Daikin SEHVX20BAW, SEHVX32BAW, SEHVX40BAW, SEHVX64BAW, SERHQ020BAW1 Installer reference guide

...
Installer and user
reference guide
Inverter heat pump chilling unit with separate hydro
module
SEHVX20BAW SEHVX32BAW SEHVX40BAW SEHVX64BAW
Installer and user reference guide
Inverter heat pump chilling unit with separate hydro module
English

Table of contents

Table of contents
1 General safety precautions 3
1.1 About the documentation .......................................................... 3
1.1.1 Meaning of warnings and symbols.............................. 3
1.2 For the user ............................................................................... 3
1.3 For the installer.......................................................................... 4
1.3.1 General ....................................................................... 4
1.3.2 Installation site ............................................................ 4
1.3.3 Refrigerant .................................................................. 4
1.3.4 Brine............................................................................ 5
1.3.5 Water .......................................................................... 5
1.3.6 Electrical ..................................................................... 5
2 About the documentation 6
2.1 About this document.................................................................. 6
For the installer 7
3 About the box 7
3.1 Overview: About the box ........................................................... 7
3.2 Indoor unit ................................................................................. 7
3.2.1 To unpack the indoor unit ........................................... 7
3.2.2 To remove the accessories from the indoor unit......... 7
4 About the units and options 8
4.1 Overview: About the units and options...................................... 8
4.2 Identification label: Indoor unit................................................... 8
4.3 About the indoor unit ................................................................. 8
4.4 Operation range ........................................................................ 8
4.5 System layout............................................................................ 8
4.6 Combining units and options ..................................................... 9
4.6.1 About combining units and options............................. 9
4.6.2 Possible options for the unit........................................ 9
5 Preparation 9
5.1 Overview: Preparation............................................................... 9
5.2 Preparing the installation site .................................................... 9
5.2.1 Installation site requirements of the indoor unit .......... 9
5.3 Preparing water piping .............................................................. 9
5.3.1 Water circuit requirements .......................................... 9
5.3.2 Formula to calculate the expansion vessel pre-
pressure ...................................................................... 10
5.3.3 To check the water volume and expansion vessel
pre-pressure................................................................ 10
5.3.4 Changing the pre-pressure of the expansion vessel... 11
5.3.5 To check the water volume: Examples ....................... 12
5.4 Preparing refrigerant piping....................................................... 12
5.4.1 Refrigerant piping requirements.................................. 12
5.4.2 To select the piping size ............................................. 12
5.4.3 About the piping length ............................................... 12
5.5 Preparing electrical wiring ......................................................... 12
5.5.1 About electrical compliance ........................................ 12
5.5.2 Cable requirements..................................................... 13
5.5.3 Safety device requirements ........................................ 13
6.4.1 About connecting the water piping............................... 14
6.4.2 Precautions when connecting the water piping............ 14
6.4.3 To fill the water circuit .................................................. 15
6.4.4 To insulate the water piping ......................................... 15
6.5 Connecting the refrigerant piping ............................................... 15
6.6 Charging refrigerant ................................................................... 16
6.6.1 To determine the additional refrigerant amount........... 16
6.7 Connecting the electrical wiring.................................................. 16
6.7.1 Precautions when connecting electrical wiring ............ 16
6.7.2 Field wiring: Overview.................................................. 17
6.7.3 About the electrical wiring ............................................ 17
6.7.4 To route and fix the power supply................................ 17
6.7.5 To connect the power supply and transmission
cables........................................................................... 17
6.7.6 To install the remote controller..................................... 18
6.7.7 To install optional equipment ....................................... 18
7 Configuration 19
7.1 Overview: Configuration ............................................................. 19
7.2 Making field settings................................................................... 19
7.2.1 About making field settings .......................................... 19
7.2.2 Field setting components ............................................. 19
7.2.3 To access the field setting components....................... 19
7.2.4 To access mode 1 or 2 ................................................ 20
7.2.5 To use mode 1 ............................................................. 20
7.2.6 To use mode 2 ............................................................. 20
7.2.7 Mode 1: Monitoring settings......................................... 20
7.2.8 Mode 2: Field settings.................................................. 21
7.2.9 Field settings on the remote controller......................... 22
7.3 Switching between cooling and heating ..................................... 26
8 Commissioning 27
8.1 Overview: Commissioning.......................................................... 27
8.2 Precautions when commissioning .............................................. 27
8.3 Checklist before commissioning................................................. 27
8.4 Final check ................................................................................. 28
8.5 Checklist handover to the user................................................... 28
8.6 To complete the model fill-in ...................................................... 28
9 Maintenance and service 29
9.1 Overview: Maintenance and service .......................................... 29
9.2 Maintenance safety precautions................................................. 29
9.3 Checklist for yearly maintenance of the indoor unit.................... 29
10 Troubleshooting 29
10.1 Overview: Troubleshooting......................................................... 29
10.2 Error codes: Overview ................................................................ 29
11 Disposal 30
12 Technical data 31
12.1 Overview: Technical data ........................................................... 31
12.2 Service space: Indoor unit .......................................................... 31
12.3 Piping diagram: Indoor unit ........................................................ 32
12.4 Wiring diagram: Indoor unit ........................................................ 33
12.5 Technical specifications: Outdoor unit........................................ 33
12.6 Field settings on the remote controller – overview ..................... 34
12.7 Field settings on the outdoor module ......................................... 36
12.8 ESP curve: Outdoor unit............................................................. 37
6 Installation 13
6.1 Overview: Installation ................................................................ 13
6.2 Opening the units ...................................................................... 13
6.2.1 To open the indoor unit............................................... 13
6.2.2 To open the electrical component box of the indoor
unit .............................................................................. 14
6.3 Mounting the indoor unit............................................................ 14
6.3.1 About mounting the indoor unit................................... 14
6.3.2 To provide the installation structure............................ 14
6.3.3 Precautions when mounting the indoor unit................ 14
6.4 Connecting the water piping...................................................... 14
Installer and user reference guide
2
For the user 38
13 About the system 38
13.1 System layout ............................................................................. 38
14 User interface 38
15 Before operation 38
16 Operation 38
16.1 Operation range ......................................................................... 38
SEHVX20~64BAW
Inverter heat pump chilling unit with separate hydro module
4P508020-1 – 2017.10

1 General safety precautions

16.2 Quick start-up ............................................................................ 38
16.3 Operating the system ................................................................ 39
16.3.1 About the clock ........................................................... 39
16.3.2 About operating the system ........................................ 40
16.3.3 Space cooling operation ............................................. 40
16.3.4 Space heating operation ............................................. 40
16.3.5 Other operation modes ............................................... 41
16.3.6 Schedule timer ............................................................ 41
16.3.7 Operating the optional demand PCB .......................... 45
16.3.8 Operating the optional external control adapter .......... 46
16.3.9 Operating the optional remote controller..................... 46
17 Maintenance and service 46
17.1 About the refrigerant.................................................................. 46
17.2 After-sales service and warranty ............................................... 46
17.2.1 Warranty period .......................................................... 46
17.2.2 Recommended maintenance and inspection .............. 46
17.2.3 Recommended maintenance and inspection cycles ... 46
18 Troubleshooting 47
18.1 Error codes: Overview ............................................................... 47
19 Relocation 47
20 Disposal 47
21 Glossary 47
1 General safety precautions

1.1 About the documentation

▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide MUST be performed by an authorised installer.

1.1.1 Meaning of warnings and symbols

NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.

1.2 For the user

▪ If you are NOT sure how to operate the unit, contact your installer.
▪ This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall NOT play with the appliance. Cleaning and user maintenance shall NOT be made by children without supervision.
WARNING
To prevent electric shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet hands.
▪ Do NOT place any objects containing water on the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
▪ Units are marked with the following symbol:
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
SEHVX20~64BAW Inverter heat pump chilling unit with separate hydro module 4P508020-1 – 2017.10
This means that electrical and electronic products may NOT be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation. Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.
▪ Batteries are marked with the following symbol:
This means that the batteries may NOT be mixed with unsorted household waste. If a chemical symbol is printed beneath the symbol, this chemical symbol means that the battery contains a heavy metal above a certain concentration. Possible chemical symbols are: Pb: lead (>0.004%). Waste batteries must be treated at a specialized treatment facility for reuse. By ensuring waste batteries are disposed of correctly, you will help to prevent potential negative consequences for the environment and human health.
Installer and user reference guide
3
1 General safety precautions

1.3 For the installer

1.3.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.

1.3.2 Installation site

▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.

1.3.3 Refrigerant

If applicable. See the installation manual or installer reference guide of your application for more information.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leakage in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the system into the outdoor unit. Possible consequence: Self-combustion and explosion of the compressor because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
Installer and user reference guide
4
Inverter heat pump chilling unit with separate hydro module
SEHVX20~64BAW
4P508020-1 – 2017.10
1 General safety precautions
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant MUST be treated according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside
Charge with the cylinder upright.
down.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.
WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.

1.3.5 Water

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.

1.3.6 Electrical

DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.

1.3.4 Brine

If applicable. See the installation manual or installer reference guide of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring.
SEHVX20~64BAW Inverter heat pump chilling unit with separate hydro module 4P508020-1 – 2017.10
Installer and user reference guide
5

2 About the documentation

WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure above.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
2 About the documentation

2.1 About this document

INFORMATION
Make sure that the user has the printed documentation and ask him/her to keep it for future reference.
Target audience
Authorised installers + end users
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the outdoor unit)
Outdoor unit installation and operation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the box of the outdoor unit)
Indoor unit installation and operation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the box of the indoor unit)
Installer and user reference guide:
▪ Preparation of the installation, reference data,…
▪ Detailed step-by-step instructions and background information
for basic and advanced usage
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
extranet (authentication required).
For installation of the heat pump unit (location, piping, and wiring), refer to the installation and operation manual of the RXYQ*.
INFORMATION
First read the indoor unit manual, and only then the outdoor unit manual.
Installer and user reference guide
6
Inverter heat pump chilling unit with separate hydro module
SEHVX20~64BAW
4P508020-1 – 2017.10

For the installer

b
a
a d ec
b
f g
h
1×/2×
i
j k
l
3 About the box

3.1 Overview: About the box

This chapter describes what you have to do after the box with the indoor unit is delivered on-site.
It contains information about:
▪ Unpacking and handling the indoor unit
▪ Removing the accessories from the unit
Keep the following in mind:
▪ At delivery, the unit MUST be checked for damage. Any damage
MUST be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
▪ When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.

3 About the box

▪ Prepare the path along which you want to bring the unit inside in
advance.
a Opening b Forklift
▪ A forklift can only be used for transport as long as the unit remains
on its pallet as shown above.

3.2 Indoor unit

3.2.1 To unpack the indoor unit

Remove the packaging material from the unit:
▪ Take care not to damage the unit when removing the shrink foil
with a cutter.
▪ Remove the 4 bolts fixing the unit to its pallet.
▪ Take care not to drop the unit when removing it from the pallet. Lift
the unit with at least 2installers.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.

3.2.2 To remove the accessories from the indoor unit

a General safety precautions b Installation manual and operation manual (panel 3) c Remote controller (panel 3) d Tie wraps (panel 3) e Shut-off valves (panel 3)
f Threaded connection (panel 3) (1× for SEHVX20+32BAW,
2× for SEHVX40+64BAW)
g Filter (panel 3) h Elbow (panel 3)
i Black grommet (2×) j L-shaped support (2×)
k M5 screws (3×)
l Accessory pipes (Ø12.7→Ø9.52 and Ø25.4→Ø28.6)
SEHVX20~64BAW Inverter heat pump chilling unit with separate hydro module 4P508020-1 – 2017.10
Installer and user reference guide
7

4 About the units and options

43
–5
–15
0
0 5 20 25
LWE
T
A
A B
C
0
35
25
5
–15
5 (EWC) 20 25 35 50
LWC
T
A
A B
RC
RT1M1RT2M2RT3
M3
FC1 FC2 FC3
a c e f
f g g g
h
db
4 About the units and options

4.1 Overview: About the units and options

This chapter contains information about:
1 Identification of the indoor unit
2 Where the indoor unit fits in the system layout
3 With which outdoor units and options you can combine the
indoor units

4.2 Identification label: Indoor unit

Location

4.4 Operation range

Cooling
TAAmbient temperature (°CDB)
LWE Leaving water evaporator temperature (°C)
A Standard water operation range B Pull down area
Heating
Model identification
Example: SE HV X 20 BA W
Code Explanation
SE Special European model
HVX Hydro module/Floor-standing
20 Capacity class
BA Model series
W Power supply: 3P, 400V

4.3 About the indoor unit

This installation manual concerns the inverter heat pump chilling unit with separate hydro module. The unit is intended for indoor installation and can be combined with VRV outdoor units (SERHQ020+032BAW1) for air conditioning purposes, or it can be used for supplying water for process cooling applications.
The units are available in 4 standard sizes with nominal capacities ranging from 16.8 to 63 kW.
The unit is designed to work in heating mode at ambient temperatures from –15°C to 35°C and in cooling mode at ambient temperatures from –5°C to 43°C.
The main component is the water heat exchanger.
The indoor unit is connected to the outdoor unit by field refrigerant piping and the compressor in the outdoor unit circulates refrigerant into the heat exchangers.
▪ In cooling mode, the refrigerant transports the heat taken from the
water heat exchanger to the air heat exchanger where the heat is released to the air.
▪ In heating mode, the refrigerant transports the heat taken from the
air heat exchanger to the water heat exchanger where the heat is released to the water.
Installer and user reference guide
8
TAAmbient temperature (°CDB)
LWC Leaving water condenser temperature (°C)
EWC Entering water condenser temperature (°C)
A Pull up area B Standard water operation range C Protect the system against freezing by installing an optional
water piping heater tape.

4.5 System layout

a Outdoor unit b Indoor unit c Plate heat exchanger d Pump e Expansion vessel
f Shut-off valve
g Motorized valve
SEHVX20~64BAW
Inverter heat pump chilling unit with separate hydro module
4P508020-1 – 2017.10

5 Preparation

h Bypass valve
FC1…3 Fancoil unit (field supply)
RC Remote controller
RT1…3 Room thermostat

4.6 Combining units and options

4.6.1 About combining units and options

This packaged air-cooled water chiller can be combined with fan coil units and is intended for R410A use only.

4.6.2 Possible options for the unit

INFORMATION
Refer to the technical engineering data for the latest option names.
Optional kits that are ordered with the unit will be delivered in a separate box together with their specific manuals.
Remote controller (EKRUAHTB)
A second remote controller to control the unit from 2 locations.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB. In case of SEHVX40+64BAW, 2 sets of this option are required.
External control adaptor (DTA104A62)
To instruct specific operation with an external input coming from a central control, the external control adaptor can be used. Instructions (group or individual) can be given for low noise operation and power consumption limitation operation. In case of SEHVX40+64BAW, 2 sets of this option are required.
5 Preparation

5.1 Overview: Preparation

This chapter describes what you have to do and know before going on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the water piping
▪ Preparing the electrical wiring

5.2 Preparing the installation site

5.2.1 Installation site requirements of the indoor unit

▪ Mind the following spacing installation guidelines:
▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the unit is level.
▪ Select the location of the unit in such a way that the sound
generated by the unit does not disturb anyone, and the location is selected according the applicable legislation.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
NOTICE
This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected from easy access.
This unit is suitable for installation in a commercial and light industrial environment.
▪ Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.

5.3 Preparing water piping

5.3.1 Water circuit requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
NOTICE
In case of plastic pipes, make sure they are fully oxygen diffusion tight according to DIN 4726. The diffusion of oxygen into the piping can lead to excessive corrosion.
Connecting piping – Legislation. Make all piping connections in
accordance with the applicable legislation and the instructions in the "Installation" chapter, respecting the water inlet and outlet.
Connecting piping – Force. Do NOT use excessive force when
connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
Connecting piping – Tools. Only use appropriate tooling to
handle brass, which is a soft material. If NOT, pipes will get damaged.
Connecting piping – Air, moisture, dust. If air, moisture or dust
gets into the circuit, problems may occur. To prevent this:
▪ Only use clean pipes
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall, to prevent
dust and/or particles entering the pipe.
▪ Use a decent thread sealant to seal connections.
SEHVX20~64BAW Inverter heat pump chilling unit with separate hydro module 4P508020-1 – 2017.10
Installer and user reference guide
9
5 Preparation
a
b
a
c
d
b
Capacity class Minimum required flow rate
20 23 l/min
32 36 l/min
40 46 l/min
64 72 l/min
Field supply components – Water pressure and temperature.
Check that all components in the field piping can withstand the water pressure and water temperature.
Drainage – Low points. Provide drain taps at all low points of the
system in order to allow complete drainage of the water circuit.
Non-brass metallic piping. When using non-brass metallic
piping, insulate the brass and non-brass properly so that they do NOT make contact with each other. This to prevent galvanic corrosion.
Shut-off valves. Two shut-off valves are delivered with the unit.
Install them as shown in the following figure.
Air vents. Provide air vents at all high points of the system, which
must also be easily accessible for servicing. An automatic air purge valve is provided inside the unit. Check that this air purge valve is NOT tightened too much, so that automatic release of air from the water circuit is possible. Refer to field setting[E‑04] in
"7.2.9Field settings on the remote controller"on page22.
Water pressure. Take care that the components installed in the
field piping can withstand the water pressure (maximum 3 bar + static pressure of the pump). Refer to "12.8ESP curve: Outdoor
unit"on page37.
WARNING
▪ For correct operation of the system, a regulating valve
must be installed in the water system. The regulating valve is to be used to regulate the water flow in the system (field supply).
▪ Selecting a flow outside the curves can cause
malfunction or damage to the unit. Also refer to the Technical specifications.
▪ The maximum water piping temperature is 50°C according to
safety device setting.
▪ Always use materials which are compatible with the water used in
the system and with the materials used in the unit. (The unit piping fittings are made of brass, the plate heat exchangers are made of stainless steel 316 plates brazed together with copper and the optional pump housing is made of cast iron.)
▪ Select the piping diameter in relation to the required water flow
and available external static pressure (ESP) of the pump. See the following table for the recommended water piping diameter.
a Adapter piece (on the inlet only in case of
SEHVX40+64BAW)
b Shut-off valve c Bend d Filter
NOTICE
Before mounting the bend, attach the filter to it.
NOTICE
If the bend is not used during installation, replace it with an extension (5cm long for a 1¼"filter, and 6 cm long for a 2"filter) to ensure proper cleaning operation of the filter.
NOTICE
Be sure to install the filter properly. Failure to install or incorrect installation will damage the plate heat exchanger permanently.
Drain taps. Drain taps must be provided at all low points of the
system to permit complete drainage of the circuit. A drain valve is provided inside the unit.
Capacity class Water piping diameter
20+32 1-1/4"
40+64 2"
NOTICE
It is strongly recommended to install an additional filter on the water circuit. Especially to remove metallic particles from the field water piping, it is advised to use a magnetic or cyclone filter which can remove small particles. Small particles can damage the unit and will not be removed by the standard filter of the unit.

5.3.2 Formula to calculate the expansion vessel pre-pressure

The pre-pressure (Pg) of the vessel depends on the installation height difference (H):
Pg=0.3+(H/10) (bar)

5.3.3 To check the water volume and expansion vessel pre-pressure

The unit has an expansion vessel of 12 litre with a default pre­pressure of 1bar.
To make sure that the unit operates properly:
▪ You must check the minimum and maximum water volume.
▪ You might need to adjust the pre-pressure of the expansion
vessel.
Minimum water volume
Model Minimum total water volume (l)
20 76
32 110
40 152
64 220
Installer and user reference guide
10
Inverter heat pump chilling unit with separate hydro module
SEHVX20~64BAW
4P508020-1 – 2017.10
INFORMATION
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5
9
a
b
0
0.5
1
1.5
2
2.5
3
0 50 100 150 200 250 300 350 400 450 500 550 600
A
B
33
b
a
In critical processes, or in rooms with a high heat load, extra water might be required.
INFORMATION
The temperature step difference can be modified using settings [A‑02] and [F‑00]. This has an impact on the minimum water volume required when the unit operates in cooling.
By default, the unit is set to have a water temperature difference of 3.5 K which allows it to operate with the minimum volume mentioned in the previous table. However, if a smaller temperature differential is set, as in the case of process cooling applications where temperature fluctuations must be avoided, a larger minimum water volume will be required.
To ensure proper operation of the unit when changing the values of setting [F‑00] (for cooling mode), the minimum water volume has to be corrected. If this volume exceeds the range allowed in the unit, an additional expansion vessel or a buffer tank must be installed in the field piping.
Example:
To illustrate the impact on the system when modifying the setting [F‑00], we will consider a unit with a minimum allowable water volume of 66l. The unit is installed 5m below the highest point in the water circuit.
Assuming that the setting [F‑00] is changed from 5°C (default value) to 0°C. From the below table we see that 5°C corresponds to a temperature differential of 3.5K and 0°C to 1K, which is actually the lowest value we can set.
[F‑00] value (°C) Temperature differential (K)
0 1
1 1.5
2 2
3 2.5
4 3
5 3.5
6 4
7 4.5
8 5
9 5.5
10 6
11 6.5
12 7
13 7.5
14 8
15 8.5
The water volume correction factor according to the curve shown in the below graph is 3.5; this means that the minimum volume will be
3.5 times larger.
Correction factor curve for minimum water volume
5 Preparation
a Water volume correction factor b Temperature differential (K)
When multiplying 64 l by the correction factor, we get 224 l, which will be the minimum water volume allowed in the installation if a temperature differential of 1K is used.
Now it is very important to check that for the height difference of the system, the volume in the system is less than the maximum allowed value at that pre-pressure (Pg). If we take a look at the curve, for 1bar of pre-pressure, the maximum volume allowed is 350l.
The total volume in the system will definitely be larger after adding the internal volume of the unit. In this case, some pre-pressure can be applied or an additional expansion vessel or buffer tank must be installed in the field piping.
The default value of pre-pressure (Pg) is for a height difference of 7m.
If the height difference of the system is lower than 7 m AND the volume in the system is less than the maximum allowed value at that pre-pressure (Pg) (see graph), then NO pre-pressure (Pg) adjustment is required.
Maximum water volume
Use the following graph to determine the maximum water volume for the calculated pre-pressure.
a Pre-pressure (bar)
b Maximum water volume (l) A System B Default
If the total water volume in the entire circuit exceeds the maximum allowed water volume (see graph), an additional expansion vessel must be installed in the field piping.

5.3.4 Changing the pre-pressure of the expansion vessel

SEHVX20~64BAW Inverter heat pump chilling unit with separate hydro module 4P508020-1 – 2017.10
NOTICE
Only a licensed installer may adjust the pre-pressure of the expansion vessel.
When changing the default pre-pressure of the expansion vessel (1bar) is required, take following guidelines into account:
▪ Only use dry nitrogen to set the expansion vessel pre-pressure.
▪ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Installer and user reference guide
11
5 Preparation
a
G
L
G1
L2
G2
L1
1
2
Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the Schrader valve of the expansion vessel.
a Schrader valve

5.3.5 To check the water volume: Examples

Example 1
The unit is installed 5m below the highest point in the water circuit. The total water volume in the water circuit is 250l.
No actions or adjustments are required.
Example 2
The unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 420l.
Actions:
▪ Because the total water volume (420 l) is more than the default
water volume (340l), the pre-pressure must be decreased.
▪ The required pre-pressure is:
Pg=(0.3+(H/10))bar=(0.3+(0/10))bar=0.3bar
▪ The corresponding maximum water volume is approximately 490l
(see graph).
▪ Because 420 l is lower than 490 l, the expansion vessel is
appropriate for the installation.

5.4 Preparing refrigerant piping

5.4.1 Refrigerant piping requirements

NOTICE
The refrigerant R410A requires strict cautions for keeping the system clean, dry and tight.
▪ Clean and dry: foreign materials (including mineral oils
or moisture) should be prevented from getting mixed into the system.
▪ Tight: R410A does not contain any chlorine, does not
destroy the ozone layer, and does not reduce earth's protection against harmful ultraviolet radiation. R410A can contribute slightly to the greenhouse effect if it is released. Therefore pay special attention to check the tightness of the installation.
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant.

5.4.2 To select the piping size

Determine the proper size using the following tables and reference figure (only for indication).
Indoor unit (hydro module)
Outdoor unit (heat pump unit)
▪ Piping connection sizes
Hydro module Gas Liquid Heat pump unit Gas Liquid
SEHVX20BAW 25.4 12.7 1× SERHQ020BAW1 22.2 9.52
SEHVX32BAW 25.4 12.7 1× SERHQ032BAW1 28.6 12.7
SEHVX40BAW 25.4 12.7 2× SERHQ020BAW1 22.2 9.52
SEHVX64BAW 25.4 12.7 2× SERHQ032BAW1 28.6 12.7
▪ Field piping sizes
Model G/G1 L/L1 G2 L2
SEHVX20BAW 28.6 9.52
SEHVX32BAW 28.6 12.7
SEHVX40BAW 28.6 9.52 28.6 9.52
SEHVX64BAW 28.6 12.7 28.6 12.7
Maximum piping length and height difference
Height difference between outdoor unit 1 and outdoor unit 2 (if applicable)

5.5 Preparing electrical wiring

0m

5.5.1 About electrical compliance

If the hydro module connections do not match the diameter of the specified piping requirements, the piping diameter requirements must be met using reducers/expanders (field supply) on the hydro module connections.
This equipment complies with:

5.4.3 About the piping length

Maximum piping length and height difference
Maximum allowable piping length 30m
Height difference between indoor and outdoor unit <10m
Installer and user reference guide
12
Inverter heat pump chilling unit with separate hydro module
SEHVX20~64BAW
4P508020-1 – 2017.10

6 Installation

1
3
2
EN/IEC 61000‑3‑11 provided that the system impedance Z
less than or equal to Z
at the interface point between the user's
max
is
sys
supply and the public system.
▪ EN/IEC 61000‑3‑11 = European/International Technical
Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤75A.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a system impedance Z
less than or equal to Z
sys
max
.
EN/IEC 61000‑3‑12 provided that the short-circuit power Ssc is
greater than or equal to the minimum Ssc value at the interface point between the user's supply and the public system.
▪ EN/IEC 61000‑3‑12 = European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤75A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to the minimum Ssc value.
Model Z
(Ω) Minimum Ssc value
max
(kVA)
SEHVX20BAW 0.27 820
SEHVX32BAW 0.24 874
SEHVX40BAW 0.25 1639
SEHVX64BAW 0.22 1747
Model Recommended fuses
SEHVX20BAW 6A
SEHVX32BAW 10A
SEHVX40BAW
SEHVX64BAW
NOTICE
When using residual current operated circuit breakers, be sure to use a high-speed type 300 mA rated residual operating current.
6 Installation

6.1 Overview: Installation

This chapter describes what you have to do and know on-site to install the system.
Typical workflow
Installation typically consists of the following stages:
1 Mounting the indoor unit
2 Connecting the refrigerant piping
3 Connecting the electrical wiring
4 Connecting the communication cable between indoor and
outdoor unit

6.2 Opening the units

5.5.2 Cable requirements

Item Cable
bundle
1 PS Power supply hydro module 4+GND
2 LV Communication cable between hydro
3 LV Standard remote controller (F1/F2) 2
4 LV Secondary remote controller (F1/F2)
5 LV Thermostat ON/OFF signal
6 LV Thermostat cooling/heating signal
7 LV Operation ON signal
8 LV Operation OFF signal
9 HV Cooling/heating output 2 0.3 A
10 HV Operation ON/OFF output 2 0.3 A
11 HV Error output 2 0.3 A
12 HV Water piping heater output 2 1 A
13 HV Pump ON/OFF output 2 0.3 A
module and heat pump unit
(a) Optional (b) Refer to the nameplate on the unit or to the technical data
book.
(c) Minimum cable section 0.75mm2. (d) Minimum cable section 1.5mm2. PS Power supply LV Low voltage
HV High voltage
Description Required
(a)
(a)
(a)
(a)
(a)
number of
conductors
(d) (d)
2
2
2
2
2
2

5.5.3 Safety device requirements

The power supply must be protected with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leakage protector in accordance with the applicable legislation.
Selection and sizing of the wiring should be done in accordance with the applicable legislation based on the information mentioned in the table below.
Maximum
running
current
(b)
(c)
(c)
(c)
(c)
(c)
(c)

6.2.1 To open the indoor unit

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
To gain access to the unit, front plates need to be opened as follows:
Panel
1 Electrical parts of the hydro module
2 Hydro module (side panel)
3 Hydro module (front panel)
Once the front plates open, the electrical component box can be accessed. See "6.2.2 To open the electrical component box of the
indoor unit"on page14.
INFORMATION
Multi units are standard combinations.
SEHVX20~64BAW Inverter heat pump chilling unit with separate hydro module 4P508020-1 – 2017.10
Installer and user reference guide
13
6 Installation
1
766.5 500200
396500
(mm)
a
b

6.2.2 To open the electrical component box of the indoor unit

NOTICE
Do NOT apply excessive force when opening the electronic component box cover. Excessive force can deform the cover, resulting in entering of water to cause equipment failure.
▪ Fasten the unit to the wall using the 2 accessory L-shaped
supports to prevent it from falling over. The supports can be fixed to the top panel of the hydro module (2× M5 screws on either side, but one screw is already mounted on the right side of the top plate).

6.3 Mounting the indoor unit

6.3.1 About mounting the indoor unit

Typical workflow
Mounting the indoor unit typically consists of the following stages:
1 Providing the installation structure.
2 Installing the indoor unit.
3 Connecting the water piping and the refrigerant piping.

6.3.2 To provide the installation structure

Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.
▪ The unit must be mounted against the wall.
▪ The unit must be fixed to prevent it from tilting.
▪ The preferred installation is on a solid longitudinal foundation
(steel beam frame or concrete).
▪ Observe the minimum installation space requirements.
a Attach one L-shaped support to the left side of the top plate
using 2screws from the accessory bag
b Attach the other L-shaped support to the right side of the
top plate using 1screw from the accessory bag and 1screw that is already attached to the unit
NOTICE
Use the proper kind of screw for the type of wall or foundation material where the unit will be fixed to.

6.3.3 Precautions when mounting the indoor unit

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

6.4 Connecting the water piping

6.4.1 About connecting the water piping

Typical workflow
Connecting the water piping typically consists of the following stages:
1 Connecting the water piping of the indoor unit.
2 Filling the water circuit.
3 Insulating the water piping.
▪ Fasten the unit to the floor using the holes in the bottom beams.
Installer and user reference guide
14

6.4.2 Precautions when connecting the water piping

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation
SEHVX20~64BAW
Inverter heat pump chilling unit with separate hydro module
4P508020-1 – 2017.10
6 Installation
a
b
To connect the water piping
Water connections must be made in accordance with all applicable legislations and the outlook drawing delivered with the unit, respecting the water inlet and outlet.
NOTICE
Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
If dirt gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit:
▪ Use clean pipes only.
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall so that no dust
and dirt enter.
▪ Use a good thread sealant for the sealing of the connections. The
sealing must be able to withstand the pressures and temperatures of the system.
▪ When using non-brass metallic piping, make sure to insulate both
materials from each other to prevent galvanic corrosion.
▪ Make sure to provide a proper drain for the pressure relief valve.
▪ Because brass is a soft material, use appropriate tooling for
connecting the water circuit. Inappropriate tooling will cause damage to the pipes.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
INFORMATION
The unit may dispose of some excessive water through the pressure relief valve.

6.4.4 To insulate the water piping

The complete water circuit, inclusive all piping, must be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity as well as prevention of freezing of the outside water piping during winter time. The thickness of the insulation materials must be at least 13 mm with λ=0.039W/mK in order to prevent freezing of the outside water piping at ambient temperature of –15°C.
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.

6.5 Connecting the refrigerant piping

▪ For the SEHVX20+32BAW, remove the top knockout hole in the
side service plate and add the grommet (accessory) to cover any burrs. For the SEHVX40+64BAW, remove both top and bottom knockout holes in the side service plate and add the grommets (accessory) to cover any burrs.
▪ For correct operation of the system, a regulating valve must be
installed in the water system. The regulating valve is to be used to regulate the water flow in the system (field supply).

6.4.3 To fill the water circuit

1 Connect the water supply to the drain and fill valve.
2 Make sure the automatic air purge valve is open (at least 2
turns).
3 Fill with water until the pressure gauge indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge valves (refer to field setting [E‑04] in "7.2.9Field settings on the remote controller"on page22).
NOTICE
▪ Air in the water circuit can cause malfunctioning. During
filling, it may not be possible to remove all the air from the circuit. Remaining air will be removed through the automatic air purge valves during the initial operating hours of the system. Additional filling with water afterwards may be required.
▪ To purge the system, use the special function as
described in "8Commissioning"on page27.
NOTICE
The water pressure indicated on the manometer will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure shall remain above 1bar to avoid air entering the circuit.
a Knockout hole b Grommet
▪ First cut off the refrigerant liquid piping inside the unit
approximately 7 cm before the clamp and the refrigerant gas piping 4 cm before the clamp. This is necessary in order to avoid the piping cutter tool from interfering with the piping. Remove any burrs from the piping.
▪ Use accessory pipes to connect field refrigerant piping to the
piping connections on the hydro module. For SEHVX20BAW, after cutting off the end of both the liquid and gas refrigerant piping, braze accessory pipe 1 to the liquid connection and accessory pipe 2 to the gas connection. For SEHVX32BAW, after cutting off the end of both the liquid and gas refrigerant piping, braze the field piping directly to the liquid connection and accessory pipe 2 to the gas connection. For SEHVX40BAW, perform the procedure for SEHVX20BAW twice. For SEHVX64BAW, perform the procedure for SEHVX32BAW twice.
NOTICE
After brazing, fix the pipes to the unit using the clamps in the pipe supports.
SEHVX20~64BAW Inverter heat pump chilling unit with separate hydro module 4P508020-1 – 2017.10
Installer and user reference guide
15
6 Installation
VRV
C1
VRV
C2
f
e
g
C2
g
C1
C1
C2
d
d
a
b
c
a Indoor unit b Outdoor unit 1 c Outdoor unit 2 (only in case of SEHVX40+64BAW) d Refrigerant piping e Pump
f Switchbox
g Evaporator

6.6 Charging refrigerant

6.6.1 To determine the additional refrigerant amount

INFORMATION
For final charge adjustment in a test laboratory, contact your dealer.
Refrigerant type: R410A
Global warming potential (GWP) value: 2087.5
The additional refrigerant charge calculation is based on the liquid piping size.
Formula:
R=(X
Example
SEHVX64BAW + 2× SERHQ032BAW1
R=(L1+L2)
×0.059)+(X
Ø9.52
R Additional refrigerant to be charged [in kg and rounded off
X
1, 2
×0.12
Ø12.7
×0.12)
Ø12.7
to 1 decimal place] Total length [m] of liquid piping size at Øa
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Do NOT operate the unit until the refrigerant piping is complete. Running the unit before the piping is ready will break the compressor.
NOTICE
If the power supply has a missing or wrong N-phase, equipment will break down.
NOTICE
Do NOT install a phase advancing capacitor, because this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.

6.7 Connecting the electrical wiring

6.7.1 Precautions when connecting electrical wiring

DANGER: RISK OF ELECTROCUTION
WARNING
All field wiring and components MUST be installed by a licensed electrician and MUST comply with the applicable legislation.
Installer and user reference guide
16
NOTICE
NEVER remove a thermistor, sensor, etc., when connecting power wiring and transmission wiring. (If operated without thermistor, sensor, etc., the compressor may break down.)
SEHVX20~64BAW
Inverter heat pump chilling unit with separate hydro module
4P508020-1 – 2017.10
Loading...
+ 36 hidden pages