READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
Precautions
■Do not install or operate the unit in rooms mentioned below.
- Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)
- Where corrosive gas like sulphurous gas exists. (Copper
tubing and brazed spots may corrode.)
- Where volatile flammable gas like thinner or gasoline is used.
- Where machines generating electromagnetic waves exist.
(Control system may malfunction.)
- Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories).
Also in vehicles or vessels.
■When selecting the installation site, use the supplied paper
pattern for installation.
■Do not install accessories on the casing directly. Drilling holes in
the casing may damage electrical wires and consequently cause
fire.
Accessories
Check if the following accessories are included with your unit.
See figure 1
1Drain hose
2Metal clamp
3Washer for hanger bracket
4Paper pattern for installation
5Srews (M5) for paper pattern for installation
6Insulation for gas pipe fitting
7Insulation for liquid pipe fitting
8Large sealing pad
9Small sealing pad
10Sealing material
11Installation manual and operation manual
BEFOREINSTALLATION
■When moving the unit while removing it from the carton box, be
sure to lift it by holding on to the four lifting lugs without exerting
any pressure on other parts, especially on the swing flap, the
refrigerant piping, drain piping, and other resin parts.
■Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.
■Especially, do not unfasten the packing case (top) guarding the
switch box until suspending the unit.
■Refer to the installation manual of the outdoor unit for items not
described in this manual.
■Caution concerning refrigerant series R410A:
The connectable outdoor units must be designed exclusively for
R410A.
Installation manual
1
Optional accessories
■There are two types of remote controllers: wired and wireless.
Select a remote controller according to customers request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.
■A decoration panel is also required for this indoor unit.
FFQ25~60B8V1B
Split System air conditioners
4PW23700-1B
Page 5
For the following items, take special care during
1Sealing material
2False ceiling
construction and check after installation is finished
Tick ✓
when
checked
Is the indoor unit fixed firmly?
■
■
■
■
■
■
■
■
■
■
The unit may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the
name plate?
The unit may malfunction or components may burn out.
Are wiring and piping correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded?
Dangerous at electric leakage.
Is the wiring size according to specifications?
The unit may malfunction or components may burn out.
Is nothing blocking the air outlet or inlet of either the indoor or
outdoor units?
It may result in insufficient cooling.
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system might not be clear.
3Air flow directions
Select the air flow directions best suited to the room and point of
installation. (For air discharge in 2 or 3 directions, it is necessary
to make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to "Field setting" on page 7. (See
figure 2) (: air flow direction)
1Air discharge in 4 directions
2Air discharge in 3 directions
3Air discharge in 2 directions
4Use suspension bolts for installation. Check whether the
ceiling is strong enough to support the weight of the indoor
unit. If there is a risk, reinforce the ceiling before installing
the unit.
(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see figure 6 (: air flow
direction)
1Air inlet
2Air outlet
NOTE
Leave 200 mm or more space where marked with *, on
sides where the air outlet is closed.
Notes to the installer
■Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.
■Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.
SELECTINGINSTALLATIONSITE
When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 mm thickness,
polyethylene foam).
For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 2 or
3 directions.
1Select an installation site where the following conditions
are fulfilled and that meets your customer's approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate water can be properly drained.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service can be
ensured.
• Where piping between indoor and outdoor units is possible within
the allowable limit. (Refer to the installation manual of the outdoor
unit.)
•Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions and
radios. This is to prevent image interference and noise in those
electrical appliances. (Noise may be generated depending on the
conditions under which the electric wave is generated, even if
1 meter is kept.)
2Ceiling height
Install this unit where the height of bottom panel is more than
2.5 m so that the user cannot easily touch.
PREPARATIONSBEFOREINSTALLATION
1Relation of ceiling opening to unit and suspension bolt
2Make the ceiling opening needed for installation where
Installation is possible with a ceiling dimension of
660 mm (marked with *). However, to achieve a ceilingpanel overlapping dimension of 20 mm, the spacing
between the ceiling and the unit should be 45 mm or
less. If the spacing between ceiling and the unit is over
45 mm, attach sealing material in the part marked
or recover the ceiling.
(See figure 3)
applicable. (For existing ceilings.)
- Refer to the paper pattern for installation for the ceiling
opening dimensions.
- Create the ceiling opening required for installation. From the
side of the opening to the casing outlet, implement the
refrigerant and drain piping and wiring for remote controller
(unnecessary for wireless type). Refer to each piping or
wiring section.
- After making an opening in the ceiling, it may be necessary
to reinforce ceiling beams to keep the ceiling level and to
prevent it from vibrating. Consult the builder for details.
FFQ25~60B8V1B
Split System air conditioners
4PW23700-1B
Installation manual
2
Page 6
3Install the suspension bolts. (Use either a M8~M10 size bolt.)
Pipe size
Further tightening
angle
Recommended arm
length of tool
Ø6.460~90°±150 mm
Ø9.560~90°±200 mm
Ø12.730~60°±250 mm
Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce
the ceiling in order to bear the weight of the unit. Adjust
clearance from the ceiling before proceeding further.
Installation example. (See figure 4)
■For other installation than standard installation,
contact your Daikin dealer for details.
INDOORUNITINSTALLATION
When installing optional accessories (except for the decoration
panel), read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed. However, for existing
ceilings, install fresh air inlet component kit and branch duct before
installing the unit.
1Install the indoor unit temporarily.
- Attach the hanger bracket to the suspension bolt. Be sure to
fix it securely by using a nut and washer from the upper and
lower sides of the hanger bracket.
- Securing the hanger bracket (See figure 5)
1Nut (field supply)
2Hanger bracket
3Washer (supplied with the unit)
4Tighten (double nut)
2Fix the paper pattern for installation. (For new ceilings only.)
- The paper pattern for installation corresponds with the
measurements of the ceiling opening. Consult the builder for
details.
- The centre of the ceiling opening is indicated on the paper
pattern for installation. The centre of the unit is indicated on
the paper pattern for installation.
- After removing the packaging material from the paper pattern
for installation, attach the paper pattern for installation to the
unit with the attached screws as shown in figure 8.
1Paper pattern for installation (supplied with the unit)
2Screws (supplied with the unit)
3Adjust the unit to the right position for installation.
(See "Preparations before installation" on page 2.)
4Check if the unit is horizontally levelled.
- Do not install the unit tilted. The indoor unit is equipped with a
built-in drain pump and float switch. (If the unit is tilted
against condensate flow, the float switch may malfunction
and cause water to drip.)
- Check if the unit is levelled at all four corners with a water
level or a water-filled vinyl tube as shown in figure 9.
1Water level
2Vinyl tube
REFRIGERANTPIPINGWORK
All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.
■For refrigerant piping of outdoor unit, refer to the installation
manual supplied with the outdoor unit.
■Execute heat insulation work completely on both sides of the
gas piping and the liquid piping. Otherwise, this can sometimes
result in water leakage.
(When using a heat pump, the temperature of the gas piping can
reach up to approximately 120°C
sufficiently resistant.)
■Also, in cases where the temperature and humidity of the
refrigerant piping sections might exceed 30°C or RH 80%,
reinforce the refrigerant insulation (20 mm or thicker).
Condensation may form on the surface of the insulating
material.
■Before rigging tubes, check which type of refrigerant is used.
■Use a pipe cutter and flare suitable for the used refrigerant.
■Apply ether oil or ester oil around the flare portions before
connecting.
■To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.
■Use copper alloy seamless pipes (ISO 1337).
■The outdoor unit is charged with refrigerant.
■Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.
1Torque wrench
2Flare nut
3Piping union
4Spanner
■Do not mix anything other than the specified refrigerant, such as
air, etc.., inside the refrigerant circuit.
■Refer to the table below for the dimensions of flare nuts and the
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)
Pipe gaugeTightening torque
Ø6.4
Ø9.5
Ø12.7
NOTE
14.2~17.2 N•m
(144~176 kgf•cm)
32.7~39.9 N•m
(333~407 kgf•cm)
49.5~60.3 N•m
(504~616 kgf•cm)
Not recommended but in case of emergency.
You must use a torque wrench but if you are obliged to
install the unit without a torque wrench, you may follow
the installation method mentioned below.
After the work is finished, make sure to check that
there is no gas leak.
When you keep on tightening the flare nut with a
spanner, there is a point where the tightening torque
suddenly increases. From that position, further tighten
the flare nut within the angle shown below.
. Useinsulation which is
2314
Flare dimension A
(mm)
8.7~9.1
12.8~13.2
16.2~16.6
Flare shape
±2
90°
45°
±2
A
R0.4~0.8
5Remove the paper pattern for installation. (For new ceilings
only.)
Installation manual
3
FFQ25~60B8V1B
Split System air conditioners
4PW23700-1B
Page 7
■When connecting the flare nut, coat the flare both inside and
m
1T-joint converging drain pipes
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly.
■Check the pipe connector for gas leaks, then insulate it as
shown in figure 10.
1Liquid pipe
2Gas pipe
3Insulation for fitting of liquid line (supplied with the unit)
4Insulation for fitting of gas line (supplied with the unit)
5Clamps (use 2 clamps per insulation)
6Small sealing pad (supplied with the unit)
■Wrap the sealing pad only around the insulation for the joints on
the gas piping side.
Be sure to insulate any field piping all the way to the
piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.
■If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a
fire.
■Finally make sure there is no refrigerant gas leak. A toxic gas
may be released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.
DRAINPIPINGWORK
Rig the drain piping as shown in figure and take measures against
condensation. Improperly rigged piping could lead to leaks and
eventually wet furniture and belongings.
1-1.5
1Hanging bar
2≥1/100 gradient
1Install the drain pipes.
•Keep piping as short as possible and slope it downwards so that
air may not remain trapped inside the pipe.
•Keep pipe size equal to or greater than that of the connecting
(PVC pipe, nominal diameter 20 mm, outside diameter
pipe
26 mm).
• Insert the drain hose into the drain socket up to the base, and
tighten the clamp securely within the portion of a grey tape.
• Tighten the clamp until the screw head is less then 4 mm from the
hose.
1Metal clamp
(supplied with the unit)
2Grey tape
(field supply)
3Drain hose
(supplied with the unit)
1
2
3
• Make sure that heat insulation work is executed on the following 2
spots to prevent any possible water leakage due to dew
condensation.
• Indoor drain pipe
•Drain socket
•Wrap the supplied sealing pad over the clamp and
drain hose to insulate.
1Metal clamp (supplied with the unit)
2Large sealing pad (supplied with the unit)
≤4 mm
How to perform piping (See figure 14)
1Ceiling slab
2Hanger bracket
3Drain raising pipe
4Raising section
5Drain hose (supplied with the unit)
6Metal clamp (supplied with the unit)
Precautions
■Install the drain raising pipes at a height of less than 545 mm.
■Install the drain raising pipes at a right angle to the indoor unit
and no more than 300 mm from the unit.
NOTE
■The incline of attached drain hose should be
75 mm or less so that the drain socket does not
have to stand additional force.
■To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.
■If unifying multiple drain pipes, install the pipes as
shown in figure 11. Select converging drain pipes
whose gauge is suitable for the operating capacity
of the unit.
1After piping work is finished, check if drainage flows
smoothly.
■ Open the water inlet lid, add approximately 2 l of water
gradually and check the drainage flow.
Method of adding water. See figure 12.
1Drain pipe
2Service drain outlet with rubber plug. Use this outlet to drain
water from the drain pan.
3Plastic container for pouring
■Drain piping connections
Do not connect the drain piping directly to sewage pipes
that smell of ammonia. The ammonia in the sewage might
enter the indoor unit through the drain pipes and corrode
the heat exchanger.
■Keep in mind that it will become the cause of getting
drain pipe blocked if water collects on drain pipe.
When electric wiring work is finished
Check drainage flow during COOL running, explained in "Test
operation" on page 7.
1
2
• Insulate the drain hose inside the building.
• If the drain hose cannot be sufficiently set on a slope, fit the hose
with drain raising piping (field supply).
FFQ25~60B8V1B
Split System air conditioners
4PW23700-1B
Installation manual
4
Page 8
When electric wiring work is not finished
Specifications for field wire
■ Remove the switch box lid and connect the power supply to
the terminals.
See figure 17.
1Switch box lid
2Remove the switch box lid (take off 2 screws)
3Power supply terminal block
4DO NOT CONNECT
The drain pump will not work in this case.
■ After confirming drainage, turn off the power and disconnect
the single phase power supply.
■ Note that the fan also starts rotating.
■ Attach the switch box lid as before.
ELECTRICWIRINGWORK
General instructions
■All field supplied parts and materials and electric works must
conform to local codes.
■Use copper wire only.
■Follow the 'Wiring diagram' attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".
■All wiring must be performed by an authorized electrician.
■A circuit breaker capable of shutting down power supply to the
entire system must be installed.
■Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
■Refer to the installation manual attached to the outdoor unit for
the size of power supply electric wire connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wiring
instructions.
■Be sure to ground the air conditioner.
■Do not connect the ground wire to gas pipes, water pipes,
lightning rods, or telephone ground wires.
• Gas pipes: might cause explosions or fire if gas leaks.
•Water pipes: no grounding effect if hard vinyl piping is used.
•Telephone ground wires or lightning rods: might cause
abnormally high electric potential in the ground during lightning
storms.
Electrical characteristics
NOTE
For details, refer to "Electrical data".
Wire
Between
indoor units
Unit-Remote
controller
Wiring to ground
terminal
(1) Shows only in case of protected pipes. Use H07RN-F in case of no protection.
(2) Run transmission wiring between the indoor and outdoor units through a conduit
to protect against external forces, and feed the conduit through the wall together
with refrigerant piping.
(3) For European and Asian market: Vinyl cord with sheath or cable (insulated
thickness: 1 mm or more)
For Australian regular: Shield wire (insulated thickness: 1 mm or more)
(4) This length shall be the total extended length in the system of the group control.
H05VV-U4G
Vinyl cord with sheath
or cable (2 wires)
Ground wire conform
with local regulations
(1) (2)
Size (mm2)
2,5—
0.75~1.25Max. 500 m
(3)
2.0—
Length
(4)
WIRINGEXAMPLEANDHOWTOSETTHE
REMOTECONTROLLER
How to connect wiring (See figure 22)
AWiring remote controller cord
BWiring between units
CHow to connect power supply terminal block (4P) with ground wire
DHow to attach sealing material
1Control box lid
2Wiring diagram label (on the backside of the control box lid)
3Remote controller cord (Ground the shield part of the shielded
wire.)
4Te r minal block for remote controller (6P)
5Wiring between units
6Power supply terminal block
7Big clamp (field supply)
8Small clamp (field supply)
9Clamp material
10Outdoor unit
11Indoor unit
12Sealing material (supplied with the unit)
13Wiring to outside
14Outside
15Inside
■Wiring between units and ground wire
Remove the control box lid and connect wires of matching
number to the power supply terminal block (4P) inside. (See C).
And connect the ground wire to the terminal block. In doing this,
pull the wires inside through the hole and fix the wires securely
with a field supplied clamp. (See B).
■Give enough slack to the wires between the clamp and power
supply terminal block. (Use the figure as a guide and allow at
least 80 mm for removing the sheath.)
■Pull the wires inside through the hole and connect to the
terminal block for remote controller (6P). (See A). (no polarity)
Securely fix the remote controller cord with a field supplied
clamp.
■Give enough slack to the wires between the clamp and the
terminal block for the remote controller.
■After connection, attach sealing material. (See D).
■Be sure to attach the sealing material to prevent the infiltration of
water, as well as of any insects or other small creatures. Otherwise a short circuit may occur inside the control box. (See D).
Installation manual
5
FFQ25~60B8V1B
Split System air conditioners
4PW23700-1B
Page 9
PRECAUTIONS
1Observe the notes mentioned below when wiring to the power
supply terminal board.
■ Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
■ When connecting wires of the same gauge, connect them
according to the figure.
Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. (Tightening torque: 1.31 N•m±10%).
2Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm
2
(Ø1.6).
The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.
3Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.
4Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.
5For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.
6Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire system.
WIRINGEXAMPLE
For the wiring of outdoor units, refer to the installation manual
attached to the outdoor units.
Confirm the system type:
■Pair type or multi system: 1 remote controller controls 1 indoor
unit (standard system). (See figure 18)
■Multi system: 1 to 4 indoor units connected to 1 outdoor unit.
The indoor unit is controlled by a remote controller connected to
each indoor unit. However, the group control is not expected.
(See figure 19)
■Group control: 1 remote controller controls up to 16 indoor
units (All indoor units operate according to the remote
controller). (See figure 20)
■2 remote controller control: 2 remote controllers control 1
indoor unit. (See figure 21)
Figures 18, 19, 20 and 21
1Main power supply
2Main switch
3Fuse
4Outdoor unit
5Indoor unit
6Remote controller (optional accessories)
7Master indoor unit
8Slave indoor unit
NOTE
PRECAUTIONS
1All transmission wiring except for the remote controller wiring is
It is not necessary to designate indoor unit address
when using group control. The address is automatically set when the power is activated.
polarized and must match the terminal symbol.
7Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worst case, electric shock
or fire.
2In case of group control, perform the remote controller wiring to
the master unit when connecting to the simultaneous operation
system (wiring to the slave unit is unnecessary).
3For group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions
(as attached swing flap).
4Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper grounding could result in electric shock.
5In case a shielding wire is to be used, connect a shielded portion
with the of a remote controller terminal board. (Also, connect the
ground for the remote control to a grounded metal part.)
FFQ25~60B8V1B
Split System air conditioners
4PW23700-1B
Installation manual
6
Page 10
FIELDSETTING
INSTALLATIONOFTHEDECORATIONPANEL
Field setting must be made from the remote controller in accordance
with the installation condition.
■Setting can be made by changing the "Mode number", "FIRST
CODE No." and "SECOND CODE No.".
■For setting and operation, refer to "Field setting" in the
installation manual of the remote controller.
Setting air discharge direction
For changing air discharge direction (2 or 3 directions), refer to the
option handbook of the optional blocking pad kit. (SECOND CODE
No. is factory set to "01" for air discharge in 4 directions.)
Settings for options
For settings of options, see the installation instructions provided with
the option.
Setting air filter sign
Remote controllers are equipped with liquid crystal air filter signs to
display the time to clean the air filter.
Change the SECOND CODE No. Depending on the amount of dirt or
dust in the room. (SECOND CODE No. is factory set to "01" for air
filter contamination-light)
Air Filter contamination
Display
Setting
Light±2500 hrs10 (20)001
Heavy±1250 hrs10 (20)002
interval
Mode n°1st code n°2nd code n°
Read the chapter "Test operation" on page 7 before making a test run
without attaching the decoration panel.
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop. (See figure 15)
TESTOPERATION
Make sure the control box lids are closed on the indoor and outdoor units.
Refer to "For the following items, take special care during
construction and check after installation is finished" on page 2.
After finishing the construction of refrigerant piping, drain piping, and
electric wiring, conduct test operation accordingly to protect the unit.
TEST OPERATION AFTER INSTALLING DECORATION PANEL
1Open the gas side stop valve.
2Open the liquid side stop valve.
3Electrify crank case heater for 6 hours.
4Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.
5Press Inspection/Test Operation button 4 times (2 times for
wireless remote controller) and operate at Test Operation mode
for 3 minutes.
6Push air flow direction adjust button to make sure the unit is in
operation.
When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.
Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".
Main/sub changeover
1Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. (See figure 13)
(The remote controller PC board is attached to the upper part of
the remote controller.)
2Tu rn the main/sub changeover switch on one of the two remote
controller PC boards to "S". (See figure 16)
(Leave the switch of the other remote controller set to "M".)
1Remote controller PC board
2Factory setting
3Only one remote controller needs to be changed
7Press Inspection/Test Operation button and operate normally.
8Confirm function of unit according to the operation manual.
TEST OPERATION BEFORE INSTALLING DECORATION PANEL
(See NOTE 3. on page 8)
1Open the gas side stop valve.
2Open the liquid side stop valve.
3Electrify crank case heater for 6 hours.
4Set to cooling operation with the wired remote controller and
start operation by pushing ON/OFF button. "A7" appears on the
display.
5Press Inspection/Test Operation button on the remote controller
and operate at Test Operation mode for 3 minutes.
6Press Inspection/Test Operation button and operate normally.
7Confirm function of unit according to the operation manual.
8Tu rn off the main power supply after operation.
PRECAUTIONS
1Refer to the installation manual attached to the outdoor unit in
case of Individual Operation System type.
2Conduct test operation after installing decoration panel if the
TO OUTDOOR UNIT:
IN CASE OF SIMULTANEOUS OPERATION SYSTEM:
INDOOR UNIT (MASTER):
INDOOR UNIT (SLAVE):
REMOTE CONTROLLER:
WIRED REMOTE CONTROLLER:
SWITCH BOX:
COLOR OF PCB CONNECTOR:
COLOR OF WIRE:
(MARKED) COLOR OF WIRE CONNECTOR:
COLOUR:
NOTE
FFQ25~60B8V1B
Split System air conditioners
4PW23700-1B
1.WHEN USING THE CENTRAL REMOTE CONTROLLER, SEE MANUAL FOR CONNECTION TO UNIT.
2.X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS USED.
3.THE REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM. SEE TECHNICAL DATA AND
CATALOGS, ETC. BEFORE CONNECTING.
4.IN CASE OF USING SHIELDED WIRE, GROUND THE SHIELD OF THE REMOTE CONTROLLER CORD TO THE INDOOR UNIT.