Danfoss 088U0215 Instruction

088U0215
Instruction CF-RF Room Thermostat with Infrared Floor Sensor
GB
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
Danfoss Heating Solutions VIUHR402 © Danfoss 05/2011
2
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
Index
1. Functional Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3. Temperature Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Transmission Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
© Danfoss 05/2011 VIUHR402 Danfoss Heating Solutions
3
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
1. Functional Overview
Front (fig. 1)
Up/down selector Push button Red LED (behind the cover)
InfraRed floor sensor
LED modes
Permanent light . . . . . . ON
No light . . . . . . . . . . . . . . OFF
Slow flashing . . . . . . . . . Flashes
Fast flashing. . . . . . . . . . Flickers
Back (fig. 2)
Back plate Back plate lock/unlock (turn 90°) Screw hole for wall mounting Battery placement Screw and wall plug
Note: To activate batteries please remove enclosed strips
from batteries.
Danfoss Heating Solutions VIUHR402 © Danfoss 05/2011
4
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
2. Installation
Note: Assignment of Room Thermostats to Master Controller
should be within a distance of 1.5 m.
Activate Install mode on Master Controller (fig. 1)
• Use the menu selection button to select the Install mode. Install LED flashes.
• Activate Install mode by pressing OK. Install LED goes ON.
Activate Install mode on room thermostat
• Press the push button . LED and flicker during communication.
Select output on Master Controller
• All available output LEDs on Master Controller light up, and the first one flashes.
• Press output selection button to select desired output (flashes). Accept with OK .
• All output LEDs go OFF. Selected output stays ON shortly.
Room thermostat installation status
• Satisfactory: LED goes OFF.
• Not satisfactory: LED flashes 5 times.
Note: A room thermostat can be assigned to several outputs
if needed by repeating the installation process.
© Danfoss 05/2011 VIUHR402 Danfoss Heating Solutions
5
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
3. Temperature Settings
Digital Display (fig. 1)
SET Set value adjustment
MIN Minimum temperature limitation
MAX Maximum temperature limitation
Transmission link icon
Low battery indicator
Alarm icon
Settings only available from CF-RC Remote controller:
Lock icon
Timer icon
Room temperature icon
Floor temperature icon
Changing default display temperature (fig. 1)
1. The actual room temperature is shown in the display as default.
2. To change default display from actual room tempera-
ture to actual floor surface temperature, press and hold the push button until SET MAX is shown in the display.
3. Press the button shortly and repeatedly until or
is flashing in the display.
4. Press the up/down selector to select the new default
display temperature: Room temperature Floor surface temperature.
Danfoss Heating Solutions VIUHR402 © Danfoss 05/2011
6
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
Setting of room temperature
1. Make sure actual room temperature is shown in the display.
2. Press the up/down selector to set the desired room temperature value. SET is shown in the display.
3. When releasing the up/down selector the display returns to actual temperature.
Note: The thermostat regulates the floor heating system
according to room temperature set point, within the maximum and minimum limitations defined for the floor surface temperature.
Room temperature limitation
1. Make sure actual room temperature is shown in the display.
2. Press the push button until SET MAX is shown in the display.
3. Press the up/down selector to set the maximum room temperature limitation.
4. Press the push button shortly, SET MIN is shown in the display.
5. Press the up/down selector to set the minimum room temperature limitation.
6. Press the push button shortly and the actual floor surface temperature is shown in the display.
© Danfoss 05/2011 VIUHR402 Danfoss Heating Solutions
7
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
Floor surface temperature limitation
1. Ensure actual floor surface temperature is shown in the display illustrated by .
2. Press and hold the push button until SET MAX is
also shown in the display.
3. Press the up/down selector to set the maximum
floor surface temperature limitation.
4. Press the push button shortly, SET MIN is also
shown in the display.
5. Press the up/down selector to set the minimum
floor surface temperature limitation.
IMPORTANT!
As heat emission from the floor may vary slightly depending on floor covering - and thereby cause inaccurate temperature measurement - it may be necessary to adjust the setting of max. and min. floor surface temperatures accordingly. It is important always to follow recommendations from the floor manufacturer regarding max. floor surface tempera­ture. It is recommended always to include mixing shunt for floor heating circuits in order to ensure optimal flow tempera­ture. - In addition to minimised energy consumption, correct setting of the flow temperature will eliminate the risk of excessive heat transfer to the floor.
Danfoss Heating Solutions VIUHR402 © Danfoss 05/2011
8
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
4. Transmission Test
Initiate transmission test on room thermostat (fig. 1)
• Press the push button .
• LED goes ON.
Link test is satisfactory
• LED goes OFF.
Link test is unsatisfactory
• LED flashes 5 times.
No Link connection to room thermostat
• Try to relocate room thermostat in the room.
• Or install CF-RU Repeater Unit and locate between Master Controller and room thermostat.
Note: When connected to a room thermostat, the Master
Controller output LED(s) flash(es) during Link test.
© Danfoss 05/2011 VIUHR402 Danfoss Heating Solutions
9
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
5. Mounting
Placing a room thermostat (fig. 3)
• A room thermostat should be placed in accordance with fig. 3.
IMPORTANT!
Wherever possible, a room thermostat should be installed at a place where the effect of sunlight, strong artificial light (e.g. halogen spotlight), draught, other heat-emitting equipment (e.g. TVs) etc. is avoided. Please note that no furniture, rugs etc. should be perma­nently placed within the area of the InfraRed Floor Sensor as shown in fig. 3.
6. Uninstallation
Activate Uninstall mode on Master Controller (fig. 1)
• Use the Menu selection button to choose the Unin­stall menu. Uninstall LED flashes.
• Activate Uninstall mode by pressing OK . Uninstall LED goes ON.
Deselect output on Master Controller
• Select output to be removed by output selection button .
• Remove flashing output with OK .
Danfoss Heating Solutions VIUHR402 © Danfoss 05/2011
10
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
7. Specifications
Temperature setting range 5-35°C
Transmission frequency 868.42 MHz
Transmission range in normal buildings (up to)
Transmission power < 1 mW
Battery Alkaline 2xAA, 1.5 V
Battery lifetime (up to) 1-3 years
Ambient temperature 0-50°C
IP class 21
Floor ensor accuracy +/- 1°C
Floor sensor emission coefficient
30 m
0.9
© Danfoss 05/2011 VIUHR402 Danfoss Heating Solutions
11
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
8. Troubleshooting
Error Indication Possible Cause
The LED, and flashes every 5th minute
The LED, and flashes every 30 sec.
The LED, , and flashes
The LED, and flashes 5 times
E03 and
E05 and
Low battery
Critical low battery
Critical low battery
- transmission has stopped
Installation/Link Test is unsatisfactory
Actuator error on output (CF-MC)
Room temperature below 5°C
Danfoss Heating Solutions VIUHR402 © Danfoss 05/2011
12
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
© Danfoss 05/2011 VIUHR402 Danfoss Heating Solutions
13
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
Fig. 1
Danfoss Heating Solutions VIUHR402 © Danfoss 05/2011
14
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
Fig. 2
Fig. 3
1,5 m.
0,5 m.
0,25 m.
© Danfoss 05/2011 VIUHR402 Danfoss Heating Solutions
15
Instructi on CF-RF Room Thermostat with Infrare d Floor Sensor
Danfoss Heating Solutions VIUHR402 © Danfoss 05/2011
16
Loading...