This manual provides the procedures of installation to ensure a safe and good standard of operation for the air
conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for
commercial use by lay persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
SAFETY PRECAUTIONS
! WARNING! CAUTION
Installation and maintenance should be performed by
•
qualified persons who are familiar with local code
and regulation, and experienced with this type of
appliance.
All field wiring must be installed in accordance with
•
the national wiring regulation.
Ensure that the rated voltage of the unit corresponds to
•
that of the name plate before commencing wiring work
according to the wiring diagram.
The unit must be GROUNDED to prevent possible
•
hazard due to insulation failure.
All electrical wiring must not touch the refrigerant
•
piping, or any moving parts of the fan motors.
Confirm that the unit has been switched OFF before
•
installing or servicing the unit.
Disconnect from the main power supply before servicing
•
the air conditioner unit.
DO NOT pull out the power cord when the power is
•
ON. This may cause serious electrical shocks which
may result in fire hazards.
•
Keep the indoor and outdoor units, power cable and
transmission wiring, at least 1m from TVs and radios,
to prevent distorted pictures and static. {Depending on
the type and source of the electrical waves, static may
be heard even when more than 1m away}.
Please take note of the following important points when
installing.
Do not install the unit where leakage of flammable
•
gas may occur.
If gas leaks and accumulates around the unit, it
may cause fire ignition.
Ensure that the drainage piping is connected
•
properly.
If the drainage piping is not connected properly,
it may cause water leakage which will dampen
the furniture.
Do not overcharge the unit.
•
This unit is factory pre-charged. Overcharge
will cause over-current or damage to the
compressor.
Ensure that the unit’s panel is closed after service or
•
installation.
Unsecured panels will cause the unit to operate
noisily.
•
Sharp edges and coil surfaces are potential locations
which may cause injury hazards. Avoid from being in
contact with these places.
•
Before turning off the power supply, set the remote
controller’s ON/OFF switch to the “OFF” position to
prevent the nuisance tripping of the unit. If this is not
done, the unit’s fans will start turning automatically when
power resumes, posing a hazard to service personnel or
the user.
•
Do not install the units at or near doorway.
•
Do not operate any heating apparatus too close to the air
conditioner unit or use in room where mineral oil, oil
vapour or oil steam exist, this may cause plastic part to
melt or deform as a result of excessive heat or chemical
reaction.
•
When the unit is used in kitchen, keep flour away from
going into suction of the unit.
•
This unit is not suitable for factory used where cutting oil
mist or iron powder exist or voltage fluctuates greatly.
•
Do not install the units at area like hot spring or oil refinery
plant where sulphide gas exists.
•
Ensure the color of wires of the outdoor unit and the
terminal markings are same to the indoors respectively.
•
IMPORTANT : DO NOT INSTALL OR USE THE
AIR CONDITIONER UNIT IN A LAUNDRY
ROOM.
•
Don’t use joined and twisted wires for incoming power
supply.
•
The equipment is not intended for use in a potentially
explosive atmosphere.
English
3
Page 6
INSTALLATION DIAGRAM
Indoor Unit
Front Panel
Air Filter
(behind the grille)
Air Discharge Louver
Air Intake
Drain Piping
Air Discharge
Thermal Insulation
Wrap the insulated pipe with the
À nishing tape from bottom to top
Air Intake Grille
Air Intake
Outdoor Unit
INSTALLATION OF THE INDOOR UNIT
Preliminary Site Survey
Be sure to read this manual before installing the air-conditioner indoor unit.
•
Voltage supply Á uctuation must not exceed +10% of rated voltage. Electricity supply lines must be independent of
welding transformers which can cause high supply Á uctuation.
•
Ensure that the location is convenient for wiring, piping and drainage.
•
Do not exert pressure on the resin parts when opening the unit or when moving it after opening.
•
Do not move the unit from packaging while moving, until it reaches the installation site. Use safe material or protection
plates when unpacking it or lifting it to avoid damage or scratches to the unit.
Beam
1m or more
Obstacle
0.5m or more0.5m or more0.5m or more
3m or more
Floor
0.3m or less
4
Page 7
•
Ensure a location where:
a)
Drainage can be done easily.
b)
Convenient for wiring and piping.
c)
Which have enough space for installation and service work.
d)
Where no risk of flammable gas leakage.
e)
When free from any obstacles in path of cool air discharge and warm air return and must allow spreading of air
throughout the room (near the center of the room).
f)
Must be provided clearance for indoor unit from the wall and obstacles as shown in figure below.
g)
The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying
noise and vibration.
h)
The installation place (hanging ceiling surface) must be assuring levelness and the height in the ceiling is 350mm or
more.
i)
The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
Unit Installation
•
Measure and mark the position for the hanging rod.
Ceiling Opening Site = 890mm
Hanging Rod Site = 790mm
Unit size 820mm
Drill the hole for the angle nut on the ceiling and fix the
hanging rod.
•
The installation template is extended according to
temperature and humidity. Check on dimensions in use.
•
The dimensions of the installation template are the same
as those of the ceiling opening dimensions.
Before ceiling laminating work is completed, be sure to
•
fit the installation template to the indoor unit.
English
Unit Hanging
Unit
Indoor Unit
Unit size 820mm
Hanging rod size = 621mm
Piping Direction
Ceiling
Board
30 mm
NOTE
Be sure to discuss the ceiling drilling work with the
installers concerned.
Ceiling Opening Site = 890mm
•
Confirm the pitch of the hanging rod is 770mm x 622mm
sharp.
•
Hold the unit and hang it on the hanging rod with the nut
and washer.
•
Adjust the unit height to 30mm between the indoor unit
bottom surface and the ceiling surface.
•
Confirm with a level gauge that the unit is installed
horizontally and tighten the nut and bolt to prevent unit
falling and vibration.
•
Open the ceiling board along the outer edge of the paper
installation template.
5
Page 8
Avoid installing the drain pipe in upward gradient after
Drain Piping Work
Flexible Hose
Pipe Clamp
•
the drain connection.
Ensure the height of drain pipe from ceiling is 700mm or
•
less if it is necessary to increase the height of drain pipe
to prevent water leak.
Avoid installing the drain pipe in up and down slope to
•
prevent reversed water flow.
During the drain pipe connection, be careful not to exert
•
extra force on the drain connector at indoor unit.
The outside diameter of the drain connection at the
•
Panel
Indoor
Unit
700.0mm or less
Ceiling
flexible drain hose is 20mm.
Be sure to execute heat insulation (polyethylene foam
•
with thickness more than 8mm) on the drain piping to
Drain Test
Feed Water
Main Drain Pipe
avoid the condensed water dripping inside the room.
Connect the main drain pipe to the flexible drain hose.
•
Feed water from flexible drain hose to check the piping
•
for leakage.
When the test is completed, connect the flexible drain
•
Flexible Drain Hose
hose to the drain connector on the indoor unit.
NOTE
This Indoor Unit uses a drain pump for condensed water drainage. Install the unit horizontally to prevent water leakage
or condensation around the air outlet.
Panel Installation
The front panel can only be fitted in one direction, follow the piping direction. (Follow piping arrow sticker on front
•
panel)
Be sure to remove the installation template before installing the front panel.
•
Open
Screw
•
Open the air intake grille by pulling back the catchers and removing it together with filter from panel.
•
Install the front frame panel onto the indoor unit by 4 screws and tighten it completely to prevent cool air leakage.
•
Connect the LED wire and air swing wire to the indoor unit.
•
The air swing connector must put inside the control box after connected.
LED Wire
From Front
Panel
From Unit
Control Box
Air Swing Wire
6
Page 9
NOTE
Install the front frame panel À rmly to prevent cool air leakage which will cause condensation and water dripping.
Indoor Unit
Cool
Air
Cool
Air
Air Leak
English
Ceiling Board
Air Leak
Panel
Cover Lock Grille (The moving part protection for user direct touching)
Cover lock grille must be installed as the figure below.
Intake Grille
Ceiling Board
Panel
Frame
Cover Lock Grille
(2pcs)
Screw 4 x 6
(2pcs)
If the unit need to be service, steps below shall be followed:
1.
ConÀ rm that the unit had been switched off before servicing the unit.
2.
Use screwdriver to unlock the screw on the cover lock grille.
3.
Remove the cover lock grille and open the intake grille for the service purpose.
4.
Install the intake grille and screw the cover lock grille after service and make sure the unit is proper install.
7
Page 10
Wires Installation
Figure A
Figure A and Figure B shows the location of cover wire in indoor unit.
Steps to install power supply wires and wires from outdoor unit.
1.
Remove wire cover by removing 2 screws as shown in Figure C.
2.
Wires will go through the hole as shown in Figure D and E respectively without crossing the height of the hole.
3.
After that, wire cover will be assembled back to close the wire.
Figure BFigure C
Figure DFigure E
8
Page 11
INSTALLATION OF THE OUTDOOR UNIT
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum
cooling capacity, the location selected for outdoor unit should fulfill the following requirements:
Install the condensing (outdoor) unit in a way such that the hot air distributed by the outdoor condensing unit cannot be drawn
•
in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.
Ensure that there is no obstruction of air Á ow into or out of the unit. Remove obstacles which block air intake or
•
discharge.
The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering the condensing
•
temperature.
English
A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
•
A place protected from the direct sunlight. Otherwise use an awning for protection, if necessary.
•
The location must not be susceptible to dust or oil mist.•
! CAUTION
Do not install the unit at altitude over 2000m for both indoor and outdoor.•
9
Page 12
INSTALLATION CLEARANCE
Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air Á ow.
•
Select the coolest possible place where intake air should not be hotter than the outside temperature (refer to operating
range).
AB
Air
Inlet
Obstacle
All Model
Minimum Distance (mm)
Air
Discharge
Obstacle
ABCD
3001000300500
C
Obstacle
D
MADE IN MALAYSIA
Service
Space
Obstacle
REFRIGERANT PIPING
Allowable Pipe Length and Elevation
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to
the Á ow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective.
Always choose the shortest path and follow the recommendations as tabulated below:
Be sure to add the proper amount of additional refrigerant, failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor unit is for the piping length up to 7.5m.
10
Page 13
Piping Works And Flaring Technique
Do not use contaminated or damaged copper tubing. If any pipings, evaporator or condenser had been exposed or had been
•
opened for 15 seconds or more, the system must be vacuumed. Generally, do not remove plastic, rubber plugs and brass
nuts from the valves, fittings, tubings and coils until it is ready to connect suction or liquid line into valves or fittings.
If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is
•
being done. This will eliminate soot formation on the inside walls of the copper tubings.
Cut the pipe stage by stage, advancing the blade of the pipe cutter slowly. Extra force and deep cut will cause more distortion
•
on the pipe and thus extra burr. See Figure I.
Remove burrs from cut edges of the pipes with remover
•
as shown in Figure II. This will avoid unevenness on the
flare faces which will cause gas leak. Hold the pipe on
top position and burr remover at lower position to prevent
metal chips from entering the pipe.
Insert the flare nuts, mounted on the connection parts
•
Figure I
Cutting Copper Tube
1/4t
of both the indoor unit and outdoor unit, into the copper
pipes.
The exact length of pipe protruding from the top surface
•
Figure II
of the swaging block is determined by the flaring tool.
Refer Figure III.
Fix the pipe firmly on the flare die. Match the centers of
•
Remove Burr
both the flare die and the flaring punch, and then tighten
the flaring punch fully.
Piping Connection To The Units
Align the center of the piping and tighten the flare nut
•
sufficiently with fingers. Refer Figure IV.
Finally, tighten the flare nut with the torque wrench until
•
the wrench clicks.
When tightening the flare nut with the torque wrench,
•
ensure that the tightening direction follows the arrow
indicated on the wrench.
The refrigerant pipe connection are insulated by closed
* These values are for information only. They should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and size of conductors.
** The appropriate voltage range should be checked with data label on the unit.
FHC20JEV1K - RD20JEV1K
FHC25JEV1K - RD25JEV1K
COMP
L1
Outdoor Unit
Terminal Block
N1
L
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
Indoor Unit
Terminal Block
COMP
L
N
Interconnection Cable
Power Supply
Cable
ModelIndoorFHC20JEV1KFHC25JEV1K
OutdoorRD20JEV1KRD25JEV1K
Voltage range**Indoor
Outdoor
Power supply cable size* mm
Number of conductors
Interconnection cable size* mm
Number of conductors
2
2
220-240V/1Ph/50Hz + !
220-240V/1Ph/50Hz + !
2.5
3
1.0
4
4
3
1.0
4
Recommended time delay fuse* A2025
FHC30JEV1K - RD30JEV1K
Indoor Unit
Terminal Block
COMP
L
N
Interconnection Cable
Power Supply Cable
Outdoor Unit
COMP
Terminal Block
L
N
L
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
ModelIndoorFHC30JEV1K
OutdoorRD30JEV1K
Voltage range**Indoor
Outdoor
Power supply cable size* mm
Number of conductors
Interconnection cable size* mm
Number of conductors
2
2
220-240V/1Ph/50Hz + !
220-240V/1Ph/50Hz + !
4
3
2.5
4
Recommended time delay fuse* A30
12
Page 15
FHC40JEV1K - RD40JEV1K
L
N
S
R
Outdoor Unit
COMP
Terminal Block
L
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
Indoor Unit
Terminal Block
Power Supply Cable
COMP
L
N
Interconnection Cable
ModelIndoorFHC40JEV1K
OutdoorRD40JEV1K
Voltage range**Indoor
Outdoor
Power supply cable size* mm
Number of conductors
Interconnection cable size* mm
Number of conductors
2
2
220-240V/1Ph/50Hz + !
220-240V/1Ph/50Hz + !
4.0
3
2.5
4
Recommended time delay fuse* A35
FHC40JEV1K - RD40JEY1K
English
Interconnection Cable
Power Supply Cable
COMP
L
N
Outdoor Unit
Terminal Block
R
S
T
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
Indoor Unit
Terminal Block
COMP
L
N
ModelIndoorFHC40JEV1K
OutdoorRD40JEY1K
Voltage range**Indoor
Outdoor
Power supply cable size* mm
Number of conductors
Interconnection cable size* mm
Number of conductors
2
2
220-240V/1Ph/50Hz + !
308-415V/3N~/50Hz + !
2.5
5
2.5
4
Recommended time delay fuse* A15
13
Page 16
FHC50JEV1K - RD50JEY1K
Indoor Unit
Terminal Block
COMP
L
N
Interconnection Cable
Power Supply Cable
Outdoor Unit
COMP
Terminal Block
L
N
R
S
T
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
ModelIndoorFHC50JEV1K
OutdoorRD50JEY1K
Voltage range**Indoor
Outdoor
Power supply cable size* mm
Number of conductors
Interconnection cable size* mm
Number of conductors
2
2
220-240V/1Ph/50Hz + !
308-415V/3N~/50Hz + !
2.5
5
2.5
4
Recommended time delay fuse* A16
•
All wires must be firmly connected.
•
Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
•
The connecting wire between the indoor unit and the outdoor unit must be clamped on the wire clamps.
•
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
•
Make sure no external pressure is applied to the terminal connectors and wires.
•
Make sure all the covers are properly fixed to avoid any gap.
•
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
Attach insulation sleeve
Round crimp-style terminal
Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
•
Over tightening can damage the terminal screw.
•
Do not connect wire of different gauge to same terminal.
•
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
•
Connect wires of the
same gauge to both side.
Do not connect wires of the
same gauge to one side.
Electric wire
Do not connect wires
of different gauges.
14
Page 17
VACUUMING AND CHARGING
Vacuuming is necessary to eliminate all moisture and air from the system. The series II Outdoor Unit is provided with flare
valve fittings.
Vacuuming The Piping And The Indoor Unit
Except for the outdoor unit which is pre-charged with refrigerant,
Allen key
Flare nut
Refrigerant Piping
the indoor unit and the refrigerant connection pipes must be
air-purged because the air containing moisture that remains in the
refrigerant cycle may cause malfunction of the compressor.
Remove the caps from the valve and the service port.
•
Connect the center of the charging gauge to the vacuum
•
pump.
Connect the charging gauge to the service port of the 3-way
•
Service Port
Outdoor Unit 3 ways valve
valve.
Start the vacuum pump. Evacuate for approximately 30
•
minutes. The evacuation time varies with different vacuum
pump capacity. Confirm that the charging gauge needle has
LOW PRESSURE GAUGE
-760mmHg
HIGH PRESSURE GAUGE
GAUGE MANIFOLD
moved towards -760mmHg.
Caution
•
If the gauge needle does not move to -760mmHg, be sure to
check for gas leaks (using the refrigerant detector) at flare type
connection of the indoor and outdoor unit and repair the leak
before proceeding to the next step.
•
Close the valve of the changing gauge and stop the vacuum
pump.
•
On the outdoor unit, open the suction valve (3 way) and liquid
valve (2 way) (in anti-clockwise direction) with 4mm key for
hexagon sacked screw.
HANDLE LO
CHARGE HOSE
LIQUID VALVE
GAS VALVE
(3-WAY)
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
VACUUM PUMP
ADAPTER FOR
COUNTER FLOW
PREVENTION
CHECK VALVE
CONFIGURATION OF AIR
PURGE BY CHARGING
Charge Operation
This operation must be done by using a gas cylinder and a precise
weighing machine. The additional charge is topped-up into the
outdoor unit using the suction valve via the service port.
•
Remove the service port cap.
•
Connect the low pressure side of the charging gauge to the
suction service port center of the cylinder tank and close the
high pressure side of the gauge. Purge the air from the service
hose.
•
Start the air conditioner unit.
•
Open the gas cylinder and low pressure charging valve.
•
When the required refrigerant quantity is pumped into the unit,
close the low pressure side and the gas cylinder valve.
•
Disconnect the service hose from service port. Put back the
service port cap.
LOW PRESSURE GAUGE
-760mmHg
HANDLE LO
CHARGE HOSE
LIQUID VALVE
GAS VALVE
(3-WAY)
HIGH PRESSURE GAUGE
GAUGE MANIFOLD
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
CHECK VALVE
CONFIGURATION OF AIR
PURGE BY CHARGING
English
ADDITIONAL CHARGE
The refrigerant is pre-charge in the outdoor unit. If the piping length is less than 7.5m, then additional charge after
vacuuming is not necessary. If the piping length is more than 7.5m then use the additional charge value as indicated in the
table.
Additional refrigerant charge [g] per additional 1m length as tabulated
Cooling only
Model
Additional charge [g/m]193855656554
Example:
FHC25JEV1K & RD25HEV1K with 13m piping length, additional piping length is 5.5m. Thus,
Additional charge = 5.5[m] x 38[g/m]
= 209[g]
SPECIAL PRECAUTIONS WHEN CHARGING UNIT WITH SCROLL COMPRESSORS
These precautions are intended for use with Scroll compressors only with R22 refrigerants but are not applied to others
competitive Scroll compressors.
Scroll compressors have a very high volumetric efficiency and quickly pump a deep vacuum if there is insufficient refrigerant
in the system or if refrigerant is added too slowly. Operation with low suction pressure will quickly lead to very high discharge
temperatures. While this process is happening, the scrolls are not being well lubricated – scrolls depend on the oil mist in the
refrigerant for lubrication. A lack of lubrication leads to high friction between the scroll flanks and tips and generates additional
heat. The combination of heat of compression and heat from increased friction is concentrated in a small localized discharge
area where temperatures can quickly rise to more than 300ÝC. These extreme temperatures damage the Scroll spirals and the
orbiting Scroll bearing. This damage can occur in less than one minute especially on larger compressors. Failure may occur
in the first few hours or the damage done during field charging may show up some time later.
Other typical field charging problems include undercharging, overcharging, moisture or air in the system etc. In time each
one of these problems can cause compressor failure.
Minimal equipment is required for field charging. The minimum equipment required to do a satisfactory job is:-
Set of service gauges1.Vacuum gauge4.
Hoses2.Scales5.
Vacuum pump3.Thermometer6.
The proper refrigerant charge should follow the volume as recommended by manufacturer and recommendation should be
followed by the installer.
Charging procedures – Single phase compressors
1.
Evacuate the system to -760mmHg. To reduce evacuation time, use short, large diameter hoses and connect to unrestricted
service ports on the system. Quality of vacuum cannot be determined by time – a reliable vacuum gauge must be used.
(etc. electronic vacuum gauge)
Turn the refrigerant cylinder upside down, purge the charging hose and charge liquid through the liquid line charging port
until refrigerant no longer Á ows or until the correct charge has been weighed in. If additional charge is required start the
system and slowly bleed liquid into the suction side until the system is full.
It recommends charging liquid in a CONTROLLED manner into the suction side until the system is full.
This recommendation does not hold true for reciprocating compressors where liquid charging into the suction side could
cause severe damage.
Carefully monitor the suction and discharge pressures – ensure that the suction pressure does not fall below 25 psig (1.7 bar)
at any time during the charging process.
Dip-pipe
Invert cylinder
without dip-pipe
Liquid withdrawal
! CAUTION
Manifold Gauge will show cylinder pressure rather than suction pressure if the cylinder valve and Manifold
•
valve “A” are both open.
There are many ways of charging liquid in a “controlled manner” into the
suction side:-
Use valve A on the manifold gauge set
1.
Use the valve on the refrigerant cylinder
2.
Charge through a Shredder valve
3.
Use a hose with a Shredder valve depressor
4.
Charge into the suction side at some distance from the compressor
A
5.
All of the above
6.
16
Page 19
Charging procedures – Three phase compressors
2.
The fundamental procedure is the same as for single phase models but the compressor can run in the wrong direction on
starting.
If this happens reverse any two phases and start again. Short term reverse rotation will not damage the compressor.
All Specter compressors have internal discharge temperature protectors which are very effective in preventing dangerously
high discharge temperatures during charging. The protection module will trip and lock the compressor out for 30 minutes.
It is not normally necessary to wait 30 minutes for the module to reset. When the compressor has cooled down the module
can be reset by breaking the power supply to the control circuit. Very often the serviceman does not understand why the
module tripped and uses a jumper wire to bypass it. He continues to charge the system and removes the jumper when
charging is complete. The compressor may or may not run with the protector back in the circuit but it is certain that the
compressor has been damaged and premature failure is inevitable.
OPTIONAL FUNCTIONS
Short Duct SpeciÀ cation
The indoor unit is provided with air discharge and air intake “knock-out” hole for duct connection. However the connection
•
of the short duct for air discharge is possible on only one side.
The use of short duct for air discharge will improve airflow distribution if there is an obstruction (such as a lighting fixture)
•
or in a long, narrow room or an L-shaped room. It also use for air conditioning of two rooms simultaneously.
Possible Direction For Air Discharge And Air Intake
Air DischargeAir Discharge
Possible Opening Dimension For Duct Connection
50 50 50 50 50 10
10
90
207020
PCD Ø140
Ø100
English
11520115
Air DischargeAir Discharge
Air Intake
Air Discharge Knock Out HoleAir Intake Knock
Out Hole
NOTE
Avoid using the short duct on which the air discharge grille can be completely closed, to prevent evaporator
•
freezing.
In order to prevent condensation forming, be sure that there is sufficient thermal insulation and no leakage of cool air
•
when installing the short duct.
Keep the introduction of fresh air intake within 20% of total air Á ow. Also provide a chamber and use a booster fan.
•
Sealing Material
It is possible to seal one of the four air discharge outlet. (sealing two or more air discharge outlet could cause a
•
malfunction)
Remove the front panel and insert the sealing material into the air discharge outlet on the indoor unit to seal the air
•
outlet.
The sealing material is the same length as the longer air discharge outlet. If it is desired to seal the shorter air discharge
•
outlet, cut the sealing material to shorten it.
•
Push the sealing material in about 10mm beyond the bottom surface of the indoor unit so that it does not touch the air
louver. Be sure not to push the sealing material in any farther than about 10mm.
17
Page 20
INDICATOR LIGHTS
FAULT DIAGNOSIS
Wireless Controller
When there is infrared remote control operating signal, the signal receiver on indoor unit will make a <beep> for signal
acceptance conÀ rmation.
Wired Controller
If there is any abnormal condition detected, wired controller will blink the error code.
EventPower LEDTimer LEDOther LEDsError Code
1. Room Sensor Open or ShortBlink 1 time-Blink FanBlink E1
Power LED = Cool/Dry/Fan LED, turns on in these modes
The unit will not detect sensor missing when the compressor is ON
Call your dealer immediately when this error happen
OPERATING RANGE
COOLING
Outdoor
DB (°C)
54
52
19
14
1923 Indoor WB (°C)
DB = Dry Bulb WB = Wet Bulb
18
Page 21
OVERALL CHECKING
Ensure that:
•
The unit has been mounted solidly and rigid in
1)
position.
The piping and connections are leak-proof after the
2)
charging.
3)
Proper wiring has been installed.
•
Drainage check
– pour some water into the left side of the drain pan (the
drainage is at the right side of the unit).
•
Test run:
1)
Conduct a test run on the unit after having perform the
water drainage test and the gas leakage test.
2)
Check the following items:
a)
Is the electrical plug inserted firmly into the socket?
b)
there any abnormal sounds from the unit?
Is
c)
Is there any abnormal vibrations on the unit or the
piping?
he drainage of water smooth?
d)
Is t
Confirm that:
•
The condenser fan is running. Check the warm air
1)
blowing from the condensing unit.
The evaporator blower is running and discharge cool
2)
air.
The suction (low side) pressure is as recommended.
3)
The remote controller incorporates a 3-minute delay
4)
protection in the circuit, whereby the outdoor condensing
unit requires about 3 minutes delay before it can start
operating.
PHASE PROTECTOR (OPTIONAL)
The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase protector) is fitted
to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase protector
operates, and the unit will not start. This device is located in the control box of the outdoor unit.
The following table shows the LED indicator light for phase protector under normal operation and fault conditions.
English
Description
Normal operation
Reverse phase
T phase missing
S phase missing
R phase missing
S &T phase missing
Overload
Sensor missing
ON
LED
+
+
PW
(Red)
P_R
(Yellow)
P_S
(Yellow)
P_T
(Yellow)
Actions
-
Switch off the unit. Check the 3 phase wiring.
Switch off the unit. Check the 3 phase wiring.
Switch off the unit. Check the 3 phase wiring.
Switch off the unit. Check the 3 phase wiring.
+
Switch off the unit. Check the 3 phase wiring.
High discharge temperature. Check the refrigerant system.
Switch off the unit. Plug in sensor.
OFF
Fast Blink
NOTE
1. “+” indicates additional functions for PP01 phase protector.
2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 and relay 81 will cut off.
19
Page 22
SERVICE AND MAINTENANCE
Service PartsMaintenance ProceduresPeriod
Indoor Air FilterRemove any dust adhering to the À lter by using a vacuum cleaner
1.
or wash in lukewarm water (below 40°C) with a neutral cleaning
detergent.
Rinse the À lter well and dry before placing it back onto the unit.
2.
Do not use gasoline, volatile substances or chemicals to clean the À lter.
3.
At least every
2 week.
More frequently
if necessary.
Indoor UnitClean any dirt or dust on the grille or panel by wiping it with a soft
Indoor FanCheck for any abnormal noise.1.When necessary
1.
cloth soaked in lukewarm water (below 40°C) and a neutral detergent
solution.
Do not use gasoline, volatile substances or chemicals to clean the indoor
2.
unit.
At least every
2 week.
More frequently
if necessary.
! CAUTION
Avoid direct contact of any coil treatment cleaners on plastic part. This may cause plastic part to deform
•
as a result of chemical reaction.
TROUBLESHOOTING
For any enquiries on spare parts, please contact your authorized dealer. If any malfunction of the air
conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault
conditions and causes for some simple troubleshooting tips.
FaultCauses / Action
The compressor does not start operate after 3 minutes
1.Protection against frequent starting. Wait for 3 to 4
from starting the air conditioner unit.
The air conditioner unit does not operate.2.Power failure, or the fuse need to be replaced.
minutes for the compressor to start operating.
-
-
The power plug is disconnected.
-
It is possible that your delay timer has been set
incorrectly.
The air flow is too low.3.The air filter is dirty.
Discharge air flow has bad odor.4.Odors may be caused by cigarettes, smoke particles,
Condensation on the front air grille of the indoor unit.5.This is caused by air humidity after an extended long
Water flowing out from the air conditioner unit.6.Switch off unit and call local dealer/serviceman.-
-
-
The air suction and discharge are clogged.
-
The regulated temperature is not high enough (applicable
for auto fan mode only).
perfume etc. which might have adhered onto the coil.
period of operation.
-
The set temperature is too low, increase the temperature
setting and operate the unit at high fan speed.
If the fault persists, please call your local dealer / serviceman.
20
Page 23
Page 24
In the event that there is any conflict in the interpretation of this manual and any translation of the same in any language,
•
the English version of this manual shall prevail.
The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior