Daikin EHSX04P30D2, EHSX04P50D, EHSH04P30D2, EHSX08P30D2, EHSX08P50D Operation manuals

...
Installation and operating manual
Daikin Altherma 3 R ECHO
EHSX(B)04P30D2 EHSX(B)04P50D EHSH(B)04P30D2
EHSX(B)08P30D2 EHSX(B)08P50D EHSH(B)08P30D2 EHSH(B)08P50D
Installation and operating manual
Daikin Altherma 3 R ECHO
English

List of contents

List of contents
1 General safety precautions 3
1.1 Particular safety instructions ..................................................... 3
1.1.1 Observing the instructions .......................................... 3
1.1.2 Meaning of warnings and symbols.............................. 4
1.2 Safety instructions for installation and operation....................... 4
1.2.1 General ....................................................................... 4
1.2.2 Intended use ............................................................... 5
1.2.3 Installation room.......................................................... 5
1.2.4 Electrical installation ................................................... 6
1.2.5 Requirements for heating and storage water.............. 6
1.2.6 Heating system and sanitary connection .................... 6
1.2.7 Operation .................................................................... 6
1.3 Maintenance, troubleshooting and decommissioning ............... 6
1.4 Warranty conditions................................................................... 7
2 Product description 7
2.1 Design and components............................................................ 7
2.2 Function of the 3‑way changeover valves ................................. 10
3 Set-up and installation 10
3.1 Dimensions and connection dimensions ................................... 11
3.2 Transport and delivery............................................................... 12
3.3 Installing the heat pump ............................................................ 12
3.3.1 Selecting the installation site....................................... 12
3.3.2 Installing the device .................................................... 12
3.4 Preparing the device for installation .......................................... 13
3.4.1 Remove the front screen............................................. 13
3.4.2 Remove the protective cover ...................................... 13
3.4.3 Moving the switch box to the service position............. 14
3.4.4 Open the switch box ................................................... 14
3.4.5 Removing the bottom thermal insulation..................... 14
3.4.6 Opening the air purge valve........................................ 15
3.4.7 Aligning the connections of the heating inflow and
return flow ................................................................... 15
3.4.8 Making the hood opening............................................ 16
3.4.9 Installing the rotary switch of the controller................. 17
3.4.10 Securing the hood ....................................................... 17
3.5 Installing optional accessories................................................... 17
3.5.1 Installation of electric backup heater (EKBUxx).......... 17
3.5.2 Installation of the external heat generator connection
set (EKBUHSWB) ....................................................... 17
3.5.3 Installation of the DB connection kit............................ 18
3.5.4 Installation of the P connection kit .............................. 18
3.6 Water connection ...................................................................... 18
3.6.1 Minimum water volume ............................................... 19
3.6.2 Connecting hydraulic lines .......................................... 19
3.6.3 Connecting the drain................................................... 20
3.7 Electrical connection ................................................................. 20
3.7.1 Overall connection diagram ........................................ 21
3.7.2 Position of the PCBs and terminal strips..................... 22
3.7.3 Mains connection ........................................................ 22
3.7.4 General information on the electrical connection........ 22
3.7.5 Connecting the heat pump outdoor unit...................... 22
3.7.6 Connecting the outdoor temperature sensor
(optional) ..................................................................... 23
3.7.7 External switching contact .......................................... 23
3.7.8 EBA (external requirement request) ........................... 23
3.7.9 Connecting an external heat generator....................... 24
3.7.10 Connecting the room thermostat................................. 24
3.7.11 Connection of optional RoCon system components ... 25
3.7.12 Connecting the HP convector ..................................... 25
3.7.13 Connecting switching contacts (AUX outputs) ............ 26
3.7.14 Low rate mains connection (HT/NT) ........................... 26
3.7.15 Connecting an intelligent controller (Smart Grid - SG) 27
3.8 Connection for refrigerant........................................................... 27
3.8.1 Laying refrigerant piping .............................................. 27
3.8.2 Pressure test and filling the refrigerant circuit.............. 27
3.9 Filling the system........................................................................ 28
3.9.1 Checking the water quality and adjusting the
manometer................................................................... 28
3.9.2 Filling hot water heat exchangers ................................ 28
3.9.3 Filling the storage tank................................................. 28
3.9.4 Filling the heating system ............................................ 28
4 Configuration 29
5 Check list for start-up 30
5.1 Requirements ............................................................................. 30
5.2 Commissioning at low ambient temperatures ............................ 30
5.3 Bleeding the hydraulic system.................................................... 30
5.4 Checking the minimum flow ....................................................... 31
5.5 Start screed drying (only if required) .......................................... 31
5.6 Commissioning checklist ............................................................ 31
5.7 Handover to the operating company .......................................... 32
6 Technical data 33
6.1 Information on the type plate...................................................... 33
6.2 Characteristic lines ..................................................................... 33
6.2.1 Sensor characteristic lines ........................................... 33
6.2.2 Characteristic curves for pumps .................................. 34
6.3 Tightening torques...................................................................... 34
6.4 Minimum floor area and ventilation openings............................. 34
6.5 Electrical connection diagram .................................................... 36
6.6 Piping diagram for refrigerant circuit .......................................... 38
Installation and operating manual
2
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
1 General safety precautions

1.1 Particular safety instructions

1 General safety precautions

WARNING
Devices that have not been set up and installed correctly can impair the function of the device and/or cause serious or fatal injury to the user.
▪ Work on the indoor unit (such as set-
up, servicing, connection and initial commissioning) must only be carried out by persons who are authorised and who have successfully completed qualifying technical or vocational training, and who have taken part in advanced training sessions recognised by the relevant responsible authorities for the specific activity. These include, in particular,
certified heating engineers, qualified electricians and HVAC specialists who, because of their professional training and expert knowledge, have experience in the
professional installation and maintenance of heating, cooling and air conditioning systems as well as hot water storage tanks.
WARNING
Disregarding the following safety instructions may result in serious physical injury or death.
▪ This device may only be used by
children aged 8 and above and by persons with restricted physical, sensory or mental capabilities or with a lack of experience and knowledge if they are under supervision or if they have been instructed in the safe use of the equipment and understand the dangers arising from it. Children must not play with the device. Cleaning and user maintenance must not be carried out by children without supervision.
▪ Establish the power supply in
accordance with IEC60335‑1, via a separate isolator that separates all poles with a contact opening distance and that provides full disconnection in accordance with overvoltage categoryIII.
▪ All electrical work must only be
carried out by electrically qualified experts and with consideration of the local and national regulations and the instructions in this manual. Ensure that a suitable electrical circuit is used. Insufficient load capacity of the electrical circuit or improperly executed connections can result in electric shock or fire.
▪ The customer must install a pressure
relief device with a rated over­pressure of less than 1.0MPa (10bar). The connected drain line must have a continuous gradient and a free outlet in a frost-free environment (see "3.3Installing the
heat pump"[412]).
▪ Water may drip out of the drain line of
the pressure relief device. The drain opening must be left open to the atmosphere.
▪ The pressure relief device must be
operated regularly in order to remove scale deposits and to make sure it is not blocked.
▪ The storage tank and hot water circuit
can be drained. The instructions in "Temporary decommissioning" in the reference manual for the fitter must be complied with.

1.1.1 Observing the instructions

▪ The original documentation is written in German. All other
languages are translations.
▪ Please read this manual carefully and thoroughly before
proceeding with the installation or modification of the heating system.
Daikin Altherma EHS(X/H)(B)-D Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
Installation and operating manual
3
1 General safety precautions
▪ The precautionary measures described in this document cover
very important topics. Follow them meticulously.
▪ The installation of the system, and all activities described in this
manual and the applicable documents for the installer must be carried out by an approved installer.
Documentation set
This document is part of a documentation set of other applicable documents. The complete set comprises:
▪ Installation manual for the indoor unit (format: paper – included in
the indoor unit scope of delivery)
▪ Operating manual for the indoor unit (format: paper – included in
the indoor unit scope of delivery)
▪ Operating manual for the heat pump (format: paper – included in
the indoor unit scope of delivery)
▪ Installation manual for the outdoor unit (format: paper – included
in the outdoor unit scope of delivery)
▪ Installation instructions for optional components (format: paper –
included in the scope of delivery of the respective component)
▪ Installer reference guide of the indoor unit (format: digital)
▪ Installer reference guide of the outdoor unit (format: digital)
The reference guides contain the complete set of technical data, a detailed description of best practices and information on maintenance, troubleshooting and decommissioning.
The digital documents and the latest editions of the supplied documentation are available on the regional Daikin website or, on request, from your dealer. The Daikin website is easy to access using the QR code on your device.

1.1.2 Meaning of warnings and symbols

Warnings in this manual are classified according into their severity and probability of occurrence.
DANGER
Indicates an immediate danger.
Disregarding this warning can lead to serious injury or death
WARNING
Indicates a potentially dangerous situation
Disregarding this warning may result in serious physical injury or death.
CAUTION
Indicates a situation which may cause possible damage
Disregarding this warning can cause damage to property and the environment and result in minor injuries.
This symbol identifies user tips and particularly useful information, but not warnings or hazards
Special warning signs
Some types of danger are represented by special symbols.
Electric current
Danger of explosion
Risk of burns or scalds
Validity
Some information in this manual has limited validity. The validity is highlighted by a symbol.
Heat pump outdoor unit
Heat pump indoor unit
FWXV-ATV3
Observe the specified tightening torque
Only applies to devices with unpressurised solar system connection (DrainBack).
Only applies to devices with a bivalent solar system connection (Biv).
Only applies to indoor units with cooling function
Handling instructions
1 Handling instructions are shown as a list. Actions where the
sequential order must be adhered to are numbered.

1.2 Safety instructions for installation and operation

1.2.1 General

WARNING
Devices that have not been set up and installed correctly can impair the function of the device and/or cause serious or fatal injury to the user.
▪ Work on the indoor unit (such as set-
up, servicing, connection and initial commissioning) must only be carried out by persons who are authorised and who have successfully completed qualifying technical or vocational training, and who have taken part in advanced training sessions recognised by the relevant responsible authorities for the specific activity. These include, in particular,
certified heating engineers, qualified electricians and HVAC specialists who, because of their professional training and expert knowledge, have experience in the
professional installation and maintenance of heating, cooling and air conditioning systems as well as hot water storage tanks.
Risk of poisoning
Installation and operating manual
4
▪ Switch off the external main switch
before starting any work on the indoor unit and secure against being switched on inadvertently.
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
1 General safety precautions
▪ Do not leave any tools or other
objects below the hood of the device after finishing installation or maintenance work.
Avoid danger
The indoor unit conforms to the state of the art and meets all recognised technical requirements. However, improper use can lead to serious injuries or death, as well as causing material damage. To prevent such risks, only install and operate the devices:
▪ as stipulated and in perfect condition,
▪ with an awareness of the safety and hazards involved.
This assumes knowledge and use of the contents of this manual, the relevant accident prevention regulations and the recognised safety­related and occupational medical rules.
Before working on the hydraulic system
▪ Work on the system (such as set-up, connection and initial
commissioning, for example) must only be carried out by persons who are authorised, who have successfully completed qualifying technical or vocational training for the respective activity and who have taken part in advanced training sessions recognised by the relevant responsible authority.
▪ When carrying out any work on the system, switch off the main
switch and secure against being switched on inadvertently.
▪ Seals must not be damaged or removed.
▪ Make sure that the safety valves comply with the requirements of
EN 12828 when connecting on the heating side and with the requirements of EN 12897 when connecting on the domestic water side.

1.2.2 Intended use

The indoor unit may only be used for domestic hot water preparation, as a room heating system and, depending on its design, as a room cooling system.
The indoor unit must only be installed, connected and operated according to the indications in these instructions.
Only the use of a suitable outdoor unit approved by the manufacturer is permitted.
 1‒1 Permissible combinations
EHSX04P30D27
EHSX04P50DA7
EHSXB04P30D27
EHSXB04P50DA7
EHSH04P30D27
EHSHB04P30D27
ERGA04DAV3
ERGA06DAV3
ERGA08DAV3
ERGA04DAV3A
ERGA06DAV3A
ERGA08DAV3A
ERGA04DAV37
EHSX08P30D27
EHSX08P50DA7
EHSXB08P30D27
EHSXB08P50DA7
EHSH08P30D27
EHSH08P50DA7
EHSHB08P30D27
EHSHB08P50DA7
Any other use or use beyond the intended use is considered improper use. The operator alone bears responsibility for any resulting damage.
Intended use also includes compliance with the maintenance and service conditions. Spare parts must at least satisfy the technical requirements defined by the manufacturer. This is the case, for example, with original spare parts.

1.2.3 Installation room

WARNING
The plastic wall of the storage tank on the indoor unit can melt under the effects of external heat (>80°C) and, in the extreme case, can catch fire.
▪ Only install the indoor unit at a
minimum clearance of 1m from other heat sources (>80°C) (e.g. electrical heater, oil heater, chimney) and combustible materials.
CAUTION
▪ Only install the indoor unit if sufficient
load-carrying capacity of the ground of 1050kg/m2 plus safety margin is ensured. The ground must be flat, horizontal and level.
Outdoor set up is not permissible.
▪ Set-up in an explosion-risk
environment is not permissible.
▪ The electronic control system must
not be exposed to weather effects such as rain and snow under any circumstances.
▪ The storage tank may not be
exposed to continuous direct sunlight, as the UV radiation and the effects of the weather will damage the plastic.
▪ The indoor unit must be installed
protected from frost.
▪ Make sure that the supply company
does not provide corrosive domestic water. Suitable water treatment may be required.
▪ Always ensure the minimum distances from walls and other
objects ("3.1Dimensions and connection dimensions"[411]).
▪ Observe the special installation requirements of the R32
refrigerant (see "3.3.1Selecting the installation site"[412]).
Daikin Altherma EHS(X/H)(B)-D Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
Installation and operating manual
5
1 General safety precautions
CAUTION
If a DrainBack solar heating
system is connected: Install the indoor unit far enough under the solar panels to allow complete emptying of the solar heating system. (Follow the instructions in the DrainBack solar heating system manual.) An insufficient height difference may lead to destruction of the DrainBack solar heating system.
▪ The indoor unit must not be operated
in rooms with ambient temperatures of more than 40°C.

1.2.4 Electrical installation

▪ Electrical installations may only be carried out by electrical
technicians and in compliance with valid electrical guidelines as well as the specifications of the responsible energy supply company.
▪ Compare the mains voltage indicated on the nameplate with the
supply voltage before connecting to the mains.
▪ Before beginning work on live parts, disconnect them from the
power supply (switch off main switch, remove fuse) and secure against unintentional restart.
▪ Device covers and service panels must be replaced as soon as
the work is completed.

1.2.5 Requirements for heating and storage water

Damage due to deposits and corrosion: observe the relevant technical rules to avoid corrosion products and deposits.
Minimum requirements regarding the quality of filling and top-up water:
▪ Water hardness (calcium and magnesium, calculated as calcium
carbonate): ≤3mmol/l
▪ Conductivity: ≤1500 (ideal ≤100)μS/cm
▪ Chloride: ≤250mg/l
▪ Sulphate: ≤250mg/l
▪ pH value: 6.5 – 8.5
Measures for desalination, softening or hardness stabilisation are necessary if the filling and top-up water have a high total hardness (>3 mmol/l – total of the calcium and magnesium concentrations, calculated as calcium carbonate). We recommend the use of Fernox KSK limescale and corrosion protector. For other properties deviating from the minimum requirements, suitable conditioning measures are necessary to maintain the required water quality.
Using filling water and top-up water which does not meet the stated quality requirements can cause a considerably reduced service life of the equipment. The responsibility for this lies solely with the operator.
INFORMATION
If an optional external heat generator is connected, these minimum requirements also apply to the filling and supplementary water for this heating circuit.

1.2.6 Heating system and sanitary connection

▪ Create a heating system according to the safety requirements of
EN12828.
▪ The plumbing connection must comply with the requirements of
EN 12897. The requirements of the following must also be observed:
▪ EN 1717 – Protection against pollution of potable water
installations and general requirements of devices to prevent pollution by backflow
▪ EN61770 – Electric appliances connected to the water mains –
Avoidance of backsiphonage and failure of hose-sets
▪ EN 806 – Specifications for installations inside buildings
conveying water for human consumption
▪ and, in addition, the country-specific legislation.
During operation of the indoor unit with an auxiliary heat source, the storage tank temperature may exceed 65°C, above all when solar energy is used.
▪ For this reason, some form of scalding protection needs to be
included when you install the system (hot water mixing device, e.g. VTA32).
INFORMATION
The domestic water quality must comply with the EU Guideline 98/83 EC and the regionally-applicable regulations.
If the indoor unit is connected to a heating system with steel pipes, radiators or non-diffusion-proof floor heating pipes, sludge and chips can enter the hot water storage tank and cause blockages, local overheating or corrosion damage.
▪ To prevent possible damage, install a dirt filter or sludge separator
into the heating return flow of the system (SAS 1 or SAS 2).
▪ The dirt filter must be cleaned at regular intervals.

1.2.7 Operation

The indoor unit:
▪ Do not operate until all installation and connection work is
completed.
▪ Only operate with a completely full storage tank (check level
indicator) and heating circuit.
▪ Operate at a maximum pressure of 3bar.
▪ Only connect with a pressure reducer on the external water supply
(supply line).
▪ Only operate if the protective cover is installed.
The specified servicing intervals should be adhered to and inspection work must be carried out.

1.3 Maintenance, troubleshooting and decommissioning

Work for maintenance, troubleshooting and decommissioning must not be carried out without knowledge of the relevant safety precautions and in the event of disposal of the country-specific guidelines. Please refer to the corresponding information in the reference manual for the fitter.
Recommendations for disposal
We designed the indoor unit in an environmentally friendly manner. During the disposal process, the only waste created is that which can be used for material or thermal recycling. The materials used that are suitable for recycling can be sorted into individual types.
Installation and operating manual
6
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
Thanks to the environmentally friendly design of the indoor unit, we have established requirements to ensure environmentally friendly disposal. Proper disposal in compliance with the respective national regulations of the country of use is the responsibility of the user/owner.
The designation of the product means that electrical and electronic products may not be disposed of together with unsorted domestic waste.
Proper disposal in compliance with the respective national regulations of the country of use is the responsibility of the user/ owner.
▪ Disassembly of the system, handling of refrigerant, oil and other
parts may only be carried out by a qualified fitter.
▪ Disposal may only be carried out by an organisation that
specialises in reuse, recycling and recovery.
Further information is available from the installation company or the responsible local authorities.

2 Product description

2 Product description

2.1 Design and components

Outside of the device

1.4 Warranty conditions

The legal guarantee conditions fundamentally apply. Our more extensive warranty conditions can be found in the Internet. Ask your suppliers if necessary.
Incorrect installation, commissioning and maintenance will void the warranty. If you have any questions, please contact our customer service.
Warranty claims can only be made if the annual maintenance work is demonstrably carried out regularly according to the information in the installer reference guide.
 2‒1 Design and components – Outside of the device
a Status indicator b Protective cover c Mount for handle d Filling and draining connection or solar return flow
connection
e Type plate
Daikin Altherma EHS(X/H)(B)-D Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
Installation and operating manual
7
2 Product description
Upper side of the device
o Combined filling and draining valve (heating circuit) p Storage tank temperature sensor q Expansion vessel connection
r Switch box
s, t Manual air purge valves
3UVB1 3‑way changeover valve (internal heat generator circuit)
3UV DHW 3‑way changeover valve (hot water/heating)
DS Pressure sensor
FLS FlowSensor
tRReturn temperature sensor
t
Backup heater inflow temperature sensor
V,BH
Internal structure…04P30D.../…08P30D...
 2‒2 Design and components – Top of the device
a Solar flow
b Cold water connection
c Hot water
d Heating flow
e Heating return flow
f Circulation pump g Pressure relief valve h Automatic vent valve
i Connection for optional electrical backup heater EKBUxx
j Fill level indicator (tank water) k Plate heat exchanger
l Connection for refrigerant fluid line
m Connection for refrigerant gas line
n Ball valve (heating circuit)
Installation and operating manual
8
2‒3 Design and components Internal
structure ...04P30D.../...08P30D... (Biv)
a Solar flow b Cold water connection c Hot water d Heating flow e Heating return flow
f Circulation pump
g Pressure relief valve
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
2 Product description
h Storage tank (polypropylene, double-walled jacket with
PUR hard foam heat insulation)
i Filling and draining connection or solar return flow
connection
j Mount for solar controller or handle
k Heat exchanger (stainless steel) for domestic hot water
heating
l Heat exchanger (stainless steel) for storage tank
charging or heating support
m Biv heat exchanger (stainless steel) for charging with
external heat generator (e.g. pressurised solar system)
n Connection for optional electrical backup heater EKBUxx o Fill level indicator (tank water) p Optional: electric backup heater (EKBUxx) q Submersible sensor sleeve for storage tank temperature
sensor t
r Pressureless storage tank water
DHW1
and t
DHW2
s Solar zone
t Hot water zone u Safety overflow connection v Mount for handle
w Protective cover
x Solar return flow y Biv flow
z Biv return flow aa Plate heat exchanger ab Connection for refrigerant fluid line ac Connection for refrigerant gas line ad Optional: Solar control and pump unit ae Circulation stop valve (accessory)
3UVB1 3‑way changeover valve (internal heat generator circuit)
3UV DHW 3‑way changeover valve (hot water/heating)
DS Pressure sensor
FLS FlowSensor
MAG Expansion vessel (on the building side)
t
, t
DHW1
Storage tank temperature sensor
DHW2
tRReturn temperature sensor
t
Backup heater inflow temperature sensor
V,BH
Internal structure…04P50D…/…08P50D...
Daikin Altherma EHS(X/H)(B)-D Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
2‒4 Design and components - Internal
structure ...04P50D/...08P50D… (Biv)
a Solar flow b Cold water connection c Hot water d Heating flow e Heating return flow
f Circulation pump g Pressure relief valve h Storage tank (polypropylene, double-walled jacket with
PUR hard foam heat insulation)
i Filling and draining connection or solar return flow
connection
j Mount for solar controller or handle k Heat exchanger (stainless steel) for domestic hot water
heating
l Heat exchanger (stainless steel) for storage tank
charging or heating support
m Biv heat exchanger (stainless steel) for charging with
external heat generator (e.g. pressurised solar system)
n Connection for optional electrical backup heater EKBUxx o Fill level indicator (tank water)
Installation and operating manual
9

3 Set-up and installation

p Optional: electric backup heater (EKBUxx) q Submersible sensor sleeve for storage tank temperature
sensor t
r Pressureless storage tank water
s Solar zone
t Hot water zone u Safety overflow connection v Mount for handle
w Protective cover
x Solar return flow y Biv flow
z Biv return flow aa Plate heat exchanger ab Connection for refrigerant fluid line ac Connection for refrigerant gas line ad Optional: Solar control and pump unit ae Circulation stop valve (accessory)
af Solar flow layering pipe
3UVB1 3‑way changeover valve (internal heat generator circuit)
3UV DHW 3‑way changeover valve (hot water/heating)
DS Pressure sensor
FLS FlowSensor
MAG Expansion vessel (on the building side)
t
, t
DHW1
Storage tank temperature sensor
DHW2
tRReturn temperature sensor
t
Backup heater inflow temperature sensor
V,BH
DHW1
and t
DHW2

2.2 Function of the 3‑way changeover valves

3 Set-up and installation
WARNING
Cooling systems (heating pumps), climate control systems and heating devices that have been set up and installed incorrectly can both endanger human life and health and be impaired in their function.
▪ Work on the indoor unit (such as set-up, repair,
connection and initial commissioning, for example) must only be carried out by persons who are authorised, who have successfully completed qualifying technical or vocational training for the respective activity and who have taken part in advanced training sessions recognised by the relevant responsible authority. These include, in particular, certified heating engineers, qualified electricians and HVAC specialists who, because of their professional training and expert knowledge, have experience in the professional installation and maintenance of heating, cooling and air conditioning systems and heat pumps.
Incorrect set-up and installation would render the manufacturer's guarantee for the unit void. If you have questions, please contact our Technical Customer Service.
 2‒5 Function of 3‑way changeover valve
Installation and operating manual
10
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
3 Set-up and installation

3.1 Dimensions and connection dimensions

Dimensions …04P30D.../…08P30D...
Dimensions …04P50D…/…08P50D…
 3‒1 Dimensions …04P30D.../…08P30D...
a Solar flow b Domestic cold water c Hot water d Heating flow e Heating return flow
f Connection for refrigerant gas line g Connection for refrigerant fluid line h Biv flow (…Biv type only)
i Biv return flow (…Biv type only) A front B rear
Daikin Altherma EHS(X/H)(B)-D Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
 3‒2 Dimensions …04P50D…/…08P50D…
a Solar flow b Domestic cold water c Hot water d Heating flow e Heating return flow
f Connection for refrigerant gas line g Connection for refrigerant fluid line h Biv flow (…Biv type only)
i Biv return flow (…Biv type only)
A front B rear
Installation and operating manual
11
3 Set-up and installation

3.2 Transport and delivery

WARNING
When unfilled, the indoor unit is top-heavy and could tip over during transport, which could put persons in danger or damage the device.
▪ Secure the indoor unit well, transport carefully, use the
handles.
The indoor unit is delivered on a pallet. All industrial trucks, such as lifting trucks and forklift trucks, are suitable for transport.
Scope of delivery
▪ Indoor unit (pre-mounted),
▪ Bag of accessories,
▪ Document pack.
Installation area
▪ The base must be level and smooth and have sufficient ground
load-bearing capacity of 1050kg/m² plus safety factor. Install a
pedestal if necessary.
▪ Observe the installation dimensions (see "3.1 Dimensions and
connection dimensions"[411]).
Minimum distance
DANGER: RISK OF BURNING/SCALDING
The plastic wall of the storage tank on the indoor unit can melt under the effects of external heat (>80°C) and, in the extreme case, can catch fire.
▪ Only install the indoor unit at a minimum clearance of
1 m from other heat sources (>80°C) (e.g. electrical heater, oil heater, chimney) and combustible material.
CAUTION
If the indoor unit is not installed at a sufficient distance below the flat solar panels (the top edge of the storage tank is higher than the bottom edge of the solar panels), the unpressurised solar system in the outdoor area will not be able to drain completely.
▪ When a solar connection is used, install the indoor unit
low enough under the flat solar panels (observe the minimum gradient of the solar connection lines).
Recommended minimum distances:
From the wall: (rear) ≥100mm, (sides) ≥500mm
From the ceiling: ≥1200mm, at least 480mm.
 3‒3 Scope of delivery
a Handles (only required for transport) b Cover screen c Hose connecting piece for safety overflow d Fitting spanner e Ball valve
f Flat gasket g O‑ring h Cable tie
i Securing clip
j Venting hose k Condensate drain hose
l Controller rotary switch
m Hood screws
n Document pack
For further accessories for the indoor unit, see price list.

3.3 Installing the heat pump

3.3.1 Selecting the installation site

CAUTION
If the total refrigerant charge in the system is ≥1.84kg, it is essential to comply with additional requirements for minimum footprint and minimum ventilation openings. Observe "6.4 Minimum floor area and ventilation
openings"[434].
Information on the total refrigerant charge can be found on the type plate of the outdoor unit. Please follow the installation instructions.
The installation site of the indoor unit must meet the minimum requirements below (see also "1.2.3Installation room"[45]).
Distances from the outdoor unit:
When selecting the installation location, the data in the table "  3‒1
"[412] must be taken into account.
 3‒1 
Maximum refrigerant piping length between the indoor and outdoor units
Minimum refrigerant piping length between the indoor and outdoor units
Maximum height difference between the indoor and outdoor units
30m
3m
20m

3.3.2 Installing the device

WARNING
When unfilled, the indoor unit is top-heavy and could tip over during transport, which could put persons in danger or damage the device.
▪ Secure the indoor unit well, transport carefully, use the
handles.
Precondition
▪ The installation site complies with applicable country-specific
regulations and meets the minimum requirements described in
"3.3.1Selecting the installation site"[412].
Set-up
1 Remove the packaging and dispose of it in an environmentally
sound manner.
2 Pull off the cover screens from the storage tank (item b) and
unscrew the threaded fittings (item c) from the openings at which the handles are to be fitted.
3 Screw the handles (item a) into the now uncovered threaded
holes.
Installation and operating manual
12
Daikin Altherma EHS(X/H)(B)-D
Daikin Altherma 3 R ECHO
008.1451099_00 – 07/2020
Loading...
+ 28 hidden pages