Daikin FCQ18PVJU, FCQ24PVJU, FCQ30PVJU Installation Manual

INSTALLATION MANUAL
SPLIT SYSTEM Air Conditioners
MODELS
Ceiling-mounted Cassette type (Multi fl ow model)
FCQ18PVJU FCQ24PVJU FCQ30PVJU
English
Français
Lire soigneusement ces instructions avant l’installation. Conserver ce manuel à portée de main pour référence ultérieure. Ce manuel doit être donné au propriétaire de l’équipement.
Lea cuidadosamente estas instrucciones antes de instalar. Guarde este manual en un lugar a mano para leer en caso de tener alguna duda. Este manual debe permanecer con el propietario del equipo.
Español
SPLIT SYSTEM Air Conditioners Installation manual
CONTENTS
1. SAFETY CONSIDERATIONS ........................................... 1
2. BEFORE INSTALLATION .................................................. 2
3. SELECTING INSTALLATION SITE ................................... 3
4. PREPARATIONS BEFORE INSTALLATION ..................... 4
5. INSTALLATION PROCEDURES FOR FRESH AIR
INTAKE DUCT CONNECTION .......................................... 5
6. INDOOR UNIT INSTALLATION ......................................... 6
7. REFRIGERANT PIPING WORK ....................................... 7
8. DRAIN PIPING WORK ...................................................... 8
9. ELECTRIC WIRING WORK .............................................. 9
10. WIRING EXAMPLE AND HOW TO SET THE REMOTE
CONTROLLER ................................................................ 10
11. FIELD SETTING.............................................................. 12
12. INSTALLATION OF THE DECORATION PANEL ............. 12
13. TEST OPERATION ......................................................... 13
SAFETY CONSIDERATIONS1.
Please read these “SAFETY CONSIDERATIONS” carefully before installing air conditioning equipment and be sure to install it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Also, inform customers that they should store this installation manual along with the operation manual for future reference. This air conditioner comes under the term “appliances not accessible to the general public”. Meaning of danger, warning, caution and note symbols.
DANGER ................ Indicates an imminently hazardous
situation which,if not avoided, will result in death or serious injury.
WARNING .............. Indicates a potentially hazardous
situation which, if not avoided, could result in death or serious injury.
CAUTION ............... Indicates a potentially hazardous
situation which, if not avoided, may result in minor or moderate injury. It may also be sued to alert against unsafe practices.
NOTE ..................... Indicates situation that may result in
equipment or property-damage-only accidents.
DANGER
Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
Do not install unit in an area where fl ammable materials are present due to risk of explosion resulting in serious injury or death. Refrigerant gas in heavier than air and displaces oxy- gen. A massive leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death. If the refrigerant gas leaks during installation, ventilate the area immediately.
Refrigerant gas may produce toxic gas if it comes in contact with fi re such as from a fan, heater, stove or cooking device. Exposure to this gas could result in severe injury or death.
After completing the installation work, check that the refrigerant gas does not leak.
Refrigerant gas may produce toxic gas if it comes in contact with fi re such as from a fan, heater, stove or cooking device. Exposure to this gas could result in severe injury or death. Safely dispose of the packing materials. • Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face the danger of death by suffocation.
WARNING
Ask your dealer or qualifi ed personnel to carry out installation work. Do not try to install the unit by your­self.
Improper installation may result in water leakage, electric shocks or fi re.
Perform installation work in accordance with this instal- lation manual.
Improper installation may result in water leakage, electric shocks or fi re.
Be sure to use only the specifi ed accessories and parts for installation work.
Failure to use the specifi ed parts may result in water leak­age, electric shocks, fi re or the unit falling.
Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insuffi cient strength may result in the equip­ment falling and causing injuries.
Carry out the specifi ed installation work after consider- ing strong considering winds, typhoons or earth­quakes.
Improper installation work may result in the equipment falling and causing accidents.
Make sure that a separate power supply circuit is pro- vided for this unit and that all electrical work is carried out by qualifi ed personnel according to local laws and regulations and this installation manual.
An insuffi cient power supply capacity or improper electrical construction may lead to electric shocks or fi re.
Make sure that all wiring is secured, the specifi ed wires are used, and no external forces act on the terminal connections or wires.
Improper connections or installation may result in fi re.
1 English
When wiring the power supply and connecting the remote controller wire and transmission wire, position the wires so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fi re or the terminals overheating.
Before touching electrical parts, turn off the unit. Do not touch the switch with wet fi ngers.
Touching a switch with wet fi ngers can cause electric shock. Be sure to install an earth leakage breaker. • Failure to install an earth leakage breaker may result in electric shocks, or fi re.
Do not install the air conditioner in the following loca- tions:
(a) where a mineral oil mist or an oil spray or vapor is
produced, for example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage.
(b) where corrosive gas, such as sulfurous acid gas, is
produced Corroding copper pipes or soldered parts may result in refrigerant leakage.
(c) near machinery emitting electromagnetic waves
Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the equip­ment.
(d) where fl ammable gases may leak, where there are
carbon fi ber or ignitable dust suspensions in the air, or where volatile fl ammables such as thinner or gasoline are handled.
Operating the unit in such conditions may result in fi re. Heat exchanger fi ns are sharp to cut. • To avoid injury wear gloves to cover the fi ns when working around them.
Refrigerant pipes may be very hot or very cold during or immediately after operation.
Touching them could result in burns or frostbite. To avoid injury give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
CAUTION
While following the instructions in this installation manual, install drain pipe in order to ensure proper drainage and insulate pipe in order to prevent conden­sate.
Improper drain pipe may result in water leakage and prop­erty damage. Be very careful about product transportation. • Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is danger­ous. Safely dispose of the packing materials. • Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffoca­tion.
Do not turn off the power immediately after stopping operation.
Always wait at least 5 minutes before turning off the power. Otherwise, water leakage and trouble may occur.
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fi re. Please instruct the customer to keep the area around the unit clean.
NOTE
Install the indoor and outdoor units, power supply wire and transmission wire at least 3.5ft. away from televi­sions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.5ft. may not be suffi cient enough to eliminate the noise.)
Remote controller (wireless kit) transmitting distance can result shorter than expected in rooms with elec­tronic fl uorescent lamps. (inverter or rapid start types)
Install the indoor unit as far away from fl uorescent lamps as possible.
In a domestic environment this product may cause radio interference in which case the user may be re­quired to take adequate measures. Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accor­dance with the relevant local and national regulations.
BEFORE INSTALLATION2.
When moving the unit while removing it from the pack- ing case, be sure to lift it by the four hanger brackets. Avoid putting any pressure on other parts especially the refrigerant piping.
Be sure to check the type of R410A refrigerant to be used • before installing the unit. (Using an incorrect refrigerant will prevent normal operation of the unit.) The accessories needed for installation must be retained in • your custody until the installation work is completed. Do not discard them! Decide upon a line of transport.• Leave the unit inside its packaging while moving, until • reaching the installation site. Where unpacking is unavoid­able, use a sling of soft material or protective plates togeth­er with a rope when lifting, to avoid damage or scratches to the unit. When moving the unit at or after opening, hold the unit by • the hanger brackets (× 4). Do not apply force to the refriger­ant pipe, drain pipe or plastic parts. For the installation of an outdoor unit, refer to the installa-• tion manual attached to the outdoor unit. Do not install or operate the unit in rooms mentioned below.
Laden with mineral oil, or fi lled with oil vapor or spray like in kitchens. (Plastic parts may deteriorate which could eventually cause the unit to fall out of place, or could lead to leaks.) Where corrosive gas like sulfurous gas exists. (Copper tubing and brazed spots may corrode which could eventually lead to refrigerant leaks.) Where machines can generate electromagnetic waves. (Control system may malfunction.) Where the air contains high levels of salt such as that near the ocean and where voltage fl uctuates greatly such as that in factories. Also in vehicles or vessels.
English 2
3 English
This unit, both indoor and outdoor, is suitable for installation • in a commercial and light industrial environment. If installed as a household appliance it could cause electro­magnetic interference.
WARNING
Entrust installation to the place of purchase or a qualifi ed • person. Improper installation could lead to leak and, in worse cases, electric shock of fi re. Use of unspecifi ed parts could lead to the unit falling, leaks • and, in worse cases, electric shock or fi re.
NOTE
Be sure to read this manual before installing the indoor unit.• Be sure to mount an air fi lter (part to be procured in the fi eld) in
• the suction air passage in order to prevent water leaking, etc.
ACCESSORIES2-1
Check the following accessories are included with your unit.
Name
Quantity 1 pc. 1 pc. 8 pcs. 4 pcs.
Shape
Name
Quantity 1 pc. 4 pcs. 4 pcs. 1 each
Shape
Name Sealing pad
Quantity 1 each 2 pcs.
Shape
(1) Drain
hose
(5) Paper
pattern for
installation
Also used
as packing
material
(10) Large
(11) Medium
(2) Metal
clamp
(6) Screws
(M5)
For paper
pattern for
installation
(12) Small
(3) Washer for
hanger bracket
(7) Washer fi xing plate
Installation manual
Operation manual
(4) Clamp
Insulation
for fi tting
(8) for gas
pipe
(9) for liquid
pipe
(Other)
OPTIONAL ACCESSORIES2-2
The optional decoration panel and remote controller are • required for this indoor unit.
Table 1
Model
FCQ18 · 24 · 30PVJU BYC125K-W1
Optional decoration panel
Color White
Table 2
Remote controller
Wired type BRC1C71
Wireless type BRC7C812
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
Items to be checked
Are the indoor and outdoor unit fi xed fi rmly?
Is the gas leak test fi nished?
Is the unit fully insulated? Condensate water may drip.
Does drainage fl ow smoothly? Condensate water may drip.
Does the power supply voltage correspond to that shown on the name plate?
Are wiring and piping correct?
Is the unit safely grounded? It may result in electric shock.
Is wiring size according to specifi cations?
Is something blocking the air outlet or inlet of either the indoor or outdoor units?
Are refrigerant piping length and additional refrigerant charge noted down?
If not properly done, what is likely to occur.
The units may drop, vibrate or make noise.
It may result in insuffi cient cooling.
The unit may malfunction or the components burn out.
The unit may malfunction or the components burn out.
The unit may malfunction or the components burn out.
It may result in insuffi cient cooling.
The refrigerant charge in the system is not clear.
Check
b. Items to be checked at time of delivery
Also review the “1. SAFETY CONSIDERATIONS”
Items to be checked Check
Did you explain about operations while showing the operation manual to your customer?
Did you hand the operation manual over to your customer?
NOTE TO INSTALLER2-3
Be sure to instruct customers how to properly operate the • unit (especially cleaning fi lters, operating different functions, and adjusting the temperature) by having them carry out operations themselves while looking at the manual.
SELECTING INSTALLATION SITE3.
Please attach additional thermal insulation material to the unit body when it is believed that the relative humidity in the ceiling exceeds 80%. Use glass wool, polyethylene foam, or similar with a thickness of 3/8 in.. or more as thermal insulation mate­rial.
Select an installation site where the following conditions (1) are fulfi lled and that meets with your customer’s approval.
In the upper space (including the back of the ceiling) of the
• indoor unit where there is no possible dripping of water from the refrigerant pipe, drain pipe, water pipe, etc. Where optimum air distribution can be ensured.• Where nothing blocks the air passage.
English 4
Where condensate can be properly drained.
False ceiling
Hanger
bracket
[View as seen from A]
(5 15/16)
(length: in.)
Where the false ceiling is not noticeably on an incline.• Where suffi cient clearance for maintenance and service • can be ensured. Where piping between indoor and outdoor units is • possible within the allowable limit. (Refer to the installa­tion manual of the outdoor unit.)
DANGER
Do not install unit in an area where fl ammable materials are • present due to the risk explosion resulting in serious injury or death.
WARNING
If the supporting structural members are not strong enough • to take the unit’s weight, the unit could fall out of place and cause serious injury.
NOTE
Install the indoor and outdoor units, power supply wire and • connecting wires at least 3.5ft. away from televisions or radios in order to prevent image interference or noise. (Depending on the radio waves, a distance of 3.5ft. may not be suffi cient enough to eliminate the noise.)
Model H
FCQ18 · 24 · 30PVJU 11 3/4 or more
PREPARATIONS BEFORE INSTALLATION
4.
Relation of ceiling opening to unit and suspension (1) bolt position
33 1/16 (Indoor unit)
34 5/8 (Ceiling opening)
37 3/8 (Decoration panel)
30 11/16 (Suspension bolt pitch)
26 3/4 (Suspension bolt pitch)
33 1/16 (Indoor unit)
34 5/8 (Ceiling opening)
37 3/8 (Decoration panel)
A
(length: in.)
Refrigerant pipe
Suspension bolt (×4)
Ceiling height(2)
This indoor unit may be installed on ceilings up to 10.5 ft. in height.
Use suspension bolts for installation. Check whether (3) the ceiling is strong enough to support the weight of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is marked on the paper pattern for installation. Refer to it to check for points requiring rein­forcing.)
[Space required for installation]
H
59
or more
Air discharge
Air discharge
Air
39 3/8 or more
inlet
59
or more
Installation is possible when ceiling opening dimensions is as follows.
When installing the unit within the frame for fi xing false • ceiling.
35 13/16
33 1/16 (Indoor unit)
(Dimension inside frame)
Air
59
or more
discharge
Air inlet
discharge
Air
H
59
or more
33 1/16 (Indoor unit)
35 13/16
(Dimension inside frame)
(length: in.)
Loading...
+ 11 hidden pages