Daikin EKHBHE008BA3V3, EKHBXE008BA3V3 Installation manuals

INSTALLATION MANUAL
Indoor unit for air to water heat pump system
>6 kW
EKHBHE008BA3V3 EKHBXE008BA3V3
35
8
01
SP
1
12 3 45
1
3
2
2x2x1x 1x 1x
2
4
260
T T
1" MB
895
90°
922
30°
830
B B
469
4
361
48
2 3
4
1
96
39
4 5
3
ONTENTS
C
EKHBHE008BA*** EKHBXE008BA***
Indoor unit for air to water heat pump system
age
P
Introduction........................................................................................ 1
General information ...................................................................................1
Scope of this manual .................................................................................2
Model identification ....................................................................................2
Accessories .......................................................................................2
Accessories supplied with the indoor unit..................................................2
Safety considerations ........................................................................3
Typical application examples.............................................................4
Application 1 ..............................................................................................4
Application 2 ..............................................................................................4
Application 3 ..............................................................................................5
Application 4 ..............................................................................................5
Application 5 ..............................................................................................6
Application 6 ..............................................................................................8
Overview of the indoor unit................................................................ 9
Opening the indoor unit.............................................................................. 9
Main components..................................................................................... 10
Switch box main components ..................................................................11
Functional diagram ..................................................................................11
Installation of the indoor unit............................................................12
Selecting an installation location.............................................................. 12
Dimensions and service space ................................................................12
Inspecting, handling and unpacking the unit............................................ 12
Mounting the indoor unit ..........................................................................13
Installation of the EKHBDP drain pan kit (only for EKHBX models).........13
Refrigerant pipework................................................................................ 13
Water pipework........................................................................................14
Charging water......................................................................................... 16
Piping insulation....................................................................................... 16
Field wiring............................................................................................... 16
Start-up and configuration ...............................................................20
DIP switch settings overview....................................................................20
Room thermostat installation configuration.............................................. 20
Pump operation configuration..................................................................21
Domestic hot water tank installation configuration................................... 21
Initial start-up at low outdoor ambient temperatures................................ 21
Pre-operation checks...............................................................................21
Powering up the indoor unit ..................................................................... 22
Setting the pump speed...........................................................................22
Field settings............................................................................................ 22
Field settings table...................................................................................31
Test run and final check...................................................................33
Final check............................................................................................... 33
Test run operation (manual) ..................................................................... 33
Maintenance and service ................................................................33
Troubleshooting ...............................................................................34
General guidelines................................................................................... 34
General symptoms................................................................................... 35
Error codes ..............................................................................................36
Technical specifications................................................................... 38
General ....................................................................................................38
Electrical specifications............................................................................ 38
Installation manual
READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL.
ALL ACTIVITIES DESCRIBED IN THIS MANUAL SHALL BE CARRIED OUT BY A LICENSED TECHNICIAN.
BE SURE TO WEAR ADEQUATE PERSONEL PROTEC­TION EQUIPMENT (PROTECTION GLOVES, SAFETY GLASSES, ...) WHEN PERFORMING INSTALLATION, MAINTENANCE OR SERVICE TO THE UNIT.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.
THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT TEMPERATURES RANGING 4°C~35°C.
The English text is the original instruction. Other languages are translations of the original instructions.
NTRODUCTION
I

General information

Thank you for purchasing this indoor unit. The unit is the indoor part of the air to water ERHQ or ERLQ heat
pumps. These units are designed for wall mounted indoor installation. See "Selecting an installation location" on page 12. The units can be combined with Daikin fan coil units, floor heating applications, low temperature radiators, Daikin domestic water heating applications and Daikin solar kit for domestic hot water applications.
Heating/cooling units and heating only units
The unit range consists of two main versions: a heating/cooling (EKHBX) version and a heating only (EKHBH) version.
Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures. The backup heater also serves as a backup in case of malfunctioning of the outdoor unit.
Backup heater
Indoor unit model Backup heater capacity
EKHB*E008BA3V3
3 kW 1x 230 V
nominal voltage
EKHBH/XE008BA
Indoor unit for air to water heat pump system
4PW56303-1A
NOTE
An ERLQ0* BA outdoor unit can only be connected to an EKHBH/XE008 BA indoor unit (bottom plate heater at outdoor unit has to be controlled by indoor unit).
An ERHQ0* BA outdoor unit can be connected to an EKHBH/XE008 BA indoor unit or to an EKHBH/XE008 AA indoor unit (if a bottom plate heater kit is required, see "Possible options" on
page 2).
Installation manual
1
1
2
3
4
1
2
3
4
5
The heat pump unit is preset to a restricted power supply condition mode. The information in this manual is only valid in case the power supply condition is not restricted. Refer to the chapter "Field settings" on page 22 on how to disable the restricted power supply condition mode [D-02].
P
H
43
1
2
T
A
Heat pump capacity Required heating capacity (site dependent) Additional heating capacity provided by the backup heater Equilibriumtemperature (can be set through the user interface,
refer to "Field settings" on page 22)
T
Ambient (outdoor) temperature
A
P
Heating capacity
H
Domestic hot water tank (option)
An optional EKHW* domestic hot water tank with integrated 3 kW electrical booster heater can be connected to the indoor unit. The domestic hot water tank is available in three sizes: 150, 200 and 300 litre. Refer to the domestic hot water tank installation manual for further details.
Drain pan kit (option)
For heating/cooling versions (EKHBX), it is necessary to install the EKHBDP drain pan kit. For more information concerning the drain pan kit, refer to
"Installation of the EKHBDP drain pan kit (only for EKHBX models)" on page 13.
Solar kit for domestic hot water tank (option)
For information concerning the EKSOLHW solar kit, refer to the installation manual of that kit.
Digital I/O PCB kit (option)
An optional EKRP1HB digital I/O PCB can be connected to the indoor unit and allows:
remote alarm output heating/cooling ON/OFF output bivalent operation (permission signal for the auxiliary boiler)
Refer to the operation manual of the indoor unit and to the installation manual of the digital I/O PCB for more information.
Refer to the wiring diagram or connection diagram for connecting this PCB to the unit.
Remote thermostat kit (option)
An optional room thermostat EKRTW, EKRTWA, or EKRTR can be connected to the indoor unit. Refer to the installation manual of the room thermostat for more information.
Possible options
EKBPHT08 EKBPHT08BA
EKHBH/XE008 AA EKHBH/XE008 BA
Possible Not allowed Possible Possible

Scope of this manual

This installation manual describes the procedures for handling, installing and connecting all EKHBH/X indoor unit models.
NOTE
Installation of the ERHQ or ERLQ heat pump outdoor unit is described in the outdoor unit installation manual.
Operation of the indoor unit is described in the indoor unit operation manual.
Model identification
Indoor unit
EK HB XE 008 AA 3 V3
Backup heater nominal voltage: V3 = 1P, 230 V
Backup heater capacity (kW)
Series
Indication of heating/cooling capacity (kW)
XE = heating and cooling, HE = heating only
Hydro box
European kit
(a) For exact values, refer to "Technical specifications" on page 38.
(a)
Drain pan kit (optional)
EK HB DP 150
Drain pan
Hydro box
European kit
A
CCESSORIES

Accessories supplied with the indoor unit

See figure 1
Installation manual Operation manual Shut-off valve Wiring diagram sticker (inside indoor unit cover) Indoor unit cover fixing screw
Installation manual
2
Indoor unit for air to water heat pump system
EKHBH/XE008BA
4PW56303-1A
S
AFETY
The precautions listed here are divided into the following two types. Both cover very important topics, so be sure to follow them carefully.
Meanings of DANGER , WARNING , CAUTION and NOTE symbols.
CONSIDERATIONS
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE
Indicates situations that may result in equipment or property-damage accidents only.
Danger
Before touching electric terminal parts, turn off power switch. When service panels are removed, live parts can be easily
touched by accident. Never leave the unit unattended during installation or servicing
when the service panel is removed. Do not touch water pipes during and immediately after operation
as the pipes may be hot. Your hand may suffer burns. To avoid injury, give the piping time to return to normal temperature or be sure to wear proper gloves.
Do not touch any switch with wet fingers. Touching a switch with wet fingers can cause electrical shock.
Before touching electrical parts, turn off all applicable power supply.
Warning
Tear apart and throw away plastic packaging bags so that children will not play with them.
Children playing with plastic bags face danger of death by suffocation.
Safely dispose of packing materials. Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
Do not touch the internal parts (pump, backup heater, etc.) during and immediately after operation.
Your hands may suffer burns if you touch the internal parts. To avoid injury, give the internal parts time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
Caution
Earth the unit. Earthing resistance should be according to local and national
regulations. Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire. Incomplete earthing may cause electric shocks.
Gas pipe. Ignition or explosion may occur if the gas leaks.
Water pipe. Hard vinyl tubes are not effective earths.
Lightning conductor or telephone earth wire. Electric potential may rise abnormally if struck by a lightning bolt.
Install the power wire at least 1 meter away from televisions or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
Do not rinse the unit. This may cause electric shocks or fire. Do not install the unit in places such as the following:
Where there is mist of mineral oil, oil spray or vapour. Plastic parts may deteriorate, and cause them to fall out or water to leak.
Where corrosive gas, such as sulphurous acid gas, is produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
Where there is machinery which emits electromagnetic waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
Where flammable gases may leak, where carbon fibre or ignitable dust is suspended in the air or where volatile flammables, such as thinner or gasoline, are handled. Such gases may cause a fire.
Where the air contains high levels of salt. Where voltage fluctuates a lot, such as that in factories. In vehicles or vessels. Where acidic or alkaline vapour is present.
EKHBH/XE008BA
Indoor unit for air to water heat pump system
4PW56303-1A
Installation manual
3
T
YPICAL
APPLICATION
EXAMPLES

Application 2

1
6
2
7
3
4
T
5
The application examples given below are for illustration purposes only.

Application 1

Space heating only application with the room thermostat connected to the indoor unit.
T
5 64321
7
Outdoor unit Indoor unit Heat exchanger Pump Shut-off valve
FHL1..3 Floor heating loop
Pump operation and space heating
When the room thermostat (T) is connected to the indoor unit, the pump (4) will operate when there is a heating request from the room thermostat, and the outdoor unit will start operating to achieve the target leaving water temperature as set on the user interface.
When the room temperature is above the thermostat set point, the outdoor unit and pump will stop operating.
Make sure to connect the thermostat wires to the correct terminals (see "Connection of the thermostat cable" on
page 18) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
on page 20).
FHL1
FHL2
FHL3
Collector (field supply) Shut-off valve
Room thermostat (optional)
Space heating only application without room thermostat connected to the indoor unit. The temperature in each room is controlled by a valve on each water circuit. Domestic hot water is provided through the domestic hot water tank which is connected to the indoor unit.
54321
8 6
T1
T2M3T3
M
M1
M2
121011
7
1 Outdoor unit 10 Domestic hot water tank 2 Indoor unit 3 Heat exchanger 11 Booster heater 4 Pump 12 Heat exchanger coil 5 Shut-off valve FHL1..3 Floor heating loop 6 Collector (field supply) T1..3 Individual room 7 Shut-off valve 8 Motorised 3-way valve
(delivered with domestic hot water tank)
9 By-pass valve
(field supply)
FHL1
FHL2
(optional)
thermostat (optional)
M1..3 Individual motorised
valve to control loop FHL1 (field supply)
9
FHL3
Pump operation
With no thermostat connected to the indoor unit (2), the pump (4) can be configured to operate either as long as the indoor unit is on, or until the required water temperature is reached.
NOTE
Details on pump configuration can be found under
"Pump operation configuration" on page 21.
Installation manual
4
Space heating
The outdoor unit (1) will operate to achieve the target leaving water temperature as set on the user interface.
NOTE
When circulation in each space heating loop (FHL1..3) is controlled by remotely controlled valves (M1..3), it is important to provide a by-pass valve (9) to avoid the flow switch safety device from being activated.
The by-pass valve should be selected as such that at all time the minimum water flow as mentioned under
"Water pipework" on page 14 is guaranteed.
It is recommended to select a pressure difference controlled by-pass valve.
Indoor unit for air to water heat pump system
EKHBH/XE008BA
4PW56303-1A
Domestic water heating
When domestic water heating mode is enabled (either manually by the user, or automatically through a schedule timer) the target domestic hot water temperature will be achieved by a combination of the heat exchanger coil and the electrical booster heater.
When the domestic hot water temperature is below the user configured set point, the 3-way valve will be activated to heat the domestic hot water by means of the heat pump. In case of large domestic hot water demand or a high domestic hot water temperature setting, the booster heater (11) can provide auxiliary heating.
NOTE
The indoor unit can be configured so that at low outdoor temperatures the domestic hot water is exclusively heated by the booster heater. This assures that the full capacity of the heat pump is available for space heating.
Details on domestic hot water tank configuration for low outdoor temperatures can be found under "Field
settings" on page 22, field settings [5-02] to [5-04].

Application 3

Space cooling and heating application with the room thermostat set for heating/cooling connected to the indoor unit. Heating is provided
through floor heating loops and fan coil units. Cooling is provided through the fan coil units only. Domestic hot water is provided through the domestic hot water tank which is connected to the indoor unit.
Pump operation and space heating and cooling
According to the season, the customer will select cooling or heating on the room thermostat (T). This selection is not possible by operating the user interface.
When space heating/cooling is requested by the room thermostat (T), the pump will start operating and the indoor unit (2) will switch to "heating mode"/"cooling mode". The outdoor unit (1) will start operating to achieve the target leaving hot/cold water temperature.
In case of cooling mode, the 2-way valve (13) will close as to prevent cold water running through the floor heating loops (FHL).
NOTE
Make sure to connect the thermostat wires to the correct terminals (see "Connection of the thermostat
cable" on page 18) and to configure the DIP switch
toggle switches correctly (see "Room thermostat
installation configuration" on page 20).
NOTE
Wiring of the 2-way valve (13) is different for a NC (normal closed) valve and a NO (normal open) valve! Make sure to connect to the correct terminal numbers as detailed on the wiring diagram.
The ON/OFF setting of the heating/cooling operation is done by the room thermostat and cannot be done by the user interface on the indoor unit.
Domestic water heating
Domestic water heating is as described under "Application 2" on
page 4.
6
T
54321
8 13
M M
7
1 Outdoor unit 10 Domestic hot water tank 2 Indoor unit 3 Heat exchanger 11 Booster heater 4 Pump 12 Heat exchanger coil 5 Shut-off valve 13 Motorised 2-way valve 6 Collector (field supply) 7 Shut-off valve FCU1..3 Fan coil unit (optional) 8 Motorised 3-way valve
(delivered with domestic hot water tank)
11 12
FHL1..3 Floor heating loop
T Room thermostat with
FCU1
FCU2
FCU3
FHL1
FHL2
FHL3
10
(optional)
(field supply)
heating/cooling switch (optional

Application 4

Space cooling and heating application without the room thermostat connected to the indoor unit, but with the heating only room
thermostat (set heating only) controlling the floor heating and the heating/cooling thermostat (set heating/cooling) controlling the fan coil units. Heating is provided through floor heating loops and fan coil units. Cooling is provided through the fan coil units only.
9
6
T4
T5
FCU2
6
FHL2
T6
FCU3
FHL3
FCU1
T
54321
7
13M14
M
FHL1
EKHBH/XE008BA
Indoor unit for air to water heat pump system
4PW56303-1A
Installation manual
5
1 Outdoor unit 14 Motorised 2-way valve for 2 Indoor unit 3 Heat exchanger 4 Pump FCU1..3 Fan coil unit with 5 Shut-off valve 6 Collector (field supply) FHL1..3 Floor heating loop 7 Shut-off valve T Heating only room 9 By-pass valve (field
supply) T4..6 Individual room
13 Motorised 2-way valve
to shut off the floor heating loops during cooling operation (field supply)
activation of the room thermostat (field supply)
thermostat (optional)
thermostat (optional)
thermostat for fan coil heated/cooled room (optional)
Pump operation
With no thermostat connected to the indoor unit (2), the pump (4) can be configured to operate either as long as the indoor unit is on, or until the required water temperature is reached.
NOTE
Details on pump configuration can be found under
"Pump operation configuration" on page 21.
Space heating and cooling
According to the season, the customer will select heating or cooling through the user interface on the indoor unit.
The outdoor unit (1) will operate in heating mode or cooling mode to achieve the target leaving water temperature.
With the unit in heating mode, the 2-way valve (13) is open. Hot water is provided to both the fan coil units and the floor heating loops.
With the unit in cooling mode, the 2-way valve (13) is closed to prevent cold water running through the floor heating loops (FHL).
When closing several loops in the system by remotely controlled valves, it might be required to install a by-pass valve (9) to avoid the flow switch safety device from being activated. See also "Application 2" on page 4.

Application 5

Space heating with an auxiliary boiler (alternating operation)
Space heating application by either the Daikin indoor unit or by an auxiliary boiler connected in the system. The decision whether either the EKHB* indoor unit or the boiler will operate can be achieved by an auxiliary contact or an EKHB* indoor controlled contact.
The auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. See
"Field wiring configuration A" on page 7.
The EKHB* indoor unit controlled contact (also called ’permission signal for the auxiliary boiler") is determined by the outdoor temperature (thermistor located at the outdoor unit). See "Field wiring
configuration B" on page 7.
Bivalent operation is only possible for space heating operation, not for the domestic water heating operation. Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the Daikin indoor unit.
The auxiliary boiler must be integrated in the piping work and in the field wiring according to the illustrations below.
CAUTION
Be sure that the boiler and the integration of the boiler in the system is in accordance with relevant European and national regulations.
Daikin can not be put responsible for incorrect or unsafe situations in the boiler system.
54321 8 18
M
617
Wiring of the 2-way valve (13) is different for a NC (normal closed) valve and a NO (normal open) valve! Make sure to connect to the correct terminal numbers as detailed on the wiring diagram.
The ON/OFF setting of the heating/cooling operation is done by the user interface on the indoor unit.
16 17157
10
11
FHL1
FHL2
12
1 Outdoor unit 11 Heat exchanger coil 2 Indoor unit 12 Domestic hot water tank 3 Heat exchanger 4 Pump 15 Boiler (field supply) 5 Shut-off valve 16 Aquastat valve 6 Collector (field supply) 7 Shut-off valve 17 Shut-off valve 8 Motorised 3-way valve
(delivered with the domestic hot water tank)
FHL1...3 Floor heating loop
(optional)
(field supply)
(field supply)
18 Non-return valve
(field supply)
(field supply)10 Booster heater
FHL3
Installation manual
6
Indoor unit for air to water heat pump system
EKHBH/XE008BA
4PW56303-1A
Field wiring configuration A
L
H
Com
EKHB*
EKHB*/auto
Boiler thermostat input
A Auxiliary contact (normal closed) H Heating demand room thermostat (optional) K1A Auxiliary relay for activation of EKHB* unit (field
K2A Auxiliary relay for activation of boiler (field supply)
/ Boiler
N
A
K1A
K2A
Boiler thermostat input
supply)
X2M
123 4
K1A
Boiler
thermostat input
Y
X
K2A
Field wiring configuration B
EKHB*
X2M
12
3 4
K1A
Com
HC
EKRTR*
Boiler thermostat input
C Cooling demand room thermostat (optional) H Heating demand room thermostat (optional) Com Common room thermostat (optional) K1A Auxiliary relay for activation of bolier unit
KCR Permission signal for the auxiliary boiler
EKHB*
X2M
3 4
12
K1A
Com
H
C
EKRTW*
Boiler thermostat input
(field supply)
EKRP1HB
KCR
X1 X2
K1A
Y
X
Boiler
thermostat input
Operation
Configuration A
When the room thermostat requests heating, either the EKHB* unit or the boiler starts operating, depending on the position of the auxiliary contact (A).
Configuration B
When the room thermostat requests heating, either the EKHB* unit or the boiler starts operating, depending on the outdoor temperature (status of "permission signal for the auxiliary boiler").
When the permission is given towards the boiler, the space heating operation by the EKHB* unit will be automatically switched off.
For more details see field setting [C-02~C-04].
NOTE
Configuration A
Make sure that auxiliary contact (A) has sufficient differential or time delay so as to avoid frequent changeover between the EKHB* unit and the boiler. If the auxiliary contact (A) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun.
Configuration B
Make sure that the bivalent hysteresis [C-04] has sufficient differential to avoid frequent changeover between the EKHB* unit and the boiler. As the outdoor temperature is measured via the outdoor unit, air thermistor make sure to install the outdoor unit in the shade, so that it is not influenced by the sun.
Frequent switching may cause corrosion of the boiler in an early stage. Contact the manufacturer of the boiler.
During heating operation of the EKHB* unit, the unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature.
During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature set point on the boiler controller above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Daikin indoor unit.
NOTE
Make sure to configure the DIP switch SS2-3 on the PCB of the EKHB* switchbox correctly. Refer to "Room
thermostat installation configuration" on page 20.
For configuration B: Make sure to configure the field settings [C-02, C-03 and C-04] correctly. Refer to
"Bivalent operation" on page 28.
CAUTION
Make sure that return water to the EKHB* heat exchanger never exceeds 55°C.
For this reason, never put the target leaving water temperature set point on the boiler controller above 55°C and install an aquastat
(a)
valve in the return water flow of
the EKHB* unit. Make sure that the non-return valves (field supply) are
correctly installed in the system. Make sure that the room thermostat (th) is not frequently
turned ON/OFF. Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
(a) The aquastat valve must be set for 55°C and must operate to close the return
water flow to the unit when the measured temperature exceeds 55°C. When the temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the EKHB* unit again.
EKHBH/XE008BA
Indoor unit for air to water heat pump system
4PW56303-1A
Manual permission towards the EKHB* unit on the boiler. In case only the EKHB* unit should operate in space
heating mode, disable the bivalent operation via setting [C-02].
In case only the boiler should operate in space heating mode, increase the bivalent ON temperature [C-03] to 25°C.
Installation manual
7

Application 6

Space heating with room thermostat application through floor heating loops and fan coil units. The floor heating loops and fan coil units require different operating water temperatures.
The floor heating loops require a lower water temperature in heating mode compared to fan coil units. To achive these two set points, a mixing station is used to adapt the water temperature according to requirements of the floor heating loops. The fan coil units are directly connected to the indoor unit water circuit and the floor heating loops after the mixing station. The control of this mixing station is not done by the indoor unit.
The operation and configuration of the field water circuit is the responsibility of the installer.
Daikin only offers a dual set point control function. By this function two set points can be generated. Depending on the required water temperature (floor heating loops and/or fan coil units are required) first set point or second set point can be activated.
B
7
T1
T2
54321
8 9
1 Outdoor unit 8 Shut-off valve 2 Indoor unit 9 Mixing station (field supply) 3 Heat exchanger T1 Room thermostat for zone 4 Pump 5 Shut-off valve T2 Room thermostat for zone 6 Collector zone A
(field supply) FCU1..3 Fan coil unit (optional)
7 Collector zone B
(field supply)
FHL1...3 Floor heating loop
The advantage of the dual set point control is that the heat pump will/can operate at the lowest required leaving water temperature when only floor heating is required. Higher leaving water temperatures are only required in case fan coil units are operating. This results in a better performance of the heat pump.
FCU1
A
6
FHL1
A (optional)
B (optional)
(field supply)
FCU2
FHL2
FCU3
FHL3
Pump operation and space heating
When the room thermostat for the floor heating loop (T1) and the fan coil units (T2) are connected to the indoor unit, the pump (4) will operate when there is a request for heating from T1 and/or T2. The outdoor unit will start operating to achieve the target leaving water temperature. The target leaving water temperature depends on which room thermostat is requesting heating.
Set point Field setting Thermo status
Zone A First UI ON OFF ON OFF Zone B Second [7-03] OFF ON ON OFF Resulting water temperature UI [7-03] [7-03] — Result pump operation ON ON ON OFF
When the room temperature of both zones is above the thermostat set point, the outdoor unit and pump will stop operating.
NOTE
Make sure to connect the thermostat wires to the correct terminals (see "Overview of the indoor
unit" on page 9).
Make sure to configure the field settings [7-02], [7-03] and [7-04] correctly. Refer to "Dual set point
control" on page 26.
Make sure to configure the DIP switch SS2-3 on the PCB of the EKHBH switch box correctly. Refer to "Room thermostat installation configuration" on
page 20.
NOTE
The request signals for space heating can be implemented in two different ways (installer choice).
- Thermo ON/OFF signal from room thermostat
- Status signal (active/not active) from the
mixing station
It is the installers responsibility to make sure no unwanted situations can occur (e.g. too high water temperatures towards floor heating loops, etc.)
Daikin does not offer any type of mixing station. Dual set point control only provides the possibility to use two set points.
When only zone A request heating, zone B will be fed with water at a temperature equal to the first set point. This can lead to unwanted heating of zone B.
When only zone B request heating, the mixing station will be fed with water at a temperature equal to the second set point. Depending on the control of the mixing station, the floor heating loop can still receive water at a temperature equal to set point of the mixing station.
Be aware that the actual water temperature through the floor heating loops depends on the control and setting of the mixing station.
Installation manual
8
Indoor unit for air to water heat pump system
EKHBH/XE008BA
4PW56303-1A

OVERVIEW OF THE INDOOR UNIT

Opening the indoor unit

The front flap on the indoor unit cover gives access to the manometer and user interface.
The indoor unit cover can be removed by removing the 2 bottom screws and unhitching the cover.
DANGER
Do not touch water pipes during and immediately after operation as the pipes may be hot. Your hand may suffer burns. To avoid injury, give the piping time to return to normal temperature or be sure to wear proper gloves.
When service panels are removed, live parts can be easily touched by accident. Never leave the unit unattended during installation or servicing when the service panel is removed.
Make sure to fix the cover with the screws when installing the cover (screws are delivered as accessory).
Parts inside the unit can be hot.
To gain access to the switch box components – e.g. to connect the field wiring – the switch box service panel can be removed. Thereto, loosen the front screws and unhitch the switch box service panel.
WARNING
Switch off all power supply – i.e. outdoor unit power supply and backup heater and domestic hot water tank power supply (if applicable) – before removing the switch box service panel.
Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
Do not touch the internal parts (pump, backup heater, etc.) during and immediately after operation.
Your hands may suffer burns if you touch the internal parts. To avoid injury, give the internal parts time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
1
1
33
3
2
EKHBH/XE008BA
Indoor unit for air to water heat pump system
4PW56303-1A
Installation manual
9

Main components

20
19 18
17
3
16
14
13. Drain and fill valves
14. Water filter
The water filter removes dirt from the water to prevent damage to the pump or blockage of the evaporator. The water filter must
1
be cleaned on a regular base. See "Maintenance and service"
on page 33.
15. Manometer The manometer allows readout of the water pressure in the
water circuit.
16. Flow switch
2
The flow switch checks the flow in the water circuit and protects the heat exchanger against freezing and the pump against damage.
3
4
17. Pump The pump circulates the water in the water circuit.
18. Backup heater thermal protector The backup heater is equipped with a thermal protector. The
thermal protector is activated when the temperature becomes
5 6
too high.
19. Backup heater thermal fuse The backup heater is equipped with a thermal fuse. The thermal
fuse is blown when the temperature becomes too high (higher than the backup heater thermal protector temperature).
20. Pressure relief valve
3
7 15
The pressure relief valve prevents excessive water pressure in the water circuit by opening at 3 bar and discharging some water.
21. Pressure relief valve hose The actual outlet of the pressure relief valve. Make sure to
3
provide a proper drain.
21
13
10
12
1. Air purge valve Remaining air in the water circuit will be automatically removed
via the air purge valve.
2. Backup heater The backup heater consists of an electrical heating element in
the backup heater vessel that will provide additional heating capacity to the water circuit if the heating capacity of the outdoor unit is insufficient due to low outdoor temperatures.
3. Temperature sensors Four temperature sensors determine the water and refrigerant
temperature at various points in the water circuit.
4. Switch box The switch box contains the main electronic and electrical parts
of the indoor unit.
5. Heat exchanger
6. Expansion vessel (10 l)
7. User interface
The user interface allows the installer and user to set up, use and maintain the unit.
8. Refrigerant liquid connection
9. Refrigerant gas connection
10. Shut-off valves (accessory)
The shut-off valves on the water inlet connection and water outlet connection allow isolation of the indoor unit water circuit side from the residential water circuit side. This facilitates draining and filter replacement of the indoor unit.
11. Water inlet connection
12. Water outlet connection
8 9 13 10
11
Installation manual
10
Indoor unit for air to water heat pump system
EKHBH/XE008BA
4PW56303-1A

Switch box main components

14
TR1
K1M
K5M
12. X9A socket The X9A socket receives the thermistor connector (only for
installations with domestic hot water tank).
13. Fuse FU2 (in line fuse)
14. Tr ansformer TR1
1
15. A4P Digital I/O PCB (only for installations with solar kit or digital I/O
PCB kit).
12
11
10
15
X9A
NOTE
2 3
The electrical wiring diagram can be found on the inside of the switch box cover.

Functional diagram

X13A
SS2
FU1
9
6
A1P
A4P
X2M X4M
6
X1M
K3M
F2B F3B F1B
X3M
FU2
4 5
5
13
8
8
7
32 4 8
R1T
t >
R3T
t >
5 6 7
H
O
2
R2T
t >
R4T
t >
9
10
11
1. Backup heater contactors K1M and K5M.
2. Main PCB
The main PCB (Printed Circuit Board) controls the functioning of the unit.
3. Booster heater contactor K3M (only for installations with domestic hot water tank)
4. Booster heater circuit breaker F2B (only for installations with domestic hot water tank)
The circuit breaker protects the booster heater in the domestic
hot
water tank against overload or short circuit.
5. Backup heater circuit breaker F1B, F3B The circuit breaker protects the backup heater electrical circuit
against overload or short circuit.
6. Ter minal blocks The terminal blocks allow easy connection of field wiring.
7. Cable tie mountings The cable tie mountings allow to fix the field wiring with cable
ties to the switch box to ensure strain relief.
8. Ter minal blocks X3M, X4M (only for installations with domestic hot water tank)
9. PCB fuse FU1
10. DIP switch SS2
The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters. See "DIP switch settings
overview" on page 20.
11. X13A socket The X13A socket receives the K3M connector (only for
installations with domestic hot water tank).
12131
1 Outdoor unit 10 Shut-off valve water outlet 2 Indoor unit
3 Expansion vessel 11 Shut-off valve water inlet with 4 Manometer 5 Air purge valve 12 Filter 6 Pressure relief valve 13 Heat exchanger 7 Backup heater R1T
9 Flow switch
with drain valve (field installation)
drain valve (field installation)
R2T
Temperature sensors8 Pump
R3T R4T
EKHBH/XE008BA
Indoor unit for air to water heat pump system
4PW56303-1A
Installation manual
11
Loading...
+ 29 hidden pages