9.2.1Piping diagram: Outdoor unit ...................................... 15
Installation manual
4
a General safety precautions
b Outdoor unit installation manual
c Fluorinated greenhouse gases label
d Multilingual fluorinated greenhouse gases label
e Drain plug (located on the bottom of the packing case)
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Page 5
3Preparation
>100
>50
>350
(mm)
b
a
>100
>50
b
a
>100
b
a
b
a
>350
>350
>50
b
a
b
a
b
c
a
b
c
c
d
3.1Preparing the installation site
CAUTION
▪ Check if the installation location can support the unit's
weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.
▪ Provide sufficient service space.
▪ Do NOT install the unit so that it is in contact with a
ceiling or a wall, as this may cause vibrations.
▪ Choose the installation location with sufficient space for carrying
the unit in and out of the site.
3 Preparation
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
3.1.1Installation site requirements of the
outdoor unit
Mind the following spacing guidelines:
a Air outlet
b Air inlet
NOTICE
The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200mm.
It is recommended to install a baffle plate when the air outlet is
exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.
a Baffle plate
b Prevailing wind direction
c Air outlet
Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom), so that the operation noise will cause no trouble.
Note: If the sound is measured under actual installation conditions,
the measured value might be higher than the sound pressure level
mentioned in "Sound spectrum" in the data book due to
environmental noise and sound reflections.
INFORMATION
The sound pressure level is less than 70dBA.
3.1.2Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
In any case, provide at least 300mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100mm above
the maximum expected level of snow. See "4.1 Mounting the
outdoor unit"on page6 for more details.
In heavy snowfall areas it is very important to select an installation
site where the snow will NOT affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Liquid pipingØ6.4mm (1/4")
Gas pipingØ12.7mm (1/2")
▪ Piping temper grade and thickness:
Outer diameter
(Ø)
6.4mm (1/4")Annealed (O)≥0.8mm
12.7mm (1/2")
(a) Depending on the applicable legislation and the unit's
Temper gradeThickness (t)
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.
3.2.2Refrigerant piping length and height
difference
What?Distance
Maximum allowable pipe length30m
Minimum allowable pipe length1.5m
Maximum allowable height difference20m
(a)
In any case, provide at least 300mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100mm above
the maximum expected level of snow. In this case, it is
recommended to construct a pedestal.
3.2.3Refrigerant piping insulation
Pipe outer diameter
(Øp)
6.4mm (1/4")8~10mm≥10mm
12.7mm (1/2")14~16mm
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20 mm to prevent condensation on the surface of the
insulation.
Insulation inner
diameter (Øi)
Insulation thickness
(t)
4Installation
4.1Mounting the outdoor unit
4.1.1To provide the installation structure
Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field
supply).
a Maximum snowfall height
If the unit is installed on brackets to the wall, install the unit as
follows:
Installation manual
6
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Page 7
4 Installation
>300
>250
>100
(mm)
a
4× M8/M10
b
c
d
a
R=0.4~0.8
45°
±2
90°
±2
A
c
d
a
b
2 Use a Ø16mm hose (field supply).
a Drain port
b Bottom frame
c Drain plug
d Hose (field supply)
4.1.4To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4 Attach the cable’s ends. Tighten those ends.
a Maximum snowfall height
4.1.2To install the outdoor unit
4.1.3To provide drainage
NOTICE
If the unit is installed in a cold climate, take adequate
measures so that the evacuated condensate CANNOT
freeze.
INFORMATION
For information on the available options, contact your
dealer.
4.2Connecting the refrigerant piping
DANGER: RISK OF BURNING
4.2.1Guidelines when connecting the
refrigerant piping
Piping size
(mm)
Ø6.415~178.7~9.1
Ø12.750~6016.2~16.6
4.2.2Using the stop valve and service port
CAUTION
Do NOT open the valves before flaring is complete. This
would cause refrigerant gas leakage.
Tightening
torque (N•m)
Flare
dimensions (A)
(mm)
Flare shape
(mm)
1 Use a drain plug for drainage.
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
NOTICE
Provide at least 300 mm of free space below the unit.
Additionally, make sure the unit is positioned at least
100mm above the expected level of snow.
a Service port and service port cap
b Valve stem
c Field piping connection
Installation manual
7
Page 8
4 Installation
a
bc
d Stem cap
ItemTightening torque (N∙m)
Stem cap, liquid side21.6~28.4
Stem cap, gas side48.1~59.8
ItemTightening torque (N∙m)
Service port cap10.8~14.7
4.2.3To connect the refrigerant piping to the
outdoor unit
▪ Piping length. Keep field piping as short as possible.
▪ Piping protection. Protect the field piping against physical
damage.
WARNING
Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be sucked in. This will cause abnormal pressure in the
refrigeration cycle, which may result in equipment damage
and even injury.
CAUTION
▪ Use the flare nut fixed to the unit.
▪ To prevent gas leakage, apply refrigeration oil only to
the inside of the flare. Use refrigeration oil for R32.
▪ Do NOT reuse joints.
1 Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.
2 Check for leaks by applying the bubble test solution to all
connections.
3 Discharge all nitrogen gas.
4.3.2To perform vacuum drying
DANGER: RISK OF EXPLOSION
Do NOT start the unit if it is vacuumed.
1 Vacuum the system until the pressure on the manifold indicates
−0.1MPa (−1bar).
2 Leave as is for 4-5minutes and check the pressure:
If the pressure…Then…
Does not changeThere is no moisture in the
system. This procedure is
finished.
IncreasesThere is moisture in the
system. Go to the next step.
3 Vacuum the system for at least 2hours to a manifold pressure
of −0.1MPa (−1bar).
4 After turning the pump OFF, check the pressure for at least
1hour.
5 If you do NOT reach the target vacuum or CANNOT maintain
the vacuum for 1hour, do the following:
▪ Check for leaks again.
▪ Perform vacuum drying again.
NOTICE
Make sure to open the stop valves after installing the
refrigerant piping and performing vacuum drying. Running
the system with the stop valves closed may break the
compressor.
a Liquid stop valve
b Gas stop valve
c Service port
2 Connect the gas refrigerant connection from the indoor unit to
the gas stop valve of the outdoor unit.
NOTICE
It is recommended that the refrigerant piping between
indoor and outdoor unit is installed in a ducting or the
refrigerant piping is wrapped with finishing tape.
4.3Checking the refrigerant piping
4.3.1To check for leaks
NOTICE
Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).
NOTICE
Make sure to use a recommended bubble test solution
from your wholesaler. Do not use soap water, which may
cause cracking of flare nuts (soap water may contain salt,
which absorbs moisture that will freeze when the piping
gets cold), and/or lead to corrosion of flared joints (soap
water may contain ammonia which causes a corrosive
effect between the brass flare nut and the copper flare).
1 Charge the system with nitrogen gas up to a gauge pressure of
at least 200kPa (2 bar). It is recommended to pressurize to
3000kPa (30bar) in order to detect small leaks.
Installation manual
8
4.4Charging refrigerant
4.4.1About charging refrigerant
The outdoor unit is factory charged with refrigerant, but in some
cases the following might be necessary:
WhatWhen
Charging additional refrigerantWhen the total liquid piping
length is more than specified
(see later).
Completely recharging refrigerant Example:
▪ When relocating the system.
▪ After a leak.
Charging additional refrigerant
Before charging additional refrigerant, make sure the outdoor unit's
external refrigerant piping is checked (leak test, vacuum drying).
INFORMATION
Depending on the units and/or the installation conditions, it
might be necessary to connect electrical wiring before you
can charge refrigerant.
Typical workflow – Charging additional refrigerant typically consists
of the following stages:
1 Determining if and how much you have to charge additionally.
2 If necessary, charging additional refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Page 9
4 Installation
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
Completely recharging refrigerant
Before completely recharging refrigerant, make sure the following is
done:
1 All refrigerant is recovered from the system.
2 The outdoor unit's external refrigerant piping is checked (leak
test, vacuum drying).
3 Vacuum drying on the outdoor unit's internal refrigerant piping is
performed.
NOTICE
Before completely recharging, perform vacuum drying on
the outdoor unit's internal refrigerant piping as well.
Typical workflow – Completely recharging refrigerant typically
consists of the following stages:
1 Determining how much refrigerant to charge.
2 Charging refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
4.4.2About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
WARNING: FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
If the total liquid
Then…
piping length is…
>10mR=(total length (m) of liquid
piping–10m)×0.020
R=Additional charge (kg)(rounded in units
of 0.1kg)
INFORMATION
Piping length is the one way length of liquid piping.
4.4.4To determine the complete recharge
amount
INFORMATION
If a complete recharge is necessary, the total refrigerant
charge is: the factory refrigerant charge (see unit name
plate) + the determined additional amount.
4.4.5To charge additional refrigerant
WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, ALWAYS use protective
gloves and safety glasses.
Prerequisite: Before charging refrigerant, make sure the refrigerant
piping is connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
4.4.6To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
WARNING
The refrigerant inside the unit is mildly flammable, but
normally does NOT leak. If the refrigerant leaks in the
room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.
Turn off any combustible heating devices, ventilate the
room, and contact the dealer where you purchased the
unit.
Do NOT use the unit until a service person confirms that
the part from which the refrigerant leaked has been
repaired.
a If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Greenhouse gas emissions of the total refrigerant charge
expressed as tonnes CO2-equivalent
f GWP = Global warming potential
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes
4.4.3To determine the additional refrigerant
amount
If the total liquid
piping length is…
≤10mDo NOT add additional refrigerant.
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Then…
CO2-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
2 Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.
Installation manual
9
Page 10
4 Installation
DC+
DC-
b
c
a
d
e
g
f
50Hz
220-240V
c
d
f
a
e
b
4.5Connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in
electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes
without thermal insulation as such pipes will be very hot.
e S90 – thermistor lead wire
f LED
g S70 – fan motor lead wire
4.5.1Guidelines when connecting the electrical
wiring
Tightening torques
ItemTightening torque (N•m)
M4 (X1M)1.2~1.3
M4 (earth)
4.5.2Specifications of standard wiring
components
Component
Power supply cable Voltage220~240V
Phase1~
Frequency50Hz
Wire sizesMUST comply with
applicable legislation
Interconnection cable
(indoor↔outdoor)
Recommended field fuse13A
Earth leakage circuit breakerMUST comply with
4-core cable ≥1.5 mm² and
applicable for 220~240 V
applicable legislation
4.5.3To connect the electrical wiring on the
outdoor unit
1 Open the wire clamp.
2 Connect the interconnection cable and power supply as follows:
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10 minutes,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing. The
voltage MUST be less than 50VDC before you can touch
electrical components. For the location of the terminals,
see the wiring diagram.
DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by
the power supply. Do not touch them with bare hands.
3 Tighten the terminal screws securely. We recommend using a
4 Install the switch box cover.
a Interconnection cable
b Power supply cable
c Field fuse
d Earth leakage circuit breaker
e Power supply
f Earth
Phillips screwdriver.
4.6Finishing the outdoor unit
installation
4.6.1To finish the outdoor unit installation
DANGER: RISK OF ELECTROCUTION
a Multimeter (DC voltage range)
b S80 – reversing solenoid valve lead wire
c S20 – electronic expansion valve lead wire
d S40 – thermal overload relay lead wire
▪ Make sure that the system is earthed properly.
▪ Turn off the power supply before servicing.
▪ Install the switch box cover before turning on the power
supply.
1 Insulate and fix the refrigerant piping and interconnection cable
as follows:
Installation manual
10
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Page 11
5 Commissioning
f
b
a
e
d
c
a
d
b
c
J6
J4
J9
J5
J7
J8
J12
The indoor unit receives the signals of the user interface.
The specified wires are used for the interconnection
cable.
a Gas pipe
b Gas pipe insulation
c Interconnection cable
d Liquid pipe
e Liquid pipe insulation
f Finishing tape
2 Install the service cover.
4.7About the compressor
DANGER: RISK OF EXPLOSION
▪ Use a pipe cutter to remove the compressor.
▪ Do NOT use the brazing torch.
▪ Use approved refrigerants and lubricants only.
DANGER: RISK OF BURNING
Do NOT touch the compressor with bare hands.
5Commissioning
NOTICE
NEVER operate the unit without thermistors and/or
pressure sensors/switches. Burning of the compressor
might result.
5.1Checklist before commissioning
Do NOT operate the system before the following checks are OK:
The indoor unit is properly mounted.
The outdoor unit is properly mounted.
The system is properly earthed and the earth terminals
are tightened.
The fuses or locally installed protection devices are
installed according to this document, and have NOT been
bypassed.
The power supply voltage matches the voltage on the
identification label of the unit.
There are NO loose connections or damaged electrical
components in the switchbox.
There are NO damaged components or squeezedpipes on the inside of the indoor and outdoor units.
There are NO refrigerant leaks.
5.2Checklist during commissioning
To perform an air purge.
To perform a test run.
5.3To perform a test run
Prerequisite: Power supply MUST be in the specified range.
Prerequisite: Test run may be performed done in cooling or heating
mode.
Prerequisite: Test run should be performed in accordance with the
operation manual of the indoor unit to make sure that all functions
and parts are working properly.
1 In cooling mode, select the lowest programmable temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.
2 When the test run is finished, set the temperature to a normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3 minutes after turning the unit
OFF.
INFORMATION
▪ Even if the unit is turned OFF, it consumes electricity.
▪ When the power turns back on after a power break, the
previously selected mode will be resumed.
6Configuration
6.1To set the facility mode
When cutting jumper J6 on the PCB, the operation range will expand
to –15°C. The facility mode will stop if the outdoor temperature drops
below –20°C and resume when the temperature rises again.
To cut jumper J6
1 Remove the top plate of the outdoor unit.
2 Remove the front plate.
3 Remove the drip proof cover.
4 Cut jumper J6 on the outdoor unit PCB.
The refrigerant pipes (gas and liquid) are thermally
insulated.
The correct pipe size is installed and the pipes are
properly insulated.
The stop valves (gas and liquid) on the outdoor unit are
fully open.
The following field wiring has been carried out according
to this document and the applicable legislation between
the outdoor unit and the indoor unit.
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Drainage
Make sure drainage flows smoothly.
Possible consequence: Condensate water might drip.
a Front plate
b Top plate
c Drip proof cover
d Jumpers
Installation manual
11
Page 12
7 Troubleshooting
c
b
e
d
d
a
INFORMATION
▪ The indoor unit may produce Intermittent noise due to
the outdoor unit fan turning ON and/or OFF.
▪ Do NOT place humidifiers or other items which might
raise humidity in rooms when you use the facility mode.
▪ Cutting jumper J6 sets the indoor unit fan to the highest
speed.
▪ Do NOT use this setting in residences or offices with
people.
7Troubleshooting
7.1Fault diagnosis using LED on
outdoor unit PCB
LED is…Diagnosis
flashingNormal.
▪ Check the indoor unit.
ON▪ Turn the power OFF and back ON, and
check the LED within approximately 3
minutes.
If the LED is ON again, the outdoor unit
PCB is faulty.
OFF1Supply voltage (for power saving).
2Power supply fault.
3Turn the power OFF and back ON, and
check the LED within approximately 3
minutes.
If the LED is ON again, the outdoor unit
PCB is faulty.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leakage in the refrigerant
circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit. Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
NOTICE
During pump down operation, stop the compressor before
removing the refrigerant piping. If the compressor is still
running and the stop valve is open during pump down, air
will be sucked into the system. Compressor breakdown or
damage to the system can result due to abnormal pressure
in the refrigerant cycle.
Pump down operation will extract all refrigerant from the system into
the outdoor unit.
1 Remove the valve cap from the liquid stop valve and the gas
stop valve.
2 Carry out forced cooling. See "8.2 To start and stop forced
cooling"on page12.
3 After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<−10°C)), close the liquid stop valve
with a hexagonal wrench.
4 Check on the manifold if the vacuum is reached.
5 After 2-3 minutes, close the gas stop valve and stop forced
cooling.
DANGER: RISK OF ELECTROCUTION
▪ When the unit is not operating, the LEDs on the PCB
are turned off in order to save power.
▪ Even when the LEDs are off, the terminal block and the
PCB may be powered.
8Disposal
NOTICE
Do NOT try to dismantle the system yourself: the
dismantling of the system, treatment of the refrigerant, oil
and other parts MUST comply with applicable legislation.
Units MUST be treated at a specialised treatment facility
for reuse, recycling and recovery.
8.1To pump down
Example: To protect the environment, pump down when relocating
the unit or when disposing of the unit.
a Gas stop valve
b Closing direction
c Hexagonal wrench
d Valve cap
e Liquid stop valve
8.2To start and stop forced cooling
There are 2methods to perform forced cooling.
▪ Method 1. Using the indoor unit ON/OFF switch (if present on the
indoor unit).
▪ Method 2. Using the indoor unit user interface.
8.2.1To start/stop forced cooling using the
indoor unit ON/OFF switch
1 Press the ON/OFF switch for at least 5seconds.
Result: Operation will start.
Note: Forced cooling stops automatically after 15minutes.
2 To stop operation sooner, press the ON/OFF switch.
8.2.2To start/stop forced cooling using the
Installation manual
12
1 Set the operation mode to cooling.
indoor unit user interface
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Page 13
For the procedure, refer to "To perform a test run" in the installation
manual of the indoor unit.
Note: Forced cooling will stop automatically after around
30minutes.
2 To stop operation sooner, press the ON/OFF switch.
INFORMATION
If forced cooling is used and the outside temperature is <
−10°C, the safety device may prevent operation.
▪ Warm the outside temperature thermistor on the
outdoor unit to ≥−10°C. Result: Operation will start.
8 Disposal
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Installation manual
13
Page 14
9 Technical data
Unified Wiring Diagram Legend
For applied parts and numbering refer to the wiring diagram sticker supplied on the unit. Part numbering is realized by Arabic numbers in ascending order for each part and
is represented in the overview below by symbol “*” in the part code.
:CIRCUIT BREAKER: PROTECTIVE EARTH
:CONNECTION: PROTECTIVE EARTH (SCREW)
,
:CONNECTOR
A
: RECTIFIER
:EARTH: RELAY CONNECTOR
:FIELD WIRING: SHORT CIRCUIT CONNECTOR
:FUSE: TERMINAL
INDOOR
:INDOOR UNIT: TERMINAL STRIP
OUTDOOR
:OUTDOOR UNIT: WIRE CLAMP
BLK : BLACKGRN : GREENPNK: PINKWHT : WHITE
BLU : BLUEGRY : GREYPRP, PPL : PURPLEYLW : YELLOW
BRN : BROWNORG : ORANGERED: RED
A*P:PRINTED CIRCUIT BOARDPS: SWITCHING POWER SUPPLY
BS*:PUSH BUTTON ON / OFF, OPERATION SWITCHPTC*: THERMISTOR PTC
SHEET METAL : TERMINAL STRIP FIXED PLATEM*:STEPPER MOTOR
T*R: TRANSFORMER
M*C:COMPRESSOR MOTOR
TC, TRC: TRANSMITTERM*F: FAN MOTOR
V*, R*V: VARISTORM*P:DRAIN PUMP MOTOR
V*R: DIODE BRIDGE
M*S:SWING MOTOR
WRC: WIRELESS REMOTE CONTROLLER
MR*, MRCW*, MRM*, MRN* : MAGNETIC RELAY
X*: TERMINALN::NEUTRAL
X*M: TERMINAL STRIP (BLOCK)n = *, N=*NUMBER OF PASSES THROUGH FERRITE CORE
Y*E: ELECTRONIC EXPANSION VALVE COIL
PAM: PULSE-AMPLITUDE MODULATION
Y*R, Y*S: REVERSING SOLENOID VALVE COIL
PCB*:P
RINTED CIRCUIT BOARD
Z*C: FERRITE COREPM*:POWER MODULE
ZF, Z*F: NOISE FILTER
CIRCUIT BREAKER
9Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is
available on the Daikin extranet (authentication required).
9.1Wiring diagram
Installation manual
14
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Page 15
9.2Piping diagram
M
( )
( )
EV
Propeller fan
Heat exchanger
Outdoor air temperature thermistor
Muffler with filter
Muffler
Muffler
4-way valve
ON: heating
Muffler
Discharge pipe thermistor
Compressor
Accumulator
Liquid stop valve
Field piping
Field piping
Electronic expansion valve
Cooling
Heating
Refrigerant flow
Heat exchanger thermistor
1
2
3
4
1-4
Capillary tube
Muffler
Receiver gas
Filter
S1PH
Automatic reset
High pressure switch
·6.4· CuT
·4.0· CuT
·7.9· CuT
·7.9· CuT
·7.9· CuT
·7.9· CuT
·7.9· CuT
·7.9· CuT
·7.9· CuT
·7.9· CuT
·4.0· CuT
·4.0· CuT
·7.9· CuT
·4.0· CuT
·12.7· CuT
·6.4· CuT
Gas stop valve with service port
·12.7· CuT
·12.7· CuT
·12.7· CuT
·9.5· CuT
·9.5· CuT
·9.5· CuT
·9.5· CuT
·7.9· CuT
·7.9· CuT
·12.7· CuT
·12.7· CuT
·6.4· CuT
·6.4· CuT
·6.4· CuT
·6.4· CuT
·9.5· CuT
·9.5· CuT
Muffler
9.2.1Piping diagram: Outdoor unit
9 Technical data
PED categories of equipment – High pressure switch: category IV; Compressor: category II; Other art. 4§3 equipment.
RXA42+50A2V1B
R32 split series
3P517827-2 – 2017.12
Installation manual
15
Page 16
3P517827-2 2017.12
Copyright 2017 Daikin
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.