Daikin PR71B7W1B, PR100B7V3B, PR71B7V3B, PR100B7W1B, PR125B7W1B Technical Data Manual

RR-B7
Pair/Twin/Triple/Double Twin
Application
technical data
Split Sky Air
air conditioning systems
Split - Sky Air
EEDE05-1/3 • 05/2005
Prepared in Belgium by Goekint Graphics
Zandvoordestraat 300 B - 8400 Ostend Belgium
Specifications are subject to change without prior notice.
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.
www.daikineurope.com
• Split Sky Air • Outdoor Units
1
• Outdoor Units • R-410A • RR-B7
TABLE OF CONTENTS
RR-B7
1 Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety device settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3Options
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4 Capacity tables
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Combination table
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Cooling capacity tables
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cooling capacity tables simultaneous operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5 Dimensional drawing & centre of gravity
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensional drawing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Centre of gravity
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6 Piping diagram
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7 Wiring diagram
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Wiring diagram
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
External connection diagram
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8 Sound data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sound pressure spectrum
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sound power spectrum
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9 Operation range
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
• Outdoor Units • R-410A • RR-B7
• Split Sky Air • Outdoor Units
2
27
1
OutdooSplitRR-B7R-410a
1Features
• Outdoor units for pair, twin, triple, double twin application
• Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.
• Outdoor units are fitted with a scroll compressor, renowned for low noise and high energy efficiency.
• The piping connections can be accessed from underneath, front, side or rear.
• The sevice valves are hidden inside the casing.
• A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions
27
2
• Split Sky Air • Outdoor Units
3
• Outdoor Units • R-410A • RR-B7
2 Specifications
2-1 TECHNICAL SPECIFICATIONS
RR71B7V3B RR71B7W1B RR100B7V3B RR100B7W1B RR125B7W1B
Casing Colour Daikin White
Material Painted galvanized steel plate
Dimensions Packing Height mm 900 900 1300 1300 1300
Width mm 980 980 980 980 980 Depth mm 420 420 420 420 420
Unit Height mm 770 770 1170 1170 1170
Width mm 900 900 900 900 900 Depth mm 320 320 320 320 320
Weight Machine Weight kg 83 81 102 99 106
Gross Weight kg 87 85 107 104 111
Heat Exchanger Dimensions Length mm 857 857 857 857 857
Nr of Rows 2 2 2 2 2 Fin Pitch mm 2.00 2.00 2.00 2.00 2.00 Nr of Passes 6 6 10 10 10 Face Area m
3
0.641 0.641 0.980 0.980 0.980
Nr of Stages 34 34 52 52 52 Tube type Hi-XSS cooling tube Fin Type Non-symmetric waffle louvre
Treatment Anti-corrosion treatment (PE)
Fan Type Direct Drive Propeller
Discharge direction Horizontal Quantity 11112 Air Flow Rate
(nominal)
Cooling m
3
/min 48.0 48.0 55.0 55.0 89.0
MotorQuantity 11111
Model P47L11S
Position Lower
Motor Speed (nominal
at 230V)
Steps 3 3 3 3 3
Fan Motor Output W 65 65 65 65 85
Drive direct drive
Position Upper
Motor Speed (nominal
at 230V)
Steps 3
Fan Motor Output W 65
Drive direct drive
Compressor Quantity 1 1 1 1 1
Motor Model JT90G-V1N JT90G-YE JT125G-V1N JT125G-YE JT160G-YE
Type Hermetically sealed scroll compressor
Motor
Output
W 2200 2200 3000 3000 3750
Starting Method Direct
Crankcase
Heater
W3333333333
Operation Range Cooling Min
°
CDB -15.0 -15.0 -15.0 -15.0 -15.0
Max
°
CDB 46.0 46.0 46.0 46.0 46.0
Sound Level (nominal)
Cooling Sound
Power
dBA 63.0 63.0 66.0 66.0 67.0
Sound
Pressure
dBA 50.0 50.0 53.0 53.0 53.0
Refrigerant Type R-410A
Charge kg 2.70 2.70 3.70 3.70 3.70 Control Expansion valve (electronic type) Nr of Circuits 11111
Refrigerant Oil Type Daphne FVC68D
Charged Volume l 1.5 1.5 1.5 1.5 1.5
• Outdoor Units • R-410A • RR-B7
• Split Sky Air • Outdoor Units
4
27
2
Piping connections
Liquid (OD)Quantity 11111
Type Flare connection Diameter
(OD)
mm 9.52 9.52 9.52 9.52 9.52
GasQuantity 11111
Type Flare connection Diameter
(OD)
mm 15.9 15.9 15.9 15.9 15.9
DrainQuantity 33333
Type Hole Diameter
(OD)
mm 26 26 26 26 26
Piping Length Minimum m 5 5 5 5 5
Maximum m 70 70 70 70 70 Equivalentm9090909090 Chargelessm3030303030
Installation height difference
Maximum m 30.0 30.0 30.0 30.0 30.0
Max. internunit level difference m 0.5 0.5 0.5 0.5 0.5
Heat Insulation Both liquid and gas pipes Defrost Method Reversed cycle Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method None Safety Devices Reverse phase protector
PC board fuse
Overcurrent relay (compressor)
Low pressure switch High pressure switch
Fan motor thermal protector
Standard Accessories
Item Declaration of conformity
Quantity 11111
Item Installation manual
Quantity 11111
2-1 TECHNICAL SPECIFICATIONS
RR71B7V3B RR71B7W1B RR100B7V3B RR100B7W1B RR125B7W1B
27
2
• Split Sky Air • Outdoor Units
5
• Outdoor Units • R-410A • RR-B7
2 Specifications
2-2 ELECTRICAL SPECIFICATIONS
RR71B7V3B RR71B7W1B RR100B7V3B RR100B7W1B RR125B7W1B
Power Supply Name V3 W1 V3 W1 W1
Phase 1 3N 1 3N 3N FrequencyHz5050505050
Voltage V 230 400 230 400 400 Current Recomended fuses A 32 16 40 16 20 Voltage range Minimum V 207 360 207 360 360
Maximum V 253 440 253 440 440 Wiring
connections
For Power Supply Quantity 1 1 1 1 1
Remark 3 wires (earth wire
included)
5 wires (earth wire
included)
3 wires (earth wire
included)
5 wires (earth wire
included)
5 wires (earth wire
included)
For connection
with indoor
Quantity 11111 Remark 4 wires (earth wire included)
Power Supply Intake Outdoor unit only
NOTES
1 Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings of
this chapter.
2 The sound power level is an absolute value indicating the power which a sound source generates.
3 Sound values are measured in a semi-anechoic room.
4 Heating capacity is only applicable for combination with heat pump outdoor unit.
5 In case of drain piping for outdoor unit, drain piping kit (option) is needed.
6 Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m,
level difference : 0m.
7 Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m,
level difference : 0m.
• Outdoor Units • R-410A • RR-B7
• Split Sky Air • Outdoor Units
6
27
2
2 Specifications
2 - 3 Electrical data
3TW26379-9A
Electrical data
Unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit Hz-volts Voltage range MCA TOCA MFA MSC RLA kW FLA kW FLA
FCQ71 RR71B7V3B 50-230
Max. 50Hz-264V Min. 50Hz-198V
16.6 23.3 32 75.5 12.2 0.065 0.6 0.045 0.7 FUQ71 RR71B7V3B 50-230 16.6 23.2 32 75.5 12.3 0.065 0.6 0.045 0.6 FHQ71 RR71B7V3B 50-230 16.8 23.2 32 75.5 12.5 0.065 0.6 0.062 0.6 FAQ71 RR71B7V3B 50-230 16.1 22.9 32 75.5 12.2 0.065 0.6 0.043 0.3 FBQ71 RR71B7V3B 50-230 17.4 23.5 32 75.5 12.7 0.065 0.6 0.125 0.9 FCQ71 RR71B7W1B 50-400/230
Max. 50Hz-440/253V Min. 50Hz-360/197V
7.4 11.3 16 41.1 4.8 0.065 0.6 0.045 0.7 FUQ71 RR71B7W1B 50-400/230 7.3 11.2 16 41.1 4.9 0.065 0.6 0.045 0.6 FHQ71 RR71B7W1B 50-400/230 7.5 11.2 16 41.1 5.0 0.065 0.6 0.062 0.6 FAQ71 RR71B7W1B 50-400/230 6.8 10.9 16 41.1 4.7 0.065 0.6 0.043 0.3 FBQ71 RR71B7W1B 50-400/230 8.1 11.5 16 41.1 5.3 0.065 0.6 0.125 0.9
SYMBOLS
MCA : Min. Circuit Amps TOCA : Total Over Current Amps MFA : Max. Fuse Amps (See note 7) LRA : Locked Rotor Amps RLA : Rated Load Amps OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps kW : Fan Motor Rated Output
NOTES
1 RLA is based on the following conditions:
Indoor temperature 27°CDB/19.5°CWB
Outdoor temperature 35°CDB 2 TOCA means the total value of each OC set 3 Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed
operation range limits 4 Maximum allowable voltage unbalance between phases is 2% 5 MCA/MFA
MCA = 1.25 x RLA + all FLA
MFA 2.25 x RLA + all FLA
(next lower standard fuse rating, min. 16A) 6 Select wire size based on the larger value of MCA or TOCA 7 Instead of fuse, use circuit breaker 8 For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select ’’Daikin
Documentation’’ and select ’’conditional connection’’, ’’the
requested product type’’ and ’’English’’ from the drop down
lists, click the search button.
Finally, click on the document title of your choice.
27
2
• Split Sky Air • Outdoor Units
7
• Outdoor Units • R-410A • RR-B7
2 Specifications
2 - 3 Electrical data
Electrical data
3TW26399-9
SYMBOLS
MCA: Min. Circuit Amps TOCA: Total Over-current Amps MFA: Max. Fuse Amps (see note 7) LRA: Locked rotor Amps RLA: Rated Load Amps OFM: Outdoor Fan Motor IFM: Indoor Fan Motor FLA: Full Load Amps KW: Fan Motor Rated Output
NOTES
1 RLA based on the following conditions:
Indoor temp. 27°CDB/19.5°CWB
Outdoor temp. 35°CDB 2 TOCA means the total value of each OC set. 3 Voltage range: units are suitable for use on electrical systems
where the voltage supplied to the unit terminals is not below
or above the listed range limits. 4 Maximum allowable voltage unbalance between phases is 2%. 5 MCA/MFA
MCA = 1.25 x RLA + all FLA
MFA 2.25 x RLA + all FLA
(next lower standard fuse rating Min. 16A) 6 Select wire size based on the larger value of MCA or TOCA. 7 Instead of fuse, use circuit breaker. 8 For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select “Daikin
Documentation” and select “conditional connection”, “the
requested product type” and “English” from the drop down
lists, click the search button. Finally, click on the document title
of your choice.
Unit combination
Power supply Compressor OFM IFM
Indoor unit Outdoor unit Hz-Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA
FCQ100 RR100B7V3B 50-230
Max. 50Hz - 264V
Min. 50Hz - 198V
23.8 34.8 40 98.5 17.6 0.090 0.8 0.090 1.0
FUQ100 RR100B7V3B 50-230 23.3 34.8 40 98.5 17.2 0.090 0.8 0.090 1.0
FHQ100 RR100B7V3B 50-230 23.0 34.5 40 98.5 17.2 0.090 0.8 0.130 0.7
FAQ100 RR100B7V3B 50-230 23.0 34.2 40 98.5 17.4 0.090 0.8 0.049 0.4
FBQ100 RR100B7V3B 50-230 23.2 34.8 40 98.5 17.1 0.090 0.8 0.135 1.0
FCQ100 RR100B7W1B 50-400/230
Max. 50Hz - 440/253V
Min. 50Hz - 360/197V
9.2 11.8 16 48.2 5.9 0.090 0.8 0.090 1.0
FUQ100 RR100B7W1B 50-400/230 8.9 11.8 16 48.2 5.7 0.090 0.8 0.090 1.0
FHQ100 RR100B7W1B 50-400/230 8.6 11.5 16 48.2 5.7 0.090 0.8 0.130 0.7
FAQ100 RR100B7W1B 50-400/230 8.3 11.2 16 48.2 5.7 0.090 0.8 0.049 0.4
FBQ100 RR100B7W1B 50-400/230 8.9 11.8 16 48.2 5.7 0.090 0.8 0.135 1.0
• Outdoor Units • R-410A • RR-B7
• Split Sky Air • Outdoor Units
8
27
2
2 Specifications
2 - 3 Electrical data
Electrical data
3TW26419-9
SYMBOLS
MCA: Min. Circuit Amps TOCA: Total Over-current Amps MFA: Max. Fuse Amps (see note 7) LRA: Locked rotor Amps RLA: Rated Load Amps OFM: Outdoor Fan Motor IFM: Indoor Fan Motor FLA: Full Load Amps KW: Fan Motor Rated Output
NOTES
1 RLA based on the following conditions:
Indoor temp. 27°CDB/19.5°CWB
Outdoor temp. 35°CDB 2 TOCA means the total value of each OC set. 3 Voltage range: units are suitable for use on electrical systems
where the voltage supplied to the unit terminals is not below
or above the listed range limits. 4 Maximum allowable voltage unbalance between phases is 2%. 5 MCA/MFA
MCA = 1.25 x RLA + all FLA
MFA 2.25 x RLA + all FLA
(next lower standard fuse rating Min. 16A) 6 Select wire size based on the larger value of MCA or TOCA. 7 Instead of fuse, use circuit breaker. 8 For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select “Daikin
Documentation” and select “conditional connection”, “the
requested product type” and “English” from the drop down
lists, click the search button. Finally, click on the document title
of your choice.
Unit combination
Power supply Compressor OFM IFM
Indoor unit Outdoor unit Hz-Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA
FCQ125 RR125B7W1B 50-400/230
Max. 50Hz - 440/253V
Min. 50Hz - 360/197V
11.9 15.3 20 63 7.7
0.065
+ 0.085
0.6
+ 0.7
0.09 1.0
FUQ125 RR125B7W1B 50-400/230 11.7 15.3 20 63 7.5
0.065
+ 0.085
0.6
+ 0.7
0.09 1.0
FHQ125 RR125B7W1B 50-400/230 11.4 15.0 20 63 7.5
0.065
+ 0.085
0.6
+ 0.7
0.13 0.7
FBQ125 RR125B7W1B 50-400/230 12.2 15.7 20 63 7.6
0.065
+ 0.085
0.6
+ 0.7
0.225 1.4
FDQ125 RR125B7W1B 50-400/230 14.9 18.5 20 63 7.5
0.065
+ 0.085
0.6
+ 0.7
0.5 4.2