6.6Piping diagram for refrigerant circuit .......................................... 38
Installation and operating manual
2
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
1General safety precautions
1.1Particular safety instructions
1 General safety precautions
WARNING
Devices that have not been set up and
installed correctly can impair the
function of the device and/or cause
serious or fatal injury to the user.
▪ Work on the indoor unit (such as set-
up, servicing, connection and initial
commissioning) must only be carried
out by persons who are authorised
and who have successfully
completed qualifying technical orvocational training, and who have
taken part in advanced training
sessions recognised by the relevant
responsible authorities for the specific
activity. These include, in particular,
certified heating engineers,
qualified electricians and HVAC
specialists who, because of their
professional training and expert
knowledge, have experience in the
professional installation and
maintenance of heating, cooling and
air conditioning systems as well as
hot water storage tanks.
WARNING
Disregarding the following safety
instructions may result in serious
physical injury or death.
▪ This device may only be used by
children aged 8 and above and by
persons with restricted physical,
sensory or mental capabilities or with
a lack of experience and knowledge if
they are under supervision or if they
have been instructed in the safe use
of the equipment and understand the
dangers arising from it. Children
must not play with the device.
Cleaning and user maintenance
must not be carried out by children
without supervision.
▪ Establish the power supply in
accordance with IEC60335‑1, via a
separate isolator that separates all
poles with a contact opening distance
and that provides full disconnection in
accordance with overvoltage
categoryIII.
▪ All electrical work must only be
carried out by electrically qualified
experts and with consideration of the
local and national regulations and the
instructions in this manual.
Ensure that a suitable electrical
circuit is used.
Insufficient load capacity of the
electrical circuit or improperly
executed connections can result in
electric shock or fire.
▪ The customer must install a pressure
relief device with a rated overpressure of less than 1.0MPa
(10bar). The connected drain line
must have a continuous gradient and
a free outlet in a frost-free
environment (see "3.3Installing the
heat pump"[412]).
▪ Water may drip out of the drain line of
the pressure relief device. The drain
opening must be left open to the
atmosphere.
▪ The pressure relief device must be
operated regularly in order to remove
scale deposits and to make sure it is
not blocked.
▪ The storage tank and hot water circuit
can be drained. The instructions in
"Temporary decommissioning" in the
reference manual for the fitter must
be complied with.
1.1.1Observing the instructions
▪ The original documentation is written in German. All other
languages are translations.
▪ Please read this manual carefully and thoroughly before
proceeding with the installation or modification of the heating
system.
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
Installation and operating manual
3
1 General safety precautions
▪ The precautionary measures described in this document cover
very important topics. Follow them meticulously.
▪ The installation of the system, and all activities described in this
manual and the applicable documents for the installer must be
carried out by an approved installer.
Documentation set
This document is part of a documentation set of other applicable
documents. The complete set comprises:
▪ Installation manual for the indoor unit (format: paper – included in
the indoor unit scope of delivery)
▪ Operating manual for the indoor unit (format: paper – included in
the indoor unit scope of delivery)
▪ Operating manual for the heat pump (format: paper – included in
the indoor unit scope of delivery)
▪ Installation manual for the outdoor unit (format: paper – included
in the outdoor unit scope of delivery)
▪ Installation instructions for optional components (format: paper –
included in the scope of delivery of the respective component)
▪ Installer reference guide of the indoor unit (format: digital)
▪ Installer reference guide of the outdoor unit (format: digital)
The reference guides contain the complete set of technical data, a
detailed description of best practices and information on
maintenance, troubleshooting and decommissioning.
The digital documents and the latest editions of the supplied
documentation are available on the regional Daikin website or, on
request, from your dealer. The Daikin website is easy to access
using the QR code on your device.
1.1.2Meaning of warnings and symbols
Warnings in this manual are classified according into their severity
and probability of occurrence.
DANGER
Indicates an immediate danger.
Disregarding this warning can lead to serious injury or
death
WARNING
Indicates a potentially dangerous situation
Disregarding this warning may result in serious physical
injury or death.
CAUTION
Indicates a situation which may cause possible damage
Disregarding this warning can cause damage to property
and the environment and result in minor injuries.
This symbol identifies user tips and particularly useful
information, but not warnings or hazards
Special warning signs
Some types of danger are represented by special symbols.
Electric current
Danger of explosion
Risk of burns or scalds
Validity
Some information in this manual has limited validity. The validity is
highlighted by a symbol.
Heat pump outdoor unit
Heat pump indoor unit
FWXV-ATV3
Observe the specified tightening torque
Only applies to devices with unpressurised solar system
connection (DrainBack).
Only applies to devices with a bivalent solar system
connection (Biv).
Only applies to indoor units with cooling function
Handling instructions
1 Handling instructions are shown as a list. Actions where the
sequential order must be adhered to are numbered.
1.2Safety instructions for installation
and operation
1.2.1General
WARNING
Devices that have not been set up and
installed correctly can impair the
function of the device and/or cause
serious or fatal injury to the user.
▪ Work on the indoor unit (such as set-
up, servicing, connection and initial
commissioning) must only be carried
out by persons who are authorised
and who have successfully
completed qualifying technical orvocational training, and who have
taken part in advanced training
sessions recognised by the relevant
responsible authorities for the specific
activity. These include, in particular,
certified heating engineers,
qualified electricians and HVAC
specialists who, because of their
professional training and expert
knowledge, have experience in the
professional installation and
maintenance of heating, cooling and
air conditioning systems as well as
hot water storage tanks.
Risk of poisoning
Installation and operating manual
4
▪ Switch off the external main switch
before starting any work on the
indoor unit and secure against being
switched on inadvertently.
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
1 General safety precautions
▪ Do not leave any tools or other
objects below the hood of the device
after finishing installation or
maintenance work.
Avoid danger
The indoor unit conforms to the state of the art and meets all
recognised technical requirements. However, improper use can lead
to serious injuries or death, as well as causing material damage. To
prevent such risks, only install and operate the devices:
▪ as stipulated and in perfect condition,
▪ with an awareness of the safety and hazards involved.
This assumes knowledge and use of the contents of this manual, the
relevant accident prevention regulations and the recognised safetyrelated and occupational medical rules.
Before working on the hydraulic system
▪ Work on the system (such as set-up, connection and initial
commissioning, for example) must only be carried out by persons
who are authorised, who have successfully completed qualifying
technical or vocational training for the respective activity and who
have taken part in advanced training sessions recognised by the
relevant responsible authority.
▪ When carrying out any work on the system, switch off the main
switch and secure against being switched on inadvertently.
▪ Seals must not be damaged or removed.
▪ Make sure that the safety valves comply with the requirements of
EN 12828 when connecting on the heating side and with the
requirements of EN 12897 when connecting on the domestic
water side.
1.2.2Intended use
The indoor unit may only be used for domestic hot water
preparation, as a room heating system and, depending on its design,
as a room cooling system.
The indoor unit must only be installed, connected and operated
according to the indications in these instructions.
Only the use of a suitable outdoor unit approved by the manufacturer
is permitted.
1‒1 Permissible combinations
EHSX04P30D27
EHSX04P50DA7
EHSXB04P30D27
EHSXB04P50DA7
EHSH04P30D27
EHSHB04P30D27
ERGA04DAV3
ERGA06DAV3
ERGA08DAV3
ERGA04DAV3A
ERGA06DAV3A
ERGA08DAV3A
ERGA04DAV37
EHSX08P30D27
EHSX08P50DA7
EHSXB08P30D27
EHSXB08P50DA7
EHSH08P30D27
EHSH08P50DA7
EHSHB08P30D27
EHSHB08P50DA7
Any other use or use beyond the intended use is considered
improper use. The operator alone bears responsibility for any
resulting damage.
Intended use also includes compliance with the maintenance and
service conditions. Spare parts must at least satisfy the technical
requirements defined by the manufacturer. This is the case, for
example, with original spare parts.
1.2.3Installation room
WARNING
The plastic wall of the storage tank on
the indoor unit can melt under the
effects of external heat (>80°C) and, in
the extreme case, can catch fire.
▪ Only install the indoor unit at a
minimum clearance of 1m from other
heat sources (>80°C) (e.g. electrical
heater, oil heater, chimney) and
combustible materials.
CAUTION
▪ Only install the indoor unit if sufficient
load-carrying capacity of the ground
of 1050kg/m2 plus safety margin is
ensured. The ground must be flat,
horizontal and level.
▪ Outdoor set up is not permissible.
▪ Set-up in an explosion-risk
environment is not permissible.
▪ The electronic control system must
not be exposed to weather effects
such as rain and snow under any
circumstances.
▪ The storage tank may not be
exposed to continuous direct sunlight,
as the UV radiation and the effects of
the weather will damage the plastic.
▪ The indoor unit must be installed
protected from frost.
▪ Make sure that the supply company
does not provide corrosive domestic
water. Suitable water treatment may
be required.
▪ Always ensure the minimum distances from walls and other
objects ("3.1Dimensions and connection dimensions"[411]).
▪ Observe the special installation requirements of the R32
refrigerant (see "3.3.1Selecting the installation site"[412]).
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
Installation and operating manual
5
1 General safety precautions
CAUTION
▪ If a DrainBack solar heating
system is connected: Install the
indoor unit far enough under the solar
panels to allow complete emptying of
the solar heating system. (Follow the
instructions in the DrainBack solar
heating system manual.) An
insufficient height difference may lead
to destruction of the DrainBack solar
heating system.
▪ The indoor unit must not be operated
in rooms with ambient temperatures
of more than 40°C.
1.2.4Electrical installation
▪ Electrical installations may only be carried out by electrical
technicians and in compliance with valid electrical guidelines as
well as the specifications of the responsible energy supply
company.
▪ Compare the mains voltage indicated on the nameplate with the
supply voltage before connecting to the mains.
▪ Before beginning work on live parts, disconnect them from the
power supply (switch off main switch, remove fuse) and secure
against unintentional restart.
▪ Device covers and service panels must be replaced as soon as
the work is completed.
1.2.5Requirements for heating and storage
water
Damage due to deposits and corrosion: observe the relevant
technical rules to avoid corrosion products and deposits.
Minimum requirements regarding the quality of filling and top-up
water:
▪ Water hardness (calcium and magnesium, calculated as calcium
carbonate): ≤3mmol/l
▪ Conductivity: ≤1500 (ideal ≤100)μS/cm
▪ Chloride: ≤250mg/l
▪ Sulphate: ≤250mg/l
▪ pH value: 6.5 – 8.5
Measures for desalination, softening or hardness stabilisation are
necessary if the filling and top-up water have a high total hardness
(>3 mmol/l – total of the calcium and magnesium concentrations,
calculated as calcium carbonate). We recommend the use of Fernox
KSK limescale and corrosion protector. For other properties
deviating from the minimum requirements, suitable conditioning
measures are necessary to maintain the required water quality.
Using filling water and top-up water which does not meet the stated
quality requirements can cause a considerably reduced service life
of the equipment. The responsibility for this lies solely with the
operator.
INFORMATION
If an optional external heat generator is connected, these
minimum requirements also apply to the filling and
supplementary water for this heating circuit.
1.2.6Heating system and sanitary connection
▪ Create a heating system according to the safety requirements of
EN12828.
▪ The plumbing connection must comply with the requirements of
EN 12897. The requirements of the following must also be
observed:
▪ EN 1717 – Protection against pollution of potable water
installations and general requirements of devices to prevent
pollution by backflow
▪ EN61770 – Electric appliances connected to the water mains –
Avoidance of backsiphonage and failure of hose-sets
▪ EN 806 – Specifications for installations inside buildings
conveying water for human consumption
▪ and, in addition, the country-specific legislation.
During operation of the indoor unit with an auxiliary heat source, the
storage tank temperature may exceed 65°C, above all when solar
energy is used.
▪ For this reason, some form of scalding protection needs to be
included when you install the system (hot water mixing device,
e.g. VTA32).
INFORMATION
The domestic water quality must comply with the
EU Guideline 98/83 EC and the regionally-applicable
regulations.
If the indoor unit is connected to a heating system with steel pipes,
radiators or non-diffusion-proof floor heating pipes, sludge and chips
can enter the hot water storage tank and cause blockages, local
overheating or corrosion damage.
▪ To prevent possible damage, install a dirt filter or sludge separator
into the heating return flow of the system (SAS 1 or SAS 2).
▪ The dirt filter must be cleaned at regular intervals.
1.2.7Operation
The indoor unit:
▪ Do not operate until all installation and connection work is
completed.
▪ Only operate with a completely full storage tank (check level
indicator) and heating circuit.
▪ Operate at a maximum pressure of 3bar.
▪ Only connect with a pressure reducer on the external water supply
(supply line).
▪ Only operate if the protective cover is installed.
The specified servicing intervals should be adhered to and
inspection work must be carried out.
1.3Maintenance, troubleshooting and
decommissioning
Work for maintenance, troubleshooting and decommissioning must
not be carried out without knowledge of the relevant safety
precautions and in the event of disposal of the country-specific
guidelines. Please refer to the corresponding information in the
reference manual for the fitter.
Recommendations for disposal
We designed the indoor unit in an environmentally friendly manner.
During the disposal process, the only waste created is that which
can be used for material or thermal recycling. The materials used
that are suitable for recycling can be sorted into individual types.
Installation and operating manual
6
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
Thanks to the environmentally friendly design of the
indoor unit, we have established requirements to ensure
environmentally friendly disposal. Proper disposal in compliance
with the respective national regulations of the country of use is the
responsibility of the user/owner.
The designation of the product means that electrical and
electronic products may not be disposed of together with unsorted
domestic waste.
Proper disposal in compliance with the respective national
regulations of the country of use is the responsibility of the user/
owner.
▪ Disassembly of the system, handling of refrigerant, oil and other
parts may only be carried out by a qualified fitter.
▪ Disposal may only be carried out by an organisation that
specialises in reuse, recycling and recovery.
Further information is available from the installation company or the
responsible local authorities.
2 Product description
2Product description
2.1Design and components
Outside of the device
1.4Warranty conditions
The legal guarantee conditions fundamentally apply. Our more
extensive warranty conditions can be found in the Internet. Ask your
suppliers if necessary.
Incorrect installation, commissioning and maintenance will void the
warranty. If you have any questions, please contact our customer
service.
Warranty claims can only be made if the annual maintenance work is
demonstrably carried out regularly according to the information in the
installer reference guide.
2‒1 Design and components – Outside of the device
a Status indicator
b Protective cover
c Mount for handle
d Filling and draining connection or solar return flow
connection
e Type plate
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
Installation and operating manual
7
2 Product description
Upper side of the device
o Combined filling and draining valve (heating circuit)
p Storage tank temperature sensor
q Expansion vessel connection
f Circulation pump
g Pressure relief valve
h Automatic vent valve
i Connection for optional electrical backup heater EKBUxx
j Fill level indicator (tank water)
k Plate heat exchanger
l Connection for refrigerant fluid line
m Connection for refrigerant gas line
n Ball valve (heating circuit)
Installation and operating manual
8
2‒3 Design and components – Internal
structure ...04P30D.../...08P30D... (Biv)
a Solar flow
b Cold water connection
c Hot water
d Heating flow
e Heating return flow
f Circulation pump
g Pressure relief valve
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
2 Product description
h Storage tank (polypropylene, double-walled jacket with
PUR hard foam heat insulation)
i Filling and draining connection or solar return flow
connection
j Mount for solar controller or handle
k Heat exchanger (stainless steel) for domestic hot water
heating
l Heat exchanger (stainless steel) for storage tank
charging or heating support
m Biv heat exchanger (stainless steel) for charging with
external heat generator (e.g. pressurised solar system)
n Connection for optional electrical backup heater EKBUxx
o Fill level indicator (tank water)
p Optional: electric backup heater (EKBUxx)
q Submersible sensor sleeve for storage tank temperature
sensor t
r Pressureless storage tank water
DHW1
and t
DHW2
s Solar zone
t Hot water zone
u Safety overflow connection
v Mount for handle
w Protective cover
x Solar return flow
y Biv flow
z Biv return flow
aa Plate heat exchanger
ab Connection for refrigerant fluid line
ac Connection for refrigerant gas line
ad Optional: Solar control and pump unit
ae Circulation stop valve (accessory)
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
2‒4 Design and components - Internal
structure ...04P50D/...08P50D… (Biv)
a Solar flow
b Cold water connection
c Hot water
d Heating flow
e Heating return flow
f Circulation pump
g Pressure relief valve
h Storage tank (polypropylene, double-walled jacket with
PUR hard foam heat insulation)
i Filling and draining connection or solar return flow
connection
j Mount for solar controller or handle
k Heat exchanger (stainless steel) for domestic hot water
heating
l Heat exchanger (stainless steel) for storage tank
charging or heating support
m Biv heat exchanger (stainless steel) for charging with
external heat generator (e.g. pressurised solar system)
n Connection for optional electrical backup heater EKBUxx
o Fill level indicator (tank water)
Installation and operating manual
9
3 Set-up and installation
p Optional: electric backup heater (EKBUxx)
q Submersible sensor sleeve for storage tank temperature
sensor t
r Pressureless storage tank water
s Solar zone
t Hot water zone
u Safety overflow connection
v Mount for handle
w Protective cover
x Solar return flow
y Biv flow
z Biv return flow
aa Plate heat exchanger
ab Connection for refrigerant fluid line
ac Connection for refrigerant gas line
ad Optional: Solar control and pump unit
ae Circulation stop valve (accessory)
Cooling systems (heating pumps), climate control systems
and heating devices that have been set up and installed
incorrectly can both endanger human life and health and
be impaired in their function.
▪ Work on the indoor unit (such as set-up, repair,
connection and initial commissioning, for example)
must only be carried out by persons who are
authorised, who have successfully completed qualifying
technical or vocational training for the respective
activity and who have taken part in advanced training
sessions recognised by the relevant responsible
authority. These include, in particular, certified heating
engineers, qualified electricians and HVAC specialists
who, because of their professional training and expert
knowledge, have experience in the professional
installation and maintenance of heating, cooling and air
conditioning systems and heat pumps.
Incorrect set-up and installation would render the manufacturer's
guarantee for the unit void. If you have questions, please contact our
Technical Customer Service.
2‒5 Function of 3‑way changeover valve
Installation and operating manual
10
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
3 Set-up and installation
3.1Dimensions and connection
dimensions
Dimensions …04P30D.../…08P30D...
Dimensions …04P50D…/…08P50D…
3‒1 Dimensions …04P30D.../…08P30D...
a Solar flow
b Domestic cold water
c Hot water
d Heating flow
e Heating return flow
f Connection for refrigerant gas line
g Connection for refrigerant fluid line
h Biv flow (…Biv type only)
i Biv return flow (…Biv type only)
A front
B rear
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
3‒2 Dimensions …04P50D…/…08P50D…
a Solar flow
b Domestic cold water
c Hot water
d Heating flow
e Heating return flow
f Connection for refrigerant gas line
g Connection for refrigerant fluid line
h Biv flow (…Biv type only)
i Biv return flow (…Biv type only)
A front
B rear
Installation and operating manual
11
3 Set-up and installation
3.2Transport and delivery
WARNING
When unfilled, the indoor unit is top-heavy and could tip
over during transport, which could put persons in danger or
damage the device.
▪ Secure the indoor unit well, transport carefully, use the
handles.
The indoor unit is delivered on a pallet. All industrial trucks, such as
lifting trucks and forklift trucks, are suitable for transport.
Scope of delivery
▪ Indoor unit (pre-mounted),
▪ Bag of accessories,
▪ Document pack.
Installation area
▪ The base must be level and smooth and have sufficient ground
load-bearing capacity of 1050kg/m² plus safety factor. Install a
pedestal if necessary.
▪ Observe the installation dimensions (see "3.1 Dimensions and
connection dimensions"[411]).
Minimum distance
DANGER: RISK OF BURNING/SCALDING
The plastic wall of the storage tank on the indoor unit can
melt under the effects of external heat (>80°C) and, in the
extreme case, can catch fire.
▪ Only install the indoor unit at a minimum clearance of
1 m from other heat sources (>80°C) (e.g. electrical
heater, oil heater, chimney) and combustible material.
CAUTION
If the indoor unit is not installed at a sufficient
distance below the flat solar panels (the top edge of the
storage tank is higher than the bottom edge of the solar
panels), the unpressurised solar system in the outdoor
area will not be able to drain completely.
▪ When a solar connection is used, install the indoor unit
low enough under the flat solar panels (observe the
minimum gradient of the solar connection lines).
Recommended minimum distances:
From the wall: (rear) ≥100mm, (sides) ≥500mm
From the ceiling: ≥1200mm, at least 480mm.
3‒3 Scope of delivery
a Handles (only required for transport)
b Cover screen
c Hose connecting piece for safety overflow
d Fitting spanner
e Ball valve
f Flat gasket
g O‑ring
h Cable tie
i Securing clip
j Venting hose
k Condensate drain hose
l Controller rotary switch
m Hood screws
n Document pack
For further accessories for the indoor unit, see price list.
3.3Installing the heat pump
3.3.1Selecting the installation site
CAUTION
If the total refrigerant charge in the system is ≥1.84kg, it is
essential to comply with additional requirements for
minimum footprint and minimum ventilation openings.
Observe "6.4 Minimum floor area and ventilation
openings"[434].
Information on the total refrigerant charge can be found on
the type plate of the outdoor unit. Please follow the
installation instructions.
The installation site of the indoor unit must meet the minimum
requirements below (see also "1.2.3Installation room"[45]).
Distances from the outdoor unit:
When selecting the installation location, the data in the table " 3‒1
"[412] must be taken into account.
3‒1
Maximum refrigerant piping length between the
indoor and outdoor units
Minimum refrigerant piping length between the
indoor and outdoor units
Maximum height difference between the indoor and
outdoor units
30m
3m
20m
3.3.2Installing the device
WARNING
When unfilled, the indoor unit is top-heavy and could tip
over during transport, which could put persons in danger or
damage the device.
▪ Secure the indoor unit well, transport carefully, use the
handles.
Precondition
▪ The installation site complies with applicable country-specific
regulations and meets the minimum requirements described in
"3.3.1Selecting the installation site"[412].
Set-up
1 Remove the packaging and dispose of it in an environmentally
sound manner.
2 Pull off the cover screens from the storage tank (item b) and
unscrew the threaded fittings (item c) from the openings at
which the handles are to be fitted.
3 Screw the handles (item a) into the now uncovered threaded
holes.
Installation and operating manual
12
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECH₂O
008.1451099_00 – 07/2020
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.