Daikin EPRA14DAV3, EPRA16DAV3, EPRA18DAV3, EPRA14DAW1, EPRA16DAW1 Installer reference guide

...
Installer reference guide
https://daikintechnicaldatahub.eu
Daikin Altherma 3 H HT F
EPRA14DAV3 EPRA16DAV3 EPRA18DAV3
EPRA14DAW1 EPRA16DAW1 EPRA18DAW1
ETVZ16S18DA6V ETVZ16S23DA6V ETVZ16S18DA9W ETVZ16S23DA9W
Table of contents
1 General safety precautions 6
1.1 About the documentation .............................................................................................................................................. 6
1.1.1 Meaning of warnings and symbols ................................................................................................................ 6
1.2 For the installer............................................................................................................................................................... 7
1.2.1 General ........................................................................................................................................................... 7
1.2.2 Installation site ............................................................................................................................................... 8
1.2.3 Refrigerant — in case of R410A or R32.......................................................................................................... 9
1.2.4 Water .............................................................................................................................................................. 10
1.2.5 Electrical ......................................................................................................................................................... 11
2 About the documentation 13
2.1 About this document ...................................................................................................................................................... 13
2.2 Installer reference guide at a glance .............................................................................................................................. 14
3 About the box 16
3.1 Overview: About the box ................................................................................................................................................ 16
3.2 Outdoor unit ................................................................................................................................................................... 16
3.2.1 To handle the outdoor unit ............................................................................................................................ 16
3.2.2 To unpack the outdoor unit ........................................................................................................................... 18
3.2.3 To remove the accessories from the outdoor unit........................................................................................ 19
3.3 Indoor unit ...................................................................................................................................................................... 20
3.3.1 To unpack the indoor unit .............................................................................................................................. 20
3.3.2 To remove the accessories from the indoor unit .......................................................................................... 20
3.3.3 To handle the indoor unit............................................................................................................................... 20
4 About the units and options 21
4.1 Overview: About the units and options.......................................................................................................................... 21
4.2 Identification ................................................................................................................................................................... 21
4.2.1 Identification label: Outdoor unit .................................................................................................................. 21
4.2.2 Identification label: Indoor unit ..................................................................................................................... 22
4.3 Combining units and options.......................................................................................................................................... 22
4.3.1 Possible combinations of indoor unit and outdoor unit................................................................................ 22
4.3.2 Possible options for the outdoor unit ............................................................................................................ 22
4.3.3 Possible options for the indoor unit............................................................................................................... 23
5 Application guidelines 26
5.1 Overview: Application guidelines ................................................................................................................................... 26
5.2 Setting up the space heating/cooling system ................................................................................................................ 27
5.2.1 Multiple rooms – TwoLWT zones.................................................................................................................. 28
5.3 Setting up the domestic hot water tank......................................................................................................................... 30
5.3.1 System layout – Integrated DHW tank........................................................................................................... 30
5.3.2 Selecting the volume and desired temperature for the DHW tank .............................................................. 30
5.3.3 Setup and configuration – DHW tank ............................................................................................................ 32
5.3.4 DHW pump for instant hot water .................................................................................................................. 32
5.3.5 DHW pump for disinfection ........................................................................................................................... 33
5.4 Setting up the energy metering...................................................................................................................................... 34
5.4.1 Produced heat ................................................................................................................................................ 34
5.4.2 Consumed energy........................................................................................................................................... 34
5.4.3 Normal kWh rate power supply ..................................................................................................................... 35
5.4.4 Preferential kWh rate power supply .............................................................................................................. 36
5.5 Setting up the power consumption control ................................................................................................................... 37
5.5.1 Permanent power limitation .......................................................................................................................... 38
5.5.2 Power limitation activated by digital inputs .................................................................................................. 38
5.5.3 Power limitation process................................................................................................................................ 40
5.5.4 BBR16 power limitation.................................................................................................................................. 40
5.6 Setting up an external temperature sensor ................................................................................................................... 41
Installer reference guide
2
6 Unit installation 43
6.1 Preparing the installation site......................................................................................................................................... 43
6.1.1 Installation site requirements of the outdoor unit........................................................................................ 43
6.1.2 Additional installation site requirements of the outdoor unit in cold climates............................................ 46
6.1.3 Installation site requirements of the indoor unit .......................................................................................... 46
6.2 Opening and closing the units ........................................................................................................................................ 47
6.2.1 About opening the units................................................................................................................................. 47
6.2.2 To open the outdoor unit ............................................................................................................................... 48
6.2.3 To remove the transportation stay ................................................................................................................ 48
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
6.2.4 To close the outdoor unit ............................................................................................................................... 48
6.2.5 To open the indoor unit ................................................................................................................................. 49
6.2.6 To lower the switch box on the indoor unit .................................................................................................. 51
6.2.7 To close the indoor unit ................................................................................................................................. 52
6.3 Mounting the outdoor unit............................................................................................................................................. 52
6.3.1 About mounting the outdoor unit ................................................................................................................. 52
6.3.2 Precautions when mounting the outdoor unit .............................................................................................. 52
6.3.3 To provide the installation structure ............................................................................................................. 52
6.3.4 To install the outdoor unit ............................................................................................................................. 53
6.3.5 To provide drainage........................................................................................................................................ 54
6.3.6 To install the discharge grille.......................................................................................................................... 56
6.3.7 To remove the discharge grille, and put the grille in safety position............................................................ 57
6.4 Mounting the indoor unit ............................................................................................................................................... 59
6.4.1 About mounting the indoor unit .................................................................................................................... 59
6.4.2 Precautions when mounting the indoor unit................................................................................................. 59
6.4.3 To install the indoor unit ................................................................................................................................ 59
6.4.4 To connect the drain hose to the drain ......................................................................................................... 60
7 Piping installation 62
7.1 Preparing water piping ................................................................................................................................................... 62
7.1.1 Water circuit requirements............................................................................................................................ 62
7.1.2 Formula to calculate the expansion vessel pre-pressure .............................................................................. 64
7.1.3 To check the water volume and flow rate ..................................................................................................... 64
7.1.4 Changing the pre-pressure of the expansion vessel...................................................................................... 67
7.1.5 To check the water volume: Examples .......................................................................................................... 67
7.2 Connecting water piping................................................................................................................................................. 68
7.2.1 About connecting the water piping ............................................................................................................... 68
7.2.2 Precautions when connecting the water piping ............................................................................................ 68
7.2.3 To connect the water piping .......................................................................................................................... 68
7.2.4 To connect the recirculation piping ............................................................................................................... 71
7.2.5 To fill the water circuit ................................................................................................................................... 72
7.2.6 To protect the water circuit against freezing ................................................................................................ 72
7.2.7 To fill the domestic hot water tank ................................................................................................................ 75
7.2.8 To insulate the water piping .......................................................................................................................... 75
8 Electrical installation 77
8.1 About connecting the electrical wiring .......................................................................................................................... 77
8.1.1 Precautions when connecting the electrical wiring....................................................................................... 77
8.1.2 Guidelines when connecting the electrical wiring......................................................................................... 78
8.1.3 About electrical compliance........................................................................................................................... 79
8.1.4 About preferential kWh rate power supply ................................................................................................... 79
8.1.5 Overview of electrical connections except external actuators ..................................................................... 80
8.2 Connections to the outdoor unit.................................................................................................................................... 81
8.2.1 To connect the electrical wiring to the outdoor unit .................................................................................... 81
8.2.2 To reposition the air thermistor on the outdoor unit ................................................................................... 87
8.3 Connections to the indoor unit ...................................................................................................................................... 88
8.3.1 To connect the main power supply................................................................................................................ 91
8.3.2 To connect the backup heater power supply ................................................................................................ 93
8.3.3 To connect the shut-off valve ........................................................................................................................ 95
8.3.4 To connect the electricity meters .................................................................................................................. 96
8.3.5 To connect the domestic hot water pump .................................................................................................... 97
8.3.6 To connect the alarm output ......................................................................................................................... 98
8.3.7 To connect the space cooling/heating ON/OFF output................................................................................. 99
8.3.8 To connect the changeover to external heat source..................................................................................... 100
8.3.9 To connect the power consumption digital inputs........................................................................................ 101
8.3.10 To connect the safety thermostat (normally closed contact)....................................................................... 102
8.4 After connecting the electrical wiring to the indoor unit .............................................................................................. 104
9 Configuration 106
9.1 Overview: Configuration................................................................................................................................................. 106
9.1.1 To access the most used commands ............................................................................................................. 107
9.2 Configuration wizard....................................................................................................................................................... 109
9.3 Possible screens .............................................................................................................................................................. 110
9.3.1 Possible screens: Overview ............................................................................................................................ 110
9.3.2 Home screen................................................................................................................................................... 111
9.3.3 Main menu screen.......................................................................................................................................... 114
9.3.4 Menu screen ................................................................................................................................................... 115
9.3.5 Setpoint screen............................................................................................................................................... 115
9.3.6 Detailed screen with values ........................................................................................................................... 116
9.3.7 Schedule screen: Example.............................................................................................................................. 116
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Installer reference guide
3
9.4 Weather-dependent curve ............................................................................................................................................. 121
9.4.1 What is a weather-dependent curve? ........................................................................................................... 121
9.4.2 2-points curve ................................................................................................................................................. 121
9.4.3 Slope-offset curve........................................................................................................................................... 122
9.4.4 Using weather-dependent curves.................................................................................................................. 124
9.5 Settings menu ................................................................................................................................................................. 126
9.5.1 Malfunctioning ............................................................................................................................................... 126
9.5.2 Room............................................................................................................................................................... 126
9.5.3 Main zone ....................................................................................................................................................... 130
9.5.4 Additional zone ............................................................................................................................................... 141
9.5.5 Space heating/cooling .................................................................................................................................... 146
9.5.6 Tank................................................................................................................................................................. 154
9.5.7 User settings ................................................................................................................................................... 161
9.5.8 Information ..................................................................................................................................................... 165
9.5.9 Installer settings ............................................................................................................................................. 167
9.5.10 Commissioning ............................................................................................................................................... 185
9.5.11 Operation........................................................................................................................................................ 185
9.5.12 WLAN .............................................................................................................................................................. 186
9.6 Menu structure: Overview user settings........................................................................................................................ 188
9.7 Menu structure: Overview installer settings.................................................................................................................. 189
10 Commissioning 190
10.1 Overview: Commissioning .............................................................................................................................................. 190
10.2 Precautions when commissioning .................................................................................................................................. 191
10.3 Checklist before commissioning ..................................................................................................................................... 191
10.4 Checklist during commissioning ..................................................................................................................................... 192
10.4.1 Minimum flow rate......................................................................................................................................... 192
10.4.2 Air purge function........................................................................................................................................... 193
10.4.3 Operation test run.......................................................................................................................................... 196
10.4.4 Actuator test run ............................................................................................................................................ 197
10.4.5 Underfloor heating screed dryout ................................................................................................................. 197
11 Hand-over to the user 201
12 Maintenance and service 202
12.1 Overview: Maintenance and service .............................................................................................................................. 202
12.2 Maintenance safety precautions .................................................................................................................................... 202
12.3 Yearly maintenance ........................................................................................................................................................ 203
12.3.1 Yearly maintenance outdoor unit: overview ................................................................................................. 203
12.3.2 Yearly maintenance outdoor unit: instructions............................................................................................. 203
12.3.3 Yearly maintenance indoor unit: overview.................................................................................................... 203
12.3.4 Yearly maintenance indoor unit: instructions ............................................................................................... 203
12.4 To drain the domestic hot water tank............................................................................................................................ 206
12.5 About cleaning the water filter in case of trouble ......................................................................................................... 207
12.5.1 To remove the water filter ............................................................................................................................. 207
12.5.2 To clean the water filter in case of trouble.................................................................................................... 207
12.5.3 To install the water filter ................................................................................................................................ 209
13 Troubleshooting 210
13.1 Overview: Troubleshooting ............................................................................................................................................ 210
13.2 Precautions when troubleshooting ................................................................................................................................ 210
13.3 Solving problems based on symptoms ........................................................................................................................... 211
13.3.1 Symptom: The unit is NOT heating or cooling as expected........................................................................... 211
13.3.2 Symptom: Hot water does NOT reach the desired temperature.................................................................. 212
13.3.3 Symptom: The compressor does NOT start (space heating or domestic water heating) ............................ 212
13.3.4 Symptom: The system is making gurgling noises after commissioning ........................................................ 212
13.3.5 Symptom: The pump is blocked..................................................................................................................... 213
13.3.6 Symptom: The pump is making noise (cavitation)......................................................................................... 213
13.3.7 Symptom: The pressure relief valve opens.................................................................................................... 214
13.3.8 Symptom: The water pressure relief valve leaks........................................................................................... 214
13.3.9 Symptom: The space is NOT sufficiently heated at low outdoor temperatures........................................... 215
13.3.10 Symptom: The pressure at the tapping point is temporarily unusually high................................................ 216
13.3.11 Symptom: Tank disinfection function is NOT completed correctly (AH-error)............................................. 216
13.4 Solving problems based on error codes ......................................................................................................................... 216
13.4.1 To display the help text in case of a malfunction .......................................................................................... 217
13.4.2 Error codes: Overview.................................................................................................................................... 217
Installer reference guide
4
14 Disposal 222
14.1 To recover refrigerant..................................................................................................................................................... 222
15 Technical data 224
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
15.1 Service space: Outdoor unit ........................................................................................................................................... 225
15.2 Piping diagram: Outdoor unit ......................................................................................................................................... 226
15.3 Piping diagram: Indoor unit ............................................................................................................................................ 227
15.4 Wiring diagram: Outdoor unit ........................................................................................................................................ 229
15.5 Wiring diagram: Indoor unit ........................................................................................................................................... 234
16 Glossary 240
17 Field settings table 241
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Installer reference guide
5
1 | General safety precautions

1 General safety precautions

In this chapter

1.1 About the documentation...................................................................................................................................................... 6
1.2 For the installer....................................................................................................................................................................... 7

1.1 About the documentation

The original documentation is written in English. All other languages are
translations.
The precautions described in this document cover very important topics, follow
them carefully.
1.1.1 Meaning of warnings and symbols ........................................................................................................................ 6
1.2.1 General ................................................................................................................................................................... 7
1.2.2 Installation site ....................................................................................................................................................... 8
1.2.3 Refrigerant — in case of R410A or R32 ................................................................................................................. 9
1.2.4 Water ...................................................................................................................................................................... 10
1.2.5 Electrical ................................................................................................................................................................. 11
The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised installer.

1.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
Installer reference guide
6
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
1 | General safety precautions
Symbols used in the documentation:

1.2 For the installer

1.2.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
WARNING
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Installer reference guide
7
1 | General safety precautions
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.Do NOT sit, climb or stand on the unit.

1.2.2 Installation site

NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Installer reference guide
8
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.

1.2.3 Refrigerant — in case of R410A or R32

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
1 | General safety precautions
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self­combustion and explosion of the compressor because of air going into the operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
Installer reference guide
9
1 | General safety precautions
In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the system.
Charge the liquid refrigerant as follows:
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of oxygen going into the operating compressor.
If Then
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside down.
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.

1.2.4 Water

Installer reference guide
10
If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12

1.2.5 Electrical

1 | General safety precautions
DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50VDC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage categoryIII condition, MUST be installed in the fixed wiring.
WARNING
ONLY use copper wires.Make sure the field wiring complies with the applicable legislation.All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
Installer reference guide
11
1 | General safety precautions
Install power cables at least 1 m away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 m may not be sufficient.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/ OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
Installer reference guide
12
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12

2 About the documentation

In this chapter

2.1 About this document.............................................................................................................................................................. 13
2.2 Installer reference guide at a glance...................................................................................................................................... 14

2.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the indoor unit)
2 | About the documentation
Operation manual:
- Quick guide for basic usage
- Format: Paper (in the box of the indoor unit)
User reference guide:
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Installation manual – Outdoor unit:
- Installation instructions
- Format: Paper (in the box of the outdoor unit)
Installation manual – Indoor unit:
- Installation instructions
- Format: Paper (in the box of the indoor unit)
Installer reference guide:
- Preparation of the installation, good practices, reference data,…
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Addendum book for optional equipment:
- Additional info about how to install optional equipment
- Format: Paper (in the box of the indoor unit) + Digital files on http://
www.daikineurope.com/support-and-manuals/product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Installer reference guide
13
2 | About the documentation
Technical engineering data
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
Online tools
In addition to the documentation set, some online tools are available for installers:
Daikin Technical Data Hub
- Central hub for technical specifications of the unit, useful tools, digital
- Publicly accessible via https://daikintechnicaldatahub.eu.
Heating Solutions Navigator
- Digital toolbox that offers a variety of tools to facilitate the installation and
- To access Heating Solutions Navigator, registration to the Stand By Me
resources, and more.
configuration of heating systems.
platform is required. For more information, see https://
professional.standbyme.daikin.eu.
Daikin e-Care
- Mobile app for installers and service technicians that allows you to register,
configure and troubleshoot heating systems.
- The mobile app can be downloaded for iOS and Android devices using the QR
codes below. Registration to the Stand By Me platform is required to access the app.
App Store Google Play

2.2 Installer reference guide at a glance

Chapter Description
General safety precautions Safety instructions that you must read before
installing
About the documentation What documentation exists for the installer
About the box How to unpack the units and remove their
accessories
Installer reference guide
14
About the units and options How to identify the units
Possible combinations of units and options
Application guidelines Various installation setups of the system
Unit installation What to do and know to install the system,
including information on how to prepare for an installation
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
2 | About the documentation
Chapter Description
Piping installation What to do and know to install the piping of the
system, including information on how to prepare for an installation
Electrical installation What to do and know to install the electrical
components of the system, including information on how to prepare for an installation
Configuration What to do and know to configure the system
after it is installed
Commissioning What to do and know to commission the system
after it is configured
Hand‑over to the user What to give and explain to the user
Maintenance and service How to maintain and service the units
Troubleshooting What to do in case of problems
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
Field settings table Table to be filled in by the installer, and kept for
future reference
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Installer reference guide
15
3 | About the box

3 About the box

In this chapter

3.1 Overview: About the box

3.1 Overview: About the box........................................................................................................................................................ 16
3.2 Outdoor unit ........................................................................................................................................................................... 16
3.2.1 To handle the outdoor unit.................................................................................................................................... 16
3.2.2 To unpack the outdoor unit ................................................................................................................................... 18
3.2.3 To remove the accessories from the outdoor unit ............................................................................................... 19
3.3 Indoor unit .............................................................................................................................................................................. 20
3.3.1 To unpack the indoor unit...................................................................................................................................... 20
3.3.2 To remove the accessories from the indoor unit .................................................................................................. 20
3.3.3 To handle the indoor unit ...................................................................................................................................... 20
This chapter describes what you have to do after the boxes with the outdoor and indoor unit are delivered on-site.
Keep the following in mind:
At delivery, the unit MUST be checked for damage. Any damage MUST be
reported immediately to the claims agent of the carrier.
Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
Prepare the path along which you want to bring the unit inside in advance.

3.2 Outdoor unit

3.2.1 To handle the outdoor unit

CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.
Crane
Keep the slings within the marked area to not damage the unit.
Installer reference guide
16
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
3 | About the box
±150
kg
Forklift or pallet truck
Enter the pallet from the heavy side.
Manually
After unpacking, carry the unit using the slings attached to the unit.
See also:
"To unpack the outdoor unit"[418]
"To install the outdoor unit"[453]
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Installer reference guide
17
3 | About the box
1 2
3
4

3.2.2 To unpack the outdoor unit

Installer reference guide
18
a, b Accessories
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12

3.2.3 To remove the accessories from the outdoor unit

b
c
d
e
f
a
g
ENERG
IJAY
IAIE
ENERG
IJAY
IAIE
h
i
3 | About the box
a Shut-off valve (with integrated filter) b O-ring for drain socket
c Drain socket d Thermistor fixture (for installations in areas with low ambient temperatures) e Installation manual – Outdoor unit
f Disposal manual – Recovering refrigerant g Energy label h Discharge grille (upper + lower part)
i Installation manual – Discharge grille
NOTICE
Unpacking. When you remove the top packaging/accessories, hold the box
containing the discharge grille to prevent it from falling.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Installer reference guide
19
3 | About the box
1 2
12×1×4×
a b
g h ic d e f
b
a a
b

3.3 Indoor unit

3.3.1 To unpack the indoor unit

3.3.2 To remove the accessories from the indoor unit

a Shut-off valves for water circuit b Overpressure bypass valve
c General safety precautions d Addendum book for optional equipment e Indoor unit installation manual
f Operation manual g Sealing rings for shut-off valves (space heating water circuit) h Sealing rings for field-supplied shut-off valves (domestic hot water circuit)
i Sealing tape for low voltage wiring intake

3.3.3 To handle the indoor unit

Use the handles at the back and at the bottom to carry the unit.
Installer reference guide
20
a Handles at the back of the unit b Handles at the bottom of the unit. Carefully tilt the unit to the back so that the
handles become visible.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12

4 About the units and options

In this chapter

4.1 Overview: About the units and options ................................................................................................................................. 21
4.2 Identification........................................................................................................................................................................... 21
4.2.1 Identification label: Outdoor unit .......................................................................................................................... 21
4.2.2 Identification label: Indoor unit ............................................................................................................................. 22
4.3 Combining units and options.................................................................................................................................................. 22
4.3.1 Possible combinations of indoor unit and outdoor unit ....................................................................................... 22
4.3.2 Possible options for the outdoor unit.................................................................................................................... 22
4.3.3 Possible options for the indoor unit ...................................................................................................................... 23

4.1 Overview: About the units and options

This chapter contains information about:
Identifying the outdoor unit
Identifying the indoor unit
Combining the outdoor unit with options
4 | About the units and options
Combining the indoor unit with options

4.2 Identification

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.

4.2.1 Identification label: Outdoor unit

Location
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Model identification
Example: EPRA14DAV3
Code Explanation
EP European hydro-split outdoor pair heat pump
R High water temperature – ambient zone 2 (see operation
range)
A Refrigerant R32
Installer reference guide
21
4 | About the units and options
14 Capacity class
DA Model series
V3 Power supply

4.2.2 Identification label: Indoor unit

Location
Model identification
Example: ETVZ16S18DA6V
E European model
Code Explanation
Code Description
TV Floor-standing hydro-split unit with integrated tank
Z Dual-zone model
16 Capacity class
S Integrated tank material: Stainless steel
18 Integrated tank volume
DA Model series
6V Backup heater model

4.3 Combining units and options

INFORMATION
Certain options might not be available in your country.

4.3.1 Possible combinations of indoor unit and outdoor unit

Indoor unit Outdoor unit
EPRA14 EPRA16 EPRA18

4.3.2 Possible options for the outdoor unit

Installer reference guide
22
ETVZ16 O O O
Mounting stand (EKMST1, EKMST2)
In colder regions where heavy snowfall can occur, it is recommended to install the outdoor unit on a mounting frame. Use one of the following models:
EKMST1 with flange feet: to install the outdoor unit on a concrete foundation
where drilling is allowed.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
EKMST2 with rubber feet: to install the outdoor unit on foundations where
drilling is not allowed or possible, such as flat roofs or pavements.
For installation instructions, see the installation manual of the mounting stand.

4.3.3 Possible options for the indoor unit

Multi-zoning wired controls
You can connect the following multi-zoning wired controls:
Multi-zoning base unit 230V (EKWUFHTA1V3)
Digital thermostat 230V (EKWCTRDI1V3)
Analogue thermostat 230V (EKWCTRAN1V3)
Actuator 230V (EKWCVATR1V3)
For installation instructions, see the installation manual of the control, and the addendum book for optional equipment.
Wireless room thermostat (EKRTR1)
You can connect an optional wireless room thermostat to the indoor unit.
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
4 | About the units and options
Remote sensor for wireless thermostat (EKRTETS)
You can use the remote indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (EKRTR1).
For installation instructions, see the installation manual of the room thermostat and the addendum book for optional equipment.
Digital I/O PCB (EKRP1HBAA)
The digital I/O PCB is required to provide following signals:
Alarm output
Space heating/cooling On/OFF output
Changeover to external heat source
For installation instructions, see the installation manual of the digital I/O PCB and addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
By default the internal sensor of the dedicated Human Comfort Interface (BRC1HHDA used as room thermostat) will be used as room temperature sensor.
As an option the remote indoor sensor can be installed to measure the room temperature on another location.
For installation instructions, see the installation manual of the remote indoor sensor and addendum book for optional equipment.
Installer reference guide
23
4 | About the units and options
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor temperature on another location (e.g. to avoid direct sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor sensor and the addendum book for optional equipment.
PC cable (EKPCCAB4)
INFORMATION
The remote indoor sensor can only be used in case the user interface is
configured with room thermostat functionality.
You can only connect either the remote indoor sensor or the remote outdoor
sensor.
INFORMATION
You can only connect either the remote indoor sensor or the remote outdoor sensor.
The PC cable makes a connection between the switch box of the indoor unit and a PC. It gives the possibility to update the software of the indoor unit.
For installation instructions, see the installation manual of the PC cable.
Heat pump convector (FWXV, FWXT, FWXM)
For providing space heating/cooling, it is possible to use the following heat pump convectors:
FWXV: floor-standing model
FWXT: wall-mounted model
FWXM: concealed model
For installation instructions, see:
The installation manual of the heat pump convectors
The installation manual of the heat pump convector options
The addendum book for optional equipment
LAN adapter for smartphone control + Smart Grid applications (BRP069A61)
You can install this LAN adapter to:
Control the system via a smartphone app.
Use the system in various Smart Grid applications.
Installer reference guide
24
For installation instructions, see the installation manual of the LAN adapter and the addendum book for optional equipment.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a smartphone app.
For installation instructions, see the installation manual of the LAN adapter and the addendum book for optional equipment.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
4 | About the units and options
WLAN adapter (BRP069A71)
You can install the wireless LAN adapter to control the system via a smartphone app.
For installation instructions, see the installation manual of the WLAN adapter and the addendum book for optional equipment.
Universal centralised controller (EKCC8-W)
Controller for cascade control.
Conversion kit (EKHVCONV2)
Use the connection kit to convert a heating only model to a reversible model.
For installation instructions, see the installation manual of the conversion kit.
Human Comfort Interface (BRC1HHDA) used as room thermostat
The Human Comfort Interface (HCI) used as room thermostat can only be used in
combination with the user interface connected to the indoor unit.
The Human Comfort Interface (HCI) used as room thermostat needs to be
installed in the room that you want to control.
For installation instructions, see the installation and operation manual of the Human Comfort Interface (HCI) as room thermostat.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Installer reference guide
25
5 | Application guidelines

5 Application guidelines

In this chapter

INFORMATION
Cooling is only applicable in case a conversion kit (EKHVCONV2) is installed.
5.1 Overview: Application guidelines........................................................................................................................................... 26
5.2 Setting up the space heating/cooling system ........................................................................................................................ 27
5.2.1 Multiple rooms – TwoLWT zones ......................................................................................................................... 28
5.3 Setting up the domestic hot water tank ................................................................................................................................ 30
5.3.1 System layout – Integrated DHW tank .................................................................................................................. 30
5.3.2 Selecting the volume and desired temperature for the DHW tank ...................................................................... 30
5.3.3 Setup and configuration – DHW tank .................................................................................................................... 32
5.3.4 DHW pump for instant hot water .......................................................................................................................... 32
5.3.5 DHW pump for disinfection ................................................................................................................................... 33
5.4 Setting up the energy metering ............................................................................................................................................. 34
5.4.1 Produced heat ........................................................................................................................................................ 34
5.4.2 Consumed energy .................................................................................................................................................. 34
5.4.3 Normal kWh rate power supply............................................................................................................................. 35
5.4.4 Preferential kWh rate power supply...................................................................................................................... 36
5.5 Setting up the power consumption control........................................................................................................................... 37
5.5.1 Permanent power limitation.................................................................................................................................. 38
5.5.2 Power limitation activated by digital inputs .......................................................................................................... 38
5.5.3 Power limitation process ....................................................................................................................................... 40
5.5.4 BBR16 power limitation ......................................................................................................................................... 40
5.6 Setting up an external temperature sensor........................................................................................................................... 41

5.1 Overview: Application guidelines

The purpose of the application guidelines is to give a glance of the possibilities of the heatpump system.
NOTICE
The illustrations in the application guidelines are meant for reference only, and
are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic dimensioning and balancing are NOT shown, and are the responsibility of the installer.
For more information about the configuration settings to optimize heat pump
operation, see "9Configuration"[4106].
This chapter contains application guidelines for:
Setting up the space heating/cooling system
Setting up the domestic hot water tank
Setting up the energy metering
Setting up the power consumption control
Setting up an external temperature sensor
Installer reference guide
26
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
NOTICE
Certain types of fan coil units –in this document referred to as "heat pump convectors"–, are able to receive input of the indoor unit operation mode (cooling or heating X2M/3 and X2M/4) and/or to send output of the heat pump convector thermostatic condition (main zone: X2M/30 and X2M/35; additional zone: X2M/30 and X2M/35a).
The application guidelines illustrate the possibility of receiving or sending digital input/output. This functionality can only be used in case the heat pump convector has such features and the signals meet following requirements:
Output of indoor unit (input to heat pump convector): cooling/heating
signal=230V (cooling=230V, heating=0V).
Input to indoor unit (output of heat pump convector): thermostat ON/OFF
signal=voltage-free contact (closed contact=thermo ON, open contact=thermo OFF).

5.2 Setting up the space heating/cooling system

The heat pump system supplies leaving water to heat emitters in one or more rooms.
5 | Application guidelines
Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:
How many rooms are heated or cooled by the heatpump system?
Which heat emitter types are used in each room and what is their design leaving
water temperature?
Once the space heating/cooling requirements are clear, we recommend to follow the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if [C.2] Space heating/cooling=On.
INFORMATION
In case an external room thermostat is used and room frost protection needs to be guaranteed in all conditions, then you have to set Emergency [9.5.1] to Automatic.
NOTICE
An overpressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
Installer reference guide
27
5 | Application guidelines
a
5.2.1 Multiple rooms – TwoLWT zones
NOTICE
If you install this unit as a single-zone application, then:
Setup. Install a bypass between the space heating water inlet and outlet of the additional zone (=direct zone). Do NOT interrupt the water flow by closing the shut­off valves.
a Bypass
Configuration. Set field setting [7-02]=0 (Number of zones = Single zone).
This unit is designed to deliver water at 2 different temperatures. A typical installation consists of underfloor heating at a lower temperature and radiators at a higher water temperature.
In this document:
Main zone = Zone with the lowest design temperature in heating, and the highest
design temperature in cooling
Additional zone = Zone with the highest design temperature in heating, and the
lowest design temperature in cooling
Typical example:
Room (zone) Heat emitters: Design temperature
Living room (main zone) Underfloor heating:
In heating: 35°C
In cooling: 20°C (only refreshment, no
real cooling allowed)
Bed rooms (additional zone) Heatpump convectors:
In heating: 45°C
In cooling: 12°C
Installer reference guide
28
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
5 | Application guidelines
B
A
D
E
C
a
b
a
Setup
A Additional leaving water temperature zone B Room 1
C Room 2
D Main leaving water temperature zone
E Room 3 a Heatpump convectors (+ controllers)
b Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
For the main zone: the room temperature is controlled by the dedicated Human
Comfort Interface (BRC1HHDA used as room thermostat).
For the additional zone:
- The external thermostat is directly connected to the indoor unit.
- The desired room temperature is set via the external thermostat and the
thermostatic valves of the radiators in each room.
- The heating demand signal from the external thermostat is connected to the
digital input on the indoor unit (X2M/35a and X2M/30). The indoor unit will only supply the desired additional leaving water temperature when there is an actual demand.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
2 (Room thermostat): Unit operation is decided based on the ambient temperature of the dedicated Human
Code: [C-07]
Comfort Interface.
Note:
Main room = dedicated Human
Comfort Interface used as room thermostat functionality
Other rooms = external room
Number of water temperature zones:
thermostat functionality
1 (Dual zone): Main + additional
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W Daikin Altherma 3 H HT F 4P587503-1B – 2020.12
#: [4.4]
Code: [7-02]
Installer reference guide
29
5 | Application guidelines
A
a
b
Setting Value
In case of heatpump convectors:
External room thermostat for the additional zone:
1 (1 contact): When the used external room thermostat or heatpump convector can only send a thermo ON/ OFF condition. No separation between
#: [3.A]
heating or cooling demand.
Code: [C-06]
Shut-off valve output Set to follow the thermo demand of the
main zone.
Benefits
Comfort.
- The smart room thermostat functionality can decrease or increase the desired
leaving water temperature based on the actual room temperature (modulation).
- The combination of the two heat emitter systems provides the excellent
heating comfort of the underfloor heating, and the excellent cooling comfort of the heatpump convectors.
Efficiency.
- Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
- Underfloor heating has the best performance with the heat pump system.

5.3 Setting up the domestic hot water tank

5.3.1 System layout – Integrated DHW tank

A Domestic hot water
a Cold water IN
b Hot water OUT
Installer reference guide
30

5.3.2 Selecting the volume and desired temperature for the DHW tank

People experience water as hot when its temperature is 40°C. Therefore, the DHW consumption is always expressed as equivalent hot water volume at 40°C. However, you can set the DHW tank temperature at a higher temperature (example: 53°C), which is then mixed with cold water (example: 15°C).
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1B – 2020.12
Loading...
+ 222 hidden pages