Danfoss A231, A331 Operating guide

OperatingGuide
ECLComfort210/296/310,applicationA231/ A331

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.3Mounting...........................................................16
2.4Placingthetemperaturesensors................................20
2.5Electricalconnections.............................................22
2.6InsertingtheECLApplicationKey..............................31
2.7Checklist............................................................38
2.8Navigation,ECLApplicationKeyA231/A331................39
3.0Dailyuse.........................................................45
3.1Howtonavigate...................................................45
3.2Understandingthecontrollerdisplay..........................46
3.3Ageneraloverview:Whatdothesymbolsmean?...........49
3.4Monitoringtemperaturesandsystem
components........................................................50
3.5Influenceoverview................................................51
3.6Manualcontrol.....................................................52
3.7Schedule............................................................53
4.0Settingsoverview............................................54
5.0Settings...........................................................56
5.1IntroductiontoSettings..........................................56
5.2Flowtemperature..................................................57
5.3Returnlimit.........................................................62
5.4Flow/powerlimit.................................................66
5.5Optimization........................................................70
5.6Controlparameters................................................76
5.7Pumpcontrol.......................................................79
5.8Refillwater..........................................................82
5.9Application.........................................................87
5.10Alarm................................................................92
5.11Alarmoverview....................................................96
6.0Commoncontrollersettings..............................97
6.1Introductionto‘Commoncontrollersettings’................97
6.2Time&Date.........................................................98
6.3Holiday..............................................................99
6.4Inputoverview...................................................101
6.5Log.................................................................102
6.6Outputoverride..................................................103
6.7Keyfunctions.....................................................104
6.8System.............................................................106
7.0Miscellaneous................................................113
7.1ECA30/31setupprocedures.................................113
7.2Overridefunction................................................121
7.3Severalcontrollersinthesamesystem......................124
7.4Frequentlyaskedquestions....................................127
7.5Definitions........................................................131
7.6Type(ID6001),overview.......................................135
7.7Automatic/manualupdateoffirmware.....................136
7.8ParameterIDoverview..........................................137
©Danfoss|2021.02AQ000086469805en-010501|1
ECLComfort210/296/310,applicationA231/A331

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA231 (ordercodeno.087H3805).
TheA231Keycontainstwosetsofapplications:oneset(A231.1/ A231.2)andanotherset(A331.1/A331.2).
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationexamplesandelectricalconnections.
Thedescribedfunctionsarerealizedin:
ECLComfort210forbasicsolutions
ECLComfort296forbasicsolutions,inclusiveM-bus,Modbus andEthernet(Internet)communication
ECLComfort310foradvancedsolutions,inclusiveM-bus, ModbusandEthernet(Internet)communication.
TheextensionmoduleECA32canbeusedforextendingthe numbersofinputsformonitoringviatheECLPortal.Eachinputcan beconfiguredasPt1000,0-10Voltordigital. TheApplicationKeyA231complieswithECLComfort210/310 controllersasoffirmwareversion1.11. TheApplicationKeyA231alsocomplieswithECLComfort296 controllersasoffirmwareversion1.58. Thefirmware(controllersoftware)versionisvisibleatstart-upof thecontrollerandin‘Commoncontrollersettings’in‘System’ .Up totwoRemoteControlUnits,ECA30orECA31,canbeconnected forremotemonitoringandsetting.
ECLPortal,internet-basedconnection,allowsECL296,310and 310Btobemonitoredandcontrolledremotelyviastandard Internetbrowsers(forexampleInternetExplorer,GoogleChrome andSafari).
TogetherwiththeECLComfort310,theadditionalInternalI/O moduleECA32(ordercodeno.087H3202)canbeusedforextra datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool". Navigation:Danfoss.com>Serviceandsupport>Downloads> Tools>Heating>ECLTool. TheURLis:
https://www.danfoss.com/en/service-and-support/downloads/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volt(087H3240)
forECLComfort310,230voltand24volt(087H3230)
forECLComfort310,230voltand24volt(087H3230)
Extensionmodule(tobeinsertedintothebasepartofECL310):
ECA32(087H3202)
AdditionaldocumentationforECLComfort210,296and310, modulesandaccessoriesisavailableonhttp://heating.danfoss.com/ orhttp://store.danfoss.com. DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware): Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AQ000086469805en-010501
©Danfoss|2021.02|3
ECLComfort210/296/310,applicationA231/A331
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
4|©Danfoss|2021.02
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
2
Circuit2Parameterno.
174
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
AQ000086469805en-010501
©Danfoss|2021.02|5
ECLComfort210/296/310,applicationA231/A331

2.0Installation

2.1Beforeyoustart

TheapplicationA231.1isveryflexible.Thesearethebasic principles:
Heating:
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein ‘Comfort’or‘Saving’mode(twodifferenttemperaturevaluesfor desiredroomtemperature).
ThemotorizedcontrolvalvesM1isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingofthe motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent oftheoutdoortemperature.Typically,thelowertheoutdoor temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1) bemeasuredasa0-10Vsignal(fromapressuretransmitter)or
2)beaswitchsignalfromapressureswitch.Incaseofatoolow pressure,therefillwaterfunctionwillsupplementwithwaterfrom thesupplyside.
TypicalA231.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5Returntemperaturesensor
S7
Differentialpressureswitch
S8
Pressuretransmitterorpressureswitch
P1
Circulationpump
P2
Circulationpump
P3
Refillwaterpump
M1
Motorizedcontrolvalve
V1
ON/OFFvalve,refillwatervalve
A1
Relayoutput,alarm
WhentheECLComfortcontrolleroperatesasaslave,onlytherefill watervalveiscontrolled.Themastercontrolsacommonrefill waterpumpfortheentiresystem.
6|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ApplicationA231.1ingeneral:
ThecirculationpumpsP1andP2workinshiftaccordingtoa schedule.Onepumpisusedassparepumpandtheotherpump isworking.Incaseofmalfunction(missingdifferentialpressure) ofonepump,theotherpumpwilltakeover.Analarmwillbe generatedandthedefectivepumpcanbeinspected/repaired.
Alarm(relay4)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin apresettime.
TypicalA231.1application:
AQ000086469805en-010501
©Danfoss|2021.02|7
ECLComfort210/296/310,applicationA231/A331
TheapplicationA231.2isveryflexible.Thesearethebasic principles:
Heating:
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Thesupplytemperature(S2)isusedto1)controltheS3 temperatureinrelationtotheS2temperatureor2)maximizethe limitofthedesiredflowtemperature.
Thefactorysetting,wherethesupplytemperature(S2)determines thedesiredflowtemperature,doesnotchangethedesiredflow temperatureaccordingto‘Comfort’or‘Saving’mode.
However,ifthesupplytemperature(S2)determinesamax. limitationofthedesiredflowtemperature,the‘Comfort’and ‘Saving’modewillhavetwodifferenttemperaturevaluesfor desiredroomtemperature.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingofthe motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent oftheoutdoortemperature.Typically,thelowertheoutdoor temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost protection.
TypicalA231.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplyflowtemperaturesensor
S3
Flowtemperaturesensor
S5Returntemperaturesensor
S7
Differentialpressureswitch
S8
Pressuretransmitterorpressureswitch
P1
Circulationpump
P2
Circulationpump
P3
Refillwaterpump
M1
Motorizedcontrolvalve
V1
ON/OFFvalve,refillwatervalve
A1
Relayoutput,alarm
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1) bemeasuredasa0-10Vsignal(fromapressuretransmitter)or
2)beaswitchsignalfromapressureswitch.Incaseofatoolow pressure,therefillwaterfunctionwillsupplementwithwaterfrom thesupplyside.
WhentheECLComfortcontrolleroperatesasaslave,onlytherefill watervalveiscontrolled.Themastercontrolsacommonrefill waterpumpfortheentiresystem.
8|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ApplicationA231.2ingeneral:
ThecirculationpumpsP1andP2workinshiftaccordingtoa schedule.Onepumpisusedassparepumpandtheotherpump isworking.Incaseofmalfunction(missingdifferentialpressure) ofonepump,theotherpumpwilltakeover.Analarmwillbe generatedandthedefectivepumpcanbeinspected/repaired.
Alarm(relay4)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin apresettime.
TypicalA231.2application:
AQ000086469805en-010501
©Danfoss|2021.02|9
ECLComfort210/296/310,applicationA231/A331
TheapplicationA331.1isveryflexible.Thesearethebasic principles:
Heating:
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Bymeansofaweekschedule,theheatingcircuitcanbein ‘Comfort’or‘Saving’mode(twodifferenttemperaturevaluesfor desiredroomtemperature).
ThemotorizedcontrolvalvesM1isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingofthe motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent oftheoutdoortemperature.Typically,thelowertheoutdoor temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1)be measuredasa0-10Vsignal(fromapressuretransmitter)or2)bea switchsignalfromapressureswitch.Incaseofatoolowpressure, therefillwaterfunctionwillsupplementwithwaterfromthe supplyside.Thetworefillwaterpumpsareoperatedalternately.
WhentheECLComfortcontrolleroperatesasaslave,onlytherefill watervalveiscontrolled.Themastercontrolsacommonrefill waterpumpfortheentiresystem.
TypicalA331.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5Returntemperaturesensor
S7
Differentialpressureswitch
S8
Pressuretransmitterorpressureswitch
S9
Alarminput
S10
Pressuretransmitter(formonitoringonly)
P1
Circulationpump
P2
Circulationpump
P3
Refillwaterpump
P5
Refillwaterpump
M1
Motorizedcontrolvalve
V1
ON/OFFvalve,refillwatervalve
A1
Relayoutput,alarm
10|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ApplicationA331.1ingeneral:
ThecirculationpumpsP1andP2workinshiftaccordingtoa schedule.Onepumpisusedassparepumpandtheotherpump isworking.Incaseofmalfunction(missingdifferentialpressure) ofonepump,theotherpumpwilltakeover.Analarmwillbe generatedandthedefectivepumpcanbeinspected/repaired.
Alarm(relay4)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin apresettime.
TheuniversalalarminputsS9isactivated.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
M-buscommunicationenablesconnectiontofloworenergymeter. Thecontrollercanlimitthefloworenergytoasetmaximumbut alsoinrelationtotheoutdoortemperature.
Furthermore,theM-busdatacanbetransferredtotheModbus communication.
TypicalA331.1application:
AQ000086469805en-010501
©Danfoss|2021.02|11
ECLComfort210/296/310,applicationA231/A331
TheapplicationA331.2isveryflexible.Thesearethebasic principles:
Heating:
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature.Thelowertheoutdoortemperature, thehigherthedesiredflowtemperature.
Thesupplytemperature(S2)isusedto1)controltheS3 temperatureinrelationtotheS2temperatureor2)maximizethe limitofthedesiredflowtemperature.
Thefactorysetting,wherethesupplytemperature(S2)determines thedesiredflowtemperature,doesnotchangethedesiredflow temperatureaccordingto‘Comfort’or‘Saving’mode.
However,ifthesupplytemperature(S2)determinesamax. limitationofthedesiredflowtemperature,the‘Comfort’and ‘Saving’modewillhavetwodifferenttemperaturevaluesfor desiredroomtemperature.
ThemotorizedcontrolvalvesM1isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingofthe motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent oftheoutdoortemperature.Typically,thelowertheoutdoor temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1)be measuredasa0-10Vsignal(fromapressuretransmitter)or2)bea switchsignalfromapressureswitch.Incaseofatoolowpressure, therefillwaterfunctionwillsupplementwithwaterfromthe supplyside.Thetworefillwaterpumpsareoperatedalternately.
TypicalA331.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplyflowtemperaturesensor
S3
Flowtemperaturesensor
S5Returntemperaturesensor
S7
Differentialpressureswitch
S8
Pressuretransmitterorpressureswitch
S9
Alarminput
S10
Pressuretransmitter(formonitoringonly)
P1
Circulationpump
P2
Circulationpump
P3
Refillwaterpump
P5
Refillwaterpump
M1
Motorizedcontrolvalve
V1
ON/OFFvalve,refillwatervalve
A1
Relayoutput,alarm
WhentheECLComfortcontrolleroperatesasaslave,onlytherefill watervalveiscontrolled.Themastercontrolsacommonrefill waterpumpfortheentiresystem.
12|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ApplicationA331.2ingeneral:
ThecirculationpumpsP1andP2workinshiftaccordingtoa schedule.Onepumpisusedassparepumpandtheotherpump isworking.Incaseofmalfunction(missingdifferentialpressure) ofonepump,theotherpumpwilltakeover.Analarmwillbe generatedandthedefectivepumpcanbeinspected/repaired.
Alarm(relay4)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin apresettime.
TheuniversalalarminputsS9isactivated.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
M-buscommunicationenablesconnectiontofloworenergymeter. Thecontrollercanlimitthefloworenergytoasetmaximumbut alsoinrelationtotheoutdoortemperature.
Furthermore,theM-busdatacanbetransferredtotheModbus communication.
TypicalA331.2application:
AQ000086469805en-010501
©Danfoss|2021.02|13
ECLComfort210/296/310,applicationA231/A331
A231,ingeneral:
Offsetadjustment
Ameasuredtemperaturecanbeoffsetadjusted,ifneeded. (Navigation:MENU>Commoncontroller>System>Sensoroffset)
Applicationupload
Theapplicationuploadprocedureisthefollowingafterhaving powereduptheECLComfortcontroller:
1.Inserttheapplicationkey
2.Selectlanguage
3.Selectsubtype(theInstallationGuideshowssubtypes)
4.SetTimeandDate
TheECLComfortcontrollerinstallstheapplication,initializesand restarts.Outputrelaysareactivated/de-activated(click-sounds fromthiscanbeheard).Thisalsomeansthat,forexample, circulationpumpscanbeswitchedONandOFFshortly.
Commissioning
WhentheA231/A331applicationhasbeenuploadedtheECL ComfortcontrollerstartsinManualmode.Thiscanbeusedto verifycorrectconnectionsoftemperature,pressureandflow sensors.Alsoverifyingthecontrolledcomponents(valveactuators, pumpsetc.)forcorrectfunctionalitycanbedone.
Theapplicationkeyisdeliveredwithfactorysettings. Dependingonsystemtype,itmightbenecessarytochangesome factorysettingsindividuallyinordertooptimizethefunctionality.
Theapplicationkeymustbeinsertedinordertochangesettings.
Power-down/power-up
WhenthepowersupplytotheECLComfortcontrolleris disconnected(power-down),theoutputrelaysgotode-activated position. Thismeansthat,forexample,circulationpumpscanbeswitched ON. SeetheelectricalconnectiondiagramsintheInstallationGuide. Allrelaycontactsareshowninde-activatedsituation.Somerelay contactsareclosed,somerelaycontactsareopen. WhenthepowersupplytotheECLComfortcontrolleris re-established(power-up),theoutputrelaysareactivated/ de-activated(click-soundsfromthiscanbeheard).Thisalsomeans that,forexample,circulationpumpscanbeswitchedONandOFF shortly.
Important:
Setthecorrectrunningtime"Mrun"oftheMotorizedControl ValveM1.(Circuit1>MENU>Settings>Controlparameters >Mrun).
14|©Danfoss|2021.02
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
AQ000086469805en-010501
©Danfoss|2021.02|15
ECLComfort210/296/310,applicationA231/A331

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
16|©Danfoss|2021.02
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
AQ000086469805en-010501
©Danfoss|2021.02|17
ECLComfort210/296/310,applicationA231/A331
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
18|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
AQ000086469805en-010501
©Danfoss|2021.02|19
ECLComfort210/296/310,applicationA231/A331

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
20|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ000086469805en-010501
©Danfoss|2021.02|21
ECLComfort210/296/310,applicationA231/A331

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
22|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ000086469805en-010501
©Danfoss|2021.02|23
ECLComfort210/296/310,applicationA231/A331
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
24|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
2.5.3Electricalconnections,Pt1000temperaturesensorsandsignals
A231.1/A231.2:
Sensor
S1
S2
S3
S5Returntemperaturesensor
S7 S8Pressuretransmitter
*
** ***
Description
Outdoortemperature sensor*
Supplyflowtemperature sensor**
Flowtemperaturesensor***
Differentialpressureswitch
(0–10V) orpressureswitch
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
OnlyforapplicationA231.2. Theflowtemperaturesensormustalwaysbeconnected
inordertohavethedesiredfunctionality.Ifthesensoris notconnectedorthecableisshort-circuited,themotorized controlvalvecloses(safetyfunction).
Recommendedtype
ESMT
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
Connectionofdifferentialpressureswitch,S7
ThedrawingshowsconnectiontoECL210,butisalsovalidfor connectiontoECL296andECL310.
Connectionofapressuretransmitterwith0-10Voutput,S8
AQ000086469805en-010501
©Danfoss|2021.02|25
ECLComfort210/296/310,applicationA231/A331
Connectionofapressureswitch,S8
ThedrawingshowsconnectiontoECL210,butisalsovalidfor connectiontoECL296andECL310.
A331.1/A331.2:
Sensor
S1
S2
S3
S5Returntemperaturesensor
S7 S8Pressuretransmitter
S9 S10Pressuretransmitter
*
** ***
Description
Outdoortemperature sensor*
Supplyflowtemperature sensor**
Flowtemperaturesensor***
Differentialpressureswitch
(0–10V) orpressureswitch
Alarmswitch
(0–10V)
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
OnlyforapplicationA331.2. Theflowtemperaturesensormustalwaysbeconnected
inordertohavethedesiredfunctionality.Ifthesensoris notconnectedorthecableisshort-circuited,themotorized controlvalvecloses(safetyfunction).
Recommendedtype
ESMT
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
Connectionofdifferentialpressureswitch,S7
26|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Connectionofapressuretransmitterwith0-10Voutput,S8
Connectionofapressuretransmitterwith0-10Voutput,S10
Connectionofapressureswitch,S8
Connectionofalarmswitch,S9
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus) Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ000086469805en-010501
©Danfoss|2021.02|27
ECLComfort210/296/310,applicationA231/A331
2.5.4Electricalconnections,ECA30/31
Terminal ECL310
Terminal ECA30/
Description
Type (recomm.)
31
30 31 322 333
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
4
Twistedpair
1
Twistedpair
4
Ext.roomtemperature sensor*
5
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
28|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
2.5.5Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.6Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
AQ000086469805en-010501
©Danfoss|2021.02|29
ECLComfort210/296/310,applicationA231/A331
2.5.7Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
30|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
AQ000086469805en-010501
ECLComfort296
©Danfoss|2021.02|31
ECLComfort210/296/310,applicationA231/A331
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
32|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
AQ000086469805en-010501
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
©Danfoss|2021.02|33
ECLComfort210/296/310,applicationA231/A331
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
34|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
AQ000086469805en-010501
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
©Danfoss|2021.02|35
ECLComfort210/296/310,applicationA231/A331
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
36|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ000086469805en-010501
©Danfoss|2021.02|37
ECLComfort210/296/310,applicationA231/A331

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
38|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

2.8Navigation,ECLApplicationKeyA231/A331

Navigation,applicationA231.1/A331.1
Home
IDno.
MENU ScheduleSelectable
Settings
Flowtemperature
11178 11177
Returnlimit
Flow/powerlimitActual
Optimization
Controlpar.
11031 11032 11033 11034 11035 11036 11037 11085
11119 11117 11118 11116 11112 11113 11109 11115 11011 11012 11013 11014 11026 11021 11179 11174 11184 11185 11186 11187
Heating
Function
Heatcurve Temp.max. Temp.min. HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority
Limit HighToutX1 LowlimitY1 LowToutX2
HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Prestop Totalstop Cut-out Motorpr. Xp Tn Mrun Nz
AQ000086469805en-010501
©Danfoss|2021.02|39
ECLComfort210/296/310,applicationA231/A331
Navigation,applicationsA231.1/A331.1,continued
Home
MENU
Settings
HolidaySelectable
Alarm
InfluenceoverviewDes.flowT
Pumpcontrol
Refillwater
Application
Temp.monitor.
Clearalarm
AlarmoverviewSelectable
IDno.
11314 11310 11313 11311 11312 11022
11327 11323 11321 11322 11320 11325 11326 11017 11023 11052 11077 11078 11093 11141 11142 11189
11147 11148 11149 11150 11315 11324
Heating
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise Pressure Inputtype Time-out Pressure,des. Pressure,diff. Pexercise Valvedelay No.ofpumps Demandoffset Mexercise DHWpriority PfrostT PheatT Frostpr.T Ext.input Ext.mode Min.act.time
Upperdifference Lowerdifference Delay Lowesttemp. Circ.pumps Refillwater
Returnlim. Flow/powerlim.
Holiday Ext.override Boost Ramp Slave,demand Heatingcut-out DHWpriority
40|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Navigation,applicationA231.1/A331.1,Commoncontrollersettings(*applicationA331.1only)
Home MENU Time&Date Settings* Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
Supplypressure*
OutdoorTLogtoday Heatingflow&des. HeatreturnT&limitLog2days Staticpressure
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet M-busconfig EnergyMeters Display
Communication
Language
Function
Selectable Pressure* OutdoorT HeatflowT HeatreturnT Staticpressure S7status S9status*
Logyesterday
Log4days M1,P1,P2,P3,P5*,V1,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
Selectable Selectable
60058
Backlight
60059
Contrast
38
Modbusaddr.
2048
ECL485addr.
2150
Servicepin
2151
Ext.reset
2050
Language
AQ000086469805en-010501
©Danfoss|2021.02|41
ECLComfort210/296/310,applicationA231/A331
Navigation,applicationA231.2/A331.2
Home
IDno.
MENU ScheduleSelectable
Settings
Flowtemperature
11177 11300 11301 11302 11303
Returnlimit
Flow/powerlimitActual
Optimization
Controlpar.
11031 11032 11033 11034 11035 11036 11037 11085
11119 11117 11118 11116 11112 11113 11109 11115 11011 11012 11013 11014 11026 11021 11179 11174 11184 11185 11186 11187
Heating
Function
Heatcurve Temp.max. Temp.min. Highsupp.TX2 HighTmaxY2 LowsupplyTX1 LowTmaxY1 HighToutX1 LowlimitY1 LowToutX2 HighlimitY2 Infl.-max. Infl.-min. Adapt.time Priority
Limit HighToutX1 LowlimitY1 LowToutX2
HighlimitY2 Adapt.time Filterconstant Inputtype Units Autosaving Boost Ramp Optimizer Prestop Totalstop Cut-out Motorpr. Xp Tn Mrun Nz
42|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Navigation,applicationA231.2/A331.2,continued
Home
MENU
Settings
HolidaySelectable
Alarm
InfluenceoverviewDes.flowT
Pumpcontrol
Refillwater
Application
Temp.monitor.
Clearalarm
AlarmoverviewSelectable
IDno.
11314 11310 11313 11311 11312 11022
11327 11323 11321 11322 11320 11325 11326 11017 11023 11052 11077 11078 11093 11141 11142 11189
11147 11148 11149 11150 11315 11324
Heating
Function
Chan.-overtime Retrytime Stab.time Change,duration Changetime Pexercise Pressure Inputtype Time-out Pressure,des. Pressure,diff. Pexercise Valvedelay No.ofpumps Demandoffset Mexercise DHWpriority PfrostT PheatT Frostpr.T Ext.input Ext.mode Min.act.time
Upperdifference Lowerdifference Delay Lowesttemp. Circ.pumps Refillwater
Returnlim. Flow/powerlim.
Holiday Ext.override Boost Ramp Slave,demand Heatingcut-out DHWpriority
AQ000086469805en-010501
©Danfoss|2021.02|43
ECLComfort210/296/310,applicationA231/A331
Navigation,applicationA231.2/A331.2,Commoncontrollersettings(*applicationA331.2only)
Home MENU Time&Date Settings* Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
Supplypressure*
OutdoorTLogtoday SupplyTLogyesterday Heatingflow&des. HeatreturnT&limitLog4days Staticpressure Supplypressure*
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet M-busconfig EnergyMeters Display
Communication
Language
Function
Selectable Pressure* OutdoorT HeatflowT HeatreturnT Staticpressure S7status S9status*
Log2days
M1,P1,P2,P3,P5*,V1,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
Selectable Selectable
60058
Backlight
60059
Contrast
38
Modbusaddr.
2048
ECL485addr.
2150
Servicepin
2151
Ext.reset
2050
Language
44|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ000086469805en-010501
©Danfoss|2021.02|45
ECLComfort210/296/310,applicationA231/A331

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
46|©Danfoss|2021.02
)
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
thesensorinquestionisnotconnected.
"---"
thesensorconnectionisshort-circuited.
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Examples:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
20.5
21.0
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
AQ000086469805en-010501
©Danfoss|2021.02|47
ECLComfort210/296/310,applicationA231/A331
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
48|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
DamperOFF
AQ000086469805en-010501
©Danfoss|2021.02|49
ECLComfort210/296/310,applicationA231/A331

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
50|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
AQ000086469805en-010501
©Danfoss|2021.02|51
ECLComfort210/296/310,applicationA231/A331

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
52|©Danfoss|2021.02
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
AQ000086469805en-010501
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
©Danfoss|2021.02|53
ECLComfort210/296/310,applicationA231/A331

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Heatcurve
Temp.max.(flowtemp.limit,max.)—A231.2/A331.2
Actual(actualfloworpower)
Pressure
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Demandoffset
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Pre-stop(optimizedstoptime)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
DHWpriority(closedvalve/normaloperation)
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
1x01170
1x012
1x01372
1x01472
1x01787
1x02173
1x02279
1x02387
1x026
1x03163
1x03263
1x03363
1x03464
1x03564
1x03664
1x03764
1x05287
1x07788
1x07888
1x08565
1x09388
1x10967
1x111
1x11267
1x11368
1x115
1x11668
1x117
1x11869
1x11969
1x141
1x14289
1x147
Factorysettingsincircuit(s)
1
57
59
60
67
82
71
74
67
68
69
88
93
54|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
SettingIDPage
Lowerdifference
Delay,example
Lowesttemp.
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Highsupp.TX2(highvalueofsupplytemp.)
HighTmaxY2(highvalueofmaxlimitation)
LowsupplyTX1(lowvalueofsupplytemp.)
LowTmaxY1(lowvalueofmaxlimitation)
Retrytime
Change,duration
Changetime(changeovertime)
Stab.time(stabilizationtime)
Chan.-overtime(change-overtime)
Circ.pumps
Pexercise(pumpexercise)
Pressure,des.(desiredpressure)
Pressure,diff.(switchingdifference)
Time-out
Refillwater
Valvedelay
No.ofpumps
Inputtype
1x14893
1x14993
1x15094
1x174
1x177
1x17860
1x179
1x18476
1x18576
1x186
1x187
1x18991
1x30060
1x30160
1x30261
1x30361
1x31079
1x31179
1x31280
1x31380
1x31480
1x31594
1x32083
1x32183
1x32283
1x32383
1x32494
1x32584
1x32685
1x32785
Factorysettingsincircuit(s)
1
76
60
74
77
77
AQ000086469805en-010501
©Danfoss|2021.02|55
ECLComfort210/296/310,applicationA231/A331

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
56|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
AQ000086469805en-010501
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
©Danfoss|2021.02|57
ECLComfort210/296/310,applicationA231/A331
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
Max.limitationofthedesiredflowtemperature:
IntheapplicationsA231.1andA331.1themax.limitationvalueis selectablein‘Temp.max. ’.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
58|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
5.2.1A231.2/A331.2
TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtothesupplytemperature(S2).This relationshipissetinthecontroller.
Theheatcurveissetinallcoordinatepointstothemax.desired flowtemperature(150°C).Thedesiredflowtemperaturewill alwaysbeinrelationtothesupplytemperature(S2).
Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Outdoortemp.
FactorysettingY oursettings
-30°C150°C
-15°C150°C
-5°C150°C
0°C150°C
5°C150°C
15°C150°C
Adjustthedesiredflowtemperatureat-30,-15,-5,0,5,and15°C, ifrequired.
MENU>Settings>Flowtemperature
Desiredflowtemperature
Supplytemp.(S2)
Heatcurve
CircuitSettingrange
1
Read-outonly
Factorysetting
Thefactorysetting(ageneraldesiredflowtemperatureof150°C)is limitedtoamax.valuebasedonthesupplytemperature(S2)and thesettingsinparameters‘Highsupp.TX2’ ,‘HighTmaxY2’ ,‘Low supplyTX1’and‘LowTmaxY1’ .
Desiredflowtemperature
Supplytemp.(S2)
Theaboveheatcurveisanexampleofasupplytemperature(S2)of 85°C.Thedesiredflowtemperature(58°C)isbasedontheset-upof therelationshipbetweenthesupplytemperature(S2)andthedesired flowtemperature.
AQ000086469805en-010501
©Danfoss|2021.02|59
ECLComfort210/296/310,applicationA231/A331
Max.limitationofthedesiredflowtemperature:
IntheapplicationA231.2/A331.2thedesiredflowtemperatureor max.limitationvaluedependsonthesupplytemperature(S2).The relationshipissetinthefoursettings‘Highsupp.TX2’ ,‘HighTmax Y2’ ,‘LowsupplyTX1’and‘LowTmaxY1’ .
Whensettingtheheatcurvecoordinatesasdescribedinthe section'A231.1/A331.1’ ,thedesiredflowtemperaturecanbe limitedtoamaximumaccordingtothesupplytemperature(S2).
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
MENU>Settings>Flowtemperature
Temp.max.(flowtemp.limit,max.)—A231.2/A331.2
CircuitSettingrange
1
Read-outonly
Factorysetting
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesupplytemperature(S2)determinesthedesiredflow temperature.Thevalueiscalculatedonbasisofthesettingsin thefollowingparameters:'Highsupp.TX2' ,'HighTmaxY2' ,'Low supplyTX1'and'LowTmaxY1' .
MENU>Settings>Flowtemperature
Highsupp.TX2(highvalueofsupplytemp.)
1x300
SeeAppendix“ParameterIDoverview”
Setthehighvalueforthesupplytemperatureinrelationtothe desiredmax.flowtemperature.Whenthesupplytemperatureis abovethesetvalue,themax.limitationoftheflowtemperatureis theY2value.Whenthesupplytemperatureisbelowthesetvalue, themax.limitationoftheflowtemperaturewillbelower.
60|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Flowtemperature
HighTmaxY2(highvalueofmaxlimitation)
1x301
SeeAppendix“ParameterIDoverview”
Setthehighvalueforthemax.limitationofthedesiredflow temperature.
MENU>Settings>Flowtemperature
LowsupplyTX1(lowvalueofsupplytemp.)
1x302
SeeAppendix“ParameterIDoverview”
Setthelowvalueforthesupplytemperatureinrelationtothe desiredmax.flowtemperature.Whenthesupplytemperatureis belowthesetvalue,themax.limitationoftheflowtemperatureis theY1value.Whenthesupplytemperatureisabovethesetvalue, themax.limitationoftheflowtemperaturewillbehigher.
MENU>Settings>Flowtemperature
LowTmaxY1(lowvalueofmaxlimitation)
1x303
SeeAppendix“ParameterIDoverview”
Setthelowvalueforthemax.limitationofthedesiredflow temperature.
Set-upprocedurewhenthesupplytemperature(S2)hastolimit thedesiredflowtemperaturetoamaximum:
1.Choose‘Heatcurve’ .
2.Setthedesiredflowtemperatureinall6coordinates(-30°C,-15 °Cetc.)tothedesiredvalues.
Result: Thedesiredflowtemperaturewillbeinrelationtotheoutdoor temperaturebutwillbelimitedtoamaximumaccordingthe settingsin‘Highsupp.TX2’ ,‘HighTmaxY2’ ,‘LowsupplyTX1’and ‘LowTmaxY1’ .
Theexampleshowsthemax.limitationofthedesiredflow temperaturewhenthesupplytemperature(S2)is105°C.
AQ000086469805en-010501
©Danfoss|2021.02|61
ECLComfort210/296/310,applicationA231/A331

5.3Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
62|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
1x031
1x032
AQ000086469805en-010501
©Danfoss|2021.02|63
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
1x033
1x034
Example
1x035
Thereturnlimitisactiveabove50°C. Theinfluenceissetto0.5. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby0.5x2=1.0degree.
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthesetlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthesetlimit.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Example
1x036
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
64|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x037
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
AQ000086469805en-010501
©Danfoss|2021.02|65
ECLComfort210/296/310,applicationA231/A331

5.4Flow/powerlimit

Heatingcircuit
AfloworenergymetercanbeconnectedtotheECLcontrollerin ordertolimitthefloworconsumedpower.Thesignalfromthe floworenergymeterisapulsesignal.
WhentheapplicationrunsinanECLComfort296/310controller, theflow/powersignalcanbeobtainedfromaflow/energymeter viatheM-busconnection.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2'.
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2#
#Y1#
#Y2#
X
Y
#1#
#2#
#3#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
=
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
Theparameter'Units'(ID1x115)hasareducedsettingrangewhen theflow/energysignalcomesviaM-bus.
66|©Danfoss|2021.02
Ifthe‘Adapt.time’istoohigh,thereisariskofunstablecontrol.
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Pulsebasedsignalforflow/power ,appliedtoinputS7
Formonitoring: Frequencyrangeis0.01-200Hz
Forlimitation: Minimumfrequencyisrecommendedtobe1Hzinordertohavea
stablecontrol.Furthermore,thepulsesmustappearregularly.
Inputtype
Choiceofinputtypefromflow/energymeter
SeeAppendix“ParameterIDoverview”
OFF:
IM1-
Noinput
Flow/energymetersignalbasedonpulses.
IM5: EM1-
Flow/energymetersignalfromM-bus.
EM5:
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
1x109
ThesettingrangeforIMandEMdependsonchosensubtype.
1x111
SeeAppendix“ParameterIDoverview”
AQ000086469805en-010501
©Danfoss|2021.02|67
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
1x113
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Unitstotheleft:pulsevalue. Unitstotheright:actualandlimitationvalues.
Thevaluefromtheflowmeterisexpressedasmlorl. ThevaluefromtheenergymeterisexpressedasWh,kWh,MWh orGWh.
Thevaluesfortheactualflowandtheflowlimitationareexpressed asl/horm³/h.
Thevaluesfortheactualpowerandthepowerlimitationare expressedaskW,MWorGW.
1x115
Listforsettingrangeof'Units': ml,l/h l,l/h ml,m³/h l,m³/h Wh,kW kWh,kW kWh,MW MWh,MW MWh,GW GWh,GW
Example1:
'Units'(11115):
'Pulse'(11114):
l,m³/h 10
Eachpulserepresents10litresandtheflowisexpressedascubic meters(m³)perhour.
Example2:
'Units'(11115):
'Pulse'(11114):
kWh,kW(=kiloWatthour,kiloWatt) 1
Eachpulserepresents1kiloWatthourandthepoweris expressedinkiloWatt.
68|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Flow/powerlimit
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperaturesetin 'HighToutX1' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
MENU>Settings>Flow/powerlimit
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighflow/powerlimitation.
1x116
1x117
Thelimitationfunctioncanoverruletheset'Temp.min'ofthedesired flowtemperature.
1x118
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Flow/powerlimit
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowflow/powerlimitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
1x119
AQ000086469805en-010501
©Danfoss|2021.02|69
ECLComfort210/296/310,applicationA231/A331

5.5Optimization

Thesection"Optimization"describesspecificapplicationrelated issues. Theparameters'Autosaving' ,'Boost' ,'Optimizer' ,'T otalstop'areall relatedtoheatingmodeonly. 'Summer,cut-out'determine,atrisingoutdoortemperature,the stopofheating.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
70|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Optimization
Autosaving(savingtemp.dependentonoutdoortemp.)
Belowthesetvaluefortheoutdoortemperature,thesavingtemperature settinghasnoinfluence.Abovethesetvaluefortheoutdoortemperature, thesavingtemperaturerelatestotheactualoutdoortemperature.The functionisrelevantindistrictheatinginstallationsinordertoavoidabig changeinthedesiredflowtemperatureafterasavingperiod.
SeeAppendix“ParameterIDoverview”
OFF:
Thesavingtemperaturedoesnotdependonthe outdoortemperature;thereductionis100%.
Value:Thesavingtemperaturedependsontheoutdoor
temperature.Whentheoutdoortemperatureisabove 10°C,thereductionis100%.Thelowertheoutdoor temperature,thelessthetemperaturereduction. Belowthesetvalue,thesavingtemperaturesetting hasnoinfluence.
Comforttemperature:
Thedesiredroomtemperaturein Comfortmode
Savingtemperature:
ThedesiredroomtemperatureinSaving mode
ThedesiredroomtemperaturesforComfortandSavingmodes aresetinthedisplayoverviews.
1x011
=
X
Y
#1#
#2#
#3#
Example:
Actualoutdoortemperature(T.out):
DesiredroomtemperaturesettinginComfortmode:
DesiredroomtemperaturesettinginSavingmode:
Settingin‘Autosaving’:
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
=
Desiredroomtemperature(°C),Comfortmode
=
Desiredroomtemperature(°C),Savingmode
=
Autosavingtemperature(°C),ID11011
–5°C
22°C
16°C
–15°C
Theconditionfortheoutdoortemperatureinfluence:
T.out.influence=(10-T.out)/(10-setting)= (10-(-5))/(10-(-15))= 15/25=0,6
ThecorrecteddesiredroomtemperatureinSavingmode: T.room.ref.Saving+(T.out.influencex(T.room.ref.Comfort­T.room.ref.Saving)) 16+(0,6x(22-16))=19,6°C
=
X
Y
Outdoortemperature(°C)
=
Desiredroomtemperature(°C)
AQ000086469805en-010501
©Danfoss|2021.02|71
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Optimization
Boost
Shortenstheheating-upperiodbyincreasingthedesiredflowtemperature bythepercentageyouset.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theboostfunctionisnotactive. Thedesiredflowtemperatureisincreasedtemporarily
withthesetpercentage.
Inordertoshortentheheating-upperiodafterasaving temperatureperiod,thedesiredflowtemperaturecanbeincreased temporarily(max.1hour).Atoptimizingtheboostisactiveinthe optimizationperiod('Optimizer'). IfaroomtemperaturesensororanECA30/31isconnected,the booststopswhentheroomtemperatureisreached.
MENU>Settings>Optimization
Ramp(referenceramping)
Thetime(minutes)inwhichthedesiredflowtemperatureincreases graduallytoavoidloadpeaksintheheatsupply.
SeeAppendix“ParameterIDoverview”
1x012
1x013
OFF:
Value:
Therampingfunctionisnotactive. Thedesiredflowtemperatureisincreasedgraduallywith
thesetminutes.
Inordertoavoidloadpeaksinthesupplynetwork,theflow temperaturecanbesettoincreasegraduallyafteraperiodwith savingtemperature.Thiscausesthevalvetoopengradually.
=
X Y #1#
Time
=
Desiredflowtemperature
=
Rampingtime
=
Comforttemperature
=
Savingtemperature
72|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Optimization
Optimizer(optimizingtimeconstant)
Optimizesthestartandstoptimesforthecomforttemperatureperiodto obtainthebestcomfortatthelowestenergyconsumption. Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower theoutdoortemperature,thelatertheheatingcut-out. Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The calculatedstartandstoptimesarebasedonthesettingoftheoptimizing timeconstant.
SeeAppendix“ParameterIDoverview”
Adjusttheoptimizingtimeconstant.
Thevalueconsistsofatwodigitnumber.Thetwodigitshavethe followingmeaning(digit1=TableI,digit2=TableII).
OFF:
Nooptimization.Theheatingstartsandstopsatthe timessetintheschedule.
10...59:
SeetablesIandII.
TableI:
1x014
Systemtype
LeftdigitHeataccumulationofthe
building
Radiator
1-light
systems
2-medium
3-heavy
Floorheating
4-medium
systems
5-heavy
TableII:
RightdigitDimensioningtemperatureCapacity
-0-50°Clarge 
-1
-45°C
-5
-25°C
normal
-9
Dimensioningtemperature:
Thelowestoutdoortemperature(usuallydeterminedbyyoursystem designerinconnectionwiththedesignoftheheatingsystem)atwhich theheatingsystemcanmaintainthedesignedroomtemperature.
Example
Thesystemtypeisradiator,andtheheataccumulationofthebuilding ismedium.
Theleftdigitis2. Thedimensioningtemperatureis-25°C,andthecapacityisnormal. Therightdigitis5. Result: Thesettingistobechangedto25.
-5°C
small
AQ000086469805en-010501
©Danfoss|2021.02|73
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Optimization
Totalstop
Decidewhetheryouwantatotalstopduringthesavingtemperatureperiod.
1x021
SeeAppendix“ParameterIDoverview”
OFF:
Nototalstop.Thedesiredflowtemperatureisreduced accordingto:
•desiredroomtemperatureinsavingmode
•autosaving
ON:
Thedesiredflowtemperatureisloweredtothesetvalue in‘Frostpr. ’Thecirculationpumpisstoppedbutfrost protectionisstillactive,see'PfrostT' .
Totalstop=OFF
Totalstop=ON
X Y
=
Time
=
Desiredflowtemperature
=
Comforttemperature
=
Savingtemperature
=
Frostprotection
MENU>Settings>Optimization
Pre-stop(optimizedstoptime)
Disabletheoptimizedstoptime.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Theoptimizedstoptimeisdisabled. Theoptimizedstoptimeisenabled.
Themin.flowtemperaturelimitation('Temp.min.')isoverruledwhen 'Totalstop'isON.
1x026
Example:OptimizationofComfortfrom07:00-22:00
=
X #1# #2# #3# #4# #5#
Time
=
Schedule
=
Prestop=OFF
=
Prestop=ON
=
Optimizedstart
=
Optimizedstop
74|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Optimization
Summer,cut-out(limitforheatingcut-out)
1x179
SeeAppendix“ParameterIDoverview”
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanthesetvalue.Thevalveclosesandafterthepost-run time,theheatingcirculationpumpstops.‘Temp.min.’willbe overruled.
TheheatingsystemswitchesONagainwhentheoutdoor temperatureandtheaccumulated(filtered)outdoortemperature becomelowerthanthesetlimit.
Thisfunctioncansaveenergy.
Setthevalueforoutdoortemperatureatwhichyouwantthe heatingsystemtoswitchOFF .
Summer,cut-out
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
Temperature
=
Actualoutdoortemperature
=
Cut-outtemperature(1x179)
=
Accummulated(filtered)outdoortemperature
=
Heatingenabled
=
Heatingdisabled
Theheatingcut-outisonlyactivewhenthecontrollermodeisin scheduledoperation.Whenthecut-outvalueissettoOFF,thereis noheatingcut-out.
AQ000086469805en-010501
©Danfoss|2021.02|75
ECLComfort210/296/310,applicationA231/A331

5.6Controlparameters

Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point controlsignal.
Valvecontrol: Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
MENU>Settings>Controlparameters
Xp(proportionalband)
SeeAppendix“ParameterIDoverview”
Settheproportionalband.Ahighervaluewillresultinastablebut slowcontroloftheflowtemperature.
1x174
1x184
76|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
MENU>Settings>Controlparameters
1x185
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
AQ000086469805en-010501
©Danfoss|2021.02|77
ECLComfort210/296/310,applicationA231/A331
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
Criticaltimeperiod
Time
78|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

5.7Pumpcontrol

Thisapplicationcanoperatewithoneortwocirculationpumps. Whenoperatingwithtwocirculationpumps,thepumpsare controlledalternately,accordingtoatimeset-up.Whenapump isswitchedONthecontrolleriswaitingfordifferentialpressure (S7)tobuildup.Ifdifferentialpressureisnotachieved,analarmis generatedandtheECLComfortcontrollerswitchesONtheother pump.
Ifnoneofthepumpscancomeintooperation(detectedbymeans ofthedifferentialpressureswitch),thealarmisactivatedandthe motorizedcontrolvalvecloses(asafetyfunction).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Pumpcontrol
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat noon(12:14hours).
MENU>Settings>Pumpcontrol
Retrytime
Ifanalarmhasbeengeneratedforthepumporalarmshavebeengenerated forbothpumps,thissettingwilldeterminethetimebetweenthetimeofthe alarmandtheretrytimeforrepeatedpumpstart.
SeeAppendix“ParameterIDoverview”
OFF:
Noretrytimerequiredafteranalarm.Thepumpor pumpsinquestionwillnotberestarted.
1...99:
Afteranalarm,thepumporpumpswillberestarted afterthesettime.
1x022
1x310
AQ000086469805en-010501
©Danfoss|2021.02|79
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Pumpcontrol
Change,duration
Thenumberofdaysbetweenshiftofcirculationpumps.Theshifttakesplace atthetimesetin'Changetime' .
SeeAppendix“ParameterIDoverview”
MENU>Settings>Pumpcontrol
Changetime(changeovertime)
Theexacttimeoftheday,wheretheshiftmusttakeplace.Thedayisdivided into24hours.Thefactorysettinghereis12whichmeans12:00(noon).
1x311
=
X #1# #2# #3#
1x312
Time
=
PumpP1
=
PumpP2
=
Change,duration(days)
SeeAppendix“ParameterIDoverview”
MENU>Settings>Pumpcontrol
Stab.time(stabilizationtime)
Settingofmax.timetoelapsebetweenpumpstartcommandandfeedback fromdifferentialpressureswitch. Ifthedifferentialpressureswitchdoesnotgivefeedbackwithinthesettime, thealarmwillbeactivatedandtheotherpumpwillgetastartcommand.
SeeAppendix“ParameterIDoverview”
=
X #1# #2# #3#
1x313
Time
=
PumpP1
=
PumpP2
=
Changetime(clocktime)
Ifthechosenstabilizationtime(‘Stab.time’)istooshort,theactive pumpwillstopimmediatelyafterthestabilizationtimehaselapsed.
80|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Pumpcontrol
Chan.-overtime(change-overtime)
Settingoftimetoelapsebetweenthepumpstopcommandforonepump andthestartcommandfortheotherpump. Thechange-overtimecanensurethatapumpisstoppedefficientlybefore theotherpumpstarts.
SeeAppendix“ParameterIDoverview”
OFF:
1...99:
Onecirculationpumpintheapplication.
Timeforchange-over.
1x314
=
X #1# #2# #3#
Time
=
PumpP1
=
PumpP2
=
Change-overtime(sec.)
‘Chan.-overtime’hastobechoseninsystemswithtwopumps.
Thestatusofthedifferentialpressureswitchisshownin'Input overview'.
(Navigation:MENU>Commoncontroller>Inputoverview).
Example:
S7status...OFF/ON
OFF:
Thedifferentialpressureswitchisclosed(differential pressureisOK)
ON:
Thedifferentialpressureswitchisopen(differential pressureisnotOK)
AQ000086469805en-010501
©Danfoss|2021.02|81
ECLComfort210/296/310,applicationA231/A331
5.8Refillwater
Leaksontheconsumerssidewillresultinfallingstaticpressureand therebyapoorsupplyofheating.Arefillwaterfunctioncaninject watertoincreasethestaticpressure.
Thisapplicationcanmonitorthestaticpressureandenablethe refillwaterfunctionwhenthepressureistoolow.
Thepressureismeasuredbymeansofapressuretransmitter (givinga0-10voltsignalinrelationtothemeasuredpressure)or apressureswitch.
Whenapressuretransmittersignalisused,twosettingsinthe controllerrepresentpressuresetpointanddifference.
Whenapressureswitchsignalisused,thesetpointand(maybe) theswitchingdifferenceissetonthepressureswitch.
Whenatoolowpressureisdetectedtherefillwaterpumpis switchedONand,afterasettime,theON-OFFvalveisactivated.
Ifthepressureisnotachievedwithinasettime,analarmis generated.TheECLComfortcontrollerswitchesOFFthecirculation pumpsafter60secondsandthecontrolvalvecloses(asafety function).
MENU>Settings>Refillwater
Pressure
CircuitSettingrange
1
Read-outonly
Factorysetting
Theread-outcanbeavalue(inbar):
Thepressureismeasuredbymeansofapressuretransmitter. Thetransmittersendsthemeasuredpressureasa0-10V. ThevoltagesignalcanbeapplieddirectlytoinputS8.The measuredvoltageoninputS8mustbeconvertedtoapressure valuebythecontroller.Thisproceduresetsupthescaling:
Pushthedialtoseethegraphandenterthevaluesetsforthe inputvoltage(2and10volt)anddisplayedpressure(inbar).
Pressurevaluerange:0.0...30.0bar
Fixedvoltagesettings:2Vand10V
Factorysettings:(2.0,0)and(10,20.0)
Thismeansthatthe‘Pressure'is0.0barat2Vand20.0barat 10V.
Typically,thehigherthevoltage,thehigherthedisplayed pressure.
Ortheread-outcanbeOFForON:
Thepressureismeasuredbymeansofapressureswitch.The pressureswitchhasanopencontactwhenmeasuringatoolow pressure(shownasOFF).WhenmeasuredpressureisOK,the contactisclosed(shownasON).
Thepressureswitchcontact(potentialfree)isconnected directlytoinputS8.
=
X Y #1# #2#
Volt
=
Bar
=
0bar
=
30,0bar
Thisscalingmenuisalwaysshown,regardlesswhetherapressure transmitterorapressureswitchisused.
Examplesforsettingtherelationshipbetweenpressuretransmitter voltage(0-10Volt)andpressurevalue(bar)canbeseeninthesection "Frequentlyaskedquestions" .
82|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Refillwater
Pexercise(pumpexercise)
Thetimethepumpisactivatedduringexercise.Exercisetakesplaceevery day(at12:00).
SeeAppendix“ParameterIDoverview”
OFF:
1...200:
Nopumpexercise.
Activationtimeduringexercise.
MENU>Settings>Refillwater
Pressure,des.(desiredpressure)
SettingofdesiredpressureatS8inordertoON/OFFcontroltherefill pump(s)P3/P5. Seealso'Pressurediff. '
SeeAppendix“ParameterIDoverview”
MENU>Settings>Refillwater
Pressure,diff.(switchingdifference)
Settingoftheswitchingdifferenceformeasuredstaticpressure(pressure transmitter).Thedifferenceissymmetricalaroundthe'Pressuredes. 'See also'Pressuredes. '
1x320
1x321
1x322
SeeAppendix“ParameterIDoverview”
AQ000086469805en-010501
=
X Y #1#
#2# #3#
Time
=
Pressure
=
Pressuredesired
=
Actualpressure
=
Pressuredifference
Thesettingsin'Pressure,des. 'and'Pressure,diff.'havenoinfluence whenapressureswitchisused.
©Danfoss|2021.02|83
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Refillwater
Time-out
Settingofthemax.timeforrefill.Thepressure,measuredbyS8,mustbe OKwithinthesettime.Ifnot,therefillwaterfunctionstopsandanalarm isactivated.
SeeAppendix“ParameterIDoverview”
1x323
=
X #1# #2# #3#
Time
=
PressureOK/notOK
=
Refillpump
=
Time-out
84|©Danfoss|2021.02
=
X #1# #2# #3# #4#
Time
=
PressureOK/notOK
=
Refillpump
=
Time-out
=
Alarm
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Refillwater
Valvedelay
SettingofthetimeforactivationoftheON/OFFvalveafterstartoftherefill waterpump.
SeeAppendix“ParameterIDoverview”
1x325
=
X Y #1# #2# #3# #4#
Time
=
Pressure
=
Pressuredesired
=
Actualpressure
=
Pressuredifference
=
Valvedelay
MENU>Settings>Refillwater
No.ofpumps
Settingofthenumberofpumpsintherefillwatercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Therefillwaterpumpfunctioniscontrolledbythe mastercontroller.
1...2:
Therefillwaterfunctionhasoneortwopumps.
1x326
Refillwater pump
WhenselectingOFFandademandforrefilloccurs,thecontroller fortheactualcircuitsendstherequirementviatheECL485 communicationbustothemastercontroller.
Themastermustberunninganapplicationwithrefillwaterfunction. Themasterstartstherefillwaterpumpandsends,viatheECL485 communicationbus,amessagethattherefillwaterpumpisstarted. Therefillwatervalvethenopens.
Theslavemusthaveanaddress1...9.
Refillwater valve
ECL485 communication bus
AQ000086469805en-010501
©Danfoss|2021.02|85
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Refillwater
Inputtype
Choiceofpressureinputsignal.
SeeAppendix“ParameterIDoverview”
OFF:
Pressuresignalisnotrequired.Therefillwaterfunction isdisabled.
AI:
DI:
Theinputsignalisananalogsignal(0-10V). Theinputsignalisadigitalsignal(switchOFForON).
1x327
Whenselecting‘OFF’ ,therefillwatersystemcouldbeself-acting.
Thestaticpressureisshownin'Inputoverview'asavalueinbaror OFF/ON.
Example:
OFF:
Thepressureswitchisopen(pressureisnotOK)
ON:
Thepressureswitchisclosed(pressureisOK)
86|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

5.9Application

Thesection"Application"describesspecificapplicationrelated issues. Someoftheparameterdescriptionsareuniversalfordifferent applicationkeys.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Application
Demandoffset
Thedesiredflowtemperatureinheatingcircuit1canbeinfluencedbythe demandforadesiredflowtemperaturefromanothercontroller(slave)or anothercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredflowtemperatureincircuit1isnot influencedbythedemandofanyothercontroller(slave orcircuit2).
Value:
Thedesiredflowtemperatureisincreasedbytheset valuein‘Demandoffset’ ,ifthedemandoftheslave/ circuit2ishigher.
MENU>Settings>Application
Mexercise(valveexercise)
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
Temp.
1x017
Thefunctionof‘Demandoffset’cancompensateforheatlosses betweenmasterandslavecontrolledsystems.
1x023
Settingin ‘Demandoffset’
Des.flowtemp., circuit1
Des.flowtemp., circuit2
Time
OFF:
ON:
AQ000086469805en-010501
Thevalveexerciseisnotactive.
Thevalveopensfor7minutesandclosesfor7minutes everythirddayatnoon(12:00hours).
©Danfoss|2021.02|87
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Application
DHWpriority(closedvalve/normaloperation)
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen DHWheating/chargingisactiveinthemaster.
SeeAppendix“ParameterIDoverview”
OFF:
Theflowtemperaturecontrolremainsunchanged duringactiveDHWheating/charginginthemaster controller.
ON:
Thevalveintheheatingcircuitisclosed*duringactive DHWheating/charginginthemastercontroller.
*Thedesiredflowtemperatureissettothevaluesetin ‘Frostpr.T’
MENU>Settings>Application
PfrostT(circulationpump,frostprotectiontemp.)
Frostprotection,basedontheoutdoortemperature. Whentheoutdoortemperaturegetsbelowthesettemperaturevaluein‘P frostT’ ,thecontrollerautomaticallyswitchesONthecirculationpump(for exampleP1orX3)toprotectthesystem.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Nofrostprotection. CirculationpumpisONwhentheoutdoortemperature
isbelowthesetvalue.
1x052
Thissettingmustbeconsideredifthiscontrollerisaslave.
1x077
Undernormalconditions,yoursystemisnotfrostprotectedifyour settingisbelow0°CorOFF.
Forwater-basedsystems,asettingof2°Cisrecommended.
Iftheoutdoortemperaturesensorisnotconnectedandthefactory settinghasnotbeenchangedto'OFF' ,thecirculationpumpisalways ON.
MENU>Settings>Application
PheatT(heatdemand)
Whenthedesiredflowtemperatureisabovethesettemperaturein‘PheatT’ , thecontrollerautomaticallyswitchesONthecirculationpump.
1x078
SeeAppendix“ParameterIDoverview”
Value:
ThecirculationpumpisswitchedONwhenthedesired flowtemperatureisabovethesetvalue.
MENU>Settings>Application
Frostpr .T(frostprotectiontemp.)
SetthedesiredflowtemperatureattemperaturesensorS3toprotectthe systemagainstfrost(atheatingcut-out,totalstopetc.). WhenthetemperatureatS3getslowerthanthesetting,themotorized controlvalveopensgradually.
1x093
SeeAppendix“ParameterIDoverview”
Thevalveisfullyclosedaslongasthepumpisnotswitchedon.
Thefrostprotectiontemperaturecanalsobesetinyourfavorite displaywhenthemodeselectorisinfrostprotectionmode.
88|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Overridemodefunctions:
ThefollowingsettingsdescribethefunctioningeneralfortheECL Comfort210/296/310series.Theexplainedmodesaretypical andnotapplicationrelated.Theymightdifferfromtheoverride modesinyourapplication.
MENU>Settings>Application
Ext.input(externaloverride)
Choosetheinputfor'Ext.input'(externaloverride).Bymeansofaswitch thecontrollercanbeoverriddento‘Comfort’,'Saving' ,'Frostprotection'or 'Constanttemperature'mode.
1x141
SeeAppendix“ParameterIDoverview”
OFF:
S1...S16:
Noinputshavebeenselectedforexternaloverride. Inputselectedforexternaloverride.
IfS1...S6ischosenasoverrideinput,theoverrideswitchmusthave gold-platedcontacts. IfS7...S16ischosenasoverrideinput,theoverrideswitchcanbea standardcontact.
Seethedrawingsforconnectionexamplesofoverrideswitchand overriderelaytoinputS8.
S7...S16arerecommendedforoverrideswitch.
Example:Connectionofanoverrideswitch
Example:Connectionofanoverriderelay
IfECA32ismounted,alsoS11...S16canbeused.
IfECA35ismounted,alsoS11orS12canbeused.
Chooseonlyanunusedinputforoverride.Ifanalreadyusedinputis appliedforoverride,thefunctionalityofthisinputisalsoneglected.
Seealso‘Ext.mode’.
AQ000086469805en-010501
©Danfoss|2021.02|89
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Application
Ext.mode(externaloverridemode)
ThemodeoverridecanbeactivatedforSaving,Comfort,Frostpr.or ConstantTmode. Foroverride,thecontrollermodemustbeinscheduledmode.
SeeAppendix“ParameterIDoverview”
Chooseanoverridemode:
SAVING:
Thecircuitinquestionisinsavingmodewhenthe overrideswitchisclosed.
COMFORT:
Thecircuitinquestionisincomfortmodewhenthe overrideswitchisclosed.
FROSTPR.:
TheheatingorDHWcircuitcloses,butisstillfrost protected.
CONSTANTT:
Thecircuitinquestioncontrolsaconstant temperature*)
*)
Seealso'DesiredT'(1x004),settingofdesiredflow temperature(MENU>Settings>Flowtemperature) Seealso'Con.T,ret.Tlim. '(1x028),settingofreturn temperaturelimitation(MENU>Settings>Return limit)
Theprocessdiagramsshowthefunctionality.
1x142
Seealso‘Ext.input’.
Example:OverridetoComfortmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Comfort) #3#=Time
Example:OverridetoSavingmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Saving) #3#=Time
Theresultofoverrideto'Saving'modedependsonthesettingin 'Totalstop'.
Totalstop=OFF:Heatingreduced Totalstop=ON:Heatingstopped
90|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
Example:OverridetoFrostprotectionmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Frostpr.) #3#=Time
Example:OverridetoConstanttemperaturemode
MENU>Settings>Application
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Const.T) #3#=Time
The"Const.T"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
AQ000086469805en-010501
©Danfoss|2021.02|91
ECLComfort210/296/310,applicationA231/A331

5.10Alarm

Thesection"Alarm"describesspecificapplicationrelatedissues. ApplicationA231offerstwotypesofalarms:
Type:
1
1
2
2
Thealarmfunctionsactivatethealarmbellsymbol. ThealarmfunctionsactivateA1(Relay4).
Thealarmrelaycanactivatealamp,ahorn,aninputtoanalarm transmittingdeviceetc.
Thealarmsymbol/relayisactivated:
(type1)aslongasthealarmreasonispresent(automaticreset).
(type2)evenifthealarmreasondisappearsagain(manual reset).
Alarmtype1:
Iftheflowtemperaturedeviatesmorethanthesetdifferences fromthedesiredflowtemperature,thealarmsymbol/relay willbeactivated.
Iftheflowtemperaturebecomesacceptable,thealarmsymbol/ relaywillbede-activated.
Description:
Actualflowtemperaturediffersfromthedesired flowtemperature
A331.1,A331.2: TheuniversalalarminputS9isactivated
Anactivatedcirculationpumpdoesnotgenerate apressuredifference
Therefillwaterfunctiondoesnotgeneratea pressurewithinsettime
IftheuniversalalarminputS9isactivated.
IftheuniversalalarminputS9isde-activated,thealarmsymbol/ relaywillbede-activated.
Alarmtype2:
IfpumpdifferentialpressureS7isnotregistered,thealarm symbol/relaywillbeactivated.Furthermore,thecontrolvalve willclose.
Thisalarmmustbemanuallyreset.
IfRefillwaterfunctionhasnotgeneratedacceptablepressure, thealarmsymbol/relaywillbeactivated.
Thisalarmmustbemanuallyreset.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
92|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
5.10.1Temp.monitor.
MENU>Settings>Alarm
Upperdifference
Thealarmisactivatediftheactualflowtemperatureincreasesmorethan thesetdifference(acceptabletemperaturedifferenceabovethedesired flowtemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
1x147
Upperdifference
OFF:
Value:
Therelatedalarmfunctionisnotactive. Thealarmfunctionisactiveiftheactualtemperature
getsabovetheacceptabledifference.
MENU>Settings>Alarm
Lowerdifference
Thealarmisactivatediftheactualflowtemperaturedecreasesmorethan thesetdifference(acceptabletemperaturedifferencebelowthedesired flowtemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Therelatedalarmfunctionisnotactive. Thealarmfunctionisactiveiftheactualtemperature
getsbelowtheacceptabledifference.
=
X Y #1# #2#
1x148
Lowerdifference
Time
=
Temperature
=
Upperdifference
=
Desiredflowtemperature
=
X Y #1# #2#
AQ000086469805en-010501
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
©Danfoss|2021.02|93
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Alarm
Delay,example
Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'is presentforalongertimethanthesetdelay(inminutes),thealarmfunction isactivated.
SeeAppendix“ParameterIDoverview”
1x149
Delay,example
Value:
Thealarmfunctionwillbeactivatedifthealarm conditionremainsafterthesetdelay.
MENU>Settings>Alarm
Lowesttemp.
Thealarmfunctionwillnotbeactivatedifthedesiredflowtemperature islowerthanthesetvalue.
SeeAppendix“ParameterIDoverview”
5.10.2Clearalarm
=
X Y #1# #2# #3# #4#
1x150
Ifthecauseofthealarmdisappears,thealarmindicationandoutput alsodisappear.
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
=
Actualflowtemperature
=
Delay(ID1x149)
Clearalarm
Ifanalarmhasbeengenerated,abellisshowninoneof thefavoritedisplay(see‘Monitoringtemperaturesandsystem components’)orinanoverviewdisplay(see‘Understandingthe controllerdisplay’).Thefollowingmenusareusedtolocatethe alarmcauseandreset(clear)thealarmsignal.Evenwhenthecause ofthealarmhasdisappeared,theindicationwillstillbeactiveuntil theclearalarmprocedurehasbeencarriedout.
MENU>Settings>Alarm
Circ.pumps
Choosewhetherthealarmshouldbeclearedornot.
1x315
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thealarmhasnotbeenactivated. Thealarmhasbeenactivated.
Clearalarmprocedure:
Ifthestatusis‘ON’:Change‘ON’to‘OFF’ .
Ifthestatusis‘OFF’:Itisnotpossibletochangeitto‘ON’ .
94|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331
MENU>Settings>Alarm
Refillwater
Choosewhetherthealarmshouldbeclearedornot.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thealarmhasnotbeenactivated. Thealarmhasbeenactivated.
Clearalarmprocedure:
Ifthestatusis‘ON’:Change‘ON’to‘OFF’ .
Ifthestatusis‘OFF’:Itisnotpossibletochangeitto‘ON’ .
1x324
AQ000086469805en-010501
©Danfoss|2021.02|95
ECLComfort210/296/310,applicationA231/A331

5.11Alarmoverview

Alarmoverview,list:
Alarmno.:
1
8
9
10
Tofindthereasonforanalarm:
selectMENU
select‘Alarm’
select‘Alarmoverview’ .A"bell"( inquestion.
Alarmoverview(example): 8:Temp.monitor 9:Pump1
Thenumbersinthe'Alarmoverview'refertothealarmnumber intheModbuscommunication.
Thealarmhasbeenactivatedifthealarmsymbol(abell)( presenttotherightofthealarmtype.
Toresetanalarm: Whenthebellsymbolispresenttotherightinthealarmline,place thecursoratthealarmlineinquestionandpressthedial.
Description:
Refillwater
Temp.monitor
Pump1
Pump2
Alarmtype:
2
1
2
2
)willbeshownatthealarm
Sensorref.:
S8
S3
S7
S7
)is
AlarminputS9(subtypesA331.1,A331.2):
Statusonactivated/de-activatedalarminputcanbeseenhere: MENU>Commoncontroller>Inputoverview>S9status:
ON:
OFF:
Alarminputisnotactivated
Alarminputisactivated
96|©Danfoss|2021.02
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

6.0Commoncontrollersettings

6.1Introductionto‘Commoncontrollersettings’

Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ000086469805en-010501
©Danfoss|2021.02|97
ECLComfort210/296/310,applicationA231/A331

6.2Time&Date

Itisonlynecessarytosetthecorrectdateandtimeinconnection withthefirstuseoftheECLComfortcontrollerorafterapower breakofmorethan72hours.
Thecontrollerhasa24hourclock.
Aut.daylight(Daylightsavingtimechangeover)
YES:
NO:
Thecontroller’sbuilt-inclockautomaticallychanges+/
-onehouronthestandardizeddaysfordaylightsaving timechangeoverforCentralEurope.
Youchangemanuallybetweensummerandwintertime bysettingtheclockbackwardorforward.
Howtosettimeanddate:
Action:
Purpose:
Choose‘MENU’
Confirm Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Time&Date’
Confirm Placethecursoratthepositiontobe
changed
Confirm
Enterthedesiredvalue
Confirm
Movethecursortothenextposition tobechanged.Continueuntil‘Time& Date’hasbeenset.
Finallymovethecursorto‘MENU’
Whencontrollersareconnectedasslavesinamaster/slavesystem
Examples:
(viaECL485communicationbus),theywillreceive‘Time&Date’from themaster.
98|©Danfoss|2021.02
Confirm
Movethecursorto‘HOME’
Confirm
AQ000086469805en-010501
ECLComfort210/296/310,applicationA231/A331

6.3Holiday

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Thereisaholidayprogramforeachcircuitandaholidayprogram forthecommoncontroller.
Eachholidayprogramcontainsoneormoreschedules.Each schedulecanbesettoastartdateandanenddate.Thesetperiod startsonthestartdateat00.00andstopsontheenddateat00.00.
SelectablemodesareComfort,Saving,FrostprotectionorComfort 7-23(before7andafter23,themodeisscheduled).
Howtosetyourholidayschedule:
Action:
Purpose:
Examples:
Choose‘MENU’
Confirm Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm Chooseacircuitor'Commoncontroller
settings' Heating
DHW Commoncontrollersettings
Confirm
Goto‘Holiday’
Confirm
Theholidayprograminthe‘Commoncontrollersettings’isvalidfor allcircuits.Theholidayprogramcanalsobesetindividuallyinthe heatingorDHWcircuits.
Theenddatemustbeatleastbeonedaylaterthanthestartdate.
Chooseaschedule
Confirm
Confirmchoiceofmodeselector
Choosemode
Comfort
·Comfort7–23
Saving
·Frostprotection
Confirm Enterthestarttimefirstandthenthe
endtime Confirm
Goto‘Menu’
Confirm Choose‘Yes’or‘No’in‘Save’ .Choose
thenextschedule,ifrequired
AQ000086469805en-010501
©Danfoss|2021.02|99
ECLComfort210/296/310,applicationA231/A331
Holiday,specificcircuit/CommonController
Whensettingoneholidayprograminspecificcircuitandanother holidayprograminCommonController,aprioritywillbetaken intoaccount:
1.Comfort
2.Comfort7-23
3.Saving
4.Frostprotection
Holiday,deletingasetperiod:
ChoosetheScheduleinquestion
Changethemodeto"Clock"
Confirm
Example1:
Circuit1: Holidaysetto"Saving"
CommonController: Holidaysetto"Comfort"
Result: Aslongas"Comfort"isactiveinCommonController,circuit1willbein
"Comfort".
Example2:
Circuit1: Holidaysetto"Comfort"
CommonController: Holidaysetto"Saving"
Result: Aslongas"Comfort"isactiveincircuit1,itwillbein"Comfort".
Example3:
Circuit1: Holidaysetto"Frostprotection"
TheECA30/31cannotoverridetheholidayscheduleofthe controllertemporarily.
However,itispossibletomakeuseofthefollowingoptionsfrom theECA30/31whenthecontrollerisinscheduledmode:
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
CommonController: Holidaysetto"Saving"
Result: Aslongas"Saving"isactiveinCommonController,circuit1willbe
in"Saving".
Energy-savingtrick: Use'Goingout'(theextendedsavingperiod)forairingpurposes(e.g. forventilatingtheroomsbymeansoffreshairfromopenwindows).
ConnectionsandsetupproceduresforECA30/31: Seesection'Miscellaneous'.
Quickguide"ECA30/31tooverridemode":
1.GotoECAMENU
2.Movecursorto"Clock"symbol
3.Selectthe"Clock"symbol
4.Chooseandselectoneof4overridefunctions
5.Belowtheoverridesymbol:Sethoursordate
6.Belowhours/date:Setdesiredroomtemperaturefortheoverride period
100|©Danfoss|2021.02
AQ000086469805en-010501
Loading...