Danfoss A230, B230 Operating guide

OperatingGuide
ECLComfort210/296/310/311,applicationkeys A230andB230

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................9
2.1Beforeyoustart.....................................................9
2.3Mounting...........................................................18
2.4Placingthetemperaturesensors................................22
2.5Electricalconnections.............................................24
2.6InsertingtheECLApplicationKey..............................35
2.7Checklist............................................................42
2.8Navigation,ECLApplicationKeyA230/B230................43
3.0Dailyuse.........................................................70
3.1Howtonavigate...................................................70
3.2Understandingthecontrollerdisplay..........................71
3.3Ageneraloverview:Whatdothesymbolsmean?...........74
3.4Monitoringtemperaturesandsystem
components........................................................75
3.5Influenceoverview................................................76
3.6Manualcontrol.....................................................77
3.7Schedule............................................................78
4.0Settingsoverview............................................79
5.0Settings...........................................................82
5.1IntroductiontoSettings..........................................82
5.2Flowtemperature..................................................83
5.3Roomlimit..........................................................88
5.4Returnlimit.........................................................91
5.5Flow/powerlimit.................................................97
5.6Windinfluence...................................................102
5.7Optimization......................................................104
5.8Controlparameters..............................................110
5.9Compensation1.................................................116
5.10Compensation2.................................................118
5.11Application.......................................................120
5.12Heatcut-out......................................................129
5.13Alarm..............................................................132
5.14Alarmoverview..................................................138
5.15Twocirculationpumpsinsequence..........................139
6.0Commoncontrollersettings............................140
6.1Introductionto‘Commoncontrollersettings’..............140
6.2Time&Date.......................................................141
6.3Holiday............................................................142
6.4Inputoverview...................................................144
6.5Log.................................................................145
6.6Outputoverride..................................................146
6.7Keyfunctions.....................................................147
6.8System.............................................................149
7.0Miscellaneous................................................156
7.1ECA30/31setupprocedures.................................156
7.2Overridefunction................................................164
7.3Severalcontrollersinthesamesystem......................167
7.4Frequentlyaskedquestions....................................170
7.5Definitions........................................................174
7.6Type(ID6001),overview.......................................178
7.7Automatic/manualupdateoffirmware.....................179
7.8ParameterIDoverview..........................................180
©Danfoss|2022.01AQ163786479450en-010801|1
ECLComfort210/296/310/311,applicationkeysA230andB230

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwith:
ECLApplicationKeyA230
(ordercodeno.087H3802)forECLComfort210/296/310
ECLApplicationKeyB230
(ordercodeno.087H3902)forECLComfort311
TheECLApplicationKeysA230andB230contain5subtypes:
A230.1:Temperaturecontrolinheatinginstallations.Optional compensationfromwind.Electronicbypassfunction.
A230.2:Temperaturecontrolincoolinginstallations.Optional externalsignal(0-10V)forflowtemperaturesetpoint.
A230.3:Temperaturecontrolinheatinginstallations. Compensationforhighrelativehumidity.Optional compensationfromwind.
A230.4:Temperaturecontrolinheatinginstallations.Pressure measurementbyS8or,alternatively,useS8asexternalsignal(0
-10V)fortemperaturesetpoint.Electronicbypassfunction.
A230.5:Temperaturecontrolinheatinginstallations.Flow temperature-basedcontrolofcirculationpump.Alarminput. PressuremeasurementbyS8or,alternatively,useS8asexternal signal(0-10V)forflowtemperaturesetpoint.
TheA230/B230applicationkeyalsocontainsaFloor(Screed) DryingProgramforthesubtypesA230.1,A230.3,A230.4and A230.5.Seeseparatedocumentation.(InEnglishandGerman languageonly).
Electronicbypassfunction(A230.1andA230.4)isusedtoensure sufficientsupplytemperaturefromtheDistrictHeatingUtilityfor heatingaself-actingDHWcircuit(DomesticHotWater).
Temperatures,measuredbyheat-meterviaM-Bus
ThesubtypesA230.1,A230.3andA230.5can,whenusedinECL296 /310/311,utilizetheflowandreturntemperaturesensorvaluesof theheat-meter.Thevalueforflowtemperatureisusedinsteadof S4(supplytemperature);thevalueforreturntemperatureisused insteadofS5(returntemperature).
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationexamplesandelectricalconnections.
Theapplicationdiagramsshowmandatorytemperaturesensors withanunderscore;exampleS3
.
2|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
A230
Thedescribedfunctionsarerealizedin:
ECLComfort210forbasicsolutions
ECLComfort296forbasicsolutions,inclusiveM-bus,Modbus andEthernet(Internet)communication
ECLComfort310foradvancedsolutions,inclusiveM-bus, ModbusandEthernet(Internet)communication.Theextension moduleECA32canbeused,viaa0-10Voltoutput,to controlamodulatedactuator,forexampleDanfosstypesAME. Furthermore,theextensionmoduleECA32canbeusedfor extendingthenumbersofinputsformonitoringviatheECL Portal.EachinputcanbeconfiguredasPt1000,0-10Voltor digital.
TheApplicationKeyA230complieswithECLComfort210/310 controllersasoffirmwareversion1.11. TheApplicationKeyA230compliesalsowithECLComfort296 controllersasoffirmwareversion1.58. Thefirmware(controllersoftware)versionisvisibleatstart-upof thecontrollerandin‘Commoncontrollersettings’in‘System’ .
UptotwoRemoteControlUnits,ECA30orECA31,canbe connectedforremotemonitoringandsetting.Thebuilt-inroom temperaturesensorcanbeutilized.
ECLPortal,Internetbasedconnection,allowsECL296,310and 310Btobemonitoredandcontrolledremotelyviastandard Internetbrowsers(forexampleInternetExplorer,MicrosoftEdge, GoogleChromeandSafari).
AQ163786479450en-010801
©Danfoss|2022.01|3
ECLComfort210/296/310/311,applicationkeysA230andB230
TogetherwiththeECLComfort310,theadditionalInternalI/O moduleECA32(ordercodeno.087H3202)canbeusedforextra datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool". Navigation:Danfoss.com>Serviceandsupport>Downloads> Tools>Heating>ECLTool. TheURLis:
https://www.danfoss.com/en/service-and-support/downloads/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volt(087H3240)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210,296and310, modulesandaccessoriesisavailableonhttp://danfoss.com/or http://store.danfoss.com.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
4|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
B230
Thedescribedfunctionsarerealizedin:
ECLComfort311formultiplesolutions,inclusiveM-bus, ModbusandEthernet(Internet)communication.Theextension moduleECA32canbeused,viaa0-10Voltoutput,tocontrola modulatedactuator,forexampleDanfosstypesAME.
Furthermore,theextensionmoduleECA32canbeusedfor extendingthenumbersofinputsformonitoringviatheECL Portal.EachinputcanbeconfiguredasPt1000,0-10Voltor digital.
TheApplicationKeyB230complieswithECLComfort311 controllersasoffirmwareversion11.01.
Thefirmware(controllersoftware)versionisvisibleatstart-upof thecontrollerandin‘Commoncontrollersettings’in‘System’ . ECLPortal,Internetbasedconnection,allowsECL311tobe monitoredandcontrolledremotelyviastandardInternetbrowsers (forexampleInternetExplorer,GoogleChromeandSafari).
TogetherwiththeECLComfort311,theadditionalInternalI/O moduleECA32(ordercodeno.087H3202)canbeusedforextra datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10Voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss Software"ECLTool".Navigation:Danfoss.com>Serviceand support>Downloads>Tools>Heating>ECLTool.TheURLis: https://www.danfoss.com/en/service-and-support/downloads/ TheInternalI/OmoduleECA32isplacedinthebasepartforECL Comfort311.
ECLComfort311isavailableas:
ECLComfort311,230Volta.c.(087H3041)
ECLComfort311cannotbeoperatedbymeansoftheRemote ControlunitECA30/31.
AdditionaldocumentationforECLComfort210,296,310and 311,modulesandaccessoriesisavailableonhttp://danfoss.com/ orhttp://store.danfoss.com.DocumentationforECLPortal:See http://ecl.portal.danfoss.com.
AQ163786479450en-010801
©Danfoss|2022.01|5
ECLComfort210/296/310/311,applicationkeysA230andB230
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310/311:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
6|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted:
•ECL210/310,asofcontrollerversion1.11
•ECL296,asofcontrollerversion1.58
•ECL311,asofcontrollerversion11.01
Thefollowinganimationwillbeshownwhenthesoftwareisbeing updated:
Progressbar
Duringupdate:
•DonotremovetheKEY
•Donotdisconnectthepower
•Manualupdateofcontrollersoftware(firmware):
Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
Seethesection"Automatic/manualupdateoffirmware"
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
Circuit1Parameterno.
2
Circuit2Parameterno.
174
AQ163786479450en-010801
©Danfoss|2022.01|7
ECLComfort210/296/310/311,applicationkeysA230andB230
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
8|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

2.0Installation

2.1Beforeyoustart

ThesubtypesinA230/B230areveryflexible.Thesearethebasic principles:
Heating(applicationA230.1):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3iscalculated intheECLcontroller,basedontheoutdoortemperature(S1)and thedesiredroomtemperature. Thelowertheoutdoortemperature,thehigherthedesiredflow temperature.
Bymeansofaweekschedule,theheatingcircuitcanbein ‘Comfort’or‘Saving’mode.Theweekschedulecanhaveupto3 ‘Comfort’periods/day.Avalueforthedesiredroomtemperature canbesetineachofthemodes. InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted (typicallytoalowervalue),thusresultinginagradualclosingofthe motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent oftheoutdoortemperature.Typically,thelowertheoutdoor temperature,thehighertheacceptedreturntemperature.
Ifthemeasuredroomtemperature(directlyconnectedtemperature sensorESM-10(S2)orRemotecontrolunitECA30/31)doesnot equalthedesiredroomtemperature,thedesiredflowtemperature canbeadjusted.
Thecirculationpump,P1,isONatheatdemandoratfrost protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit thefloworenergytoasetmaximumvalue.Furthermore,the limitationcanbeinrelationtotheoutdoortemperature.Typically, thelowertheoutdoortemperature,thehighertheacceptedflow/ power.WhenthissubtypeisusedinanECLComfort296/310/311 theflow/energysignalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature, forexample10°C.
TypicalA230.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296/ 310/311
S1
S2
S3
S4
ElectroniccontrollerECLComfort210,296/310 /311
Outdoortemperaturesensor
(Optional)Roomtemperaturesensor/ECA30
(Mandatory)Flowtemperaturesensor
(Optional)Supplyflowtemperaturesensor (read-outonly)
S5
S7
S8
P1
P2
M1
(Optional)Returntemperaturesensor
(Optional)Flow/energymeter(pulsesignal)
(Optional)Windspeedsignal(0-10V)
Circulationpump
(notillustrated)RelayoutputforSchedule2
Motorizedcontrolvalve,3-pointcontrolled Alternative1:Controlvalve,thermo-actuator controlled(DanfosstypeABV) Alternative2(ECL310/311withECA32):Motorized controlvalve,0-10Voltcontrolled
A1
TheA230.1applicationcanutilizeaconnectedflow/energymeter tolimittheflow/power.
Alarm
Tocompensatefortheinfluenceofwind,awindspeedsensorcan beconnected.Basedonthewindspeedsensorsignal(0-10V),the controllercanbesettoincreasethedesiredflowtemperaturein relationtoincreasedwindspeed.
Unusedinputs(fromS7andup)can,bymeansofanoverride switchorrelaycontact,beusedforoverridingthescheduletoa fixed'Comfort','Saving','Frostprotection'or'Constanttemperature' mode.
Analarmcanbeactivatediftheactualflowtemperaturediffers fromthedesiredflowtemperature.
AQ163786479450en-010801
ECA30/31doesnotworkwithECL311.
©Danfoss|2022.01|9
ECLComfort210/296/310/311,applicationkeysA230andB230
Cooling(applicationA230.2):
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredflowtemperatureatS3issetinthe ECLcontroller.Furthermore,theoutdoortemperature(S1)can influencethedesiredflowtemperature.Thehighertheoutdoor temperature,thelowerthedesiredflowtemperature.
Bymeansoftheweekschedule,thecoolingcircuitcanbein ‘Comfort’or‘Saving’mode(twovaluesforthedesiredflow temperature). Theweekschedulealsocontrolstwovalues(‘Comfort’and ‘Saving’)forthedesiredroomtemperature.Ifthemeasuredroom temperaturedoesnotequalthedesiredroomtemperature,the desiredflowtemperaturecanbeadjusted.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe flowtemperatureishigherthanthedesiredflowtemperatureand viceversa.
ThereturntemperatureS5tothecoolingsupplyshouldnotbetoo low.Ifso,thedesiredflowtemperaturecanbeadjusted(typicallyto ahighervalue),thusresultinginagradualclosingofthemotorized controlvalve.
Thecirculationpump,P1,isONatcoolingdemand.
Anexternalsignalforthedesiredflowtemperaturecanbeapplied asa0–10voltsignaltotheterminalsforS8.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit thefloworenergytoasetmaximumvalue. WhentheA230.2isusedinanECLComfort296/310/311theflow /energysignalcanalternativelycomeasanM-bussignal.
Thestandbymodemaintainsaselectableflowtemperature,for example30°C.
Unusedinputs(fromS7andup)can,bymeansofanoverride switchorrelaycontact,beusedforoverridingthescheduletoa fixed'Comfort'or'Saving'mode.
ThetemperaturesS4andS6areusedformonitoringpurposesonly.
Theschedulein"Commoncontrollersettings"controlstherelays 2and3.Thiscanbeutilizedforshiftingbetweentwocirculation pumps. Seetheinstallationguide,appl.A230.2,ex.dandrelatedelectrical connections.
TypicalA230.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296
ElectroniccontrollerECLComfort210/296/310/311
/310/311 S1
S2
S3
S4
(Optional)Outdoortemperaturesensor
(Optional)Roomtemperaturesensor/ECA30
(Mandatory)Flowtemperaturesensor,cooling
(Optional)Supplyflowtemperaturesensor(read-out only)
S5
S6
S7
(Optional)Returntemperaturesensor
(Optional)Returntemperaturesensor(read-outonly)
(Optional)Flow/energymeter(pulsesignal),not illustrated
(S8)
(Optional)(Externalvoltage(0–10V)forexternal settingofdesiredflowtemperature)
P1
P2/P3
M1
Circulationpump
Schedule2
Motorizedcontrolvalve,3-pointcontrolled Alternative1:Controlvalve,thermo-actuator controlled(DanfosstypeABV) Alternative2(ECL310/311withECA32):Motorized controlvalve,0-10Voltcontrolled
10|©Danfoss|2022.01
TheA230.2applicationcanutilizeaconnectedflow/energymeter tolimittheflow/power.
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Heating(applicationA230.3):
ThissubtypeworkslikeA230.1,buttheflow-orenergylimitation, basedonpulsesignalisnotimplemented.Ifflow-orenergy limitationisneeded,theM-Busbasedsignalcanbeused(ECL Comfort296,310or311).
Inaddition,A230.3canminimizetheriskofdew(condensation).
TheRH(RelativeHumidity)signalcanarrangeaminimumdesired roomtemperatureforprotectionagainstdew(condensation). Dewcanoccurwhenairwithhightemperatureandhumidity comestocolderwalls,forexampleinchurches,castlesandother thick-wallbuildings.
Theequation-
T.dew=(0.96xT.room)+(0.25xRH)-22.4
isusedforcalculationofthedewtemperature(T.dew).
T.roomisthemeasuredroomtemperature.RHistheRelative Humidity,basedonmeasuredroomtemperatureandhumidity.
RoomtemperatureandRHcomeseitherfrom
theRemoteControlUnitECA31
or
aroomtemperaturesensorandanappliedRHsignal,0-10 Volt,toS7.
TherelationshipbetweenappliedvoltageandrelatedRHvalue canbeset.
AnOffsetvalueforthecalculateddewtemperature(T.dew)canbe addedforcompensationbetweenwallandroomtemperatures.
Favoritedisplay1canshowthefollowing:
TypicalA230.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296
ElectroniccontrollerECLComfort210/296/310/311
/310/311 S1
S2
S3
S4
Outdoortemperaturesensor
(Optional)Roomtemperaturesensor/ECA31
(Mandatory)Flowtemperaturesensor
(Optional)Supplyflowtemperaturesensor(read-out only)
S5
S7
S8
P1
P2
M1
(Optional)Returntemperaturesensor
(Optional)RHsignal(0-10V)
(Optional)Windspeedsignal(0-10V)
Circulationpump
(notillustrated)RelayoutputforSchedule2
Motorizedcontrolvalve,3-pointcontrolled Alternative1:Controlvalve,thermo-actuator controlled(DanfosstypeABV) Alternative2(ECL310/311withECA32):Motorized controlvalve,0-10Voltcontrolled
A1
Alarm
RHvalue:76.3% Roomtemperature:20.9°C Desiredroomtemperature:19.5°C Minimumdesiredroomtemperature,inclusive6Koffset:22.7°C
AQ163786479450en-010801
©Danfoss|2022.01|11
ECLComfort210/296/310/311,applicationkeysA230andB230
Heating(A230.4)
ThissubtypeworksassubtypeA230.1,butthewindinfluence functionalityisnotimplemented. Inaddition,A230.4canmonitorDHW(DomesticHotWater) temperaturesS4andS6.
Anappliedvoltagesignal(0-10Volt)toS8canbeusedfor:
pressuremeasuring.ThevoltageisconvertedintheECL controllertoapressure,measuredinbar
or
settingthedesiredflowtemperature.Thevoltageisconverted intheECLcontrollertoatemperaturevalue.
TypicalA230.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296
ElectroniccontrollerECLComfort210/296/310/311
/310/311 S1
S2
S3
S4
Outdoortemperaturesensor
(Optional)Roomtemperaturesensor/ECA30
(Mandatory)Flowtemperaturesensor
(Optional)DHWflowtemperaturesensor(read-out only)
S5
S6
(Optional)Returntemperaturesensor
(Optional)DHWcirculationreturntemperature sensor(read-outonly)
S7
S8
(Optional)Flow/energymeter(pulsesignal)
(Optional)0-10Voltsignalfrompressuresensor Alternative:0-10Voltsignalforexternalsettingof desiredflowtemperature
P1
M1
Circulationpump,heating
Motorizedcontrolvalve,3-pointcontrolled Alternative1:Controlvalve,thermo-actuator controlled(DanfosstypeABV) Alternative2(ECL310/311withECA32):Motorized controlvalve,0-10Voltcontrolled
A1
Alarm
12|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Heating(A230.5)
ThissubtypeworksassubtypeA230.1,butthewindinfluence functionalityisnotimplemented.Inaddition,A230.5controlsthe circulationpumpP1atheatdemandtobeswitchedOFFifthe flowtemperatureS3islowerthanasetvalue(f.ex.28°C).The circulationpumpwillbeswitchedONwhentheflowtemperature S3getsaboveanothersetvalue(f.ex.32°C).Thisfunctionprevents heatedwatertogobackinthedistrictheatingnetworkifthe supplytemperatureistoolow. Furthermore,thecontrolvalvepositioncanbedisplayed,basedon avariableresistanceappliedtoinputS6.Seewiringdiagraminthe InstallationGuide.InputS7actsasanalarminput.
Anappliedvoltagesignal(0-10Volt)toS8canbeusedfor:
pressuremeasuring.ThevoltageisconvertedintheECL controllertoapressure,measuredinbar
or
settingthedesiredflowtemperature.Thevoltageisconverted intheECLcontrollertoatemperaturevalue.
Specialinfo:
IfreturntemperaturesensorS5isnotconnected,thereturn temperaturevaluecancomefromanM-Busconnectedheat-meter. Thevaluewillnot*)beshowninthedisplayoftheECL,butdespite ofthat,thevaluecanbeusedforreturntemperaturelimitation. Furthermore,thereturntemperaturevaluefromtheM-Bus connectedheat-meterisshowninECLPortal/LeanHeat®Monitor.
*)updatesoftheapplicationsubtypetoV02andupwillshowthe returntemperaturevaluefromtheheat-meter.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationexampleandelectricalconnections.
TypicalA230.5application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296 /310/311
S1
S2
S3
S4
ElectroniccontrollerECLComfort210,296,310or 311
Outdoortemperaturesensor
(Optional)Roomtemperaturesensor/ECA30
(Mandatory)Flowtemperaturesensor
(Optional)Supplyflowtemperaturesensor.For monitoringpurpose.S4-valuecan,ifsupply temperaturesensorisnotconnected,comefroman M-Busconnectedheat-meter.
S5
(Optional)Returntemperaturesensor. S5-valuecan,ifreturntemperaturesensoris notconnected,comefromanM-Busconnected heat-meter.
S6
S7
S8
(Optional)M1'sposition
(Optional)Alarminput
(Optional)0-10Voltsignalfrompressuresensor Alternative:0-10Voltsignalforexternalsettingof desiredflowtemperature.
P1
P2
M1
Circulationpump
RelayoutputforSchedule2
Motorizedcontrolvalve,3-pointcontrolled. Alternative1:Controlvalve,thermo-actuator controlled(DanfosstypeABV). Alternative2(ECL310/311withECA32):Motorized controlvalve,0-10Voltcontrolled.
A1
M-Bus
Alarm
Heat-meterconnectedviaM-Bus
AQ163786479450en-010801
©Danfoss|2022.01|13
ECLComfort210/296/310/311,applicationkeysA230andB230
A230,ingeneral:
UptotwoRemoteControlUnits,ECA30/31,canbeconnectedto oneECLcontrollertocontroltheECLcontrollerremotely. SeveralECLcontrollers,internallyconnectedviaECL485bus,work inMaster/Slaveconnection.InaMaster/Slavesystemmaximum 2ECA30/31canbepresent.
A230/B230,ingeneral:
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout heatingorcoolingdemandcanbearranged. AdditionalECLComfortcontrollerscanbeconnectedviatheECL 485bustoutilizecommonoutdoortemperaturesignal,timeand datesignals. SeveralECLcontrollers,internallyconnectedviaECL485bus,work inMaster/Slaveconnection. Anunusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixedmode: PossibilitiesforA230.1,A230.3,A230.4andA230.5: 'Comfort','Saving','Frostprotection'or'Constanttemperature' mode PossibilitiesforA230.2: 'Comfort'or'Saving'mode
Heat-meters:
Upto5heat-meterscanbeconnectedtotheM-busterminals(ECL 296/310/311). DatacanbetransferredtotheSCADAsystemviaModbusandTCP/ IPtotheECLPortal.
Temperatures,measuredbyheat-meter
ThesubtypesA230.1,A230.3andA230.5can,whenusedinECL296 /310/311,utilizetheheat-meter'sflowandreturntemperature sensorvalues.Thevalueforflowtemperatureisusedinsteadof S4(supplytemperature);thevalueforreturntemperatureisused insteadofS5(returntemperature). DirectlyconnectedtemperaturesensorsS4andS5havepriority overthetemperaturevaluesfromtheheat-meter. ThetemperaturevaluesforS4andS5,whencomingfromthe heat-meter,willtypicallyappear10sec.afterpower-up.
Modbuscommunication(ECLComfort296/310/311)toaSCADA systemcanbeestablished. TheM-busdata(ECLComfort296/310/311)canfurthermorebe transferredtotheModbuscommunication.
Alarm
A230.1,A230.3,A230.4andA230.5: AlarmA1(=relay4)canbeactivatedif:
theactualflowtemperaturediffersfromthedesiredflow temperature.
atemperaturesensororitsconnectiondisconnects/short circuits.(See:Commoncontrollersettings>System>Raw inputoverview).
A230.2: Alarmrelay4isnotused,butatemperaturesensororits connectionscanbemonitored. (See:Commoncontrollersettings>System>Rawinputoverview).
A230.4andA230.5: AlarmA1(=relay4)canbeactivatedif:
theactualpressureisnotinsideanacceptablepressurerange
A230.5: AlarmA1(=relay4)canbeactivatedif:
thealarminputS7isactivated
14|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
A230/B230,ingeneral(continued):
Offsetadjustment
Ameasuredtemperaturecanbeoffsetadjusted,ifneeded. (Navigation:MENU>Commoncontroller>System>Sensoroffset)
Inputconfiguration
Inputs(asfromS7andup)whicharenotpartoftheapplicationcan beconfiguredtobePt1000,0-10Volt,frequency(pulsecounter) orDigitalinput.ThisfeaturemakesitpossibleinECL296/310/ 311tocommunicateextrasignals,suchastemperatures,pressures, ON/OFFconditions,viaModbusandECLPortal. TheconfigurationisdonebymeansoftheECLTool(freesoftware fordownload)ordirectlyinadedicatedmenuintheECLPortalor theconnectionforModbus(BMS/SCADA).
Applicationupload
Theapplicationuploadprocedureisthefollowingafterhaving powereduptheECLComfortcontroller:
1.Inserttheapplicationkey
2.Selectlanguage
3.Selectsubtype(theInstallationGuideshowssubtypes)
4.SetTimeandDate
TheECLComfortcontrollerinstallstheapplication,initializesand restarts.Outputrelaysareactivated/de-activated(click-sounds fromthiscanbeheard).Thisalsomeansthat,forexample, circulationpumpscanbeswitchedONandOFFshortly.
Commissioning
WhentheapplicationhasbeenuploadedtheECLComfort controllerstartsinManualmode.Thiscanbeusedtoverifycorrect connectionsoftemperature,pressureandflowsensors.Also verifyingthecontrolledcomponents(valveactuators,pumpsetc.) forcorrectfunctionalitycanbedone.
Theapplicationkeyisdeliveredwithfactorysettings. Dependingonsystemtype,itmightbenecessarytochangesome factorysettingsindividuallyinordertooptimizethefunctionality.
Theapplicationkeymustbeinsertedinordertochangesettings.
Power-down/power-up
WhenthepowersupplytotheECLComfortcontrolleris disconnected(power-down),theoutputrelaysgotode-activated position. Thismeansthat,forexample,circulationpumpscanbeswitched ON. SeetheelectricalconnectiondiagramsintheInstallationGuide. Allrelaycontactsareshowninde-activatedsituation.Somerelay contactsareclosed,somerelaycontactsareopen. WhenthepowersupplytotheECLComfortcontrolleris re-established(power-up),theoutputrelaysareactivated/ de-activated(click-soundsfromthiscanbeheard).Thisalsomeans that,forexample,circulationpumpscanbeswitchedONandOFF shortly.
Important:
Setthecorrectrunningtime"Mrun"oftheMotorizedControl ValveM1.(Circuit1>MENU>Settings>Controlparameters >Mrun).
AQ163786479450en-010801
©Danfoss|2022.01|15
ECLComfort210/296/310/311,applicationkeysA230andB230
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
16|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
AQ163786479450en-010801
©Danfoss|2022.01|17
ECLComfort210/296/310/311,applicationkeysA230andB230

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310/311canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310/311controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
18|©Danfoss|2022.01
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
AQ163786479450en-010801
©Danfoss|2022.01|19
ECLComfort210/296/310/311,applicationkeysA230andB230
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
20|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310B/311basepartforadditionalinput andoutputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310B/311andECA 32isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310B/311isplacedon thebasepart.
AQ163786479450en-010801
©Danfoss|2022.01|21
ECLComfort210/296/310/311,applicationkeysA230andB230

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedfor theECLComfort210/296/310/311serieswhichnotallwillbe neededforyourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
22|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ163786479450en-010801
©Danfoss|2022.01|23
ECLComfort210/296/310/311,applicationkeysA230andB230

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
24|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310/311
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
A230.2(cooling):2-pumpcontrol
ApplicationA230.2,ex.disanexampleforscheduledshiftbetween twocirculationpumps. ControlofP1isbasedonthecoolingdemandanddetermines viaK1theON/OFFcontrolofthepumpsP2andP3.P2andP3 arerelatedtotheoutputoftheschedulein"Commoncontroller settings". TheelectricdiagramforA230.2,P2andP3showsanexamplefor connection.
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ163786479450en-010801
©Danfoss|2022.01|25
ECLComfort210/296/310/311,applicationkeysA230andB230
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
1A/24Va.c.
relay)terminals
A230.2(cooling):2-pumpcontrol
ApplicationA230.2,ex.disanexampleforscheduledshiftbetween 2circulationpumps. ControlofP1isbasedonthecoolingdemandanddetermines viaK1theON/OFFcontrolofthepumpsP2andP3.P2andP3 arerelatedtotheoutputoftheschedulein"Commoncontroller settings". TheelectricdiagramforA230.2,P2andP3showsanexamplefor connection.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
26|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
2.5.3Electricalconnections,safetythermostats,ingeneral
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Theconnectiondiagramsshowvarioussolutions/examples:
Safetythermostat,1–stepclosing: Motorizedcontrolvalvewithoutsafetyfunction
Safetythermostat,1–stepclosing: Motorizedcontrolvalvewithsafetyfunction
Safetythermostat,2–stepclosing: Motorizedcontrolvalvewithsafetyfunction
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
AQ163786479450en-010801
©Danfoss|2022.01|27
ECLComfort210/296/310/311,applicationkeysA230andB230
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Sensor
S1 S2
Description
Outdoortemperaturesensor* Roomtemperaturesensor**
Alternative:ECA30/31
S3
S4
Flowtemperaturesensor***
A230.1,A230.2,A230.3, A230.5:Supplytemperature sensor,formonitoring A230.4:DHWtemperature sensor,formonitoring
S5Returntemperaturesensor
S6A230.2:Returntemperature
sensor,formonitoring A230.4:DHWcirculation returntemperaturesensor,for monitoring A230.5:M1position
S7
A230.1,A230.2,A230.4:Flow/ energymeter(pulsesignal) A230.3:RelativeHumidity signal(0-10V) A230.5:Alarm
S8
A230.2:Desiredcooling temperature,0-10V A230.4/A230.5:Pressure transmitter,0-10V. Alternatively,desiredheating temperature,0-10V
Recommendedtype
ESMT ESM-10
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
*
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
**
Onlyforroomtemperaturesensorconnection.Theroom temperaturesignalcanalsobeavailablefromaRemote ControlUnit(ECA30/31).SeetheInstallationGuide (deliveredwiththeapplicationkey)forspecificconnections.
***
Theflowtemperaturesensormustalwaysbeconnected inordertohavethedesiredfunctionality.Ifthesensoris notconnectedorthecableisshort-circuited,themotorized controlvalvecloses(safetyfunction).
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
28|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Connectionofflow/energymeterwithpulsesignal
SeetheInstallationGuide(deliveredwiththeapplicationkey).
Theoutputoftheflow/energymetercanbeequippedwithan externalpull-upresistorifaninternalpull-upresistorisnotpresent.
Pulsebasedsignalforflow/power ,appliedtoinputS7
Formonitoring: Frequencyrangeis0.01-200Hz
Forlimitation: Minimumfrequencyisrecommendedtobe1Hzinordertohavea
stablecontrol.Furthermore,thepulsesmustappearregularly.
A230.1,A230.3 Connectionofwindspeedsensor
SeetheInstallationGuide(deliveredwiththeapplicationkey).
A230.4,A230.5 Connectionofpressuresensor
SeetheInstallationGuide(deliveredwiththeapplicationkey).
Set-upofrelationbetweenappliedvoltage(0-10V)from pressuresensorandexpressedpressure(inBar)inECL:Seesection Frequentlyaskedquestions.
AQ163786479450en-010801
©Danfoss|2022.01|29
ECLComfort210/296/310/311,applicationkeysA230andB230
A230.2,A230.4,A230.5
Connectionofexternalvoltage(0–10V)forexternalsetting ofdesiredflowtemperature
Connectionofswitchforexternaloverride
S?: ECL210/296:S7-S8 ECL310:S7-S10 ECL310/311+ECA32:S7-S16
Usinganinputforoverriderequiresavoltfreecontact/switch.
IfS1...S6ischosenasoverrideinput,theoverrideswitchmusthave gold-platedcontacts.
IfS7...S16ischosenasoverrideinput,theoverrideswitchcanbea standardcontact.
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus) Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
30|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
2.5.5Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
AQ163786479450en-010801
©Danfoss|2022.01|31
ECLComfort210/296/310/311,applicationkeysA230andB230
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
32|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310/311:GalvanicisolatedModbusconnections
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
AQ163786479450en-010801
©Danfoss|2022.01|33
ECLComfort210/296/310/311,applicationkeysA230andB230
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310/311:Onboard,non-galvanicisolated.Max. cablelength50m.
34|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310/311
ECLComfort210/310/311
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
AQ163786479450en-010801
ECLComfort296
©Danfoss|2022.01|35
ECLComfort210/296/310/311,applicationkeysA230andB230
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted:
•ECL210/310,asofcontrollerversion1.11
•ECL296,asofcontrollerversion1.58
•ECL311,asofcontrollerversion11.01
Thefollowinganimationwillbeshownwhenthesoftwareisbeing updated:
Progressbar
Duringupdate:
•DonotremovetheKEY
•Donotdisconnectthepower
•Manualupdateofcontrollersoftware(firmware):
Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310/311,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
36|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date' , 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Y es' .
AQ163786479450en-010801
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
©Danfoss|2022.01|37
ECLComfort210/296/310/311,applicationkeysA230andB230
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
38|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296,310or311)mustbeconfiguredwiththesameapplication butuser/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
AQ163786479450en-010801
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
©Danfoss|2022.01|39
ECLComfort210/296/310/311,applicationkeysA230andB230
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210,310or311). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
40|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
ECLComfort210/310/311,controllerversions1.36andup:
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ163786479450en-010801
©Danfoss|2022.01|41
ECLComfort210/296/310/311,applicationkeysA230andB230

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
42|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

2.8Navigation,ECLApplicationKeyA230/B230

Navigation,A230/B230,applicationA230.1
Home
IDno.
MENU
ScheduleSelectable
Settings
Flowtemperature
11178
11177
11004
Roomlimit
Returnlimit
Flow/powerlimitActual
Windinfluence
11015
11182
11183
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
11119
11117
11118
11116
11112
11113
11109
11115
11114
11099
11057
11081
ApplicationA230.1
Function
Heatcurve
Temp.max.
Temp.min.
DesiredT
Adapt.time
Infl.-max.
Infl.-min.
HighToutX1
LowlimitY1 LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1 LowToutX2
HighlimitY2
Adapt.time
Filterconstant Inputtype
Units
Pulse
Windactual Limit
Infl.-max.
Filterconstant
AQ163786479450en-010801
©Danfoss|2022.01|43
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.1,continued
Home
MENU
Settings
Optimization
Controlpar.
Application
Heatcut-out
IDno.
11011 11012 11013 11014 11026 11020 11021 11179 11174 11184 11185 11186 11187 11189 11024 11010
11017
11050
11500
11022
11023
11052
11077
11078
11040
11093
11141
11142
11393
11392
11179
11395
11397
11396
11398
11399
ApplicationA230.1
Function
Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Motorpr. Xp Tn Mrun Nz Min.act.time Actuator ECAaddr.
Demandoffset
Pdemand
SenddesiredT
Pexercise
Mexercise
DHWpriority
PfrostT
PheatT
Ppost-run
Frostpr.T
Ext.input
Ext.mode
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Winterstart,month
Winter,cut-out
Winter,filter
44|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.1,continued
Home
MENU
HolidaySelectable
Alarm
InfluenceoverviewDes.flowTReturnlim.
Temp.monitoring
AlarmoverviewSelectable
IDno.
11147
11148
11149
11150
ApplicationA230.1
Function
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Roomlim.
Windinfluence
Flow/powerlim.
Holiday
Ext.override
ECAoverride
Boost
Ramp
Slave,demand
Heatingcut-out
DHWpriority
SCADAoffset
Floordry.,active
AQ163786479450en-010801
©Danfoss|2022.01|45
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,ApplicationA230.1,Commoncontrollersettings
Home
MENU
Time&Date
ScheduleSelectable
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
FloordryingFunctionalheating
OutdoorTLogtoday
Heatingflow&des.
RoomT&desiredLog2days
HeatreturnT&limitLog4days
SupplyT
Windspeed
Curingheating
Commoncontrollersettings
IDno.
Function
Selectable
OutdoorT
Outdooracc.T
RoomT
HeatflowT
HeatreturnT
SupplyT
Windactual
Logyesterday
M1
P1
V1
P2
A1
DesiredflowT
X1
X2
X3
X4
DesiredflowT
X5
X6
X7
X8
RampX5–X6
RampX7–X8
Max.pwr.failure
Afterpowerfail.
Prog.execution
Appl.continue
46|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.1,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet(ECLComfort296/310/311only)
Portalconfig(ECLComfort296/310/311 only)
M-busconfig(ECLComfort296/310/311 only)
EnergyMeters (ECLComfort296/310/311only)
Rawinputoverview
SensoroffsetS1...S8offset(ECLComfort
Function
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Buildno.
Serialno.
Productiondate
Addresstype
ECLportal
Portalstatus
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210/
296) S1-S10(ECLComfort310 /311) S1-S18(ECLComfort310/ 311withECA32)
210/296) S1...S10offset(ECL Comfort310/311)
AQ163786479450en-010801
©Danfoss|2022.01|47
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.1,Commoncontrollersettings,continued
Home
MENU
Alarm
Display
Communication
Language
Commoncontrollersettings
IDno.
32:
60058
60059
2048
38
39
2150
2151
2050
Function
Tsensordefect
Backlight
Contrast
ECL485addr.
Modbusaddr.
Baud
Servicepin
Ext.reset
Language
48|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.2
Home
IDno.
MENU
ScheduleSelectable
Settings
FlowtemperatureExt.desiredT
11084
11018
11019
11178
11177
Roomlimit
Returnlimit
Compensation1
Compensation2
Flow/powerlimitActual
11015
11182
11183
11030
11037
11035
11036
11060 11061
11062
11063
11064 11065
11066
11067
11111
11112
11113
11109
11115
11114
ApplicationA230.2
Function
Ext.signal
Des.Tcomfort Des.Tsaving
Temp.max.
Temp.min.
Adapt.time
Infl.-max.
Infl.-min. Limit
Adapt.time
Infl.-max.
Infl.-min. Limit Adapt.time
Infl.-max.
Infl.-min. Limit Adapt.time
Infl.-max.
Infl.-min.
Limit
Adapt.time
Filterconstant Inputtype
Units
Pulse
AQ163786479450en-010801
©Danfoss|2022.01|49
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.2,continued
Home
MENU
Settings
HolidaySelectable
InfluenceoverviewDes.flowT
Controlpar.
Application
IDno.
11174 11184 11185 11186 11187 11189 11024 11010
11017
11050
11500
11022
11023
11070
11092
11040
11141
11142
ApplicationA230.2
Function
Motorpr. Xp Tn Mrun Nz Min.act.time Actuator ECAaddr.
Demandoffset
Pdemand
SenddesiredT
Pexercise
Mexercise
PcoolT
StandbyT
Ppost-run
Ext.input
Ext.mode
Returnlim.
Roomlim.
Compensation1
Compensation2
Flow/powerlim.
Holiday
Ext.override
ECAoverride
Slave,demand
SCADAoffset
50|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,ApplicationA230.2,Commoncontrollersettings
Home
MENU
Time&Date
ScheduleSelectable
Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
OutdoorTLogtoday
CoolT&desiredLogyesterday
RoomT&desiredLog2days
Coolreturn&lim.Log4days
ReturnTsec.
SupplyT
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Commoncontrollersettings
IDno.
Function
Selectable
OutdoorT
RoomT
CoolflowT
SupplyT
CoolreturnT
ReturnTsec.
Ext.desiredT
M1
P1
V1
P2
P3
A1
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
AQ163786479450en-010801
©Danfoss|2022.01|51
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.2,Commoncontrollersettings,continued
Home
MENU
SystemECLversion
Commoncontrollersettings
IDno.
Extension
Ethernet(ECLComfort296/310/311only)
Portalconfig(ECLComfort296/310/311 only)
M-busconfig(ECLComfort296/310/311 only)
EnergyMeters (ECLComfort296/310/311only)
Rawinputoverview
SensoroffsetS1...S8offset(ECLComfort
Alarm
Display
Communication
Language
60058
60059
Function
Codeno.
Hardware
Software
Buildno.
Serialno.
Productiondate
Addresstype
ECLportal
Portalstatus
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210/
296) S1-S10(ECLComfort310 /311) S1-S18(ECLComfort310/ 311withECA32)
210/296) S1...S10offset(ECL Comfort310/311)
32:
Tsensordefect
Backlight
Contrast
2048
ECL485addr.
38
Modbusaddr.
39
Baud
2150
Servicepin
2151
Ext.reset
2050
Language
52|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.3
Home
IDno.
MENU
ScheduleSelectable
Settings
Flowtemperature
11178
11177
11004
RoomlimitHumidity
11164
11015
11182
11183
Returnlimit
Flow/powerlimitActual
Windinfluence
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
11119
11117
11118
11116
11112
11113
11109
11115
11099
11057
11081
ApplicationA230.3
Function
Heatcurve
Temp.max.
Temp.min.
DesiredT
Dewp.Toffset
Adapt.time
Infl.-max.
Infl.-min.
HighToutX1
LowlimitY1 LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1 LowToutX2
HighlimitY2
Adapt.time
Filterconstant Inputtype
Units
Windactual Limit
Infl.-max.
Filterconstant
AQ163786479450en-010801
©Danfoss|2022.01|53
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.3,continued
Home
MENU
Settings
Optimization
Controlpar.
Application
Heatcut-out
IDno.
11011 11012 11013 11014 11026 11020 11021 11179 11174 11184 11185 11186 11187 11189 11024 11010
11017
11050
11500
11022
11023
11052
11077
11078
11040
11093
11141
11142
11393
11392
11179
11395
11397
11396
11398
11399
ApplicationA230.3
Function
Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Motorpr. Xp Tn Mrun Nz Min.act.time Actuator ECAaddr.
Demandoffset
Pdemand
SenddesiredT
Pexercise
Mexercise
DHWpriority
PfrostT
PheatT
Ppost-run
Frostpr.T
Ext.input
Ext.mode
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Winterstart,month
Winter,cut-out
Winter,filter
54|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.3,continued
Home
MENU
HolidaySelectable
Alarm
InfluenceoverviewDes.flowTReturnlim.
Temp.monitoring
AlarmoverviewSelectable
IDno.
11147
11148
11149
11150
ApplicationA230.3
Function
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Roomlim.
Windinfluence
Flow/powerlim.
Holiday
Ext.override
ECAoverride
Boost
Ramp
Slave,demand
Heatingcut-out
DHWpriority
SCADAoffset
Floordry.,active
AQ163786479450en-010801
©Danfoss|2022.01|55
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,ApplicationA230.3,Commoncontrollersettings
Home
MENU
Time&Date
ScheduleSelectable
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
FloordryingFunctionalheating
OutdoorTLogtoday
Heatingflow&des.
RoomT&desiredLog2days
HeatreturnT&limitLog4days
SupplyT
Windspeed
Humidity
Curingheating
Commoncontrollersettings
IDno.
Function
Selectable
OutdoorT
Outdooracc.T
RoomT
HeatflowT
HeatreturnT
SupplyT
Windactual
Humidity
Logyesterday
M1
P1
V1
P2
A1
DesiredflowT
X1
X2
X3
X4
DesiredflowT
X5
X6
X7
X8
RampX5–X6
RampX7–X8
Max.pwr.failure
Afterpowerfail.
Prog.execution
Appl.continue
56|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.3,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet(ECLComfort296/310/311only)
Portalconfig(ECLComfort296/310/311 only)
M-busconfig(ECLComfort296/310/311 only)
EnergyMeters (ECLComfort296/310/311only)
Rawinputoverview
SensoroffsetS1...S8offset(ECLComfort
Function
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Buildno.
Serialno.
Productiondate
Addresstype
ECLportal
Portalstatus
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210/
296) S1-S10(ECLComfort310 /311) S1-S18(ECLComfort310/ 311withECA32)
210/296) S1...S10offset(ECL Comfort310/311)
AQ163786479450en-010801
©Danfoss|2022.01|57
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.3,Commoncontrollersettings,continued
Home
MENU
Alarm
Display
Communication
Language
Commoncontrollersettings
IDno.
32:
60058
60059
2048
38
39
2150
2151
2050
Function
Tsensordefect
Backlight
Contrast
ECL485addr.
Modbusaddr.
Baud
Servicepin
Ext.reset
Language
58|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.4
Home
IDno.
MENU
ScheduleSelectable
Settings
Flowtemperature
11178
11177
11004
Roomlimit
Returnlimit
Flow/powerlimitActual
11015
11182
11183
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
11119
11117
11118
11116
11112
11113
11109
11115
11114
ApplicationA230.4
Function
Heatcurve
Temp.max.
Temp.min.
Ext.desiredT
DesiredT
Adapt.time
Infl.-max.
Infl.-min.
HighToutX1
LowlimitY1 LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1 LowToutX2
HighlimitY2
Adapt.time
Filterconstant Inputtype
Units
Pulse
AQ163786479450en-010801
©Danfoss|2022.01|59
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.4,continued
Home
MENU
Settings
Optimization
Controlpar.
Application
Heatcut-out
IDno.
11011 11012 11013 11014 11026 11020 11021 11179 11174 11184 11185 11186 11187 11189 11024 11010
11017
11050
11500
11022
11023
11052
11077
11078
11040
11093
11141
11142
11327
11393
11392
11179
11395
11397
11396
11398
11399
ApplicationA230.4
Function
Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Motorpr. Xp Tn Mrun Nz Min.act.time Actuator ECAaddr.
Demandoffset
Pdemand
SenddesiredT
Pexercise
Mexercise
DHWpriority
PfrostT
PheatT
Ppost-run
Frostpr.T
Ext.input
Ext.mode
Inputtype
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Winterstart,month
Winter,cut-out
Winter,filter
60|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B23,applicationA230.4,continued
Home
MENU
HolidaySelectable
Alarm
InfluenceoverviewDes.flowTReturnlim.
PressurePressure
Temp.monitoring
AlarmoverviewSelectable
IDno.
11614
11615
11617
11147
11148
11149
11150
ApplicationA230.4
Function
Alarmhigh
Alarmlow
Alarmtime-out
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Roomlim.
Flow/powerlim.
Holiday
Ext.override
ECAoverride
Boost
Ramp
Slave,demand
Heatingcut-out
DHWpriority
SCADAoffset
Floordry.,active
AQ163786479450en-010801
©Danfoss|2022.01|61
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,ApplicationA230.4,Commoncontrollersettings
Home
MENU
Time&Date
ScheduleSelectable
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
FloordryingFunctionalheating
OutdoorTLogtoday
Heatingflow&des.
RoomT&desiredLog2days
HeatreturnT&limitLog4days
Pressure
Curingheating
Commoncontrollersettings
IDno.
Function
Selectable
OutdoorT
Outdooracc.T
RoomT
HeatflowT
HeatreturnT
Pressure
Ext.desiredT
Logyesterday
M1
P1
V1
P2
A1
DesiredflowT
X1
X2
X3
X4
DesiredflowT
X5
X6
X7
X8
RampX5–X6
RampX7–X8
Max.pwr.failure
Afterpowerfail.
Prog.execution
Appl.continue
62|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.4,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet(ECLComfort296/310/311only)
Portalconfig(ECLComfort296/310/311 only)
M-busconfig(ECLComfort296/310/311 only)
EnergyMeters (ECLComfort296/310/311only)
Rawinputoverview
SensoroffsetS1...S8offset(ECLComfort
Function
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Buildno.
Serialno.
Productiondate
Addresstype
ECLportal
Portalstatus
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210/
296) S1-S10(ECLComfort310 /311) S1-S18(ECLComfort310/ 311withECA32)
210/296) S1...S10offset(ECL Comfort310/311)
AQ163786479450en-010801
©Danfoss|2022.01|63
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.4,Commoncontrollersettings,continued
Home
MENU
Alarm
Display
Communication
Language
Commoncontrollersettings
IDno.
32:
60058
60059
2048
38
39
2150
2151
2050
Function
Tsensordefect
Backlight
Contrast
ECL485addr.
Modbusaddr.
Baud
Servicepin
Ext.reset
Language
64|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.5
Home
IDno.
MENU
ScheduleSelectable
Settings
Flowtemperature
11178
11177
11004
Roomlimit
Returnlimit
Flow/powerlimitActual
11015
11182
11183
11031
11032
11033
11034
11035
11036
11037
11085
11029
11028
11119
11117
11118
11116
11112
11113
11109
11115
ApplicationA230.5
Function
Des.flowT Heatcurve
Temp.max.
Temp.min.
Ext.desiredT
DesiredT
Adapt.time
Infl.-max.
Infl.-min.
HighToutX1
LowlimitY1 LowToutX2
HighlimitY2
Infl.-max.
Infl.-min.
Adapt.time Priority
DHW,ret.Tlimit
Con.T,re.Tlim.
Limit
HighToutX1
LowlimitY1 LowToutX2
HighlimitY2
Adapt.time
Filterconstant Inputtype
Units
AQ163786479450en-010801
©Danfoss|2022.01|65
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.5,continued
Home
MENU
Settings
Optimization
Controlpar.
Application
Heatcut-out
IDno.
11011 11012 11013 11014 11026 11020 11021 11179 11174 11184 11185 11186 11187 11189 11024 11010
11017
11500
11022
11023
11052
11077
11342
11344
11040
11093
11141
11142
11327
11393
11392
11179
11395
11397
11396
11398
11399
ApplicationA230.5
Function
Autosaving Boost Ramp Optimizer Pre-stop Basedon Totalstop Summer,cut-out Motorpr. Xp Tn Mrun Nz Min.act.time Actuator ECAaddr.
Demandoffset
SenddesiredT
Pexercise
Mexercise
DHWpriority
PfrostT
Startheat
Stopheat
Ppost-run
Frostpr.T
Ext.input
Ext.mode
Inputtype
Sum.start,day
Sum.start,month
Summer,cut-out
Summer,filter
Winterstart,day
Winterstart,month
Winter,cut-out
Winter,filter
66|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.5,continued
Home
MENU
HolidaySelectable
Alarm
InfluenceoverviewDes.flowTReturnlim.
Temp.monitoring
AlarmoverviewSelectable
IDno.
11147
11148
11149
11150
ApplicationA230.5
Function
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Roomlim.
Windinfluence
Flow/powerlim.
Holiday
Ext.override
ECAoverride
Boost
Ramp
Slave,demand
Heatingcut-out
DHWpriority
SCADAoffset
Ext.desiredT
AQ163786479450en-010801
©Danfoss|2022.01|67
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,ApplicationA230.5,Commoncontrollersettings
Home
MENU
Time&Date
ScheduleSelectable
HolidaySelectable
Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
OutdoorTLogtoday
Heatingflow&des.
RoomT&desiredLog2days
HeatreturnT&limitLog4days
SupplyT
Pressure
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Commoncontrollersettings
IDno.
Function
Selectable
OutdoorT
Outdooracc.T
RoomT
HeatflowT
HeatreturnT
SupplyT
Pressure
Ext.desiredT
Position
Logyesterday
M1
P1
V1
P2
A1
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
68|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Navigation,A230/B230,applicationA230.5,Commoncontrollersettings,continued
Home
MENU
SystemECLversion
Commoncontrollersettings
IDno.
Extension
Ethernet(ECLComfort296/310/311only)
Portalconfig(ECLComfort296/310/311 only)
M-busconfig(ECLComfort296/310/311 only)
EnergyMeters (ECLComfort296/310/311only)
Rawinputoverview
SensoroffsetS1...S8offset(ECLComfort
Alarm
Display
Communication
60058
60059
Function
Codeno.
Hardware
Software
Buildno.
Serialno.
Productiondate
Addresstype
ECLportal
Portalstatus
Portalinfo
5998
Command
5997
Baud
6000
M-busaddress
6002
Scantime
6001
Type
EnergyMeter1....5
S1-S8(ECLComfort210/
296) S1-S10(ECLComfort310 /311) S1-S18(ECLComfort310/ 311withECA32)
210/296) S1...S10offset(ECL Comfort310/311)
32:
Tsensordefect
Backlight
Contrast
2048
ECL485addr.
38
Modbusaddr.
39
Baud
2150
Servicepin
2151
Ext.reset
2153
Portalencryption
Language
AQ163786479450en-010801
2050
Language
©Danfoss|2022.01|69
ECLComfort210/296/310/311,applicationkeysA230andB230

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
70|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310/311series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
Heatingcircuit
Overviewdisplay1informsabout: actualoutdoortemperature,controllermode, actualroomtemperature,desiredroomtemperature.
Overviewdisplay2informsabout: actualoutdoortemperature,trendinoutdoortemperature, controllermode,max.andmin.outdoortemperaturessince midnightaswellasdesiredroomtemperature.
Overviewdisplay3informsabout: date,actualoutdoortemperature,controllermode,time,desired roomtemperatureaswellasshowsthecomfortscheduleofthe currentday.
Overviewdisplay4informsabout: stateofthecontrolledcomponents,actualflowtemperature, (desiredflowtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredflowtemperature.
ThevalueabovetheV2symbolindicates0–100%oftheanalogue signal(0–10V).
Note:
Anactualflowtemperaturevaluemustbepresent,otherwisethe circuit'scontrolvalvewillclose.
Overviewdisplay1:Overviewdisplay2:
Overviewdisplay3:Overviewdisplay4:
Exampleofoverviewdisplaywith Influenceindication:
Example,favoritedisplay1in A230.3,wheremin.desiredroom temperatureisindicated(22.7):
Dependentonthechosendisplay,theoverviewdisplaysforthe heatingcircuitinformyouabout:
•actualoutdoortemperature(-0.5)
•controllermode()
•actualroomtemperature(24.5)
•desiredroomtemperature(20.7°C)
•trendinoutdoortemperature(
)
•min.andmax.outdoortemperaturessincemidnight(
•date(23.02.2010)
•time(7:43)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M2,P2)
•actualflowtemperature(49°C),(desiredflowtemperature(31))
•returntemperature(24°C)(limitationtemperature(50))
AQ163786479450en-010801
)
©Danfoss|2022.01|71
ECLComfort210/296/310/311,applicationkeysA230andB230
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
Ifthetemperaturevalueisdisplayedas
"--"
"---"
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
thesensorinquestionisnotconnected.
thesensorconnectionisshort-circuited.
Settingthedesiredroomtemperature
Thedesiredroomtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheheatingcircuit.
Action:Purpose:
Examples:
Desiredroomtemperature
Confirm
Adjustthedesiredroomtemperature
Confirm
Thisoverviewdisplayinformsaboutoutdoortemperature,actual roomtemperatureaswellasdesiredroomtemperature.
Thedisplayexampleisforcomfortmode.Ifyouwanttochange thedesiredroomtemperatureforsavingmode,choosethemode selectorandselectsaving.
20.5
21.0
72|©Danfoss|2022.01
Thesettingofthedesiredroomtemperatureisimportantevenifa roomtemperaturesensor/RemoteControlUnitisnotconnected.
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Settingthedesiredroomtemperature,ECA30/ECA31
Thedesiredroomtemperaturecanbesetexactlyasinthe controller.However,othersymbolscanbepresentinthedisplay (pleasesee'Whatdothesymbolsmean?').
WiththeECA30/ECA31youcanoverridethedesiredroom temperaturesetinthecontrollertemporarilybymeansoftheoverride
functions:
AQ163786479450en-010801
©Danfoss|2022.01|73
ECLComfort210/296/310/311,applicationkeysA230andB230

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
74|©Danfoss|2022.01
DamperOFF
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

3.4Monitoringtemperaturesandsystemcomponents

Heatingcircuit
Theoverviewdisplayintheheatingcircuitensuresaquick overviewoftheactualand(desired)temperaturesaswellasthe actualstateofthesystemcomponents.
Displayexample:
49°C
(31)
24°C
(50)
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
Flowtemperature
Desiredflowtemperature Returntemperature
Returntemperaturelimitation
AQ163786479450en-010801
©Danfoss|2022.01|75
ECLComfort210/296/310/311,applicationkeysA230andB230
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310/311series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
76|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310/311series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
AQ163786479450en-010801
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
Manualcontrolof0–10voltcontrolledactuator:
Theactuatorsymbolhasavalue(in%)whichcanbechanged.The% valueiscorrespondingtoavoltageintherange0–10volt.
©Danfoss|2022.01|77
ECLComfort210/296/310/311,applicationkeysA230andB230

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310/311series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
78|©Danfoss|2022.01
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Heatcurve
Ext.desiredT
Humidity(Relativehumidity)
Actual(actualfloworpower)
Windactual
Awaittime(read-outonly)
Extendedheatcut-outsetting
Extendedwintercut-outsetting
DesiredT(Desiredflowtemperature)
ECAaddr.(ECAaddress,choiceofRemoteControlUnit)
Autosaving(savingtemp.dependentonoutdoortemp.)
Boost
Ramp(referenceramping)
Optimizer(optimizingtimeconstant)
Adapt.time(adaptiontime)
Demandoffset
Des.TComfort
Des.TSaving
Basedon(optimizationbasedonroom/outdoortemp.)
Totalstop
Pexercise(pumpexercise)
Mexercise(valveexercise)
Actuator
Pre-stop(optimizedstoptime)
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
DHW,ret.Tlimit
Limit(returntemp.limitation)
HighToutX1(returntemp.limitation,highlimit,X-axis)
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
LowToutX2(returntemp.limitation,lowlimit,X-axis)
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Ppost-run
Pdemand
DHWpriority(closedvalve/normaloperation)
Infl.—max.
1x00485
1x010120
1x011104
1x012105
1x013106
1x014106
1x01589
1x017120
1x01886
1x01986
1x020107
1x021107
1x022121
1x023122
1x024112
1x026108
1x02893
1x02993
1x03094
1x03194
1x03294
1x03394
1x03495
1x03595
1x03695
1x03795
1x040122
1x050122
1x052123
1x057102
Factorysettingsincircuit(s)
1
83
84
88
98
102
111
130
130
2
AQ163786479450en-010801
©Danfoss|2022.01|79
ECLComfort210/296/310/311,applicationkeysA230andB230
SettingIDPage
Limit(compensationtemp.,1.point)
Adapt.time(adaptationtime)
Infl.-max.(compensationtemp.,1.point)
Infl.-min.(compensationtemp.,1.point)
Limit(compensationtemp.,2.point)
Adapt.time(adaptationtime)
Infl.-max.(compensationtemp.,2.point)
Infl.-min.(compensationtemp.,2.point)
PcoolT(coolingdemand)
PfrostT(circulationpump,frostprotectiontemp.)
PheatT(heatdemand)
Filterconstant
Ext.signal
Priority(priorityforreturntemp.limitation)
StandbyT
Frostpr.T(frostprotectiontemp.)
SupplyT(idle)
Limit
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Pulse
Units
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
LowlimitY1(flow/powerlimitation,lowlimit,Y-axis)
LowToutX2(flow/powerlimitation,lowlimit,X-axis)
HighToutX1(flow/powerlimitation,highlimit,X-axis)
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Mon.Tselect(Monitoringtemperature,selectionof monitoringtemperaturesensor)
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Dewp.Toffset(Dewpointtemperature,offset)
Dewp.Toffset(Dewpointtemperatureoffset)
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Summer,cut-out(limitforheatingcut-out)
1x060116
1x061116
1x062116
1x063
1x064118
1x065118
1x066118
1x067118
1x070123
1x077123
1x078124
1x081102
1x08486
1x08596
1x092124
1x093124
1x097112
1x099103
1x10998
1x111
1x11299
1x11399
1x114
1x115
1x116100
1x117
1x118101
1x119101
1x141
1x142125
1x145
1x147
1x148135
1x149136
1x150136
1x16486
1x16489
1x174
1x177
1x17887
1x179108
Factorysettingsincircuit(s)
1
117
99
99
99
100
124
112
135
112
87
2
80|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
SettingIDPage
Infl.-max.(roomtemp.limitation,max.)
Infl.-min.(roomtemp.limitation,min.)
Xp(proportionalband)
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Inputtype
Wakeuplevel
Startheat
Stopheat
Control,delay
SenddesiredT
Alarmhigh
Alarmlow
Alarmvalue
Alarmtime-out
Alarmtime-out
1x18289
1x18390
1x184113
1x185113
1x186113
1x187113
1x189
1x327127
1x330
1x342127
1x344128
1x364
1x500128
1x614134
1x615134
1x616136
1x617135
1x617137
Factorysettingsincircuit(s)
1
114
114
114
2
AQ163786479450en-010801
©Danfoss|2022.01|81
ECLComfort210/296/310/311,applicationkeysA230andB230

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310/311controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310/311controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
82|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

5.2Flowtemperature

TheECLComfortcontrollerdeterminesandcontrolstheflow temperaturerelatedtotheoutdoortemperature.Thisrelationship iscalledtheheatcurve. Theheatcurveissetbymeansof6coordinatepoints.Thedesired flowtemperatureissetat6pre-definedoutdoortemperature values. Theshownvaluefortheheatcurveisanaveragevalue(slope), basedontheactualsettings.
Desiredflowtemperature
Outdoor
temp.
Desiredflowtemp.
A
BC
Your
settings
-30°C45°C75°C95°C
-15°C40°C60°C90°C
-5°C35°C50°C80°C 0°C32°C45°C70°C 5°C30°C40°C60°C
15°C25°C28°C35°C
A:Exampleforfloorheating B:Factorysettings C:Exampleforradiatorheating(highdemand)
MENU>Settings>Flowtemperature
Heatcurve
1
0.1...4.01.0
Theheatcurvecanbechangedintwoways:
1.Thevalueoftheslopeischanged(seeheatcurveexamples onnextpage)
2.Thecoordinatesoftheheatcurvearechanged
Changethevalueoftheslope:
Pushthedialtoenter/changetheslopevalueoftheheatcurve (example:1.0). Whentheslopeoftheheatcurveischangedbymeansoftheslope value,thecommonpointforallheatcurveswillbeadesiredflow temperature=24.6°Catanoutdoortemperature=20°Canda desiredroomtemperature=20.0°C.
Slopechanges
Coordinatechanges
Changethecoordinates:
Pushthedialtoenter/changethecoordinatesoftheheatcurve (example:-30,75). Theheatcurverepresentsthedesiredflowtemperaturesat differentoutdoortemperaturesandatadesiredroomtemperature of20°C. Ifthedesiredroomtemperatureischanged,thedesiredflow temperaturealsochanges: (DesiredroomT-20)×HC×2.5 where"HC"istheHeatCurveslopeand"2.5"isaconstant.
AQ163786479450en-010801
Thecalculatedflowtemperaturecanbeinfluencedbythe‘Boost’and ‘Ramp’functionsetc.
Example:
Heatcurve: Desiredflowtemp.:
Desiredroomtemp.: Calculation(22–20)×1.0×2.5=
Result:
Thedesiredflowtemperaturewillbecorrectedfrom50°Cto55°C.
1.0 50°C
22°C 5
©Danfoss|2022.01|83
ECLComfort210/296/310/311,applicationkeysA230andB230
Choosingaheatcurveslope
Theheatcurvesrepresentthedesiredflowtemperatureatdifferentoutdoortemperaturesandatadesiredroomtemperatureof20°C.
Thesmallarrows()indicate6differentoutdoortemperaturevaluesatwhichyoucanchangetheheatcurve.
Thedesiredflowtemperatureissetin'Des.Tcomfort'and'Des.T saving'.Setvaluesforcomfortmodecouldforexamplebe7.5°C andforsavingmode25°C.
Alternativelythedesiredflowtemperaturecanbesetbyapplying anexternalsignal.Thechoiceissetin'Ext.signal' .
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
84|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Externalsignalfordesiredflowtemperature(A230.2,A230.4 andA230.5):
Avoltage(0-10V)canbeappliedtotheinputterminalS8inorder todeterminethedesiredflowtemperature. ThemeasuredvoltageoninputS8isconvertedtoatemperature valuebythecontroller.Whenthevoltagegetshigher,thedesired flowtemperatureincreases.
Thefollowingsettingssetupthescaling.
MENU>Settings>Flowtemperature
Ext.desiredT
CircuitSettingrange
AllRead-outonly
Theremotelysetvalueforthedesiredflowtemperatureisindicatedbythe unit°C.
Factorysetting
Pushthedialtoseethegraph.Turnthedialtoenterthedesired flowtemperaturevaluefortheinputvoltages(fixedvalues)at 1and10volt.
FactorysettingsaredifferentinA230.2,A230.4andA230.5.
Theappliedvoltagesignalmustbe1Voltasaminimum.
Example:Relationshipbetweeninputvoltageanddisplayedvalueforthe desiredflowtemperature
Desiredflowtemp.(°C)
Volt
Thisexampleshowsthat1voltcorrespondsto10.0°Cand10volt correspondto100.0°C.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
A230.2
Avalueforthedesiredflowtemperatureisindicatedonlywhen'Ext. signal’(ID11084)issettoON.
Theread-out'--'meansthat'Ext.signal'issettoOFF.
A230.4/A230.5
Avalueforthedesiredflowtemperatureisindicatedonlywhen'Input type’(ID11327)issettoON.
Theread-out'--'meansthat'Inputtype'issettoOFF .
AQ163786479450en-010801
©Danfoss|2022.01|85
ECLComfort210/296/310/311,applicationkeysA230andB230
MENU>Settings>Flowtemperature
DesiredT(Desiredflowtemperature)
WhentheECLComfortisinoverridemode,type"Const.T",thedesiredflow temperaturecanbeset. A"Const.T"relatedreturntemperaturelimitationcanalsobeset.SeeMENU >Settings>Returnlimit>'Con.T,ret.Tlim. '
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Des.TComfort
SettingofdesiredflowtemperaturewhentheECLcontrollerisincomfort mode.
1x004
Overridemode
WhenECLComfortisinScheduledmode,acontact(switch)signalcan beappliedtoaninputinordertooverridetoComfort,Saving,Frost ProtectionorConstanttemperature.Aslongasthecontact(switch) signalisapplied,theoverrideisactive.
The"DesiredT"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
1x018
Thissettinghasnoinfluenceifthecontrollerreceivesanexternalvalue forthedesiredflowtemperature.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Des.TSaving
SettingofdesiredflowtemperaturewhentheECLcontrollerisinsaving mode.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flowtemperature
Ext.signal
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thedesiredflowtemperatureissetinthecontroller. Thedesiredflowtemperatureisappliedasa0-10V
signal.
1x019
Thissettinghasnoinfluenceifthecontrollerreceivesanexternalvalue forthedesiredflowtemperature.
1x084
See'Ext.desiredT' .Thevalueisanexternallysetdesiredflow temperature.
86|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
MENU>Settings>Flowtemperature
Dewp.Toffset(Dewpointtemperature,offset)
Thevaluecalculatedbythecontrollerforthedewpointtemperaturecanbe offsetadjusted(displaced).Thedewpointtemperatureisthetemperatureat whichwaterintheaircondenses.IftheECA31isnotplacedcorrectly,itcan beusefultooffsetadjustthecalculateddewpointtemperature.
1x164
SeeAppendix“ParameterIDoverview”
Value:
Settheoffsetvalue
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
MENU>Settings>Flowtemperature
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min. ’ .
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Pressure
Seethesection"Pressuremeasuring"
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min. ’ .
AQ163786479450en-010801
©Danfoss|2022.01|87
ECLComfort210/296/310/311,applicationkeysA230andB230

5.3Roomlimit

Thissectionisonlyrelevantifyouhaveinstalledaroom temperaturesensororaRemoteControlUnit. Thecontrolleradjuststhedesiredflowtemperaturetocompensate forthedifferencebetweenthedesiredandtheactualroom temperature. Iftheroomtemperatureishigherthanthedesiredvalue,the desiredflowtemperaturecanbereduced. The'Infl.-max.'(Influence,max.roomtemp.)determineshow muchthedesiredflowtemperatureshouldbereduced. Usethisinfluencetypetoavoidatoohighroomtemperature.The controllerwillallowforfreeheatgains,i.e.solarradiationetc. Iftheroomtemperatureislowerthanthedesiredvalue,thedesired flowtemperaturecanbeincreased. The'Infl.-min.'(Influence,min.roomtemperature)determines howmuchthedesiredflowtemperatureshouldbeincreased. Usethisinfluencetoavoidatoolowroomtemperature. Atypicalsettingwillbe-4.0for'Infl.-max.'and4.0for'Infl.-min.'
Influence
‘Infl.-min.’(min.limitation)
Desiredroomtemperature Actualroomtemperature
‘Infl.-max. ’(max.limitation)
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
Example1:
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. The‘Infl.-min.’issetto3.0. Result: Thedesiredflowtemperatureisdecreasedby2x-4.0=8.0degrees.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
Example2:
Theactualroomtemperatureis3degreestoolow. The‘Infl.-max.’issetto-4.0. The‘Infl.-min.’issetto3.0. Result: Thedesiredflowtemperatureisincreasedby3x3.0=9.0degrees.
88|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
RelativeHumidityconversionsetting
MENU>Settings>Roomlimit
Humidity(Relativehumidity)
Thevalueforrelativehumidityisindicatedasa%value.
WhentheRelativeHumidity(RH)signal(0-10V)isappliedtothe inputS7,aconversionmustbemade.
Pushthedialtoseethegraphand,ifneeded,entertheRHvalues fortheinputvoltageat2.0and10.0Volt.
Fixedvoltagesettings:2.0Vand10.0V
Factorysettings:
Typically,thehigherthevoltage,thehigherthedisplayedRHvalue.
MENU>Settings>Roomlimit
(2.0,20)and(10,100).Thismeansthat theRHis20%at2.0Voltand100% at10Volt.
Adapt.time(adaptiontime)
Controlshowfasttheactualroomtemperatureadaptstothedesiredroom temperature(Icontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe'Adapt. time'.
Minor
Thedesiredroomtemperatureisadaptedquickly.
value: Major
Thedesiredroomtemperatureisadaptedslowly.
value:
MENU>Settings>Roomlimit
Dewp.Toffset(Dewpointtemperatureoffset)
Thecalculateddewpointtemperaturecanbeoffsetadjustedfor compensatingthedifferencebetweenwallandroomtemperatures. Anoffsetvalueof+6Kisanexperiencedandrecommendablevalue.
SeeAppendix“ParameterIDoverview”
1x015
Theadaptationfunctioncancorrectthedesiredroomtemperature withmax.8Kxheatcurveslopevalue.
1x164
AQ163786479450en-010801
©Danfoss|2022.01|89
ECLComfort210/296/310/311,applicationkeysA230andB230
MENU>Settings>Roomlimit
Infl.-max.(roomtemp.limitation,max.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (decreased)iftheactualroomtemperatureishigherthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
0.0:
-2.0:
-5.0:
-9.9:
Noinfluence Minorinfluence Mediuminfluence Maximuminfluence
1x182
=
X
#1#
#2#
#3#
Roomtemperature
=
Desiredroomtemperature
=
Negativeinfluence(1x082)whenactualroomtemp.getshigher thandesiredroomtemp.
=
Positiveinfluence(1x083)whenactualroomtemp.getslowerthan desiredroomtemp.
The‘Infl.-max.’and'Infl.-min. 'determinehowmuchtheroom temperatureshouldinfluencethedesiredflowtemperature.
Ifthe‘Infl. ’factoristoohighand/orthe‘ Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Theactualroomtemperatureis2degreestoohigh. The‘Infl.-max.’issetto-4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x-4.0x1.8) –14.4degrees.
MENU>Settings>Roomlimit
Infl.-min.(roomtemp.limitation,min.)
Determineshowmuchthedesiredflowtemperaturewillbeinfluenced (increased)iftheactualroomtemperatureislowerthanthedesiredroom temperature(Pcontrol).
SeeAppendix“ParameterIDoverview”
9.9:
5.0:
2.0:
0.0:
Maximuminfluence Mediuminfluence Minorinfluence Noinfluence
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x-4.0x1): –8.0degrees.
Example
1x183
Theactualroomtemperatureis2degreestoolow. The‘Infl.-min.’issetto4.0. Theheatcurveslopeis1.8(see'Heatcurve'in'Flowtemperature'). Result: Thedesiredflowtemperatureischangedby(2x4.0x1.8)
14.4degrees.
Inapplicationsubtypes,whereaheatcurveslopevalueisnotpresent, theheatcurveslopevalueissetto1:
Result: Thedesiredflowtemperatureischangedby(2x4.0x1):
8.0degrees.
90|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

5.4Returnlimit

A230.1,A230.3,A230.4,A230.5
Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
ApplicationA230.2:
Thereturntemperaturelimitationisbasedonaselectable temperaturevalue.Thecontrollerautomaticallychanges thedesiredflowtemperaturetoobtainanacceptablereturn temperaturewhenthereturntemperaturefallsbeloworgets higherthanthesetlimit.
ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Typicalforcoolingsystemsisthatthereturntemperaturemustbe ashighaspossible.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
Desiredflowtemperature
Returntemp.
Limit
AQ163786479450en-010801
©Danfoss|2022.01|91
ECLComfort210/296/310/311,applicationkeysA230andB230
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
T
Y
X
#1#
#2#
#3#
#4#
=
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
92|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
T
Y
X
#1#
#2#
#3#
#4#
=
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
Con.T,re.Tlim.(Constanttemperaturemode,return temperaturelimitation)
The"Con.T ,ret.Tlimit"isthereturntemperaturelimitationvaluewhenthe circuitissettooverridemodetype"Const.T"(=Constanttemperature).
SeeAppendix“ParameterIDoverview”
Value:Setthereturntemperaturelimitation
1x028
AQ163786479450en-010801
©Danfoss|2022.01|93
ECLComfort210/296/310/311,applicationkeysA230andB230
MENU>Settings>Returnlimit
DHW,ret.Tlimit
WhenanaddressedslaveisactiveinDHW-tankheating/charging,the returntemperaturelimitationinthemastercanbeset. Notes:
Themastercircuitmustbesettoreactonthedesiredflowtemperature intheslave(s).See"Demandoffset"(ID11017).
Theslave(s)mustbesettosendits/theirdesiredflowtemperatureto themaster.See"SenddesiredT"(ID1x500).
SeeAppendix“ParameterIDoverview”
OFF:
Noinfluencefromslaves.Thereturntemperature limitationisrelatedtosettingsin"Returnlimit" .
Value:Returntemperaturelimitationvaluewhenslaveisin
DHWtankheating/chargingoperation.
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x029
#1#=Master,exampleA266,address15 #2#=Slave,exampleA237,address9 #3#=Slave,exampleA367,address6
SomeexamplesofapplicationswithDHW-tankheating/chargingare:
•A217,A237,A247,A367,A377
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe setvalue,thecontrollerautomaticallychangesthedesiredflow/ ducttemperaturetoobtainanacceptablereturntemperature.The influenceissetin'Infl.-max. 'and'Infl.-min.'.
MENU>Settings>Returnlimit
HighToutX1(returntemp.limitation,highlimit,X-axis)
Settheoutdoortemperaturevalueforthelowreturntemperaturelimitation.
1x031
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'LowlimitY1' .
MENU>Settings>Returnlimit
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'HighToutX1' .
1x032
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'HighToutX1' .
94|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
MENU>Settings>Returnlimit
LowToutX2(returntemp.limitation,lowlimit,X-axis)
Settheoutdoortemperaturevalueforthehighreturntemperature limitation.
SeeAppendix“ParameterIDoverview”
ThecorrespondingYcoordinateissetin'HighlimitY2'.
MENU>Settings>Returnlimit
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
Setthereturntemperaturelimitationreferringtotheoutdoortemperature valuesetin'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthesetlimit.
SeeAppendix“ParameterIDoverview”
1x033
1x034
Example
1x035
Thereturnlimitisactiveabove50°C. Theinfluenceissetto0.5. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby0.5x2=1.0degree.
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthesetlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthesetlimit.
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Example
1x036
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
AQ163786479450en-010801
©Danfoss|2022.01|95
ECLComfort210/296/310/311,applicationkeysA230andB230
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x037
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
1x085
96|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230

5.5Flow/powerlimit

Heatingcircuit
A230.1,A230.2,A230.4
AfloworenergymetercanbeconnectedtotheECLcontrollerin ordertolimitthefloworconsumedpower.Thesignalfromthe floworenergymeterisapulsesignal. Alternatively,thefloworpowersignalcancomefromanM-Bus connectedmeter.
A230.3andA230.5
FloworpowerlimitationonlyviaM-Bus.
WhentheapplicationrunsinanECLComfort296/310/311 controller,theflow/powersignalcanbeobtainedfromaflow /energymeterviatheM-busconnection.
Theflow/powerlimitationcanbebasedontheoutdoor temperature.Typically,indistrictheatingsystemsahigherflowor powerisacceptedatloweroutdoortemperatures.
Therelationshipbetweenthefloworpowerlimitsandtheoutdoor temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .
Thefloworpowercoordinatesaresetin'LowlimitY1'and'High limitY2' .Basedonthesesettings,thecontrollercalculatesthe limitationvalue.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyreducesthedesiredflowtemperaturetoobtain anacceptablemax.floworpowerconsumption.
X
Y
#X1#
#X2#
#Y1#
#Y2#
X
Y
#1#
#2#
#3#
=
Outdoortemperature
=
Limitation,floworpower
=
HighTout(1x119)
=
LowTout(1x118)
=
Lowlimit(1x117)
=
Highlimit(1x116)
=
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
AQ163786479450en-010801
©Danfoss|2022.01|97
ECLComfort210/296/310/311,applicationkeysA230andB230
Coolingcircuit
AfloworenergymetercanbeconnectedtotheECLcontrollerin ordertolimitthefloworconsumedpower.Thesignalfromthe floworenergymeterisapulsesignal.
WhentheapplicationrunsinanECLComfort296/310/311 controller,theflow/powersignalcanbeobtainedfromaflow /energymeterviatheM-busconnection.
Whentheflow/powergetshigherthanthecalculatedlimit,the controllergraduallyincreasesthedesiredflowtemperatureto obtainanacceptablemax.floworpowerconsumption.
X
Y
#1#
#2#
#3#
=
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
Theparameter'Units'(ID1x115)hasareducedsettingrangewhen theflow/energysignalcomesviaM-bus.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flow/powerlimit
Inputtype
Choiceofinputtypefromflow/energymeter
Pulsebasedsignalforflow/power ,appliedtoinputS7
Formonitoring: Frequencyrangeis0.01-200Hz
Forlimitation: Minimumfrequencyisrecommendedtobe1Hzinordertohavea
stablecontrol.Furthermore,thepulsesmustappearregularly.
1x109
ThesettingrangeforIMandEMdependsonchosensubtype.
SeeAppendix“ParameterIDoverview”
OFF:
IM1-
Noinput
Flow/energymetersignalbasedonpulses.
IM5: EM1-
Flow/energymetersignalfromM-bus.
EM5:
98|©Danfoss|2022.01
AQ163786479450en-010801
ECLComfort210/296/310/311,applicationkeysA230andB230
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
MENU>Settings>Flow/powerlimit
1x111
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Pulse
Setthevalueofthepulsesfromtheflow/energymeter.
SeeAppendix“ParameterIDoverview”
OFF:
1...9999:
Noinput.
Pulsevalue.
1x113
Example:
1x114
Onepulsecanrepresentanumberoflitres(fromaflowmeter) oranumberofkWh(fromaenergymeter).
AQ163786479450en-010801
©Danfoss|2022.01|99
ECLComfort210/296/310/311,applicationkeysA230andB230
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Unitstotheleft:pulsevalue. Unitstotheright:actualandlimitationvalues.
Thevaluefromtheflowmeterisexpressedasmlorl. ThevaluefromtheenergymeterisexpressedasWh,kWh,MWh orGWh.
Thevaluesfortheactualflowandtheflowlimitationareexpressed asl/horm³/h.
Thevaluesfortheactualpowerandthepowerlimitationare expressedaskW,MWorGW.
1x115
Listforsettingrangeof'Units': ml,l/h l,l/h ml,m³/h l,m³/h Wh,kW kWh,kW kWh,MW MWh,MW MWh,GW GWh,GW
Example1:
'Units'(11115):
'Pulse'(11114):
l,m³/h 10
Eachpulserepresents10litresandtheflowisexpressedascubic meters(m³)perhour.
Example2:
'Units'(11115):
'Pulse'(11114):
kWh,kW(=kiloWatthour,kiloWatt) 1
Eachpulserepresents1kiloWatthourandthepoweris expressedinkiloWatt.
MENU>Settings>Flow/powerlimit
HighlimitY2(flow/powerlimitation,highlimit,Y-axis)
Settheflow/powerlimitationreferringtotheoutdoortemperatureset in'LowToutX2' .
SeeAppendix“ParameterIDoverview”
ThecorrespondingXcoordinateissetin'LowToutX2' .
Listforsettingrangeof'Units'whenM-busconnectiontoflowor energymeter:
l/h m³/h kW MW GW
1x116
100|©Danfoss|2022.01
AQ163786479450en-010801
Loading...