideECLComfort210/296/310,applicationA247/A347
DomesticHotWater ,DHW(circuit2):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent
temperaturevaluesfordesiredDHWtemperature).
Chargingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthe
charging-starttemperature,theDHWchargingpump(P2)is
switchedON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain
thechargingtemperatureatS4.
Adelayedstartofchargingpumpcanbearranged.Also,itcan
bearrangedthatthestartofthechargingpumpdependson
thechargingtemperature.Inthiscase,S4mustbeplacedinthe
heat-exchanger.
TheDHWchargingtemperatureisdeterminedbythedesiredDHW
temperatureatS6plusthesetchargingdifference.Thecharging
temperatureistypically5–10degreeshigherthanthedesired
DHWtemperature.
Thereturntemperature,whentheDHWheating/chargingis
active,canbelimitedtoafixedvalue.
A247.2:
WhenthemeasuredDHWtemperatureS6getslowerthanthe
charging-starttemperature,theDHWheatingpump(P2)is
switchedONandthemotorizedcontrolvalveM1iscontrolledin
ordertomaintainthechargingtemperatureatS4.Thecharging
pumpisswitchedONwhentheS4temperatureisacceptable.
A247.1,examplea
Charging-starttemperature:
DesiredDHWtemperature+Startdifference.
Example:
50°C+(-3K)=47°C
A247.3:
TheDHWheatingcircuithasapreheatingcircuit,wheretheDHW
heatingtemperatureatS4isadaptedtothedesiredDHWcharging
temperatureatS7.IftheDHWchargingtemperatureatS7cannot
bereached,theECLcontrollergraduallyincreasesthedesiredDHW
heatingtemperatureatS4inordertoobtaintheDHWcharging
temperature.TheECLcontrollerrememberstheadaptedS4
temperature.Amaximumtemperaturevaluecanbeset.
A347.2:
TheDHWheatingcircuithasapreheatingcircuit,wheretheDHW
heatingtemperatureatS4isadaptedtothedesiredDHWcharging
temperatureatS9.IftheDHWchargingtemperatureatS9cannot
bereached,theECLcontrollergraduallyincreasesthedesiredDHW
heatingtemperatureatS4inordertoobtaintheDHWcharging
temperature.TheECLcontrollerrememberstheadaptedS4
temperature.Amaximumtemperaturevaluecanbeset.
8|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
Chargingstop,DHWtankwith1temperaturesensor:
WhenthemeasuredDHWtemperatureS6getshigherthan
thecharging-stoptemperature,theDHWchargingpumpP2is
switchedOFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors:
WhenthemeasuredDHWtemperatureS6gets2Khigherthan
thecharging-starttemperatureANDthelowertanktemperature
S8getshigherthanthecharging-stoptemperature,theDHW
chargingpumpP2isswitchedOFF.Apost-runtimecanbeset.
DHWcirculation
InchargingapplicationstheDHWcirculationcanbethrough
theDHWtank(connectionA)orthroughtheheat-exchanger
(connectionB).
ThesolutionwithconnectionAresultsinclosingofthemotorized
controlvalveaftertheDHWtankchargingprocedure.
ThesolutionwithconnectionBstopstheDHWchargingpump
aftertheDHWtankchargingprocedure.Thetemperatureatthe
chargingtemperaturesensorismaintainedaccordingtothevalue
ofthedesiredDHWtemperatureinordertocompensateforthe
heatlossintheDHWcirculationpipe.
Flow/powerlimitation
A247.1,A247.2:
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworpowertoasetmaximumvalue.
Charging-stoptemperature:
DesiredDHWtemperature+Stopdifference.
Example,S6only:
50°C+(3K)=53°C
Example,S6andS8:
50°C+(-8K)=42°C
A347.1,A347.2,A347.3(onlyinECLComfort310):
Theflow/powersignalcancomeasanM-bussignal.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheDHWcirculationpumpP3hasaweekscheduleforupto3
ON-periodsperday.
IfthedesiredDHWtemperaturecannotbereached,theheating
circuitcanbeclosedgraduallytoallowmoreenergytotheDHW
circuit.
AQ192386469094en-010802
©Danfoss|2021.12|9
OperatingGuideECLComfort210/296/310,applicationA247/A347
A247,ingeneral
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
HolidayprogramsarepresentforHeatingandDHWcircuits.
Besides,aholidayprogramispresentfortheentirecontroller.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.TheECLcontrollersintheECL485system
canworkinmaster-slavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beused
tooverridethescheduletoafixed'Comfort' ,'Saving','Frost
protection'or'Constanttemperature'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdata(ECLComfort310)canfurthermorebetransferred
totheModbuscommunication.
Alarm
A247.1:
AlarmA1(=relay4)canbeactivated:
•iftheactualflowtemperaturediffersfromthedesiredflow
temperature
•ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
A347.1,A347.2,A347.3:
AlarmA1(=relay6)canbeactivated:
•iftheactualflowtemperaturediffersfromthedesiredflow
temperature
•ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
WhentheA247hasbeenuploadedtheECLComfortcontroller
startsinManualmode.Thiscanbeusedforcheckingthecontrolled
componentsforcorrectfunctionality.
Inputconfiguration
Inputs(asfromS7andup)whicharenotreservedforthe
applicationcanbeconfiguredtobePt1000,0-10Volt,frequency
(pulsecounter)ordigitalinput.Thisfeaturemakesitpossibleto
monitorextrasignals,suchastemperatures,pressures,ON/OFF
conditions,viaModbusandECLPortal.
TheconfigurationisdonebymeansoftheECLTool(freesoftware
fordownload)ordirectlyinadedicatedmenuintheECLPortalor
theconnectionforModbus(BMS/SCADA).
TypicalA247.2application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
S7
S8
P1
P2
P3
P4
M1
DHWtanktemperaturesensor,upper
Flow/energymeter(pulsesignal)
DHWtanktemperaturesensor,lower
Circulationpump,heating,circuit1
DHWheatingpump,circuit2
Circulationpump,DHW,circuit2
DHWchargingpump,circuit2
Motorizedcontrolvalve(3-pointcontrolled),
circuit2
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),
circuit1
Alternative:Thermoactuator(DanfosstypeABV)
A/B
Internal/externalconnectionsforDHWcirculation
10|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
TypicalA247.3application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWheatingtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
S7
S8
P1
P2
P3
P4
M1
DHWtanktemperaturesensor,upper
DHWchargingtemperaturesensor,circuit2
DHWtanktemperaturesensor,lower
Circulationpump,heating,circuit1
DHWheatingpump,circuit2
Circulationpump,DHW,circuit2
DHWchargingpump,circuit2
Motorizedcontrolvalve(3-pointcontrolled),
circuit2
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),
circuit1
Alternative:Thermoactuator(DanfosstypeABV)
A/B
Internal/externalconnectionsforDHWcirculation
AQ192386469094en-010802
©Danfoss|2021.12|11
OperatingGuideECLComfort210/296/310,applicationA247/A347
TypicalA347.1application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7Roomtemperaturesensor,circuit1
S8
S10
DHWtanktemperaturesensor,lower
Externalvoltage(0–10V)forexternalsettingof
desiredflowtemperature,circuit1
P1
P2
P3
M1
Circulationpump,heating,circuit1
Chargingpump,DHW,circuit2
Circulationpump,DHW,circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
A1
A/B
Alarm
Internal/externalconnectionsforDHWcirculation
12|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
TypicalA347.2application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWheatingtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7Roomtemperaturesensor,circuit1
S8
S9
S10
DHWtanktemperaturesensor,lower
DHWchargingtemperaturesensor,circuit2
Externalvoltage(0–10V)forexternalsettingof
desiredflowtemperature,circuit1
P1
P2
P3
M1
Circulationpump,heating,circuit1
Chargingpump,DHW,circuit2
Circulationpump,DHW,circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
A1
A/B
Alarm
Internal/externalconnectionsforDHWcirculation
AQ192386469094en-010802
©Danfoss|2021.12|13
OperatingGuideECLComfort210/296/310,applicationA247/A347
TypicalA347.3application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWchargingtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7Roomtemperaturesensor,circuit1
S8
S10
DHWcirculationreturntemperaturesensor
Externalvoltage(0–10V)forexternalsettingof
desiredflowtemperature,circuit1
P1
P2
P3
M1
Circulationpump,heating,circuit1
Chargingpump,DHW,circuit2
Circulationpump,DHW,circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit2
Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1
Alternative:Thermoactuator(DanfosstypeABV)
A1
A/B
Alarm
Internal/externalconnectionsforDHWcirculation
14|©Danfoss|2021.12
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
AQ192386469094en-010802
©Danfoss|2021.12|15
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
Factorysettingsinthesubtypeswillrunthemostapplication
examples.Someoftheapplicationexamplesneedchangeof
dedicatedsettings.
Seethedocumentationforapplicationsandsubtypes,delivered
withtheapplicationkey.
A247.1,ex.a
A347.1,ex.a
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
A247.1,ex.b
A347.1,ex.b
Nospecialsettingsrequired.
A247.1,ex.c
A347.1,ex.c
Circuit2mustbeabletoreceivetheheatdemandfromcircuit1.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
IDno.:
12054
12054
IDno.:
11017
12017
Recommended
setting:
OFF
ON
Recommended
setting:
OFF
3K*
*Thisvalueisaddedtotheheatdemandvaluefromcircuit1.
16|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
A247.2,ex.a
A347.2,ex.a
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
A247.2,ex.b
A347.2,ex.b
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit2.
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
IDno.:
12054
12054
IDno.:
11017
12017
Recommended
setting:
OFF
ON
Recommended
setting:
3K*
OFF
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
12054
12054
Recommended
setting:
OFF
ON
AQ192386469094en-010802
©Danfoss|2021.12|17
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
A247.2,ex.c
A347.2,ex.c
Circuit2mustbeabletoreceivetheheatdemandfromcircuit1.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit1.
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
11017
12017
IDno.:
12054
12054
Recommended
setting:
OFF
3K*
Recommended
setting:
OFF
ON
18|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
A247.3,ex.a
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
A247.3,ex.b
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit2.
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
IDno.:
12054
12054
IDno.:
11017
12017
Recommended
setting:
OFF
ON
Recommended
setting:
3K*
OFF
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
12054
12054
Recommended
setting:
OFF
ON
AQ192386469094en-010802
©Danfoss|2021.12|19
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
A247.3,ex.c
Circuit2mustbeabletoreceivetheheatdemandfromcircuit1.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit1.
DHWcirculationpipecanbeconnectedtotheDHWtankat'A'
forinternalcirculationortotheheat-exchangerat'B'forexternal
circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
A347.3,ex.a
Nospecialsettingsrequired.
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
11017
12017
IDno.:
12054
12054
Recommended
setting:
OFF
3K*
Recommended
setting:
OFF
ON
20|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
•onawall
•onaDINrail(35mm)
ECLComfort296canbemounted
•inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
AQ192386469094en-010802
©Danfoss|2021.12|21
OperatingGuideECLComfort210/296/310,applicationA247/A347
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
22|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
•Mountingonawall,ECA30/31
•Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
AQ192386469094en-010802
©Danfoss|2021.12|23
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
24|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
AQ192386469094en-010802
©Danfoss|2021.12|25
OperatingGuideECLComfort210/296/310,applicationA247/A347
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
26|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage,
relaycontactsandtriacoutputsdonothavemutualsafetydistanceof
minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic
separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis
recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby
meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
AQ192386469094en-010802
©Danfoss|2021.12|27
OperatingGuideECLComfort210/296/310,applicationA247/A347
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
28|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic
relay)terminals
4(2)A/24Va.c.
(4Aforohmicload,2Afor
inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power
suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230
Va.c.from24Va.c.
AQ192386469094en-010802
©Danfoss|2021.12|29
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.5.3Electricalconnections,safetythermostats,230Va.c.or24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Theconnectiondiagramsshowvarioussolutions/examples:
Safetythermostat,1–stepclosing:
Motorizedcontrolvalvewithoutsafetyfunction
Safetythermostat,1–stepclosing:
Motorizedcontrolvalvewithsafetyfunction
Safetythermostat,2–stepclosing:
Motorizedcontrolvalvewithsafetyfunction
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe
motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the
motorizedcontrolvalveisclosedgradually.Atahighertemperature
(theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve
closesthevalveimmediately.