READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN
YOUR FILES FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
DAIKIN EQUIPMENT IS DESIGNED FOR COMFORT
APPLICATIONS. FOR USE IN OTHER APPLICATIONS,
PLEASE CONTACT YOUR LOCAL DAIKIN DEALER.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DEALER FOR ADVICE AND
INFORMATION.
THIS AIR CONDITIONER COMES UNDER THE TERM
"APPLIANCES NOT ACCESSIBLE TO THE GENERAL
PUBLIC".
1. SAFETYCONSIDERATIONS
The precautions listed here are divided into the following two types.
Both cover very important topics, so be sure to follow them carefully.
WARNINGIf the warning is not obeyed, it may cause
CAUTIONIf the caution is not observed, it may cause
WARNING
■
Ask your dealer or qualified personnel to carry out
installation work
yourself.
Improper installation may result in water leakage,
electric shocks or fire.
■Perform installation work in accordance with this
installation manual.
Improper installation may lead to water leakage,
electric shocks or fire.
■Be sure to use only the specified accessories and
parts for installation work.
Failure to use the specified parts may result in water
leakage, electric shocks, fire, or the unit falling.
■When wiring between the indoor and outdoor units,
and wiring the power supply, form the wires so that
the frontside panel can be securely fastened.
If the frontside panel is not in place, overheat of the
terminals, electric shocks or a fire may be caused.
■If refrigerant gas leaks during installation work,
ventilate the area immediately.
To xic gas may be produced if refrigerant gas comes
into contact with fire.
■After completing the installation work, check to make
sure that there is no leakage of refrigerant gas.
To xic gas may be produced if refrigerant gas leaks
into the room and comes into contact with a source of
fire, such as a fan heater, stove or cooker.
■Before touching electric terminal parts, turn off power
switch.
■Live parts can be easily touched by accident.
Do never leave the unit unattended during installation
or servicing when the service panel is removed.
■When planning to relocate former installed units, you
must first recover the refrigerant after the pumpingdown operation. Refer to chapter "Precaution for
pumping-down operation" on page 9.
CAUTION
■Install drain piping according to this installation
manual to ensure good drainage, and insulate the
pipe to prevent condensation.
Improper drain piping may cause water leakage, and
make the furnitures get wet.
■Install the indoor and outdoor units, power wire and
connecting wire at least 1 meter away from televisions
or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter
may not be sufficient to eliminate the noise.)
■Do not rinse the outdoor unit. This may cause electric
shocks or fire.
serious injuries.
injury or damage to the equipment.
. Do not install the machine by
RZQ200+250B7W1B
Split system air conditioner
4PW21952-1A
Installation manual
1
Precautions for R-410A
■The refrigerant requires strict cautions for keeping the
system clean, dry and tight.
- Clean and dry
Foreign materials (including mineral oils or moisture)
should be prevented from getting mixed into the
system.
- Tight
Read "7.5. Precautions on refrigerant piping" on
page 5 carefully and follow these procedures correctly.
■Since R-410A is a mixed refrigerant, the required
additional refrigerant must be charged in its liquid
state. (If the refrigerant is in state of gas, its
composition changes and the system will not work
properly).
■The connected indoor units must be indoor units
designed exclusively for R-410A.
Read "7. Refrigerant piping" on page 4 carefully and follow
these procedures correctly.
Since design pressure is 4.0 MPa or 40 bar, pipes of larger
wall thickness may be required. Refer to paragraph
"7.1. Selection of piping material" on page 4.
2. INTRODUCTION
3. MAINCOMPONENTS
For main components and function of the main components, refer to
the Engineering Data Book.
4. SELECTIONOFLOCATION
This is a class A product. In a domestic environment this product may
cause radio interference in which case the user may be required to
take adequate measures.
This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment. If installed as a house-hold appliance it could
cause electromagnetic inteference.
The inverter units should be installed in a location that meets the
following requirements:
1The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation. If
not, the unit may fall over and cause injury.
2The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available. (Refer to
figure 1 and choose one of the possibilities).
In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.
2.1. Combination
The indoor units can be installed in the following range.
■Always use appropriate indoor units compatible with R-410A.
To learn which models of indoor units are compatible with
R-410A, refer to the product catalogs.
■For installation of the indoor unit(s), refer to the installation
manual delivered with the indoor unit(s).
2.2. Standard supplied accessories
RZQ200RZQ250
Gas line piping (1)11
Gas line piping (2)11
Gas line piping (3)11
Installation manual11
Additional refrigerant charge label11
Auxiliary pipe—1
Refer to figure 2.
A B C DSides along the installation site with obstacles
Suction side
3Make sure to provide for adequate measures in order to prevent
that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause
malfunctions, smoke or fire. Please instruct the customer to
keep the area around the unit clean.
4There is no danger of fire due to leakage of inflammable gas.
5Ensure that water cannot cause any damage to the location in
case it drips out the unit (e.g. in case of a blocked drain pipe).
6The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length.
7Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturb
anyone.
8Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction. Frontal wind will
disturb the operation of the unit. If necessary, use a windscreen
to block the wind.
9Do not install or operate the unit on locations where air contains
high levels of salt, like e.g. in the vicinity of oceans.
10 During installation, avoid the possibility that children can mount
on the unit or place any object on the unit.
Falling or tumble may result in injury.
1Installation manual
2Accessory pipes
2.3. Optional accessories
This outdoor unit requires the pipe branching kit (optional) when
using a twin, triple or double twin application. Refer to catalogues for
details.
2.4. Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of
specifications.
Installation manual
2
RZQ200+250B7W1B
Split system air conditioner
4PW21952-1A
■The equipment described in this manual may cause
XNot allowed
OAllowed
electronic noise generated from radio-frequency
energy. The equipment complies to specifications that
are designed to provide reasonable protection against
such interference. However, there is no guarantee that
interference will not occur in a particular installation.
It is therefore recommended to install the equipment and
electric wires keeping proper distances away from stereo
equipment, personal computers, etc... (See figure 3).
5. INSPECTINGANDHANDLINGTHEUNIT
At delivery, the package should be checked and any damage should
be reported immediately to the carrier claims agent.
When handling the unit, take into account the following:
1Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
1Personal computer or radio
2Fuse
3Earth leakage breaker
4Remote controller
5Indoor unit
In extreme circumstances you should keep distances of
3 m or more and use conduit tubes for power and
transmission lines.
■In heavy snowfall areas, select an installation site
where snow will not affect operation of the unit.
■The refrigerant R-410A itself is nontoxic,
nonflammable and is safe. If the refrigerant should
leak however, its concentration may exceed the
allowable limit depending on room size. Due to this it
could be necessary to take measures against
leakage.
■Do not install in the following locations.
• Locations where acidic or alkaline vapour is
present.
• Locations where sulfurous acids and other corrosive
gases may be present in the atmosphere.
Copper piping and soldered joints may corrode,
causing refrigerant to leak.
• Locations where there is mist of mineral oil, oil spray or
vapor for example a kitchen.
Plastic parts may deteriorate, and cause them to
fall out or water to leak.
• Locations where the air contains high levels of salt
such as that near the ocean.
• Locations where flammable gases may leak, where
thinner, gasoline, and other volatile substances are
handled, or where carbon dust and other incendiary
substances are found in the atmosphere.
Leaked gas may accumulate around the unit, causing
an explosion.
• Locations where equipment that produces electro-
magnetic waves is found.
The electromagnetic waves may cause the control
system to malfunction, preventing normal operation.
• Locations where voltage fluctuates a lot, such as
that in factories.
• In vehicles or vessels.
■During installation, take strong winds, typhoons or
earthquakes into account.
Improper installation may result in fall over of the unit.
2Choose on beforehand the path along which the unit is to be
brought in.
3Lift the unit preferably with a crane and 2 belts of at least 8 m
long.
4When lifting the unit with a crane, always use protectors to
prevent belt damage and pay attention to the position of the
unit's centre of gravity.
NOTE
Use belt sling of ≤20 mm width which adequately
bears the weight of the unit.
5Bring the unit as close to its final installation position in its
original package to prevent damage during transport. (See
figure 4)
1Packaging material
2Opening (large)
3Belt sling
4Opening (small) (40x30)
5Protector
6. UNPACKINGANDPLACINGTHEUNIT
■Remove the four screws fixing the unit to the pallet.
■Make sure the unit is installed level on a sufficiently strong base
to prevent vibration and noise.
■Fasten the unit in place using four anchor bolts M12.
■Make sure the base under the unit is more than 765 mm.
■The unit must be installed on a solid longitudinal foundation
(steelbeam frame or concrete) as indicated in figure 5.
ModelAB
RZQ200+250930792
■Support the unit with a foundation of 66 mm width or more. (The
support leg of the unit is 66 mm width).
Do not use stands to support the corners. (See figure 6)
■Prepare a water drainage channel around the
foundation to drain waste water from around the unit.
■If the unit is to be installed on a roof, check the
strength of the roof and its drainage facilities first.
■If the unit is to be installed on a frame, install the
waterproofing board within a distance of 150 mm
under the unit in order to prevent infiltration of water
coming from under the unit.
■When installed in a corrosive
environment, use a nut with a
resin clip plate (1) to protect the
nut tightening part from rust.
1
RZQ200+250B7W1B
Split system air conditioner
4PW21952-1A
Installation manual
3
PRECAUTION
Block all gaps in the holes for passing out piping and wiring using
sealing material (field supply). (Small animals may enter the
machine.)
Example: passing piping out through the front
1Plug the areas marked with "".
(When the piping is routed from the front
panel.)
2Gas side piping
123
3Liquid side piping
7. REFRIGERANTPIPING
Use R-410A to add refrigerant.
All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.
CAUTION TO BE TAKEN WHEN BRAZING
REFRIGERANT PIPING
■Do not use flux when brazing copper-to-copper
refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing
filler metal (BCuP) which does not require flux.
Flux has extremely harmful influence on refrigerant
piping systems. For instance, if the chlorine based flux
is used, it will cause pipe corrosion or, in particular, if
the flux contains fluorine, it will damage the refrigerant
oil.
■Be sure to perform a nitrogen blow when brazing.
(Brazing without performing nitrogen replacement or
releasing nitrogen into the piping will create large
quantities of oxidized film on the inside of the pipes,
adversely affecting valves and compressors in the
refrigerating system and preventing normal
operation.)
■After completing the installation work, check that the
refrigerant gas does not leak.
To xic gas may be produced if the refrigerant gas leaks
into the room and when it comes in contact with a
source of fire.
If any leak would happen:
•ventilate the area immediately.
• do not directly touch the refrigerant that leaks.
Frostbite may be caused.
NOTE
Installation tools:
Make sure to use installation tools (gauge manifold
charge hose, etc.) that are exclusively used for R-410A
installations to withstand the pressure and to prevent
foreign materials (e.g. mineral oils such as SUNISO
and moisture) from mixing into the system.
(The screw specifications differ for R-410A and
R-407C.)
Vacuum pump (use a 2-stage vacuum pump with a
non-return valve):
■Make sure the pump oil does not flow oppositely
into the system while the pump is not working.
7.1. Selection of piping material
■Construction material: phosphoric acid deoxidized seamless
copper for refrigerant.
■Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.
■The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R-410A piping must be in accordance with the
table below.
Pipe Ø
9.5 / 12.7O0.80
15.9O1.00
22.21/2H1.00
O=Annealed
1/2H=Half hard
Temper grade
of piping material
Minimal thickness t (mm)
7.2. Refrigerant pipe size
■Pair system (See figure 8)
■Simultaneous operation system (twin: see figure 9, triple: see
figure 12, double twin: see figure 13)
Refrigerant pipe size
ModelStandard sizeSize-up
RZQ200
RZQ250
(1) In case of twin, triple and double twin applications, the listed refrigerant pipe
sizes relate to the main pipes only. (L1 = the pipes between the outdoor unit and
the branch in figures 9, 12 and 13).
NOTE
Gas pipeØ22.2Ø25.4
Liquid pipeØ9.5Ø12.7
Gas pipeØ22.2Ø25.4
Liquid pipeØ12.7Ø15.9
For new installations, use the standard pipe sizes.
■Twin system (see figure 9) and triple system (see figure 12)
The pipes between the outdoor unit and the branch (L1) should
have the same size as the outdoor connections. The pipes
between the branch and the indoor units (L2~L4) should have
the same size as the indoor connections. Branch: see marking
'■' on figures 9 and 12.
■Double twin system (see figure 13)
The pipes between the outdoor unit and the branch (L1) should
have the same size as the outdoor connections. The pipes
between the branch and the indoor units (L4~L7) should have
the same size as the indoor connections. Branch: see marking
'■' on figure 13.
For branch pipes L2 and L3: see table below for the branch pipe
sizes.
Branch pipe size L2, L3
ModelGas pipeLiquid pipe
RZQ200,250Ø15.9Ø9.5
(1)
Installation manual
4
RZQ200+250B7W1B
Split system air conditioner
4PW21952-1A