Danfoss A237, A337 Operating guide

OperatingGuide
ECLComfort210/296/310,applicationA237/A337

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................13
2.4Placingthetemperaturesensors................................20
2.5Electricalconnections.............................................22
2.6InsertingtheECLApplicationKey..............................30
2.7Checklist............................................................37
2.8Navigation,ECLApplicationKeyA237/A337................38
3.0Dailyuse.........................................................44
3.1Howtonavigate...................................................44
3.2Understandingthecontrollerdisplay..........................45
3.3Ageneraloverview:Whatdothesymbolsmean?...........49
3.4Monitoringtemperaturesandsystem
components........................................................50
3.5Influenceoverview................................................51
3.6Manualcontrol.....................................................52
3.7Schedule............................................................53
4.0Settingsoverview............................................54
5.0Settings...........................................................57
5.1IntroductiontoSettings..........................................57
5.2Flowtemperature/Inlettemperature.........................58
5.3Roomlimit..........................................................62
5.5Flow/powerlimit.................................................70
5.6Optimization........................................................75
5.7Controlparameters................................................81
5.8Application.........................................................85
5.10Tanktemperature..................................................99
5.11Alarm..............................................................104
5.12Alarmoverview..................................................107
5.13Anti-bacteria......................................................108
6.0Commoncontrollersettings............................110
6.1Introductionto‘Commoncontrollersettings’..............110
6.2Time&Date.......................................................111
6.3Holiday............................................................112
6.4Inputoverview...................................................114
6.5Log.................................................................115
6.6Outputoverride..................................................116
6.7Keyfunctions.....................................................117
6.8System.............................................................119
7.0Miscellaneous................................................126
7.1ECA30/31setupprocedures.................................126
7.2Overridefunction................................................134
7.3Severalcontrollersinthesamesystem......................137
7.4Frequentlyaskedquestions....................................140
7.5Definitions........................................................143
7.6Type(ID6001),overview.......................................147
7.7Automatic/manualupdateoffirmware.....................148
7.8ParameterIDoverview..........................................149
©Danfoss|2021.02AQ000086479358en-010501|1
OperatingGuideECLComfort210/296/310,applicationA237/A337

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA237 (ordercodeno.087H3806).
TheECLApplicationKeyA237contains4subtypes:
A237.1andA237.2(applicableinECLComfort210,296and310)
A337.1andA337.2(applicableinECLComfort310)
A237.1:HeatingandDHWheating
A237.2:HeatingandDHWcharging
A337.1:HeatingandDHWheating.Externalsetpointoptional (0-10V)
A337.2:HeatingandDHWcharging.Externalsetpointoptional (0-10V)
TheA237applicationkeyalsocontainsaFloor(Screed)Drying Program.Seeseparatedocumentation.(InEnglishandGerman languageonly).
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationexamplesandelectricalconnections.
Thedescribedfunctionsarerealizedin:
ECLComfort210forbasicsolutions
ECLComfort296forbasicsolutions,M-busandEthernet (Internet)communication
ECLComfort310foradvancedsolutions,M-bus,Modbusand Ethernet(Internet)communication.
TheApplicationKeyA237complieswithECLComfort210/310 controllersasoffirmwareversion1.11. TheApplicationKeyA237compliesalsowithECLComfort296 controllersasoffirmwareversion1.58. Thefirmware(controllersoftware)versionisvisibleatstart-upof thecontrollerandin‘Commoncontrollersettings’in‘System’ .
UptotwoRemoteControlUnits,ECA30orECA31,canbe connectedforremotemonitoringandsetting.Thebuilt-inroom temperaturesensorcanbeutilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O moduleECA32(ordercodeno.087H3202)canbeusedforextra datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating andCooling>T ools&Software>ECLTool.
TheURLis:
https://www.danfoss.com/en/service-and-support/downloads/
2|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
TheInternalI/OmoduleECA32isplacedinthebasepartforECL Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volt(087H3240)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210,296and310, modulesandaccessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
AQ000086479358en-010501
©Danfoss|2021.02|3
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
4|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
1
-
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
2
Circuit2Parameterno.
174
AQ000086479358en-010501
©Danfoss|2021.02|5
OperatingGuideECLComfort210/296/310,applicationA237/A337

2.0Installation

2.1Beforeyoustart

Thetwoapplications,A237.1/A337.1arealmostidentical. However,A337.1hassomeextrafunctionswhicharedescribed additionally.
TheapplicationsA237.1/A337.1areveryflexible.Thesearethe basicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature. Thelowertheoutdoortemperature,thehigherthedesiredflow temperature.
Bymeansofaweekschedule,theheatingcircuitcanbein ‘Comfort’or‘Saving’mode.Theweekschedulecanhaveupto3 ‘Comfort’periods/day.Avalueforthedesiredroomtemperature canbesetineachofthemodes. InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
ThereturntemperatureS5canbelimited,forexamplenottobe toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingof themotorizedcontrolvalve.Furthermore,thereturntemperature limitationcanbedependentontheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedreturntemperature.Inboiler-basedheatingsupplythe returntemperatureshouldnotbetoolow(sameadjustment procedureasabove).
Ifthemeasuredroomtemperature(directlyconnectedtemperature sensorESM-10(S2)orRemotecontrolunitECA30/31)doesnot equalthedesiredroomtemperature,thedesiredflowtemperature canbeadjusted.
ThecirculationpumpP1isONatheatdemandoratfrost protection.ThecirculationpumpP1canbeswitchedOFFwhen heatingtheDHW.Ifthesystemhasachangeovervalve(P2/M2) betweentheheatingandDHWcircuit,thecirculationpumpP1 isONwhenheatingtheDHW.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
TypicalA237.1/A337.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296/ 310
S1
S2Roomtemperaturesensor
S3
S5Returntemperaturesensor,circuit1
S6
S7
S8
P1
P2DHWpump,circuit2
P3
M1
A1
ElectroniccontrollerECLComfort210,296or310
Outdoortemperaturesensor
Flowtemperaturesensor,circuit1
DHWtanktemperaturesensor,upper
Flow/energymeter(pulsesignal)
DHWtanktemperaturesensor,lower
Circulationpump,heating,circuit1
DHWcirculationpump,circuit2
Motorizedcontrolvalve(3-pointcontrolled). Alternative:Thermoactuator(DanfosstypeABV)
Alarm
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit thefloworenergytoasetmaximumvalue.Furthermore,the limitationcanbeinrelationtotheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedflow/power.
Thefrostprotectionmodemaintainsaselectableflowtemperature value,forexample10°C.
Analarmcanbeactivatediftheactualflowtemperaturediffers fromthedesiredflowtemperature.
6|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
A237.1,ex.a,A337.1,ex.a
DuringDHWheating,thecirculationpumpP1intheheatingcircuit can:
beswitchedOFF(DHWprioritymode)
or
remainON,aslongastheheatingtemperatureatS3doesnot differmorethanasetvaluefromthedesiredtemperature (dependentparallelmode)
or
becontinuouslyON.Thismeanssametemperatureinthe heatingcircuitastheDHWheatingtemperature(parallel mode).
A237.1usedinECL296/310
Theflow/powersignalcancomeasapulsesignaloranM-bus signal.
A337.1
Thedesiredflowtemperatureoftheheatingcircuitcan,viaS10,be controlledbymeansofanexternalvoltageintherange0-10volt.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
AconnectedfloworenergymeterbasedonM-bussignalcan limitthefloworpowertoasetmaximumvalue.Furthermore,the limitationcanbeinrelationtotheoutdoortemperature. Typically,thelowertheoutdoortemperature,thehigherthe acceptedflow/power. M-busdatacanbetransferredtotheModbuscommunication.
Heatingingeneral
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout heatingdemandcanbearranged.
AQ000086479358en-010501
©Danfoss|2021.02|7
OperatingGuideECLComfort210/296/310,applicationA237/A337
DHW(circuit2):
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’ or‘Saving’mode.Theweekschedulecanhaveupto3‘Comfort’ periods/day.AvalueforthedesiredDHWtemperaturecanbe setineachofthemodes.
DHWheatingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthestart temperature,theheatingcirculationpumpP1isswitchedOFFand theDHWheatingpumpP2isswitchedON. ThemotorizedcontrolvalveM1iscontrolledinordertomaintain theheatingtemperatureatS3. AdelayedstartoftheDHWheatingpumpcanbearranged.Inthis case,S3mustbeplacedintheheat-exchanger. TheDHWheatingtemperatureisdeterminedbythedesiredDHW temperatureatS6plusthesetchargingdifference.Thecharging temperatureistypically5-10degreeshigherthanthedesired DHWtemperature.
ThereturntemperatureS5,whentheDHWheating/chargingis active,canbelimitedtoasetvalue.
Chargingstop,DHWtankwith1temperaturesensor
WhenthemeasuredDHWtemperatureS6getshigherthanthe charging-stoptemperature,theDHWheatingpumpP2isswitched OFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors
A237.1/A337.1examplea:
A237.1/A337.1exampleb:
A237.1/A337.1examplec:
WhenthemeasuredDHWtemperatureS6gets2Khigherthanthe heating-starttemperatureANDthelowertanktemperatureS8gets higherthantheheating-stoptemperature,theDHWheatingpump P2isswitchedOFF.Apost-runtimecanbeset.
Iftheinstallationhasachangeovervalve(P2/M2),alsocalled priority-valve,betweentheheatingandtheDHWcircuits,the changeovervalveisactivatedatDHWheatingdemand.The circulationpump(P1)isONwhenheatingtheDHW.
Parallelmodeintwo-pumpapplications: Ifthechargingtemperaturehasavalueclosetothedesiredflow temperatureintheheatingcircuit,thecirculationpump(P1)inthe heatingcircuitwillnotbeswitchedOFFduringDHWheating.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
TheDHWcircuitcanbeconnectedprimarilyandthevalve‘P2/ M2’operatesasON/OFFvalve.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3 ON-periods/day.
TheDHWcirculationpumpP3canbeswitchedOFFduringDHW heating/charging.
A237.1/A337.1exampled:
8|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
ApplicationA237.1andA337.1,ingeneral
Unusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished. InECLComfort296/310theM-busdatacanfurthermorebe transferredtotheModbuscommunication.
Thetwoapplications,A237.2/A337.2arealmostidentical. However,A337.2hassomeextrafunctionswhicharedescribed additionally.
TheapplicationsA237.2/A337.2areveryflexible.Thesearethe basicprinciples:
Heating(circuit1):
Theheatingcircuitworksasdescribedpreviously.
A237.2,ex.a,A337.2,ex.a
DuringDHWheating,thecirculationpumpP1intheheatingcircuit can:
beswitchedOFF(DHWprioritymode)
or
remainON,aslongastheheatingtemperatureatS3doesnot differmorethanasetvaluefromthedesiredtemperature (dependentparallelmode)
or
becontinuouslyON.Thismeanssametemperatureinthe heatingcircuitastheDHWheatingtemperature(parallel mode).
A237.2usedinECL296
Theflow/powersignalcancomeasapulsesignaloranM-bus signal.
A337.2
Thedesiredflowtemperatureoftheheatingcircuitcan,viaS10,be controlledbymeansofanexternalvoltageintherange0-10volt.
TypicalA237.2/A337.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296/
ElectroniccontrollerECLComfort210,296or310
310 S1
Outdoortemperaturesensor
S2Roomtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S5Returntemperaturesensor,circuit1
S6
S7
S8
P1
DHWtanktemperaturesensor,upper
Flow/energymeter(pulsesignal)
DHWtanktemperaturesensor,lower
Circulationpump,heating,circuit1
P2DHWpump,circuit2
P3
P4
M1
DHWcirculationpump,circuit2
DHWchargingpump,circuit2
Motorizedcontrolvalve(3-pointcontrolled). Alternative:Thermoactuator(DanfosstypeABV).
A1
Alarm(A337.2only)
AQ000086479358en-010501
©Danfoss|2021.02|9
OperatingGuideECLComfort210/296/310,applicationA237/A337
DHW(circuit2):
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’ or‘Saving’mode.Theweekschedulecanhaveupto3‘Comfort’ periods/day.AvalueforthedesiredDHWtemperature canbesetineachofthemodes.
DHWchargingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthe charging-starttemperature,theheatingcirculationpumpP1is switchedOFFandtheDHWheatingpumpP2isswitchedON.
AdelayedstartoftheDHWchargingpumpP4canbearranged. Also,itcanbearrangedthatthestartofthechargingpump dependsontheDHWheatingtemperature.Inthiscase,S4mustbe placedintheheat-exchanger.
TheDHWheatingtemperatureisdeterminedbythedesiredDHW temperatureatS6plusthesetchargingdifference.Thecharging temperatureistypically5-10degreeshigherthanthedesired DHWtemperature.
ThereturntemperatureS5,whentheDHWheating/chargingis active,canbelimitedtoasetvalue.
TheDHWheatingtemperatureatS3isadaptedtothedesiredDHW chargingtemperatureatS4.IftheDHWchargingtemperatureat S4cannotbereached,theECLcontrollergraduallyincreasesthe desiredDHWheatingtemperatureatS3inordertoobtaintheDHW chargingtemperature.TheECLcontrollerrememberstheadapted S3temperature.Amaximumtemperaturevaluecanbeset.
A237.2/A337.2examplea:
A237.2/A337.2exampleb:
ThemotorizedcontrolvalveM1iscontrolledinordertomaintain thechargingtemperatureatS4.
DHWchargingstop,DHWtankwith1temperaturesensor
WhenthemeasuredDHWtemperatureS6getshigherthan thecharging-stoptemperature,theDHWchargingpumpP4is switchedOFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors
WhenthemeasuredDHWtemperatureS6gets2Khigherthan thecharging-starttemperatureANDthelowertanktemperature S8getshigherthanthecharging-stoptemperature,theDHW chargingpumpP4isswitchedOFF.Apost-runtimecanbeset.
Iftheinstallationhasachangeovervalve(P2/M2),alsocalled priority-valve,betweentheheatingandtheDHWcircuits,the changeovervalveisactivatedatDHWheatingdemand.The circulationpump(P1)isONwhenheatingtheDHW.
Parallelmodeintwo-pumpapplications: Ifthechargingtemperaturehasavalueclosetothedesiredflow temperatureintheheatingcircuit,thecirculationpump(P1)inthe heatingcircuitwillnotbeswitchedOFFduringDHWheating.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3 ON-periodsperday.
10|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
ApplicationA237.2andA337.2,ingeneral:
Unusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In ECLComfort310theM-busdatacanfurthermorebetransferred totheModbuscommunication.
A237,ingeneral
Flow/energylimitation.
ECLComfort210: ThesubtypesA237.1andA237.2canutilizetheflow/powersignal comingasapulsesignal.
ECLComfort296: ThesubtypesA237.1andA237.2canutilizetheflow/powersignal comingasapulsesignaloranM-bussignal.
ECLComfort310: ThesubtypesA337.1andA337.2canutilizetheflow/powersignal comingasanM-bussignal.
Alarm
A237.1: AlarmA1(=relay4)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow temperature
ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview)
A237.2: Noalarmfunctionpresent
A337.1,A337.2: AlarmA1(=relay6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow temperature
ifatemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview)
Inputconfiguration
Inputs(asfromS7andup)whicharenotpartoftheapplication canbeconfiguredtobePt1000,0-10VoltorDigitalinput.This featuremakesitpossibletocommunicateextrasignals,suchas temperatures,pressures,ON/OFFconditions,viaModbusand ECLPortal. TheconfigurationisdonebymeansoftheECLTool(freesoftware fordownload)ordirectlyinadedicatedmenuintheECLPortal.
Dependingonsystemtype,itisrecommendedtochangesome factorysettingsindividuallyinordertooptimizethefunctionality. Thesesettingchanges,ifrequired,arelistedbelowthesystem typesinthesection'Identifyingthesystemtype'.
WhentheA237hasbeenuploadedtheECLComfortcontroller startsinManualmode.Thiscanbeusedforcheckingthecontrolled componentsforcorrectfunctionality.
AQ000086479358en-010501
©Danfoss|2021.02|11
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
12|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
AQ000086479358en-010501
©Danfoss|2021.02|13
OperatingGuideECLComfort210/296/310,applicationA237/A337
Adviceforsettings:
Factorysettingsinthesubtypeswillrunthemostapplication examples.Someoftheapplicationexamplesneedchangeof dedicatedsettings.
Seethedocumentationforapplicationsandsubtypes,delivered withtheapplicationkey.
A237.1,ex.a A337.1,ex.a
Twopumpsystem:
Issue:
DHWcircuit(2):
Pump
A237.1,ex.b A337.1,ex.b
OnepumpandChange-overvalvesystem:
Issue:
DHWcircuit(2):
Change-overvalve
A237.1,ex.c A237.1,ex.d A337.1,ex.c A337.1,ex.d
DHWheatingconnectedprimarily:
Issue:
DHWcircuit(2):
Change-overvalve
DHWcircuit(2):
Tankprimarily
Navigation:
MENU\Settings\Application: 'Ch.-o.valve/P'
Navigation:
MENU\Settings\Application: 'Ch.-o.valve/P'
Navigation:
MENU\Settings\Application: 'Ch.-o.valve/P'
MENU\Settings\Application: 'Tank,sec./prim'
IDno.:
12051
IDno.:
12051
IDno.:
12051
12053
Recommended setting:
ON
Recommended setting:
OFF
Recommended setting:
OFF
ON
14|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Adviceforsettings:
A237.2,ex.a A337.2,ex.a
Twopumpsystem:
Issue:
DHWcircuit(2):
Pump
A237.2,ex.b A337.2,ex.b
OnepumpandChange-overvalvesystem:
Issue:
DHWcircuit(2):
Pump
Navigation:
MENU\Settings\Application: 'Ch.-o.valve/P'
Navigation:
MENU\Settings\Application: 'Ch.-o.valve/P'
IDno.:
12051
IDno.:
12051
Recommended setting:
ON
Recommended setting:
OFF
AQ000086479358en-010501
©Danfoss|2021.02|15
OperatingGuideECLComfort210/296/310,applicationA237/A337

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
16|©Danfoss|2021.02
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
AQ000086479358en-010501
©Danfoss|2021.02|17
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
18|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
AQ000086479358en-010501
©Danfoss|2021.02|19
OperatingGuideECLComfort210/296/310,applicationA237/A337

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
20|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ000086479358en-010501
©Danfoss|2021.02|21
OperatingGuideECLComfort210/296/310,applicationA237/A337

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
22|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ000086479358en-010501
©Danfoss|2021.02|23
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.5.2Electricalconnections,Pt1000temperaturesensors
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Sensor
S1
Description
Outdoortemperature sensor*
S2 S3
S4
Roomtemperaturesensor**
Flowtemperaturesensor***
A237.2/A337.2: DHWchargingtemperature sensor
S5Returntemperaturesensor
S6
DHWtanktemperature sensor,upper****
S7
A237.1,A237.2: Flow/energymeter(pulse signal)
S8
DHWtanktemperature sensor,lower
S9
ECL310only: Notused
S10
ECL310only: A337.1,A337.2 Voltagesignal(0-10V)for externalcontrolofdesired flowtemperature
Recommended type
ESMT
ESM-10
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESMB/ ESMU
ESMB/ ESMU
*
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
**
Onlyforroomtemperaturesensorconnection.Theroom temperaturesignalcanalternativelybeavailablefroma RemoteControlUnit(ECA30/31).See'Electricalconnections, ECA30/31'.
***
Theflowtemperaturesensormustalwaysbeconnected inordertohavethedesiredfunctionality.Ifthesensoris notconnectedorthecableisshort-circuited,themotorized controlvalvecloses(safetyfunction).
****
Thissensorisusedifonlyonetanktemperaturesensoris required.
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
24|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
A337.1/A337.2:
Connectionofvoltagesignal(0–10V)forexternalcontrolof desiredflowtemperature
Connectionofflow/energymeterwithpulsesignal
SeetheInstallationGuide(deliveredwiththeapplicationkey).
Theoutputoftheflow/energymetercanbeequippedwithan externalpull-upresistorifaninternalpull-upresistorisnotpresent.
Connectionofswitchforexternaloverride
Pulsebasedsignalforflow/power ,appliedtoinputS7
Formonitoring: Frequencyrangeis0.01-200Hz
Forlimitation: Minimumfrequencyisrecommendedtobe1Hzinordertohavea
stablecontrol.Furthermore,thepulsesmustappearregularly.
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ000086479358en-010501
©Danfoss|2021.02|25
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.5.3Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
26|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ000086479358en-010501
©Danfoss|2021.02|27
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.5.4Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.5Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
28|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.5.6Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
AQ000086479358en-010501
©Danfoss|2021.02|29
OperatingGuideECLComfort210/296/310,applicationA237/A337

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
30|©Danfoss|2021.02
ECLComfort296
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ000086479358en-010501
©Danfoss|2021.02|31
OperatingGuideECLComfort210/296/310,applicationA237/A337
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
32|©Danfoss|2021.02
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
AQ000086479358en-010501
©Danfoss|2021.02|33
OperatingGuideECLComfort210/296/310,applicationA237/A337
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
34|©Danfoss|2021.02
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
AQ000086479358en-010501
©Danfoss|2021.02|35
OperatingGuideECLComfort210/296/310,applicationA237/A337
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
36|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
AQ000086479358en-010501
©Danfoss|2021.02|37
OperatingGuideECLComfort210/296/310,applicationA237/A337

2.8Navigation,ECLApplicationKeyA237/A337

Navigation,applicationA237.1/A337.1(*A237.1only,**A337.1only)
Home
IDno.
MENU ScheduleSelectableSelectable Schedulecirc.PSelectable Settings
Flowtemperature(circuit1) Tanktemperature(circuit2)
Roomlimit
Returnlimit
Flow/powerlimitActualActual
Optimization
Controlpar.
11178 11177 11004
11182 11183 11015 11031 11032 11033 11034 11035 11036 11037 11085 11028
11119 11117 11118 11116 11112 11113 11109 11115 11114 11011 11012 11013 11014 11026 11020 11021 11179 11043 11174 11184 11185 11186 11187 11189 11024
Heating,circuit1DHW,circuit2
Function
Heatcurve12193Chargedifference Temp.max.
Temp.min. DesiredT Ext.desiredT** Infl.—max. Infl.—min. Adapt.time HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority Con.T,ret.Tlim.
Actuallimit HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Pulse* Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Paralleloperation Motorpr. Xp Tn Mrun Nz Min.act.time Actuator
IDno.
12195 12194 12152
12030
12111
Function
Startdifference Stopdifference Max.chargeT
Limit
Limit
38|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Navigation,applicationA237.1/A337.1,continued(*A337.1only)
Home
IDno.
MENU
Settings
HolidaySelectableSelectable
Alarm
Influenceoverview
Application
Heatcut-out
Anti-bacteriaSelectable
Temp.monitor.
AlarmoverviewSelectable Des.flowT(circuit1)
Des.DHWT(circuit2)
11010
11017 11050 11500 11022 11023 11052 11077 11078 11040 11093 11141 11142 11393 11392 11179 11395 11397 11396 11398 11399
11147
11148 11149
11150
Heating,circuit1DHW,circuit2
Function
ECAaddr.
Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority PfrostT PheatT Ppost-run Frostpr.T Ext.input Ext.mode Sum.start,day Sum.start,month Summer,cut-out Summer,filter Winterstart,day Winterstart,month Winter,cut-out Winter,filter
Upperdifference
Lowerdifference Delay Lowesttemp.
Returnlim.Holiday Roomlim.Ext.override
Flow/powerlim.Anti-bacteria HolidaySCADAoverride Ext.override ECAoverride Boost Ramp Slave,demand Heatingcut-out DHWpriority DHWinfluence SCADAoffset Ext.desiredT*
IDno.
12051
12053 12055 12044 12045 12041 12059 12500 12076 12093 12141 12142
Function
Ch.-o.valve/P
Tank,sec./prim. Circ.Ppriority Max.DHWtime DHWdeact.time DHWPpost-run Pchargedelay SenddesiredT Circ.PfrostT Frostpr.T Ext.input Ext.mode
AQ000086479358en-010501
©Danfoss|2021.02|39
OperatingGuideECLComfort210/296/310,applicationA237/A337
Navigation,applicationA237.1/A337.1,Commoncontrollersettings(*A337.1only)
Home MENU Time&Date HolidaySelectable Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
OutdoorTLogtoday RoomT&desiredLogyesterday FlowT&desiredLog2days ReturnT&limitLog4days TankTup.&des. TankTup.&low.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet Portalconfig M-busconfig EnergyMeters RawinputoverviewS1...S10 Alarm Display
Communication
Language
IDno.
60058 60059
38
39 2048 2150 2151 2050
Commoncontrollersettings
Function
Selectable
OutdoorT Outdooracc.T RoomT FlowT ReturnT TankupperT TanklowerT Ext.desiredT*
M1,P1,P2,P3,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
Selectable Selectable
Backlight Contrast Modbusaddr. Baud ECL485addr. Servicepin Ext.reset Language
40|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Navigation,applicationA237.2/A337.2(*A237.2only,**A337.2only)
Home
IDno.
ScheduleSelectableSelectable Schedulecirc.PSelectable Settings
Flowtemperature(circuit1) Tanktemperature(circuit2)
Roomlimit
Returnlimit
Flow/powerlimitActualActual
Optimization
Controlpar.
11178 11177 11004
11182 11183 11015 11031 11032 11033 11034 11035 11036 11037 11085 11028
11119 11117 11118 11116 11112 11113 11109 11115 11114 11011 11012 11013 11014 11026 11020 11021 11179 11043 11174 11184 11185 11186 11187 11189 11024
Heating,circuit1DHW,circuit2
Function
Heatcurve12193Chargedifference Temp.max.
Temp.min. DesiredT Ext.desiredT** Infl.—max. Infl.—min. Adapt.time HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority Con.T,ret.Tlim.
Actuallimit HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Adapt.time Filterconstant Inputtype Units Pulse* Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Paralleloperation Motorpr. Xp Tn Mrun Nz Min.act.time Actuator
IDno.
12195 12194 12152 12068
12030
12111
Function
Startdifference Stopdifference Max.chargeT FlowTadapttime
Limit
Limit
AQ000086479358en-010501
©Danfoss|2021.02|41
OperatingGuideECLComfort210/296/310,applicationA237/A337
Navigation,applicationA237.2/A337.2,continued(*A337.2only)
Home
IDno.
MENU
Settings
HolidaySelectableSelectable
Alarm
Influenceoverview
Application
Heatcut-out
Anti-bacteriaSelectable
Temp.monitor.
AlarmoverviewSelectable Des.flowT(circuit1)
Des.DHWT(circuit2)
11010
11017 11050 11500 11022 11023 11052 11077 11078 11040
11093 11141 11142 11393 11392 11179 11395 11397 11396 11398 11399
11147 11148
11149 11150
Heating,circuit1DHW,circuit2
Function
ECAaddr.
Demandoffset Pdemand SenddesiredT Pexercise Mexercise DHWpriority PfrostT PheatT Ppost-run
Frostpr.T Ext.input Ext.mode Sum.start,day Sum.start,month Summer,cut-out Summer,filter Winterstart,day Winterstart,month Winter,cut-out Winter,filter
Upperdifference Lowerdifference
Delay Lowesttemp.
Returnlim.Holiday Roomlim.Ext.override
Flow/powerlim.Anti-bacteria HolidaySCADAoverride Ext.override ECAoverride Boost Ramp Slave,demand Heatingcut-out DHWpriority DHWinfluence SCADAoffset Ext.desiredT*
IDno.
12051
12055 12044 12045 12041 12059 12042 12500 12076 12093
12141 12142
Function
Ch.-o.valve/P
Circ.Ppriority Max.DHWtime DHWdeact.time DHWPpost-run Pchargedelay Char.Ppost-run SenddesiredT Circ.PfrostT Frostpr.T
Ext.input Ext.mode
42|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Navigation,applicationA237.2/A337.2,Commoncontrollersettings(*A337.2only)
Home MENU Time&Date HolidaySelectable Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
OutdoorTLogtoday RoomT&desiredLogyesterday FlowT&desiredLog2days ReturnT&limitLog4days TankTup.&des. TankTup.&low. ChargeT
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet Portalconfig M-busconfig EnergyMeters RawinputoverviewS1...S10 Alarm Display
Communication
Language
IDno.
60058 60059
38
39 2048 2150 2151 2050
Commoncontrollersettings
Function
Selectable
OutdoorT Outdooracc.T RoomT FlowT ChargeT ReturnT TankupperT TanklowerT Ext.desiredT*
M1,P1,P2,P3,P4,A1*
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
Selectable Selectable
Backlight Contrast Modbusaddr. Baud ECL485addr. Servicepin Ext.reset Language
AQ000086479358en-010501
©Danfoss|2021.02|43
OperatingGuideECLComfort210/296/310,applicationA237/A337

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
44|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
AQ000086479358en-010501
)
©Danfoss|2021.02|45
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
DHWcircuit
Overviewdisplay1informsabout: actualDHWtemperature,controllermode,desiredDHW temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout: stateofthecontrolledcomponents,actualDHWtemperature, (desiredDHWtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith Influenceindication:
46|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
Examples:
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled operationandincomfortmode.
Examples:
50
55
AQ000086479358en-010501
©Danfoss|2021.02|47
OperatingGuideECLComfort210/296/310,applicationA237/A337
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
48|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
DamperOFF
AQ000086479358en-010501
©Danfoss|2021.02|49
OperatingGuideECLComfort210/296/310,applicationA237/A337

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview oftheactualand(desired)temperaturesaswellastheactualstate ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
(30)
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
Flowtemperature
Desiredflowtemperature
--
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
50|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
AQ000086479358en-010501
©Danfoss|2021.02|51
OperatingGuideECLComfort210/296/310,applicationA237/A337

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
52|©Danfoss|2021.02
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
AQ000086479358en-010501
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
©Danfoss|2021.02|53
OperatingGuideECLComfort210/296/310,applicationA237/A337

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Ext.desiredT—(ECLComfort310)
Actual(actualfloworpower)
Extendedheatcut-outsetting
Extendedwintercut-outsetting
Day
Starttime
Duration
DesiredT
DesiredT(Desiredflowtemperature)
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Adapt.time(adaptiontime)
Demandoffset
Basedon(optimizationbasedonroom/outdoortemp.)
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Actuator
Pre-stop(optimizedstoptime)
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
Limit(returntemp.limitation)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Ppost-run
DHWPpost-run(DHWpump,post-run)
Char.Ppost-run(DHWchargingpump,post-run)
Paralleloperation
Max.DHWtime
DHWdeact.time(DHWdeactivationtime)
1x00459
1x01085
1x011
1x01276
1x013
1x014
1x01562
1x01785
1x02078
1x02178
1x02286
1x02386
1x02482
1x02679
1x02866
1x03066
1x03167
1x03267
1x03367
1x03467
1x03567
1x03668
1x03768
1x04087
1x04187
1x04287
1x04379
1x04487
1x04588
Factorysettingsincircuit(s)
1
58
60
71
97
97
108
108
109
109
75
77
77
2
54|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
SettingIDPage
Pdemand
Ch.-o.valve/P(changeovervalve/pump)
DHWpriority(closedvalve/normaloperation)
Tank,sec./prim.(Tanksecondarilyorprimarilyconnected)
Circ.Ppriority
Pchargedelay(Chargingpump,delayedstart)
FlowTadapttime(Flowtemperature,adaptationtime)
Circ.PfrostT
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Pulse
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Max.chargeT(maximumheating/chargingtemperature)
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Infl.-max.(roomtemp.limitation,max.)
Infl.-min.(roomtemp.limitation,min.)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Chargedifference
Stopdifference
1x05088
1x05188
1x05289
1x05389
1x05589
1x05990
1x06899
1x07690
1x07790
1x07890
1x08568
1x09391
1x109
1x111
1x11272
1x11372
1x114
1x115
1x11673
1x117
1x118
1x119
1x141
1x14292
1x147
1x148105
1x149106
1x150106
1x15299
1x174
1x177
1x17860
1x17980
1x18262
1x18363
1x18483
1x18583
1x18683
1x18783
1x18984
1x19399
1x194100
Factorysettingsincircuit(s)
1
71
72
72
72
73
74
74
91
105
82
60
2
AQ000086479358en-010501
©Danfoss|2021.02|55
OperatingGuideECLComfort210/296/310,applicationA237/A337
Startdifference
SenddesiredT
SettingIDPage
1x195102
1x50094
Factorysettingsincircuit(s)
1
2
56|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
AQ000086479358en-010501
©Danfoss|2021.02|57
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.2Flowtemperature/Inlettemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature/Inlettemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
58|©Danfoss|2021.02
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
TheECLComfort210/296/310controlstheDHWtemperature accordingtothedesiredflowtemperatureforexampleunderthe influenceofthereturntemperature.
ActualDHWtemp.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DesiredDHW temp.
AQ000086479358en-010501
©Danfoss|2021.02|59
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Flowtemperature/Inlettemperature
DesiredT(Desiredflowtemperature)
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow temperaturecanbeset. A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU >Settings>Returnlimit>'Con.T,ret.Tlim. '
1x004
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature/Inlettemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan beappliedtoaninputinordertooverridetoComfort,Saving,Frost ProtectionorConstanttemperature.Aslongasthecontact(switch) signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
MENU>Settings>Flowtemperature/Inlettemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
60|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Externalsignalfordesiredflowtemperature
Avoltage(0-10V)canbeappliedtotheinputterminalS10in ordertodeterminethedesiredflowtemperature.
ThemeasuredvoltageoninputS10mustbeconvertedtoa temperaturevaluebythecontroller.Whenthevoltagegetshigher, thedesiredflowtemperatureincreases.
Thefollowingsettingssetupthescaling.
MENU>Settings>Flowtemperature/Inlettemperature
Ext.desiredT—(ECLComfort310)
CircuitSettingrange
1
Theactualdesiredflowtemperatureisindicatedbytheunit°C.
Read-outonly
Factorysetting
Read-out:
--:
°C:
Externalvoltagesignalisnotconnected..
Externalvoltagesignalconvertedtodesiredflow temperature.
Pushthedialtoseethegraphandenterthevaluesetsfortheinput voltage(1and10volt)anddisplayeddesiredflowtemperature.
Example:Relationshipbetweeninputvoltageanddisplayeddesiredflow temperature
Desiredflowtemp.(°C)
Volt
Thisexampleshowsthat1voltcorrespondsto10.0°Cand10volt correspondto100°C.
Desiredflowtemperature:
10...120°C
Fixedvoltagesettings:1Vand10V Factorysettings:
(1,10)and(10,100)
Thismeansthatthe‘Desiredflowtemperature’is10°Cat1.0V and100°Cat10V.
Typically,thehigherthevoltage,thehigherthedisplayeddesired flowtemperature.
Theexternalvoltagesignalmustbehigherthan1.0Vinorderto activatetheoverride.
AQ000086479358en-010501
©Danfoss|2021.02|61
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.3Roomlimit

ThefollowingsectionisageneraldescriptionforRoom temperaturelimitation. Theactualapplicationmightnothavebothlimitationtypes.
Thissectionisonlyrelevantifyouhaveinstalledaroom temperaturesensororaRemoteControlUnitforutilizingtheroom temperaturesignal.
Inthefollowingdescriptionisreferredto"flowtemperature"in general.
Thecontrolleradjuststhedesiredflowtemperaturetocompensate forthedifferencebetweenthedesiredandtheactualroom temperature.
Iftheroomtemperatureishigherthanthedesiredvalue,the desiredflowtemperaturecanbereduced.
The'Infl.-max.'(Influence,max.roomtemp.)determineshow muchthedesiredflowtemperatureshouldbereduced.
Usethisinfluencetypetoavoidatoohighroomtemperature.The controllerwillallowforfreeheatgains,i.e.solarradiationorheat fromafireplaceetc.
Iftheroomtemperatureislowerthanthedesiredvalue,thedesired flowtemperaturecanbeincreased.
The'Infl.-min.'(Influence,min.roomtemperature)determines howmuchthedesiredflowtemperatureshouldbeincreased.
Usethisinfluencetypetoavoidatoolowroomtemperature.This coulde.g.becausedbywindysurroundings.
Atypicalsettingwillbe-4.0for'Infl.-max.'and4.0for'Infl.-min. '
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Roomlimit
Adapt.time(adaptiontime)
Controlshowfasttheactualroomtemperatureadaptstothedesiredroom temperature(Icontrol).
1x015
Theadaptationfunctioncancorrectthedesiredroomtemperature withmax.8Kxheatcurveslopevalue.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe'Adapt. time'.
Minor
Thedesiredroomtemperatureisadaptedquickly.
value: Major
Thedesiredroomtemperatureisadaptedslowly.
value:
62|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Roomlimit
Infl.-max.(roomtemp.limitation,max.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (decreased)iftheactualroomtemperatureishigherthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
0.0:
-2.0:
-5.0:
-9.9:
Noinfluence Minorinfluence Mediuminfluence Maximuminfluence
1x182
=
X
#1#
#2#
#3#
Roomtemperature
=
Desiredroomtemperature
=
Negativeinfluence(1x082)whenactualroomtemp.getshigher thandesiredroomtemp.
=
Positiveinfluence(1x083)whenactualroomtemp.getslowerthan desiredroomtemp.
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x-4.0x1.8) –14.4degrees.
MENU>Settings>Roomlimit
Infl.-min.(roomtemp.limitation,min.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (increased)iftheactualroomtemperatureislowerthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
9.9:
5.0:
2.0:
0.0:
Maximuminfluence Mediuminfluence Minorinfluence Noinfluence
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x-4.0x1): –8.0degrees.
Example
1x183
Theactualroomtemperatureis2degreestoolow. The‘Infl.-min.’issetto4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x4.0x1.8)
14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x4.0x1):
8.0degrees.
AQ000086479358en-010501
©Danfoss|2021.02|63
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.4Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant temperaturevalue. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthesetlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
64|©Danfoss|2021.02
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
AQ000086479358en-010501
©Danfoss|2021.02|65
OperatingGuideECLComfort210/296/310,applicationA237/A337
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
The"Con.T ,ret.Tlimit"isthereturntemperaturelimitationvaluewhenthe circuitissettooverridemodetype"Const.T"(=Constanttemperature).
SeeAppendix“ParameterIDoverview”
Value:Setthereturntemperaturelimitation
1x028
66|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe setvalue,thecontrollerautomaticallychangesthedesiredflow/ ducttemperaturetoobtainanacceptablereturntemperature.The influenceissetin'Infl.-max. 'and'Infl.-min.' .
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
1x031
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
1x032
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
1x033
1x034
ThecorrespondingXcoordinateissetin'LowToutX2' .
AQ000086479358en-010501
©Danfoss|2021.02|67
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthesetlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthesetlimit.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Example
1x035
1x036
Thereturnlimitisactiveabove50°C. Theinfluenceissetto0.5. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby0.5x2=1.0degree.
Example
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
1x037
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
68|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
AQ000086479358en-010501
©Danfoss|2021.02|69
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.5Flow/powerlimit

Heatingcircuit
AfloworenergymetercanbeconnectedtotheECLcontrollerin ordertolimitthefloworconsumedpower.Thesignalfromthe floworenergymeterisapulsesignal.
WhentheapplicationrunsinanECLComfort296/310controller, theflow/powersignalcanbeobtainedfromaflow/energymeter viatheM-busconnection.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2#
#Y1#
#Y2#
X
Y
#1#
#2#
#3#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
=
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
70|©Danfoss|2021.02
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
DHWcircuit
AfloworheatmetercanbeconnectedtotheECLcontrollerin ordertolimitthefloworconsumedpower.Thesignalfromthe floworheatmeterisapulsesignal.
WhentheapplicationrunsinanECLComfort296/310controller, theflow/powersignalcanbeobtainedfromaflow/heatmeter viatheM-busconnection.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
=
X
Y
#1#
#2#
#3#
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
Theparameter'Units'(ID1x115)hasareducedsettingrangewhen theflow/energysignalcomesviaM-bus.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Inputtype
Choiceofinputtypefromflow/energymeter
Pulsebasedsignalforflow/power ,appliedtoinputS7
Formonitoring: Frequencyrangeis0.01-200Hz
Forlimitation: Minimumfrequencyisrecommendedtobe1Hzinordertohavea
stablecontrol.Furthermore,thepulsesmustappearregularly.
1x109
ThesettingrangeforIMandEMdependsonchosensubtype.
SeeAppendix“ParameterIDoverview”
OFF:
IM1-
Noinput
Flow/energymetersignalbasedonpulses.
IM5: EM1-
Flow/energymetersignalfromM-bus.
EM5:
AQ000086479358en-010501
©Danfoss|2021.02|71
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
1x111
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Pulse
Setthevalueofthepulsesfromtheflow/energymeter.
SeeAppendix“ParameterIDoverview”
OFF:
1...9999:
Noinput.
Pulsevalue.
1x113
Example:
1x114
Onepulsecanrepresentanumberoflitres(fromaflowmeter) oranumberofkWh(fromaenergymeter).
72|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Unitstotheleft:pulsevalue. Unitstotheright:actualandlimitationvalues.
Thevaluefromtheflowmeterisexpressedasmlorl. ThevaluefromtheenergymeterisexpressedasWh,kWh,MWh orGWh.
Thevaluesfortheactualflowandtheflowlimitationareexpressed asl/horm³/h.
Thevaluesfortheactualpowerandthepowerlimitationare expressedaskW,MWorGW.
1x115
Listforsettingrangeof'Units': ml,l/h l,l/h ml,m³/h l,m³/h Wh,kW kWh,kW kWh,MW MWh,MW MWh,GW GWh,GW
Example1:
'Units'(11115):
'Pulse'(11114):
l,m³/h 10
Eachpulserepresents10litresandtheflowisexpressedascubic meters(m³)perhour.
Example2:
'Units'(11115):
'Pulse'(11114):
kWh,kW(=kiloWatthour,kiloWatt) 1
Eachpulserepresents1kiloWatthourandthepoweris expressedinkiloWatt.
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
Listforsettingrangeof'Units'whenM-busconnectiontoflowor energymeter:
l/h m³/h kW MW GW
1x116
AQ000086479358en-010501
©Danfoss|2021.02|73
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
1x118
1x119
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
74|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.6Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost','Optimizer' ,'Totalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
AQ000086479358en-010501
©Danfoss|2021.02|75
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
76|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
X Y #1#
=
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
AQ000086479358en-010501
©Danfoss|2021.02|77
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
MENU>Settings>Optimization
Basedon(optimizationbasedonroom/outdoortemp.)
Theoptimizedstartandstoptimecanbebasedoneitherroomoroutdoor temperature.
SeeAppendix“ParameterIDoverview”
OUT:
Optimizationbasedonoutdoortemperature.Usethis settingiftheroomtemperatureisnotmeasured.
ROOM:
Optimizationbasedonroomtemperature,ifmeasured.
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
1x020
-5°C
small
78|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost protectionisstillactive,see'PfrostT' .
Totalstop=OFF
Totalstop=ON
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
1x026
Example:OptimizationofComfortfrom07:00-22:00
=
X #1# #2# #3# #4# #5#
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
AQ000086479358en-010501
©Danfoss|2021.02|79
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Optimization
Paralleloperation
ChoosewhethertheheatingcircuitistooperateparalleltotheDHWcircuit.
SeeAppendix“ParameterIDoverview”
OFF:
DHWheatinghas100%priority.Theheatingcircuit circulationpumpisOFFduringDHWheating.
1...99K:
Dependentparalleloperation.Theheatingcircuit circulationpumpisONifthedifferencebetweenDHW heatingtemperature(chargingtemperature)and desiredflowtemperatureislessthanthesetvalue.
ON:
Paralleloperation.Theheatingcircuitcirculationpump isONduringDHWheating.
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
SeeAppendix“ParameterIDoverview”
1x043
=
X
Y
#1#
#2#
#3#
#4#
#5#
Summer,cut-out
1x179
Time
=
Temperature
=
Acceptabledeviation(Paralleloperation,1x043)
=
DesiredDHWheatingtemperature
=
ActualDHWheatingtemperature
=
100%paralleloperation
=
100%DHWpriority
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
80|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.7Controlparameters

Controlofvalve
Themotorizedcontrolvalveiscontrolledbymeansof3-point controlsignal.
Valvecontrol: Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
AQ000086479358en-010501
©Danfoss|2021.02|81
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thermo-hydraulicactuator,ABV
Danfossthermo-actuatortypeABVisaslowactingvalveactuator. InsidetheABVanelectricheatcoilwillheatathermostaticelement whenanelectricsignalisapplied.Whenheatingthethermostatic elementitexpandsinordertomanagethecontrolvalve.
Twobasictypesareavailable:ABVNC(NormalClosed)andABVNO (normalopen).Forexample,ABVNCkeepsa2-portcontrolvalve closedwhennoopen-signalsareapplied.
Electricopen-signalscomefromtheelectronicoutputoftheECL Comfortcontrollerinordertomanagethecontrolvalve.When open-signalsareappliedtotheABVNC,thevalvegraduallyopens.
Open-signalsareintheECLComfortcontrollerexpressedas "Arrow-up"(open)anddisplayedatthevalvesymbol.
Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,relativelylongopen-signalscomefrom theECLComfortcontrollerinordertoincreasetheflow.Bythis, theflowtemperaturewillovertimebealignedwiththedesired temperature.
Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,relativelyshortopen-signalscomefromtheECL Comfortcontrollerinordertoreducetheflow.Again,theflow temperaturealigns,overtime,withthedesiredtemperature.
ThecontroloftheDanfossthermo-actuatortypeABVusesaunique designedalgorithmandisbasedonthePWMprinciple(Pulse WidthModulation),wherethedurationofthepulsedetermines themanagementofthecontrolvalve.Thepulsesarerepeated each10sec.
Aslongastheflowtemperaturecorrespondstothedesired temperature,thedurationoftheopen-signalswillremainconstant.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Actuator
ABV/GEAR
1x024
GEAR
Selectionofvalveactuatortype.
Whenselecting"ABV",thecontrolparameters:
•Motorprotection(ID1x174)
ABV:
GEAR:
82|©Danfoss|2021.02
DanfosstypeABV(thermoactuator). Gearmotorbasedactuator.
•Xp(ID1x184)
•Tn(ID1x185)
•Mrun(ID1x186)
•Nz(ID1x187)
•Min.act.time(ID1x189)
arenotconsidered.
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
1x174
1x184
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
AQ000086479358en-010501
©Danfoss|2021.02|83
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Criticaltimeperiod
Time
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
84|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.8Application

Thesection"Application"describesspecificapplicationrelated issues. Someoftheparameterdescriptionsareuniversalfordifferent applicationkeys.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Application
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Decidestheroomtemperaturesignaltransferandcommunicationwiththe RemoteControlUnit.
SeeAppendix“ParameterIDoverview”
OFF:
NoRemoteControlUnit.Onlyroomtemperaturesensor, ifany.
A:
B:
RemoteControlUnitECA30/31withaddressA. RemoteControlUnitECA30/31withaddressB.
1x010
TheRemoteControlUnitmustbesetaccordingly(AorB).
AQ000086479358en-010501
©Danfoss|2021.02|85
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Application
Demandoffset
Thedesiredflowtemperatureinheatingcircuit1canbeinfluencedbythe demandforadesiredflowtemperaturefromanothercontroller(slave)or anothercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredflowtemperatureincircuit1isnot influencedbythedemandofanyothercontroller(slave orcircuit2).
Value:
Thedesiredflowtemperatureisincreasedbytheset valuein‘Demandoffset’ ,ifthedemandoftheslave/ circuit2ishigher.
Heatingapplication
1x017
=
X
Y
#1#
#2#
#3#
Time
=
Desiredflowtemperatures
=
Demandoffset
=
Desiredflowtemperature,master
=
Desiredflowtemperature,slave
MENU>Settings>Application
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
Thefunctionof‘Demandoffset’cancompensateforheatlosses betweenmasterandslavecontrolledsystems.
'Demandoffset'withavalueistobeusedintheMastercontrolleronly.
Whensetting"Demandoffset"toavalue,thereturntemperature limitationwillreactaccordingtothehighestlimitationvalue(Heating /DHW).
1x022
OFF:
ON:
86|©Danfoss|2021.02
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat noon(12:14hours).
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Application
Mexercise(valveexercise)
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thevalveexerciseisnotactive.
Thevalveopensfor7minutesandclosesfor7minutes everythirddayatnoon(12:00hours).
MENU>Settings>Application
Ppost-run
Heatingapplications:
ThecirculationpumpintheheatingcircuitcanbeONforanumberof minutes(m)afterheatingstop.Heatingstopiswhenthedesiredflow temperaturegetslowerthanthesettingin'PheatT'(IDno.1x078).
Coolingapplications:
ThecirculationpumpinthecoolingcircuitcanbeONforanumberof minutes(m)aftercoolingstop.Coolingstopiswhenthedesiredflow temperaturegetshigherthanthesettingin'PcoolT'(IDno.1x070). ThisPpost-runfunctioncanutilizetheremainingenergyinforexamplea heatexchanger.
SeeAppendix“ParameterIDoverview”
1x023
1x040
0:
Thecirculationpumpstopsimmediatelyafterheating orcoolingstop.
Value:
ThecirculationpumpisONforthesettimeafterheating orcoolingstop.
MENU>Settings>Application
DHWPpost-run(DHWpump,post-run)
SettheDHWpumppost-runtime(minutes).TheDHWpumpcancontinue tobeswitchedONaftertheDHWheatingprocedureinordertoutilizethe remainingheatintheheatexchanger/boiler.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
MENU>Settings>Application
Char.Ppost-run(DHWchargingpump,post-run)
SettheDHWchargingpumppost-runtime(minutes).TheDHWcharging pumpcancontinuetobeswitchedONaftertheDHWheatingprocedurein ordertoutilizetheremainingheatintheheatexchanger.
1x041
1x042
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
AQ000086479358en-010501
©Danfoss|2021.02|87
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Application
Max.DHWtime
SetthemaxDHWheatingtime(minutes).WhenDHWheatingisactiveand theset'Max.DHWtime'expires,DHWheatingisdeactivated.
1x044
SeeAppendix“ParameterIDoverview”
OFF:
IftheDHWtemperatureislowerthantheDHWcharging cut-intemperature,theDHWchargingremainsactive forunlimitedperiodoftime.IftheDHWtemperatureis higherthantheDHWchargingcut-intemperature,the chargingisdeactivatedafter35minutes.
Value:TheDHWheating/chargingisdeactivatedwhentheset
'Max.DHWtime'(inminutes)expires.
MENU>Settings>Application
DHWdeact.time(DHWdeactivationtime)
Setthetime(minutes)thatmustelapseafteraDHWheatingperiodbeforea newDHWheatingperiodcanbestarted.
1x045
SeeAppendix“ParameterIDoverview”
Value:WhentheDHWheating/chargingtimehasreachedits
maximum,DHWcanonlybeheated/chargedagain afterthesetdeactivationtime(inminutes)hasexpired.
MENU>Settings>Application
Pdemand
Thecirculationpumpinthemastercircuitcanbecontrolledinrelationto themastercircuit'sdemandorslavecircuit'sdemand.
SeeAppendix“ParameterIDoverview”
Heatingapplications:
OFF:
ThecirculationpumpisONwhenthedesiredflow temperatureintheheatingcircuitishigherthanthe valuesetin'PheatT'.
ON:
ThecirculationpumpisONwhenthedesiredflow temperaturefromslavesishigherthanthevaluesetin 'PheatT'.
Coolingapplications:
OFF:
ThecirculationpumpisONwhenthedesiredflow temperatureinthecoolingcircuitislowerthanthevalue setin'PcoolT'.
ON:
ThecirculationpumpisONwhenthedesiredflow temperaturefromslavesislowerthanthevaluesetin 'PcoolT'.
1x050
Thecirculationpumpisalwayscontrolledaccordingtofrostprotection conditions.
88|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Application
Ch.-o.valve/P(changeovervalve/pump)
ChoosewhethertheDHWheatingcontrolisbasedonachangeovervalve orapump.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Changeovervalve Pump
MENU>Settings>Application
DHWpriority(closedvalve/normaloperation)
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen DHWheating/chargingisactiveinthemaster.
SeeAppendix“ParameterIDoverview”
OFF:
Theflowtemperaturecontrolremainsunchanged duringactiveDHWheating/charginginthemaster controller.
ON:
Thevalveintheheatingcircuitisclosed*duringactive DHWheating/charginginthemastercontroller.
*Thedesiredflowtemperatureissettothevaluesetin ‘Frostpr.T’
1x051
Whenthechangeovervalveischosen,pumpP1isONatheatingas wellasatDHWheatingdemand.
Whenthepumpischosen,pumpP1isONatheatingandOFFatDHW heatingdemand.
Aparalleloption(heatingandDHWheatinginparallel)exists,based onthesetting‘Paralleloperation’ .
1x052
Thissettingmustbeconsideredifthiscontrollerisaslave.
MENU>Settings>Application
Tank,sec./prim.(Tanksecondarilyorprimarily connected)
ChoosewhethertheheatingoftheDHWtankisdependentontheflow temperatureatS3.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWtankisplacedonthesecondarysideofthe heatexchangerandtheS3temperaturedetermines theDHWheating.
ON:
TheDHWtankisplacedontheprimarysideoftheheat exchangerandtheS3temperaturehasnoinfluence ontheDHWheating.
1x053
AQ000086479358en-010501
©Danfoss|2021.02|89
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Application
Circ.Ppriority
ChoosewhethertheDHWcirculationpumpshouldbeONduringDHW heating.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWcirculationpumpisswitchedOFFduringDHW heating.
ON:
TheDHWcirculationpumpisnotswitchedOFFduring DHWheating.
MENU>Settings>Application
Pchargedelay(Chargingpump,delayedstart)
ConditionsforswitchingtheDHWheating/chargingpumpONatDHW heating/chargingdemand. Correctsettingcanavoiddischarging.
SeeAppendix“ParameterIDoverview”
OFF:
DHWheating/chargingpumpisswitchedONwhen DHWheating/chargingtemperatureisOK.
0:
Value:
DHWheating/chargingpumpisswitchedON.
DHWheating/chargingpumpisswitchedONafterthe setnumberofminutes.
1x055
Whenthe'Circ.Ppriority'issettoOFF ,theschedulefortheDHW circulationpumpisoverruled.
1x059
Whenthesetting"OFF"isselected,thetemperaturesensorforDHW heating/chargingmustbeplacedintheheat-exchanger.
MENU>Settings>Application
Circ.PfrostT
SettheoutdoortemperaturevalueatwhichtheDHWcirculationpumpisto beactivetoprotecttheDHWcircuitagainstfrost.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
TheDHWcirculationpumpisnotactive. TheDHWcirculationpumpisactivewhentheoutdoor
temperatureislowerthanthesetvalue.
MENU>Settings>Application
PfrostT(circulationpump,frostprotectiontemp.)
Frostprotection,basedontheoutdoortemperature. Whentheoutdoortemperaturegetsbelowthesettemperaturevaluein‘P frostT’ ,thecontrollerautomaticallyswitchesONthecirculationpump(for exampleP1orX3)toprotectthesystem.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Nofrostprotection. CirculationpumpisONwhentheoutdoortemperature
isbelowthesetvalue.
1x076
1x077
Undernormalconditions,yoursystemisnotfrostprotectedifyour settingisbelow0°CorOFF.
Forwater-basedsystems,asettingof2°Cisrecommended.
Iftheoutdoortemperaturesensorisnotconnectedandthefactory settinghasnotbeenchangedto'OFF' ,thecirculationpumpisalways ON.
90|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Application
PheatT(heatdemand)
Whenthedesiredflowtemperatureisabovethesettemperaturein‘PheatT’ , thecontrollerautomaticallyswitchesONthecirculationpump.
1x078
SeeAppendix“ParameterIDoverview”
Value:ThecirculationpumpisswitchedONwhenthedesired
flowtemperatureisabovethesetvalue.
MENU>Settings>Application
Frostpr .T(frostprotectiontemp.)
SetthedesiredflowtemperatureattemperaturesensorS3toprotectthe systemagainstfrost(atheatingcut-out,totalstopetc.). WhenthetemperatureatS3getslowerthanthesetting,themotorized controlvalveopensgradually.
1x093
SeeAppendix“ParameterIDoverview”
Thevalveisfullyclosedaslongasthepumpisnotswitchedon.
Thefrostprotectiontemperaturecanalsobesetinyourfavorite displaywhenthemodeselectorisinfrostprotectionmode.
AQ000086479358en-010501
©Danfoss|2021.02|91
OperatingGuideECLComfort210/296/310,applicationA237/A337
Overridemodefunctions:
ThefollowingsettingsdescribethefunctioningeneralfortheECL Comfort210/296/310series.Theexplainedmodesaretypical andnotapplicationrelated.Theymightdifferfromtheoverride modesinyourapplication.
MENU>Settings>Application
Ext.input(externaloverride)
Choosetheinputfor'Ext.input'(externaloverride).Bymeansofaswitch thecontrollercanbeoverriddento‘Comfort’,'Saving' ,'Frostprotection'or 'Constanttemperature'mode.
1x141
SeeAppendix“ParameterIDoverview”
OFF:
S1...S16:
Noinputshavebeenselectedforexternaloverride. Inputselectedforexternaloverride.
IfS1...S6ischosenasoverrideinput,theoverrideswitchmusthave gold-platedcontacts. IfS7...S16ischosenasoverrideinput,theoverrideswitchcanbea standardcontact.
Seethedrawingsforconnectionexamplesofoverrideswitchand overriderelaytoinputS8.
S7...S16arerecommendedforoverrideswitch.
Example:Connectionofanoverrideswitch
Example:Connectionofanoverriderelay
IfECA32ismounted,alsoS11...S16canbeused.
IfECA35ismounted,alsoS11orS12canbeused.
Chooseonlyanunusedinputforoverride.Ifanalreadyusedinputis appliedforoverride,thefunctionalityofthisinputisalsoneglected.
Seealso‘Ext.mode’.
92|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Application
Ext.mode(externaloverridemode)
ThemodeoverridecanbeactivatedforSaving,Comfort,Frostpr.or ConstantTmode. Foroverride,thecontrollermodemustbeinscheduledmode.
SeeAppendix“ParameterIDoverview”
Chooseanoverridemode:
SAVING:
Thecircuitinquestionisinsavingmodewhenthe overrideswitchisclosed.
COMFORT:
Thecircuitinquestionisincomfortmodewhenthe overrideswitchisclosed.
FROSTPR.:
TheheatingorDHWcircuitcloses,butisstillfrost protected.
CONSTANTT:
Thecircuitinquestioncontrolsaconstant temperature*)
*)
Seealso'DesiredT'(1x004),settingofdesiredflow temperature(MENU>Settings>Flowtemperature) Seealso'Con.T,ret.Tlim. '(1x028),settingofreturn temperaturelimitation(MENU>Settings>Return limit)
Theprocessdiagramsshowthefunctionality.
1x142
Seealso‘Ext.input’.
Example:OverridetoComfortmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Comfort) #3#=Time
Example:OverridetoSavingmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Saving) #3#=Time
Theresultofoverrideto'Saving'modedependsonthesettingin 'Totalstop'.
Totalstop=OFF:Heatingreduced Totalstop=ON:Heatingstopped
AQ000086479358en-010501
©Danfoss|2021.02|93
OperatingGuideECLComfort210/296/310,applicationA237/A337
Example:OverridetoFrostprotectionmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Frostpr.) #3#=Time
Example:OverridetoConstanttemperaturemode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Const.T) #3#=Time
The"Const.T"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
94|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Application
SenddesiredT
Whenthecontrolleractsasaslavecontrollerinamaster/slavesystem, informationaboutthedesiredflowtemperaturecanbesenttothemaster controllerviatheECL485bus. Stand-alonecontroller: Sub-circuitscansendthedesiredflowtemperaturetothemastercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Informationaboutthedesiredflowtemperatureisnot senttothemastercontroller.
ON:
Informationaboutthedesiredflowtemperatureissent tothemastercontroller.
1x500
Inthemastercontroller,'Demandoffset'mustbesettoavalueinorder toreactonadesiredflowtemperaturefromaslavecontroller.
Whenthecontrolleractsasaslave,itsaddressmustbe1,2,3...9in ordertosendthedesiredtemperaturetothemaster(seethesection ‘Miscellaneous’ ,‘Severalcontrollersinthesamesystem’).
AQ000086479358en-010501
©Danfoss|2021.02|95
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.9Heatcut-out

MENU>Settings>Heatcut-out
Thesetting“Summercut-out”under“Optimization”fortheheating circuitinquestiondeterminesaheatingcut-outwhentheoutdoor temperatureexceedsthesetvalue.
Afilteringconstantforcalculatingtheaccumulatedoutdoor temperatureisinternallysettoavalueof"250".Thisfiltering constantrepresentsanaveragebuildingwithsolidouterandinner walls(bricks).
Anoptionfordifferentiatedcut-outtemperatures,basedona setsummerperiod,canbeutilizedinordertoavoiddiscomfort atfallingoutdoortemperature.Furthermore,separatefiltering constantscanbeset.
ThefactorysetvaluesforSummerperiodstartandWinterperiod startaresettosamedate:May,20(Date=20,Month=5). Thismeans:
"Differentiatedcut-outtemperatures"aredisabled(notactive)
Separate"Filteringconstant"valuesaredisabled(notactive)
Inordertoenabledifferentiated
cut-outtemperaturebasedonsummer/winterperiod
filteringconstants
thestartdatesfortheperiodsmustbedifferent.
96|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337
5.9.1Differentiatedheatcut-out
Tosetdifferentiatedcut-outparametersforaheatingcircuitfor “Summer”and“Winter”goto“Heatcut-out”: (MENU>Settings>Heatcut-out) Thisfunctionisactivewhenthedatesfor“Summer”and“Winter” aredifferentinthe“Heatcut-out”menu.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Heatcut-out
Extendedheatcut-outsetting
ParameterIDSettingrange
Summerday
Summermonth
Summercut-out
Summerfilter
1x393
1x392
1x179
1x395
**
**
**
**
Factory
setting
SeeAppendix“ParameterIDoverview”
MENU>Settings>Heatcut-out
Extendedwintercut-outsetting
ParameterIDSettingrange
Winterday
Wintermonth
Wintercut-out
Winterfilter
1x397
1x396
1x398
1x399
**
**
**
**
Factory
SeeAppendix“ParameterIDoverview”
Theabovesettingsofthedatesforthecut-outfunctionareonly tobedoneintheheatingcircuit1andarevalidforotherheating circuitsinthecontrolleraswell,ifapplicable.
Thecut-outtemperaturesaswellasthefilterconstantaretobeset individuallyperheatingcircuit.
setting
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
AQ000086479358en-010501
©Danfoss|2021.02|97
OperatingGuideECLComfort210/296/310,applicationA237/A337
5.9.2Summer/winterfilterconstant
Thefilterconstantof250isapplicableforaveragebuildings.A filterconstantof1iscloseswitchingaccordingtoactualoutdoor temperaturemeaninglowfiltering(very“light”building).
Afilterconstantof300isthentobechosenifabigfilteringis needed(veryheavybuilding).
Forheatingcircuitswheretheheatcut-outisdemandedaccording tothesameoutdoortemperatureforthewholeyear,butdifferent filteringiswanted,differentdateshavetobesetinthe“Heat cut-out”menuenablingaselectionofafilterconstantdifferent fromthefactorysetting. Thesedifferentvalueshavetobesetinboththe“Summer”and “Winter”menu.
98|©Danfoss|2021.02
AQ000086479358en-010501
OperatingGuideECLComfort210/296/310,applicationA237/A337

5.10Tanktemperature

MENU>Settings>Tanktemperature
FlowTadapttime(Flowtemperature,adaptationtime)
Settheadaptationtime(inseconds)forthedesiredtemperatureinthe primarycircuit,basedonthedesiredchargingtemperature. TheECLComfortcontrollergraduallyincreasesthedesiredflowtemperature intheprimarycircuitinordertomaintainthedesiredchargingtemperature.
1x068
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredflowtemperatureintheprimarycircuitis notadaptedtothedesiredchargingtemperature.
Low
Theadaptationisquick.
value: High
Theadaptationisslow.
value:
MENU>Settings>Tanktemperature
Max.chargeT(maximumheating/chargingtemperature)
Setthemax.heating/chargingtemperaturefortheDHW.
1x152
SeeAppendix“ParameterIDoverview”
Value:Setthetemperature.
Thedesiredheating/chargingtemperaturecannotbehigherthanthe settemperaturein'Max.chargeT’ .
NOTE: ThedesiredDHWtemperaturewillbereducedif"Max.chargeT"is
lowerthan(DesiredDHWtemp.+Chargedifference).
Example:
DesiredDHWtemp.=
Chargedifference=
Max.chargeT=
50°C
10K
55°C
Result: DesiredDHWtemp.willbereducedto45°C.
AQ000086479358en-010501
©Danfoss|2021.02|99
OperatingGuideECLComfort210/296/310,applicationA237/A337
MENU>Settings>Tanktemperature
Chargedifference
SetthenumberofdegreesabovethedesiredDHWtemperaturethatwill resultintheDHWheating(charging)temperature.
SeeAppendix“ParameterIDoverview”
Value:
NumberofdegreestobeaddedtothedesiredDHW temperaturetoobtaintheDHWheating(charging) temperature.
1x193
=
X
#1#
#2#
#3#
#4#
#5#
ThedesiredDHWtemperatureisrelatedtothetanktemperature sensor.
Iftwotanktemperaturesensorsareinstalled,therelationistothe uppertanktemperaturesensor.
Time
=
Chargingdifference(ID1x193)
=
DesiredDHWtemperature
=
Startdifference(ID1x195)
=
ActualDHWtemperature
=
DHWheating/chargingactivity
100|©Danfoss|2021.02
AQ000086479358en-010501
Loading...