Daikin FT25CV1A, FT35CV1A, FT50CV1A, FT60CV1A, R25CV1A Service Manual

...
Si01-406
SPLIT Pair C-Series
[Applied Models]
zzzzNon-Inverter Pair : Cooling Only
zzzzNon-Inverter Pair : Heat Pump
Si01-406
Table of Contents i
Non Inverter Pair
Non Inverter PairNon Inverter Pair
Non Inverter Pair
C-Series
C-SeriesC-Series
C-Series
zCooling Only
Indoor Unit
FT25CV1A FT35CV1A FT50CV1A FT60CV1A
Outdoor Unit
R25CV1A R35CV1A R50CV1A R60CV1A
zHeat Pump
Indoor Unit
FTY25CVMA FTY35CVMA
Outdoor Unit
RY25CVMA RY35CVMA
Si01-406
ii Table of Contents
1. Introduction ........................................................................................... vii
1.1 Safety Cautions ...................................................................................... vii
Part 1 List of Function .................................................................1
1. Functions.................................................................................................2
Part 2 Specifications ................................................................... 5
1. Specifications..........................................................................................6
Part 3 Printed Circuit Board Connector Wiring Diagram ...........11
1. Printed Circuit Board Connector Wiring Diagram..................................12
1.1 FT25/35CV1A.........................................................................................12
1.2 FT50/60CV1A.........................................................................................14
1.3 FTY25/35CVMA .....................................................................................16
1.4 RY25/35CVMA .......................................................................................18
Part 4 Functions and Control......................................................21
1. Functions of Cooling Only Models ........................................................22
1.1 Cooling Monitoring Function...................................................................22
1.2 Programme Dry Function .......................................................................23
1.3 Freeze-up Protection Control .................................................................24
1.4 Air Flow Rate Control .............................................................................25
1.5 Power-Airflow Dual Flaps, Wide-Angle Louvers, and Auto-Swing .........25
1.6 Signal Receiving Sign ............................................................................26
1.7 ON / OFF Button on Indoor Unit.............................................................26
1.8 Filters......................................................................................................26
1.9 Night Set Mode.......................................................................................27
1.10 Powerful Operation.................................................................................27
1.11 3-minutes Standby Function...................................................................27
1.12 Auto-restart Function..............................................................................28
1.13 Test Run Function ..................................................................................28
2. Functions of Heat Pump Models...........................................................29
2.1 Frequency Principle................................................................................29
2.2 Power-Airflow Dual Flaps, Wide-Angle Louvers and Auto-Swing ..........31
2.3 Fan Speed Control for Indoor Units........................................................32
2.4 Programme Dry Function .......................................................................33
2.5 Automatic Operation...............................................................................34
2.6 Night Set Mode.......................................................................................35
2.7 Powerful Operation.................................................................................36
2.8 Other Functions......................................................................................37
2.9 Function of Thermistor ...........................................................................38
3. Control for Heat Pump Models..............................................................39
3.1 Mode Hierarchy ......................................................................................39
3.2 Frequency Control..................................................................................40
3.3 Controls at Mode Changing / Start-up....................................................42
3.4 Input Current Control ..............................................................................43
3.5 Freeze-up Protection Control .................................................................43
3.6 Heating Peak-cut Control .......................................................................44
3.7 Fan Control.............................................................................................44
Si01-406
Table of Contents iii
3.8 Liquid Compression Protection Function 1
(Securing of Differential Pressure and Blown Air Temperature) ............45
3.9 Liquid Compression Protection Function 2.............................................46
3.10 Defrost Control .......................................................................................46
3.11 Insufficient Gas Control ..........................................................................47
3.12 Forced Operation Mode .........................................................................48
3.13 Additional Function .................................................................................48
Part 5 System Configuration.......................................................49
1. System Configuration............................................................................50
2. Instructions............................................................................................51
2.1 Manual Contents by Models...................................................................51
2.2 Safety Precautions .................................................................................52
2.3 Names of Parts.......................................................................................54
2.4 Preparation before Operation .................................................................63
2.5 AUTO • DRY • COOL • HEAT • FAN Operation.....................................66
2.6 Adjusting the Air Flow Direction .............................................................68
2.7 POWERFUL Operation ..........................................................................69
2.8 TIMER Operation ...................................................................................70
2.9 Care and Cleaning .................................................................................72
2.10 Troubleshooting......................................................................................78
Part 6 Service Diagnosis.............................................................81
1. Troubleshooting by Lamps....................................................................82
2. Problem and Solution............................................................................83
3. Service Check Function ........................................................................84
3.1 ARC423 Series Remote Controller ........................................................84
3.2 ARC433 Series Remote Controller ........................................................85
4. Troubleshooting ....................................................................................86
4.1 Error Codes ............................................................................................86
4.2 Indoor Unit PCB Abnormality .................................................................87
4.3 Freeze-up Protection Control or High Pressure Control.........................88
4.4 Fan Motor or Related Abnormality .........................................................90
4.5 Thermistor or Related Abnormality (Indoor Unit)....................................93
4.6 Indoor Unit PCB Abnormality .................................................................94
4.7 Signal Transmission Error (between Indoor and Outdoor Units)............95
4.8 OL Activation (Compressor Overload) ...................................................96
4.9 Compressor Lock ...................................................................................97
4.10 Input Over Current Detection .................................................................98
4.11 Four Way Valve Abnormality ..................................................................99
4.12 High Pressure Control in Cooling .........................................................101
4.13 CT or Related Abnormality ...................................................................103
4.14 Thermistor or Related Abnormality (Outdoor Unit)...............................105
4.15 Electrical Box Temperature Rise..........................................................107
4.16 Radiation Fin Temperature Rise ..........................................................109
4.17 Output Over Current Detection.............................................................111
4.18 Insufficient Gas.....................................................................................113
5. Check ..................................................................................................115
5.1 Fan Motor Connector Output Check ....................................................115
5.2 Four Way Valve Performance Check ...................................................115
Si01-406
iv Table of Contents
5.3 Thermistor Resistance Check ..............................................................116
5.4 Installation Condition Check .................................................................117
5.5 Discharge Pressure Check...................................................................118
5.6 Outdoor Unit Fan System Check..........................................................119
5.7 Power Supply Waveforms Check .........................................................119
5.8 Inverter Units Refrigerant System Check .............................................120
5.9 Capacitor Voltage Check......................................................................120
5.10 Power Transistor Check .......................................................................121
5.11 Hall IC Check .......................................................................................122
5.12 Power Transistor Output Check ...........................................................123
5.13 Inverter Units Compressor / Refrigerant System Check ......................124
Part 7 Removal Procedure ........................................................125
1. FT25/35CV1A, FTY25/35CVMA .........................................................126
1.1 Removal of Air Filter.............................................................................126
1.2 Removal of Front Grille ........................................................................129
1.3 Removal of Horizontal Blades / Vertical Blades ...................................132
1.4 Removal of Electrical Parts Box / PCB / Swing Motor..........................134
1.5 Removal of Heat Exchanger ................................................................140
1.6 Install of Drain Plug ..............................................................................143
1.7 Removal of Fan Rotor / Fan Motor.......................................................144
2. FT50/60CV1A .....................................................................................148
2.1 Removal of Air Filter / Front Panel .......................................................148
2.2 Removal of Front Grille ........................................................................151
2.3 Removal of Horizontal Blades / Vertical Blades ...................................153
2.4 Removal of Electrical Parts Box / PCB / Swing Motor..........................155
2.5 Removal of Heat Exchanger ................................................................160
2.6 Removal of Fan Rotor / Fan Motor.......................................................163
3. R25/35CV1A, RY25/35CVMA.............................................................165
3.1 Removal of Panels ...............................................................................165
3.2 Removal of Bellmouth and Left Side Plate ...........................................167
3.3 Removal of Electrical Device Mounting Plate.......................................168
3.4 Removal of Propeller Fan and Fan Motor ............................................169
3.5 Removal of Compressor Noise Absorption Pad...................................170
3.6 Removal of Partition Plate....................................................................172
3.7 Removal of Compressor.......................................................................174
4. R50/60CV1A .......................................................................................175
4.1 Removal of Panels ...............................................................................175
4.2 Removal of Electrical Parts Box ...........................................................176
4.3 Removal of Compressor.......................................................................179
Part 8 Others .............................................................................181
1. Others .................................................................................................182
1.1 Test Run from the Remote Controller ..................................................182
1.2 Jumper Settings ...................................................................................184
Part 9 Appendix.........................................................................185
1. Piping Diagrams..................................................................................186
1.1 Indoor Units ..........................................................................................186
1.2 Outdoor Units .......................................................................................187
Si01-406
Table of Contents v
2. Wiring Diagrams..................................................................................190
2.1 Indoor Units ..........................................................................................190
2.2 Outdoor Units .......................................................................................191
Index ............................................................................................. i
Drawings & Flow Charts ................................................................ v
Si01-406
vi Table of Contents
Si01-406 Introduction
vii
1. Introduction
1.1 Safety Cautions
Cautions and Warnings
Be sure to read the following safety cautions before conducting repair work.
The caution items are classified into “ Warning” and “ Caution”. The “ Warning” items are especially important since they can lead to death or serious injury if they are not followed closely. The “ Caution” items can also lead to serious accidents under some conditions if they are not followed. Therefore, be sure to observe all the safety caution items described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer.
1.1.1 Caution in Repair
Warning
Be sure to disconnect the power cable plug from the plug socket before disassembling the equipment for a repair. Working on the equipment that is connected to a power supply can cause an electrical shook. If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits, do not touch any electrically charged sections of the equipment.
If the refrigerant gas discharges during the repair work, do not touch the discharging refrigerant gas. The refrigerant gas can cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the welded section, release the refrigerant gas completely at a well-ventilated place first. If there is a gas remaining inside the compressor, the refrigerant gas or refrigerating machine oil discharges when the pipe is disconnected, and it can cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The refrigerant gas can generate toxic gases when it contacts flames.
The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. Be sure to discharge the capacitor completely before conducting repair work. A charged capacitor can cause an electrical shock.
Do not start or stop the air conditioner operation by plugging or unplugging the power cable plug. Plugging or unplugging the power cable plug to operate the equipment can cause an electrical shock or fire.
Introduction Si01-406
viii
1.1.2 Cautions Regarding Products after Repair
Caution
Do not repair the electrical components with wet hands. Working on the equipment with wet hands can cause an electrical shock.
Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning the equipment. The internal fan rotates at a high speed, and cause injury.
Do not tilt the unit when removing it. The water inside the unit can spill and wet the furniture and floor.
Be sure to check that the refrigerating cycle section has cooled down sufficiently before conducting repair work. Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place. Using the welder in an enclosed room can cause oxygen deficiency.
Warning
Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can cause an electrical shock, excessive heat generation or fire.
When relocating the equipment, make sure that the new installation site has sufficient strength to withstand the weight of the equipment. If the installation site does not have sufficient strength and if the installation work is not conducted securely, the equipment can fall and cause injury.
Be sure to install the product correctly by using the provided standard installation frame. Incorrect use of the installation frame and improper installation can cause the equipment to fall, resulting in injury.
For integral units only
Be sure to install the product securely in the installation frame mounted on a window frame. If the unit is not securely mounted, it can fall and cause injury.
For integral units only
Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire.
Si01-406 Introduction
ix
1.1.3 Inspection after Repair
Be sure to use the specified cable to connect between the indoor and outdoor units. Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals. Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure that the terminal cover does not lift off or dismount because of the cable. If the cover is not mounted properly, the terminal connection section can cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable. Damaged or modified power cable can cause an electrical shock or fire. Placing heavy items on the power cable, and heating or pulling the power cable can damage the cable.
Do not mix air or gas other than the specified refrigerant (R410A / R22) in the refrigerant system. If air enters the refrigerating system, an excessively high pressure results, causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before charging the refrigerant. After charging refrigerant, make sure that there is no refrigerant leak. If the leak cannot be located and the repair work must be stopped, be sure to perform pump-down and close the service valve, to prevent the refrigerant gas from leaking into the room. The refrigerant gas itself is harmless, but it can generate toxic gases when it contacts flames, such as fan and other heaters, stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed of the old battery to prevent children from swallowing it. If a child swallows the coin battery, see a doctor immediately.
Warning
Caution
Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of combustible gas leaks. If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly. If the packing and seal are not installed properly, water can enter the room and wet the furniture and floor.
For integral units only
Warning
Check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet all the way. If the plug has dust or loose connection, it can cause an electrical shock or fire.
If the power cable and lead wires have scratches or deteriorated, be sure to replace them. Damaged cable and wires can cause an electrical shock, excessive heat generation or fire.
Introduction Si01-406
x
1.1.4 Using Icons
Icons are used to attract the attention of the reader to specific information. The meaning of each icon is described in the table below:
1.1.5 Using Icons List
Do not use a joined power cable or extension cable, or share the same power outlet with other electrical appliances, since it can cause an electrical shock, excessive heat generation or fire.
Warning
Caution
Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, fire or an electrical shock.
If the installation platform or frame has corroded, replace it. Corroded installation platform or frame can cause the unit to fall, resulting in injury.
Check the grounding, and repair it if the equipment is not properly grounded. Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure that the resistance is 1 Mohm or higher. Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair. Faulty drainage can cause the water to enter the room and wet the furniture and floor.
Icon Type of
Information
Description
Note:
Note A “note” provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Caution
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get an unexpected result or has to restart (part of) a procedure.
Warning
Warning A “warning” is used when there is danger of personal injury.
Reference A “reference” guides the reader to other places in this binder or
in this manual, where he/she will find additional information on a specific topic.
Si01-406
List of Function 1
Part 1
Part 1Part 1
Part 1
List of Function
List of Function List of Function
List of Function
1. Functions.................................................................................................2
Functions Si01-406
2 List of Function
1. Functions
Category Functions
FT25·35CV1A
R25·35CV1A
FT50·60CV1A
R50·60CV1A
Category Functions
FT25·35CV1A
R25·35CV1A
FT50·60CV1A
R50·60CV1A
Basic Function
Inverter (with Inverter Power Control)
——
Health & Clean
Air Purifying Filter with Bacteriostatic, Virustatic Functions
——
Operation Limit for Cooling (°CDB)
19.4 ~46
19.4 ~46
Operation Limit for Heating (°CWB) Photocatalytic Deodorizing Filter
PAM Control
Air Purifying Filter with Photocatalytic Deodorizing Function
{{
Compressor
Oval Scroll Compressor
Titanium Apatite Photocatalytic Air-Purifying Filter
——
Swing Compressor
Rotary Compressor
{{
Mold Proof Air Filter
{{
Reluctance DC Motor Wipe-clean Flat Panel
{{
Comfortable Airflow
Power-Airflow Flap Washable Grille
Power-Airflow Dual Flaps
{{
Filter Cleaning Indicator
Power-Airflow Diffuser Good-Sleep Cooling Operation
Wide-Angle Louvers
{{
Timer
24-Hour On/Off Timer
{{
Vertical Auto-Swing (Up and Down)
{{
Night Set Mode
{{
Horizontal Auto-Swing (Right and Left)
——
Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure)
{{
3-D Airflow
Self-Diagnosis (Digital, LED) Display
{★{
Comfort Airflow Mode
3-Step Airflow (H/P Only) Wiring Error Check
Comfort Control
Auto Fan Speed
{{
Anticorrosion Treatment of Outdoor Heat Exchanger
{{
Indoor Unit Silent Operation
Night Quiet Mode (Automatic)
Flexibility
Multi-Split / Split Type Compatible Indoor Unit
——
Outdoor Unit Silent Operation (Manual) —
Intelligent Eye Flexible Voltage Correspondence
Quick Warming Function High Ceiling Application
Hot-Start Function
Chargeless 10m 10m
Either Side Drain (Right or Left)
{{
Automatic Defrosting Power Selection
Operation
Automatic Operation
Remote Control
5-Rooms Centralized Controller (Option)
{{
Programme Dry Function
{{
Remote Control Adaptor (Normal Open-Pulse Contact) (Option)
{{
Fan Only
{{
Lifestyle Convenience
New Powerful Operation (Non-Inverter)
{{
Remote Control Adaptor (Normal Open Contact) (Option)
{{
Inverter Powerful Operation
Priority-Room Setting DIII-NET Compatible (Adaptor)(Option)
Cooling / Heating Mode Lock
Remote Controller
Wireless
{{
Home Leave Operation Wired
Indoor Unit On/Off Switch
{{
Signal Reception Indicator
{{
Temperature Display
Another Room Operation
Note:
{
: Holding Functions
— : No Functions
: Digital Only
Si01-406 Functions
List of Function 3
Category Functions
FTY25·35CVMA
RY25·35CVMA
Category Functions
FTY25·35CVMA
RY25·35CVMA
Basic Function
Inverter (with Inverter Power Control)
Health & Clean
Air Purifying Filter with Bacteriostatic, Virustatic Functions
Operation Limit for Cooling (°CDB)
10
~46
Operation Limit for Heating (°CWB)
–10 ~20
Photocatalytic Deodorizing Filter
PAM Control
Air Purifying Filter with Photocatalytic Deodorizing Function
{
Compressor
Oval Scroll Compressor
Titanium Apatite Photocatalytic Air-Purifying Filter
Swing Compressor
Rotary Compressor
{
Mold Proof Air Filter
{
Reluctance DC Motor Wipe-clean Flat Panel
{
Comfortable Airflow
Power-Airflow Flap Washable Grille
Power-Airflow Dual Flaps
{
Filter Cleaning Indicator
Power-Airflow Diffuser Good-Sleep Cooling Operation
Wide-Angle Louvers
{
Timer
24-Hour On/Off Timer
{
Vertical Auto-Swing (Up and Down)
{
Night Set Mode
{
Horizontal Auto-Swing (Right and Left)
Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure)
{
3-D Airflow Self-Diagnosis (Digital, LED) Display
{
Comfort Airflow Mode Wiring Error Check
3-Step Airflow (H/P Only)
Anticorrosion Treatment of Outdoor Heat Exchanger
{
Comfort Control
Auto Fan Speed
{
Indoor Unit Silent Operation
Flexibility
Multi-Split / Split Type Compatible Indoor Unit
Night Quiet Mode (Automatic)
Outdoor Unit Silent Operation (Manual) Flexible Voltage Correspondence
{
Intelligent Eye High Ceiling Application
Quick Warming Function
{
Chargeless 10m
Hot-Start Function
{
Either Side Drain (Right or Left)
{
Automatic Defrosting
{
Power Selection
Operation
Automatic Operation
{
Remote Control
5-Rooms Centralized Controller (Option)
{
Programme Dry Function
{
Remote Control Adaptor (Normal Open-Pulse Contact)(Option)
{
Fan Only
{
Lifestyle Convenience
New Powerful Operation (Non-Inverter)
{
Remote Control Adaptor (Normal Open Contact)(Option)
{
Inverter Powerful Operation
Priority-Room Setting DIII-NET Compatible (Adaptor)(Option)
Cooling / Heating Mode Lock
Remote Controller
Wireless
{
Home Leave Operation Wired
Indoor Unit On/Off Switch
{
Signal Reception Indicator
{
Temperature Display
Another Room Operation
Note:
{
: Holding Functions
— : No Functions
: Digital Only
Functions Si01-406
4 List of Function
Si01-406
Specifications 5
Part 2
Part 2Part 2
Part 2
Specifications
Specifications Specifications
Specifications
1. Specifications..........................................................................................6
Specifications Si01-406
6 Specifications
1. Specifications
220-230-240V 50Hz
Notes:
MAX. interunit piping length: 25m
MAX. interunit height difference: 15m
Amount of additional charge of refrigerant 20g/m for piping length exceeding 10m
The data are based on the conditions shown in the table below.
The data on the conditions (AS/NZS3823.1):
(Conditions)
Model
Indoor Units FT25CV1A FT35CV1A Outdoor Units R25CV1A R35CV1A
Capacity
kW 2.64 3.52
Btu/h 9,000 12,000
kcal/h 2,270 3,000 Moisture Removal L/h 1.2 1.9 Running Current A 3.95-4.00-4.10 5.58-5.60-5.62 Power Consumption W 817-843-868 1,135-1,170-1,200 Power Factor % 94.0-91.6-88.2 92.5-90.8-89.0 COP W/W 3.23-3.13-3.04 3.10-3.01-2.93
Piping Connections
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ
9.5
φ
12.7
Drain mm
φ
18.0
φ
18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Indoor Unit FT25CV1A FT35CV1A
Front Panel Color White White
Air Flow Rate m³/min (cfm)
H 8.3 (291) 8.4 (297) M 6.7 (235) 7.0 (247) L 5.0 (176) 5.5 (194)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 18 18
Speed Steps 5 Steps and Auto 5 Steps and Auto Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable/Washable/Mildew Proof Removable/Washable/Mildew Proof Running Current A 0.22-0.22-0.23 0.22-0.22-0.23 Power Consumption W 45-47-51 45-47-51 Power Factor % 93.0-92.9-92.3 93.0-92.9-92.3 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 273×784×195 273×784×195 Packaged Dimensions (H×W×D) mm 258×834×325 258×834×325 Weight kg 8 8 Gross Weight kg 11 11 Operation
Sound
H/M/L dBA 38/34/28 39/35/31
Outdoor Unit R25CV1A R35CV1A
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Rotary Type Hermetically Sealed Rotary Type
Model RC30BV1R2T RC46AV1TRT
Motor Output W 700 1,100 Refrigerant
Oil
Type SUNISO 4GSD. I. SUNISO 4GSD. I.
Charge L 0.40 0.50
Refrigerant
Type R22 R22
Charge kg 0.76 0.95
Air Flow Rate m³/min (cfm)
H 28-29-30 (988-1,024-1,059) 26.5-27-28 (935-953-988) L — (—) — (—)
Fan
Type Propeller Propeller
Motor Output W 25 25 Running Current A 3.73-3.78-3.87 5.36-5.38-5.39 Power Consumption W 772-796-817 1,090-1,123-1,149 Power Factor % 94.1-91.6-88.0 92.4-90.8-88.8 Starting Current A 19-20-21 26-27-28 Dimensions (H×W×D) mm 560×695×265 560×695×265 Packaged Dimensions (H×W×D) mm 599×797×310 599×797×310 Weight kg 27 33 Gross Weight kg 30 35 Operation Sound dBA 46-47-48 48-48-49 Drawing No. 3D045880 3D045881A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Standard Cooling Piping Length
JIS C 9612
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
5m
(Rated) FT25CV1A FT35CV1A Capacity kW 2.49 3.32 Running Current A 4.28 5.41 Power Consumption W 900 1,200 COP W/W 2.77 2.77
Standard Cooling Piping Length Power Supply
AS/NZS3823.1
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
7.5m 50Hz 230V
Si01-406 Specifications
Specifications 7
220-230-240V 50Hz
Notes:
MAX. interunit piping length: 30m
MAX. interunit height difference: 15m
Amount of additional charge of refrigerant 20g/m for piping length exceeding 10m
The data are based on the conditions shown in the table below.
The data on the conditions (AS/NZS3823.1):
(Conditions)
Models
Indoor Units FT50CV1A FT60CV1A Outdoor Units R50CV1A R60CV1A
Capacity
kW 5.3 6.6
Btu/h 18,100 22,500
kcal/h 4,560 5,680 Moisture Removal L/h 2.9 5.2 Running Current A 7.4-7.3-7.2 11.0-10.9-10.8 Power Consumption W 1,600 2,390 Power Factor % 98.3-95.3-92.6 98.8-95.3-92.2 COP W/W 3.31 2.76
Piping Connections
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ
15.9
φ
15.9
Drain mm
φ
18.0
φ
18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Indoor Units FT50CV1A FT60CV1A
Front Panel Color White White
Air Flow Rate m³/min (cfm)
H 16.2 (572) 17.5 (618)
M 14.0 (494) 15.0 (530)
L 11.9 (420) 12.5 (441)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 43 43
Speed Steps 5 Steps and Auto 5 Steps and Auto Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable/Washable/Mildew Proof Removable/Washable/Mildew Proof Running Current A 0.19-0.18-0.17 0.21-0.20-0.19 Power Consumption W 40 45 Power Factor % 95.7-96.6-98.0 97.4-97.8-98.7 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 290×1,050×238 290×1,050×238 Packaged Dimensions (H×W×D) mm 337×1,147×366 337×1,147×366 Weight kg 12 12 Gross Weight kg 17 17 Operation
Sound
H/M/L dBA 43/39/35 46/41/36
Outdoor Units R50CV1A R60CV1A
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Rotary Type Hermetically Sealed Rotary Type
Model RC60V1TNRT NH41VMDT
Motor Output W 1, 500 2,200 Refrigerant
Oil
Type SUNISO 4GSD. I. MS-32
Charge L 0.85 1.20
Refrigerant
Type R22 R22
Charge kg 1.35 1.70
Air Flow Rate m³/min (cfm)
H 29-29.5-30 (1,024-1,041-1,059) 40-40.5-41 (1,412-1,430-1,447) L — (—) 23-24-25 (812-847-883)
Fan
Type Propeller Propeller
Motor Output W 53 53 Running Current A 7.21-7.12-7.03 10.79-10.70-10.61 Power Consumption W 1,560 2,345 Power Factor % 98.3-95.3-92.5 98.8-95.3-92.1 Starting Current A 32-33.5-35 55-58-60 Dimensions (H×W×D) mm 685×800×300 685×800×300 Packaged Dimensions (H×W×D) mm 732×955×390 732×955×390 Weight kg 49 61 Gross Weight kg 54 66 Operation Sound dBA 54-54-55 54-54-55 Drawing No. 3D045882 3D045883A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Standard Cooling Piping Length
JIS C 9612
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
5m
(Rated) FT50CV1A FT60CV1A Capacity kW 5.3 6.6 Running Current A 7.6 11.3 Power Consumption W 1,650 2,460 COP W/W 3.21 2.68
Standard Cooling Piping Length Power Supply
AS/NZS3823.1
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
7.5m 50Hz 230V
Specifications Si01-406
8 Specifications
220-230-240V 50Hz
Notes:
MAX. interunit piping length: 15m
MAX. interunit height difference: 15m
Amount of additional charge of refrigerant 20g/m for piping length exceeding 10m
The data are based on the conditions shown in the table below.
Models
Indoor Units FTY25CVMA FTY35CVMA
Outdoor Units
RY25CVMA RY35CVMA
Cooling Heating Cooling Heating
Capacity
kW 2.54 3.4 3.60 4.2
Btu/h 8,700 11,600 12,300 14,300
kcal/h 2,190 2,920 3,100 3,600 Moisture Removal L/h 1.2 1.9 — Running Current A 5.1 5.6 7.4 7.3 Power Consumption W 900 1,100 1,360 1,340 Power Factor % 80.2-76.7-73.5 89.3-85.4-81.8 83.5-79.9-76.6 83.4-79.8-76.5 COP W/W 2.82 3.09 2.65 3.13
Piping Connections
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ
9.5
φ
12.7
Drain mm
φ
18.0
φ
18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Indoor Units FTY25CVMA FTY35CVMA
Front Panel Color White White
Air Flow Rate
m³/min (cfm)
H 7.8 (275) 8.1 (286) 7.7 (272) 8.1 (286)
M 6.4 (226) 6.6 (233) 6.3 (222) 6.6 (233)
L 5.0 (177) 5.1 (180) 4.9 (173) 5.1 (180)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 18 18
Speed Steps 5 Steps and Auto 5 Steps and Auto Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current A 0.17-0.18-0.18 0.17-0.18-0.18 0.17-0.18-0.18 0.17-0.18-0.18 Power Consumption W 37-40-43 37-40-43 37-40-43 37-40-43 Power Factor % 98.9-96.6-99.5 98.9-96.6-99.5 98.9-96.6-99.5 98.9-96.6-99.5 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 273×784×195 273×784×195 Packaged Dimensions (H×W×D) mm 258×834×325 258×834×325 Weight kg 7.5 7.5 Gross Weight kg 11 11 Operation
Sound
H/M/L dBA 37 / 34 / 30 37 / 33 / 30 38 / 35 / 32 38 / 35 / 31
Outdoor Units RY25CVMA RY35CVMA
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Rotary Type Hermetically Sealed Rotary Type
Model RC1X26BTNT RC1X26BTNT
Motor Output W 750 750 Refrigerant
Oil
Type SUNI SO 4GSD.I. SUNISO 4GSD.I.
Charge L 0.4 0.4
Refrigerant
Type R22 R22
Charge kg 0.72 0.95
Air Flow Rate
m³/min 28.0-29.0-30.0 25.0-25.5-26.5 26.5-27.5-28.0 22.5-23.5-24.0
cfm 988-1,024-1,059 883-900-935 935-971-988 794-830-847
Fan
Type Propeller Propeller
Motor Output W 25 25 Running Current A 4.93-4.92-4.92 5.43-5.42-5.42 7.23-7.22-7.22 7.13-7.12-7.12 Power Consumption W 863-860-857 1,063-1,060-1,057 1,323-1,320-1,317 1,303-1,300-1,297 Power Factor % 79.6-76.0-72.6 89.0-85.0-81.3 83.2-79.5-76.0 83.1-79.4-75.9 Starting Current A 5.6 7.3 Dimensions (H×W×D) mm 560×695×265 560×695×265 Packaged Dimensions (H×W×D) mm 599×797×310 599×797×310 Weight kg 31 32 Gross Weight kg 34 36 Operation Sound dBA 45-46-47 46-47-48 46-47-48 47-48-49 Drawing No. 3D045884 3D045885
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Standard Cooling Heating Piping Length
JIS C 9612
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
Indoor ; 20°CDB
Outdoor ; 7°CDB/6°CWB
5m
Si01-406 Specifications
Specifications 9
The data on the conditions (AS/NZS3823.1) :
(Conditions)
(Rated)
FTY25CVMA FTY35CVMA
Cooling Heating Cooling Heating Capacity kW 2.5 3.4 3.5 4.2 Running Current A 5.1 5.6 7.4 7.3 Power Consumption W 960 1,090 1,485 1,500 COP W/W 2.60 3.12 2.36 2.80
Standard Cooling Heating Piping Length Power Supply
AS/NZS3823.1
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
Indoor ; 20°CDB
Outdoor ; 7°CDB/6°CWB
7.5m 50Hz 230V
Specifications Si01-406
10 Specifications
Si01-406
Printed Circuit Board Connector Wiring Diagram 11
Part 3
Part 3Part 3
Part 3
Printed Circuit Board
Printed Circuit BoardPrinted Circuit Board
Printed Circuit Board
Connector Wiring Diagram
Connector Wiring DiagramConnector Wiring Diagram
Connector Wiring Diagram
1. Printed Circuit Board Connector Wiring Diagram..................................12
1.1 FT25/35CV1A.........................................................................................12
1.2 FT50/60CV1A.........................................................................................14
1.3 FTY25/35CVMA .....................................................................................16
1.4 RY25/35CVMA .......................................................................................18
Printed Circuit Board Connector Wiring Diagram Si01-406
12 Printed Circuit Board Connector Wiring Diagram
1. Printed Circuit Board Connector Wiring Diagram
1.1 FT25/35CV1A
Connectors
Note: Other designations
1) S1 Connector for fan motor
2) S6 Connector for swing motor (horizontal blades)
3) S7 Connector for fan motor (Hall IC)
4) S21 Connector for centralized control (HA)
5) S26 Connector for signal receiver PCB
6) S27 Connector for control PCB
7) S32 Connector for heat exchanger thermistor
1) V1, V2, V3 Varistor
2) JA Address setting jumper JB Fan speed setting when compressor is OFF on thermostat JC Power failure recovery function
Refer to page 184 for detail.
3) SW7 Forced operation ON/OFF switch
4) LED1 LED for operation (green)
5) LED2 LED for timer (yellow)
6) FU1 Fuse (3.15A)
7) FU2 Fuse (0.315A)
8) RTH1 Room temperature thermistor
Si01-406 Printed Circuit Board Connector Wiring Diagram
Printed Circuit Board Connector Wiring Diagram 13
Control PCB Signal Receiver PCB
SW7
LED1
LED2
RTH1
S27
S7
5V Check
S6
12V Check
V1
S21
FU2
V2
V3
2P058891L
Control PCB
Signal receiver PCBS1FU1
S26JCGND JB JA S32
Printed Circuit Board Connector Wiring Diagram Si01-406
14 Printed Circuit Board Connector Wiring Diagram
1.2 FT50/60CV1A
Connectors
Note: Other designations
1) S1 Connector for fan motor
2) S6 Connector for swing motor (horizontal blades)
3) S21 Connector for centralized control (HA)
4) S26, S37 Connector for buzzer PCB
5) S27, S29 Connector for control PCB
6) S28 Connector for signal receiver PCB
7) S32 Connector for heat exchanger thermistor
8) S38 Connector for display PCB
1) V1, V2, V3 Varistor
2) JA Address setting jumper JB Fan speed setting when compressor is OFF on thermostat JC Power failure recovery function
Refer to page 184 for detail.
3) SW1 Forced operation ON/OFF switch
4) LED1 LED for operation (green)
5) LED2 LED for timer (yellow)
6) FU1 Fuse (3.15A)
7) RTH1 Room temperature thermistor
Si01-406 Printed Circuit Board Connector Wiring Diagram
Printed Circuit Board Connector Wiring Diagram 15
PCB Detail PCB(1): Control PCB
PCB(2): Signal Receiver PCB PCB(3): Buzzer PCB
PCB(4): Display PCB
S1
V1
V2
V3 FU1
S6
S26
C : 2P099167
S28S32JCJBJA
S21
SW1
S29
(R2861)
(R2862)
RTH1
S38
S27
LED1 LED2 S37
(R3087)
Printed Circuit Board Connector Wiring Diagram Si01-406
16 Printed Circuit Board Connector Wiring Diagram
1.3 FTY25/35CVMA
Connectors
Note: Other designations
1) S1 Connector for fan motor
2) S6 Connector for swing motor (horizontal blades)
3) S7 Connector for fan motor (Hall IC)
4) S21 Connector for centralized control (HA)
5) S26 Connector for signal receiver PCB
6) S27 Connector for control PCB
7) S32 Connector for heat exchanger thermistor
1) V1 Varistor
2) JA Address setting jumper JB Fan speed setting when compressor is OFF on thermostat JC Power failure recovery function
Refer to page 184 for detail.
3) SW7 Forced operation ON/OFF switch
4) LED1 LED for operation (green)
5) LED2 LED for timer (yellow)
6) FU1 Fuse (3.15A)
7) RTH1 Room temperature thermistor
Si01-406 Printed Circuit Board Connector Wiring Diagram
Printed Circuit Board Connector Wiring Diagram 17
Control PCB Signal Receiver PCB
FU1
S1
SW7
Signal receiver PCB
LED1
LED2
S27
RTH1
S7
S6
S26
S32JCJBJA
Control PCB
S21
V1
C:2P084366L
Printed Circuit Board Connector Wiring Diagram Si01-406
18 Printed Circuit Board Connector Wiring Diagram
1.4 RY25/35CVMA
Connectors
Note: Other designations
1) V1, V2, V3 Varistor
2) FU1 Fuse (3.15A)
3) FU2 Fuse (20A)
Outline of PCB
1) S10 Connector for PCB (2)
2) S11 Connector for PCB (1) (filter PCB)
3) S45 Connector for terminal board
4) S70 Connector for fan motor
5) S80 Connector for four way valve coil
6) S90 Connector for outdoor temperature thermistor / heat exchanger thermistor
7) S91 Connector for fin thermistor
C:1P101935-3K
S90S80S70
S10
FU2
PCB (1)
FU1 S91
S45
S11
PCB(2)
W
V
U
Si01-406 Printed Circuit Board Connector Wiring Diagram
Printed Circuit Board Connector Wiring Diagram 19
Detail of PCB (1)
Detail of PCB (2)
Connect to S11 on PCB (2)
C:3P100242-1B
FU2
S10
V3
V2
C:2P100238-7F
S11
S70 S80 S90
FU1
S91
S45
V1
Loading...
+ 182 hidden pages