Danfoss A247, A347 Operating guide

OperatingGuide
ECLComfort210/296/310,applicationA247/A347

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................15
2.4Placingthetemperaturesensors................................25
2.5Electricalconnections.............................................27
2.6InsertingtheECLApplicationKey..............................36
2.7Checklist............................................................43
2.8Navigation,ECLApplicationKeyA247/A347................44
3.0Dailyuse.........................................................50
3.1Howtonavigate...................................................50
3.2Understandingthecontrollerdisplay..........................51
3.3Ageneraloverview:Whatdothesymbolsmean?...........55
3.4Monitoringtemperaturesandsystem
components........................................................56
3.5Influenceoverview................................................57
3.6Manualcontrol.....................................................58
3.7Schedule............................................................59
4.0Settingsoverview............................................60
5.0Settings...........................................................63
5.1IntroductiontoSettings..........................................63
5.2Flowtemperature..................................................64
5.3Roomlimit..........................................................68
5.5Flow/powerlimit.................................................76
5.6Optimization........................................................81
5.7Controlparameters................................................88
5.8Application.........................................................93
5.9Heatcut-out......................................................104
5.10Tanktemperature................................................107
5.11Alarm..............................................................112
5.12Alarmoverview..................................................115
5.13Anti-bacteria......................................................116
6.0Commoncontrollersettings............................118
6.1Introductionto‘Commoncontrollersettings’..............118
6.2Time&Date.......................................................119
6.3Holiday............................................................120
6.4Inputoverview...................................................122
6.5Log.................................................................123
6.6Outputoverride..................................................124
6.7Keyfunctions.....................................................125
6.8System.............................................................127
7.0Miscellaneous................................................134
7.1ECA30/31setupprocedures.................................134
7.2Overridefunction................................................142
7.3Severalcontrollersinthesamesystem......................145
7.4Frequentlyaskedquestions....................................148
7.5Definitions........................................................151
7.6Type(ID6001),overview.......................................155
7.7Automatic/manualupdateoffirmware.....................156
7.8ParameterIDoverview..........................................157
©Danfoss|2021.12AQ192386469094en-010802|1
OperatingGuideECLComfort210/296/310,applicationA247/A347

1.1Importantsafetyandproductinformation

ThisInstallationGuideisassociatedwithECLApplicationKeyA247 (ordercodeno.087H3808).
TheA247Keycontains6subtypes: A247.1…A247.3(applicableinECLComfort210and310) A347.1…A347.3(applicableinECLComfort310)
A247.1:HeatingandDHWcharging/heating
A247.2:HeatingandDHWcharging
A247.3:HeatingandadvancedDHWcharging
A347.1:HeatingandDHWcharging/heating.M-busoptional
A347.2:HeatingandDHWcharging.M-busoptional
A347.3:HeatingandDHWcharging.MonitoringofDHW circulationreturn.M-busoptional
TheA247applicationkeyalsocontainsaFloor(Screed)Drying Program.Seeseparatedocumentation. SeetheMountingGuide(deliveredwiththeapplicationkey)for applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort210forbasic solutionsandinECLComfort310foradvancedsolutions,for exampleM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA247complieswithECLComfort210and ECLComfort310controllersasofsoftwareversion1.11(visible atstart-upofthecontrollerandin'Commoncontrollersettings' in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe connectedandthebuilt-inroomtemperaturesensorcanbe utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O moduleECA32(ordercodeno.087H3202)canbeusedforextra datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool". Navigation:Danfoss.com>Products&Solutions>DistrictHeating andCooling>T ools&Software>ECLTool. TheURLis:
https://www.danfoss.com/en/service-and-support/downloads/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
AdditionaldocumentationforECLComfort210and310,modules andaccessoriesisavailableonhttp://danfoss.com/.
2|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volta.c.(087H3220)
forECLComfort296,230volta.c.(087H3240)
forECLComfort310,230volta.c.and24volta.c(087H3230)
AdditionaldocumentationforECLComfort210,296and310, modulesandaccessoriesisavailableonhttp://danfoss.com/.
DocumentationforECLPortal:Seehttps://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AQ192386469094en-010802
©Danfoss|2021.12|3
OperatingGuideECLComfort210/296/310,applicationA247/A347
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310/311:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
4|©Danfoss|2021.12
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
2
Circuit2Parameterno.
174
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
AQ192386469094en-010802
©Danfoss|2021.12|5
OperatingGuideECLComfort210/296/310,applicationA247/A347

2.0Installation

2.1Beforeyoustart

Theapplications(subtypes)intheA247applicationkeyarevery flexibleandalmostidentical.However,someapplicationshave extrafunctionswhicharedescribedseparately.
Thesearethebasicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperatureS1andthe desiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredroomtemperature). InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM2isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingofthe motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent oftheoutdoortemperature.Typically,thelowertheoutdoor temperature,thehighertheacceptedreturntemperature.
Ifthemeasuredroomtemperature(RemotecontrolunitECA30/
31)doesnotequalthedesiredroomtemperature,thedesiredflow temperaturecanbeadjusted.
Thecirculationpump(P1)isONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
A247.1,A247.2: Aconnectedfloworenergymeterbasedonpulses(S7)canlimit thefloworenergytoasetmaximumvalue.Furthermore,the limitationcanbeinrelationtotheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedflow/power.
WhenthesubtypesA347.1-A347.3areused(onlyinECLComfort
310),theflow/powersignalcancomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
TypicalA247.1application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
S2DHWreturntemperaturesensor,circuit2
S3
S4
S5Returntemperaturesensor,circuit1
S6
S7
S8
P1
P2
P3
M1
M2
A1
A/B
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
DHWtanktemperaturesensor,upper
Flow/energymeter(pulsesignal)
DHWtanktemperaturesensor,lower
Circulationpump,heating,circuit1
Chargingpump,DHW,circuit2
Circulationpump,DHW,circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit2 Alternative:Thermoactuator(DanfosstypeABV)
Motorizedcontrolvalve(3-pointcontrolled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
Alarm
Internal/externalconnectionsforDHWcirculation
Analarmcanbeactivatediftheactualflowtemperaturediffers fromthedesiredflowtemperature.
6|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
A247.1,A247.2,A247.3: TheroomtemperaturesignalcanbeachievedfromtheRemote ControlUnitECA30/31,ifconnected.
A347.1,A347.2,A347.3: Theroomtemperaturesignalcanbeachievedfromtheroom temperaturesensorS7ortheRemoteControlUnitECA30/31,if connected.
A347.1,A347.2,A347.3: Thedesiredflowtemperatureofheatingcircuit1can,viaS10,be controlledbymeansofanexternalvoltageintherange0-10volt.
Heatingcircuit,ingeneral:
Exerciseofcirculationpumpandcontrolvalveinperiodswithout heatingdemandcanbearranged.
AQ192386469094en-010802
©Danfoss|2021.12|7
OperatingGuideECLComfort210/296/310,applicationA247/A347
DomesticHotWater ,DHW(circuit2):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredDHWtemperature).
Chargingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthe charging-starttemperature,theDHWchargingpump(P2)is switchedON. Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain thechargingtemperatureatS4. Adelayedstartofchargingpumpcanbearranged.Also,itcan bearrangedthatthestartofthechargingpumpdependson thechargingtemperature.Inthiscase,S4mustbeplacedinthe heat-exchanger.
TheDHWchargingtemperatureisdeterminedbythedesiredDHW temperatureatS6plusthesetchargingdifference.Thecharging temperatureistypically5–10degreeshigherthanthedesired DHWtemperature.
Thereturntemperature,whentheDHWheating/chargingis active,canbelimitedtoafixedvalue.
A247.2: WhenthemeasuredDHWtemperatureS6getslowerthanthe charging-starttemperature,theDHWheatingpump(P2)is switchedONandthemotorizedcontrolvalveM1iscontrolledin ordertomaintainthechargingtemperatureatS4.Thecharging pumpisswitchedONwhentheS4temperatureisacceptable.
A247.1,examplea
Charging-starttemperature:
DesiredDHWtemperature+Startdifference. Example: 50°C+(-3K)=47°C
A247.3: TheDHWheatingcircuithasapreheatingcircuit,wheretheDHW heatingtemperatureatS4isadaptedtothedesiredDHWcharging temperatureatS7.IftheDHWchargingtemperatureatS7cannot bereached,theECLcontrollergraduallyincreasesthedesiredDHW heatingtemperatureatS4inordertoobtaintheDHWcharging temperature.TheECLcontrollerrememberstheadaptedS4 temperature.Amaximumtemperaturevaluecanbeset.
A347.2: TheDHWheatingcircuithasapreheatingcircuit,wheretheDHW heatingtemperatureatS4isadaptedtothedesiredDHWcharging temperatureatS9.IftheDHWchargingtemperatureatS9cannot bereached,theECLcontrollergraduallyincreasesthedesiredDHW heatingtemperatureatS4inordertoobtaintheDHWcharging temperature.TheECLcontrollerrememberstheadaptedS4 temperature.Amaximumtemperaturevaluecanbeset.
8|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
Chargingstop,DHWtankwith1temperaturesensor:
WhenthemeasuredDHWtemperatureS6getshigherthan thecharging-stoptemperature,theDHWchargingpumpP2is switchedOFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors:
WhenthemeasuredDHWtemperatureS6gets2Khigherthan thecharging-starttemperatureANDthelowertanktemperature S8getshigherthanthecharging-stoptemperature,theDHW chargingpumpP2isswitchedOFF.Apost-runtimecanbeset.
DHWcirculation
InchargingapplicationstheDHWcirculationcanbethrough theDHWtank(connectionA)orthroughtheheat-exchanger (connectionB). ThesolutionwithconnectionAresultsinclosingofthemotorized controlvalveaftertheDHWtankchargingprocedure. ThesolutionwithconnectionBstopstheDHWchargingpump aftertheDHWtankchargingprocedure.Thetemperatureatthe chargingtemperaturesensorismaintainedaccordingtothevalue ofthedesiredDHWtemperatureinordertocompensateforthe heatlossintheDHWcirculationpipe.
Flow/powerlimitation
A247.1,A247.2: Aconnectedfloworenergymeterbasedonpulses(S7)canlimit thefloworpowertoasetmaximumvalue.
Charging-stoptemperature:
DesiredDHWtemperature+Stopdifference. Example,S6only: 50°C+(3K)=53°C Example,S6andS8: 50°C+(-8K)=42°C
A347.1,A347.2,A347.3(onlyinECLComfort310): Theflow/powersignalcancomeasanM-bussignal.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek. TheDHWcirculationpumpP3hasaweekscheduleforupto3 ON-periodsperday. IfthedesiredDHWtemperaturecannotbereached,theheating circuitcanbeclosedgraduallytoallowmoreenergytotheDHW circuit.
AQ192386469094en-010802
©Danfoss|2021.12|9
OperatingGuideECLComfort210/296/310,applicationA247/A347
A247,ingeneral
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto oneECLcontrollerinordertocontroltheECLcontrollerremotely.
HolidayprogramsarepresentforHeatingandDHWcircuits. Besides,aholidayprogramispresentfortheentirecontroller.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout heatingdemandcanbearranged.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL 485businordertoutilizecommonoutdoortemperaturesignal, timeanddatesignals.TheECLcontrollersintheECL485system canworkinmaster-slavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beused tooverridethescheduletoafixed'Comfort' ,'Saving','Frost protection'or'Constanttemperature'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished. TheM-busdata(ECLComfort310)canfurthermorebetransferred totheModbuscommunication.
Alarm
A247.1: AlarmA1(=relay4)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow temperature
ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview)
A347.1,A347.2,A347.3: AlarmA1(=relay6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow temperature
ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview)
WhentheA247hasbeenuploadedtheECLComfortcontroller startsinManualmode.Thiscanbeusedforcheckingthecontrolled componentsforcorrectfunctionality.
Inputconfiguration
Inputs(asfromS7andup)whicharenotreservedforthe applicationcanbeconfiguredtobePt1000,0-10Volt,frequency (pulsecounter)ordigitalinput.Thisfeaturemakesitpossibleto monitorextrasignals,suchastemperatures,pressures,ON/OFF conditions,viaModbusandECLPortal. TheconfigurationisdonebymeansoftheECLTool(freesoftware fordownload)ordirectlyinadedicatedmenuintheECLPortalor theconnectionforModbus(BMS/SCADA).
TypicalA247.2application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
S7
S8
P1
P2
P3
P4
M1
DHWtanktemperaturesensor,upper
Flow/energymeter(pulsesignal)
DHWtanktemperaturesensor,lower
Circulationpump,heating,circuit1
DHWheatingpump,circuit2
Circulationpump,DHW,circuit2
DHWchargingpump,circuit2
Motorizedcontrolvalve(3-pointcontrolled), circuit2 Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled), circuit1 Alternative:Thermoactuator(DanfosstypeABV)
A/B
Internal/externalconnectionsforDHWcirculation
10|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
TypicalA247.3application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWheatingtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
S7
S8
P1
P2
P3
P4
M1
DHWtanktemperaturesensor,upper
DHWchargingtemperaturesensor,circuit2
DHWtanktemperaturesensor,lower
Circulationpump,heating,circuit1
DHWheatingpump,circuit2
Circulationpump,DHW,circuit2
DHWchargingpump,circuit2
Motorizedcontrolvalve(3-pointcontrolled), circuit2 Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled), circuit1 Alternative:Thermoactuator(DanfosstypeABV)
A/B
Internal/externalconnectionsforDHWcirculation
AQ192386469094en-010802
©Danfoss|2021.12|11
OperatingGuideECLComfort210/296/310,applicationA247/A347
TypicalA347.1application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWflowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7Roomtemperaturesensor,circuit1
S8
S10
DHWtanktemperaturesensor,lower
Externalvoltage(0–10V)forexternalsettingof desiredflowtemperature,circuit1
P1
P2
P3
M1
Circulationpump,heating,circuit1
Chargingpump,DHW,circuit2
Circulationpump,DHW,circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit2 Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
A1
A/B
Alarm
Internal/externalconnectionsforDHWcirculation
12|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
TypicalA347.2application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWheatingtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7Roomtemperaturesensor,circuit1
S8
S9
S10
DHWtanktemperaturesensor,lower
DHWchargingtemperaturesensor,circuit2
Externalvoltage(0–10V)forexternalsettingof desiredflowtemperature,circuit1
P1
P2
P3
M1
Circulationpump,heating,circuit1
Chargingpump,DHW,circuit2
Circulationpump,DHW,circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit2 Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
A1
A/B
Alarm
Internal/externalconnectionsforDHWcirculation
AQ192386469094en-010802
©Danfoss|2021.12|13
OperatingGuideECLComfort210/296/310,applicationA247/A347
TypicalA347.3application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
S2DHWreturntemperaturesensor,circuit2
S3
S4
Flowtemperaturesensor,circuit1
DHWchargingtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7Roomtemperaturesensor,circuit1
S8
S10
DHWcirculationreturntemperaturesensor
Externalvoltage(0–10V)forexternalsettingof desiredflowtemperature,circuit1
P1
P2
P3
M1
Circulationpump,heating,circuit1
Chargingpump,DHW,circuit2
Circulationpump,DHW,circuit2
Motorizedcontrolvalve(3-pointcontrolled),circuit2 Alternative:Thermoactuator(DanfosstypeABV)
M2
Motorizedcontrolvalve(3-pointcontrolled),circuit1 Alternative:Thermoactuator(DanfosstypeABV)
A1
A/B
Alarm
Internal/externalconnectionsforDHWcirculation
14|©Danfoss|2021.12
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
AQ192386469094en-010802
©Danfoss|2021.12|15
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
Factorysettingsinthesubtypeswillrunthemostapplication examples.Someoftheapplicationexamplesneedchangeof dedicatedsettings.
Seethedocumentationforapplicationsandsubtypes,delivered withtheapplicationkey.
A247.1,ex.a A347.1,ex.a
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
A247.1,ex.b A347.1,ex.b
Nospecialsettingsrequired.
A247.1,ex.c A347.1,ex.c
Circuit2mustbeabletoreceivetheheatdemandfromcircuit1.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
IDno.:
12054
12054
IDno.:
11017
12017
Recommended setting:
OFF
ON
Recommended setting:
OFF
3K*
*Thisvalueisaddedtotheheatdemandvaluefromcircuit1.
16|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
A247.2,ex.a A347.2,ex.a
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
A247.2,ex.b A347.2,ex.b
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit2.
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
IDno.:
12054
12054
IDno.:
11017
12017
Recommended setting:
OFF
ON
Recommended setting:
3K*
OFF
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
12054
12054
Recommended setting:
OFF
ON
AQ192386469094en-010802
©Danfoss|2021.12|17
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
A247.2,ex.c A347.2,ex.c
Circuit2mustbeabletoreceivetheheatdemandfromcircuit1.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit1.
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
11017
12017
IDno.:
12054
12054
Recommended setting:
OFF
3K*
Recommended setting:
OFF
ON
18|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
A247.3,ex.a
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
A247.3,ex.b
Circuit1mustbeabletoreceivetheheatdemandfromcircuit2.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit2.
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
IDno.:
12054
12054
IDno.:
11017
12017
Recommended setting:
OFF
ON
Recommended setting:
3K*
OFF
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
12054
12054
Recommended setting:
OFF
ON
AQ192386469094en-010802
©Danfoss|2021.12|19
OperatingGuideECLComfort210/296/310,applicationA247/A347
Adviceforsettings:
A247.3,ex.c
Circuit2mustbeabletoreceivetheheatdemandfromcircuit1.
Issue:
Heatingcircuit(1):
Heatdemand
DHWcircuit(2):
Heatdemand
*Thisvalueisaddedtotheheatdemandvaluefromcircuit1.
DHWcirculationpipecanbeconnectedtotheDHWtankat'A' forinternalcirculationortotheheat-exchangerat'B'forexternal circulation.
Issue:
DHWcircuit(2):
InternalDHWcirculation
DHWcircuit(2):
ExternalDHWcirculation
A347.3,ex.a
Nospecialsettingsrequired.
Navigation:
MENU\Settings\Application:'Demandoffset'
MENU\Settings\Application:'Demandoffset'
Navigation:
MENU\Settings\Application:'Cont.Tcontrol'
MENU\Settings\Application:'Cont.Tcontrol'
IDno.:
11017
12017
IDno.:
12054
12054
Recommended setting:
OFF
3K*
Recommended setting:
OFF
ON
20|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ192386469094en-010802
©Danfoss|2021.12|21
OperatingGuideECLComfort210/296/310,applicationA247/A347
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
22|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
AQ192386469094en-010802
©Danfoss|2021.12|23
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
24|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
AQ192386469094en-010802
©Danfoss|2021.12|25
OperatingGuideECLComfort210/296/310,applicationA247/A347
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
26|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
AQ192386469094en-010802
©Danfoss|2021.12|27
OperatingGuideECLComfort210/296/310,applicationA247/A347
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
28|©Danfoss|2021.12
AQ192386469094en-010802
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
AQ192386469094en-010802
©Danfoss|2021.12|29
OperatingGuideECLComfort210/296/310,applicationA247/A347
2.5.3Electricalconnections,safetythermostats,230Va.c.or24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Theconnectiondiagramsshowvarioussolutions/examples:
Safetythermostat,1–stepclosing: Motorizedcontrolvalvewithoutsafetyfunction
Safetythermostat,1–stepclosing: Motorizedcontrolvalvewithsafetyfunction
Safetythermostat,2–stepclosing: Motorizedcontrolvalvewithsafetyfunction
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
30|©Danfoss|2021.12
AQ192386469094en-010802