Danfoss A232, A332 Operating guide

OperatingGuide
ECLComfort210/296/310,applicationA232/A332

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................14
2.4Placingthetemperaturesensors................................25
2.5Electricalconnections.............................................27
2.6InsertingtheECLApplicationKey..............................36
2.7Checklist............................................................43
2.8Navigation,ECLApplicationKeyA232/A332................44
3.0Dailyuse.........................................................57
3.1Howtonavigate...................................................57
3.2Understandingthecontrollerdisplay..........................58
3.3Ageneraloverview:Whatdothesymbolsmean?...........62
3.4Monitoringtemperaturesandsystem
components........................................................63
3.5Influenceoverview................................................64
3.6Manualcontrol.....................................................65
3.7Schedule............................................................66
4.0Settingsoverview............................................67
5.0Settings...........................................................70
5.1IntroductiontoSettings..........................................70
5.2Flowtemperature/Inlettemperature.........................71
5.3Roomlimit..........................................................75
5.6Optimization........................................................88
5.7Controlparameters................................................94
5.8Application.......................................................101
5.9Optionalfunction................................................111
5.10Alarm..............................................................115
5.11Alarmoverview..................................................118
5.12Anti-bacteria......................................................119
6.0Commoncontrollersettings............................121
6.1Introductionto‘Commoncontrollersettings’..............121
6.2Time&Date.......................................................122
6.3Holiday............................................................123
6.4Inputoverview...................................................125
6.5Log.................................................................126
6.6Outputoverride..................................................127
6.7Keyfunctions.....................................................128
6.8System.............................................................130
7.0Miscellaneous................................................137
7.1ECA30/31setupprocedures.................................137
7.2Overridefunction................................................145
7.3Severalcontrollersinthesamesystem......................148
7.4Frequentlyaskedquestions....................................151
7.5Definitions........................................................154
7.6Type(ID6001),overview.......................................158
7.7Automatic/manualupdateoffirmware.....................159
7.8ParameterIDoverview..........................................160
©Danfoss|2021.06AQ150486469826en-010501|1
OperatingGuideECLComfort210/296/310,applicationA232/A332

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA232 (ordercodeno.087H3812).
TheECLApplicationKeyA232contains5subtypes:
A232.1(applicableinECLComfort210and310) A332.1…A332.4(applicableinECLComfort310)
A232.1isheating/coolingrelatedapplication,onecontrol valve
A332.1islikeA232.1andhasadditionalreturntemperature limitation
A332.2isheating/coolingrelatedapplication,twocontrol valvesandreturntemperaturelimitation
A332.3islikeA332.2andhasadditionaladvancedDHWcircuit control
A332.4islikeA332.1andhasspecialoverridefunctionalities
ThedescribedfunctionsarerealizedinECLComfort210forbasic solutionsandinECLComfort310foradvancedsolutions,for exampleM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA232complieswithECLComfort210and ECLComfort310controllersasofsoftwareversion1.11(visible atstart-upofthecontrollerandin‘Commoncontrollersettings’ in‘System’).
ARemoteControlUnit,ECA30orECA31,canbeconnectedand thebuilt-inroomtemperaturesensorcanbeutilized.Whenusing theECA31,therelativehumiditysignalisusedforpreventing condensation(dew)whenincoolingmode.
TheapplicationA332.3workswiththeInternalI/OmoduleECA 32(ordercodeno.087H3202).
TogetherwiththeECLComfort310,theadditionalInternalI/O moduleECA32canalsobeusedforextradatacommunication toSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool". Navigation:Danfoss.com>Products&Solutions>DistrictHeating andCooling>T ools&Software>ECLTool. TheURLis:
https://www.danfoss.com/en/service-and-support/downloads
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
2|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
ECLComfort310isavailableas:
ECLComfort310,230volta.c(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby meansoftheremotecontrolunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210and310,modules andaccessoriesisavailableonhttp://danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AQ150486469826en-010501
©Danfoss|2021.06|3
OperatingGuideECLComfort210/296/310,applicationA232/A332
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
4|©Danfoss|2021.06
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
2
Circuit2Parameterno.
174
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
AQ150486469826en-010501
©Danfoss|2021.06|5
OperatingGuideECLComfort210/296/310,applicationA232/A332

2.0Installation

2.1Beforeyoustart

TheApplicationKeyA232contains5applications,allrelatedto floorheatingandceilingcoolingsystems.Theapplicationsinthe A232keyofferawiderangeofpossibilities(seetheexamples).
TheapplicationA232.1isveryflexible.Thesearethebasic principles:
Heating/coolingwithroomtemperaturecontrol:
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.
ThedesiredflowtemperatureatS3iscalculatedintheECL controller,basedontheoutdoortemperature(S1)andthedesired roomtemperature.Thelowertheoutdoortemperature,thehigher thedesiredflowtemperature(heating). Oppositely,thehighertheoutdoortemperature,thelowerthe desiredflowtemperature(cooling).Thechange-overbetween heatingandcoolingcanbe:
OutdoorANDroomtemperatureor
Roomtemperatureor
Outdoortemperaturerelated.
Bymeansofaweekschedule,thecircuitscanbein‘Comfort’or ‘Saving’mode(twovaluesforthedesiredroomtemperature).In Savingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M1)isopenedgraduallywhen:
(Heating)theflowtemperatureislowerthanthedesiredflow temperatureandviceversa.
(Cooling)theflowtemperatureishigherthanthedesiredflow temperatureandviceversa.
TheON-OFFoutputsX2/X3areactivatedatcooling/heating demandrespectively.
Roomtemperature: Ifthemeasuredroomtemperature(S2orECA30/31)doesnot equalthedesiredroomtemperature,thedesiredtemperatureat S3canbeadjusted.
Surfacetemperaturelimitation: Heating maximuminordertoavoidatoowarmfloor. Cooling:TheceilingsurfacetemperatureS6canbelimitedtoa minimuminordertoavoidatoocoldceiling(riskforcondensation).
Override: WhentheECLcontrollerisinscheduledmode,theS8inputcanbe usedforoverridingtheScheduletooperateinComfortorSaving mode.
Coolingmode: BasedontheRelativeHumidity(RH),measuredbyECA31,the desiredflowtemperaturecanbeminimumlimitedtoavoiddew (condensation).
:ThefloorsurfacetemperatureS5canbelimitedtoa
TypicalA232.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210 /296/310
S1
S2
S3
S4
S5
S6
S7
S8
P1
X2
X3
X4
M1
M2
ElectroniccontrollerECLComfort210,296or310
Outdoortemperaturesensor
ECA31RoomtemperatureandRHsensor*
Flowtemperaturesensor
notused
(Optional)Floorsurfacetemperaturesensor
(Optional)Ceilingsurfacetemperaturesensor
(notillustrated)Overrideinputforstopof circulationpump
(notillustrated)OverrideinputforComfort/ Saving
Circulationpump(ON/OFF)
Coolingdemand(ON/OFF)
Heatingdemand(ON/OFF)
(notillustrated)Multi-functionality
Motorizedcontrolvalve(3-pointcontrolled)
Motorizedchange-overvalve
*Alternative:ESM-10,roomtemperaturesensor
Thecirculationpump,P1,isONatheatingorcoolingdemandor atfrostprotection.
6|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheON-OFFoutputX4canbesetto
operateasaHumidistator
operateasaswitch,dependingontheoutdoortemperatureor
followSchedule1or
followSchedule2or
followSchedule3or
switchONatcoolingdemand
Alarm(visibleindisplay,nooutput): Alarmcanbeactivatediftheactualflowtemperaturediffersfrom thedesiredflowtemperature. Alarmwillalsobeactivatedif,inheatingmode,theflow temperatureexceedsasetmax.value.
Safetyfunction,heatingmode: IftheflowtemperatureS3exceedsasetmax.value,thealarmwill beactivated. CirculationpumpP1isswitchedOFFinordertopreventtoohigh temperaturetobecirculatedinthesystem(forexamplefloor circuit). P1isswitchedOFFfor35minutesandthenswitchedONfor30sec. Iftheflowtemperatureisbelowthesetmax.value,P1remainsON.
Foradescriptionofthechange-overfromheatingtocoolingmode, pleasereadthesection‘A232ingeneral’ .
AQ150486469826en-010501
©Danfoss|2021.06|7
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.1isverysimilartotheapplicationA232.1.
ExtrasinrelationtoA232.1:
Returntemperaturelimitation: ThereturntemperatureS10canbelimited,forexamplenotto betoohigh(heating)ortoolow(cooling).Ifso,thedesiredflow temperatureatS3canbeadjusted,forexampleatheatingtoa lowervalueor,atcoolingtoahighervalue. Thisresultsinagradualclosingofthemotorizedcontrolvalve. Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
TheON-OFFoutputX5canbesetto
followSchedule1or
followSchedule2or
followSchedule3or
switchONatcoolingdemand
AlarmA1: Analarmactivatesrelay6.
ChangesinrelationtoA332.1: TheON-OFFoutputX4canbesetto
operateasaHumidistator
operateasaswitch,dependingontheoutdoortemperature
Foradescriptionofthechange-overfromheatingtocooling operation,pleasereadthesection‘A232ingeneral’ .
TypicalA332.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S2
S3
S4
S5
S6
S7
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
ECA31RoomtemperatureandRHsensor*
Flowtemperaturesensor
notused
(Optional)Floorsurfacetemperaturesensor
(Optional)Ceilingsurfacetemperaturesensor
(notillustrated)Overrideinputforstopofcirculation pump
S8
S9
(notillustrated)OverrideinputforComfort/Saving
notused
S10Returntemperaturesensor
P1
X2
X3
X4
X5
M1
M2
A1
Circulationpump(ON/OFF)
Coolingdemand(ON/OFF)
Heatingdemand(ON/OFF)
(notillustrated)Multi-functionality
(notillustrated)Multi-functionality
Motorizedcontrolvalve(3-pointcontrolled)
Motorizedchange-overvalve
Alarm
*Alternative:ESM-10,roomtemperaturesensor
8|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.2isbasicallyliketheapplicationA332.1.
ExtrasinrelationtoA332.1:
Heatingandcoolingcircuitshaveseparateflowtemperature sensorsandcontrolvalves. Heatingandcoolingcircuitshaveseparatereturntemperature sensorsandlimitationfunctions.
ChangesinrelationtoA332.1: P2iscirculationpumpincoolingcircuit
Foradescriptionofthechange-overfromheatingtocooling operation,pleasereadthesection‘A232ingeneral’ .
TypicalA332.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S2
S3
S4
S5
S6
S7
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
ECA31RoomtemperatureandRHsensor*
Flowtemperaturesensor,heating
Flowtemperaturesensor,cooling
(Optional)Floorsurfacetemperaturesensor
(Optional)Ceilingsurfacetemperaturesensor
(notillustrated)Overrideinputforstopofcirculation pump
S8
S9
S10
P1
P2
X3
X4
X5
M1
M2
A1
(notillustrated)OverrideinputforComfort/Saving
Returntemperaturesensor,heating
Returntemperaturesensor,cooling
Circulationpump,heating(ON/OFF)
Circulationpump,cooling(ON/OFF)
Heatingdemand(ON/OFF)
Multi-functionality
Multi-functionality
Motorizedcontrolvalve,heating(3-pointcontrolled)
Motorizedcontrolvalve,cooling(3-pointcontrolled)
Alarm
*Alternative:ESM-10,roomtemperaturesensor
AQ150486469826en-010501
©Danfoss|2021.06|9
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.3isbasicallyliketheapplicationA332.2.
ExtrasinrelationtoA332.2:
TemperaturesensorsS5(heatingcircuit)andS6(coolingcircuit) canbeusedforeitherreturntemperaturelimitationorsurface temperaturelimitation.Functionalityselectionisdonebysetting aninfluencefactor.IfinfluencefactorsaresetforbothReturnand Surfacelimitation,therewillnotbeanylimitation.
AdvancedDomesticHotWater(DHW)heatingcontrol: TheDHWtemperatureatS9ismaintainedat‘Comfort’levelata DHWdraw-off(DHWtapping)(theflowswitchS8isactivated). IfthemeasuredDHWtemperatureatS9islowerthanthedesired DHWtemperature,themotorizedcontrolvalveM3isopened graduallyandviceversa. TheDHWtemperaturecontrolisinrelationtoactualsupply temperatureS7.Inordertocompensateforthereactiontime, themotorizedcontrolvalvecanbepre-activatedatthestartofa DHWdraw-off. Anidletemperature(thedesiredSavingtemperature)canbe maintainedateitherS7orS9whenthereisnoDHWdraw-off.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort’ or‘Saving’mode(twovaluesforthedesiredDHWtemperature).
ThereturntemperatureS10canbelimited,forexamplenottobe toohighortoolow. Ifso,thedesiredflowtemperatureatS9canbeadjusted,for exampletoalowervalue.Thisresultsinagradualclosingofthe motorizedcontrolvalve.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
Foradescriptionofthechange-overfromheatingtocooling operation,pleasereadthesection‘A232ingeneral’ .
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA332.3application:
Listofcomponents:
ECL310
ECA32
S1
S2
S3
S4
S5
S6
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
ECA31RoomtemperatureandRHsensor*
Flowtemperaturesensor,heating
Flowtemperaturesensor,cooling
(Optional)ReturnorFloorsurfacetemperaturesensor
(Optional)ReturnorCeilingsurfacetemperature sensor
S7
S8
S9
Supplytemperaturesensor,DHW
Flowswitch,DHWdraw-off
Flowtemperaturesensor,DHW
S10Returntemperaturesensor,DHW
P1
P2
P7
X3
X4
X5
M1
M2
M3
A1
Circulationpump,heating(ON/OFF)
Circulationpump,cooling(ON/OFF)
Circulationpump,DHW(ON/OFF)
(notillustrated)Heatingdemand(ON/OFF)
(notillustrated)Multi-functionality
(notillustrated)Multi-functionality
Motorizedcontrolvalve,heating(3-pointcontrolled)
Motorizedcontrolvalve,cooling(3-pointcontrolled)
Motorizedcontrolvalve,DHW(3-pointcontrolled)
Alarm
*Alternative:ESM-10,roomtemperaturesensor
10|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.4isbasicallyliketheapplicationA332.1.
Extras/changesinrelationtoA332.1:
Override:
WhentheECLcontrollerisinscheduledmode-
theS7inputcanbeusedforoverridingtoHeatingmode
theS9inputcanbeusedforoverridingtoCoolingmode
Foradescriptionofthechange-overfromheatingtocooling operation,pleasereadthesection‘A232ingeneral’ .
TypicalA332.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
S1
S2
S3
S4
S5
S6
S7
S8
S9
ElectroniccontrollerECLComfort310
Outdoortemperaturesensor
ECA31RoomtemperatureandRHsensor*
Flowtemperaturesensor
notused
(Optional)Floorsurfacetemperaturesensor
(Optional)Ceilingsurfacetemperaturesensor
OverrideinputforHeatingmode
OverrideinputforComfort/Saving
OverrideinputforCoolingmode
S10Returntemperaturesensor
P1
X2
X3
X4
X5
M1
M2
A1
Circulationpump(ON/OFF)
Coolingdemand(ON/OFF)
Heatingdemand(ON/OFF)
(notillustrated)Multi-functionality
(notillustrated)Multi-functionality
Motorizedcontrolvalve(3-pointcontrolled)
Motorizedchange-overvalve
Alarm
*Alternative:ESM-10,roomtemperaturesensor
AQ150486469826en-010501
©Danfoss|2021.06|11
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232,ingeneral
Thefunctionselector:
Eachcircuithasafunctionselector.Theheatingcircuitcanrun, forexample
Comfortperiodsatadesiredroomtemperatureof21°C
Savingperiodsatadesiredroomtemperatureof16°CorTotal stop
Thecoolingcircuitcanrun,forexample
Comfortperiodsatadesiredroomtemperatureof24°C
Savingperiodsatadesiredroomtemperatureof30°C
Schedules:
TheA232applicationcontains3weekschedules;oneforthe heatingcircuitandoneforthecoolingcircuit.Thethirdscheduleis foruniversaluseandisfoundin'Commoncontrollersettings'.
A232.1:Relay4(X4)canbesettofollowthethirdschedule. A332.1,A332.2,A332.3andA332.4:Relay5(X5)canbesettofollow thethirdschedule.
Overridefunctions:
Bymeansofswitches,connectedtodifferentinputs,thefollowing functionalitiesareavailablewhentheinputinquestionisactivated:
S7S8S9
A232.1
A332.1
A332.2
A332.3
A332.4
Stopthecirculationpump
Stopthecirculationpump
Stopthecirculationpump
NofunctionNofunctionNofunction
OverridetoHeating
OverridetoComfortorSavingmodeNofunction
OverridetoComfortorSavingmodeNofunction
OverridetoComfortorSavingmodeNofunction
OverridetoComfortorSavingmode
OverridetoCooling
12|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232,ingeneral,continued
Shortprocessdescriptions:
Changefromheatingtocooling(outdoorandroomtemperature based):
1.Heatingactive
2.Outdoorandroomtemperaturerising
3.Heatingstopwhenactualoutdoortemperaturegetshigher than'Summer,cut-out'(ID1x179)
4.Coolingstartwhen:
Accumulatedoutdoortemperaturevaluegetshigherthan
setlimit('Activation,acc.T' ,ID12144)
AND
Accumulatedroomtemperaturevaluegetshigherthanset
limit('Act.,acc.roomT',ID12156)
AND
Actualroomtemperaturegetshigherthandesiredroom
temperatureforcoolingoperation.
Changefromheatingtocooling(roomtemperaturebased):
1.Heatingactive
2.Roomtemperaturerising
3.Heatingstopwhenaccumulatedroomtemperaturevaluegets higherthandesiredroomtemperatureforheatingoperation.
4.Coolingstartwhen:
Accumulatedroomtemperaturevaluegetshigherthanset
limit('Act.,acc.roomT',ID12156)
AND
Actualroomtemperaturegetshigherthandesiredroom
temperatureforcoolingoperation.
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
AQ150486469826en-010501
©Danfoss|2021.06|13
OperatingGuideECLComfort210/296/310,applicationA232/A332

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
A232.1,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optional surfacetemperaturelimitations.
14|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232.1,ex.b:
Controlofflowtemperature(heating/cooling)infloorinrelationtooutdoor,roomanddewpointtemperature.Optionalsurface temperaturelimitation.
A232.1,ex.c:
Controlofflowtemperature(heating/cooling)toafan-coilinrelationtooutdoor,roomanddewpointtemperature.
AQ150486469826en-010501
©Danfoss|2021.06|15
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232.1,ex.d:
Controlofflowtemperature(heating/cooling)toafan-coilinrelationtooutdoor,roomanddewpointtemperature.Heatingsource: Districtheating.Coolingsource:Coolingmachine.
A232.1,ex.e:
Controlofflowtemperature(heating/cooling)inrelationtooutdoor,roomanddewpointtemperature.Heating/coolingsources: Districtheating/districtcooling.
16|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.1,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optionalreturn andsurfacetemperaturelimitation.
AllA232.1examplescanbecontrolledbyA332.1.
A332.2,ex.a:
Separatedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpointtemperature.Optionalreturn andsurfacetemperaturelimitations.
AQ150486469826en-010501
©Danfoss|2021.06|17
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.2,ex.b:
Districtheating/districtcoolingbasedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpoint temperature.Optionalreturnandsurfacetemperaturelimitations.
18|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.3,ex.aandb:
Separatedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpointtemperature.AdvancedDHW temperaturecontrolatDHWdraw-off.Anti-bacteriatemperaturecontrol.Optionalreturnorsurfacetemperaturelimitations.
AQ150486469826en-010501
©Danfoss|2021.06|19
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.4,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optionalreturn andsurfacetemperaturelimitation.Overridefunctionalitiesforheatingandcoolingmodes.
TheA232.1andA332.1examplescan,ingeneral,becontrolledbyA332.4.
20|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ150486469826en-010501
©Danfoss|2021.06|21
OperatingGuideECLComfort210/296/310,applicationA232/A332
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
22|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
AQ150486469826en-010501
©Danfoss|2021.06|23
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
24|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
AQ150486469826en-010501
©Danfoss|2021.06|25
OperatingGuideECLComfort210/296/310,applicationA232/A332
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
26|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
AQ150486469826en-010501
©Danfoss|2021.06|27
OperatingGuideECLComfort210/296/310,applicationA232/A332
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
0,2A/230Va.c.
28|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.5.2Electricalconnections,Pt1000temperaturesensors
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
AQ150486469826en-010501
©Danfoss|2021.06|29
OperatingGuideECLComfort210/296/310,applicationA232/A332
ConnectionsforA232,ingeneral:
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
TerminalSensor/description
29and30
28and30
27and30
26and30
25and30
24and30
23and30
22and30
21and30
20and30
S1
Outdoortemperature sensor*
S2Roomtemperature
sensor. Alternative:ECA31
S3
Flowtemperature sensor**
S4
A332.2andA332.3 only:Flowtemperature sensor,cooling**
S5
Surfaceorreturn temperaturesensor
S6
Surfaceorreturn temperaturesensor
S7
Overridesignal. A332.3only:Supply temperaturesensor
S8
Overridesignal. A332.3only:DHWflow switch
S9
ECL310only: A332.2:Return temperaturesensor. A332.3:DHWflow temperaturesensor** A332.4:Overridesignal
S10
ECL310only: Returntemperature sensor
Type (recom.)
ESMT
ESM-10
ESM-11/ ESMB/ ESMC/ ESMU
ESMC/ ESMU
ESM-11/ ESMB/ ESMC/ ESMU
ESM-11/ ESMB/ ESMC/ ESMU
Switch. ESM-11/ ESMB/ ESMC/ ESMU
Switch
ESM-11/ ESMB/ ESMC/ ESMU. Switch
ESM-11/ ESMB/ ESMC/ ESMU
Temperaturesensorsmustbeconnectedinordertohavethe desiredfunctionality.
*
Iftheoutdoortemperaturesensorisnotconnectedorthe sensorcableisshort-circuited,thecontrollerassumesthat theoutdoortemperatureis0(zero)°C.
**
Ifthesensorisnotconnectedorthesensorcableis short-circuited,themotorizedcontrolvalvecloses(safety function).
Factoryestablishedjumper: 30tocommonterminal.
30|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Overridecontacts/switches:
Exampleofoverridecontact,connectedtoS7:
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Connectionofswitchforexternaloverride
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ150486469826en-010501
©Danfoss|2021.06|31
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.5.3Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
32|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ150486469826en-010501
©Danfoss|2021.06|33
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.5.4Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
2.5.5Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
34|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.5.6Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
AQ150486469826en-010501
©Danfoss|2021.06|35
OperatingGuideECLComfort210/296/310,applicationA232/A332

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
36|©Danfoss|2021.06
ECLComfort296
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ150486469826en-010501
©Danfoss|2021.06|37
OperatingGuideECLComfort210/296/310,applicationA232/A332
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes' ,'Date' , 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
38|©Danfoss|2021.06
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
AQ150486469826en-010501
©Danfoss|2021.06|39
OperatingGuideECLComfort210/296/310,applicationA232/A332
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
40|©Danfoss|2021.06
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
AQ150486469826en-010501
©Danfoss|2021.06|41
OperatingGuideECLComfort210/296/310,applicationA232/A332
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
-
ECLComfort210/310,controllerversions1.36andup:
-
-
ECLComfort296,controllerversions1.58andup:
-
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
Takeouttheapplicationkey;for20minutes settingscanbechanged.
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
Takeouttheapplicationkey;for20minutes settingscanbechanged.
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
42|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
AQ150486469826en-010501
©Danfoss|2021.06|43
OperatingGuideECLComfort210/296/310,applicationA232/A332

2.8Navigation,ECLApplicationKeyA232/A332

Navigation,A232,applicationA232.1,heating
Home MENU
ScheduleSchedule
Settings
Sub-menu
Flow temperature
Roomlimit
Surfacelimit
Optimization
Controlpar.
Application
IDno.
11178 11177 11182 11183 11015 11060 11062 11061 11011 11012 11014 11026 11020 11021 11179 11174 11184 11185 11186 11187 11189 11024 11010 11500 11022 11023 11154 11153 11077 11078 11040 11093 11141 11142 11498
Function
Heatcurve Temp.max. Temp.min. Infl.-max. Infl.-min. Adapt.time Limit Infl.–max. Adapt.time Autosaving Boost Optimizer Pre-stop Basedon Totalstop Summer,cut-out Motorpr. Xp Tn Mrun Nz Min.act.time Actuator ECAaddr. SenddesiredT Pexercise Mexercise Filt.acc.outd.T Filt.acc.roomT PfrostT PheatT Ppost-run Frostpr.T Ext.input Ext.mode Toutdepend.
A232
A232.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
44|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A232,applicationA232.1,heatingcontinued
Home MENU
ScheduleSchedule
Settings
HolidaySelectable
Alarm
InfluenceoverviewDes.flowT
Sub-menu
IDno.
Optional function
Temp.monitor.
Max.temp.
AlarmoverviewClearalarm
11089 11160 11158 11159 11038
11147 11148 11149 11150 11079 11080
Function
Acc.outputfunc. Humidistat,setp. Humidistat,diff. Humidistat,postt. StopatTout
Upperdifference Lowerdifference Delay Lowesttemp. Max.flowT Delay
Max.temp. Temp.monitor. Tsensordefect Roomlim. Surfacelimit Holiday Ext.override ECAoverride Boost SCADAoffset Ext.stopcmd
A232
A232.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
AQ150486469826en-010501
©Danfoss|2021.06|45
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A232,applicationA232.1,cooling
Home MENU
ScheduleSchedule
Settings
HolidaySelectable
Alarm
InfluenceoverviewDes.flowT
Sub-menu
IDno.
FlowtemperatureCoolcurve
12178 12177 12164
Roomlimit
Surfacelimit
Application
Temp.monitor.
AlarmoverviewClearalarm
12182 12183 12015 12157 12027 12060 12063 12061 12144 11179 12500 12092 12141 12142
12147 12148 12149 12150
Function
Temp.max. Temp.min. Dewp.Toffset Infl.-max. Infl.-min. Adapt.time RoomTinfluence RoomTdiff. Limit Infl.–min. Adapt.time Activation,acc.T Summer,cut-out SenddesiredT StandbyT Ext.input Ext.mode
Upperdifference Lowerdifference Delay Lowesttemp.
Max.temp. Temp.monitor. Tsensordefect Roomlim. Surfacelimit Holiday SCADAoffset Ext.stopcmd
A232
A232.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
46|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A232.1,Commoncontrollersettings
Home
MENU
Time&Date
ScheduleSelectable
Inputoverview
Log1
Log2
Outputoverride
Keyfunctions
OutdoorTLogtoday
FlowT&desiredLogyesterday
RoomT&desiredLog2days
Surf.Theat&des.
FlowT&desiredLogtoday
RoomT&desiredLogyesterday
Surf.Tcool&des.
HumidityLog4days
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
IDno.
Commoncontrollersettings
Function
Selectable
OutdoorT
Outdooracc.T
RoomT
Roomacc.T
FlowT
Surf.T,heat
Surf.T,cool
Humidity
DewpointT
Ext.stopcmd
Log4days
Log2days
M1
P1
M2
X2
X3
X4
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
AQ150486469826en-010501
©Danfoss|2021.06|47
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A232.1,Commoncontrollersettingscontinued
Home
MENU SystemECLversion
Extension
Ethernet(ECLComfort310only) Portalconfig(ECLComfort310only)
M-busconfig(ECLComfort310only)
EnergyMeters (ECLComfort310only)
Rawinputoverview
Alarm Display
Communication
Language
IDno.
Commoncontrollersettings
Function
Codeno. Hardware
Software Serialno. Productiondate
Addresstype ECLportal Portalstatus
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210) S1-S10(ECLComfort310) S1-S18(ECLComfort310withECA32)
32:
Tsensordefect
60058
Backlight
60059
Contrast
2048
ECL485addr.
38
Modbusaddr.
39
Baud
2150
Servicepin
2151
Ext.reset
2050
Language
48|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A332,applicationsA332.1,A332.2,A332.3,A332.4,heating
Home
MENU
ScheduleSelectable
Settings
FlowtemperatureHeatcurve((((
Roomlimit
Returnlimit
Surfacelimit
Optimization
Controlpar.
IDno.
11178
11177
11182Infl.-max.((((
11183
11015
11031
11032
11033
11034
11035
11036
11037
11003
11060
11062
11061
12003
11011
11012
11014
11026
11020
11021
11179
11174
11184
11185
11186
11187
11189
11024
ApplicationsA332
Function
Temp.max.((((
Temp.min.
Infl.-min.((((
Adapt.time((((
HighToutX1((((
LowlimitY1((((
LowToutX2((((
HighlimitY2
Infl.–max.
Infl.–min.
Adapt.time
Circuit,sensor(
Limit
Infl.–max.
Adapt.time
Circuit,sensor(
Autosaving
Boost((((
Optimizer((((
Pre-stop((((
Basedon
Totalstop
Summer,cut-out((((
Motorpr.
Xp((((
Tn((((
Mrun((((
Nz((((
Min.act.time((((
Actuator((((
A332.1A332.2A332.3A332.4
(((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
(
AQ150486469826en-010501
©Danfoss|2021.06|49
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A332,applicationsA332.1,A332.2,A332.3,A332.4,heatingcontinued
Home
MENU
Settings
HolidaySelectable
Alarm
Application
Optionalfunction
Temp.monitor.
Max.temp.
AlarmoverviewClearalarm
IDno.
11010
11500
11022
11023
11154
11153
11077
11078
11040
11093
11141
11142
11498
11089
11160
11158
11159
11038
11083
11147
11148
11149
11150
11079
11080
ApplicationsA332
Function
ECAaddr.((((
SenddesiredT((((
Pexercise((((
Mexercise((((
Filt.acc.outd.T((((
Filt.acc.roomT((((
PfrostT((((
PheatT((((
Ppost-run((((
Frostpr.T((((
Ext.input((((
Ext.mode
Toutdepend.
Acc.outputfunc.
Humidistat,setp.
Humidistat,diff.
Humidistat,postt.
StopatTout((((
Add.function
Upperdifference
Lowerdifference
Delay
Lowesttemp.((((
Max.flowT
Delay
Max.temp.((((
Temp.monitor.((((
Tsensordefect((((
A332.1A332.2A332.3A332.4
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
50|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A332,applicationsA332.1,A332.2,A332.3,A332.4,heatingcontinued
Home
MENU
InfluenceDes.flowT
overview
IDno.
ApplicationsA332
Function
Returnlim.
Roomlim.((((
Surfacelimit((((
Holiday((((
Ext.override((((
ECAoverride((((
Boost((((
SCADAoffset((((
Ext.stopcmd(((
Ext.ONcmd(
A332.1A332.2A332.3A332.4
((((
AQ150486469826en-010501
©Danfoss|2021.06|51
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A332,applicationsA332.1,A332.2,A332.3,A332.4,cooling
Home
MENU
ScheduleSelectable
Settings
FlowtemperatureCoolcurve((((
Roomlimit
Returnlimit
Surfacelimit
Controlpar.
IDno.
12178
12177
12164
12182Infl.-max.((((
12183
12015
12157
12027
12030
12035
12036
12037
13003
12060
12063
12061
14003
12174
12184
12185
12186
12187
12189
12024
ApplicationsA332
Function
Temp.max.((((
Temp.min.
Dewp.Toffset
Infl.-min.((((
Adapt.time((((
RoomTinfluence((((
RoomTdiff.((((
Limit
Infl.–max.
Infl.–min.
Adapt.time
Circuit,sensor(
Limit
Infl.–min.
Adapt.time
Circuit,sensor(
Motorpr.
Xp((
Tn((
Mrun((
Nz((
Min.act.time((
Actuator((
A332.1A332.2A332.3A332.4
(((
(((
((((
((((
((((
((((
((((
((((
((((
((
(
(
52|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A332,applicationsA332.1,A332.2,A332.3,A332.4,coolingcontinued
Home
MENU
Settings
HolidaySelectable
Alarm
InfluenceDes.flowT
overview
Application
Temp.monitor.
AlarmoverviewClearalarm
IDno.
12156
12144
11179
12500
12022
12023
12070
12040
12092
12141
12142
12147
12148
12149
12150
ApplicationsA332
Function
Act.,acc.roomT
Activation,acc.T((((
Summer,cut-out((((
SenddesiredT((((
Pexercise((
Mexercise((
PcoolT((
Ppost-run((
StandbyT((((
Ext.input((((
Ext.mode
Upperdifference
Lowerdifference
Delay
Lowesttemp.((((
Temp.monitor.((((
Tsensordefect
Returnlim.
Roomlim.
Surfacelimit
Holiday
SCADAoffset
Ext.stopcmd
Ext.ONcmd
A332.1A332.2A332.3A332.4
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
(((
(
AQ150486469826en-010501
©Danfoss|2021.06|53
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A332,applicationA332.3,DHW
Home MENU
ScheduleSchedule Schedulecirc.PSchedule
Settings
HolidaySelectable
Alarm
InfluenceoverviewDes.flowT
Sub-menu
IDno.
Flowtemperature
Returnlimit
Controlpar.
Application
Anti-bacteriaSelectable
Temp.monitor.
AlarmoverviewClearalarm
13178 13177 13030 13035 13036 13037 13085 13173 13174
13185 13186 13187 13189 13097 13096 13094 13095 13500 13076 13040 13093 13141 13142
13147 13148 13149 13150
Function
Temp.max. Temp.min. Limit Infl.-max. Infl.-min. Adapt.time Priority Autotuning Motorpr. Xpactual Tn Mrun Nz Min.act.time SupplyT(idle) Tn(idle) Opentime Closetime SenddesiredT Circ.PfrostT Ppost-run Frostpr.T Ext.input Ext.mode
Upperdifference Lowerdifference Delay Lowesttemp.
Temp.monitor. Tsensordefect Returnlim. Holiday Ext.override Anti-bacteria SCADAoffset
A332
A332.3
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
54|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A332,applicationsA332.1,A332.2,A332.3,A332.4,Commoncontrollersettings
Home
MENU
Time&Date ScheduleSelectable HolidaySelectable
Inputoverview
Log1
Log2
LogtodayOutdoorT LogyesterdayFlowT&desired Log2daysRoomT&desired Log4daysHeatreturnT&limi
LogtodayFlowT&desired LogyesterdayRoomT&desired Log2daysCoolreturnT Log4days
IDno.
ApplicationsA332,Commoncontrollersettings
Function
Selectable
OutdoorT Outdooracc.T RoomT Roomacc.T
FlowT ReturnT
HeatflowT HeatreturnT
Surf.T,heat CoolflowT CoolreturnT Surf.T,cool DHWflowT DHWreturnT
SupplyT Humidity DewpointT
Ext.stopcmd S7status S9status
Surf.Theat&des.
Surf.Tcool&des. Humidity
A332.1A332.2A332.3A332.4
((((
((((
(
((((
((((
((((
((((
((
((
((
((
((((
((
((
((((
(
(
(
((((
((((
((
(
(
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
AQ150486469826en-010501
©Danfoss|2021.06|55
OperatingGuideECLComfort210/296/310,applicationA232/A332
Navigation,A332,applicationsA332.1,A332.2,A332.3,A332.4,Commoncontrollersettingscontinued
Home
MENU
Outputoverride
Keyfunctions
SystemECLversion
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview Alarm Display
Communication
Language
60058 60059
2048
38
39 2150 2151 2050
Function
M1 P1 M2 P2 M3 P7 X2 X3 X4 X5 A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. Productiondate
Tsensordefect Backlight Contrast ECL485addr. Modbusaddr. Baud Servicepin Ext.reset Language
ApplicationsA332,Commoncontrollersettings
A332.1A332.2A332.3A332.4
((((
((((
((((
((
(
(
((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
((((
56|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ150486469826en-010501
©Danfoss|2021.06|57
OperatingGuideECLComfort210/296/310,applicationA232/A332

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
58|©Danfoss|2021.06
)
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
DHWcircuit
Overviewdisplay1informsabout: actualDHWtemperature,controllermode,desiredDHW temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout: stateofthecontrolledcomponents,actualDHWtemperature, (desiredDHWtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith Influenceindication:
AQ150486469826en-010501
©Danfoss|2021.06|59
OperatingGuideECLComfort210/296/310,applicationA232/A332
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
Examples:
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled operationandincomfortmode.
Examples:
50
55
60|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
AQ150486469826en-010501
©Danfoss|2021.06|61
OperatingGuideECLComfort210/296/310,applicationA232/A332

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
62|©Danfoss|2021.06
DamperOFF
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview oftheactualand(desired)temperaturesaswellastheactualstate ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
(30)
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
Flowtemperature
Desiredflowtemperature
--
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
AQ150486469826en-010501
©Danfoss|2021.06|63
OperatingGuideECLComfort210/296/310,applicationA232/A332
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
64|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
AQ150486469826en-010501
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
©Danfoss|2021.06|65
OperatingGuideECLComfort210/296/310,applicationA232/A332

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
66|©Danfoss|2021.06
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Xpactual
Day
Starttime
Duration
DesiredT
Circuit,sensor(functionalityofreturn/surfacetemperature sensor)
Circuit,sensor(functionalityofreturn/surfacetemperature sensor)
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Optimizer(optimizingtimeconstant)
Adapt.time(adaptiontime)
Basedon(optimizationbasedonroom/outdoortemp.)
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Actuator
Pre-stop(optimizedstoptime)
RoomTdiff.(Roomtemperaturedifferenceforswitching coolingmodeONandOFF)
Limit(returntemp.limitation)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
StopatTout(Stopfunctionrelatedtotheoutdoor temperature)
Ppost-run
Limit(Limitationofsurfacetemperature)
Adapt.time(adaptationtime)
Infl.max(Influenceduringheatingmode)
Infl.min(Influenceduringcoolingmode)
PcoolT(coolingdemand)
Circ.PfrostT
1x00381
1x00385
1x010101
1x01188
1x01289
1x01490
1x015
1x02091
1x02191
1x022101
1x023101
1x02495
1x02692
1x027
1x03082
1x03182
1x03282
1x03382
1x03482
1x03583
1x03683
1x03783
1x038
1x040102
1x06086
1x06186
1x06286
1x06386
1x070102
1x076102
Factorysettingsincircuit(s)
1
71
97
119
119
120
120
75
75
111
2
AQ150486469826en-010501
©Danfoss|2021.06|67
OperatingGuideECLComfort210/296/310,applicationA232/A332
SettingIDPage
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Max.flowT(Maximumflowtemperature)
Delay
Add.function(Additionalfunction,Relay5(X5))
Priority(priorityforreturntemp.limitation)
Acc.outputfunc.(Accessoryoutputfunction,Relay4(X4))
Frostpr.T(frostprotectiontemp.)
Opentime
Closetime
Tn(idle)
SupplyT(idle)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Activation,acc.T(Activationofcoolingmode,basedon accumulatedoutdoortemperaturevalue)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Filt.acc.roomT(Filterforaccumulatedroomtemperature value)
Filt.acc.outd.T(Filterforaccumulatedoutdoortemperature value)
Act.,acc.roomT(Activationofcoolingmode,basedon accumulatedroomtemperaturevalue)
RoomTinfluence(Roomtemperatureinfluenceincooling mode)
Humidistat,diff.(Humidistat,differenceforswitching)
Humidistat,postt.(Humidistat,postON-time)
Humidistat,setp.(Humidistat,setpoint)
Dewp.Toffset(Dewpointtemperature,offset)
Autotuning
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Summer,cut-out(limitforheatingcut-out)
Infl.-max.(roomtemp.limitation,max.)
Infl.-min.(roomtemp.limitation,min.)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
1x077102
1x078103
1x079
1x080116
1x083
1x08583
1x089112
1x093103
1x09495
1x09596
1x09696
1x09796
1x141
1x142104
1x144
1x147
1x148116
1x149
1x150
1x153107
1x154
1x156108
1x157
1x158112
1x159113
1x160113
1x16473
1x17396
1x174
1x17774
1x178
1x17993
1x179108
1x18276
1x183
1x18497
1x18598
1x18698
1x18798
Factorysettingsincircuit(s)
1
115
111
103
106
116
117
117
107
76
97
74
77
2
68|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
SettingIDPage
Min.act.time(min.activationtimegearmotor)
Toutdepend.(Outdoortemperaturedependentactivation ofcoolingmode)
SenddesiredT
1x18998
1x498109
1x500109
Factorysettingsincircuit(s)
1
2
AQ150486469826en-010501
©Danfoss|2021.06|69
OperatingGuideECLComfort210/296/310,applicationA232/A332

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Y oumightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
70|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

5.2Flowtemperature/Inlettemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature/Inlettemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
AQ150486469826en-010501
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
©Danfoss|2021.06|71
OperatingGuideECLComfort210/296/310,applicationA232/A332
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
TheECLComfort210/296/310controlstheDHWtemperature accordingtothedesiredflowtemperatureforexampleunderthe influenceofthereturntemperature.
ActualDHWtemp.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
DesiredDHW temp.
72|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Coolcurve
Theapplicationdeterminesandcontrolsthecoolingflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledthecoolcurve.
Thecoolcurveisformedby6coordinatepoints.Thedesired coolingflowtemperatureissetat6pre-definedoutdoor temperaturevalues.
Theshownvalueforthecoolcurveisanaveragevalue(slope), basedontheactualsettings.
Outdoortemp.
Desiredflowtemp.
Yoursettings
(factorysettings) 20°C 25°C 30°C 35°C 40°C 45°C
20 19 18 17 16 15
Changethecoordinates:
Pushthedialtoenter/changethedesiredflowtemperatureatthe 6coordinatesofthecoolingcurve,(example:20,20).
Thecoolcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C.
Coolcurve
Thesmallarrows()indicate6differentoutdoortemperature valuesatwhichyoucanchangethecoolcurve.
Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×CC×2.5 where"CC"istheCoolcurveslopeand"2.5"isaconstant.
Coolcurve
Example,changeofdesiredroomtemperature:
Coolcurve: Desiredflowtemp.: Desiredroomtemp.: Calculation(18-20)×0.2×2.5= Result: Thedesiredflowtemperaturewillbecorrectedfrom18°Cto17°C.
0.2 18°C 18°C
-1
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
AQ150486469826en-010501
©Danfoss|2021.06|73
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Flowtemperature/Inlettemperature
Dewp.Toffset(Dewpointtemperature,offset)
Thevaluecalculatedbythecontrollerforthedewpointtemperaturecanbe offsetadjusted(displaced).Thedewpointtemperatureisthetemperatureat whichwaterintheaircondenses.IftheECA31isnotplacedcorrectly,itcan beusefultooffsetadjustthecalculateddewpointtemperature.
1x164
SeeAppendix“ParameterIDoverview”
Value:
Settheoffsetvalue
MENU>Settings>Flowtemperature/Inlettemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
MENU>Settings>Flowtemperature/Inlettemperature
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
74|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

5.3Roomlimit

ThefollowingsectionisageneraldescriptionforRoom temperaturelimitation. Theactualapplicationmightnothavebothlimitationtypes.
Thissectionisonlyrelevantifyouhaveinstalledaroom temperaturesensororaRemoteControlUnitforutilizingtheroom temperaturesignal.
Inthefollowingdescriptionisreferredto"flowtemperature"in general.
Thecontrolleradjuststhedesiredflowtemperaturetocompensate forthedifferencebetweenthedesiredandtheactualroom temperature.
Iftheroomtemperatureishigherthanthedesiredvalue,the desiredflowtemperaturecanbereduced.
The'Infl.-max.'(Influence,max.roomtemp.)determineshow muchthedesiredflowtemperatureshouldbereduced.
Usethisinfluencetypetoavoidatoohighroomtemperature.The controllerwillallowforfreeheatgains,i.e.solarradiationorheat fromafireplaceetc.
Iftheroomtemperatureislowerthanthedesiredvalue,thedesired flowtemperaturecanbeincreased.
The'Infl.-min.'(Influence,min.roomtemperature)determines howmuchthedesiredflowtemperatureshouldbeincreased.
Usethisinfluencetypetoavoidatoolowroomtemperature.This coulde.g.becausedbywindysurroundings.
Atypicalsettingwillbe-4.0for'Infl.-max.'and4.0for'Infl.-min. '
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Roomlimit
Adapt.time(adaptiontime)
Controlshowfasttheactualroomtemperatureadaptstothedesiredroom temperature(Icontrol).
1x015
Theadaptationfunctioncancorrectthedesiredroomtemperature withmax.8Kxheatcurveslopevalue.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe'Adapt. time'.
Minor
Thedesiredroomtemperatureisadaptedquickly.
value: Major
Thedesiredroomtemperatureisadaptedslowly.
value:
AQ150486469826en-010501
©Danfoss|2021.06|75
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Roomlimit
RoomTdiff.(Roomtemperaturedifferenceforswitching coolingmodeONandOFF)
Settingthedifferenceforroomtemperatureincoolingmodeforswitching coolingONandOFF .
SeeAppendix“ParameterIDoverview”
Value:
Setthedifference
1x027
=
X
T
#1#
#2#
#3#
#4#
Inordertohavethedesiredfunctionality,theparameter'RoomT influence'(ID12157)mustbesettoON.
Time
=
Temperature
=
Actualroomtemperature
=
'RoomTdiff. '(ID1x027)
=
Desiredroomtemperature,cooling
=
Cooling
MENU>Settings>Roomlimit
RoomTinfluence(Roomtemperatureinfluenceincooling mode)
DeterminationforroomtemperatureinfluencewheninCoolingmode.
SeeAppendix“ParameterIDoverview”
OFF:
RoomtemperaturehasnoinfluenceforCoolingON /OFF
ON:
RoomtemperaturehasinfluenceforCoolingON/OFF
Selectthedesiredfunctionality.
1x157
76|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Roomlimit
Infl.-max.(roomtemp.limitation,max.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (decreased)iftheactualroomtemperatureishigherthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
0.0:
-2.0:
-5.0:
-9.9:
Noinfluence Minorinfluence Mediuminfluence Maximuminfluence
1x182
=
X
#1#
#2#
#3#
Roomtemperature
=
Desiredroomtemperature
=
Negativeinfluence(1x082)whenactualroomtemp.getshigher thandesiredroomtemp.
=
Positiveinfluence(1x083)whenactualroomtemp.getslowerthan desiredroomtemp.
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x-4.0x1.8) –14.4degrees.
MENU>Settings>Roomlimit
Infl.-min.(roomtemp.limitation,min.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (increased)iftheactualroomtemperatureislowerthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
9.9:
5.0:
2.0:
0.0:
Maximuminfluence Mediuminfluence Minorinfluence Noinfluence
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x-4.0x1): –8.0degrees.
Example
1x183
Theactualroomtemperatureis2degreestoolow. The‘Infl.-min.’issetto4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x4.0x1.8)
14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x4.0x1):
8.0degrees.
AQ150486469826en-010501
©Danfoss|2021.06|77
OperatingGuideECLComfort210/296/310,applicationA232/A332

5.4Returnlimit

Thereturntemperaturelimitationisbasedonaselectable temperaturevalue.Thecontrollerautomaticallychanges thedesiredflowtemperaturetoobtainanacceptablereturn temperaturewhenthereturntemperaturefallsbeloworgets higherthanthesetlimit.
ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')respondsslower andovertimeremovesthesmalloffsetsbetweenthedesiredand actualvalues.Thisisdonebychangingthedesiredflow/duct temperature.
Typicalforheating
systemsisthatthereturntemperaturemustbe
aslowaspossible.
Typicalforcoolingsystemsisthatthereturntemperaturemustbe ashighaspossible.
Someparameterdescriptionsreferto"ducttemperature"because theparameterinquestionisusedinotherapplicationstoo.
Someparameterdescriptionsreferto"surfacetemperature" becausetheparameterinquestionisusedinotherapplicationstoo.
Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Influence
‘Infl.-min. ’>0
‘Limit’
‘Infl.-max. ’>0
Returntemperature
‘Infl.-max. ’<0
‘Infl.-min. ’<0
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
=
X Y #X1# #X2# #Y1# #Y2#
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
78|©Danfoss|2021.06
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant temperaturevalue. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthesetlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
=
X
=
#1#
=
#2#
=
#3#
=
#4#
=
#5#
Returntemperature Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan limit.temp.
Negativeinfluence(1x036)whenreturntemp.getslowerthan limit.temp.
Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit. temp.
Positiveinfluence(1x035)whenreturntemp.getshigherthan limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
AQ150486469826en-010501
©Danfoss|2021.06|79
OperatingGuideECLComfort210/296/310,applicationA232/A332
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
80|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
Circuit,sensor(functionalityofreturn/surface temperaturesensor)
Settingthefunctionalityforthereturn/surfacetemperaturesensor.
SeeAppendix“ParameterIDoverview”
OFF:
Sensorinquestionisnotusedasreturn/surface temp.sensor
ON:
Sensorinquestionisusedasreturn/surfacetemp. sensor
Selectthedesiredfunctionality.
1x003
AQ150486469826en-010501
©Danfoss|2021.06|81
OperatingGuideECLComfort210/296/310,applicationA232/A332
SubtypeA332.3only: TemperaturesensorsS5(heatingcircuit)andS6(coolingcircuit)canbe
usedforeitherreturntemperaturelimitationorsurfacetemperature limitation.
Functionalityselectionisdonebysettinganinfluencefactor. IfinfluencefactorsaresetforbothReturnandSurfacelimitation,there
willnotbeanylimitation.
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe setvalue,thecontrollerautomaticallychangesthedesiredflow/ ducttemperaturetoobtainanacceptablereturntemperature.The influenceissetin'Infl.-max. 'and'Infl.-min.' .
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
1x031
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
1x032
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
82|©Danfoss|2021.06
1x033
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthesetlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthesetlimit.
1x034
Example
1x035
Thereturnlimitisactiveabove50°C. Theinfluenceissetto0.5. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby0.5x2=1.0degree.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
Example
1x036
1x037
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
AQ150486469826en-010501
©Danfoss|2021.06|83
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
84|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332

5.5Surfacelimit

Thesurfacetemperatureoftheheatedfloorcanbelimitedtoa maximumtemperature. Thesurfacetemperatureofthecooledceilingorthecooled floorcanbelimitedtoaminimumtemperatureinordertoavoid condensation.
Thesurfacetemperaturelimitationsarebasedonselectable temperaturevalues;onevalueforheatingmode,anothervalue forcoolingmode. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablesurfacetemperaturewhenthetemperature getshigherthan(heating)orfallsbelow(cooling)thesetlimits.
Typicalforheatingsystemsisthatatoohighsurfacetemperature shouldbeavoided.
Typicalforcoolingsystemsisthatatoolowsurfacetemperature shouldbeavoided.Riskforcondensationmayexist.
Someparameterdescriptionsreferto"ducttemperature"because theparameterinquestionisusedinotherapplicationstoo.
Someparameterdescriptionsreferto"compensationtemperature" becausetheparameterinquestionisusedinotherapplicationstoo.
Someparameterdescriptionsreferto"returntemperature"because theparameterinquestionisusedinotherapplicationstoo.
NoteforsubtypeA332.3: TemperaturesensorsS5(heatingcircuit)andS6(coolingcircuit) canbeusedforeitherreturntemperaturelimitationorsurface temperaturelimitation. Functionalityselectionisdonebysettinganinfluencefactor.If influencefactorsaresetforbothReturnandSurfacelimitation, therewillnotbeanylimitation.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Surfacelimit
Circuit,sensor(functionalityofreturn/surface temperaturesensor)
Settingthefunctionalityforthereturn/surfacetemperaturesensor.
1x003
SeeAppendix“ParameterIDoverview”
OFF:
Sensorinquestionisnotusedasreturn/surface temp.sensor
ON:
Sensorinquestionisusedasreturn/surfacetemp. sensor
Selectthedesiredfunctionality.
AQ150486469826en-010501
©Danfoss|2021.06|85
OperatingGuideECLComfort210/296/310,applicationA232/A332
SubtypeA332.3only: TemperaturesensorsS5(heatingcircuit)andS6(coolingcircuit)canbe
usedforeitherreturntemperaturelimitationorsurfacetemperature limitation.
Functionalityselectionisdonebysettinganinfluencefactor. IfinfluencefactorsaresetforbothReturnandSurfacelimitation,there
willnotbeanylimitation.
MENU>Settings>Surfacelimit
Limit(Limitationofsurfacetemperature)
Whenthesurfacetemperaturegetshigherthan(heatingmode)orlower than(coolingmode)thesetvalue,thecontrollerautomaticallydecreases orincreasesthedesiredflowtemperaturetoobtainanacceptablesurface temperature.Theinfluencesissetin'Infl.-max. '(heating)and'Infl.-min. ' (cooling).
SeeAppendix“ParameterIDoverview”
Value:Setthelimitationvalue
MENU>Settings>Surfacelimit
Adapt.time(adaptationtime)
Controlshowfastthecompensation/surfacetemperatureinfluencesthe desiredflow/ducttemperature.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredflow/ducttemperatureisadaptedquickly.
value: Major
Thedesiredflow/ducttemperatureisadaptedslowly.
value: Value:Settheadaptationtime
1x060
1x061
Theadaptationfunctioncancorrectthedesiredflow/duct temperaturewithmax.8K.
MENU>Settings>Surfacelimit
Infl.max(Influenceduringheatingmode)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (decreased)iftheactualsurfacetemperaturegetshigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
0.0:
-2.0:
-5.0:
-9.9:
Value:
Noinfluence Minorinfluence Mediuminfluence Maximuminfluence
Settheinfluencevalue
86|©Danfoss|2021.06
Example
1x062
Thelimitvalueissetto25°C. ‘Infl.max. ’issetto2.5. Theactualsurfacetemperatureis27°C(2degreesabovethelimit
value). Result: Thedesiredflowtemperatureisdecreasedwith2.5x2=5degrees.
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Surfacelimit
Infl.min(Influenceduringcoolingmode)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (increased)iftheactualsurfacetemperaturegetslowerthanthesetlimit.
SeeAppendix“ParameterIDoverview”
9.9:
5.0:
2.0:
0.0:
Value:
Maximuminfluence Mediuminfluence Minorinfluence Noinfluence
Settheinfluencevalue
Example
1x063
Thelimitvalueissetto15°C. ‘Infl.min. ’issetto1.3. Theactualsurfacetemperatureis12°C(3degreesbelowthelimit
value). Result: Thedesiredflowtemperatureisincreasedby1.3x3=3.9degrees.
AQ150486469826en-010501
©Danfoss|2021.06|87
OperatingGuideECLComfort210/296/310,applicationA232/A332

5.6Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost' ,'Optimizer','Totalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
88|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
AQ150486469826en-010501
©Danfoss|2021.06|89
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
1x012
90|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
MENU>Settings>Optimization
Basedon(optimizationbasedonroom/outdoortemp.)
Theoptimizedstartandstoptimecanbebasedoneitherroomoroutdoor temperature.
SeeAppendix“ParameterIDoverview”
OUT:
Optimizationbasedonoutdoortemperature.Usethis settingiftheroomtemperatureisnotmeasured.
ROOM:
Optimizationbasedonroomtemperature,ifmeasured.
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
1x020
-5°C
small
AQ150486469826en-010501
©Danfoss|2021.06|91
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
Totalstop=OFF
OFF:
ON:
Nototalstop.
Heatingapplicationsingeneral: Savingmode:
Thedesiredflow/duct temperatureisreduced accordingtodesiredduct/ roomtemperature.
Comfortmode:Iftheroomtemperaturegets
higherthandesiredroom temperature,theheating switchesOFF .
Seealsotheheatingrelatedexamples.
Coolingapplications: Savingmode:Themotorizedcontrolvalve
closes.
Totalstop.
Heatingapplicationswithdesiredducttemperature: Savingmode:
Thedesiredflowtemperature issetto'Frostpr.T'(Frost protectiontemperature).
Heatingapplicationswithdesiredroomtemperature: Savingmode:
Theheatingisstoppedaslong astheroomtemperatureis higherthanthedesiredroom temperature.
Seealsotheheatingrelatedexamples.
Coolingapplications: Savingmode:
Themotorizedcontrolvalve closes.
Ingeneral,whentotalstopisON,theheatingorcooling closestotallywhenthecontrollergoesintosavingmode. However,when'Totalstop'isON,thecontrollerhasroom temperaturerelatedfunctionsalsoincomfortmode.
Totalstop=ON
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
92|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
1x026
Example:OptimizationofComfortfrom07:00-22:00
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min. ’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
X #1# #2# #3# #4# #5#
Summer,cut-out
=
X
=
Y
=
#1#
=
#2#
=
#3#
=
#4#
=
#5#
=
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
Time
Temperature
Actualoutdoortemperature
Cut-outtemperature(1x179)
Accummulated(filtered)outdoortemperature
Heatingenabled
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
AQ150486469826en-010501
©Danfoss|2021.06|93
OperatingGuideECLComfort210/296/310,applicationA232/A332

5.7Controlparameters

Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point controlsignal.
Valvecontrol: Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
94|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
Thermo-actuator,DanfosstypeABV
Danfossthermo-actuatortypeABVisaslowactingvalveactuator. InsidetheABVanelectricheatcoilwillheatathermostaticelement whenanelectricsignalisapplied.Whenheatingthethermostatic elementitexpandsinordertomanagethecontrolvalve. Twobasictypesareavailable:ABVNC(NormalClosed)andABVNO (normalopen).Forexample,ABVNCkeepsa2-portcontrolvalve closedwhennoopen-signalsareapplied. Electricopen-signalscomefromtheelectronicoutputoftheECL Comfortcontrollerinordertomanagethecontrolvalve.When open-signalsareappliedtotheABVNC,thevalvegraduallyopens. Open-signalsareintheECLComfortcontrollerexpressedas "Arrow-up"(open)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,relativelylongopen-signalscomefrom theECLComfortcontrollerinordertoincreasetheflow.Bythis, theflowtemperaturewillovertimebealignedwiththedesired temperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,relativelyshortopen-signalscomefromtheECL Comfortcontrollerinordertoreducetheflow.Again,theflow temperaturealigns,overtime,withthedesiredtemperature. ThecontroloftheDanfossthermo-actuatortypeABVusesaunique designedalgorithmandisbasedonthePWMprinciple(Pulse WidthModulation),wherethedurationofthepulsedetermines themanagementofthecontrolvalve.Thepulsesarerepeated each10sec. Aslongastheflowtemperaturecorrespondstothedesired temperature,thedurationoftheopen-signalswillremainconstant.
DHWtemperaturecontrol(subtypeA332.3): 'Opentime'and'Closetime'areusedforcompensationofthedelay inthetemperaturecontrol. 'Tn(idle)'canensureaminimumsupplytemperatureinidle(=no DHWdraw-off(tapping)).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Actuator
ABV/GEAR
1x024
GEAR
Selectionofvalveactuatortype.
ABV:
GEAR:
DanfosstypeABV(thermoactuator). Gearmotorbasedactuator.
Whenselecting"ABV",thecontrolparameters:
•Motorprotection(ID1x174)
•Xp(ID1x184)
•Tn(ID1x185)
•Mrun(ID1x186)
•Nz(ID1x187)
•Min.act.time(ID1x189)
arenotconsidered.
AQ150486469826en-010501
©Danfoss|2021.06|95
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Controlparameters
Opentime
The‘Opentime’istheforcedtime(inseconds)thatittakestoopenthe motorizedcontrolvalvewhenaDHWdraw-off(tapping)isdetected(the flowswitchisactivated).Thisfunctioncompensatesforthedelaybeforethe flowtemperaturesensormeasuresachangeintemperature.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
Closetime
The‘Closetime’istheforcedtime(inseconds)thatittakestoclosethe motorizedcontrolvalvewhenaDHWdraw-off(tapping)isstopped(the flowswitchisdeactivated).Thisfunctioncompensatesforthedelaybefore theflowtemperaturesensormeasuresachangeintemperature.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
Tn(idle)
WhennoDHWdraw-off(tapping)isdetected(theflowswitchisdeactivated), thetemperatureismaintainedatalowlevel(savingtemperature).The integrationtime‘Tn(idle)’canbesettoobtainaslowbutstablecontrol.
1x094
1x095
1x096
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
SupplyT(idle)
The‘supplyT(idle)’isthesupplytemperaturewhenthereisnoDHW draw-off(tapping).WhenDHWdraw-offisnotdetected(theflowswitch isdeactivated),thetemperatureismaintainedatalowerlevel(saving temperature).Choosewhichtemperaturesensoristomaintainthesaving temperature.
SeeAppendix“ParameterIDoverview”
OFF:
ThesavingtemperatureismaintainedattheDHWflow temperaturesensor.
ON:
Thesavingtemperatureismaintainedatthesupply temperaturesensor.
1x097
Ifthesupplytemperaturesensorisnotconnected,theidlesupply temperaturewillbemaintainedattheDHWflowtemperaturesensor.
96|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Controlparameters
Autotuning
AutomaticallydeterminesthecontrolparametersfortheDHWcontrol.'Xp' 'Tn'and'Mrun'donotneedtobeset,whenusingautotuning.'Nz'must beset.
1x173
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Autotuningisnotactivated. Autotuningisactivated.
Theautotuningfunctionautomaticallydeterminesthecontrol parametersforDHWcontrol.Thusyoudonotneedtosetthe'Xp', 'Tn'and'Mrun',astheyareautomaticallysetwhentheautotuning functionissettoON.
Autotuningistypicallyusedinconnectionwiththeinstallationof thecontroller,butitcanbeactivatedwhenneeded,e.g.foran extracheckofthecontrolparameters.
Beforestartingtheautotuning,thetappingflowshouldbe adjustedtotherelevantvalue(seetable).
Ifpossible,anyadditionalDHWconsumptionshouldbeavoided duringtheautotuningprocess.Shouldthetappingloadvarytoo much,theautotuningandcontrollerwillreturntothedefault settings.
No.of apartments
Heat transfer
ConstantDHWdraw-off(l/min)
(kW)
1-230-493 3-950-796 10-4980-14912
50-129150-24918
130-210250-35024
Inordertomeetthesummer-/wintervariations,theECLclockmust besettothecorrectdateforansuccessfulautotuning.
Themotorprotectionfunction('Motorpr.')hastobedeactivated duringautotuning.Duringautotuningthecirculationpumpfortap watermustbeswitchedoff.Thisisdoneautomaticallyifthepumpis controlledbytheECLcontroller.
Autotuningisonlyapplicableinconnectionwithvalvesthatare approvedforautotuning,i.e.theDanfosstypesVB2andVM2with splitcharacteristicaswellaslogarithmicvalvessuchasVFandVFS.
(or1tap25%open) (or1tap50%open) (or1tap100%open)
(or1tap100%+1tap50% open)
(or2taps100%open)
AutotuningisactivatedbysettingthefunctiontoON.Whenthe autotuningisended,thefunctionisautomaticallyconvertedto OFF(defaultsetting).Thiswillbeindicatedinthedisplay.
Theautotuningprocesstakesupto25minutes.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
1x174
1x184
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
AQ150486469826en-010501
©Danfoss|2021.06|97
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Controlparameters
Xpactual
‘Xpactual’istheread-outoftheactualXp(proportionalband)basedon thesupplytemperature.Xpisdeterminedbysettingsrelatedtothesupply temperature.Typically,thehigherthesupplytemperature,thehighertheXp mustbeinordertoachieveastabletemperaturecontrol.
Xpsettingrange:
5...250K
Fixedsupplytemperaturesettings:65°Cand90°C Factorysettings:
(65,40)and(90,120)
Thismeansthatthe‘Xp’is40Kat65°Csupplytemperature,and ‘Xp’is120Kat90°C.
SetthedesiredXpvaluesatthetwofixedsupplytemperatures.
Ifthesupplytemperatureisnotmeasured(thesupplytemperature sensorisnotconnected),theXpvalueatthesetting65°Cisused.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
1x186
1x187
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
98|©Danfoss|2021.06
AQ150486469826en-010501
OperatingGuideECLComfort210/296/310,applicationA232/A332
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
AQ150486469826en-010501
©Danfoss|2021.06|99
OperatingGuideECLComfort210/296/310,applicationA232/A332
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
Criticaltimeperiod
Time
100|©Danfoss|2021.06
AQ150486469826en-010501
Loading...