1.4Branch Selector Unit ................................................................................ 306
Table of Contentsvi
Safety CautionsSiUS371614E
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the equipment
operates normally, and explain the cautions for operating the product to the customer.
Caution ItemsThe caution items are classified into Warning and Caution. The Warning items are
especially important since death or serious injury can result if they are not followed closely. The
Caution items can also lead to serious accidents under some conditions if they are not
followed. Therefore, be sure to observe all the safety caution items described below.
PictogramsThis symbol indicates the item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates the prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates the action that must be taken, or the instruction.
The instruction is shown in the illustration or near the symbol.
1.1Warnings and Cautions Regarding Safety of Workers
Warning
Do not store the equipment in a room with fire sources (e.g. naked flames,
gas appliances, electric heaters).
Be sure to disconnect the power cable from the socket before
disassembling equipment for repair.
Working on equipment that is connected to the power supply may cause an
electrical shock.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If refrigerant gas is discharged during repair work, do not touch the
discharged refrigerant gas.
Refrigerant gas may cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at
the welded section, evacuate the refrigerant gas completely at a wellventilated place first.
If there is gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it may
cause injury.
If refrigerant gas leaks during repair work, ventilate the area.
Refrigerant gas may generate toxic gases when it contacts flames.
vii
Be sure to discharge the capacitor completely before conducting repair
work.
The step-up capacitor supplies high-voltage electricity to the electrical
components of the outdoor unit.
A charged capacitor may cause an electrical shock.
SiUS371614ESafety Cautions
Warning
Do not turn the air conditioner on or off by plugging in or unplugging the
power cable.
Plugging or unplugging the power cable to operate the equipment may cause
an electrical shock or fire.
Be sure to wear a safety helmet, gloves, and a safety belt when working
in a high place (more than 2 m (6.5 ft)).
Insufficient safety measures may cause a fall.
In case of R-32 and R-410A refrigerant models, be sure to use pipes, flare
nuts and tools intended for exclusive use with R-32 and R-410A
refrigerant.
The use of materials for R-22 refrigerant models may cause a serious accident,
such as damage to the refrigerant cycle or equipment failure.
Do not mix air or gas other than the specified refrigerant (R-32, R-410A,
R-22) in the refrigerant system.
If air enters the refrigerating system, excessively high pressure results, causing
equipment damage and injury.
Caution
Do not repair electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Do not clean the air conditioner with water.
Washing the unit with water may cause an electrical shock.
Be sure to provide an earth/grounding when repairing the equipment in a
humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when
cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Be sure to conduct repair work with appropriate tools.
The use of inappropriate tools may cause injury.
viii
Safety CautionsSiUS371614E
Caution
Be sure to check that the refrigerating cycle section has cooled down
enough before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
Conduct welding work in a well-ventilated place.
Using a welder in an enclosed room may cause oxygen deficiency.
1.2Warnings and Cautions Regarding Safety of Users
Warning
Do not store the equipment in a room with fire sources (e.g. naked flames,
gas appliances, electric heaters).
Be sure to use parts listed in the service parts list of the applicable model
and appropriate tools to conduct repair work. Never attempt to modify the
equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires are scratched or have deteriorated, be
sure to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same
power outlet with other electrical appliances, since it may cause an
electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and follow
the local technical standards related to the electrical equipment, the
internal wiring regulations, and the instruction manual for installation
when conducting electrical work.
Insufficient power circuit capacity and improper electrical work may cause an
electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and
outdoor units.
Make the connections securely and route the cable properly so that there is no
force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
ix
SiUS371614ESafety Cautions
Warning
When wiring between the indoor and outdoor units, make sure that the
terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cables may cause an electrical shock or fire.
Placing heavy items on the power cable, or heating or pulling the power cable
may damage it.
Do not mix air or gas other than the specified refrigerant (R-32, R-410A,
R-22) in the refrigerant system.
If air enters the refrigerating system, excessively high pressure results, causing
equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leakage and repair it
before charging the refrigerant. After charging the refrigerant, make sure
that there is no leakage.
If the leakage cannot be located and the repair work must be stopped, be sure
to pump-down, and close the service valve, to prevent refrigerant gas from
leaking into the room. Refrigerant gas itself is harmless, but it may generate
toxic gases when it contacts flames, such as those from fan type and other
heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation site
has sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength or if the installation work
is not conducted securely, the equipment may fall and cause injury.
Check to make sure that the power cable plug is not dirty or loose, then
insert the plug into a power outlet securely.
If the plug is dusty or has a loose connection, it may cause an electrical shock
or fire.
When replacing the coin battery in the remote controller, be sure to
dispose of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending
on the conditions of the installation site, to prevent electrical shocks.
x
Safety CautionsSiUS371614E
Caution
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If combustible gas leaks and remains around the unit, it may cause a fire.
Check to see if parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections may cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
A corroded installation platform or frame may cause the unit to fall, resulting in
injury.
Check the earth/grounding, and repair it if the equipment is not properly
earthed/grounded.
Improper earth/grounding may cause an electrical shock.
Be sure to measure insulation resistance after the repair, and make sure
that the resistance is 1 MΩ or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture and
floor.
Do not tilt the unit when removing it.
The water inside the unit may spill and wet the furniture and floor.
xi
SiUS371614EIcons Used
2. Icons Used
The following icons are used to attract the attention of the reader to specific information.
IconType of
Information
WarningA warning is used when there is danger of personal injury.
Warning
CautionA caution is used when there is danger that the reader, through
Caution
NoteA note provides information that is not indispensable, but may
Note:
ReferenceA reference guides the reader to other places in this binder or in
Description
incorrect manipulation, may damage equipment, lose data, get
an unexpected result or have to restart (part of) a procedure.
nevertheless be valuable to the reader, such as tips and tricks.
this manual, where he/she will find additional information on a
specific topic.
xii
SiUS371614E
Part 1
General Information
1. Model Names of Indoor/Outdoor Units........................................................2
1.3.1Combination of Outdoor Units (Heat Recovery 460 V)
REYQ-TAYDU
Model nameREYQ72TAYDUREYQ96TAYDUREYQ120TAYDUREYQ144TAYDUREYQ168TAYDU
Outdoor unit 1REYQ72TAYDUREYQ96TAYDUREYQ120TAYDUREYQ144TAYDUREYQ168TAYDU
Model nameREYQ192TAYDUREYQ216TAYDUREYQ240TAYDUREYQ264TAYDUREYQ288TAYDU
Outdoor unit 1REYQ72TAYDUREYQ96TAYDUREYQ96TAYDUREYQ120TAYDUREYQ144TAYDU
Outdoor unit 2REYQ120TAYDUREYQ120TAYDUREYQ144TAYDUREYQ144TAYDUREYQ144TAYDU
Model nameREYQ312TAYDUREYQ336TAYDUREYQ360TAYDUREYQ384TAYDUREYQ408TAYDU
Outdoor unit 1REYQ144TAYDUREYQ168TAYDUREYQ120TAYDUREYQ96TAYDUREYQ96TAYDU
Outdoor unit 2REYQ168TAYDUREYQ168TAYDUREYQ120TAYDUREYQ120TAYDUREYQ144TAYDU
Outdoor unit 3——REYQ120TAYDUREYQ168TAYDUREYQ168TAYDU
Model nameREYQ432TAYDUREYQ456TAYDU
Outdoor unit 1REYQ144TAYDUREYQ144TAYDU
Outdoor unit 2REYQ144TAYDUREYQ144TAYDU
Outdoor unit 3REYQ144TAYDUREYQ168TAYDU
1.3.2Combination of Outdoor Units (Heat Recovery 208/230 V)
REYQ-TATJU
Model nameREYQ72TATJUREYQ96TATJUREYQ120TATJUREYQ144TATJUREYQ168TATJU
Outdoor unit 1REYQ72TATJUREYQ96TATJUREYQ120TATJUREYQ144TATJUREYQ168TATJU
Model nameREYQ192TATJUREYQ216TATJUREYQ240TATJUREYQ264TATJUREYQ288TATJU
Outdoor unit 1REYQ72TATJUREYQ96TATJUREYQ96TATJUREYQ120TATJUREYQ144TATJU
Outdoor unit 2REYQ120TATJUREYQ120TATJUREYQ144TATJUREYQ144TATJUREYQ144TATJU
Model nameREYQ312TATJUREYQ336TATJUREYQ360TATJUREYQ384TATJUREYQ408TATJU
Outdoor unit 1REYQ144TATJUREYQ168TATJUREYQ120TATJUREYQ96TATJUREYQ96TATJU
Outdoor unit 2REYQ168TATJUREYQ168TATJUREYQ120TATJUREYQ120TATJUREYQ144TATJU
Outdoor unit 3——REYQ120TATJUREYQ168TATJUREYQ168TATJU
Model nameREYQ432TATJUREYQ456TATJU
Outdoor unit 1REYQ144TATJUREYQ144TATJU
Outdoor unit 2REYQ144TATJUREYQ144TATJU
Outdoor unit 3REYQ144TATJUREYQ168TATJU
3General Information
SiUS371614EModel Names of Indoor/Outdoor Units
1.4Air Treatment Equipment
Outdoor Air Processing Unit
SeriesModel NamePower Supply, Standard
FXMQ48MF72MF96MFVJU
Energy Recovery Ventilator (VAM series)
SeriesModel NamePower Supply, Standard
VAM300G470G600G1200GVJU
VJ: 1 phase, 208/230 V, 60 Hz
) : Standard Symbol
U(VJU
1.5Branch Selector Unit
Single Branch Selector Unit for Heat Recovery
SeriesModel NamePower Supply, Standard
Heat RecoveryBSQ36T60T96TVJ
Note: No interchangeability with BSVQ36/60/96PVJU.
VJ: 1 phase, 208/230 V, 60 Hz
Multi Branch Selector Unit for Heat Recovery
SeriesModel NamePower Supply, Standard
Heat RecoveryBS4Q54T6Q54T8Q54T10Q54T12Q54TVJ
Note: No interchangeability with BSV4/6Q36PVJU.
VJ: 1 phase, 208/230 V, 60 Hz
General Information4
External AppearanceSiUS371614E
2. External Appearance
2.1Indoor Unit
Ceiling mounted cassette (Round flow with sensing) type
FXFQ-T
Shown with BYCQ125B-W1
Ceiling mounted cassette (Round flow) type
FXFQ-P
Shown with BYCP125K-W1
4 way ceiling mounted cassette (2’×2’) type
FXZQ-M
Shown with BYFQ60B8W1U
4-way blow ceiling-suspended type
FXUQ-P
Ceiling mounted duct type
FXMQ-M
Ceiling suspended type
FXHQ-M
Wall mounted type
FXAQ-P
Floor standing type
FXLQ-M
One way blow cassette type
FXEQ-P
Slim ceiling mounted duct type
FXDQ-M
Ceiling mounted duct type (Middle and high static pressure)
FXMQ-PB
Concealed floor standing type
FXNQ-M
Air handling unit
FXTQ-TA
5General Information
SiUS371614EExternal Appearance
2.2DOAS Unit
DVSV05/10/12
2.3Outdoor Unit
Single Outdoor Unit
REYQ72TAYDU
REYQ72TATJU
REYQ96/120/144/168TAYDU
REYQ96/120/144/168TATJU
Double Outdoor Unit
REYQ192TAYDU
REYQ192TATJU
General Information6
REYQ216/240/264/288/312/336TAYDU
REYQ216/240/264/288/312/336TATJU
External AppearanceSiUS371614E
Triple Outdoor Unit
REYQ360/384/408/432/456TAYDU
REYQ360/384/408/432/456TATJU
2.4Air Treatment Equipment
Outdoor air processing unit
FXMQ-MF
2.5Branch Selector Unit
Single branch selector unit
BSQ-T
Energy recovery ventilator
(VAM series)
VAM-G
Multi branch selector unit
BS-Q54T
7General Information
SiUS371614ECombination of Outdoor Units
3. Combination of Outdoor Units
System capacity
TonHPkW
67.521.11
81028.11
1012.535.21
121542.21
1417.549.21
162056.32
1822.563.32
202570.32
2227.577.42
243084.42
2632.591.42
283598.52
3037.5105.53
3240112.53
3442.5119.63
3645126.63
3847.5133.63
Number of
units
7296120144168
O
OO
Module
Outdoor Unit Multi Connection
O
O
O
O
OO
OO
OO
OO
OO
OO
OOO
OOO
OOO
OOO
OOO
Piping Kit 1
—
BHFP26P100U
BHFP26P151U
Note:1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
General Information8
Capacity RangeSiUS371614E
4. Capacity Range
4.1Combination Ratio
Combination ratio =
Type
Single outdoor units
Double outdoor units160% ∗1
Triple outdoor units130%100%
Total capacity index of the indoor units
Capacity index of the outdoor units
Min.
combination
ratio
50%200% ∗1130%
Types of connected indoor units
When using
only FXDQ,
FXMQ-PB,
FXAQ
When using
only FXTQ,
or at least one
FXFQ07 or
FXFQ09
Max. combination ratio
Other
indoor unit
models
200% ∗1
Type of connected air treatment
When FXMQ-MF
is only connected
equipments
FXMQ-MF
When FXMQ-MF
and indoor units
are connected
100%100% ∗2
When DVS are
connected
120%
Notes: ∗1. If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all
the indoor units. Refer to the table below.
∗2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the
capacity index of the outdoor units. And the connection ratio must not exceed 100%.
(10)Y3SSolenoid valve (Liquid shutoff) Used to return oil from the accumulator to the compressor.
(11)Y4SFour way valve (HP/LP gas)Used to switch dual pressure gas pipe to high pressure or low pressure.
(12)Y5S
(13)Y6S
(14)S1NPH High pressure sensorUsed to detect the high pressure.
(15)S1NPL Low pressure sensorUsed to detect the low pressure.
(16)S1PH
(17)—
(18)—Subcooling heat exchangerApply subcooling to liquid refrigerant.
(19)—Capillary tube
(20)R1TThermistor (Outdoor air)Used to detect outdoor air temperature, correct discharge pipe temperature and others.
(21)R2TThermistor (M1C discharge)Used to detect discharge pipe temperature.
(22)R3TThermistor (Receiver inlet)Used to detect liquid pipe temperature of receiver inlet.
(23)R4T
(24)R5T
(25)R6TThermistor (Subcooling gas)Used to detect outdoor air temperature, correct discharge pipe temperature and others.
(26)R7TThermistor (Subcooling liquid) This detects temperature of liquid pipe for subcooling heat exchanger.
(27)R8T
(28)R9T
(29)R10TThermistor (Suction)Used to detect suction pipe temperature.
Inverter compressor is operated on frequencies between 52 Hz to 210 Hz by using the
inverter. Compressor operation steps: Refer to page 66~
Because the system is an air heat exchange type, the fan is operated at 9-step rotation
speed by using the inverter.
While in heating, PI control is applied to keep the outlet superheated degree of air heat
exchanger constant.
PI control is applied to keep the outlet superheated degree of subcooling heat exchanger
constant.
While in heating, PI control is applied to keep the outlet superheated degree of air heat
exchanger constant.
Used to collect the refrigerant to receiver.
Used to control the refrigerant amount to cool the diode bridge and power module of the
inverter PCB.
Used to detect refrigerant leakage.
Used to switch outdoor heat exchanger to evaporator or condenser.
This functions when pressure increases to stop operation and avoid high pressure
increase in the fault operation.
This is used when pressure increases, to prevent any damage on components caused by
pressure increase in transport or storage.
Used to return the refrigerating oil separated through the oil separator to the M1C
compressor.
This detects temperature of liquid pipe for air heat exchanger.
This detects temperature of gas pipe for air heat exchanger.
Used to detect liquid pipe temperature of air heat exchanger. Used to make judgements
on defrost operation.
Used to detect suction pipe temperature of compressor.
Used to detect gas pipe temperature of receiver gas purge piping.
Detects compressor surface temperature, this switch is activated at surface temperature
of 120°C (248°F) or more to stop the compressor.
U
Refrigerant Circuit12
Refrigerant CircuitSiUS371614E
REYQ72TAYDU, REYQ72TATJU
(22)
Check valveCheck valve
)
flare connection
)
7.9mm
(
valve
Electronic
expansion
Four way valve
(12)
(20)
Heat sink
Filter
Check valve
S1NPH
sensor
High pressure
Double tube
heat exchanger
(14)
Oil separator
S1PH
switch
(16)
High pressure
(32)
Filter
(21)
(9)
valve
Solenoid
port
Charge
tube
Capillary
Capillary
SV
(1)
M1C
Compressor
(33)
Filter
tube
(31)
(19)
plug
Fusible
Accumulator
C: 3D091128A
(7)
tube
Capillary
Check
valve
Electronic
expansion
(34)
valve
valve
(8)
expansion
(10)
SV
valve
valve
(6)
Filter
Capillary
Check
Liquid
tube
(18)
(2)
Pressure
regulating
Fusible
Receiver
Filter
Check valve
Fan
Electronic
Check valve
Solenoid
Electronic expansion
(5)
(24)
(30)
(27)
(13)
valve
Electronic expansion
Filter
Filter
(28)
Four way valve
(3)
valve
(23)
Filter
M
(17)
valve
plug
Filter
Check valve
With service port φ5/16in.
(
(26)
Filter
Stop valve
Liquid
pipe
valve
Electronic
expansion
(4)
Double tube
heat exchanger
(25)
Four way valve
(11)
pipe
High/low pressure gas
(15)
sensor
Low pressure
(29)
S1NPL
pipe
Suction gas
13Refrigerant Circuit
SiUS371614ERefrigerant Circuit
1.1.2REYQ96-168TAYDU, REYQ96-168TATJU
No. in
piping
diagram
(10)Y6E
(11)Y1S
(12)Y2S
(13)Y3SSolenoid valve (Liquid shutoff) Used to return oil from the accumulator to the compressor.
(14)Y4SFour way valve (HP/LP gas)Used to switch dual pressure gas pipe to high pressure or low pressure.
(15)Y5S
(16)Y6S
(17)S1NPH High pressure sensorUsed to detect the high pressure.
(18)S1NPL Low pressure sensorUsed to detect the low pressure.
(19)S1PH
(20)S2PH
(21)—
(22)—Subcooling heat exchangerApply subcooling to liquid refrigerant.
(23)—Capillary tube
(24)—Capillary tube
(25)R1TThermistor (Outdoor air)Used to detect outdoor air temperature, correct discharge pipe temperature and others.
(26)R21TThermistor (M1C discharge)
(27)R22TThermistor (M2C discharge)
(28)R3TThermistor (Receiver inlet)Used to detect liquid pipe temperature of receiver inlet.
(29)R4T
(30)R5T
(31)R6TThermistor (Subcooling gas)
(32)R7TThermistor (Subcooling liquid) This detects temperature of liquid pipe for subcooling heat exchanger.
(33)R8T
(34)R9T
(35)R10TThermistor (Suction)Used to detect suction pipe temperature.
Inverter compressor is operated on frequencies between 52 Hz to 210 Hz by using the
inverter. Compressor operation steps: Refer to page 66~
Because the system is an air heat exchange type, the fan is operated at 9-step rotation
speed by using the inverter.
While in heating, PI control is applied to keep the outlet superheated degree of air heat
exchanger constant.
PI control is applied to keep the outlet superheated degree of subcooling heat exchanger
constant.
While in heating, PI control is applied to keep the outlet superheated degree of air heat
exchanger constant.
Used to collect the refrigerant to receiver.
Used to control the refrigerant amount to cool the diode bridge and power module of the
inverter PCB.
Used to detect refrigerant leakage.
Used to return oil from the oil separator to the compressor (M1C).
Used to return oil from the oil separator to the compressor (M2C).
Used to switch outdoor heat exchanger to evaporator or condenser.
This functions when pressure increases to stop operation and avoid high pressure
increase in the fault operation.
This is used when pressure increases, to prevent any damage on components caused by
pressure increase in transport or storage.
Used to return the refrigerating oil separated through the oil separator to the M1C
compressor.
Used to return the refrigerating oil separated through the oil separator to the M2C
compressor.
Used to detect discharge pipe temperature.
This detects temperature of liquid pipe for air heat exchanger.
Used to detect gas pipe temperature on the evaporating side of subcooling heat
exchanger. Used to exercise the constant control of superheated degree at the outlet of
subcooling heat exchanger.
This detects temperature of gas pipe for air heat exchanger.
Used to detect liquid pipe temperature of air heat exchanger. Used to make judgements
on defrost operation.
Used to detect suction pipe temperature of compressor.
Used to detect gas pipe temperature of receiver gas purge piping.
Detects compressor surface temperature, this switch is activated at surface temperature
of 120°C (248°F) or more to stop the compressor. (144/168 class models only)
Refrigerant Circuit14
Refrigerant CircuitSiUS371614E
REYQ96-168TAYDU, REYQ96-168TATJU
(25)
(9)
valve
Filter
(19)
Filter
S1NPH
sensor
High pressure
(20)
Oil Separator
Filter
(26)
switch
S1PH
High pressure
Oil Separator
Filter
(27)
S2PH
switch
High pressure
SV
valve
Solenoid
(1)(11)
SV
valve
Solenoid
(2)(12)
Check
Heat sink
Check
valve
valve
(17)
tube
valve
valve
Pressure
Receiver
valve
Electronic
expansion
(5)
(29)
MM
(4)(3)
FanFan
(21)
valve
regulating
plug
Fusible
Filter
(7)
(30)
Filter
(36)
(33)
Capillary
(28)
Electronic
Check valve
Check valve
Check
(40)
expansion valve
(10)
Check
(13)
SV
Solenoid valve
Electronic expansion
valve
Electronic expansion
Filter
(34)
(23)
Capillary
tube
M1CCapillary
Compressor
(24)
tube
M2C
Compressor
(39)
(37)
C: 3D091127A
)
flare connection
)
7.9mm
(
Check valve
With service port φ5/16in.
(
(32)
Filter
Stop valve
Check valve
Electronic expansion valve
valve
Electronic
expansion
Four way valve
Filter
Filter
tube
Capillary
Check valve
(8)
(22)
(6)
Double tube
heat exchanger
Filter
(16)
(31)
(15)
Four way valve
Four way valve
(38)
Double tube
heat exchanger
Four way valve
(14)
port
Charge
tube
Capillary
S1NPL
sensor
Lows pressure
(18)
Filter
(35)
Fusible
Accumulator
plug
pipe
Liquid
pipe
High/low pressure gas
pipe
Suction gas
15Refrigerant Circuit
SiUS371614ERefrigerant Circuit
1.2Indoor Unit
Symbol
No. in piping
diagram
(1)
Electronic expansion
valve
Name
(2)Suction air thermistorR1TR1TR1T (∗1)Used for thermostat control.
(3)Liquid pipe thermistorR2TR2TR2T
(4)Gas pipe thermistorR3TR3TR3T
(5)Discharge air thermistor—R4T—Used for discharge air temperature control.
∗1. R1T is for remote controller thermistor or optional remote sensor.
FXFQ-T, FXFQ-P, FXHQ-M FXZQ-M
(4)
Except
FXMQ-PB,
FXMQ-PBFXTQ-TA
FXTQ-TA
Y1EY1EY1E
Gas piping
connection port
Function
Used for gas superheated degree control while
in cooling or subcooled degree control while in
heating.
Used for gas superheated degree control while
in cooling or subcooled degree control while in
heating.
Used for gas superheated degree control while
in cooling.
Gas piping
connection port
(4)
Indoor heat exchanger
Fan
(3)
FilterFilter
(2)
(1)
Liquid piping
connection port
C: 4D024460M
FXUQ-P, FXEQ-P, FXMQ-M, FXAQ-P, FXLQ-M,
FXNQ-M
Gas piping
connection port
(4)
Indoor heat exchanger
Fan
(3)
FilterFilter
(2)
(1)
Liquid piping
connection port
C: 4D034245P
Indoor heat exchanger
(3)
FilterFilter
FXDQ-M
Gas piping connection port
Liquid piping connection port
Fan
(2)
(1)
(3)
Filter
(4)
(1)
Filter
(2)
Fan
Liquid piping
connection port
C: 4D040157B
Indoor heat exchanger
C: 4D043864N
Refrigerant Circuit16
Refrigerant CircuitSiUS371614E
FXMQ-PB FXTQ-TA
Gas piping
connection port
(4)
Indoor heat exchanger
(3)
FilterFilter
Fan
(2)
(1)
Liquid piping
connection port
C: 4D034245P
(4)
(3)
(1)
C: 4D068194
17Refrigerant Circuit
Loading...
+ 294 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.