READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
ALL ACTIVITIES DESCRIBED IN THIS MANUAL SHALL
BE CARRIED OUT BY A LICENSED TECHNICIAN.
BE SURE TO WEAR ADEQUATE PERSONEL PROTECTION EQUIPMENT (PROTECTION GLOVES, SAFETY
GLASSES, ...) WHEN PERFORMING INSTALLATION,
MAINTENANCE OR SERVICE TO THE UNIT.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED
FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT
TEMPERATURES RANGING 5°C~30°C.
The English text is the original instruction. Other languages are
translations of the original instructions.
INTRODUCTION
General information
Thank you for purchasing this unit.
The unit is the indoor part of the air to water ERSQ or ERRQ heat
pump. The unit is designed for floor standing indoor installation and
used for heating applications. The unit can be combined with space
heating radiators (field supply) and with an EKHTS* domestic hot
water tank (option).
A remote controller with room thermostat functionality is standard
supplied with this unit to control your installation.
NOTE
Domestic hot water tank (option)
An optional EKHTS* domestic hot water tank can be connected to
the indoor unit. The domestic hot water tank is available in two
different water capacities: 200 and 260 litre.
Refer to the domestic hot water tank installation manual for further
details.
Remote controller (option)
An optional secondary EKRUAHTA remote controller (with room
thermostat functionality) can be connected to the indoor unit.
Purpose is to provide the possibility to install the standard remote
controller near the unit (for service reasons), and install another
remote controller in another place (e.g. living room) to operate your
installation.
Refer to the "Installation of the remote controller" on page 15 for
further details.
An EKHBRD indoor unit can only be connected to an
ERSQ or ERRQ outdoor unit.
Installation manual
1
Indoor unit for air to water heat pump system
EKHBRD011~016AAV1+Y1
4PW54465-1C
Room thermostat (option)
An optional room thermostat EKRTR or EKRTW can be connected to
the indoor unit.
Refer to the room thermostat installation manual for further details.
If this option is installed it is not possible to use the remote
controller thermostat function.
Heater kit (option)
An optional EKBUH heater kit can be combined with the indoor unit.
Purpose is to provide an additional heating capacity during cold
outdoor temperatures. The heater kits are available for a heating
capacity of 2-6 kW, and both available for 1-phase and 3-phase
power supply specifications. When using this heater kit the optional
demand PCB is required.
Refer to the heater kit installation manual for further details.
P
H
2
3
1
T
A
1Heat pump capacity
2Required heating capacity (site dependent)
3Additional heating capacity provided by the heater kit
T
Ambient (outdoor) temperature
A
P
Heating capacity
H
Digital I/O PCB (option)
An optional EKRP1HBA digital I/O PCB can be connected to the
indoor unit and be used to remotely monitor your system. This
address card offers 3 voltage free outputs.
Refer to the operation manual of the indoor unit and to the digital I/O
PCB installation manual for more information.
Refer to the wiring diagram or connection diagram for connecting this
PCB to the unit.
Demand PCB (option)
An optional EKRP1AHTA demand PCB can be connected to the
indoor unit. This PCB is needed when the optional heater kit EKBUH
or Daikin room thermostat EKRTR or EKRTW is installed or when
multiple set point control is used, and provides the communication
with the indoor unit.
Refer to the demand PCB installation manual for further details.
Refer to the wiring diagram or connection diagram for connecting this
PCB to the unit.
Scope of this manual
This installation manual describes the procedures for handling,
installing and connecting all EKHBRD indoor unit models.
Model identification
Indoor unit
EKHBRD016AAV1
V1=1N~, 220-240 V, 50 Hz
Y1=3N~, 380-415 V, 50 Hz
Series
Indication of heating capacity (kW)
Refrigerant type R134a
Hydro box - high temperature heating only
European kit
(a) For exact values, refer to "Unit specifications" on page 36.
(a)
Typical application examples
The application examples given below are for illustration purposes
only.
Application 1
Space heating and domestic hot water heating with a single remote
controller installed in the living room.
The remote controller gives immediate feedback to the indoor unit
and by doing so it matches in a smart way the unit performance to
the demanded space heating requirements. In this way there is no
frequent start/stop of the unit or there are no too big temperature
fluctuations in the to be heated rooms. This remote controller has
also a smart logic functionality which controls the combined space
heating and domestic hot water demand (e.g. if room temperature
drops more than 3°C during domestic hot water operation, the unit
will automatically switch back to space heating). There is no remote
controller near the unit. During service maintenance an additional
remote controller can be connected by a service person.
9
NOTE
Installation of the ERSQ or ERRQ heat pump outdoor
is described in the outdoor unit installation manual.
Operation of the indoor unit is described in the indoor
unit operation manual.
EKHBRD011~016AAV1+Y1
Indoor unit for air to water heat pump system
4PW54465-1C
Installation manual
2
Application 2
Space heating and domestic hot water heating with one remote
controller installed with the unit, and another remote controller
installed in the living room.
Application 3
Space heating and domestic hot water heating with a single remote
controller installed with the unit, and the external room thermostat
installed in the living room.
The remote controller gives immediate feedback to the indoor unit
and by doing so it matches in a smart way the unit performance to
the demanded space heating requirements. In this way there is no
frequent start/stop of the unit or there are no too big temperature
fluctuations in the to be heated rooms. This remote controller has
also a smart logic functionality which controls the combined space
heating and domestic hot water demand (e.g. if room temperature
drops more than 3°C during domestic hot water operation, the unit
will automatically switch back to space heating). The main remote
controller (C1) is installed in the living room and can access all
settings (master). The second remote controller (C2) can not access
schedule and parameter settings (slave).
MasterSlave
Operation ON/OFFOperableOperable
Domestic water heating operation ON/OFFOperableOperable
Setting the leaving water temperatureOperableOperable
Setting the room temperatureOperableOperable
Quiet mode ON/OFFOperableOperable
Weather dependent set point operation
ON/OFF
Setting the clockOperableOperable
Programming the schedule timerOperable—
Schedule timer operation ON/OFFOperable—
Field settingsOperable—
Error code displayOperableOperable
Test operationOperableOperable
Room thermostat functionalityOperable—
OperableOperable
Optionally the Daikin room thermostat EKRTR or EKRTW
can be connected to the Daikin system. Daikin can not
guarantee neither good operation nor reliability of the
system if another thermostat is used. For those reasons
Daikin can not give warranty of the system in such case.
There is only a room thermostat on/off control. There is no smart
logic functionality for space heating. The domestic hot water
operation is performed according to the minimum and maximum
timer operation.
Refer to the chapter "Electrical wiring work" on page 13 about
connecting the master and slave remote controller.
Installation manual
3
Indoor unit for air to water heat pump system
EKHBRD011~016AAV1+Y1
4PW54465-1C
Application 4
Space heating provided through floor heating loops. For floor heating
applications in combination with radiators the water temperature
delivered by the Daikin system is too high. For this reason a
temperature reducing device (field supply) is required to lower the
water temperature (the hot water will be mixed with cold water to
lower the temperature). The control of this field supplied feature is not
done by the heat pump system. The operation and configuration of
the field water circuit is the responsibility of the installer. Daikin only
offers the possibility to have multiple set points on request.
Pattern A
The domestic hot water tank is installed in parallel with the mixing
station(s). This allows operating the unit in space heating and
domestic water heating simultaneously. The balancing of the water
distribution is in this case the responsibility of the installer.
Pattern B
The domestic hot water tank is installed in a separate circuit (with a
3-way valve) of the temperature reducing device(s). This
configuration does not allow simultaneous domestic hot water and
space heating operation.
C1
7431010 21
6
M
TRD1
45°C
TRD2
35°C65°C
C1
8
7431010 216
TRD1
59
1Outdoor unit9Domestic hot water tank
2Indoor unit
3Refrigerant heat exchanger10Electronic expansion
4Water heat exchanger
5CompressorC1Remote controller
6Pump
7Shut-off valve
8Valve (field supply)
7
TRD1
TRD2
(optional)
valve
Temperature reducing
device 1
Temperature reducing
device 2
65°C
TRD2
35°C
5
8
7
1Outdoor unit9Domestic hot water tank
2Indoor unit
3Refrigerant heat exchanger10Electronic expansion
4Water heat exchanger
5CompressorC1Remote controller
6Pump
7Shut-off valve
8Motorized 3-way valve
(optional)
TRD1
TRD2
9
(optional)
valve
Temperature reducing
device 1
Temperature reducing
device 2
Refer to the chapter "Multiple set point control" on page 27 for more
information about the configuration of your system.
EKHBRD011~016AAV1+Y1
Indoor unit for air to water heat pump system
4PW54465-1C
Installation manual
4
Application 5
Space heating with an auxiliary boiler (alternating operation)
Space heating application by either the Daikin indoor unit or by an
auxiliary boiler connected in the system. An auxiliary contact decides
whether either the EKHBRD* indoor unit or the boiler will operate.
This auxiliary contact can e.g. be an outdoor temperature thermostat,
an electricity tariff contact, a manually operated contact, etc.
Bivalent operation is only possible for space heating operation, not
for the domestic hot water heating operation. Domestic hot water in
such an application is always provided by the domestic hot water
tank which is connected to the Daikin indoor unit.
The auxiliary boiler must be integrated in the piping work and in the
field wiring according to the illustrations below.
■Be sure that the boiler and the integration of the boiler
in the system is in accordance with relevant European
and national regulations.
■Daikin can not be put responsible for incorrect or
unsafe situations in the boiler system.
A B
C1
7431212 21
6
M
8
5
1Outdoor unit12Electronic expansion
2Indoor unit
3Refrigerant heat
tankC1Remote controller
10Collector (field supply)AInstallation place
11Radiator (field supply)BLiving room
10 13
11
15
17
16
valve
13By-pass valve (field
supply)
(field supply)
(field supply)
(field supply)
15
16
149
Field wiring
L
th
EKHBRD*
EKHBRD*/auto
Boiler thermostatBoiler thermostat
CAuxiliary contact (normal closed)
thHeating only room thermostat
K1AAuxiliary relay for activation of EKHBRD* unit (field
K2AAuxiliary relay for activation of boiler (field supply)
/Boiler
N
K1A
C
K2A
supply)
A8P
123 4 5
K1A
Boiler
thermostat
X
K2A
Y
Operation
When the room thermostat (th) closes, either the EKHBRD* unit or
the boiler starts operating, depending on the position of the auxiliary
contact (C).
NOTE
■Make sure that auxiliary contact (C) has sufficient
differential or time delay so as to avoid frequent
changeover between the EKHBRD* unit and the
boiler. If the auxiliary contact (C) is an outdoor
temperature thermostat, make sure to install the
thermostat in the shade, so that it is not
influenced or turned ON/OFF by the sun.
Frequent switching may cause corrosion of the
boiler in an early stage. Contact the manufacturer
of the boiler.
■During heating operation of the EKHBRD* unit,
the unit will operate so as to achieve the target
leaving water temperature as set on the user
interface. When weather dependent operation is
active, the water temperature is determined
automatically depending on the outdoor
temperature.
During heating operation of the boiler, the boiler
will operate so as to achieve the target leaving
water temperature as set on the boiler controller.
Never set the target leaving water temperature set
point on the boiler controller above 80°C.
Make sure that return water to the EKHBRD* heat
exchanger never exceeds 80°C.
For this reason, never put the target leaving water
temperature set point on the boiler controller above 80°C
and install an aquastat
(a)
valve in the return water flow of
the EKHBRD* unit.
Make sure that the non-return valves (field supply) are
correctly installed in the system.
Make sure that the room thermostat (th) is not frequently
turned ON/OFF.
Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
(a) The aquastat valve must be set for 80°C and must operate to close the return
water flow to the unit when the measured temperature exceeds 80°C. When the
temperature drops to a lower level, the aquastat valve must operate to open the
return water flow to the EKHBRD* unit again.
9Grommet (large)
10Top plate insulation
11Kit for lifting the unit (2 plates, 3 screws)
12Refrigerant piping connections kit (4 piping parts, 2 screws,
2 clamps)
OVERVIEWOFTHEINDOORUNIT
Main components
162213
82
711232314
21
10
5202419171829 7
2
1.Air purge valve
Remaining air in the water circuit will be automatically removed
via the air purge valve.
2.Temperature sensors (thermistors)
Temperature sensors determine the water and refrigerant
temperature at various points in the circuit.
3.Switch box
The switch box contains the main electronic and electrical parts
of the indoor unit.
4.Heat exchangers
5.Refrigerant liquid connection R410A
6.Refrigerant gas connection R410A
7.Shut-off valves
The shut-off valves on the water inlet connection and water
outlet connection allow isolation of the indoor unit water circuit
side from the residential water circuit side. This facilitates
draining and filter replacement of the indoor unit.
8.Water inlet connection
9.Water outlet connection
10. Drain valve
11. Water filter
The water filter removes dirt from the water to prevent damage
to the pump or blockage of the evaporator. The water filter must
be cleaned on a regular base. See "Maintenance activities" on
page 33.
12. Expansion vessel (12 l)
13. Manometer
The manometer allows readout of the water pressure in the
water circuit.
14. Pump
The pump circulates the water in the water circuit.
15. Pressure relief valve
The pressure relief valve prevents excessive water pressure in
the water circuit by opening at 3 bar and discharging some
water.
16. Service ports R134a
17. Compressor
18. Accumulator
19. 3-way valve
The motorized 3-way valve controls whether the water outlet is
used for space heating or the domestic hot water tank.
20. 4-way valve
21. 2-way valve
22. Thermal cut-out
23. Electronic expansion valve
EKHBRD011~016AAV1+Y1
Indoor unit for air to water heat pump system
4PW54465-1C
15123
216
Installation manual
6
Switch box main components
V1 unit types (1-phase)
101411 17161521697
8
18
15
12
20
13
1
2
3
5
19
15
10. Te r minal block X3M
Field wiring terminal block for DC connections.
11. Te r minal block X2M
Field wiring terminal block for AC connections.
12. DC connector X1Y
13. Pump connector X2Y
14. AC connector X3Y
15. Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable
ties to the switch box to ensure strain relief.
16. Power wiring entry
17. AC field wiring entry
18. DC field wiring entry
19. Compressor cable entry
20. Interface relay K1A
21. Wiring bridges
22. Fuse F1 (only Y1)
23. Fuse F2 (only Y1)
NOTE
The electrical connection diagram can be found on the
inside of the switch box cover.
Functional diagram
Y1 unit types (3-phase)
10 7 14 11 17 16219
1522 615
8
18
15
12
13
20
23
4
1
2
3
19
1.Main PCB
The main PCB (Printed Circuit Board) controls the functioning of
the unit.
2.Control PCB
3.Inverter PCB
4.Inverter control PCB (only Y1)
5.QA PCB (only V1)
6.Filter PCB
7.Digital I/O PCB (optional)
8.Demand PCB (optional)
9.Te rminal block X1M
Main terminal block which allows easy connection of field wiring
for power supply.
The unit is to be placed in an indoor location that meets the following
requirements:
■The installation location is frost-free.
■The space around the unit is adequate for servicing. (See
■The space around the unit allows for sufficient air circulation.
■There is a provision for pressure relief valve blow-off.
■There is no danger of fire due to leakage of inflammable gas.
■The equipment is not intended for use in a potentially explosive
■All piping lengths and distances have been taken into
■Make sure to provide for adequate measures in
order to prevent that the indoor unit should be
used as a shelter by small animals.
■Small animals making contact with electrical parts
can cause malfunctions, smoke or fire. Please
instruct the customer to keep the area around the
unit clean.
figure 2).
atmosphere.
consideration.
Requirement Value
Maximum allowable refrigerant piping length between
outdoor unit and indoor unit
Minimum required refrigerant piping length between
outdoor unit and indoor unit
Maximum allowable height difference between
outdoor unit and indoor unit
Maximum allowable distance between the domestic
hot water tank and the indoor unit (only for
installations with domestic hot water tank).
50 m
3 m
30 m
10 m
Unit of measurement: mm
Dimensions of the unit, see figure 4
1Gas pipe connection10Water filter
2Liquid pipe connection11Water inlet connection
3Service port12Water outlet connection
4Manometer13Electrical wir ing knock out
5Pressure relief valve
6Flexible hose blow off
valve
7Drain valve water circuit15Water piping knock out
8Air purge valve
9Shut-off valve16Levelling feet
holes
14Refrigerant piping knock
out holes
holes
Required service space, see figure 2
ASpace required for switch box removal
BLeft installation (top view)
CRight installation (top view)
DSpace required for wiring (in case of right installation)
Inspecting and handling the unit
■At delivery, the unit must be checked and any damage must be
reported immediately to the carrier claims agent.
■Bring the unit as close as possible to its final installation position
in its original package in order to prevent damage during
transport.
■Unpack the indoor unit completely according to the instructions
mentioned on the unpacking instructions sheet.
■Check if all indoor unit accessories (see "Accessories" on
page 6) are enclosed.
NOTE
If the installation is equipped with a domestic hot water
tank (optional), please refer to the domestic hot water
tank installation manual.
■Do not install the unit in places often used as workplace.
In case of construction works (e.g. grinding works) where a lot of
dust is created, the unit must be covered.
■Do not install the unit in places with high humidity (e.g.
bathroom) (maximum humidity (RH)=85%).
■If the sound is measured under actual installation conditions, the
measured value will be higher than the sound pressure level
mentioned in the "Unit specifications" on page 36 due to
environmental noise and sound reflections. Choose the
installation location carefully and do not install in a sound
sensitive environment (e.g. living room, bedroom, ...).
■Ta ke care that in the event of a water leak, water can not cause
any damage to the installation space and surroundings.
■The foundation must be strong enough to support the weight of
the unit (or unit and optional domestic hot water tank completely
filled with water in case the optional domestic hot water tank is
mounted on top of the unit).
The floor is flat to prevent vibrations and noise generation and to
have sufficient stability especially when the optional domestic
hot water tank is mounted on top of the unit.
■Do not place any objects or equipment on top of the unit (top
plate).
■Do not climb, sit or stand on top of the unit.
■Be sure that sufficient precautions are taken, in accordance with
relevant local and national regulations, in case of refrigerant
leakage.
Installing the indoor unit
NOTE
■For connecting piping and electrical cables, knockout holes are
For installation of the outdoor unit, refer to the
installation manual of the outdoor unit.
provided at the back of the unit.
■Knockout holes are foreseen at both sides of the
unit. Pay attention to knock out the correct holes
depending on your installation location.
■Refrigerant piping and water piping must go
through different knockout holes.
■The electrical wiring must always enter the unit
through the 2 upper knockout holes at the left
side of the unit (see figure 4).
■Do NOT use the 2 lower knockout holes.
■ To punch a knockout hole, hit on it with a hammer.
■ When passing electrical wiring or piping through the
knockout holes, remove any burrs from the knockout holes.
EKHBRD011~016AAV1+Y1
Indoor unit for air to water heat pump system
4PW54465-1C
Installation manual
8
■ Install the grommets (accessories) around the knockout
holes to prevent damage.
1234
1Knockout hole3Grommet
2Burr4Putty or insulation
materials (field supply)
■Put the flexible pipes through the knockout holes.
■Level the unit to a stable position
using the levelling feet.
■Close the sound panel(s) and decoration panel(s) which will be
on the wall side and for which fixation is not possible anymore
after the unit is put on its final location.
■Fix the sound bottom strips on both sides of the unit with the
appropriate screws.
1
3
3
1
2
2
0 mm
2x
■Perform the piping work as described in the chapter "Piping
connection work" on page 10.
■Fill the system with water as described in the chapter "Charging
water" on page 13.
■Perform the electrical wiring work as described in the chapter
"Electrical wiring work" on page 13.
■To make the casing completely sealed, plug the knockout holes
with putty or insulation materials (to be prepared on-site).
■Perform the pre-operation checks as described in the chapter
"Start-up and configuration" on page 17.
■Close the unit
1 Put the sound bottom plate at the bottom of the unit and fix it
with the appropriate screws.
12
■
■Place the unit in the appropriate installation location.
■Cut the tie wraps to release the flexible pipes.
Standard installation location of the optional domestic
hot water tank is on top of the indoor unit.
If available service space to left and/or right side is
limited, carefully consider all tank module installation
steps first.
The weight of the unit is approximately 145 kg. At
least two persons are required to lift the unit.
Use the plates delivered with the unit to lift the unit.
34
2 Fix the top panel on the unit with the appropriate screws.
4x
2x
Installation manual
9
Indoor unit for air to water heat pump system
EKHBRD011~016AAV1+Y1
4PW54465-1C
3 Fix the front and remaining side decoration panel(s) back to
the unit using the appropriate screws.
PIPINGCONNECTIONWORK
Refrigerant piping work
For all guidelines, instructions and specifications regarding
refrigerant piping work between the indoor unit and the outdoor unit,
please refer to the outdoor unit installation manual.
4 refrigerant pipes are delivered with the unit to make the refrigerant
connections inside the unit. Refer to the instructions mentioned on
the top plate of the unit.
■ In case of right connection, only 2 pipes are required.
■ In case of left connection, the 4 pipes are required.
Do not braze the piping connections inside the unit.
75 mm
2x
4 Stick the top plate insulation (accessory) at the inside of the
top decoration panel according to the figure below.
12
5 mm
34
5 Fix the top decoration panel on top of the unit using the
appropriate screws. In case a domestic hot water tank
(optional) is installed, refer to the domestic hot water tank
installation manual.
2x
150 mm
11
1Self-tapping screws
Please apply sufficient force to drive the screw into the
sheetmetal!
Guidelines for flare connection
■Flares should not be re-used. New ones should be made in
order to prevent leaks.
■Use a pipe cutter and flare tool suitable for the refrigerant used.
■Only use the annealed flare nuts included with the unit. Using
different flare nuts may cause the refrigerant to leak.
■Please refer to the table for flaring dimensions and tightening
torques (too much tightening will result in splitting the flare).
Piping size
(mm)
Ø9.533~3912.8~13.2
Ø15.963~7519.4~19.7
Tightening
torque (N•m)
Flare dimensions A
(mm)
Flare shape
(mm)
±2
90
45
±2
A
R=0.4~0.8
EKHBRD011~016AAV1+Y1
Indoor unit for air to water heat pump system
4PW54465-1C
■When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.
Installation manual
10
■When loosening a flare nut, always use two wrenches together.
When connecting the piping, always use a spanner and torque
wrench together to tighten the flare nut to prevent flare nut
cracking and leaks.
42
1
3
1Piping union
2Spanner
3Flare nut
4Torque wrench
Not recommended, but in case of emergency
Should you be forced to connect the piping without a torque
wrench, follow the following installation method:
■ Tighten the flare nut using a spanner until the tightening
torque suddenly increases.
■ From that position further tighten the flare nut the angle listed
below:
Piping size
(mm)
Ø9.560~90±200
Ø15.930~60±300
Further tightening
angle (degrees)
Recommended arm
length of spanner (mm)
Water piping work
Checking the water volume and expansion vessel
pre-pressure
The unit is equipped with an expansion vessel of 12 litre which has a
default pre-pressure of 1 bar.
To assure proper operation of the unit, the pre-pressure of the
expansion vessel might need to be adjusted and the minimum and
maximum water volume must be checked.
1Check that the total water volume in the installation, excluding
the internal water volume of the unit, is 20 l minimum.
In most applications this minimum water volume will have a
satisfying result.
In critical processes or in rooms with a high heat load
though, extra water volume might be required.
When circulation in each space heating/radiator loop is
controlled by remotely controlled valves, it is important that
this minimum water volume is kept even if all the valves are
closed.
Example
A B
11
C1
11
77 8432916 10
Checking the water circuit
The units are equipped with a water inlet and water outlet for
connection to a water circuit. This circuit must be provided by a
licensed technician and must comply with all relevant European and
national regulations.
The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
corrosion of the water piping.
Before continuing the installation of the unit, check the following
points:
■The maximum water pressure is 4 bar.
■The maximum water temperature is 85°C.
■Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance.
One drain valve in the indoor unit, and a drain valve on the
expansion vessel are provided to drain the water from the indoor
unit water system.
■Make sure to provide a proper drain for the pressure relief valve
to avoid any water coming into contact with electrical parts.
■Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing. An automatic air purge is provided inside the indoor
unit. Check that this air purge valve is not tightened too much so
that automatic release of air in the water circuit remains possible.
■Ta ke care that the components installed in the field piping can
withstand the water pressure and temperature.
■Always use materials which are compatible with the water used
in the system and with the materials used on the indoor unit.