Daikin EKRSVHTA Installation manuals

INSTALLATION MANUAL
Refrigerant stop valves kit
EKRSVHTA
1
2
3
4
5
1
2
3
EKRSVHTA
ONTENTS
C
1. Introduction................................................................................ 1
2. Accessories ............................................................................... 1
3. Installing the stop valves............................................................ 1
4. Guidelines for handling stop valves........................................... 1
5. Final check ................................................................................ 1
6. Vacuuming/recovery and maintenance on refrigerant side ....... 2
6.1. System overview............................................................................ 3
6.2. Recovery/vacuuming overview for 1 indoor unit maintenance
(R410A circuit connections) ........................................................... 3
NTRODUCTION
1. I
Thank you for purchasing this option kit. The kit can only be connected to the EKHBRD indoor unit. The kit is designed for wall mounted indoor installation.
The original instructions are written in English. All other languages are translations of the original instructions.
2. A
CCESSORIES
21345
1x 1x1x1x 1x 1x
Refrigerant stop valves kit
age
P
Installation manual
1
2
3 3
Support plate Stop valve To outdoor unit
Finalise the refrigerant piping work (connect the prepared refrigerant piping to the piping coming from the outdoor unit).
4. G
UIDELINES
FOR
HANDLING
STOP
VALVES
Installation manual Support plate Gas stop valve Liquid stop valve Fixing screws
3. I
NSTALLING
Caution for brazing.
Refer to the outdoor unit installation manual for cautions for brazing.
These stop valves must be installed near to the unit, and on an accessible place (when service is needed the stop valves need to be closed and equipment for recovery/vacuuming has to be connected).
Decide where to install the stop valves and position the stop valves on the wall by using the support plate.
THE
STOP
VALVES
Refer to the outdoor unit installation manual for guidelines for handling stop valves.
INAL
5. F
Refer to the indoor unit installation manual for final check of the indoor unit. Additionally, make sure that all stop valves are open. Refer to the vacuuming procedure of the outdoor unit.
CHECK
Installation manual
1
Refrigerant stop valves kit
4PW73662-1 – 04.2012
EKRSVHTA
6. V
ACUUMING
/
RECOVERY
AND
MAINTENANCE
ON
REFRIGERANT
SIDE
This flow chart indicates the main items and actions which have to be considered during vacuuming/recovery operations on the system. When certain settings and operations explained in the flow chart are not followed this can be improper operation of the unit due to bad vacuuming/ recovery. In case of problems, please contact your local dealer.
R134a circuit needs
to be maintenanced?
No
R410A circuit needs
to be maintenanced?
Ye s
First installation
Ye s Ye s
Indoor unit was
powered on?
Ye s Ye s Ye s
Valves on R410A circuit need to be
opened. Apply
outdoor unit field
setting 2-21 (see
installation manual of
outdoor unit)
Yes Indoor unit remocon
setting [E-00]=1 to
open electronic
expansion valve
No
Other indoor or
outdoor unit(s) were
powered on?
No
No Open stop valve
Start recovery/
vacuuming of R134a circuit
indoor units
(a)
. Field
(2)
piping and indoor unit
R410A
vacuuming can
start
Ye s
Open all
stopvalves (1)
(a)
and (2)
Maintenance
Complete indoor
system R410A
circuit?
Field piping +
indoor + outdoor
unit(s)?
No
Field piping only +
indoor unit
No
1 indoor unit?
Close this indoor
unit stop valve
(a)
(2)
Apply outdoor
unit field setting
2-21 (see
installation
manual of
outdoor unit)
Recovery start +
measure
recovered
R410A amount
Open stop valve
(a)
indoor units.
(2)
Field piping and
indoor unit R410A
vacuuming can start
Apply outdoor
unit field setting
2-21 (see
installation
manual of
outdoor unit)
Close stop valve
outdoor unit (1)
Open stop valve indoor unit (2)
Apply outdoor unit
field setting 2-21
(see installation
manual of outdoor
(a)
(a)
unit)
Maintenance
Start vacuuming
Recharge
system with
measured
R410A amount
Cancel outdoor unit field setting
2-21 (see
installation
manual of
outdoor unit)
Open stop valve(s) (if applicable)
Restart system
(a) (1) and (2) refers to the legend of the figure in next chapter "System overview" on page 3.