Danfoss A214, A314 Operating guide

OperatingGuide
ECLComfort210/296/310,applicationA214/A314

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................25
2.4Placingthetemperaturesensors................................60
2.5Electricalconnections.............................................62
2.6InsertingtheECLApplicationKey..............................80
2.7Checklist............................................................87
2.8Navigation,ECLApplicationKeyA214/A314................88
3.0Dailyuse.......................................................106
3.1Howtonavigate.................................................106
3.2Understandingthecontrollerdisplay........................107
3.3Ageneraloverview:Whatdothesymbols
mean?..............................................................110
3.4Monitoringtemperaturesandsystem
components......................................................111
3.5Influenceoverview..............................................112
3.6Manualcontrol...................................................113
3.7Schedule..........................................................115
4.0Settingsoverview..........................................116
5.0Settings.........................................................119
5.1IntroductiontoSettings........................................119
5.2Flowtemperature/Inlettemperature.......................120
5.3DuctTlimit/Roomlimit........................................122
5.4Returnlimit.......................................................124
5.5LimitTsafety.....................................................126
5.6Compensation1.................................................127
5.7Compensation2.................................................129
5.8Controlparameters..............................................131
5.9Fan/acc.control(fan/accessorycontrol)..................140
5.10Application.......................................................147
5.11Alarm..............................................................161
6.0Commoncontrollersettings............................167
6.1Introductionto‘Commoncontrollersettings’..............167
6.2Time&Date.......................................................168
6.3Holiday............................................................169
6.4Inputoverview...................................................171
6.5Log.................................................................172
6.6Outputoverride..................................................173
6.7Keyfunctions.....................................................174
6.8System.............................................................176
7.0Miscellaneous................................................183
7.1ECA30/31setupprocedures.................................183
7.2Severalcontrollersinthesamesystem......................191
7.3Frequentlyaskedquestions....................................194
7.4Definitions........................................................196
7.5Type(ID6001),overview.......................................200
7.6Automatic/manualupdateoffirmware.....................201
7.7ParameterIDoverview..........................................202
©Danfoss|2021.06AQ146286475947en-010601|1
OperatingGuideECLComfort210/296/310,applicationA214/A314

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA214 (ordercodeno.087H3811).
TheECLApplicationKeyA214containsthesubtypes:
A214.1…A214.6(applicableinECLComfort210,296and310) A314.1…A314.7(applicableinECLComfort310) A314.9(applicableinECLComfort310)
A214.1iscoolingrelatedapplication A214.2,A214.3andA214.6areheatingrelatedapplications A214.4andA214.5arebasicheating/coolingapplications
A314.1andA314.2arebasicheating/coolingapplications A314.3isaspecialheatingapplication A314.4andA314.5areadvancedheatingapplications A314.6andA314.7areadvancedheating/coolingapplications A314.9isanadvancedheatingapplication
ThedescribedfunctionsarerealizedinECLComfort210forbasic solutionsandinECLComfort310foradvancedsolutions,e.g. M-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA214complieswithECLComfort210and ECLComfort310controllersasofsoftwareversion1.11(visible atstart-upofthecontrollerandin‘Commoncontrollersettings’ in‘System’).
ARemoteControlUnit,ECA30orECA31,canbeconnectedand thebuilt-inroomtemperaturesensorcanbeutilized.
TheapplicationsA314.1…A314.7andA314.9workwiththe InternalI/OmoduleECA32(ordercodeno.087H3202). ECA32isplacedinthebasepartforECLComfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby meansoftheremotecontrolunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volta.c.(087H3240)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210,296and310, modulesandaccessoriesisavailableonhttp://danfoss.com/or http://store.danfoss.com/.
2|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
AQ146286475947en-010601
©Danfoss|2021.06|3
OperatingGuideECLComfort210/296/310,applicationA214/A314
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
1
-
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
2
Circuit2Parameterno.
174
4|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314

2.0Installation

2.1Beforeyoustart

TheApplicationKeyA214containsseveralapplications,mainly relatedtoventilationsystemswithheatingorcoolingora combinationofthese.TheapplicationsintheA214keyofferawide rangeofpossibilities(seetheexamples).
TheapplicationA214.1isveryflexible.Thesearethebasic principles:
Coolingwithroomtemperaturecontrol:
Typically,theairducttemperatureisadjustedaccordingtoyour requirements.TheairducttemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM2(controllingthecoolingtransfer)is openedgraduallywhentheducttemperatureishigherthanthe desiredducttemperatureandviceversa.
Roomtemperature:
Ifthemeasuredroomtemperature(S4orECA30)doesnotequal thedesiredroomtemperature,thedesiredtemperatureatS3can beadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the coolingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredroomtemperature).
Thedesiredroomtemperaturedeterminesacorrectionofthe desiredtemperatureatS3.
Iftheroomtemperatureisnotmeasured,thedesiredroom temperatureequals(willbe)thedesiredtemperatureatS3.Inthis case,thesettingofthe'Balancetemperature'isnotconsidered(or: hasnoinfluence).
Thefan(F1)isON/OFFcontrolledaccordingtothescheduleand coolingdemand.Thedamper(P2)isON/OFFcontrolledaccording toschedule.Thecirculationpump(X3)isON/OFFcontrolled accordingtocoolingdemand.
Returntemperature(optional):
Ifthemeasuredreturntemperature(S5)doesnotequalthe limitationvalue(typically,thereturntemperaturebecomeslower thanthelimitationvalue),thedesiredtemperatureatS3canbe adjusted(typicallytoahighervalue).Thisresultsinagradual closingofthemotorizedcontrolvalve.
TypicalA214.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
S2
S3Ducttemperaturesensor
S4
S5
S8
F1
P2
X3
M2
A1
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
(Optional)Compensationtemperaturesensor(not illustrated)
(Optional)Roomtemperaturesensor*
(Optional)Returntemperaturesensor
(Optional)Firethermostat
Fan(ON/OFF)
Damper(ON/OFF)
Circulationpump(ON/OFF)
Motorizedcontrolvalve,cooling(3-point controlled)
Alarm
*Alternative:ECA30
Asimplefrostprotection(viaS5)canbeestablished.Furthermore, itisexpectedthatthecoolingexchanger(fancoil)circuitcontains brine.
Foradescriptionofalarmsandcompensationtemperature,please readthesection‘A214andA314ingeneral’ .
AQ146286475947en-010601
©Danfoss|2021.06|5
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationsA214.2andA214.3areveryflexibleandalmost identical.Thesearethebasicprinciples:
A214.2:Heatingwithducttemperaturecontrol A214.3:Heatingwithroomtemperaturecontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour requirements.ThetemperaturesensorS3isthemostimportant sensor.ThedesiredtemperatureatS3issetintheECLComfort controllerasthe'Desiredbalancetemperature' .
ThemotorizedcontrolvalveM1(controllingtheheatingsupply temperature)isopenedgraduallywhentheS3temperatureis lowerthanthedesiredS3temperatureandviceversa.
S4temperature: IfthemeasuredS4temperaturedoesnotequalthedesiredS4 temperature,thedesiredtemperatureatS3canbeadjusted. Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredS4temperature).ThedesiredS4 temperaturedeterminesacorrectionofthedesiredtemperature atS3.
Thefan(F1)isON/OFFcontrolledaccordingtothescheduleand heatingdemand.Thedamper(P2)isON/OFFcontrolledaccording toschedule.Thecirculationpump(X3)isON/OFFcontrolled accordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
TypicalA214.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
S2
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
(Optional)Compensationtemperaturesensor(not illustrated)
S3
Flowtemperaturesensor
S4Ducttemperaturesensor
S5
S6
S7
S8
F1
P2
X3
M1
A1
(Optional)Returntemperaturesensor
(Optional)Frosttemperaturesensor
(Optional)Frostthermostat
(Optional)Firethermostat
Fan(ON/OFF)
Damper(ON/OFF)
Circulationpump(ON/OFF)
Motorizedcontrolvalve,heating(3-pointcontrolled)
Alarm
6|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
TypicalA214.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
S2
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
(Optional)Compensationtemperaturesensor(not illustrated)
S3Ducttemperaturesensor
S4
S5
S6
S7
S8
F1
P2
X3
M1
A1
Roomtemperaturesensor*
(Optional)Returntemperaturesensor
(Optional)Frosttemperaturesensor
(Optional)Frostthermostat
(Optional)Firethermostat
Fan(ON/OFF)
Damper(ON/OFF)
Circulationpump(ON/OFF)
Motorizedcontrolvalve,heating(3-pointcontrolled)
Alarm
*Alternative:ECA30
AQ146286475947en-010601
©Danfoss|2021.06|7
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.4isveryflexible.Thesearethebasic principles:
Heating/coolingwithairducttemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording toyourrequirements.
TheflowtemperaturesensorS3intheheatingcircuitisthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheflowtemperatureis lowerthanthedesiredbalancetemperatureandviceversa.
Atcooling,themotorizedcontrolvalveM2controlsthecooling temperatureatS4.
Airducttemperature: AtoolowairducttemperatureS4willactivatetheheatingcircuit M1,whereasatoohighairducttemperaturewillactivatethe coolingcircuitM2.
Atheatingdemand,theairducttemperatureS4canadjustthe desiredtemperatureatS3.Atcoolingdemand,theairduct temperatureS4iscontrolledaccordingtothedesiredairduct temperature.A"Deadzone"(=numberofdegrees)canbeset inordertoavoidunstableshiftsbetweenheatingandcooling operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heating/coolingcircuitcanbein‘Comfort’or‘Saving’mode(two differenttemperaturevaluesfordesiredairducttemperature).
In'Saving'modethedesiredairducttemperaturedeterminesa correctionofthedesiredtemperatureatS3inheatingmode.In coolingmodethecoolingisOFFduring'Saving' .
ThefanF1isON/OFFcontrolledaccordingtothescheduleand heating/coolingdemand.ThedamperP2isON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
TypicalA214.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
S2
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
(Optional)Compensationtemperaturesensor(not illustrated)
S3
S4
S5
S6
S7
S8
F1
P2
X3
M1
Heatingtemperaturesensor
Airducttemperaturesensor
(Optional)Returntemperaturesensor
(Optional)Frosttemperaturesensor
(Optional)Frostthermostat
(Optional)Firethermostat
Fan(ON/OFF)
Damper(ON/OFF)
Circulationpump,heating(ON/OFF)
Motorizedcontrolvalve,heating(3-point controlled)
M2
A1
Motorizedcontrolvalve,cooling(3-pointcontrolled)
Alarm
8|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.5isveryflexible.Thesearethebasic principles:
Heating/coolingwithroomtemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording toyourrequirements. ThetemperaturesensorS3intheairductisthemostimportant sensor.ThedesiredtemperatureatS3issetintheECLComfort controllerasthe'Desiredbalancetemperature' .
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheairducttemperatureis lowerthanthedesiredbalancetemperatureandviceversa. Atcooling,themotorizedcontrolvalveM2controlsthecooling temperature.
Roomtemperature: AtoolowroomtemperatureS4willactivatetheheatingcircuitM1, whereasatoohighroomtemperaturewillactivatethecooling circuitM2.A"Deadzone"(=numberofdegrees)canbesetinorder toavoidunstableshiftsbetweenheatingandcoolingoperation.
Atheating/coolingdemand,theroomtemperatureS4canadjust thedesiredtemperatureatS3.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heating/coolingcircuitcanbein‘Comfort’or‘Saving’mode(two differenttemperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa correctionofthedesiredtemperatureatS3inheatingmode.In coolingmodethecoolingisOFFduring'Saving' .
ThefanF1isON/OFFcontrolledaccordingtothescheduleand heating/coolingdemand.ThedamperP2isON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
TypicalA214.5application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
S2
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
(Optional)Compensationtemperaturesensor(not illustrated)
S3Ducttemperaturesensor
S4
S5
S6
S7
S8
F1
P2
X3
M1
M2
A1
Roomtemperaturesensor*
(Optional)Returntemperaturesensor
(Optional)Frosttemperaturesensor
(Optional)Frostthermostat
(Optional)Firethermostat
Fan(ON/OFF)
Damper(ON/OFF)
Circulationpump,heating(ON/OFF)
Motorizedcontrolvalve,heating(3-pointcontrolled)
Motorizedcontrolvalve,cooling(3-pointcontrolled)
Alarm
*Alternative:ECA30
AQ146286475947en-010601
©Danfoss|2021.06|9
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.6isveryflexible.Thesearethebasic principles:
Heatingwithroomtemperaturecontrol:
Typically,theflowtemperatureisadjustedaccordingtoyour requirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredbalancetemperature'. ThemotorizedcontrolvalveM1isopenedgraduallywhenthe flowtemperatureislowerthanthedesiredflowtemperatureand viceversa.
Roomtemperature: Ifthemeasuredroomtemperature(S4orECA30)doesnotequal thedesiredroomtemperature,thedesiredtemperatureatS3can beadjusted. Bymeansofaweekschedule(upto3‘Comfort’periods/day), theheatingcircuitcanbein‘Comfort’or‘Saving’mode(two differenttemperaturevaluesfordesiredroomtemperature).The desiredroomtemperaturedeterminesacorrectionofthedesired temperatureatS3.
Thecirculationpump(F1)isON/OFFcontrolledaccordingtothe Schedule1.Theaccessory(P2)isON/OFFcontrolledaccording toSchedule1or2.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5),frostprotection(S6andS7)andfire alarmpleasereadthesection‘A214andA314ingeneral’ .
TypicalA214.6application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
S1
S2
S3
S4
S5
S6
S7
S8
F1
P2
X3
M1
A1
ElectroniccontrollerECLComfort210or310
Outdoortemperaturesensor
(Optional)Compensationtemperaturesensor
Flowtemperaturesensor
Roomtemperaturesensor*
(Optional)Returntemperaturesensor
(Optional)Frosttemperaturesensor(notillustrated)
(Optional)Frostthermostat(notillustrated)
(Optional)Firethermostat(notillustrated)
Circulationpump(ON/OFF)
Accessoryoutput(ON/OFF)
Optionaloutput(ON/OFF)
Motorizedcontrolvalve,heating(3-pointcontrolled)
Alarm
*Alternative:ECA30
10|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.1isveryflexible.Thesearethebasic principles:
Heatingand(passive)coolingwithairducttemperature control
Typically,theheating/coolingtemperatureisadjustedaccording toyourrequirements.TheflowtemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheflowtemperatureis lowerthanthedesiredtemperatureandviceversa.Atcooling, themotorizeddamperM2controlsthecoolingtemperature.The coolingsectioncanbepassive(re-circulation)oractive.
Airducttemperature: AtoolowtemperatureatS4willactivatetheheatingcircuit(M1), whereasatoohighducttemperaturewillactivatethecooling circuit(M2).
Atheatingdemand,thetemperatureatS4canadjustthedesired temperatureatS3.Atcoolingdemand,theS4temperatureis controlledaccordingtothedesiredS4temperature.A"Deadzone" (=numberofdegrees)canbesetinordertoavoidunstableshifts betweenheatingandcoolingoperation.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heating/coolingcircuitcanbein‘Comfort’or‘Saving’mode(two differenttemperaturevaluesfordesiredairducttemperature).
In'Saving'modethedesiredairducttemperaturedeterminesa correctionofthedesiredtemperatureatS3inheatingmode.In coolingmodethecoolingisOFFduring'Saving' .
ThefanF1isON/OFFcontrolledaccordingtothescheduleand heating/coolingdemand.ThedamperP2isON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
TypicalA314.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
S1
S2
S3
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
(Optional)Compensationtemperaturesensor
Flowtemperaturesensor
S4Ducttemperaturesensor
S5
S6
S7
S8
F1
P2
X3
M1
M2
A1
(Optional)Returntemperaturesensor
(Optional)Frosttemperaturesensor
(Optional)Frostthermostat
(Optional)Firethermostat
Fan(ON/OFF)
Damper(ON/OFF)
Circulationpump,heating(ON/OFF)
Motorizedcontrolvalve,heating(3-pointcontrolled)
Motorizeddamper(0-10voltcontrolled)
Alarm
AQ146286475947en-010601
©Danfoss|2021.06|11
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.2isveryflexible.Thesearethebasic principles:
Heatingand(passive)coolingwithroomtemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording toyourrequirements.TheairducttemperaturesensorS3isthe mostimportantsensor.ThedesiredtemperatureatS3issetinthe ECLComfortcontrollerasthe'Desiredbalancetemperature' .
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheairducttemperature islowerthanthedesiredtemperatureandviceversa.Atcooling, themotorizeddamperM2controlsthecoolingtemperature.The coolingsectioncanbepassive(re-circulation)oractive.
Roomtemperature: AtoolowtemperatureatS4willactivatetheheatingcircuit(M1), whereasatoohighducttemperaturewillactivatethecooling circuit(M2).A"Deadzone"(=numberofdegrees)canbeset inordertoavoidunstableshiftsbetweenheatingandcooling operation.
Atheating/coolingdemand,thetemperatureatS4canadjust thedesiredtemperatureatS3.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heating/coolingcircuitcanbein‘Comfort’or‘Saving’mode(two differenttemperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa correctionofthedesiredtemperatureatS3inheatingmode.In coolingmodethecoolingisOFFduring'Saving' .
ThefanF1isON/OFFcontrolledaccordingtothescheduleand heating/coolingdemand.ThedamperP2isON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
TypicalA314.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
S1
S2
ElectroniccontrollerECLComfort310
Built-inextensionmodule
Outdoortemperaturesensor
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
S5
S6
S7
S8
F1
P2
X3
M1
M2
A1
Roomtemperaturesensor*
(Optional)Returntemperaturesensor
(Optional)Frosttemperaturesensor
(Optional)Frostthermostat
(Optional)Firethermostat
Fan(ON/OFF)
Damper(ON/OFF)
Circulationpump,heating(ON/OFF)
Motorizedcontrolvalve,heating(3-pointcontrolled)
Motorizeddamper(0-10voltcontrolled)
Alarm
*Alternative:ECA30
12|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.3isveryflexible.Thesearethebasic principles:
Heatingwithroomtemperaturecontrol
Typically,theairducttemperatureisadjustedaccordingtoyour requirements.TheairducttemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheairductemperatureis lowerthanthedesiredairducttemperatureandviceversa.
Roomtemperature: Iftheroomtemperature(S4orECA30)doesnotequalthedesired roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa correctionofthedesiredtemperatureatS3.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand heatingdemand.ThedamperP2isON/OFFcontrolledaccording toschedule.ThecirculationpumpX3isON/OFFcontrolled accordingtoheatingdemand.
Variablefanspeed(optional): ThefanV1canbespeedcontrolledinrelationtothemeasured windspeedS10.Thefanspeedcontrolsignalisa0–10voltsignal, generatedbytheinternalinput/outputmoduleECA32.Amenu intheECLComfort310containssettingsforrelationshipbetween actualwindspeedanddesiredfanspeed.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
TypicalA314.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S10
Windspeedsignal(0-10volt)
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizeddamper(0-10voltcontrolled)
V1
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
AQ146286475947en-010601
©Danfoss|2021.06|13
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.4isveryflexible.These arethebasicprinciples:
Heatingwithroomtemperatureandairpressurecontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour requirements.TheairducttemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredinlettemperature' .
Therecoverycircuit,controlledbyM2,isconsideredasthemain circuit,whereastheheatingcircuit,controlledbyM1,isthe supplementarycircuit.
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheS3temperatureis lowerthanthedesiredS3temperatureandviceversa.
Roomtemperature: Iftheroomtemperature(S4orECA30)doesnotequalthedesired roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredinlettemperatureandtwodifferent temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule andheatingdemand.AdamperP2canbeON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Airpressurecontrol: ThefansV2andV3arespeedcontrolledindividuallyinrelationto desiredpressures(Pascal)atS11andS12.ThesignalsatS11and S12aremeasuredas0-10voltandconvertedintoPascalintheECL Comfort310.Furthermore,thespeedofthefanscanbeloweredat loweroutdoortemperaturesinordertoreducecoldairinlet.
Heatrecovery: Inordertoutilizeheatfromtheexitairduct,arotating heat-exchanger,acrossheat-exchangerorafluidbatterycan becontrolledbyM2.BasedontheoutdoortemperatureS1,the entryducttemperatureS13andtheexitducttemperatureS14the recoveryefficiency(in%)canbeindicated.
Nightcooling: DuringSavingmodeapassivecooling(settingthefansON)canbe arranged,mainlyunderthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom temperature
outdoortemperatureislowerthantheroomtemperature
TypicalA314.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
ElectroniccontrollerECLComfort310 Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor S3Ducttemperaturesensor S4
Roomtemperaturesensor* S5
(Optional)Returntemperaturesensor S6
(Optional)Frosttemperaturesensor S7
(Optional)Frostthermostat S8
(Optional)Firethermostat
Fanmonitor
S9
S10
Filtermonitor
S11
Inletpressuresensor
S12
Outletpressuresensor
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor F1
Fan(ON/OFF) P2
Damper(ON/OFF) X3
Circulationpump,heating(ON/OFF) X4
Schedule3 P7
Recoverycircuitpump,ON/OFF ,(notillustrated) P8
Nightdamper,ON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled) V2
Fanspeed(0-10voltcontrolled) V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
14|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heatingwithroomtemperatureandairpressurecontrol (continued)
Ventilationduringsavingperiod: Adesiredreducedpressurecanbeset.
Roomtemperaturesignalmustbepresent
ThenightdamperP8willopen
ThefanV2willoperateatreducedspeed
ThefanV3isOFF
P2isOFF
M2isOFF
Summercut-out: Whenoutdoortemperatureexceedsaselectablevalue,theheating systemclosestotally.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
AQ146286475947en-010601
©Danfoss|2021.06|15
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.5isveryflexible.These arethebasicprinciples:
Heatingwithroomtemperatureandairqualitycontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour requirements.TheairducttemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredinlettemperature' .
Therecoverycircuit,controlledbyM2,isconsideredasthemain circuit,whereastheheatingcircuit,controlledbyM1,isthe supplementarycircuit.
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheS3temperatureis lowerthanthedesiredS3temperatureandviceversa.
Roomtemperature: Iftheroomtemperature(S4orECA30)doesnotequalthedesired roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredinlettemperatureandtwodifferent temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule andheatingdemand.AdamperP2canbeON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Airqualitycontrol(CO2measuredin"ppm"): ThefansV2andV3areincreasedinspeedwhentheppmvalue(0­10voltsignalmeasuredbyS11)exceedsaselectablelimit.Speed relationbetweenV2andV3canbeset.Asanalternative,theS11 signalcanexpressanRHsignal(RelativeHumidity).
Heatrecovery: Inordertoutilizeheatfromtheexitairduct,arotating heat-exchanger,acrossheat-exchangerorafluidbatterycan becontrolledbyM2.BasedontheoutdoortemperatureS1,the entryducttemperatureS13andtheexitducttemperatureS14the recoveryefficiency(in%)canbeindicated.
Nightcooling: DuringSavingmodeapassivecoolingcanbearranged,mainly underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom temperature
outdoortemperatureislowerthantheroomtemperature
TypicalA314.5application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
ElectroniccontrollerECLComfort310 Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor S3Ducttemperaturesensor S4
Roomtemperaturesensor* S5
(Optional)Returntemperaturesensor S6
(Optional)Frosttemperaturesensor S7
(Optional)Frostthermostat S8
(Optional)Firethermostat
Fanmonitor
S9
S10
Filtermonitor
S11
Airquality(CO2)signal(ppm).Alternative:Relative
Humiditysignal.
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
P7
Recoverycircuitpump,ON/OFF ,(notillustrated)
P8
Nightdamper,ON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
16|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heatingwithroomtemperatureandairqualitycontrol (continued)
Ventilationduringsavingperiod: Adesiredfanspeedcanbeset.
Roomtemperaturesignalmustbepresent
ThenightdamperP8willopen
ThefanV2willoperateatreducedspeed
ThefanV3isOFF
P2isOFF
M2isOFF
Summercut-out: Whenoutdoortemperatureexceedsaselectablevalue,theheating systemclosestotally.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
AQ146286475947en-010601
©Danfoss|2021.06|17
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.6isveryflexible.These arethebasicprinciples:
Heating/coolingwithroomtemperatureandairpressure control
Typically,theheatingtemperatureisadjustedaccordingtoyour requirements.TheairducttemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredinlettemperature' .
Therecoverycircuit,controlledbyM2,isconsideredasthemain circuit,whereastheheatingcircuit(controlledbyM1)andthe coolingcircuit(controlledbyM3)arethesupplementarycircuits.
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheairducttemperatureis lowerthanthedesiredinlettemperatureandviceversa. Atcooling,themotorizedcontrolvalveM3controlsthecooling temperature.
Roomtemperature: Iftheroomtemperature(S4orECA30)doesnotequalthedesired roomtemperature,thedesiredtemperatureatS3canbeadjusted.
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1), whereasatoohighairducttemperaturewillactivatethecooling circuit(M3).A"Deadzone"(=numberofdegrees)canbeset inordertoavoidunstableshiftsbetweenheatingandcooling operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heating/coolingcircuitcanbein‘Comfort’or‘Saving’mode(two differenttemperaturevaluesfordesiredinlettemperatureandtwo differenttemperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule andheatingdemand.AdamperP2canbeON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Airpressurecontrol: ThefansV2andV3arespeedcontrolledindividuallyinrelationto desiredpressures(Pascal)atS11andS12.ThesignalsatS11and S12aremeasuredas0-10voltandconvertedintoPascalinthe ECLComfort310.
Heatrecovery: Inordertoutilizeheatfromtheexitairduct,arotating heat-exchanger,acrossheat-exchangerorafluidbatterycan becontrolledbyM2.BasedontheoutdoortemperatureS1,the entryducttemperatureS13andtheexitducttemperatureS14the recoveryefficiency(in%)canbeindicated.
Nightcooling: DuringSavingmodeapassivecoolingcanbearranged,mainly underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom temperature
outdoortemperatureislowerthantheroomtemperature
schedule3isinComfortmode
TypicalA314.6application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
ElectroniccontrollerECLComfort310
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
Fanmonitor
S9
S10
Filtermonitor
S11
Inletpressuresensor
S12
Outletpressuresensor
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
X5
Circulationpump,cooling(ON/OFF)
P7
Recoverycircuitpump,ON/OFF ,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
M3
Motorizedcontrolvalve,cooling(3-pointcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
18|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heating/coolingwithroomtemperatureandairpressure control(continued)
M1andM3are3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
AQ146286475947en-010601
©Danfoss|2021.06|19
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.7isveryflexible.These arethebasicprinciples:
Heating/coolingwithroomtemperatureandairquality control
Typically,theheatingtemperatureisadjustedaccordingtoyour requirements.TheairducttemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredinlettemperature' .
Therecoverycircuit,controlledbyM2,isconsideredasthemain circuit,whereastheheatingcircuit(controlledbyM1)andthe coolingcircuit(controlledbyM3)arethesupplementarycircuits.
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheS3temperatureis lowerthanthedesiredS3temperatureandviceversa. Atcooling,themotorizedcontrolvalveM3controlsthecooling temperature.
Roomtemperature: Iftheroomtemperature(S4orECA30)doesnotequalthedesired roomtemperature,thedesiredtemperatureatS3canbeadjusted.
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1), whereasatoohighairducttemperaturewillactivatethecooling circuit(M3).A"Deadzone"(=numberofdegrees)canbeset inordertoavoidunstableshiftsbetweenheatingandcooling operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredinlettemperatureandtwodifferent temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule andheatingdemand.AdamperP2canbeON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Airqualitycontrol(CO2measuredin"ppm"): ThefansV2andV3areincreasedinspeedwhentheppmvalue(0­10voltsignalmeasuredbyS11)exceedsaselectablelimit.Speed relationbetweenV2andV3canbeset.Asanalternative,theS11 signalcanexpressanRHsignal(RelativeHumidity).
Heatrecovery: Inordertoutilizeheatfromtheexitairduct,arotating heat-exchanger,acrossheat-exchangerorafluidbatterycan becontrolledbyM2.BasedontheoutdoortemperatureS1,the entryducttemperatureS13andtheexitducttemperatureS14the recoveryefficiency(in%)canbeindicated.
Nightcooling: DuringSavingmodeapassivecoolingcanbearranged,mainly underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom temperature
outdoortemperatureislowerthantheroomtemperature
schedule3isinComfortmode
TypicalA314.7application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
ElectroniccontrollerECLComfort310 Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
Fanmonitor
S9
S10
Filtermonitor
S11
Airquality(CO2)signal(ppm).Alternative:Relative Humiditysignal
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
X5
Circulationpump,cooling(ON/OFF)
P7
RecoverycircuitpumpON/OFF ,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
M3
Motorizedcontrolvalve,cooling(3-pointcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
20|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heating/coolingwithroomtemperatureandairquality control(continued)
M1andM3are3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
AQ146286475947en-010601
©Danfoss|2021.06|21
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.9isveryflexible.These arethebasicprinciples:
Heatingwithroomtemperatureandairqualitycontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour requirements.TheairducttemperaturesensorS3isthemost importantsensor.ThedesiredtemperatureatS3issetintheECL Comfortcontrollerasthe'Desiredinlettemperature' .
Theairmixingcircuit,controlledbyM2,isconsideredasthe maincircuit,whereastheheatingcircuit,controlledbyM1,isthe supplementarycircuit.
ThemotorizedcontrolvalveM1(controllingtheheating temperature)isopenedgraduallywhentheS3temperatureis lowerthanthedesiredS3temperatureandviceversa.
Roomtemperature: Iftheroomtemperature(S4orECA30)doesnotequalthedesired roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesfordesiredinlettemperatureandtwodifferent temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule andheatingdemand.AdamperP2canbeON/OFFcontrolled accordingtoschedule.ThecirculationpumpX3isON/OFF controlledaccordingtoheatingdemand.
Airqualitycontrol(CO2measuredin"ppm"): Whentheppmvalue(0-10voltsignalmeasuredbyS11)exceedsa selectablelimit,thedamperM2graduallyopensinordertosupply morefreshair.
WhenM2isfullyopen,thefansV2andV3aregraduallyincreased inspeeduntiltheppmvalueisacceptable.Speedrelationbetween V2andV3canbeset.
Asanalternative,theS11signalcanexpressanRHsignal(Relative Humidity).
Ventilationduringsavingperiod: Adesiredfanspeedcanbeset.
Roomtemperaturesignalmustbepresent
ThenightdamperP8willopen
ThefanV2willoperateatreducedspeed
ThefanV3isOFF
P2isOFF
M2isOFF
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return temperaturelimitation(S5)andfrostprotection(S6andS7),please readthesection‘A214andA314ingeneral’ .
TypicalA314.9application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECA32
ElectroniccontrollerECLComfort310
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
Fanmonitor
S9
S10
Filtermonitor
S11
Airquality(CO2)signal(ppm).Alternative:Relative Humiditysignal
F1
Fan(ON/OFF)
P2
Damper(ON/OFF),notillustrated
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
P8
Nightdamper,notillustrated
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizeddamper(0-10voltcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
22|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214andA314ingeneral:
Compensationtemperature(optional):
Ifthemeasuredcompensationtemperature(S1orS2)ishigheror lowerthanthelimitationvalue,thedesiredtemperatureatS3can beadjusted.Thecompensationtemperaturecanbemeasured bytheoutdoortemperaturesensororforexampleanadditional roomtemperaturesensor.
Overridepossibilities:
Unusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixed'Comfort'or'Saving'mode.
Alarmfunctions:
Thealarm(relay4inECL210,relay6inECL310)isactivated:
1.IfanunaccepteddeviationbetweenthedesiredandactualS3 temperatureoccurs.
2.Ifafrostthermostat(S7)isactivated.
3.IfafrosttemperatureisdetectedatS5orS6.
4.Ifthefirealarm(S8)isactivated.
5.Ifatemperaturesensororitsconnectiondisconnects/short circuits.
A214.2,A214.3,A214.4,A214.5,A314.1,A314.2andA314.3:
Returntemperature(optional):
Ifthemeasuredreturntemperature(S5)doesnotequalthe limitationvalue(typically,thereturntemperaturebecomeshigher thanthelimitationvalue),thedesiredtemperatureatS3canbe adjusted(typicallytoalowervalue).Thisresultsinagradualclosing ofthemotorizedcontrolvalve.
Frostprotection(optional):
TemperaturesensorS6and/orfrostthermostatS7canprotect theheatexchangeragainstfrost.
Furthermore,iftheS5temperaturebecomestoolow,italsocan enablethefrostprotection.
Anactivatedfrostprotectionwillstartthealarm,stopthefanF1, closethedamperP2andfullyopenthemotorizedcontrolvalveM1.
Firealarm(optional): Anactivatedfirealarminputwillstartthealarm,stopthefanF1, closethedamperP2andclosethemotorizedcontrolvalves.
AQ146286475947en-010601
©Danfoss|2021.06|23
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.4,A314.5,A314.6andA314.7:
Efficiencycalculation:
x
(Entryduct-Outdoor)
(Exitduct-Outdoor)
Example:
Outdoor(S1)
Entryduct(S13) Exitduct(S14)
(16-7)
(24-7)
A314.4,A314.5,A314.6andA314.7:
=
= =
x
100
7
16 24
=
100
=
%
°C
°C °C
53%
Circuit1'soverviewdisplayshowsoutputstatusforM1. Anapproximate%-valueforM1'spositionisalsoindicatedinorder tofollowthecontrolprocedure.
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
24|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
A214.1examplea
Ventilationsystemwithcoolingandconstantroomtemperaturecontrol
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample12°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
AQ146286475947en-010601
©Danfoss|2021.06|25
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.1exampleb
Ventilationsystemwithcoolingandconstantroomtemperaturecontrol.Chillerhasconstantflow.
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample12°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
A214.1examplec
Ventilationsystem(fancoils)withcoolingandconstantroomtemperaturecontrol
Settingadvice:
Setdesiredroomtemperature,forexample5°C. Setdesiredbalancetemperature,forexample1°C. Ifaroomtemperaturesensorisnotconnected,thedesiredflowtemperatureatS3willcorrespondtothedesiredroomtemperature.
26|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.1exampled
Coolingsystemwithconstantflowtemperaturecontrol
Settingadvice:
Setdesiredroomtemperature,forexample1°C. Ifaroomtemperaturesensorisnotconnected,thedesiredflowtemperatureatS3willcorrespondtothedesiredroomtemperature. Set‘Fancut-indelay’(IDno.11086—‘Settings’ ,‘Fan/acc.control’)to0seconds.
A214.1examplee
Coolingsysteminceilingandconstantroomtemperaturecontrolinforexampleawinecellar
Settingadvice:
Setdesiredroomtemperature,forexample14°C. Setdesiredbalancetemperature,forexample10°C. Ifaroomtemperaturesensorisnotconnected,thedesiredflowtemperatureatS3willcorrespondtothedesiredroomtemperature. Set‘Fancut-indelay’(IDno.11086—‘Settings’ ,‘Fan/acc.control’)to0seconds.
AQ146286475947en-010601
©Danfoss|2021.06|27
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.2examplea
Ventilationsystemwithheatingandconstantducttemperaturecontrol
Sensoradvice:
SensorS3andS4mustbeconnected.Ifnot,thefan(F1)stops,thedamper(P2)andmotorizedcontrolvalve(M1)close.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
28|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.2exampleb
Heatingofaswimmingpool,constantwatertemperaturecontrol
Sensoradvice:
SensorS3andS4mustbeconnected.Ifnot,thepump(F1)stopsandmotorizedcontrolvalve(M1)closes.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
Othersettings:
Fancut-indelay—MENU\Settings\Fan/acc.control
IDno.:
11676 11656 116160 11616
116360 11636
110860
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|29
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.3examplea
Ventilationsystemwithheatingandconstantroomtemperaturecontrol
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample20°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
30|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.3exampleb
Ventilationsystem(fancoils)withheatingandconstantroomtemperaturecontrol
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample35°C. Ifaroomtemperaturesensorisnotconnected,thedesiredflowtemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|31
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.4examplea
Ventilationsystemwithheating,coolingandconstantducttemperaturecontrol
Sensoradvice:
SensorS3andS4mustbeconnected.Ifnot,thefan(F1)stops,thedamper(P2)andmotorizedcontrolvalves(M1/M2)close.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
32|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.4exampleb
Ventilationsystemwithheating,passivecooling(outsideair)andconstantducttemperaturecontrol
Sensoradvice:
SensorS3andS4mustbeconnected.Ifnot,thefan(F1)stops,thedamper(P2)andmotorizedcontrolvalves(M1/M2)close.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|33
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.5examplea
Ventilationsystemwithheating,coolingandconstantroomtemperaturecontrol
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample20°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
34|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.5exampleb
Ventilationsystemwithheating,passivecooling(outsideair)andconstantroomtemperaturecontrol
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample20°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|35
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.5examplec
Ventilationsystemwithheating,cross-flowheatexchangercontrolandconstantroomtemperaturecontrol
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample20°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
36|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A214.6examplea
Heatingsystemwith3–portmixingvalve
A214.6exampleb
Heatingsystemwithheatexchanger
Settingadvice:
SensorS3mustbeconnected.Ifnot,thepump(F1)stopsandmotorizedcontrolvalve(M1)closes.
AQ146286475947en-010601
©Danfoss|2021.06|37
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.1examplea
Ventilationsystemwithheating,passivecooling(outsideair)andconstantducttemperaturecontrol.Analogcontrolledpassive cooling(M2).
Sensoradvice:
SensorS3andS4mustbeconnected.Ifnot,thefan(F1)stops,thedamper(P2)andmotorizedcontrolvalves(M1/M2)close.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
38|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.1exampleb
Ventilationsystemwithheating,coolingandconstantducttemperaturecontrol.Analogcontrolledcooling(M2).
Sensoradvice:
SensorS3andS4mustbeconnected.Ifnot,thefan(F1)stops,thedamper(P2)andmotorizedcontrolvalves(M1/M2)close.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|39
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.2examplea
Ventilationsystemwithheating,passivecooling(outsideair)andconstantroomtemperaturecontrol.Analogcontrolledpassive cooling(M2).
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample20°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
40|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.2exampleb
Ventilationsystemwithheating,coolingandconstantroomtemperaturecontrol.Analogcontrolledcooling(M2).
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample20°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|41
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.3examplea
Ventilationsystemwithheatingandconstantroomtemperaturecontrol.Analogcontrolledfanspeed(V1)basedonoutdoorwindspeed.
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample35°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
42|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.3exampleb
Ventilationsystemwithheatingandconstantroomtemperaturecontrol.Analogcontrolledaircurtain(V1)speedbasedonoutdoorwind speed.
Settingadvice:
Setdesiredroomtemperature,forexample20°C. Setdesiredbalancetemperature,forexample35°C. Ifaroomtemperaturesensorisnotconnected,thedesiredducttemperatureatS3willcorrespondtothedesiredroomtemperature.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|43
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.4examplea
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelation topressures.Analogcontrolledspeedofrotaryheatexchanger(M2)forheatrecovery.
A314.4exampleb
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelationto pressures.Analogcontrolleddamper(M2)forheatrecoverybymeansofacrossheatexchanger.
44|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.4examplec
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelationto pressures.Analogcontrolledspeedofrotaryheatexchanger(M2)forheatrecovery.ControlofNightdamperP8forreducedventilation duringsavingperiods.
A314.4exampled
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansin relationtopressures.Analogcontrolleddamper(M2)forheatrecoverybymeansofacrossheatexchanger.ControlofNightdamper P8forreducedventilationduringsavingperiods.
AQ146286475947en-010601
©Danfoss|2021.06|45
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.4examplee
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelation topressures.Analogcontrolledvalve(M2)forheatrecoverybymeansofaFluidbattery.ControlofNightdamperP8forreduced ventilationduringsavingperiods.
Sensoradvice:
SensorS3mustbeconnected.Ifnot,thefanF1stopsandmotorizedcontrolvalveM1closes. S1,S13andS14mustbeconnectedinordertocalculatetherecoveryefficiency.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
46|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.5examplea
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelationto airquality(CO2).Analogcontrolledspeedofrotaryheatexchanger(M2)forheatrecovery.
A314.5exampleb
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelationto airquality(CO2).Analogcontrolleddamper(M2)forheatrecoverybymeansofacrossheatexchanger.
AQ146286475947en-010601
©Danfoss|2021.06|47
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.5examplec
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelation toairquality(CO2).Analogcontrolledspeedofrotaryheatexchanger(M2)forheatrecovery.ControlofNightdamperP8forreduced ventilationduringsavingperiods.
A314.5exampled
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelation toairquality(CO2).Analogcontrolleddamper(M2)forheatrecoverybymeansofacrossheatexchanger.ControlofNightdamper P8forreducedventilationduringsavingperiods.
48|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.5examplee
Ventilationsystemwithheating,passivecooling(outsideair)androomtemperaturecontrol.Analogcontrolledspeedoffansinrelationto airquality(CO2).Analogcontrolledvalve(M2)forheatrecoverybymeansofaFluidbattery.ControlofNightdamperP8forreduced ventilationduringsavingperiods.
Sensoradvice:
SensorS3mustbeconnected.Ifnot,thefanF1stopsandmotorizedcontrolvalveM1closes. S1,S13andS14mustbeconnectedinordertocalculatetherecoveryefficiency.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|49
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.6examplea
Ventilationsystemwithheating,coolingandroomtemperaturecontrol.Analogcontrolledspeedoffansinrelationtopressures.Analog controlledspeedofrotaryheatexchanger(M2)forheatrecovery.
A314.6exampleb
Ventilationsystemwithheating,coolingandroomtemperaturecontrol.Analogcontrolledspeedoffansinrelationtopressures.Analog controlleddamper(M2)forheatrecoverybymeansofacrossheatexchanger.
50|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.6examplec
Ventilationsystemwithheating,coolingandroomtemperaturecontrol.Analogcontrolledspeedoffansinrelationtopressures.Analog controlledvalve(M2)forheatrecoverybymeansofaFluidbattery.
Sensoradvice:
SensorS3mustbeconnected.Ifnot,thefanF1stopsandmotorizedcontrolvalveM1closes. S1,S13andS14mustbeconnectedinordertocalculatetherecoveryefficiency.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|51
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.7examplea
Ventilationsystemwithheating,coolingandroomtemperaturecontrol.Analogcontrolledspeedoffansinrelationtoairquality(CO2). Analogcontrolledspeedofrotaryheatexchanger(M2)forheatrecovery.
A314.7exampleb
Ventilationsystemwithheating,coolingandroomtemperaturecontrol.Analogcontrolledspeedoffansinrelationtoairquality(CO2). Analogcontrolleddamper(M2)forheatrecoverybymeansofacrossheatexchanger.
52|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.7examplec
Ventilationsystemwithheating,coolingandroomtemperaturecontrol.Analogcontrolledspeedoffansinrelationtoairquality(CO2). Analogcontrolledvalve(M2)forheatrecoverybymeansofaFluidbattery.
Sensoradvice:
SensorS3mustbeconnected.Ifnot,thefanF1stopsandmotorizedcontrolvalveM1closes. S1,S13andS14mustbeconnectedinordertocalculatetherecoveryefficiency.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|53
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.9examplea
Ventilationsystemwithheatingandroomtemperaturecontrol.Analogcontrolledspeedoffansinrelationtoairquality(CO2).
54|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
A314.9exampleb
Ventilationsystemwithheatingandroomtemperaturecontrol.Analogcontrolledspeedoffansinrelationtoairquality(CO2).ON-OFF controlofdamperP2.
Sensoradvice:
SensorS3mustbeconnected.Ifnot,thefanF1stopsandmotorizedcontrolvalveM1closes. S1,S13andS14mustbeconnectedinordertocalculatetherecoveryefficiency.
Navigation:
Specialsettingsforsensors/thermostatsusedasfrostprotection:
S6*frosttemperaturesensor—MENU\Alarm\FrostT\Alarmvalue S5returntemperaturesensor—MENU\Alarm\LimitTfrost\Alarmvalue ClosingcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue OpeningcontactoftheS7*frostthermostat—MENU\Alarm\Frostthermostat\Alarmvalue *bothfrostprotectionmethods,bymeansofS6and/orS7,canbeused
Specialsettingsforthermostatsusedasfirealarm:
ClosingcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue OpeningcontactoftheS8firethermostat—MENU\Alarm\Firesafety\Alarmvalue
IDno.:
11676 11656 116160 11616
116360 11636
Recommended
setting:
5°C 5°C
1
1
AQ146286475947en-010601
©Danfoss|2021.06|55
OperatingGuideECLComfort210/296/310,applicationA214/A314

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
56|©Danfoss|2021.06
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
AQ146286475947en-010601
©Danfoss|2021.06|57
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
58|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
AQ146286475947en-010601
©Danfoss|2021.06|59
OperatingGuideECLComfort210/296/310,applicationA214/A314

2.4Placingthetemperaturesensors

Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
60|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ146286475947en-010601
©Danfoss|2021.06|61
OperatingGuideECLComfort210/296/310,applicationA214/A314

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
62|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
Factoryestablishedjumpersinthebasepart: 5to8,9to14,Lto5andLto9,Nto10
SeealsotheA214InstallationGuide(deliveredwiththeapplication key)forapplicationspecificconnections.
Electricalconnections,230Va.c.,powersupply,pumps,dampers, motorizedcontrolvalvesetc.
Connections,ingeneral: SeealsotheA214InstallationGuide(deliveredwiththeapplication
key)forapplicationspecificconnections.
AQ146286475947en-010601
©Danfoss|2021.06|63
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.5.2Electricalconnections,230Va.c.,powersupply,pumps,dampers,motorizedcontrolvalvesetc.
Connections,ingeneral.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
TerminalsMax.load
ECL210ECL310
19
18
17
1616
15
1414
13
12
15
13
12
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
11
10
9
88
7
6
55
4
3
*4Aforohmicload,2Aforinductiveload
Factoryestablishedjumpersinthebasepart: 5to8,9to14,Lto5andLto9,Nto10
11
10
9
7
6
4
3
2
1
230Va.c.,Neutral(N)
230Va.c.,Live(L)
4(2)A/230Va.c.*
0,2A/230Va.c.
0,2A/230Va.c.
0,2A/230Va.c.
0,2A/230Va.c.
0,2A/230Va.c.
0,2A/230Va.c.
64|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Electricalconnections,ECA32
Connections,ingeneral. SeealsotheA214InstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
TerminalsMax.load
ECA32
48
47
46
45
44
43
42
41
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
40
39
*4Aforohmicload,2Aforinductiveload
4(2)A/230Va.c.*
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ146286475947en-010601
©Danfoss|2021.06|65
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.5.3Electricalconnections,24Va.c.,powersupply,pumps,dampers,motorizedcontrolvalvesetc.
Connections,ingeneral. SeealsotheA214InstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
DonotuseacommontransformerforECLComfort310andmotorizedvalve/dampercontrol.Useseparatetransformers.
TerminalsMax.load
ECA310
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
*4Aforohmicload,2Aforinductiveload
24Va.c.,(SN)
24Va.c.,(SP)
4(2)A/24Va.c.*
4(2)A/24Va.c.*
4(2)A/24Va.c.*
4(2)A/24Va.c.*
4(2)A/24Va.c.*
4(2)A/24Va.c.*
1A/24Va.c.
1A/24Va.c.
1A/24Va.c.
1A/24Va.c.
1A/24Va.c.
1A/24Va.c.
Factoryestablishedjumpersinthebasepart: 5to8,9to14,L(SP)to5andL(SP)to9,N(SN)to10
66|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ146286475947en-010601
©Danfoss|2021.06|67
OperatingGuideECLComfort210/296/310,applicationA214/A314
Electricalconnections,ECA32
Connections,ingeneral. SeealsotheA214InstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
TerminalsMax.load
ECA32
48
47
46
45
44
43
42
41
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
4(2)A/230Va.c.*
40
39
*4Aforohmicload,2Aforinductiveload
4(2)A/230Va.c.*
68|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Electricalconnections,ECA32
Connections,ingeneral. SeealsotheA214InstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Thetransformersforsupplyingtheactuatorsmustbedouble-isolatedversions.
TerminalsMax.load
ECA32
56
57
58
59
60
61
62
*Thevaluemustbe47kΩasaminimum.
47kΩ*
47kΩ*
47kΩ*
AQ146286475947en-010601
©Danfoss|2021.06|69
OperatingGuideECLComfort210/296/310,applicationA214/A314
ExampleshowingseparatetransformersforECL310supplyandoutputconnections:
AMD=Danfossdamperactuator
ExampleshowingsupplyforECL310andoutputconnections:
VSD=VariableSpeedDrive
ExampleshowingsupplyforECL310,24Va.c.
Separatetransformerforsupplyoftransmitter(forinput)andoutputconnections:
AMD=Danfossdamperactuator
70|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.5.4Electricalconnections,Pt1000temperaturesensors
A214/A314:
TerminalSensor/description
29and30
28and30
27and30
26and30
25and30
24and30
23and30
22and30
21and30
20and30
S1
Outdoortemp.sensor*
S2Compensationtemp.
sensor**
S3
Airduct/flowtemp.sensor ***
A214.1,A214.3,A214.5,
S4
A214.6,A314.2-A314.9:
Roomtemp.sensor. A214.2,A214.4,A314.1: Flowtemp.sensor.
S5Returntemp.sensor
S6
Frosttemp.sensor**** (notusedinA214.1)
S7
Frostthermostat*****
S8
Firethermostat*****
S9
ECL310only. A314.4-A314.9: Fanmonitor
S10
ECL310only. A314.3:Windspeedsignal (0-10V).
Type (recomm.)
ESMT
ESM-11/ESMB / ESMC/ESMU/ ESMT
ESM-11/ESMB / ESMC/ESMU
ESM-10
ESM-11/ESMB / ESMC/ESMU
ESM-11/ESMB / ESMC/ESMU
ESMB
A314.4-A314.9: Filtermonitor
*
Iftheoutdoortemperaturesensorisnotconnectedorthe cableisshort-circuited,thecontrollerassumesthatthe outdoortemperatureis0(zero)°C.
**
Couldforexamplebeanextraroomtemperaturesensor.
***
Ifthesensorisnotconnectedorthecableisshort-circuited, themotorizedcontrolvalvecloses(safetyfunction).
****
Bothfrostprotectionmethodscanbeused.
*****
Canbesetuptoreactonaclosingoranopeningcontact.
Factoryestablishedjumper: 30tocommonterminal.
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus) Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ146286475947en-010601
©Danfoss|2021.06|71
OperatingGuideECLComfort210/296/310,applicationA214/A314
Overridecontact
Exampleofoverridecontact,connectedtoS8:
72|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Connectionoffrostthermostats,S7
Whenfrost(toolowtemperature)isdetected,contacts1-2close.
Whenfrost(toolowtemperature)isdetected,contacts1-4open.
ConnectionsofFanandFiltermonitor(S9andS10):
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ146286475947en-010601
©Danfoss|2021.06|73
OperatingGuideECLComfort210/296/310,applicationA214/A314
Donotusecommontransformerwhenpressuretransmittersaresuppliedby24Va.c.:
74|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
ConnectionsofinputsS11,S12,S13andS14
(S11andS12transmittersgenerate0-10V)
(S11andS12transmittersgenerate4-20mA)
ExampleshowingsupplyforECL310,24Va.c. Separatetransformerforsupplyoftransmitter(forinput)and outputconnections.
AMD=Danfossdamperactuator
AQ146286475947en-010601
©Danfoss|2021.06|75
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.5.5Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
76|©Danfoss|2021.06
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
AQ146286475947en-010601
©Danfoss|2021.06|77
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
78|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
AQ146286475947en-010601
©Danfoss|2021.06|79
OperatingGuideECLComfort210/296/310,applicationA214/A314

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
80|©Danfoss|2021.06
ECLComfort296
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ146286475947en-010601
©Danfoss|2021.06|81
OperatingGuideECLComfort210/296/310,applicationA214/A314
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
82|©Danfoss|2021.06
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
AQ146286475947en-010601
©Danfoss|2021.06|83
OperatingGuideECLComfort210/296/310,applicationA214/A314
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
84|©Danfoss|2021.06
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
AQ146286475947en-010601
©Danfoss|2021.06|85
OperatingGuideECLComfort210/296/310,applicationA214/A314
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
86|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
AQ146286475947en-010601
©Danfoss|2021.06|87
OperatingGuideECLComfort210/296/310,applicationA214/A314

2.8Navigation,ECLApplicationKeyA214/A314

Navigation,A214,applicationsA214.1,A214.2,A214.3,A214.4,A214.5andA214.6
Home
MENU
ScheduleSelectable
Settings
Flowtemperature11008DesiredbalanceT((((((
Roomlimit
DuctTlimit
Returnlimit
LimitTsafety
Compensation1
Compensation2
Controlpar.(1)
IDno.
11178
11177
11009
11182Infl.-max.((((
11183
11015
11182Infl.-max.((
11183
11015
11030
11035
11036
11037
11108
11105
11107
11139
11060
11062
11063
11061
11139
11064
11066
11067
11065
11174
11184
11185
11186
11187
11189
ApplicationsA214
Function
Temp.max.((((((
Temp.min.((((((
Deadzone((
Infl.-min.((((
Adapt.time((((
Infl.-min.((
Adapt.time
Limit
Infl.-max.
Infl.-min.
Adapt.time
LimitTfrost
Infl.-min.
Adapt.time
Actualcomp.T
Limit((((((
Infl.-max.
Infl.-min.
Adapt.time
Actualcomp.T
Limit((((((
Infl.-max.((((((
Infl.-min.((((((
Adapt.time((((((
Motorpr.
Xp((((((
Tn((((((
Mrun((((((
Nz((((((
Min.act.time((((
A214.1A214.2A214.3A214.4A214.5A214.6
((
((((((
((((((
((((((
((((
(((((
(((((
(((((
((((((
((((((
((((((
((((((
((((((
((((((
((
((
88|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A214,applicationsA214.1,A214.2,A214.3,A214.4,A214.5andA214.6continued
Home
MENU
Settings
Controlpar.2
Fan/acc.control
Application
IDno.
12174
12184
12185
12186
12187
12189
11088
11086
11137
11089
11087
11091
11090
11077
11027
11194
11010
11500
11021
11140
11093
10304
11082
11141
11142
Function
Motorpr.
Xp((
Tn((
Mrun((
Nz((
Min.act.time((
Fanoutputfunc.((((((
Fancut-indelay((((((
Fanfunction(((((
Acc.outputfunc.((((((
Acc.cut-indelay
Acc.timecontrol
Optionalfunction
PfrostT
RoomTdiff.
Stopdifference
ECAaddr.
SenddesiredT
Totalstop
Comp.Tselect
Frostpr.T
S4filter
Accum.filter
Ext.input((((((
Ext.mode
Applications,A214
A214.1A214.2A214.3A214.4A214.5A214.6
((
((((((
((((((
((((((
(((((
((
(
((((
((((((
((((((
((((((
(((
((
((
((((((
AQ146286475947en-010601
©Danfoss|2021.06|89
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A214,applicationsA214.1,A214.2,A214.3,A214.4,A214.5andA214.6continued
Home
MENU
HolidaySelectable
Alarm
InfluenceDes.flowT
overview
FrostT
LimitTfrost
Frostthermostat
Firesafety
Temp.monitor.
Alarmoverview
IDno.
11676
11656
11616
11617
11636
11637
11147
11148
11149
11150
Function
Alarmvalue
Alarmvalue
Alarmvalue
Alarmtime-out
Alarmvalue
Alarmtime-out
Upperdifference
Lowerdifference
Delay
Lowesttemp.
FrostT
LimitTfrost
Frostthermostat
Firesafety
Temp.monitor.
FlowTsensor
Returnlim.
Roomlim.
DuctTlimit
Compensation1
Compensation2
LimitTsafety
Holiday
Ext.override
ECAoverride
SCADAoffset
ApplicationsA214
A214.1A214.2A214.3A214.4A214.5A214.6
((((((
((((((
(((((
(((((
(((((
((((((
((((((
(((((
(((((
(((((
(((((
((((((
(((((
(((((
((((((
(((((
((((((
((((((
((((
((
((((((
((((((
(((((
((((((
((((((
((((
((((((
90|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A214,applicationsA214.1,A214.2,A214.3,A214.4,A214.5andA214.6,Commoncontrollersettings
Home
MENU
Time&Date ScheduleSelectable
Inputoverview
Log(sensors)
Outputoverride
LogtodayOutdoorT LogyesterdayFlowT&desired Log2daysDuctT&desired Log4daysRoomT&desired
IDno.
ApplicationsA214,Commoncontrollersettings
Function
Selectable
OutdoorT CompensationT
FlowT RoomT DuctT ReturnT FrostT
AccumulatedT Frostthermostat Firesafety
ReturnT&limit CompensationT FrostT M1 F1 M2 P2 X3 A1
A214.1A214.2A214.3A214.4A214.5A214.6
((((((
((((((
((((((
((((((
((((((
((((
((
((((((
((((((
((
(((((
((((((
((((((
((((((
((
((((
((((((
((((((
((((((
(((((
((((((
(((
((((((
((((((
((((((
AQ146286475947en-010601
©Danfoss|2021.06|91
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A214,applicationsA214.1,A214.2,A214.3,A214.4,A214.5andA214.6,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview
Alarm Display
Communication
Language
60058 60059
2048
38
39 2150 2151 2050
Function
Usersettings
Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. Productiondate
Tsensordefect Backlight Contrast
ECL485addr. Modbusaddr. Baud Servicepin Ext.reset Language
ApplicationsA214,Commoncontrollersettings
A214.1A214.2A214.3A214.4A214.5A214.6
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
((((((
92|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A314,applicationsA314.1,314.2andA314.3
Home
MENU
ScheduleSelectable
Settings
Flowtemperature11008DesiredbalanceT(((
Roomlimit
DuctTlimit
Returnlimit
LimitTsafety
Compensation1
Compensation2
Controlpar.(1)
IDno.
11178
11177
11009
11182Infl.-max.((
11183
11015
11182Infl.-max.(
11183
11015
11030
11035
11036
11037
11108
11105
11107
11139
11060
11062
11063
11061
11139
11064
11066
11067
11065
11174
11184
11185
11186
11187
11189
ApplicationA314
Function
Temp.max.(((
Temp.min.(((
Deadzone((
Infl.-min.((
Adapt.time((
Infl.-min.(
Adapt.time
Limit
Infl.-max.
Infl.-min.
Adapt.time
LimitTfrost
Infl.-min.
Adapt.time
Actualcomp.T
Limit(((
Infl.-max.
Infl.-min.
Adapt.time
Actualcomp.T
Limit(((
Infl.-max.
Infl.-min.(((
Adapt.time(((
Motorpr.
Xp(((
Tn(((
Mrun(((
Nz(((
Min.act.time((
A314.1A314.2A314.3
(
(((
(((
(((
(
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
((
(
AQ146286475947en-010601
©Danfoss|2021.06|93
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A314,applicationsA314.1,A314.2andA314.3continued
Home
MENU
Settings
Controlpar.2
Fan/acc.control
Application
IDno.
12174
12184
12185
12187
12165
12167
12171
11098
11081
11104
11088
11086
11137
11089
11087
11091
11090
11077
11027
11010
11500
11021
11140
11093
10304
11082
11141
11142
Function
Motorpr.
Xp((
Tn((
Nz((
Voutmax.((
Voutmin.((
Reverseout((
Windactual(
Filterconstant(
Controlvoltage(
Fanoutputfunc.
Fancut-indelay
Fanfunction
Acc.outputfunc.
Acc.cut-indelay
Acc.timecontrol
Optionalfunction
PfrostT
RoomTdiff.
ECAaddr.
SenddesiredT
Totalstop
Comp.Tselect
Frostpr.T(
S4filter
Accum.filter
Ext.input(((
Ext.mode(((
ApplicationsA314
A314.1A314.2A314.3
((
(((
(((
(((
(((
(((
(((
(((
(((
(
((
(((
(((
(((
(
((
94|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A314,applicationsA314.1,A314.2andA314.3continued
Home
MENU
HolidaySelectable
Alarm
InfluenceoverviewDes.flowT
FrostT
LimitTfrost
Frostthermostat
Firesafety
Temp.monitor.
Alarmoverview
IDno.
11676
11656
11616
11617
11636
11637
11147
11148
11149
11150
Function
Alarmvalue
Alarmvalue
Alarmvalue
Alarmtime-out
Alarmvalue
Alarmtime-out
Upperdifference
Lowerdifference
Delay
Lowesttemp.
FrostT
LimitTfrost
Frostthermostat
Firesafety
Temp.monitor.
FlowTsensor
Returnlim.
Roomlim.
DuctTlimit
Compensation1
Compensation2
LimitTsafety
Holiday
Ext.override
ECAoverride
SCADAoffset
ApplicationsA314
A314.1A314.2A314.3
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(
(
(((
(((
(((
(((
(
(((
(((
(
(((
(((
(((
((
((
((
((
((
AQ146286475947en-010601
©Danfoss|2021.06|95
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A314,applicationsA314.1,A314.2andA314.3,Commoncontrollersettings
Home
MENU
Time&Date ScheduleSelectable
Inputoverview
Log(sensors)
Outputoverride
LogtodayOutdoorT LogyesterdayFlowT&desired Log2daysDuctT&desired Log4daysRoomT&desired
IDno.
ApplicationsA314,Commoncontrollersettings
Function
Selectable
OutdoorT CompensationT
FlowT RoomT DuctT ReturnT FrostT
AccumulatedT Frostthermostat Firesafety
ReturnT&limit CompensationT FrostT
Windspeed M1 F1 V1 M2 P2
X3
A1
A314.1A314.2A314.3
(((
(((
(((
(((
(((
((
(
(((
(((
((
(((
(((
(((
(((
(
((
(((
(((
(((
(
(((
(((
(
((
(((
(((
(((
96|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A314,applicationsA314.1,A314.2andA314.3,Commoncontrollersettings,continued
Home
MENU
Keyfunctions
SystemECLversion
ApplicationsA314,Commoncontrollersettings
IDno.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet Portalconfig M-busconfig EnergyMeters Rawinputoverview
Alarm Display
Communication
Language
60058 60059
2048
38
39 2150 2151 2050
Function
Usersettings
Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. Productiondate
Tsensordefect Backlight Contrast
ECL485addr.
Modbussaddr. Baud Servicepin Ext.reset Language
A314.1A314.2A314.3
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
(((
AQ146286475947en-010601
©Danfoss|2021.06|97
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A314,applicationsA314.4,A314.5,A314.6,A314.7andA314.9,circuit1
Home
MENU
ScheduleSelectable
Settings
Inlettemperature
Roomlimit
Returnlimit
LimitTsafety
Compensation1
Compensation2
Controlpar.(1)
IDno.
11018Des.Tcomfort(((((
11019
11178
11177
11009
11182Infl.-max.(((((
11183
11015
11030
11035
11036
11037
11108
11105
11107
11139
11060
11062
11063
11061
11139
11064
11066
11067
11065
11174
11184
11185
11186
11187
11189
Applications314
Function
Des.Tsaving(((((
Temp.max.(((((
Temp.min.
Deadzone
Infl.-min.(((((
Adapt.time(((((
Limit
Infl.-max.
Infl.-min.
Adapt.time
LimitTfrost
Infl.-min.
Adapt.time
Actualcomp.T
Limit(((((
Infl.-max.
Infl.-min.
Adapt.time
Actualcomp.T
Limit(((((
Infl.-max.
Infl.-min.
Adapt.time
Motorpr.
Xp(((((
Tn(((((
Mrun(((((
Nz(((((
Min.act.time((((
A314.4A314.5A314.6A314.7A314.9
(((
(
(((((
(((((
(((((
((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
((
(
(
(
98|©Danfoss|2021.06
AQ146286475947en-010601
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A314,applicationsA314.4,A314.5,A314.6,A314.7andA314.9,circuit1,continued
Home
MENU
Settings
Controlpar.2
Fan/acc.control
Application
IDno.
12368
12369
12184
12185
12187
12165
12167
11088
11086
11137
11089
11087
11091
11010
11021
11093
11140
11368
11369
11179
11082
11141
11142
Function
1.steplevel(
2.steplevel(
Xp(((((
Tn(((((
Nz
Voutmax.
Voutmin.
Fanoutputfunc.(((((
Fancut-indelay(((((
Fanfunction(((((
Acc.outputfunc.
Acc.cut-indelay
Acc.timecontrol
ECAaddr.
Totalstop
Frostpr.T(((((
Comp.Tselect
1.steplevel
2.steplevel
Summer,cut-out
Accum.filter
Ext.input(((((
Ext.mode
Applications,A314
A314.4A314.5A314.6A314.7A314.9
(((
(((
(((
(((((
(((((
(((((
(((((
(((((
(((((
((((
((((
((
((
(((((
((
((
((
AQ146286475947en-010601
©Danfoss|2021.06|99
OperatingGuideECLComfort210/296/310,applicationA214/A314
Navigation,A314,applicationsA314.4,A314.5,A314.6,A314.7andA314.9,circuit1,continued
Home
MENU
HolidaySelectable
Alarm
FrostT
LimitTfrost
Frostthermostat
Firesafety
DigitalS9
DigitalS10
Inletpressure
Outletpressure
Airquality
Temp.monitor.
Heatrecovery
IDno.
11676
11656
11616
11617
11636
11637
10656
10657
12390
10696
10697
13614
13615
13617
13390
14614
14615
14617
14390
13614
13615
13617
11147
11148
11149
11150
12615
12617
ApplicationsA314
Function
Alarmvalue
Alarmvalue
Alarmvalue
Alarmtime-out
Alarmvalue
Alarmtime-out
Alarmvalue
Alarmtime-out
Clearalarm
Alarmvalue
Alarmtime-out
Alarmhigh
Alarmlow
Alarmtime-out
Clearalarm
Alarmhigh
Alarmlow
Alarmtime-out
Clearalarm
Alarmhigh
Alarmlow
Alarmtime-out
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Alarmlow
Alarmtime-out(
A314.4A314.5A314.6A314.7A314.9
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
(((((
((
((
((
((
((
(((
(((
(((
(((((
(((((
(((((
(((((
((((
(((
100|©Danfoss|2021.06
AQ146286475947en-010601
Loading...