1.1About the documentation .............................................................................................................................................. 4
1.1.1Meaning of warnings and symbols ................................................................................................................4
1.2For the user..................................................................................................................................................................... 5
2 About this document7
3 About the system8
3.1Components in a typical system layout..........................................................................................................................8
4.2The user interface at a glance ........................................................................................................................................ 10
4.3.1Using home pages .......................................................................................................................................... 12
4.3.2Using the menu structure .............................................................................................................................. 12
4.4.1About space heating/cooling control............................................................................................................. 14
4.4.2Setting the space operation mode................................................................................................................. 14
4.4.3Determining which temperature control you are using ................................................................................ 16
4.4.4Room thermostat control - About room thermostat control........................................................................ 17
4.4.5Room thermostat control - Using the room temperature home pages ....................................................... 18
4.4.6Room thermostat control - Using the leaving water temperature home pages .......................................... 22
4.4.7Leaving water temperature control - About leaving water temperature control ........................................ 24
4.4.8Leaving water temperature control - Using leaving water temperature control according to a schedule . 25
4.4.9Leaving water temperature control - Using leaving water temperature control NOT according to a
4.4.10External room thermostat control - About external room thermostat control............................................ 25
4.4.11External room thermostat control - Using external room thermostat control ............................................ 26
4.5Domestic hot water control............................................................................................................................................ 26
4.5.1About domestic hot water control................................................................................................................. 26
4.5.2Instant DHW (no tank installed) ..................................................................................................................... 26
4.6.4Reading out information ................................................................................................................................ 35
4.6.5Configuring date, time, units of measurement, contrast and backlight ....................................................... 36
4.6.6Configuring user profile and home pages...................................................................................................... 36
4.6.7Locking and unlocking buttons and functions ............................................................................................... 37
4.7Preset values and schedules........................................................................................................................................... 38
4.7.2Using and programming schedules................................................................................................................ 39
4.7.3Schedules: Example ........................................................................................................................................ 40
4.7.4Predefined schedules: Room temperature + leaving water temperature (main) ........................................ 41
4.7.5Predefined schedules: Leaving water temperature (additional)................................................................... 42
4.8.1To set the weather dependent settings......................................................................................................... 43
4.9Menu structure: Overview user settings........................................................................................................................ 44
4.10 Installer settings: Tables to be filled in by installer ........................................................................................................ 45
4.10.2Space heating/cooling control ....................................................................................................................... 46
4.10.3Domestic hot water control [A.4] .................................................................................................................. 46
4.10.4Contact/helpdesk number [6.3.2].................................................................................................................. 46
User reference guide
2
5 Setting the energy prices47
5.1To set the gas price......................................................................................................................................................... 47
5.2To set the electricity price .............................................................................................................................................. 47
5.3To set the electricity price schedule timer..................................................................................................................... 48
5.4About energy prices in case of an incentive per kWh renewable energy ..................................................................... 48
5.4.1To set the gas price in case of an incentive per kWh renewable energy...................................................... 48
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
Table of contents
5.4.2To set the electricity price in case of an incentive per kWh renewable energy ........................................... 48
6.1To view the energy statistics .......................................................................................................................................... 50
7 Energy saving tips51
8 Maintenance and service52
8.1Overview: Maintenance and service .............................................................................................................................. 52
8.2To find the contact/helpdesk number............................................................................................................................ 52
9.2To check the error history .............................................................................................................................................. 53
9.3To check the warning history.......................................................................................................................................... 53
9.4Symptom: You are feeling too cold (hot) in your living room........................................................................................ 53
9.5Symptom: The water at the tap is too cold.................................................................................................................... 54
▪ The original documentation is written in English. All other languages are
translations.
▪ The precautions described in this document cover very important topics, follow
them carefully.
▪ The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised
installer.
1.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or
cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
DANGER: RISK OF POISONING
Indicates a situation that could result in poisoning.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: PROTECT AGAINST FROST
Indicates a situation that could result in equipment or property damage.
User reference guide
4
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
SymbolExplanation
Before installation, read the installation and operation
manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the
service manual.
For more information, see the installer and user reference
guide.
The unit contains rotating parts. Be careful when servicing or
inspecting the unit.
Symbols used in the documentation:
SymbolExplanation
Indicates a figure title or a reference to it.
1 | General safety precautions
1.2 For the user
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
WARNING
If you are NOT sure how to operate the unit, contact your
installer.
WARNING
This appliance can be used by children aged from 8 years
and above and persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge if
they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the
hazards involved.
Cleaning and user maintenance SHALL NOT be made by
children without supervision.
User reference guide
5
1 | General safety precautions
▪ Units are marked with the following symbol:
This means that electrical and electronic products may NOT be mixed with
unsorted household waste. Do NOT try to dismantle the system yourself: the
dismantling of the system, treatment of the refrigerant, of oil and of other parts
must be done by an authorized installer and must comply with applicable
legislation.
WARNING
To prevent electrical shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet hands.
▪ Do NOT place any objects containing water on the unit.
CAUTION
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
Units must be treated at a specialized treatment facility for reuse, recycling and
recovery. By ensuring this product is disposed of correctly, you will help to
prevent potential negative consequences for the environment and human
health. For more information, contact your installer or local authority.
▪ Batteries are marked with the following symbol:
This means that the batteries may NOT be mixed with unsorted household
waste. If a chemical symbol is printed beneath the symbol, this chemical symbol
means that the battery contains a heavy metal above a certain concentration.
Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility for reuse. By
ensuring waste batteries are disposed of correctly, you will help to prevent
potential negative consequences for the environment and human health.
User reference guide
6
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
2 About this document
1
20.0°C >
18.0°C >
22.0°C >
24.0°C >
7.4.1.1Room temperature
Comfort (heating)
Eco (heating)
Comfort (cooling)
Eco (cooling)
Select
Scroll
Thank you for purchasing this product. Please:
▪ Read the documentation carefully before operating the user interface to ensure
the best possible performance.
▪ Request the installer to inform you about the settings that he used to configure
your system. Check if he has filled in the installer settings tables. If not, request
him to do so.
▪ Keep the documentation for future reference.
Target audience
Endusers
Documentation set
This document is part of a documentation set. The complete set consists of:
▪ General safety precautions:
- Safety instructions that you must read before operating your system
- Format: Paper (in the box of the indoor unit)
2 | About this document
▪ Operation manual:
- Quick guide for basic usage
- Format: Paper (in the box of the indoor unit)
▪ User reference guide:
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Latest revisions of the supplied documentation may be available on the regional
Daikin website or via your installer.
The original documentation is written in English. All other languages are
translations.
Available screens
Depending on your system layout and installer configuration, not all screens in this
document may be available on your user interface.
Installer settings tableOverview of installer settings
User reference guide
9
4 | Operation
a
ef
b
d
c
4.2 The user interface at a glance
4.2.1 Buttons
a HOME PAGES
▪ Switches between home pages (when you are on a home page).
▪ Goes to the default home page (when you are in the menu structure).
b MALFUNCTION INFORMATION
If a malfunction occurs, is displayed on the home pages. Press to display
more information about the malfunction.
c ON/OFF
Turns ON or OFF one of the controls (room temperature, leaving water
temperature, DHWtank temperature).
d MENU STRUCTURE/BACK
▪ Opens the menu structure (when you are on a home page).
▪ Goes up a level (when you are navigating through the menu structure).
▪ Goes back 1step (example: when you are programming a schedule in the
menu structure).
e NAVIGATING/CHANGING SETTINGS
▪ Navigates the cursor on the display.
▪ Navigates through the menu structure.
▪ Changes settings.
▪ Selects a mode.
f OK
▪ Confirms a selection.
▪ Enters a submenu in the menu structure.
▪ Switches between displaying actual and desired values, or between
displaying actual and offset values (if applicable) on the home pages.
▪ Goes to the next step (when you are programming a schedule in the menu
structure).
▪ Enables you to activate or deactivate button lock if pressed for more than
5seconds on a home page.
▪ Enables you to activate or deactivate a function lock if pressed for more
than 5seconds in the main menu of the menu structure.
INFORMATION
If you press or while changing settings, the changes will NOT be applied.
User reference guide
10
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
4.2.2 Status icons
4 | Operation
IconDescription
Space operation mode = Heating.
Space operation mode = Cooling.
Heat pump (compressor) operation or boiler operation. This
symbol is related to the home page.
Desired room temperature = preset value (Comfort; daytime).
Desired room temperature = preset value (Eco; nighttime).
▪ On the room temperature home page: Desired room
temperature = according to the selected schedule.
▪ On the DHWtank temperature home page: DHWtank mode =
Scheduled mode.
DHWtank mode = Reheat mode.
DHWtank mode = Scheduled + reheat mode.
Domestic hot water operation.
Actual temperature.
Desired temperature.
At the next scheduled action, the desired temperature will
increase.
At the next scheduled action, the desired temperature will NOT
change.
At the next scheduled action, the desired temperature will
decrease.
The preset value (Comfort or Eco) or scheduled value is
temporarily overruled.
The DHWtank booster mode is active or ready to be activated.
Quiet mode is active.
Holiday mode is active or ready to be activated.
Button lock mode and/or function lock mode is active.
A malfunction occurred. Press to display more information
about the malfunction.
Weather-dependent mode is active.
User permission level = Installer.
Defrost/oil return mode is active.
Hot start mode is active.
User reference guide
11
4 | Operation
4.3 Basic usage
4.3.1 Using home pages
IconDescription
Emergency operation is active.
INFORMATION
When the gas boiler is in maintenance mode, a gas boiler test run is being performed
or changes to settings are being saved, the user interface displays Busy.
If this is the case, the user interface is temporarily disabled so as not to allow
interference with the actions the system is performing at that moment.
INFORMATION
Boiler operation does NOT necessarily imply burner operation. When a heating
demand is sent to the boiler, boiler operation ( ) is continuous, but the burner will
ONLY operate alternately.
About home pages
You can use the home pages to read out and change settings that are meant for
daily usage. What you can see and do on the home pages is described where
applicable. Depending on your system layout, the following home pages may be
possible:
▪ Room temperature (Room)
▪ Main leaving water temperature (LWT main)
▪ Additional leaving water temperature (LWT add)
▪ DHWtank temperature (Tank)
▪ Instant DHW (DHW)
To go to a home page
1Press .
Result: One of the home pages is displayed.
2Press again to display the next home page (if any).
4.3.2 Using the menu structure
About the menu structure
User reference guide
12
You can use the menu structure to read out and configure settings that are NOT
meant for daily usage. What you can see and do in the menu structure is described
where applicable. For an overview of the menu structure, see "4.9Menu structure:
Overview user settings"[444].
To go to the menu structure
1From a home page, press .
Result: The menu structure is displayed.
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
1
>
>
>
>
Select
Scroll
Set time/date
Holiday
Quiet mode
Operation mode
Select schedules
Information
Auto
Heating
To navigate in the menu structure
Use , , , , and .
4.3.3 Turning ON/OFF controls
About turning ON/OFF controls
Before you can control…You have to turn ON…
Room temperatureRoom temperature control (Room)
4 | Operation
Main (+ additional) leaving water
temperature
Main (+ additional) leaving water
temperature control (LWT main and
LWT add)
Main and additional leaving water
temperature control are always turned
ON or OFF together.
DHWtank temperatureDomestic hot water control (Tank)
Instant DHW temperatureInstant domestic hot water control
(DHW)
If you turn ON…Then…
Room temperature controlMain (+ additional) leaving water
temperature control is automatically
turned ON.
Main (+ additional) leaving water
temperature control
Room temperature control is NOT
automatically turned ON.
If you turn OFF…Then…
Room temperature controlMain (+ additional) leaving water
temperature control is NOT
automatically turned OFF.
Select which room temperature schedule you want to
Menu structure
use.
Program schedules.
Define preset values that are used by the room
temperature schedule, and when you change the
mode from scheduled to preset value.
See also:
▪ "4.4.5 Room thermostat control - Using the room temperature home
pages"[418]
▪ "To set the overrule period"[421]
▪ "4.7Preset values and schedules"[438]
Leaving water temperature of the main zone
To control the leaving water temperature of the main zone, you can do the
following:
You can…Location
Read out the desired leaving water temperature.Leaving water
Adjust the leaving water temperature.
temperature home page
(main)
Condition: Leaving water setpoint is NOT linked with
the room temperature setpoint.
Only change this if the desired room temperature
cannot be reached.
Define preset values.
Menu structure
Condition: Leaving water setpoint is linked with the
room temperature setpoint.
Only change this if the desired room temperature
cannot be reached.
See also:
▪ "4.4.6 Room thermostat control - Using the leaving water temperature home
pages"[422]
▪ "4.7Preset values and schedules"[438]
4.4.5 Room thermostat control - Using the room temperature home pages
Typical room temperature home pages
Depending on the user profile, the user interface gives you either a basic or a
detailed home page. To set the user profile, refer to "4.6.6Configuring user profile
and home pages"[436].
User profile = BasicUser profile = Detailed
User reference guide
18
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
To read out the actual and desired room temperature
20.0°C
Actual temperature
22.0°C
Desired temperature
1Go to the room temperature home page (Room).
Result: You can read out the actual temperature.
2Press .
Result: You can read out the desired temperature.
To temporarily overrule the room temperature schedule
1Go to the room temperature home page (Room).
2In the detailed home page (user profile = Detailed), select the scheduled
room temperature mode () by pressing or .
Result: The room temperature follows the scheduled value.
3Use or to adjust the temperature.
Result: The room temperature follows the manually adjusted value ( ), but will
return to the scheduled value at the next scheduled action.
To change the mode from scheduled to preset value
4 | Operation
Prerequisite: User profile = Detailed.
1Go to the room temperature home page (Room).
2Press or to select a preset value ( or ).
Result: The room temperature follows the preset value (Comfort or Eco),
but will return to the scheduled value after the overrule period
(=Temperature lock: 2/4/6/8 hours or permanent).
3If necessary, you can overrule the preset value by using or to adjust the
temperature.
Result: The room temperature follows the manually adjusted value ( ), but will
return to the scheduled value after the overrule period (= Temperaturelock: 2/4/6/8 hours or permanent).
Example: Temporarily overruling the schedule AND changing the mode to preset value
2At 20:00, go to the room temperature home page (Room).
3Press to select .
Result: The preset value (Comfort) will be used until 02:00. After that, the
schedule will be used again.
Usage example: You go away for a couple of hours
If you are in the following situation:
User reference guide
21
4 | Operation
15:20
35°C
LWT main
Desired temperature
Mon
15:20
35°C
17:30
Mon
Mon
Desired temperature
LWT main
15:20
45°C
Desired temperature
LWT add
Mon
15:20
45°C
17:30
Mon
Mon
LWT add
Desired temperature
4.4.6 Room thermostat control - Using the leaving water temperature home pages
▪ You are using the following room temperature schedule:
- 08:00 preset value (Comfort) = 20°C
- 23:00 preset value (Eco) = 18°C
▪ At 14:00, you go away for 3 hours.
Then you can do the following:
1Set the overrule period (Temperature lock) to 2hours.
2Go to the room temperature home page (Room).
3Press to select .
Result: For the next 2hours, the room will NOT be heated to the scheduled 20°C,
but to the preset value (Eco = 18°C). After 2hours, the room will heat up again to
the scheduled 20°C.
Advantage:
You save energy because you do NOT heat the room unnecessary, and by the time
you come home the room is warm again.
INFORMATION
The leaving water is the water that is sent to the heat emitters. The desired leaving
water temperature is set by your installer in accordance with the heat emitter type.
Example: Underfloor heating is designed for lower leaving water temperature than
radiators and heatpump convectors and/or fan coil units. You only have to adjust
leaving water temperature settings in case of problems.
Typical leaving water temperature home pages
Main zone:
User profile = BasicUser profile = Detailed
Additional zone:
User profile = BasicUser profile = Detailed
User reference guide
22
To read out the desired leaving water temperature (main + additional)
Go to the leaving water temperature home page (LWT main or LWT add).
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
4 | Operation
35°C 37°C
45°C 47°C
To adjust/overrule the leaving water temperature (NOT linked to room temperature setpoint)
INFORMATION
To see if the leaving water temperature setpoint is linked to the room temperature
setpoint, see "4.4.3Determining which temperature control you are using"[416].
To adjust the leaving water temperature (main)
1Go to the main leaving water temperature home page (LWT main).
2Press or to adjust. Example:
INFORMATION
In case of weather dependency, an offset value can be modified.
To adjust the leaving water temperature (additional)
1Go to the additional leaving water temperature home page (LWT add).
2Press or to adjust. Example:
INFORMATION
In case of weather dependency, an offset value can be modified.
To adjust/overrule the leaving water temperature (linked to room temperature setpoint)
INFORMATION
To see if the leaving water temperature setpoint is linked to the room temperature
setpoint, see "4.4.3Determining which temperature control you are using"[416].
To set leaving water temperature preset values (main)
INFORMATION
You cannot adjust/overrule the leaving water temperature (main) for room
thermostat control with linked leaving water temperatures. However if necessary,
you can adjust the desired leaving water temperature (main) by adjusting preset
values.
INFORMATION
Adjusting the leaving water temperature is permanent unless the leaving water
temperature is according to a schedule. In that case the overruling is valid until the
next scheduled action.
1Go to [7.4.2]: > User settings > Preset values > LWT main.
2Set the Preset values according to following graph.
Example: Room thermostat comfort temperature will correspond with leaving
water comfort temperature.
User reference guide
23
4 | Operation
T
l
T
r
45°C 47°C
▪ Tr: Room temperature
▪ Tl: Leaving water temperature
3Press or to adjust/overrule.
To adjust the leaving water temperature (additional)
1Go to the additional leaving water temperature home page (LWT add).
2Press or to adjust. Example:
INFORMATION
In case of weather dependency, an offset value can be modified.
4.4.7 Leaving water temperature control - About leaving water temperature control
Leaving water temperature control means that you only control the leaving water
temperature. To control the leaving water temperature, you can do the following:
You can…Location
Read out the desired leaving water temperature
(main + additional).
▪ Adjust/overrule the leaving water temperature
(main).
▪ Adjust the leaving water temperature (additional).
Select which leaving water temperature schedule
(main + additional) you want to use.
Program leaving water temperature schedule (main +
additional).
Define preset values that are used by the leaving
water temperature schedule (main).
See also:
▪ "4.4.6 Room thermostat control - Using the leaving water temperature home
pages"[422]
Leaving water
temperature home pages
(main + additional)
Menu structure
User reference guide
24
▪ "4.7Preset values and schedules"[438]
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
4 | Operation
35°C 37°C
45°C 47°C
35°C 37°C
45°C 47°C
4.4.8 Leaving water temperature control - Using leaving water temperature control according to
a schedule
To set leaving water temperature preset values (main)
INFORMATION
Adjusting the leaving water temperature is permanent unless the leaving water
temperature is according to a schedule. In that case the overruling is valid until the
next scheduled action.
1Go to [7.4.2]: > User settings > Preset values > LWT main.
2Press or to adjust. Example:
To adjust the leaving water temperature (additional)
1Go to the additional leaving water temperature home page (LWT add).
2Press or to adjust. Example:
INFORMATION
In case of weather dependency, an offset value can be modified.
4.4.9 Leaving water temperature control - Using leaving water temperature control NOT
according to a schedule
To adjust the leaving water temperature (main)
1Go to the main leaving water temperature home page (LWT main).
2Press or to adjust. Example:
To adjust the leaving water temperature (additional)
1Go to the additional leaving water temperature home page (LWT add).
2Press or to adjust. Example:
INFORMATION
In case of weather dependency, an offset value can be modified.
4.4.10 External room thermostat control - About external room thermostat control
External room thermostat control means that you control the following:
▪ Room temperature on the external thermostat control
▪ Leaving water temperature on the user interface (Daikin)
To control the leaving water temperature, you can do the following:
User reference guide
25
4 | Operation
35°C 37°C
45°C 47°C
4.4.11 External room thermostat control - Using external room thermostat control
You can…Location
Read out the desired leaving water temperature.Leaving water
Adjust the desired leaving water temperature.
Only change this if the desired room temperature
cannot be reached.
See also: "4.4.6 Room thermostat control - Using the leaving water temperature
home pages"[422]
To adjust the leaving water temperature (main)
1Go to the main leaving water temperature home page (LWT main).
2Press or to adjust. Example:
To adjust the leaving water temperature (additional)
1Go to the additional leaving water temperature home page (LWT add).
temperature home pages
(main + additional)
2Press or to adjust. Example:
INFORMATION
In case of weather dependency, an offset value can be modified.
4.5 Domestic hot water control
NOTICE
Disinfection mode. Even if you turn OFF domestic hot water operation via the
DHWtank temperature home page (Tank), disinfection mode will remain active.
4.5.1 About domestic hot water control
Your system layout may or may not contain a domestic hot water tank. When no
tank is installed, the boiler provides domestic hot water instantly. When, on the
contrary, a tank is installed, domestic hot water control is different depending on
the DHW tank mode set by the installer:
▪ Reheat mode
▪ Scheduled mode
User reference guide
26
▪ Scheduled + reheat mode
4.5.2 Instant DHW (no tank installed)
Not applicable for Switzerland
When there is a demand for hot water tapping, the boiler provides DHW instantly.
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
Using the instant DHW home page
44°C
01:03
Tue
DHW
Desired temperature
01:03
44°C
Tue
DHW
Desired temperature
t
60°C
00:0007:00
50°C
15°C
40°C
14:0021:00
1
2
3
4
T
t
To adjust the instant DHW temperature
4.5.3 Tank
4 | Operation
Not applicable for Switzerland
Depending on the user profile, the user interface gives you either a basic or a
detailed home page.
User profile = BasicUser profile = Detailed
1Go to the instant DHW home page.
2Press or to adjust the instant DHW temperature (DHW).
The instant DHW set point temperature may NOT be below 40°C.
Reheat mode
The following modes are only applicable if a tank is installed and are set by the
installer.
To determine which DHWtank mode you are using (method1)
Check the installer settings table filled in by the installer.
To determine which DHWtank mode you are using (method 2)
Prerequisite: User profile = Detailed.
1Go to the DHWtank temperature home page (Tank).
2Check which icons are displayed:
If… is displayedThen the DHWtank mode =…
Reheat mode
Scheduled mode
Scheduled + reheat mode
In reheat mode ( ),the DHWtank continuously heats up to the temperature shown
on the DHWtank temperature home page (example: 50°C).
When the DHW tank mode is reheat, the risk for capacity shortage and comfort
problem is significant. In case of frequent reheat operation, space heating/cooling
function is regularly interrupted.
Scheduled mode
In scheduled mode ( ), the DHW tank produces hot water corresponding to a
schedule. The best time to allow the tank to produce hot water is at night, because
the space heating demand is lower.
Example:
TtDomestic hot water tank temperature
t Time
▪ Initially, the DHW tank temperature is the same as the temperature of the
domestic water entering the DHWtank (example: 15°C).
▪ At 00:00 the DHW tank is programmed to heat up the water to a preset value
(example: Storage comfort = 60°C).
▪ During the morning, you consume hot water and the DHW tank temperature
decreases.
▪ At 14:00 the DHW tank is programmed to heat up the water to a preset value
(example: Storage eco = 50°C). Hot water is available again.
▪ During the afternoon and evening, you consume hot water again and the
DHWtank temperature decreases again.
▪ At 00:00 the next day, the cycle repeats.
Scheduled + reheat mode
In scheduled + reheat mode ( ), the domestic hot water control is the same as in
scheduled mode. However, when the DHWtank temperature drops below a preset
value (=reheat tank temperature – hysteresis value; example: 35°C), the DHWtank
heats up until it reaches the reheat set point (example: 45°C). This ensures that a
minimum amount of hot water is available at all times.
Example:
User reference guide
28
TtDHWtank temperature
t Time
60°C Storage comfort
50°C Storage eco
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
45°C Reheat
15:20
60°C
Storage comfort
Tank
Mon
15:20
60°C
00:00
Mon
Tue
Tank
Storage comfort
60°C
t
a
b
T
t
A1
A2B1B2A1A1 A2B1B2A1
T
t
35°C Reheat tank temperature–hysteresis value
In scheduled + reheat mode, you can do the following:
You can…Location
Do the same things as in scheduled mode.—
Adjust the preset value (Reheat).Menu structure
See also:
▪ "Scheduled mode"[428]
▪ "4.7Preset values and schedules"[438]
Using the DHWtank temperature home page
Typical DHWtank temperature home pages
Depending on the user profile, the user interface gives you either a basic or a
detailed home page. The examples in the illustrations below are in DHWtank mode
= Scheduled.
To read out and adjust the desired reheat temperature (in scheduled and reheat
mode)
1Go to [7.4.3.3]: > User settings > Preset values > Tank
temperature > Reheat.
Result: You can read out the desired reheat temperature.
2Press or to adjust.
To read out and overrule the active or next scheduled desired temperature (in
scheduled mode or scheduled + reheat mode)
1Go to the DHWtank temperature home page (Tank).
Result:
TtDHWtank temperature
t Time
is displayed.
During period…You can read out…
A1The next scheduled action (a)
A2The active action (a)
B1The next scheduled action (b)
User reference guide
29
4 | Operation
During period…You can read out…
B2The active action (b)
2Press or to overrule.
Note: If the desired temperature is weather dependent, you cannot change it on
the home page.
Usage example: You need more hot water than scheduled
If you are in the following situation:
▪ Current time = 10:30
▪ Next scheduled action of the DHW tank = Heat up to the preset value (Eco;
example: 55°C and sufficient for 2 persons) at 14:00
▪ This evening you need hot water for 3persons
Then you can do the following:
1Go to the DHWtank temperature home page (Tank).
2Overrule the next scheduled action by changing from 55°C to 60°C.
Advantages:
▪ You will have sufficient hot water (=comfortable).
▪ You do NOT have to change the schedule (=easy).
▪ You do NOT have to activate the DHWtank booster mode (=energy saving).
Using the DHWtank booster mode
About the DHWtank booster mode
You can use the DHW tank booster mode to immediately start heating up the
water to the preset value (Storage comfort). However, this consumes extra
energy.
To check if the DHWtank booster mode is active
1Go to the DHWtank temperature home page (Tank).
2Check the following:
▪ In user profile = Basic: If is displayed, the DHW tank booster mode is
active.
▪ In user profile = Detailed: If is selected, the DHWtank booster mode is
active.
To activate the DHWtank booster mode (user profile = Basic)
1Go to the DHWtank temperature home page (Tank).
2Press for more than 5seconds.
User reference guide
30
To activate the DHWtank booster mode (user profile = Detailed)
1Go to the DHWtank temperature home page (Tank).
2Press to select .
Usage example: You immediately need more hot water
If you are in the following situation:
▪ You already consumed most of your hot water.
▪ You cannot wait for the next scheduled action to heat up the DHWtank.
Then you can activate the DHWtank booster mode.
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
Advantage: The DHWtank immediately starts heating up the water to the preset
value (Storage comfort).
INFORMATION
When the DHW tank booster mode is active, the risk of space heating/cooling and
capacity shortage comfort problems is significant. In case of frequent domestic hot
water operation, frequent and long space heating/cooling interruptions will happen.
4.6 Advanced usage
4.6.1 About changing the user permission level
To set the user permission level to Advanced end user
1Go to the main menu or any of its submenus: .
2Press for more than 4seconds.
Result: Your user permission level is now Adv. end user. The user interface
displays additional information and a "+" is added to the menu title. The user
permission level stays in Adv. end user until manually set otherwise.
4 | Operation
To set the user permission level to End user
1Press for more than 4 seconds.
Result: Your user permission level is now End user. The user interface displays
the default home page.
4.6.2 Using quiet mode
About quiet mode
You can:
▪ Completely deactivate quiet mode
▪ Manually activate a quiet mode level until the next scheduled action
▪ Use and program a quiet mode schedule
Possible quiet mode levels
INFORMATION
If the outdoor temperature is below zero, we recommend to NOT use the most quiet
level.
Level 1Least quiet. At colder ambient conditions, reduced
performance can occur.
Level 2Medium quiet. Under all circumstances, reduced
performance is possible.
Level 3Most quiet. Under all circumstances, performance will
be reduced.
To check if quiet mode is active
1Press to go to one of the home pages.
2If is displayed, quiet mode is active.
User reference guide
31
4 | Operation
To use quiet mode
Prerequisite: You switched the permission level to Advanced end user.
1Go to [3]: > Quiet mode.
2Do one of the following:
If you want to…Then…
Completely deactivate quiet modeSelect Always OFF and press .
Manually activate a quiet mode level▪ Select On and press .
▪ Go to [7.4.4]: > User
settings > Preset values >
Quiet level.
▪ Select a level and press .
Use and program a quiet mode
schedule
▪ Select Automatic and press .
▪ Program a schedule. See
"4.7.2 Using and programming
schedules"[439].
Usage example: Baby is sleeping in the afternoon
If you are in the following situation:
▪ You have programmed a quiet mode schedule:
- During the night: Level 3 (=most quiet).
- During the day: OFF to ensure the heating/cooling capacity of the system.
▪ However, during the afternoon the baby is sleeping and you want it to be quiet.
Then you can do the following:
Prerequisite: You switched the permission level to Advanced end user.
1Go to [3]: > Quiet mode.
2Select On and press .
3Go to [7.4.4]: > User settings > Preset values > Quiet level.
4Select Level 3 and press .
Advantage:
4.6.3 Using holiday mode
User reference guide
32
The outdoor unit runs in its most quiet level.
About holiday mode
During your holiday, you can use the holiday mode to deviate from your normal
schedules without having to change them. You can only use holiday mode if
temperature control = room thermostat control. See also "4.4.3Determining which
temperature control you are using"[416].
Using holiday mode typically consists of the following stages:
1Configuring the holiday for one of the following situations:
SituationThen…
You stay at home during
your holiday
You have to select a day: space heating/cooling
will be according to the desired room
temperature of the selected day.
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
SituationThen…
15:20
12.0°C
162013
Holiday
Mon
Feb
Until
Actual temp.
4 | Operation
You go away during your
holiday
You have to configure space heating/cooling
settings.
▪ Space heating/cooling will be according to
these settings.
▪ Domestic hot water operation can be turned
ON or OFF. If you decide to turn it OFF,
disinfection mode will remain active.
2Activating the holiday mode.
▪ If you do NOT activate, the configured holiday settings will NOT be used.
▪ If you activate:
PeriodThen…
Before and after your holiday Your normal schedules will be used.
During your holidayThe configured holiday settings will be used.
To check if holiday mode is activated and/or running
1Press to go to one of the home pages.
2Check the following:
If… is displayedThen…
One of the following holiday modes is
activated:
▪ Holiday mode (Away) is activated,
but NOT running yet.
▪ Holiday mode (Home) is activated.
You cannot see if the holiday mode
is already running.
Holiday mode (Away) is activated and
running.
To configure the holiday (when you stay at home)
Prerequisite: You switched the permission level to Advanced end user.
1Go to [2.2]: > Holiday > Holiday mode.
2Select Home.
3Configure the holiday mode settings (when you stay at home).
4Activate the holiday mode.
Possible holiday mode settings (when you stay at home)
Note: If you are on a home page and try to use a function that is locked, is
displayed for 1second.
To activate or deactivate button lock
1Press to go to one of the home pages.
2Press for more than 5seconds.
To activate or deactivate a function lock
1Press to go to the menu structure.
2Press for more than 5seconds.
3Select a function and press .
4Select Lock or Unlock, and press .
About preset values
You can define preset values for multiple controls. Preset values make it easy to
use the same value in many places (schedules and room temperature home page
( and )). If you later want to change the value, you only have to do it in one place.
To define preset values
1Go to [7.4]: > User settings > Preset values.
2Select for which control you want to define a preset value. Example: Room
temperature.
3Select a preset value and press . Example: Comfort (heating).
4Select a temperature and press .
Possible preset values
ControlPreset valueWhere used
Room
temperature
Comfort▪ Room temperature schedules
Eco
▪ Room temperature home page
( and ) if user profile =
Detailed
LWT mainComfortMain leaving water temperature
schedules
if DHWtank mode is
Tank
temperature
Eco
Storage comfortDHWtank temperature schedule
Storage eco
▪ Scheduled
User reference guide
38
▪ Scheduled + reheat
ReheatDHWtank temperature schedule
if DHWtank mode = Scheduled +
reheat
Quiet levelUsed when quiet mode is set to
On
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
4 | Operation
ControlPreset valueWhere used
Elec priceHigh
Fuel priceUsed when the savings mode
4.7.2 Using and programming schedules
About schedules
Depending on your system layout and installer configuration, schedules
(predefined and/or user‑defined) for multiple controls may be available.
You can:
▪ Select which schedules you currently want to use.
▪ Program your own schedules if the predefined schedules are not satisfactory.
The actions you can program are control specific.
Possible actions per control
ControlPossible actions
Medium
Low
Used when the savings mode
(installer setting) is set to
Economical.
(installer setting) is set to
Economical.
Room temperatureProgram when to heat up or cool down a space:
Main leaving water
temperature
▪ Comfort (preset value)
▪ Eco (preset value)
▪ [Custom temperature]
Additional leaving
water temperature
Program when the additional leaving water temperature
is turned ON and OFF.
DHWtank temperature Program when to heat up the DHWtank:
▪ Storage comfort (preset value)
▪ Storage eco (preset value)
▪ Storage stop
(b)
(a)
(a)
Quiet modeProgram when the unit has to use which quiet mode
level:
▪ Level 1
▪ Level 2
▪ Level 3
▪ OFF
(Only for field
supplied domestic hot
Program when the domestic hot water pump is turned
ON and OFF.
Electricity priceProgram when a certain electricity tariff is valid.
(a) Start heating up until the desired setpoint (Comfort/Eco) is reached.
(b) Stop heating, even if the desired temperature is not reached yet; example: if electric
tariffs are higher during the day, you can program a stop at 06:00.
User reference guide
39
4 | Operation
07 :00
-- : -- --
Set heating schedule
Mon
Comfort
Select
Scroll
Delete line
Clear day schedule
Copy day
Save schedule
To select which schedule you currently want to use
1Go to [5]: > Select schedules.
2Select for which control you want to use a schedule. Example: [5.1] Room
temperature.
3Select for which operation mode you want to use a schedule. Example: [5.1.1]
Heating .
4Select a predefined or user‑defined schedule and press .
To program a schedule
1Go to [7.3]: > User settings > Set schedules.
2Open an empty, predefined or user‑defined schedule.
3Change it.
4Save it.
Guidelines when programming
You can:
▪ Delete lines from the schedule
▪ Clear a day schedule
▪ Copy from one day to others
Usage example: You work in a 3-shift system
If you work in a 3-shift system, you can do the following:
1Program 3 room temperature schedules and give them appropriate names.
2Select the schedule that you currently want to use.
4.7.5 Predefined schedules: Leaving water temperature (additional)
INFORMATION
The predefined schedules are applicable for both heating and cooling operation.
: Additional zone = On
: Additional zone = OFF
Predefined 1
Mon - Fri
Sat - Sun
Predefined 2
Mon - Fri
Sat - Sun
Predefined 3
Mon - Sun
INFORMATION
The predefined schedules are applicable for both heating and cooling operation.
4.7.6 Predefined schedules: DHWtank temperature
: Start production of domestic hot water. Desired DHW tank temperature =
Preset value (Storage comfort)
: Start production of domestic hot water. Desired DHW tank temperature =
Preset value (Storage eco)
Predefined 1
Mon - Sun
Predefined 2
Mon - Sun
User reference guide
42
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
Predefined 3
a
b
:00
a
b
:00:00
d
c
T
a
T
t
ab
Mon - Fri
Sat - Sun
4.8 Weather dependent operation
In space heating/cooling control, the leaving water temperature setpoint mode can
be:
▪ Fixed
▪ Weather-dependent (the leaving water temperature is determined automatically
depending on the outdoor temperature)
To select the setpoint mode, see the installer reference guide.
To set the parameters for the weather-dependent curve, see below.
4 | Operation
4.8.1 To set the weather dependent settings
Prerequisite: You switched the permission level to Advanced end user.
1Go to [7.7]: > User settings > Set weather dependent.
2For main leaving water temperature zone [7.7.1], modify with , , , ,
and confirm with .
3If applicable, for additional leaving water temperature zone [7.7.2], modify
with , , , , and confirm with .
Set weather-dependent heating/Set weather-dependent cooling
TtTarget leaving water temperature
TaOutdoor temperature
a Low outdoor ambient temperature
b High outdoor ambient temperature
c Desired leaving water temperature when the outdoor temperature equals or drops
below the low ambient temperature. Note: in heating, this value should be higher
than (d) as for low outdoor temperatures warmer water is required. In cooling, this
value should be higher than (d) as for low outdoor temperatures less cold water
suffices
d Desired leaving water temperature when the outdoor temperature equals or rises
above the high ambient temperature. Note: in heating, this value should be lower
than (c) as for high outdoor temperatures less warm water is required. In cooling,
this value should be lower than (c) as for high outdoor temperatures colder water is
required.
Leaving water temperature: Additional zone [A.3.1.2]
LWT setpoint mode0 (Fixed)
Leaving water temperature: Modulation [A.3.1.1.5]
Modulated LWT1 (Yes)
Leaving water temperature: Emitter type [A.3.1.1.7]
Emitter type0 (Quick)
Savings mode [A.6.7]
Savings mode0 (Economical)
Electricity price [7.4.5]
Elec price20/kWh (High)
Fuel price [7.4.6]
Fuel price8.0/kWh
4.10.3 Domestic hot water control [A.4]
SettingDefaultFill in…
Type2 (Scheduled
Maximum setpointDepends on model
INFORMATION
When the DHW tank booster mode is active, the risk of space heating/cooling and
capacity shortage comfort problems is significant. In case of frequent domestic hot
water operation, frequent and long space heating/cooling interruptions will happen.
20/kWh (Medium)
15/kWh (Low)
only)
4.10.4 Contact/helpdesk number [6.3.2]
User reference guide
46
SettingDefaultFill in…
Contact/helpdesk number—
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
5 Setting the energy prices
If your system's savings mode is set to Economical, it allows you to set:
▪ a fixed gas price
▪ 3 electricity price levels
▪ a weekly schedule timer for electricity prices.
The savings mode is set by the installer and can be either ecological or economical.
In ecological mode, the primary energy use is minimised; in economical mode, the
running costs. Discuss with the installer which savings mode is preferred. Refer to
the installation manual for more information.
Example: How to set the energy prices on the user interface?
PriceValue in breadcrumb
Gas: 5.3euro cent/kWh[7.4.6]=5.3
Gas: 4.8pence/kWh[7.4.6]=4.8
Electricity: 12euro cent/kWh[7.4.5.1]=12
Electricity: 12.49pence/kWh[7.4.5.1]=12
5 | Setting the energy prices
5.1 To set the gas price
1Go to [7.4.6]: > User settings > Preset values > Fuel price.
2Use and to set the correct price.
3Press to confirm.
INFORMATION
▪ Price value ranging from 0.00~290valuta/MBtu (with 2 significant values).
▪ Price value ranging from 0.00~990valuta/kWh (with 2 significant values).
5.2 To set the electricity price
1Go to [7.4.5]: > User settings > Preset values > Elec price.
2Use and to set the correct prices for High, Medium and Low, according
to your electricity tariff.
3Press to confirm.
INFORMATION
Price value ranging from 0.00~990valuta/kWh (with 2 significant values).
If no schedule is set, the Elec price for High is taken into account.
User reference guide
47
5 | Setting the energy prices
5.3 To set the electricity price schedule timer
1Go to [7.3.8]: > User settings > Set schedules > Elec price.
2Program the schedule according to the High, Medium and Low electricity
3Press to save the schedule.
5.4 About energy prices in case of an incentive per kWh renewable
energy
An incentive can be taken into account when setting the energy prices. Although
the running cost can increase, the total operation cost, taking into account the
reimbursement will be optimized.
prices for each time interval.
INFORMATION
The values for High, Medium and Low correspond with the electricity price values
for High, Medium and Low previously set. If no schedule is set, the electricity price
for High is taken into account.
NOTICE
Make sure to modify the setting of the energy prices at the end of the incentive
period.
5.4.1 To set the gas price in case of an incentive per kWh renewable energy
Prerequisite: Calculate the value for the gas price with following formula: actual
gas price+(incentive/kWh×0.9)
1Go to [7.4.6]: > User settings > Preset values > Fuel price.
2Use and to set the correct price.
3Press to confirm.
5.4.2 To set the electricity price in case of an incentive per kWh renewable energy
Prerequisite: Calculate the value for the electricity price with following formula:
actual electricity price+incentive/kWh.
1Go to [7.4.5]: > User settings > Preset values > Elec price.
2Use and to set the correct prices for High, Medium and Low, according
to your electricity tariff.
3Press to confirm.
5.4.3 Example
User reference guide
48
This is an example and the prices and/or values used in this example are NOT
accurate.
The user interface is able to graphically display energy statistics for:
▪ produced energy: energy produced by the heat pump.
▪ consumed electricity: recorded by an electricity meter or, when none is installed,
calculated by the interface itself based on an internal calculation.
▪ consumed gas: only recorded when an external gas meter is installed. Note that
the values recorded by the meter may differ from those shown on the boiler.
Prerequisite: You switched the permission level to Advanced end user.
1Go to [6.2]: > Information > Energy metering.
2Select either Consumed elec., Produced energy or Consumed gas.
3Use the and buttons to toggle between views of the current month, the
previous month, the last 12 months and a general overview.
4Use the and buttons to toggle between different modes (if applicable).
User reference guide
50
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
7 Energy saving tips
Tips about room temperature
▪ Make sure the desired room temperature is NEVER too high (in heating mode) or
too low (in cooling mode), but ALWAYS according to your actual needs. Each
saved degree can save up to 6% of heating/cooling costs.
▪ Do NOT increase/decrease the desired room temperature to speed up space
heating/cooling. The space will NOT heat up/cool down faster.
▪ When your system layout contains slow heat emitters (example: underfloor
heating), avoid large fluctuation of the desired room temperature and do NOT let
the room temperature drop too low/rise too high. It will take more time and
energy to heat up/cool down the room again.
▪ Use a weekly schedule for your normal space heating or cooling needs. If
necessary, you can easily deviate from the schedule:
- For shorter periods: You can overrule the scheduled room temperature.
Example: When you have a party, or when you are leaving for a couple of
hours.
- For longer periods: You can use the holiday mode. Example: When you stay at
home during your holiday, or when you go away during your holiday.
7 | Energy saving tips
Tips about leaving water temperature
▪ In heating mode, a lower desired leaving water temperature results in lower
energy consumption and better performance. In cooling, the opposite is valid.
▪ Set the desired leaving water temperature in accordance with the heat emitter
type. Example: Underfloor heating is designed for lower leaving water
temperature than radiators and heatpump convectors.
Tips about DHWtank temperature
▪ Use a weekly schedule for your normal domestic hot water needs (only in
scheduled mode).
- Program to heat up the DHWtank to a preset value (Storage comfort =
higher DHW tank temperature) during the night, because then space heating
demand is lower.
- If heating up the DHW tank once at night is not sufficient, program to
additionally heat up the DHW tank to a preset value (Storage eco = lower
DHWtank temperature) during the day.
▪ Make sure the desired DHW tank temperature is NOT too high. Example: After
installation, lower the DHWtank temperature daily by 1°C and check if you still
have enough hot water.
▪ Program to turn ON the domestic hot water pump only during periods of the day
when instant hot water is necessary. Example: In the morning and evening.
The installer has to perform a yearly maintenance. You can find the contact/
helpdesk number via the user interface.
As enduser, you have to:
▪ Keep the area around the unit clean.
▪ Keep the user interface clean with a soft damp cloth. Do NOT use any detergents.
▪ Regularly check if the water pressure indicated on the gas boiler is above 1 bar.
Switch off the boiler to see the pressure on the main display of the gas boiler.
Ignore the error that appears on the user interface. When you turn the gas boiler
back on, the error will disappear.
▪ Make sure that electricity and gas prices defined in the user interface are up-to-
date.
Refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent gases into the
atmosphere.
Refrigerant type: R410A
Global warming potential (GWP) value: 2087.5
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO2 equivalent.
Formula to calculate the quantity in CO2 equivalent tonnes: GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Please contact your installer for more information.
WARNING
The refrigerant in the system is safe and normally does not leak. If the refrigerant
leaks in the room, contact with a fire of a burner, a heater or a cooker may result in a
harmful gas.
Turn off any combustible heating devices, ventilate the room and contact the dealer
where you purchased the unit.
Do not use the system until a service person confirms that the portion where the
refrigerant leaks is repaired.
8.2 To find the contact/helpdesk number
User reference guide
52
Prerequisite: You switched the permission level to Advanced end user.
1Go to [6.3.2]: > Information > Error handling > Contact/
helpdesk number.
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
9 Troubleshooting
If a malfunction occurs, is displayed on the home pages. You can press to
display more information about the malfunction.
For the symptoms listed below, you can try to solve the problem yourself. For any
other problem, contact your installer. You can find the contact/helpdesk number
via the user interface.
9.1 Overview: Troubleshooting
If a malfunction occurs, is displayed on the home pages. You can press to
display more information about the malfunction.
For the symptoms listed below, you can try to solve the problem yourself. For any
other problem, contact your installer. You can find the contact/helpdesk number
via the user interface.
9.2 To check the error history
9 | Troubleshooting
Prerequisite: Only available if is displayed on the home pages.
1Go to [6.3.1]: > Information > Error handling > Error history.
9.3 To check the warning history
Prerequisite: Only available if is displayed on the home pages.
1Go to [6.3.1]: > Information > Error handling > Warning history.
9.4 Symptom: You are feeling too cold (hot) in your living room
Possible causeCorrective action
The desired room temperature is too
low (high).
Increase (decrease) the desired room
temperature. See "4.4.5Room
thermostat control - Using the room
temperature home pages"[418].
If the problem recurs daily, do one of
the following:
programming schedules" [4 39] and
"4.7.3Schedules: Example"[440].
User reference guide
53
9 | Troubleshooting
Possible causeCorrective action
The desired room temperature cannot
be reached.
Increase the desired leaving water
temperature in accordance with the
heat emitter type. See "4.4.6Room
thermostat control - Using the leaving
water temperature home pages"[422].
The weather-dependent curve is set
incorrectly.
Adjust the weather-dependent curve.
See "4.8Weather dependent
operation"[443].
9.5 Symptom: The water at the tap is too cold
Possible causeCorrective action
Your tank ran out of domestic hot water
because of unusual high consumption.
The desired DHWtank temperature is
too low.
If you immediately need domestic hot
water, activate the DHWtank booster
mode. However, this consumes extra
energy. See "Using the DHWtank
booster mode"[430].
If you can wait, overrule (increase) the
active or next scheduled desired
temperature so that more hot water
will be produced exceptionally. See "To
read out and overrule the active or next
scheduled desired temperature (in
scheduled mode or scheduled + reheat
mode)"[429].
The instant DHW temperature is too
low. (Only applicable when no tank is
installed).
9.6 Symptom: Heat pump failure
When the heat pump fails to operate, the gas boiler can serve as an emergency
back-up heater and either automatically or non-automatically take over the entire
heat load.
If the problems recurs daily, do one of
the following:
▪ Increase the DHW tank temperature
preset value. See "4.7.1 Using preset
values"[438].
▪ Adjust the DHW tank temperature
schedule. Example: Program to
additionally heat up the DHWtank to
a preset value (Storage eco =
lower tank temperature) during the
day. See "4.7.2Using and
programming schedules" [4 39] and
"4.7.3Schedules: Example"[440].
Increase the instant DHW set point
temperature. See "To adjust the instant
DHW temperature"[427].
User reference guide
54
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
9 | Troubleshooting
▪ When auto emergency is activated and a heat pump failure occurs, the boiler
will automatically take over the heat load.
▪ When auto emergency is not activated and a heat pump failure occurs, the
domestic hot water and space heating operations will stop and need to be
recovered manually. The user interface will then ask you to confirm whether the
boiler can take over the entire heat load or not.
When the heat pump fails, will appear on the user interface.
Possible causeCorrective action
Heat pump is damaged.▪ Press to view a description of the
problem.
▪ Press again.
▪ Select to allow the gas boiler to
take over the entire heat load.
▪ Call your local dealer to get the heat
pump fixed.
INFORMATION
When the gas boiler takes over the entire heat load, gas consumption will be
considerably higher.
If you want to relocate parts of your system, contact your installer. You can find the
contact/helpdesk number via the user interface.
User reference guide
56
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
11 Disposal
11 | Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
Hot water used, in any type of building, for domestic purposes.
LWT = Leaving water temperature
Water temperature at the water outlet of the unit.
Dealer
Sales distributor for the product.
Authorised installer
Technical skilled person who is qualified to install the product.
User
Person who is owner of the product and/or operates the product.
Applicable legislation
All international, European, national and local directives, laws, regulations
and/or codes that are relevant and applicable for a certain product or
domain.
Service company
Qualified company which can perform or coordinate the required service to
the product.
Installation manual
Instruction manual specified for a certain product or application, explaining
how to install, configure and maintain it.
Operation manual
Instruction manual specified for a certain product or application, explaining
how to operate it.
Accessories
Labels, manuals, information sheets and equipment that are delivered with
the product and that need to be installed according to the instructions in
the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can be combined with the
product according to the instructions in the accompanying documentation.
Field supply
Equipment NOT made by Daikin that can be combined with the product
according to the instructions in the accompanying documentation.
User reference guide
58
EHYHBH05AF + EHYHBH/X05+08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632-1E – 2020.10
Verantwortung für Energie und Umwelt
Copyright 2013 Daikin
4P355632-1E 2020.10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.