Daikin UAT180AMY1, UATY180AMY1, UAT240AMY12, UATY240AMY12, UAT280AMY12 Installation manual [fr]

...
INSTALLATION MANUAL
Models UAT180AMY1 UATY180AMY1 UAT240AMY12 UATY240AMY12 UAT280AMY12 UATY280AMY12 UAT320AMY12 UATY320AMY12 UAT450AMY1 UATY450AMY1 UAT560AMY1 UATY560AMY1 UAT700AMY1 UATY700AMY1 UAT850AMY1B UATY850AMY1B UATC10AMY1 UATYC10AMY11 UATC12AMY1 UATYC12AMY11 UATP180AMY1 UATYP180AMY1 UATP240AMY1 UATYP240AMY1 UATP280AMY1 UATYP280AMY1 UATP320AMY1 UATYP320AMY1 UATP450AMY1 UATYP450AMY1 UATP560AMY1 UATYP560AMY1 UATP700AMY1 UATYP700AMY1 UATP850AMY1B UATYP850AMY1B UATPC10AMY1 UATYPC10AMY11 UATPC12AMY1 UATYPC12AMY11
Installation Manual
Rooftop Package Units
Installationshandbuch
Kompaktanlage Für Dachmontage
Conditionneurs D’air En Toiture
Installatiehandboek
Compactsysteem Voor Dakmontage
Manual De Instalación
Unidades Del Conjunto Del Tejado
Manuale Di Installazione
Unità A Pacchetto Per Installazione Sul Tetto
Εγхειρίδιο Εγκατάστασης
Μονάδες Συσκευασίας Της Κορυφής Της Oροφής
Manual De Instalação
Unidades De Conjuntos De Telhado
Руководство По Установке
Компактные Установки Для Кондиционирования
Воздуха, Монтируемые На Крыше Здания
Kurulum kılavuzu
Çatı Tipi Ambalaj Üniteleri
IM-RTA-0107(2)-DAIKIN (DENV)
Part No.: R08019030001B
English
Deutsch
Français
Nederlands
Español
Italiano
Ελληνικά
Português
Русский
Türkçe
UAT(Y)(P)180
OUTLINE AND DIMENSIONS
(unit ; mm) * Except : Drain size. (unit ; inch)
20 150 150 150 150 20
668
Supply air duct fl ange
208
208
668 224
Supply air
668
Return air
10
49 10
24 125 125 24
16- ø3 Holes
224
1000
35
Supply air
Return air
412 132 297
125
A
25
46
208
668
224
51 1100 51
71
50
4-15X25 Mtg. holes
265 2651000
437
1530
Control box
Wiring hole
B
1142
1100
25
46
Hanger (4 places)
Drain R1
34 150 150 150 150 34
1192
Return air duct fl ange
25
668
Detail B Detail A
Condenser Air inlet
10
49 10
36 170 170 36
16- ø3 Holes
15
(1342)
25
25
25
15
(1342)
UAT(Y)(P)240, 280, 320 - Side fl ow
10
60 150 150 150 150 150 150 60
1020
Supply air duct fl ange
1020 173107
Supply air
1020
Return air
49
10
18.5 100 100 100 18.5
21- ø3
Holes
173107
1000
41135
337
75
412
1300 51
51
Supply air
Return air
71
107
173 1020
50
4-15X25 Mtg. holes
265 2651000
Control box
437
Drain R1
Wiring hole
Check Joint
1530
A
B
25
46
1342
1300
1392
25
46
Hanger (4 places)
60 150 150 150 150 150 150 60
1020
Return air duct fl ange
25
15
Detail B
(1342)
25
Condenser Air inlet
25
Detail A
10
49 10
36 170 170 36
20- ø3
25
15
(1342)
i
UAT(Y)(P)240, 280, 320 - Down fl ow
OUTLINE AND DIMENSIONS
155
1058
87
*(4)RT80, 100A only
372
140 46
Return air duct fl ange
19-ø3 Holes
Condenser Air inlet
25
10
1038
10
10
Detail B
49
160160320
160160
49
15
(1342)
25
96
160160
832
160160
96
16-ø3 Holes
10
281
100 100
Supply air duct fl ange
261
4041
10
812
10
10
25
15
25
1000
Control box
9
Supply air
1530
Condenser Air inlet
9
A
B
265
C
Detail A
25
46
1300
1342
1392
25
46
Hanger (4 places)
Drain R 1
Wiring hole
281
637
372
45
Return air
Supply air
View C (Bottom view)
242
832
226
51
1300
51
1000
71
265
Return air
437
4-15X25 Mtg. holes
(1342)
1058
49
160160160160160160
49
140
46
368
10
UAT(Y)(P)450, 560 - Side fl ow
AB C.O 1670 1200 H.P 1800 1330
10
462
Return air
49 10
51 120 120 120 51
72 200 200 200 200 200 200 72
1744
Supply air duct flange
1744123
Supply air
123
Return air
* C.O. only
1744
123
26- ø3 Holes
123
1200
51
1990
51
35462
Supply air
151
428
124
123
1744
123
4-15X25 Mtg. holes
235 235
Return air
483
77
50
Drain R1
B
A
Condenser Air inlet
A
B
Hanger (4 places)
25
46
25
Detail A
72 200 200 200 200 200 200 200 200 72
1990
46
2032
25
2082
Condenser Air inlet
1744
Return air Duct fl ange
25
Detail B
Control box
HP1
HP2
LP1
LP2
Check Joint
Wiring hole
15
15
25
(2032)
(2032)
25
Condenser Air inlet
10
428
26-ø3 Holes
10
3434 120120120
49
ii
UAT(Y)(P)450, 560- Down fl ow
1041782
717
79
372
Return air
359
Supply air
OUTLINE AND DIMENSIONS
264294
1990
1432
A
46
1990
25
2032
2082
25
Detail A
25
15
2032
1782
46 46140140
91
20020020020020020020020091
372
Return air duct fl ange
10
1762
1432
180 180180
180180180180
359
120 120 59.559.5
86
10
1412
Supply air duct fl ange
104
View C (Bottom view)
* C.O. only
RT-A 1670 1200
RT-AR 1800 1330
UAT(Y)(P)700, 850
43 43
12080120 120 120
10
566
AB
25
20-ø3
2200
144
Supply air
1912
1200
86
51 51
77
235
8
Return air
483
4-15X25 Mtg. holes
B
Condenser Air inlet
Supply air
8
Drain R1
A
B
235
C
46
Hanger
(4 places)
25
25
Detail B
Wiring hole
1146 383383144 144
15
2032
25
Condenser Air inlet
10
368
Control box
l
r
22.5
15
27.5
150 150 150 15080 80
758
10
Detail A
10
24-ø3 Holes
Condenser Air inlet
80
10
51
10 10
28-ø3
339
22-ø3 Holes
10
Supply air duct Flange
165 100
566
Supply air
640510
640
2200
120 120 120 120 80 80
Drain R1
80
10
758
Return air
Return air
25
23 2768
144
80
1302
1735
320
2850
2720
iii
Condenser Air inlet
A
Return air duct fl ange
50
Condenser Air inlet
Control
box
Wiring hole
1302
150 150 150 150 150
150 150 150
51
Condenser Air inlet
10
UAT(Y)(P)C10, C12
OUTLINE AND DIMENSIONS
AIR INLET
CONDENSER
516 1220 516
A
3148
3180
3100
BOX
CONTROL
AIR INLET
CONDENSER
AIR INLET
CONDENSER
WIRING HOLE
SUPPLY AIR
22.5
15
DETAIL A
27.5
RETURN AIR
2252
80
100
660
782
62
SUPPLY AIR
1974
1650
AIR
RETURN
892 526
210
DRAIN 1"
iv
INSTALLATION MANUAL
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons. This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
SAFETY PRECAUTIONS
English
Original Instruction
! WARNING
• Installation and maintenance should be performed by qualifi ed persons who are familiar with local code and regulation, and experienced with this type of appliance.
• All fi eld wiring must be installed in accordance with the national wiring regulation.
• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.
• The unit must be GROUNDED to prevent possible hazard due to insulation failure.
• All electrical wiring must not touch the refrigerant piping, or any moving parts of the fan motors.
• Confi rm that the unit has been switched OFF before installing or servicing the unit.
• Disconnect from the main power supply before servicing the air conditioner unit.
• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fi re hazards.
• Keep the air-conditioner units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. (Depending on the type and source of the electrical waves, static may be heard even when more than 1m away).
IMPORTANT
ENGLISH
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type: R407C
(1)
GWP
(1)
The refrigerant quantity is indicated on the unit name plate. Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.
value: 1652.5
GWP = global warming potential
! CAUTION
Please take note of the following important points when installing.
Do not install the unit where leakage of fl ammable gas may occur.
If gas leaks and accumulates around the unit, it may
cause fi re ignition.
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it
may cause water leakage which will dampen the furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to
the compressor.
Ensure that the unit’s panel is closed after service or
installation.
Unsecured panels will cause the unit to operate
noisily.
Sharp edges and coil surfaces are potential locations
which may cause injury hazards.
Avoid from being in contact with these places.
Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit. If this is not
done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user.
Do not operate any heating apparatus too close to the
air conditioner unit.
Donʼt use joined and twisted wires for incoming power supply.
The equipment is not intended for use in a potentially explosive atmosphere.
NOTICE
Disposal Requirement
Dismantling of the unit, treatment of the refrigerant, oil and other parts must be done in accordance with the applicable legislation.
1
INSTALLATION OF THE UNIT
1.1 Location For Installation
Install the unit in such way that air distributed by the unit cannot be drawn in again (as in the case of short circuit
of discharge air). Allow suffi cient space for maintenance around the unit.
When two or more units are installed in a location, they must be positioned such that one unit will not be taking
the discharge air from another unit.
1.2 Unit Support
1. The fi gure shows the use of the roof curb for mounting these units.
Roof curb
Unit
Seal with tar
Roof deck
2. The curb should be sealed and fi xed to the roof by weather stripping. A suggested means of sealing the unit and roof curb as shown in the left.
6 - ø15 Unit mounting holes
4 - ø15 Roof mounting holes
Roof curb
1.3 Duct Construction
These unit are equiped with supply and return air openings. Duct connection to the unit should be made with duct fl anges
and secured directly to the air openings with fl exible duct connectors to avoid normal noise transmission.
To prevent air leakage, all duct seams should be sealed.
Ducts in the spaces that not air-conditioned, must be insulated.
Ducts exposed to the outside must be weather proofed.
Ducts that entering building through the roof, the entering should be sealed with weather stripping to prevent the rain,
sand, dust etc. from entering the bulding.
Correct size of fi lter must be install at the return air duct.
! CAUTION
Do not install the unit at altitude over 2000m
2
INSTALLATION OF THE UNIT
1.4 Unit Lifting
UAT 180~560
Hanger brackets at 4 corner of the unit are used for unit lifting purpose.
The angle A of the chain should be at least 45°, and insulation should be added at 4 corner of the chain to prevent the damage of the panel when lifting.
1.5 Drain piping
A 1 FPT condensate drain fi tting is provided. The drain pipe
can be led out at the front side.
The drain pipe must be provided with a trap on the outside of
the unit and also installed at an incline for proper drainage, as shown in the right.
To prevent condensate formation and leakage, provide the drain
pipe with insulation to safeguard against sweating.
Upon completion of the piping work, check that there is no
leakage and that the water drains off properly.
The drain piping should have a drain trap.
Hanger Bracket
Spreader Bar
Chain
UAT 700, 850
English
Chain
A
Lifting Beam
C
A
A  70mm B 2C C 2X ESP
Drain trap
B
Drain piping
The drain pipe should extend below this level.
Note: ESP = External Static Pressure Drain trap for condensate
Lifting Holes for shackle
(4 corners)
UAT C10, C12
3
INSTALLATION OF THE UNIT
1.6 Space required around units (unit ; mm)
All space value ; minimum clearance
UAT 180~320
Evaporator coil, air fi lter service
1000
Condenser
300
inlet
Electrical control circuit & compressor
700
service
(min clearance)
Condenser outlet
1500
300
UAT 450, 560
Evaporator coil, air fi lter service
Evaporator coil, air fi lter service
1000
1000
(min clearance)
500
Condenser inlet
(min clearance)
Condenser outlet
1500
Condenser inlet
300
Electrical
300
700
control circuit
& compressor
service
UAT 700~C12
Condenser
(min clearance)
1000
2000
(min clearance)
Evaporator coil,
motor service
inlet
1000
Electrical control circuit & compressor
1500
service
1000
Condenser
inlet
1000
Condenser outlet
3000
(min clearance)
4
1.7 Unit conversion
INSTALLATION OF THE UNIT
Please check for accessory parts as below. (Packed in the unit, and available for convertible unit only)
1. Side inlet cover 1 piece
2. Casing leg
2 pieces UAT (Y)(P)240, 280, 320 4 pieces UAT (Y)(P)450, 560
In the case of converting to down fl ow unit, change according to the following steps.
STEP 1
Remove top panel
STEP 2
2. Additional casing leg (Accessory parts)
English
Remove service panel
STEP 3
Re-install supply air cover
Re-install fan assy
Remove duct fl ange
Remove duct fl ange
Remove supply air cover
Remove
Remove low cover
STEP 4
Re-install top panel
1. Additional side inlet cover (Accessory parts)
Re-install service panel
5
PHYSICAL DATA
COOLING ONLY (R22)
MODEL UAT180 UAT240 UAT280 UAT320 UAT450 REFRIGERANT R22 REFRIGERANT CHARGE kg 5.2 4.0 5.9 6.2 4.5 x 2 EVAPORATOR AIR FLOW CFM 1800 2826 3532 3600 5651
EXTERNAL STATIC PRESSURE mmAq 10 20 CONDENSER AIR FLOW CFM 4500 5650 8000 11300
CONTROL SLM CONTROLLER SEQUENTIAL CONTROLLER CONTROL WIRE LENGTH (STANDARD / MAX) : SIZE m : mm COMPRESSOR (TYPE / QUANTITY) SCROLL / 1 SCROLL / 2 AIR FILTER (TYPE / QUANTITY) WASHABLE SARANET / 1 WASHABLE SARANET / 2 AIR FILTER DIMENSION (LENGTH x WIDTH x THICKNESS) mm 820 x 615 x 1 1020 x 615 x 1 840 x 667 x 1
MODEL UAT560 UAT700 UAT850 UATC10 UATC12 REFRIGERANT R22 REFRIGERANT CHARGE kg 5.9 x 2 10.5 x 2 10.4 x 2 16.5 / 19.5 19.5 x 2 EVAPORATOR AIR FLOW CFM 6710 8000 9600 11000 12500
EXTERNAL STATIC PRESSURE mmAq 20 30 CONDENSER AIR FLOW CFM 11300 20000
CONTROL SEQUENTIAL CONTROLLER CONTROL WIRE LENGTH (STANDARD / MAX) : SIZE m : mm COMPRESSOR (TYPE / QUANTITY) SCROLL / 2 AIR FILTER (TYPE / QUANTITY) WASHABLE SARANET / 2 WASHABLE SARANET / 2 & 4 AIR FILTER DIMENSION (LENGTH x WIDTH x THICKNESS) mm 840 x 667 x 1 1370 x 735 x 1 860 x 550 & 600 x 4
HEAT PUMP (R22)
MODEL UATY180 UATY240 UATY280 UATY320 UATY450 REFRIGERANT R22 REFRIGERANT CHARGE kg 4.5 4.7 5.6 6.0 4.7 x 2 EVAPORATOR AIR FLOW CFM 1800 2826 3532 3600 5651
EXTERNAL STATIC PRESSURE mmAq 10 20 CONDENSER AIR FLOW CFM 4500 5650 10000 11300
CONTROL SLM CONTROLLER SEQUENTIAL CONTROLLER CONTROL WIRE LENGTH (STANDARD / MAX) : SIZE m : mm COMPRESSOR (TYPE / QUANTITY) SCROLL / 1 SCROLL / 2 AIR FILTER (TYPE / QUANTITY) WASHABLE SARANET / 1 WASHABLE SARANET / 2 AIR FILTER DIMENSION (LENGTH x WIDTH x THICKNESS) mm 820 x 615 x 1 1020 x 615 x 1 840 x 667 x 1
MODEL UATY560 UATY700 UATY850 UATYC10 UATYC12 REFRIGERANT R22 REFRIGERANT CHARGE kg 5.6 x 2 10.5 x 2 9.4 x 2 16.0 / 20.5 20.5 x 2 EVAPORATOR AIR FLOW CFM 6710 8000 9600 11000 12500
EXTERNAL STATIC PRESSURE mmAq 20 30 CONDENSER AIR FLOW CFM 11300 20000
CONTROL SEQUENTIAL CONTROLLER CONTROL WIRE LENGTH (STANDARD / MAX) : SIZE m : mm COMPRESSOR (TYPE / QUANTITY) SCROLL / 2 AIR FILTER (TYPE / QUANTITY) WASHABLE SARANET / 2 WASHABLE SARANET / 2 & 4 AIR FILTER DIMENSION (LENGTH x WIDTH x THICKNESS) mm 840 x 667 x 1 1370 x 735 x 1 860 x 505 & 600 x 4
COOLING ONLY (R407C)
MODEL UATP180 UATP240 UATP280 UATP320 UATP450 REFRIGERANT R407C REFRIGERANT CHARGE kg 4.6 4.0 5.9 6.2 4.5 x 2 EVAPORATOR AIR FLOW CFM 1800 2826 3532 3600 5651
EXTERNAL STATIC PRESSURE mmAq 10 20 CONDENSER AIR FLOW CFM 4500 5650 8000 11300
CONTROL SLM CONTROLLER SEQUENTIAL CONTROLLER CONTROL WIRE LENGTH (STANDARD / MAX) : SIZE m : mm COMPRESSOR (TYPE / QUANTITY) SCROLL / 1 SCROLL / 2 AIR FILTER (TYPE / QUANTITY) WASHABLE SARANET / 1 WASHABLE SARANET / 2 AIR FILTER DIMENSION (LENGTH x WIDTH x THICKNESS) mm 820 x 615 x 1 1020 x 615 x 1 840 x 667 x 1
MODEL UATP560 UATP700 UATP850 UATPC10 UATPC12 REFRIGERANT R407C REFRIGERANT CHARGE kg 4.2 x 2 9.6 x 2 10.4 x 2 14.5 / 18.0 18.0 x 2 EVAPORATOR AIR FLOW CFM 6710 8000 9300 11000 12500
EXTERNAL STATIC PRESSURE mmAq 20 30 CONDENSER AIR FLOW CFM 11300 20000
CONTROL SEQUENTIAL CONTROLLER CONTROL WIRE LENGTH (STANDARD / MAX) : SIZE m : mm COMPRESSOR (TYPE / QUANTITY) SCROLL / 2 AIR FILTER (TYPE / QUANTITY) WASHABLE SARANET / 2 WASHABLE SARANET / 2 & 4 AIR FILTER DIMENSION (LENGTH x WIDTH x THICKNESS) mm 840 x 667 x 1 1370 x 735 x 1 860 x 505 & 600 x 4
HEAT PUMP (R407C)
MODEL UATYP180 UATYP240 UATYP280 UATYP320 UATYP450 REFRIGERANT R407C REFRIGERANT CHARGE kg 4.3 4.7 5.6 6.0 5.0 x 2 EVAPORATOR AIR FLOW CFM 1800 2826 3532 3600 5651
EXTERNAL STATIC PRESSURE mmAq 10 20 CONDENSER AIR FLOW CFM 4500 5650 10000 11300
CONTROL SLM CONTROLLER SEQUENTIAL CONTROLLER CONTROL WIRE LENGTH (STANDARD / MAX) : SIZE m : mm COMPRESSOR (TYPE / QUANTITY) SCROLL / 1 SCROLL / 2 AIR FILTER (TYPE / QUANTITY) WASHABLE SARANET / 1 WASHABLE SARANET / 2 AIR FILTER DIMENSION (LENGTH x WIDTH x THICKNESS) mm 820 x 615 x 1 1020 x 615 x 1 840 x 667 x 1
MODEL UATYP560 UATYP700 UATYP850 UATYPC10 UATYPC12 REFRIGERANT R407C REFRIGERANT CHARGE kg 5.8 x 2 9.4 x 2 9.6 x 2 13.5 / 20.5 20.0 x 2 EVAPORATOR AIR FLOW CFM 6710 8000 9600 11000 12500
EXTERNAL STATIC PRESSURE mmAq 20 30 CONDENSER AIR FLOW CFM 11300 20000
CONTROL SEQUENTIAL CONTROLLER CONTROL WIRE LENGTH (STANDARD / MAX) : SIZE m : mm COMPRESSOR (TYPE / QUANTITY) SCROLL / 2 AIR FILTER (TYPE / QUANTITY) WASHABLE SARANET / 2 WASHABLE SARANET / 2 & 4 AIR FILTER DIMENSION (LENGTH x WIDTH x THICKNESS) mm 840 x 667 x 1 1370 x 735 x 1 860 x 505 & 600 x 4
L/S 850 1334 1667 1699 2667
L/S 2124 2667 3776 5333
2
7 / 15 : 0.14 - / 100 : 0.14
L/S 3167 3776 4531 5191 5899
L/S 5333 9439
2
- / 100 : 0.14
L/S 850 1334 1667 1699 2667
L/S 2124 2667 4719 5333
2
7 / 15 : 0.14 - / 100 : 0.14
L/S 3167 3776 4531 5191 5899
L/S 5333 9439
2
- / 100 : 0.14
L/S 850 1334 1667 1699 2667
L/S 2124 2667 3776 5333
2
7 / 15 : 0.14 - / 100 : 0.14
L/S 3167 3776 4389 5191 5899
L/S 5333 9439
2
- / 100 : 0.14
L/S 850 1334 1667 1699 2667
L/S 2124 2667 4719 5333
2
7 / 15 : 0.14 - / 100 : 0.14
L/S 3167 3776 4531 5191 5899
L/S 5333 9439
2
- / 100 : 0.14
6
ELECTRICAL DATA
COOLING ONLY (R22)
MODEL UAT180 UAT240 UAT280 UAT320 UAT450 POWER SUPPLY V/ph/Hz 400 / 3N ~ / 50 VOLTAGE RANGE MAX CONTINUOUS CURRENT (COMP) FULL LOAD CURRENT (FLA, COMP) LOCKED ROTOR CURRENT (LRA, COMP)
MODEL UAT560 UAT700 UAT850 UATC10 UATC12 POWER SUPPLY V/ph/Hz 400 / 3N ~ / 50 VOLTAGE RANGE MAX CONTINUOUS CURRENT (COMP) FULL LOAD CURRENT (FLA, COMP) LOCKED ROTOR CURRENT (LRA, COMP)
HEAT PUMP (R22)
MODEL UATY180 UATY240 UATY280 UATY320 UATY450 POWER SUPPLY V/ph/Hz 400 / 3N ~ / 50 VOLTAGE RANGE MAX CONTINUOUS CURRENT (COMP) FULL LOAD CURRENT (FLA, COMP) LOCKED ROTOR CURRENT (LRA, COMP)
MODEL UATY560 UATY700 UATY850 UATYC10 UATYC12 POWER SUPPLY V/ph/Hz 400 / 3N ~ / 50 VOLTAGE RANGE MAX CONTINUOUS CURRENT (COMP) FULL LOAD CURRENT (FLA, COMP) LOCKED ROTOR CURRENT (LRA, COMP)
COOLING ONLY (R407C)
MODEL UATP180 UATP240 UATP280 UATP320 UATP450 POWER SUPPLY V/ph/Hz 400 / 3N ~ / 50 VOLTAGE RANGE MAX CONTINUOUS CURRENT (COMP) FULL LOAD CURRENT (FLA, COMP) LOCKED ROTOR CURRENT (LRA, COMP)
V A 14.0 23.0 26.9 27.5 23.0 x 2 A 12.1 15.6 16.9 22.3 15.6 x 2 A 74 95 118 118 95 x 2
V A 26.9 x 2 A A
V A 17.0 22.0 31.0 27.5 22.0 x 2 A 15.0 19.5 23.0 22.3 19.5 x 2 A 101 84 81 118 84 x 2
V A 31.0 x 2 A A
V A 14.0 23.0 26.9 31.0 23.0 x 2 A 13.0 15.9 16.9 22.3 15.6 x 2 A 74 95 118 118 95 x 2
16.9 x 2 22.3 x 2 30.0 x 2 24.0, 30.0 30.0 x 2 118 x 2 118 x 2 174 x 2 175, 215 215 x 2
23.0 x 2 22.3 x 2 30.0 x 2 24.0, 30.0 30.0 x 2
81 x 2 118 x 2 174 x 2 175, 215 215 x 2
27.5 x 2 42.0 x 2
27.5 x 2 42.0 x 2
380 ~ 415
380 ~ 415
380 ~ 415
380 ~ 415
380 ~ 415
35.0, 50.0
35.0, 50.0
50.0 x 2
50.0 x 2
English
MODEL UATP560 UATP700 UATP850 UATPC10 UATPC12 POWER SUPPLY V/ph/Hz 400 / 3N ~ / 50 VOLTAGE RANGE MAX CONTINUOUS CURRENT (COMP) FULL LOAD CURRENT (FLA, COMP) LOCKED ROTOR CURRENT (LRA, COMP)
HEAT PUMP (R407C)
MODEL UATYP180 UATYP240 UATYP280 UATYP320 UATYP450 POWER SUPPLY V/ph/Hz 400 / 3N ~ / 50 VOLTAGE RANGE MAX CONTINUOUS CURRENT (COMP) FULL LOAD CURRENT (FLA, COMP) LOCKED ROTOR CURRENT (LRA, COMP)
MODEL UATYP560 UATYP700 UATYP850 UATYPC10 UATYPC12 POWER SUPPLY V/ph/Hz 400 / 3N ~ / 50 VOLTAGE RANGE MAX CONTINUOUS CURRENT (COMP) FULL LOAD CURRENT (FLA, COMP) LOCKED ROTOR CURRENT (LRA, COMP)
V A 26.9 x 2 A A
V A 17.0 23.0 26.9 31.0 23.0 x 2 A 15.0 15.9 16.9 22.3 15.9 x 2 A 101 95 118 118 95 x 2
V A 26.9 x 2 A A
16.9 x 2 22.3 x 2 30.0 x 2 24, 30 30.0 x 2 118 x 2 118 x 2 174 x 2 175, 215 215 x 2
16.9 x 2 22.3 x 2 32.0 x 2 24, 30 30.0 x 2 118 x 2 118 x 2 174 x 2 175, 215 215 x 2
31.0 x 2 42.0 x 2
31.0 x 2 42.0 x 2
380 ~ 415
380 ~ 415
380 ~ 415
35.0, 50.0
35.0, 50.0
50.0 x 2
50.0 x 2
7
WIRE CONNECTION
All electrical work must be carried out by quali ed electrician and accordance with local supply requirement and
associated regulation.
Method for connecting electric wire
Before connecting the wire, consult the electric power company of jurisdiction.
1. The entire wiring diagram of unit. a
b
PE
g
c
2. Remote control wire connection. UAT(Y)(P)450, 560, 700, 850, C10, C12
LCD Remote
(Top case)
f
d
GND
+5 B A
remote control. Connect directly to connector 'CN2' on mainboard.
a. Power supply
Main switch/fuse
b.
(fi eld supply) Power supply
c.
wiring for unit
e
Unit
d.
e. Remote control
Connection wiring for
f.
unit & remote controller
g. Earth
Connection behind
Top case
Note: For UAT(Y)(P)180, 240, 280, 320, wire is attached the
3. Wiring connection to unit Remove the panel and connect the units power supply wires to terminal block, as shown below.
UAT(Y)(P)180, 240, 280, 320
UAT(Y)(P)450, 560
Terminal block
GND
+5
B A
Connection at
Mainboard
Connection Wire (fi eld supply)
UAT(Y)(P)180 only
Terminal block
Recommended switch box position
Recommended switch box position
UAT(Y)(P)700, 850, C10, C12
Terminal block
NOTE: While installing the circuit breaker onto the unit, make sure that the screws do not damage the components
(e.g. coil) inside of the unit.
The circuit breaker also can be installed without attaching to the unit.
8
5
N
2
3
4
OUTFAN2OUTFAN3 OUTFAN1
TRANSFORMER
NEUTRAL
DS1DS2DS3DS4
ROOM
ID4ID3ID2ID1
HP4HP3HP2HP1
ON/OFF
GND
A
5V
COMP1
COMP2
COMP3
COMP4
IN
FAN
HEATER1
HEATER2
4WV1
4WV2
4WV3
4WV4
OUTFAN 4
LIVE
B
NL3L2L1
1
UVW
A2
A1
RST
UVW
A2
A1
RST
UVW
A2
A1
RST
96
98
95
6
N
L3
L2
L1
R
U
T
R
E
S
E
T
6
8
5
2
W
2
1
T
L
N
N
1
O U T F A N 2
O U T F A N 1
R O O M
I D 4
1
2
2
NNN
R
E
S
E
T
6
8
5
2
W
2
1
T
E
WVU
RST
L
UVW
A2
A1
RST
RESET
96
98
95
62
UVW
A2
A1
RST
NNNN
N
TSR
NTS
R
WIRE CONNECTION
Arrangement of terminal block for controller are shown below.
CONTROL MODULE UAT(Y)(P)180 CONTROL MODULE UATY(P)450, 560
UATY(P) only
PCB
F1
TB1
Connector for remote control wires
52F1
T1
X1
X2
X3
51F1
Terminal Block for power supply wires
C
TB2
52C
52F2
51C
UATY(P) only
47
F1
TB1
Terminal Block for power supply wires
52F
662
47
51F1
51C1
NNLL33LL22LL1
52C252C1
51C2
TB2
NNNNNNN
UATY(P) only UATY(P) only
CONTROL MODULE UAT(Y)240, 280, UAT(Y)(P)320 CONTROL MODULE UAT(P)450, 560
Terminal Block for power supply wires
FZ
52F1
52C
RRSST
RRSST
UUVVW
WWVVU
51C
TB1
PCB
N
L
NNTTSSR
UATY240, 280 only
Connector for remote control wires
All except for UATY240, 280
X1
F1
TB1
AA1
AA2
X1
T E S
662
E R
995 998 996
52F2
AA1
RRSST
UUVVW
AA2
X2
T E S
662
E R
995 998 996
51C1
47
UATY(P) only
Terminal Block for power supply wires
52C252C1
51C2
PCB
44WWVV1
44WWVV2
O U T F A N 1
O U T F A N 2
X1 X2
52F2 52F3
47
Connector for remote control wires
R O O M
I D 4
PCB
English
Connector for remote control wires
LLIIVVE
CONTROL MODULE UATYP240, 280 CONTROL MODULE UAT(Y)(P)700
F1
PCB
52C
52F1
52F2
51C
TB1
X1
51F1
TB2
Terminal Block for power supply wires
CONTROL MODULE UAT(Y)(P)850
Connector for remote control wires
47
Connector for remote control wires
UATY(P) only
Terminal Block for power supply wires
CONTROL MODULE UAT(Y)(P)C10, C12
Connector for remote control wires
47
PCB
52C1
51C1
TB1
PCB
TB1
52C2
52F2
51C2
F1
52F
51F1
F1
Connector for remote control wires
52F1 &51F1
52F3
X2
X1
UATY(P) only
TB2&3
47
52F2
52C1
51C1
52C2
52F3
X1 X2
51C2
TB2 & 3
Terminal Block for power supply wires
Terminal Block for power supply wires
UATY(P) only
9
WIRE CONNECTION
Wiring Example and Selection of Circuit Breaker 380 ~ 415V, 3N ~ /50
MODEL
POWER CABLE
2
)
(mm
BREAKER
CAPACITY (A)
OVER CURRENT
PROTECTION SWITCH (A)
EARTH CABLE
(mm2 over)
UAT(Y)(P)180 8.4 32 32 8.4 UAT(Y)(P)240 8.4 32 32 8.4 UAT(Y)(P)280 13.3 50 50 13.3 UAT(Y)(P)320 13.3 50 50 13.3 UAT(Y)(P)450 13.3 50 50 13.3 UAT(Y)(P)500 21.2 63 63 21.2 UAT(Y)(P)700 33.6 80 80 33.6 UAT(Y)(P)850 42.4 100 100 42.4 UAT(Y)(P)C10 60.0 125 125 60.0 UAT(Y)(P)C12 60.0 125 125 60.0
Note:
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in fi xed wiring in accordance with local and national legislation.
The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse.
Fix the power supply wiring to control module. Connect control wiring to control terminal block through the control box’s hole.
Earth wiring must be connected.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used in protective tube.
! WARNING
• Before working on this unit, isolate from the power supply.
• Electrical wiring to this unit and the remote controller shall be installed in accordance with the appropriate requirements of the local wiring code.
OPERATING RANGE
Ensure the operating temperature is in allowable range.
Cooling (R22)
Cooling Only Unit & Cooling Mode For Heat Pump Unit
54 50
40
30
20
10
0
-5
Outdoor temp. (°C DB)
-10 10 15 20 25 30
24
Indoor temp. (°C WB) Indoor temp. (°C WB)
Heating (R22 & R407C)
Heat Pump Unit Only
20
15
10
Cooling (R407C)
Cooling Only Unit & Cooling Mode For Heat Pump Unit
50 46
40
30
20
10
0
-5
Outdoor temp. (°C DB)
-10 10 15 20 25 30
Note:
WB = Wet Bulb
• DB = Dry Bulb
24
5
0
-5
-10
Outdoor temp. (°C WB)
-15
10
15 20 25 30
Indoor temp. (°C DB)
! CAUTION:
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
27
10
SPECIAL PRECAUTIONS WHEN DEALING WITH R407C UNIT
R407C is a zeotropic refrigerant mixture which has zero
ozone depletion potential and thus conformed to Montreal Protocol regulation. It requires Polyester oil (POE) oil for its compressor's lubricant. Its refrigerant capacity and performance are about the same as the refrigerant R22.
POE or PVE oil is used as lubricant for R407C
compressor, which is different from the mineral oil used for R22 compressor. During installation or servicing, extra precaution must be taken not to expose the R407C system too long to moist air. Residual POE or PVE oil in the piping and components can absorb moisture from the air.
Refrigerant R407C is more easily affected by dust of
moisture compared with R22, make sure to temporarily cover the ends of the tubing prior to installation.
No additional charge of compressor oil is permitted.
No other refrigerant other than R407C.
Tools speci cally for R407C only (must not be used for
R22 or other refrigerant)
i) Manifold gauge and charging hose ii) Gas leak detector iii) Refrigerant cylinder / charging cylinder iv) Vacuum pump c/w adaptor v) Flare tools vi) Refrigerant recovery machine
Filter-dryer must be installed along the liquid line for
all R407C air conditioners. This is to minimise the contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve type. For a heat-pump system, install a two-way fl ow fi lter-dryer along the liquide line.
SERVICE AND MAINTENANCE
SERVICE OF THE FILTER
• Remove any dust adhering to the fi lter by using a vacuum cleaner or wash in lukewarm water (below 40°C) with a neutral cleaning detergent.
• Rinse the fi lter well and dry before placing it back onto the unit.
• Do not use gasoline, volatile substances or chemicals to clean the fi lter.
• Clean the fi lter at least once every 2 weeks. Or more frequently if neccesary.
English
Filter Position
The fi lters are mounted in front of the indoor heat exchanger. * (Air fi lter : special order or fi eld supply)
UAT(Y)(P)180,280,320,450,560 UAT(Y)(P)700,850
Filter
Filter cover
removed when servicing note: both side for unit 450, 560
Service panel
Filter
Filter cover
removed when servicing
11
VACUUMING AND CHARGING
The rooftop package units are factory pre-charged with suffi cient refrigerant. However, there may be a need for charge recovery during service and maintenance works. Therefore, some precautions must be taken to ensure optimum and trouble-free system operation:
(i) The system should be throughly vacuumed to ensure no incompressible gas and moisture in the system. (ii) Use a vacuum pump for R22 or R407C exclusively. Using the same vacuum pump for different refrigerants may damage
the vacuum pump or the unit.
(iii) The refrigerant should never be released directly into the environment. (iv) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can.
Invert cylinder
Dip-pipe
Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the bottom.
without dip-pipe
Liquid withdrawal
! CAUTION
• Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit thoroughly and then charge the unit with fresh R22 & R407C according to the amount recommended in the specifi cation.
TROUBLESHOOTING
If any malfunction of the air conditioner unit is noted for some simple trouble-shooting tips. Check the following fault conditions and causes for some simple troubleshooting tips. For any enquiries on spare part, please contact you authorized dealer.
Problem Causes Action
Unit does not run. Power failure. Press the [ON/OFF] after power restore.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Power supply wiring phase incorrect. Modify the wiring phase.
Compressor does not operate in 3 min after unit has started.
Air fl ow is low. Filter is fi lled with dust and dirt. Clean the fi lter.
Compressor operate continuously. Dirty air fi lter. Clean the air fi lter.
No cool air delivered during cooling cycle, or no hot air delivered during heating cycle.
On heating cycle, indoor fan stop suddenly. UAT(Y)(P)180,240,280,320 On heating cycle, delivered air does not warm enough suddenly. UAT(Y)(P)450,500,700,850
Protection against frequent starting. Wait for 3 min for the compressor to
start.
There are some obstacles at the air inlet or outlet of the units.
Temperature setting is too low (for cooling). Temperature setting is too high (for heating).
Temperature setting is too high (for cooling). Temperature setting is too low (for heating).
Unit is in defrosting cycle. Wait for a while.
Remove obstacles.
Reset the temperature.
Set the temperature lower. Set the temperature higher.
(It will be resumed after defrosting.)
If the fault persists, please call your authorized local dealer/serviceman.
12
UAT(Y)(P)180
AUSLEGUNG UND ABMESSUNGEN
(Gerät ; mm) * Außer: Ablaufgröße. (gerät ; zoll)
20 150 150 150 150 20
668
Zuluftkanal Flansch
208
208
668 224
Luftzufuhr
668
Rückluft
10
49 10
24 125 125 24
16-ø3 Öffnungen
224
1000
51 1100 51
35125 412 132 297
Luftzufuhr
Rückluft
A
25
46
208
668
224
4-15X25 Montageöffnungen
265 2651000
Steuerkasten
71
437
50
Verkabelungsöffnung
1530
B
1142
1100
25
46
Hänger (4 Stellen)
Drain R1
34 150 150 150 150 34
1192
Rückluftkanal Flansch
25
668
Detail B Detail A
Kondensator Lufteinlass
10
49 10
36 170 170 36
16-ø3 Öffnungen
15
(1342)
25
25
25
15
(1342)
UAT(Y)(P)240, 280, 320 - Seitenströmung
10
60 150 150 150 150 150 150 60
107
1020
Zuluftkanal Flansch
1020 173107
Luftzufuhr
1020
Rückluft
49
10
18,5 100 100 100 18,5
21- ø3
Öffnungen
173
1000
51 1300 51
41135
Luftzufuhr
75 337
Rückluft
412
71
107
1020
173
50
4-15X25 Montageöffnungen
265 2651000
Steuerkasten
437
Drain R1
Verkabelungsöffnung
Kontrollverbindung
1530
A
B
25
46
1342
1300
1392
25
46
Hänger (4 Stellen)
60 150 150 150 150 150 150 60
1020
Rückluftkanal Flansch
25
15
Detail B
Kondensator Lufteinlass
(1342)
25
25 Detail A
10
49 10
36 170 170 36
20- ø3
25
15
(1342)
i
AUSLEGUNG UND ABMESSUNGEN
UAT(Y)(P)240, 280, 320 - Abwärtsströmung
155
1058
87
*(4)RT80, 100A nur
25
15
25
1000
Steuer­kasten
9
Luftzufuhr
1530
Kondensator Lufteinlass
9
A
B
265
Hänger (4 Stellen)
Drain R 1
Verkabelungsöffnung
C
25
1342
25
46
1300
46
Detail A
1392
281
637
372
45
Rückluft
Luftzufuhr
Ansicht C (Unteransicht)
242
832
226
51
1300
51
1000
71
265
Rückluft
4-15X25 Montageöffnungen
437
(1342)
49
160160160160160160
1058
46
49
10
140
368
Kondensator Lufteinlass
25
Detail B
372
140 46
49
10
160160320
1038
Rückluftkanal Flansch
160160
49
10
10
19-ø3 Öffnungen
15
(1342)
25
100 100
96
160160
832
160160
96
10
16-ø3 Öffnungen
281
4041
10
812
Zuluftkanal Flansch
10
261
10
UAT(Y)(P)450, 560 - Seitenströmung
AB C.O 1670 1200 H.P 1800 1330
10
72 200 200 200 200 200 200 72
1744
Zuluftkanal Flansch
1744123
Luftzufuhr
123
Rückluft
* C.O. nur
1744
10
462
51 120 120 120 51
Rückluft
49
26- ø3
Öffnungen
123
123
1200
51
1990
51
35462151428124
Luftzufuhr
Rückluft
1744 123
123
4-15X25 Montageöffnungen
235 235
483
77
50
B
Drain R 1
A
Kondensator Lufteinlass
A
B
Hänger (4 Stellen)
25
46
25
Detail A
72 200 200 200 200 200 200 200 200 72
1990
46
2032
25
2082
Kondensator Lufteinlass
1744
Rückluftkanal Flansch
25
Detail B
Steuerkasten
HP1
HP2
LP1
LP2
Kontrollverbindung
kabelungsöffnung
Ver
25
15
(2032)
15
25 (2032)
26-ø3 Öff
Kondensator Lufteinlass
10
428
nungen
10
34
120120120
34
49
ii
AUSLEGUNG UND ABMESSUNGEN
UAT(Y)(P)450, 560 - Abwärtsströmung
1041782
717
79
372
Rückluft
359
264294
1432
Luftzufuhr
1990
A
46
1990
25
2032
2082
25
Detail A
25
15
2032
1782
46 46140140
91
20020020020020020020020091
372
10
1432
1762
Rückluftkanal Flansch
86
180
180180
180180180180
359
120120 59,559,5
10
1412
Zuluftkanal Flansch
104
Ansicht C (Unteransicht)
* C.O. nur
RT-A 1670 1200
RT-AR 1800 1330
UAT(Y)(P)700, 850
43 43
12080120 120 120
10
566
AB
25
20-ø3
2200
144
Luftzufuhr
1912
1200
86
51 51
77
4-15X25 Montageöffnungen
235
8
Rückluft
483
B
8
Drain R 1
A
Kondensator Lufteinlass
Luftzufuhr
B
235
C
46
Aufhänger
(4 stellen)
25
25
Detail B
1146 383383144 144
15
2032
25
Kondensator Lufteinlass
Verkabelungsöffnung
10
368
Steuerkasten
l
r
22,5
15
27,5
150 150 150 15080 80
758
10
Detail A
10
24-ø3 Öffnungen
Kondensator Lufteinlass
80
10
51
10 10
28-ø3
339
22-ø3 Öffnungen
10
Zuluftkanal Flansch
165 100
Luftzufuhr
640510
566
640
2200
120 120 120 120 80 80
Drain R1
10
80
758
Rückluft
Rückluft
25
23 2768
144
80
1302
1735
320
2850
2720
iii
Kondensator Lufteinlass
A
Rückluftkanal Flansch
50
Kondensator Lufteinlass
Steuerkasten
1302
150 150 150 150 150
150 150 150
10
51
Kondensator Lufteinlass
Verkabelungsöffnung
UAT(Y)(P)C10, C12
AUSLEGUNG UND ABMESSUNGEN
LUFTEINLASS
KONDENSATOR
516 1220 516
A
3148
3180
3100
STEUERKASTEN
LUFTEINLASS
KONDENSATOR
LUFTEINLASS
KONDENSATOR
VERKABELUNGSÖFFNUNG
22,5
15
DETAIL A
27,5
RÜCKLUFTLUFTZUFUHR
80
2252
782
62
100
660
LUFTZUFUHR
1974
1650
RÜCKLUFT
892 526
210
Abfl uss 1"
iv
INSTALLATIONSHANDBUCH
Das vorliegende Handbuch enthält die Installationsanweisungen für einen sicheren und ordnungsgemäßen Betrieb dieser Anlage. Je nach den örtlichen Gegebenheiten können spezielle Anpassungen notwendig sein. Vor der Inbetriebnahme des Klimagerätes dieses Handbuch bitte aufmerksam zur Kenntnis nehmen und für künftigen Bedarf aufbewahren. Dieses Gerät für den Betrieb durch Fachleute oder geschulte Benutzer in Geschäften, der Leichtindustrie und in landwirtschaftlichen Betrieben sowie für gewerbliche Zwecke durch Laien ausgelegt. Das Gerät ist nicht konzipiert, um von folgenden Personengruppen einschließlich Kindern benutzt zu werden: Personen mit eingeschränkten körperlichen, sensorischen oder geistigen Fähigkeiten oder Personen mit mangelhafter Erfahrung oder Wissen, es sei denn, sie sind von einer Person, die für ihre Sicherheit verantwortlich ist, darin unterwiesen worden, wie das Gerät ordnungsgemäß zu verwenden und zu bedienen ist. Kinder sollten beaufsichtigt werden, um sicher zu sein, dass sie nicht mit dem Gerät spielen.
VORSICHTMASSNAHMEN
Deutsch
! ACHTUNG
• Die Installation und Wartung muß durch qualifi zietes Personal erfolgen, Welches mit den örtlichen Bestimmungen und diesem Ausrüstungstyp vertraut ist.
• Die gesamte E-Verkabelung hat in Übereinstimmung mit den landesspezifi schen Anschlußvorschriften zu erfolgen.
• Vor dem Kabelanschluß gemäß Schaltbild ist sicherzustellen, daß die Betriebsspannung mit der auf dem Datenschild des Gerätes angegebenen Spannung übereinstimmt.
• Das Gerät ist zum Schutz gegen fehlerhafte Isolierungen und entsprechende Risiken zu ERDEN.
• Die Kabel dürfen weder mit der Kühlmittelleitung, noch mit den beweglichen Teilen der Gebläsemotoren in Berührung kommen.
• Vor der Installation oder Wartung der Anlage ist sicherzustellen, daß das Gerät ausgeschaltet ist (OFF).
• Ziehen Sie vor der Wartung der Klimaanlage den Stecker aus der Steckdose.
• NICHT das Stromkabel herausziehen, wenn das Gerät noch eingeschaltet ist. Ein elektrischer Schlag oder ein Wohnungsbrand kann die Folge sein.
• Halten Sie für die Klimageräte, Stromkabel und Transmissionskabel einen Abstand von 1m zu Fernsehgeräten und Radios ein, um verzerrte Bilder und elektrostatische Aufl adung zu vermeiden. (abhängig von Type und Quelle der elektrischen Wellen, können statische Entladungen auch noch hörbar sein bei Abständen von mehr als 1m).
WICHTIG
DEUTSCH
Wichtige Informationen hinsichtlich des verwendeten Kältemittels
Dieses Produkt enthält fluorierte Treibhausgase, die durch das Kyoto-Protokoll abgedeckt werden. Lassen Sie Gase nicht in die Atmosphäre ab. Kältemitteltyp: R407C
(1)
GWP
(1)
Die Kältemittelmenge ist auf dem Namensschild des Geräts vermerkt. Überprüfungen in Bezug auf Kältemittellecks müssen in regelmäßigen Abständen je nach den europäischen oder nationalen Bestimmungen durchgeführt werden. Kontaktieren Sie bitte Ihren örtlichen Händler bezüglich weiterer Informationen.
Wert: 1652.5
GWP = Treibhauspotential
! VORSICHT
Vor der Installation sind folgende wichtige Punkte zu prüfen.
Gerät nicht installieren, falls ein Leck entzündbaren Gases festgestellt wird.
Es besteht Feuergefahr, wenn Gas aus der Anlage
entweicht und sich in der Umgebung ansammelt.
Die Kondensat-Abflußleitung muß sachgemäß
angeschlossen sein.
Ist die Abfl ussleitung nicht korrekt angeschlossen,
besteht Gefahr, daß durch auslaufendes Wasser das Mobiliar feucht wird.
Gerät nicht überlasten.
Das Gerät ist werkseitig vorgefüllt. Im Falle einer Überfüllung besteht die Gefahr einer
Überbelastung oder sonstige Beschädigung des Kompressors.
Nach Installation oder Wartung ist sicherzustellen,
daß die Geräteabdeckung wieder montiert ist.
Eine mangelhafte Befestigung der Abdeckung führt
zu Geräuschentwicklung während des Betriebs.
Scharfe Kanten und Wärmetauscher ächen stellen
eine Gefahrenquelle dar. Jeglicher Kontakt mit diesen Stellen ist zu vermeiden.
Vor Abschalten der Stromzufuhr muss der ON/OFF­Schalter der Fernbedienung auf „OFF“ gestellt werden, um eine versehentliche Fehleinstellung zu vermeiden.
Andernfalls schaltet sich bei Wiederherstellung der Stromzufuhr das Kühlgebläse automatisch wieder ein und kann somit für den Benutzer oder Wartungspersonal ein unerwartetes Risiko darstellen.
Keine Heizgeräte zu dicht bei der Klimaanlage
einschalten.
Verwenden Sie zur Stromversorgung keine zusammengefügten und geknickte Kabel.
Das Gerät ist nicht zur Verwendung in einer potentiell explosiven Atmosphäre konzipiert.
Übersetzung der Original-Anleitungen
BEMERKUNG
Vorschriften zur Entsorgung
Die Demontage des Geräts, die Behandlung des Kühlmittels, des Öls und anderer Teile muss in Übereinstimmung mit relevanten Vorschriften durchgeführt werden.
1
INSTALLATION DES GERÄTES
1.1 Aufstellort
Das Gerät ist so zu installieren, dass die abgeführte Luft nicht wieder einströmen kann (im Fall von Kurzschluss bei
Abluft). Auf ausreichenden Abstand für die Wartung rund um das Gerät achten.
Bei Installation von zwei oder mehreren Geräten an einem Ort, sind diese so zu positionieren, daß die Abluft eines
Gerätes nicht von dem anderen Gerät angesaugt wird.
1.2 Maßeinheit Unterstützung
1. Die Darstellung zeigt die Verwendung ders Roof Curbs für die Befestigung dieser Geräte.
Roof Curb
Gerät
Mit Teer abdichten
Dachterrasse
2. Die Kante muss abgedichtet werden und mit dem Dach durch Dichtungsleisten fi xiert werden. Ein Vorschlag zur Abdichtung des Geräts und des Roof Curbs sind links abgebildet.
6 - ø15 Montierlöcher Gerät
4 - ø15 Montierlöcher Dach
Roof Curb
1.3 Leitungsverlegung
Dieses Gerät ist mit Versorgungs- und Rückluftöffnungen ausgestattet. Die Leitungsverbindung zum Gerät sollte mit
Leitungsfl ansch durchgeführt werden und direkt an die Luftöffnungen mit fl exiblen Leitungsverbindern befestigt werden, um Störgeräusche zu minimieren.
Um das Entweichen von Luft zu verhindern, sollten alle Leitungsnahtstellen abgedichtet werden.
Leitungen, die nicht klimatisiert sind, müssen isoliert werden.
Leitungen die offen liegen, müssen wetterbeständig sein.
Leitungen, die durch das Dach ins Gebäude geführt werden, sollten an der Eintrittsstelle mit Dichtungsleisten abgedichtet
werden, um zu verhindern, dass Regen, Sand, Staub, usw. in das Gebäude eindringen.
Die korrekte Filtergröße muss in der Rückluftleitung eingebaut sein.
! VORSICHT
Das Gerät nicht in Höhenlagen über 2000m installieren
2
INSTALLATION DES GERÄTES
1.4 Heben des Geräts
UAT 180~560
Maßeinheit werden anhebende Aufhängerhaltewinkel bei Ecke 4 der Maßeinheit für Maßeinheit anhebenden Zweck benutzt.
Der Winkel A der Kette sollte mindestens 45° sein und Isolierung sollte bei Ecke 4 der Kette hinzugefügt werden, um die Beschädigung der Verkleidung beim Anheben zu verhindern.
1.5 Ablassrohr
A 1 FPT Abfl ussarmatur üfr Kondensat wird mitgeliefert. Das
Ablaßrohr kann auf der Vorderseite herausgeführt werden.
Das Ablaufrohr muss mit einem Verschluss außerhalb des
Geräts ausgestattet sein und ebenfalls für korrekte Drainage an einem Gefälle installiert werden, wie in der rechten Abbildung dargestellt.
Um Kondensat und Leckage zu vermeiden, sollte das Ablaufrohr
isoliert sein, um kein Schwitzen zu gewährleisten.
Ist die Abfl ussleitung nicht korrekt angeschlossen, besteht
Gefahr, daß durch auslaufendes Wasser das Mobiliar feucht wird.
Anhänger-Auslegerarm
Spreizstange
Kette
UAT 700, 850
Kette
A
Deutsch
Hebebalken
Das Ablaßrohr sollte mit einen Wasserverschluss ausgestattet sein.
C
A
A  70mm B 2C C 2X ESP
Wasserverschluss
B
Ablassrohr
Das Ablaßrohr sollte länger als dieses Niveau sein.
Hinweis: ESP = External Static Pressure
(Externer statischer Druck)
Wasserverschluss für Kondensat
Hebeöffnungen für
Schäkel
(4 ecken)
UAT C10, C12
3
INSTALLATION DES GERÄTES
1.6 Benötigter Raum um das Gerät (Gerät ; mm)
Alle angegebenen Werte; Mindestwerte
UAT 180~320
Wartung des Luftfi lters, luft lter-wartung
1000
Kondensa-tor-
300
einlass
300
Wartung des elektrischen Sicherungsstromkreises
700
und wartung des kompressors
(Minimale aussparung)
Kondensa­torauslass
1500
UAT 450, 560
Wartung des Luftfi lters, luft lter-wartung
Wartung des Luftfi lters, luft lter-wartung
1000
1000
(Minimale aussparung)
Kondensa-tor-
500
einlass
300
300 Kondensa-tor­einlass
(Minimale aussparung)
Kondensa-torauslass
1500
700
Wartung des
elektrischen Siche-
rungsstromkreises
und wartung des
kompressors
UAT 700~C12
1000
Kondensa-
toreinlass
(Minimale aussparung)
1000
2000
(Minimale aussparung)
Wartung des Luftfi lters,
Motorwartung
Wartung des elektrischen Sicherungsstromkreises
1500
und wartung des kompressors
1000
Kondensa-
toreinlass
1000
Kondensa-torauslass
3000
(Minimale aussparung)
4
INSTALLATION DES GERÄTES
1.7 Umrechnung
Überprüfen Sie bitte die unten aufgeführten Zubehörteile. (Im Gerät und nur für umwandelbare Gerät verfügbar).
1. Abdeckung für Seiteneinlauf 1 Stück
2. Gehäusefuß
2 Stücke UAT (Y)(P)240, 280, 320 4 Stücke UAT (Y)(P)450, 560
Die Umwandlung des Geräts auf Down Flow, geschieht folgendermaßen.
SCHRITT 1
Oberes paneel entfernen
SCHRITT 2
Wartungspaneel entfernen
Kanalfl ansch entfernen
Deutsch
2. Zusätzlicher Gehäusefuß (Zubehörteil)
Versorgungsluftdeckel entfernen
Entfernen
SCHRITT 3
Luftversorgungsdeckel wieder installieren
Fan Assy wiederinstal­lieren
1. Zusätzlicher Seiteneinlassdeckel (Zubehörteil)
Kanalfl ansch entfernen
Niedrige Abdeckung entfernen
SCHRITT 4
Oberes paneel wieder installieren
Schalttafel wieder installieren
5
TECHNISCHE DATEN
NUR KÜHLEN (R22)
MODELL UAT180 UAT240 UAT280 UAT320 UAT450 KÜHLMITTEL R22 KÄLTEMITTELFÜLLUNG kg 5,2 4,0 5,9 6,2 4,5 x 2 VERDAMPFER LUFTTROM CFM 1800 2826 3532 3600 5651
EXTERNER STATISCHER DRUCK mmAq 10 20 KONDENSATOR LUFTSTROM CFM 4500 5650 8000 11300
STEUERUNG SLM CONTROLLER SEQUENTIAL CONTROLLER LÄNGE DER STEUERLEITUNG (STANDARD/MAX) : GRÖßE m : mm KOMPRESSOR (TYP/MENGE) SPIRALE/1 SPIRALE/2 LUFTFI LTER (TYP/MENGE) WASHABLE SARANET/1 WASHABLE SARANET/2 LUFTFI LTERABMESSUNG (LÄNGE X BREITE X DICKE) mm 820 x 615 x 1 1020 x 615 x 1 840 x 667 x 1
MODELL UAT560 UAT700 UAT850 UATC10 UATC12 KÜHLMITTEL R22 KÄLTEMITTELFÜLLUNG kg 5,9 x 2 10,5 x 2 10,4 x 2 16,5 / 19,5 19,5 x 2 VERDAMPFER LUFTTROM CFM 6710 8000 9600 11000 12500
EXTERNER STATISCHER DRUCK mmAq 20 30 KONDENSATOR LUFTSTROM CFM 11300 20000
STEUERUNG SEQUENTIAL CONTROLLER LÄNGE DER STEUERLEITUNG (STANDARD/MAX) : GRÖßE m : mm KOMPRESSOR (TYP/MENGE) SPIRALE/2 LUFTFI LTER (TYP/MENGE) WASHABLE SARANET/2 WASHABLE SARANET/ 2 & 4 LUFTFI LTERABMESSUNG (LÄNGE X BREITE X DICKE) mm 840 x 667 x 1 1370 x 735 x 1 860 x 550 & 600 x 4
HEIZPUMPE (R22)
MODELL UATY180 UATY240 UATY280 UATY320 UATY450 KÜHLMITTEL R22 KÄLTEMITTELFÜLLUNG kg 4,5 4,7 5,6 6,0 4,7 x 2 VERDAMPFER LUFTTROM CFM 1800 2826 3532 3600 5651
EXTERNER STATISCHER DRUCK mmAq 10 20 KONDENSATOR LUFTSTROM CFM 4500 5650 10000 11300
STEUERUNG SLM CONTROLLER SEQUENTIAL CONTROLLER LÄNGE DER STEUERLEITUNG (STANDARD/MAX) : GRÖßE m : mm KOMPRESSOR (TYP/MENGE) SPIRALE/1 SPIRALE/2 LUFTFI LTER (TYP/MENGE) WASHABLE SARANET/1 WASHABLE SARANET/2 LUFTFI LTERABMESSUNG (LÄNGE X BREITE X DICKE) mm 820 x 615 x 1 1020 x 615 x 1 840 x 667 x 1
MODELL UATY560 UATY700 UATY850 UATYC10 UATYC12 KÜHLMITTEL R22 KÄLTEMITTELFÜLLUNG kg 5,6 x 2 10,5 x 2 9,4 x 2 16,0 / 20,5 20,5 x 2 VERDAMPFER LUFTTROM CFM 6710 8000 9600 11000 12500
EXTERNER STATISCHER DRUCK mmAq 20 30 KONDENSATOR LUFTSTROM CFM 11300 20000
STEUERUNG SEQUENTIAL CONTROLLER LÄNGE DER STEUERLEITUNG (STANDARD/MAX) : GRÖßE m : mm KOMPRESSOR (TYP/MENGE) SPIRALE/2 LUFTFI LTER (TYP/MENGE) WASHABLE SARANET/2 WASHABLE SARANET/ 2 & 4 LUFTFI LTERABMESSUNG (LÄNGE X BREITE X DICKE) mm 840 x 667 x 1 1370 x 735 x 1 860 x 505 & 600 x 4
NUR KÜHLEN (R407C)
MODELL UATP180 UATP240 UATP280 UATP320 UATP450 KÜHLMITTEL R407C KÄLTEMITTELFÜLLUNG kg 4,6 4,0 5,9 6,2 4,5 x 2 VERDAMPFER LUFTTROM CFM 1800 2826 3532 3600 5651
EXTERNER STATISCHER DRUCK mmAq 10 20 KONDENSATOR LUFTSTROM CFM 4500 5650 8000 11300
STEUERUNG SLM CONTROLLER SEQUENTIAL CONTROLLER LÄNGE DER STEUERLEITUNG (STANDARD/MAX) : GRÖßE m : mm KOMPRESSOR (TYP/MENGE) SPIRALE/1 SPIRALE/2 LUFTFI LTER (TYP/MENGE) WASHABLE SARANET/1 WASHABLE SARANET/2 LUFTFI LTERABMESSUNG (LÄNGE X BREITE X DICKE) mm 820 x 615 x 1 1020 x 615 x 1 840 x 667 x 1
MODELL UATP560 UATP700 UATP850 UATPC10 UATPC12 KÜHLMITTEL R407C KÄLTEMITTELFÜLLUNG kg 4,2 x 2 9,6 x 2 10,4 x 2 14,5 / 18,0 18,0 x 2 VERDAMPFER LUFTTROM CFM 6710 8000 9300 11000 12500
EXTERNER STATISCHER DRUCK mmAq 20 30 KONDENSATOR LUFTSTROM CFM 11300 20000
STEUERUNG SEQUENTIAL CONTROLLER LÄNGE DER STEUERLEITUNG (STANDARD/MAX) : GRÖßE m : mm KOMPRESSOR (TYP/MENGE) SPIRALE/2 LUFTFI LTER (TYP/MENGE) WASHABLE SARANET/2 WASHABLE SARANET/ 2 & 4 LUFTFI LTERABMESSUNG (LÄNGE X BREITE X DICKE) mm 840 x 667 x 1 1370 x 735 x 1 860 x 505 & 600 x 4
HEIZPUMPE (R407C)
MODELL UATYP180 UATYP240 UATYP280 UATYP320 UATYP450 KÜHLMITTEL R407C KÄLTEMITTELFÜLLUNG kg 4,3 4,7 5,6 6,0 5,0 x 2 VERDAMPFER LUFTTROM CFM 1800 2826 3532 3600 5651
EXTERNER STATISCHER DRUCK mmAq 10 20 KONDENSATOR LUFTSTROM CFM 4500 5650 10000 11300
STEUERUNG SLM CONTROLLER SEQUENTIAL CONTROLLER LÄNGE DER STEUERLEITUNG (STANDARD/MAX) : GRÖßE m : mm KOMPRESSOR (TYP/MENGE) SPIRALE/1 SPIRALE/2 LUFTFI LTER (TYP/MENGE) WASHABLE SARANET/1 WASHABLE SARANET/2 LUFTFI LTERABMESSUNG (LÄNGE X BREITE X DICKE) mm 820 x 615 x 1 1020 x 615 x 1 840 x 667 x 1
MODELL UATYP560 UATYP700 UATYP850 UATYPC10 UATYPC12 KÜHLMITTEL R407C KÄLTEMITTELFÜLLUNG kg 5,8 x 2 9,4 x 2 9,6 x 2 13,5 / 20,5 20,0 x 2 VERDAMPFER LUFTTROM CFM 6710 8000 9600 11000 12500
EXTERNER STATISCHER DRUCK mmAq 20 30 KONDENSATOR LUFTSTROM CFM 11300 20000
STEUERUNG SEQUENTIAL CONTROLLER LÄNGE DER STEUERLEITUNG (STANDARD/MAX) : GRÖßE m : mm KOMPRESSOR (TYP/MENGE) SPIRALE/2 LUFTFI LTER (TYP/MENGE) WASHABLE SARANET/2 WASHABLE SARANET/ 2 & 4 LUFTFI LTERABMESSUNG (LÄNGE X BREITE X DICKE) mm 840 x 667 x 1 1370 x 735 x 1 860 x 505 & 600 x 4
L/S 850 1334 1667 1699 2667
L/S 2124 2667 3776 5333
2
7 / 15 : 0,14 - / 100 : 0,14
L/S 3167 3776 4531 5191 5899
L/S 5333 9439
2
- / 100 : 0,14
L/S 850 1334 1667 1699 2667
L/S 2124 2667 4719 5333
2
7 / 15 : 0,14 - / 100 : 0,14
L/S 3167 3776 4531 5191 5899
L/S 5333 9439
2
- / 100 : 0,14
L/S 850 1334 1667 1699 2667
L/S 2124 2667 3776 5333
2
7 / 15 : 0.14 - / 100 : 0,14
L/S 3167 3776 4389 5191 5899
L/S 5333 9439
2
- / 100 : 0.14
L/S 850 1334 1667 1699 2667
L/S 2124 2667 4719 5333
2
7 / 15 : 0,14 - / 100 : 0.14
L/S 3167 3776 4531 5191 5899
L/S 5333 9439
2
- / 100 : 0,14
6
ELEKTRISCHE DATEN
NUR KÜHLEN (R22)
MODELL UAT180 UAT240 UAT280 UAT320 UAT450 STROMVERSORGUNG V/ph/Hz 400 / 3N ~ / 50 SPANNUNGSBEREICH MAX, DAUERSTROM (COMP) VOLLLASTSTROM (FLA, COMP) STROM BEI FESTGEBREMSTEM LÄUFER
(LRA, COMP)
MODELL UAT560 UAT700 UAT850 UATC10 UATC12 STROMVERSORGUNG V/ph/Hz 400 / 3N ~ / 50 SPANNUNGSBEREICH MAX, DAUERSTROM (COMP) VOLLLASTSTROM (FLA, COMP) STROM BEI FESTGEBREMSTEM LÄUFER
(LRA, COMP)
HEIZPUMPE (R22)
MODELL UATY180 UATY240 UATY280 UATY320 UATY450 STROMVERSORGUNG V/ph/Hz 400 / 3N ~ / 50 SPANNUNGSBEREICH MAX, DAUERSTROM (COMP) VOLLLASTSTROM (FLA, COMP) STROM BEI FESTGEBREMSTEM LÄUFER
(LRA, COMP)
V A 14,0 23,0 26,9 27,5 23,0 x 2 A 12,1 15,6 16,9 22,3 15,6 x 2
A 74 95 118 118 95 x 2
V A 26,9 x 2 A
A
V A 17,0 22,0 31,0 27,5 22,0 x 2 A 15,0 19,5 23,0 22,3 19,5 x 2
A 101 84 81 118 84 x 2
16,9 x 2 22,3 x 2 30,0 x 2 24,0, 30,0 30,0 x 2
118 x 2 118 x 2 174 x 2 175, 215 215 x 2
27,5 x 2 42,0 x 2
380 ~ 415
380 ~ 415
35,0, 50,0
380 ~ 415
50,0 x 2
Deutsch
MODELL UATY560 UATY700 UATY850 UATYC10 UATYC12 STROMVERSORGUNG V/ph/Hz 400 / 3N ~ / 50 SPANNUNGSBEREICH MAX, DAUERSTROM (COMP) VOLLLASTSTROM (FLA, COMP) STROM BEI FESTGEBREMSTEM LÄUFER
(LRA, COMP)
NUR KÜHLEN (R407C)
MODELL UATP180 UATP240 UATP280 UATP320 UATP450 STROMVERSORGUNG V/ph/Hz 400 / 3N ~ / 50 SPANNUNGSBEREICH MAX, DAUERSTROM (COMP) VOLLLASTSTROM (FLA, COMP) STROM BEI FESTGEBREMSTEM LÄUFER
(LRA, COMP)
MODELL UATP560 UATP700 UATP850 UATPC10 UATPC12 STROMVERSORGUNG V/ph/Hz 400 / 3N ~ / 50 SPANNUNGSBEREICH MAX, DAUERSTROM (COMP) VOLLLASTSTROM (FLA, COMP) STROM BEI FESTGEBREMSTEM LÄUFER
(LRA, COMP)
HEIZPUMPE (R407C)
MODELL UATYP180 UATYP240 UATYP280 UATYP320 UATYP450 STROMVERSORGUNG V/ph/Hz 400 / 3N ~ / 50 SPANNUNGSBEREICH MAX, DAUERSTROM (COMP) VOLLLASTSTROM (FLA, COMP) STROM BEI FESTGEBREMSTEM LÄUFER
(LRA, COMP)
V A 31,0 x 2 A
A
V A 14,0 23,0 26,9 31,0 23,0 x 2 A 13,0 15,9 16,9 22,3 15,6 x 2
A 74 95 118 118 95 x 2
V A 26,9 x 2 A
A
V A 17,0 23,0 26,9 31,0 23,0 x 2 A 15,0 15,9 16,9 22,3 15,9 x 2
A 101 95 118 118 95 x 2
23,0 x 2 22,3 x 2 30,0 x 2 24,0, 30,0 30,0 x 2
81 x 2 118 x 2 174 x 2 175, 215 215 x 2
16,9 x 2 22,3 x 2 30,0 x 2 24, 30 30,0 x 2
118 x 2 118 x 2 174 x 2 175, 215 215 x 2
27,5 x 2 42,0 x 2
31,0 x 2 42,0 x 2
380 ~ 415
380 ~ 415
380 ~ 415
380 ~ 415
35,0, 50,0
35,0, 50,0
50,0 x 2
50,0 x 2
MODELL UATYP560 UATYP700 UATYP850 UATYPC10 UATYPC12 STROMVERSORGUNG V/ph/Hz 400 / 3N ~ / 50 SPANNUNGSBEREICH MAX, DAUERSTROM (COMP) VOLLLASTSTROM (FLA, COMP) STROM BEI FESTGEBREMSTEM LÄUFER
(LRA, COMP)
V A 26,9 x 2 A
A
380 ~ 415
31,0 x 2 42,0 x 2
16,9 x 2 22,3 x 2 32,0 x 2 24, 30 30,0 x 2
118 x 2 118 x 2 174 x 2 175, 215 215 x 2
35,0, 50,0
50,0 x 2
7
VERKABELUNG
Alle elektrischen Arbeiten sind von quali ziertem Personal und in Übereinstimmung mit den örtlichen Bestimmungen
und Gesetzen durchzuführen.
Methode für den Anschluss elektrokabel
Vor dem Anschließen der Kabel fi nden Sie in der Electric Power Company Gerichtsstand.
1. Der gesamte Schaltplan des Gerätes. a
b
PE
g
c
f
2. Drahtverbindung der Fernbedienung. UAT(Y)(P)450, 560, 700, 850, C10, C12
LCD Fern
(Obere Abdeckung)
GND
+5
B A
Verbindung an
Hauptplatine
d
GND
+5
B A
Verbindungsleitung (versorgung)
Fernbedienung ist beigefügt. Schließen Sie direkt an den Stecker "CN2" an der Hauptplatine an.
a. Stromversorgung
Hauptschalter/
b.
Sicherung (versorgung)
Stromversorgung
c.
für das Gerät
e
Gerät
d.
e. Fernbedienung
Anschlusskabel
f.
für Innengerät & Fernbedienung
g. Erde
Verbindung hinter oberer Abdeckung
Hinweis: Für UAT(Y)(P)180, 240, 280, 320, Leitung für die
3. Verkabelung an Gerät Entfernen Sie die Verkleidung und schließen Sie die Maßeinheiten Spg.Versorgungsteilleitungen an Klemmenblock an, wie
unten gezeigt.
UAT(Y)(P)180, 240, 280, 320
UAT(Y)(P)450, 560
Klemmblock
UAT(Y)(P)180 nur
Empfohlene Position des Schalterkastens
Klemmblock
Empfohlene Position des Schalterkastens
UAT(Y)(P)700, 850, C10, C12
Klemmblock
HINWEIS: Während Sie den Schaltschutz auf das Gerät bauen, stellen Sie sicher, dass die Schrauben die Bauteile im
Gerät nicht beschädigen (z.B. Spule).
Der Trennschalter kann auch installiert werden ohne am Gerät befestigt zu sein.
8
Loading...
+ 162 hidden pages