Danfoss 852 Installation guide

Seven Day Two Channel Electronic Timeswitch
N
L
1
2
3
4
5
6
Links for 230V control circuit(s)
230V 50Hz
Mains Supply
Channel 2
OFF
ON
Channel 1
OFF
ON
MK8-852 (3016 12/01)
N
L
6
CABLE ENTRY
APERTURE
2 fixings for
double gang
surface box
Alternative 4 fixings
for double gang
surface box
4 fixings for MK8
timeswitch
Model 852
Installation and Wiring Instructions
The model 852 timeswitch must be installed by a competent electrician and the installation should conform to IEE Wiring Regulations.
Installation and Wiring
of the unit, and carefully separate the front and rear portions. Unplug the ribbon cable from the rear portion. CAUTION: Do not allow either half of the unit to hang by the ribbon cable as damage could be caused.
2 Remove the polystyrene packing piece from the top
of the transformer. It is marked “REMOVE”.
3 Select the desired fi xing position and observe the label
“THIS WAY UP” inside the rear portion. The two halves will only assemble correctly one way round.
4 Four fi xing holes are provided for attaching the rear
portion to the wall or mounting surface.Conduit box adaptors as shown below are availabe if required.
PART NO: 8/3222 Square Conduit Box Adaptor
CABLE ENTRY
APERTURE
4 fixings for existing
square conduit box
PART NO: 8/3223 Double Gang Surface Box Adaptor
4 fixings for
MK8 timeswitch
6 For surface cable entry remove the appropriate
knockout and ensure one of the cable clamps is positioned correctly.
7 Connections to the unit should be made as shown
below:
If the control circuits are to operate at 240V then terminals L, 1 and 4 must be linked, ensuring that the cable is sheathed and of a size to carry the required load current.
If the control circuits are operating at voltages other than 230V then terminals 1 and 4 should be connected to the required power supply and not to terminal L.
5 Surface cable entries to the unit can be made from
above, below or from the lefthand side. Conduit or recessed cable entry is through the aperture in the rear moulding.
8. Upon completion of wiring, plug in the ribbon cable ensuring the polarised plug is fully inserted into the socket. Refi t the front half of the timeswich ensuring correct alignment and that no cables are trapped before re-tightening the screws.
1
SPECIFICATION
Power Supply : 230Vac, 50Hz Switch Action : 2 x SPDT, type 1 B Switch Rating : 10 to 253Vac, 50/60Hz, min 10mA, max 10 (4) A Timing Accuracy : ±1 min/month Power Reserve : 3 months on fully charged battery Max. number of switching operations : up to 200 ON or OFF operations per week Enclosure Rating : IP30 Max. Ambient Temperature : 45°C Designed to meet : BS EN60730-2-7 Overall Dimensions (mm) : 228 wide x 115 high x 50 deep Control Pollution Situation : Degree 2 Ball Pressure Test : 75°C Rated Impulse Voltage : 2.5kV
Alternative position for cable clamp
Polarised Plug
Aperture for cable entry
4 fi xing holes
2 cable clamps
THIS WAY UP
3 knock outs for surface cable entry
N
L
6
5
4
3
2
1
Terminal Block Rating & Model label
Danfoss Randall can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss Randall reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifi cations already agreed.
Danfoss Ltd
Ampthill Road, Bedford MK42 9ER Tel: (01234) 364621 Fax: (01234) 219705 Email: ukheating@danfoss.com Website: www.heating.danfoss.co.uk
2
Part No: 3078 Issue 8 12/05