11.3 Data bus addresses ................................................................... 53
List of keywords54
Operating instructions
2
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
1 General safety precaution
1General safety precaution
1.1Particular safety instructions
WARNING
Heating devices that are not set up and
installed correctly can impair the
function of the heating device and/or
cause serious or fatal injury to the user.
▪ Work on the heat generator (such as
set-up, servicing, connection and
initial start-up) must only be carried
out by persons who are authorised
and who have successfully
completed qualifying technical orvocational training and who have
taken part in advanced training
sessions recognised by the relevant
responsible authorities for the specific
activity. They include, in particular,
certified heating engineers, qualified
electricians and HVAC specialists
who, because of their professional
training and their expert
knowledge, have experience in the
professional installation and
maintenance of heating systems, oil
and gas installations and hot water
storage systems.
▪ Only operate the heat generator
when it is in perfect condition with the
protective hood closed.
WARNING
Disregarding the following safety
instructions may result in serious
physical injury or death.
▪ This device may only be used by
children aged 8 and above and by
persons with restricted physical,
sensory or mental capabilities or with
a lack of experience and knowledge if
they are under supervision or if they
have been instructed in the safe use
of the equipment and understand the
dangers arising from it. Children
must not play with the device.
Cleaning and user maintenance
must not be carried out by children
without supervision.
▪ Establish the power supply in
accordance with IEC60335‑1, via a
separate isolator that separates all
poles with a contact opening distance
and that provides full disconnection in
accordance with overvoltage
categoryIII.
▪ All the electrical work must only be
carried out by electrically qualified
experts and with consideration of the
local and national regulations, and
the instructions in this manual. Check
that a suitable electrical circuit is
being used. Insufficient load capacity
of the electrical circuit or improperly
executed connections can result in
electric shock or fire.
1.1.1Observing the instructions
▪ The original documentation is written in German. All other
languages are translations.
▪ Please read this manual carefully and thoroughly before
proceeding with the installation or modification of the heating
system.
▪ The precautionary measures described in this document cover
very important topics. Follow them meticulously.
▪ The installation of the system, and all activities described in this
manual and the applicable documents for the installer must be
carried out by an approved installer.
Documentation set
This document is part of a documentation set of other applicable
documents. The complete set comprises:
▪ Installation manual for the Daikin Altherma indoor unit –
subsequently referred to as "indoor unit " (format: paper –
included in the indoor unit scope of delivery)
▪ Operating manual for the indoor unit (format: paper – included in
the indoor unit scope of delivery)
▪ Operating manual for the heat pump (format: paper – included in
the indoor unit scope of delivery)
▪ Installation manual for the outdoor unit (format: paper – included
in the outdoor unit scope of delivery)
▪ Installation instructions for optional components (format: paper –
included in the scope of delivery of the respective component)
▪ Installer reference guide of the indoor unit (format: digital)
▪ Installer reference guide of the outdoor unit (format: digital)
▪ Operating instructions for controller RoCon HP, EHS157034,
EHS157068 (status 04/2017) (format: digital)
The reference guides contain the complete set of technical data, a
detailed description of best practices and information on
maintenance, troubleshooting and decommissioning.
The digital documents and the latest editions of the supplied
documentation are available on the regional Daikin website or, on
request, from your dealer. The Daikin website is easy to access
using the QR code on your device.
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
3
1 General safety precaution
1.1.2Meaning of warnings and symbols
Warnings in this manual are classified according into their severity
and probability of occurrence.
DANGER
Indicates an immediate danger.
Disregarding this warning can lead to serious injury or
death.
WARNING
Indicates a potentially dangerous situation.
Disregarding this warning may result in serious physical
injury or death.
CAUTION
Indicates a situation which may cause possible damage.
Disregarding this warning can cause damage to property
and the environment and result in minor injuries.
This symbol identifies user tips and particularly useful
information, but not warnings or hazards
Special warning signs
Some types of danger are represented by special symbols.
Electric current
1.2.2Intended use
The RoCon+ HP1 controller may only be used in the indoor units
specified on the title page that are approved for the control system.
The RoCon+ HP1 controller must only be operated in accordance
with the specifications in these instructions.
Any other use or use beyond the intended use is considered
improper use. The operator alone bears responsibility for any
resulting damage.
For any work on the equipment that extends above and beyond the
operation of the regulating system, the details provided in the
supplementary documents must be observed, particularly with
regard to safety instructions.
Documentation
The technical documentation included in the scope of supply is a
constituent part of the equipment. It must be stored in such a way
that it can be consulted at any time by the operator or technicians.
Risk of burns or scalds
General description
1 Handling instructions are shown as a list. Actions where the
sequential order must be adhered to are numbered.
[Language]: Parameters are shown in square brackets.
"Operating mode", "Deutsch": Available menu names and parameter
setting options are shown in quotation marks.
[→ Main menu]: The position of menus and functions is shown in
square brackets with →.
1.2Safety instructions for installation
and operation
1.2.1General
▪ For any work on the equipment that extends above and beyond
the operation of the regulating system, the details provided in the
supplementary documents must be observed, particularly with
regard to safety instructions.
Avoid danger
The indoor unit conforms to the state of the art and meets all
recognised technical requirements. However, improper use can lead
to serious injuries or death, as well as causing material damage.
To avoid hazards, only operate the indoor unit:
▪ as stipulated and in perfect condition,
▪ with an awareness of the safety and hazards involved.
This assumes knowledge and use of the contents of this manual, all
applicable documents, the relevant accident prevention regulations
as well as the recognised safety-related and occupational health
rules.
Display representation of the RoCon+HP1 controller
Certain screen displays or menu items may deviate from those
shown in these instructions depending on the national or equipment
variant of the indoor unit or the user status logged onto the
controller.
Operating instructions
4
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
2 Product description
2Product description
INFORMATION
The RoCon+HP1 controller is part of the indoor unit.
It consists of the switching panel RoCon BM2C PCB to
which the actuators and sensors as well as other
components in the regulating system are connected and
the RoCon+B1 control panel.
These operating instructions only explain the functions and
possible settings of the controller. More information on the
switch box and other equipment components can be found
in the supplementary documents.
The electronic, digital controller is able to automatically control all
heating and hot water functions for a direct HC, a storage loading
circuit and also further HCs via optionally connectible mixer
modules, depending on the heating device.
It performs all safety management for the indoor unit. This executes
a safety switch-off in the event of a water shortage or undefined
operating states. A corresponding error message shows the operator
all the information regarding fault causes.
All function settings for the indoor unit and the optional RoCon
devices that are connected via the data bus are undertaken with the
control elements of the integrated RoCon+ B1 control panel and
shown on the plain text display with coloured backlighting.
The following additional, optional devices can be connected to the
indoor unit via the controller data bus:
▪ RoConU1 (EHS157034) room station
▪ RoConM1 (EHS157068) mixer module
In addition, the RoCon+ HP1 controller has a freeze-up protection
function for the direct HC and the storage tank charging circuit as
well as an automatic function for heating support (integration of an
auxiliary heat source such as a wood-burning boiler or solar system).
The potential-free AUX switching contact can be used to carry out
different control functions in conjunction with external devices
(request from an external heat generator, changeover to bivalent
operation, external status indicator, etc.).
In addition, it also has several inputs for assessing external control
contacts (external operating mode switching or heat request, Smart
Grid and low rate EVU functions
The optional outdoor temperature sensor installed on the north side
of the building can be used to further optimise the weathercompensated leaving water temperature control.
If the optional RoCon G1 (EHS157056) gateway is installed and
connected to the Internet, the indoor unit can be conveniently
monitored and operated by remote control using a mobile phone
(app).
Initial commissioning of the heating system is described in the
installation instructions for the indoor unit.
Certain menu items of the RoCon+ HP1 controller are only
accessible to the heating expert. This security measure ensures that
no undesirable malfunctions arise during operation of the system
through incorrect settings.
All settings for the assigned HC can be made with the RoConU1
(EHS157034) room station in the same way as on the control panel.
If the terminal function is activated, all operating possibilities that are
available on the integrated control panel are available with the
exception of certain special functions (e.g. manual operation).
After appropriate assignment, a connected RoConM1 (EHS157068)
mixer module is also operated using the RoCon+ B1 control panel
and/or the RoConU1 (EHS157034) room station.
(1)
).
2.1Temporary shutdown
CAUTION
A heating system that is shut down can freeze in the event
of frost and may suffer damage.
▪ Drain the heating system that is shut down if there is
danger of frost.
▪ If the heating system is not drained, the power supply
must be ensured and the external main switch must
remain switched on if there is a danger of frost.
If the heat pump is not required for a lengthy period, it can be
temporarily decommissioned.
However, we recommend not to disconnect the system from the
power supply but merely to switch it to "Standby mode"
The system is then protected from frost. The pumps and valve
protection functions are active.
If it is not possible to guarantee the power supply when there is
danger of frost,
▪ completely drain the indoor unit on the water side, or
▪ apply suitable antifreeze measures to the connected heating
system and hot water storage tank (e.g. draining).
INFORMATION
If there is only a risk of frost for a few days when the power
supply is not reliable, it is not necessary to empty the
indoor unit due to the very good thermal insulation,
provided that the storage tank temperature is regularly
monitored and does not fall below +3°C.
However, this provides no freeze-up protection for the
connected heat emitter.
(1)
The energy supply company (EVU) sends signals that are used for controlling the power mains utilisation and that have an influence on the
cost of the power and availability.
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
5
3 Operation
3Operation
3.1General
DANGER: RISK OF ELECTROCUTION
If electrical components come into contact with water, this
can cause an electric shock as well as cause potentially
fatal burns or injuries.
▪ The displays and keys of the controller must be
protected against the effects of moisture.
▪ To clean the controller, use a dry cotton cloth. The use
of aggressive cleaning agents and other fluids can
cause damage to devices or lead to electric shock.
INFORMATION
The heat pump makes the most effective use of energy at
the lowest possible return and hot water target
temperatures.
If an external heat generator (e.g. the optional backup
heater) is activated at target leaving water temperatures
above 50°C, the efficiency (COP) of the heat pump can
deteriorate (depending on the outside temperature).
3.2Display and operating elements
3.2.1Status indicator
The LEDs of the status indicator light up or flash to indicate the
operating mode of the device.
3‒1 Status indicator
LEDModeDescription
Flashes blueStandbyThe device is not in operation.
Lights up blueOperationThe device is in operation.
Flashes redErrorAn error has occurred. For further
details, see "8Errors and
faults"[447].
3.2.2Display
During normal operation the display is deactivated (completely dark).
The activity of the system is indicated by the status indicator. Each
press of the rotary button (turn, press or hold) activates the display
with the start screen.
If the start screen is active and no user input is made for
60 seconds, the display is deactivated. If no input is made by the
user at any other point in the menu for 120seconds, the system
returns to the start screen.
3.2.3Rotary button
CAUTION
Never operate the operating elements of the controller with
a hard, pointed object. This can cause damage and can
cause the controller to malfunction.
The rotary button can be used to navigate in the respective level, to
select or change the setting value and to accept this change with a
short key press.
3‒1 RoCon+B1 display and operating elements
1 Status indicator
2 Display
3 Rotary button
3‒2 Function of the rotary button
ActionResult
TurningSelect menu, select setting, make setting
PressConfirm selection, accept setting, execute
function.
Press for 2sec. Exit menu
3.2.4Start screen
The start screen provides an overview of the current operating status
of the system. From the start screen, any operation of the rotary
switch (turn, press or hold down) leads to the Main menu.
Operating instructions
6
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
3‒2 Display position on the start screen
3‒3 Display icons on the start screen
Item IconExplanation
1Date and time
2Error message
3 Operation
Item IconExplanation
10Operating mode: Standby
Operating mode: Reduce
Operating mode: Heating
Operating mode: Cooling
Operating mode: Summer
Operating mode: Automatic 1
Operating mode: Automatic 2
Operating mode: Emergency
11Special program: Party
Special program: Absent
Special program: Holiday
Special program: Public holiday
3Only with connected room unit: Room
temperature
4Hot water temperature
5Underfloor heating leaving water temperature
Convector heating leaving water temperature
Radiator heating leaving water temperature
6Outside temperature
7Pressure in the HC
8Storage tank without heating rod
Storage tank with connected heating rod (off)
Storage tank with connected heating rod (on)
9No outdoor unit detected
Outdoor unit present, compressor off
Outdoor unit present, compressor on
Special program: 1 x hot water
Special program: Screed
Special program: Ventilation
12Quiet mode On
13Operating mode: Heating
Operating mode: Cooling
Operating mode: Hot water
Operating mode: Defrost
Operating mode: No request
14ExtExternal operating mode switched (Burner
blocking contact or Room thermostat)
INFORMATION
If the local control panel is used as a remote controller for
a mixer module, both the standard screen and the menu
structure are changed (see "9Mixer module"[448]).
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
7
3 Operation
3.3Operating concept
The operating concept of the controller allows quick navigation in the
menu:
▪ Clear display of information
▪ Straightforward selection of parameters
▪ Setting of setpoints and programs.
The basics of the operating concept are described in detail below
using a few examples. The operation of special functions follows the
same principle and is described in the corresponding sections if
required in "4Function"[411].
3.3.1Navigating in the menu
From the start screen, any operation of the rotary switch (turn, press
or hold down) leads to the main menu. The menu view consists of an
upper area for the menu icons of the various submenus and the
lower menu bar. The Back and Help icons are displayed in the menu
bar. Use the rotary button to switch between the icons (including the
icons in the menu bar). Multi-page menus are indicated by the page
break arrow. Use the rotary button to switch between the menu icons
on the different menu pages.
3‒3 Example: Elements in a two-page menu
1 Back icon
2 Menu bar
3 Menu icon
4 Page change arrow (for multi-page menus)
5 Help icon
Example: In the "Statistics" menu, change [→Main menu]:
1 Turn the rotary button clockwise until the "Statistics" icon (on
the second menu page) turns blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The "Statistics" submenu is called up
3.3.2Help function
A help text is available for each menu icon.
3‒4 Help function
Example: Calling up the help text for the "Hot water" menu and
stopping the help function again [→Main menu →User]:
1 Turn the rotary button clockwise until the help icon in the menu
bar turns blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The help function becomes active, the "?" symbol is
displayed on the last menu icon.
3 Turn the rotary button anticlockwise until the "?" symbol
appears on the "Hot water" icon.
4 Briefly press the rotary button to confirm ("OK").
Result: The help text for the "Hot water" is displayed.
5 Briefly press the rotary button to confirm ("OK").
Result: Exits the help text level.
6 Turn the rotary button clockwise until the help icon in the menu
bar turns blue.
7 Briefly press the rotary button to confirm ("OK").
Result: The help function is terminated.
3.3.3Navigating in lists and selecting list
entries
Lists exist as pure information lists or can be used to select a list
entry. Turning the rotary button switches between the list entries.
Multi-page lists are indicated by the page break arrow. Turn the
rotary button to switch between the list entries of the different pages.
In the case of selection lists, the currently selected list entry is
indicated by a tick. Click "OK" to select another list entry. The
corresponding setting is then accepted and the list is exited.
Operating instructions
8
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
3‒5 List with selected list entry
Example: Switch the operating mode to "Summer" [→Main menu
→Operating mode]
1 Turn the rotary button clockwise until the "Summer" list entry is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The box is ticked in the "Summer" list entry.
3 Turn the rotary button anticlockwise until the Back icon turns
blue.
4 Briefly press the rotary button to confirm ("OK").
Result: The setting is saved and the setting level is exited.
3.3.4Setting setpoints
The setpoint of a parameter can be changed within the displayed
scale. Click "OK" to save the new value. Press and hold the rotary
button to exit the setting level without saving. For some parameters
there is an "Off" setting in addition to values on the scale. This
setting can be selected by turning the rotary button anticlockwise
after the minimum value of the scale has been reached.
3 Operation
2 Briefly press the rotary button to confirm ("OK").
Result: The setting is saved and the setting level is exited.
3.3.5Setting the times
The clock function is used to set the current time.
3‒7 Setting the times
Example: Set the time to 16:04 [→ Main menu → Settings
→Display →Time]:
1 Turn the rotary button clockwise until the circle is displayed in
blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The hour hand is displayed in blue.
3 Turn the rotary button clockwise until 16:00 is displayed.
4 Briefly press the rotary button to confirm ("OK").
Result: The minute hand is displayed in blue.
5 Turn the rotary button clockwise until 16:04 is displayed.
6 Briefly press the rotary button to confirm ("OK").
Result: The Confirm icon in the menu bar is displayed in blue.
7 Briefly press the rotary button to confirm ("OK").
Result: The setting is saved and the setting level is exited.
3‒6 Display of the parameter setting
1 Minimum value
2 Default value
3 Currently selected value
4 Maximum value
Example: Set [Room temperature target 1] to 22°C [→ Main menu
→User →Room →Room temperature target 1]:
1 Turn the rotary button clockwise until 22°C is displayed.
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
3.3.6Calendar function
The calendar function is used to set the current date or the "Holiday"
and "Public holiday" time programs. The calendar function allows the
selection of a time period for the time programs.
3‒8 Setting the period with the calendar function
Operating instructions
9
3 Operation
Example: Set [Holiday] from 16 July2020 – 20July 2020 [→Main
menu →Time program →Holiday]:
1 Turn the rotary button clockwise until the month selection is
Jul2020.
2 Briefly press the rotary button to confirm ("OK").
Result: 1July is shown with a blue border.
3 Turn the rotary button clockwise until 16July is highlighted in
blue.
4 Briefly press the rotary button to confirm ("OK").
Result: 16July is shown on a grey background.
5 Turn the rotary button clockwise until 20July is highlighted in
blue.
6 Briefly press the rotary button to confirm ("OK").
Result: The setting is saved and the setting level is exited.
When a new holiday period is set, the previously set holiday period
is automatically deleted. Alternatively, the holiday setting can also be
reset.
Example: Reset the holiday setting [→Main menu →Time program
→Holiday]:
1 Turn the rotary button clockwise until the month selection is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The last selected day of the holiday is displayed with a
blue border.
3 Turn the rotary button anticlockwise until all days are shown in
white.
4 Briefly press the rotary button to confirm ("OK").
Result: The holiday setting is reset and the setting level is
exited.
3.3.7Setting the time programs
The time program function is used to set permanent time programs
(see "4.3.2Permanent time programs"[413]). This allows the daily
setting of 3switching cycles. The times can be entered separately
for each individual weekday or in blocks of "Monday to Friday",
"Saturday to Sunday" and "Monday to Sunday". The selected
switching cycles are highlighted in grey (" 3‒9 Time program
function with overview level (left) and setting level (right)" [410]) in
the overview level of the respective program.
3‒4 Structure of the permanent time programs
Time periodSwitching cycle
Single day of the week (Monday,
Tuesday ...)
Working week (Monday to
Friday)
Weekend (Saturday to Sunday)1. 06:00 to 22:00
Entire week (Monday to Sunday) 1. 06:00 to 22:00
1. 06:00 to 22:00
2. xx:xx to xx:xx
3. xx:xx to xx:xx
1. 06:00 to 22:00
2. xx:xx to xx:xx
3. xx:xx to xx:xx
2. xx:xx to xx:xx
3. xx:xx to xx:xx
2. xx:xx to xx:xx
3. xx:xx to xx:xx
INFORMATION
Time settings for a switching cycle in a weekday or block
program will also be accepted for other time periods as
long as they are for the same weekdays.
▪ The starting time in the first switching cycle is changed
from 06:00 am to 05:00 am for the individual weekday
"Monday". In the period "Monday to Friday" and
"Monday to Sunday", the first switching cycle is
automatically changed from 06:00 to 05:00.
3‒9 Time program function with overview level (left) and setting
level (right)
Example: For the [Heating circuit auto. 1] program, set switch cycles
1 and 2 for Monday to Friday [→Main menu →Time program →HC
auto 1]:
1 Turn the rotary button clockwise until the "Settings" icon is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: Display changes to setting level with blue flashing
period selection.
3 Turn the rotary switch clockwise until the required time period is
displayed.
4 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the start
time of the first switching cycle.
5 Briefly press the rotary button to confirm ("OK").
Result: Input window for start time of the first switching cycle
flashes blue.
6 Turn the rotary button clockwise until the required start time is
displayed.
7 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the end
time of the first switching cycle.
8 Turn the rotary button clockwise until the required end time is
displayed.
9 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the start
time of the second switching cycle.
10 Briefly press the rotary button to confirm ("OK").
Result: Input window for the start time of the second switching
cycle flashes blue.
11 Turn the rotary button clockwise until the required start time is
displayed.
12 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the end
time of the second switching cycle.
13 Turn the rotary button clockwise until the required end time is
displayed.
14 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the start
time of the third switching cycle.
Operating instructions
10
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
4 Function
15 Turn the rotary button clockwise until the Confirm icon turns
blue.
Result: The display changes to the Confirm icon.
16 Briefly press the rotary button to confirm ("OK").
Result: The programming is saved.
Result: The setting level is exited.
Result: Selected switching cycles are highlighted in grey.
17 Turn the rotary button anticlockwise until the Back icon turns
blue.
18 Briefly press the rotary button to confirm ("OK").
Result: The menu is exited
3.3.8External operation
In addition to operation via the integrated RoCon+ HP1 controller,
the system can also be adjusted and operated via external devices.
Operation via the Internet
An optional (RoCon G1 (EHS157056)) gateway can be used to
connect the RoCon+ HP1 controller to the Internet. This enables
remote control of the RoCon+HP1 by mobile phone (using an app).
Operation via the room station
It can also be operated via the optional RoCon U1 (EHS157034)
room station. The operating elements and instructions for use are
described in the "Daikin RoCon HP, EHS157034, EHS157068
Operating Instructions " (available in digital form). All application
instructions are also valid for the indoor unit.
4Function
The system fully automatically controls the operation of the room
heating, room cooling and domestic hot water preparation on the
sanitary side on the basis of the specifications set in the RoCon
+HP1 controller. The functions that can influence system operation
are described below.
Some of the functions and parameters described are restricted by
access rights and can only be set by a heating specialist (see
"4.5.1Access rights (technician code)"[416]).
4.1Operating mode
[→Main menu →Operating mode]
This menu is used to select the operating mode for operating the
device. The current operating mode is indicated by a corresponding
symbol on the start screen.
Standby operating mode (Standby)
NOTICE
A heating system that is not protected against frost can
freeze in the event of frost and thus be damaged.
▪ Drain the heating system on the water side if there is a
danger of frost.
▪ If the heating system is not drained, the power supply
must be ensured and the mains switch must remain
switched on if there is a risk of frost.
In this operating mode, the indoor unit is switched to standby mode.
The freeze-up protection function remains unchanged. In order to
maintain this function, the system must not be disconnected from the
mains.
All controllers integrated in the RoCon system via the CAN bus are
primarily also switched to the "Standby" operating mode.
INFORMATION
In the "Standby" operating mode, the heat pump and the
optionally connected backup heater are disconnected from
the power supply (energy-saving mode) if the following
conditions are met:
▪ the outdoor temperature sensor is connected and
correctly parametrised in the system configuration
▪ the outside temperature is more than 8°C
▪ there is no heating request
▪ the freeze-up protection function is not active in any
connected HC and
▪ the indoor unit has been switched on for at least
5minutes.
Reduce operating mode
Reduced heating operation (lower room target temperature)
according to the set reduction temperature in the [Reduce room
temperature] parameter (see "4.2User"[412]).
Domestic hot water preparation according to the target leaving water
temperatures and switching cycles in the [Hot water auto. 1] hot
water time program (see "4.2User"[412]).
Heating operating mode
Heating, cooling operation according to the room target temperature
set in the [Room temperature target 1] parameter (see
"4.2User"[412]).
A connected outdoor temperature sensor (weather-compensated
leaving water temperature control), a connected RoCon U1
(EHS157034) room station or a connected room thermostat also
influence the target leaving water temperature.
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
11
4 Function
Domestic hot water preparation according to the target leaving water
temperatures and switching cycles in the [Hot water auto. 1] hot
water time program (see "4.2User"[412]).
Summer operating mode
Only domestic hot water preparation according to the set target
temperatures and switching cycles is carried out in the [Hot water
auto. 1] hot water time program (see "4.2User"[412]).
All controllers integrated in the RoCon system via the CAN bus are
primarily also switched to the "Summer" operating mode.
Automatic 1 operating mode (time program)
Automatic heating and setback mode according to the permanent
time programs (see "4.3Time program"[413]):
▪ [Heating circuit auto. 1]
▪ [Hot water auto. 1]
Automatic 2 operating mode (time program)
Automatic heating and setback mode according to the permanent
time programs (see "4.3Time program"[413]):
▪ [Heating circuit auto. 2]
▪ [Hot water auto. 2]
INFORMATION: Switching contact for external
operating mode changeover
A potential-free switching contact connected to the "Ext"
terminals on connection J8 of the indoor unit and wired
with a resistor can also be used to change over from an
external device (e.g. modem, ...). See " 4‒1 Resistance
values for evaluating the EXT signal"[412].
In this case, the switching contact functionality is
dependent on the parameter [Func. burner blocking
contact]:
▪ [Func. burner blocking contact] = "Resistance
values" (default setting): Evaluation of the resistance
values.
contact": Evaluation as a burner blocking contact. If the
switching contact is closed, the external heat generator
has priority.
4‒1 Resistance values for evaluating the EXT signal
Operating modeResistanceTolerance
Standby<680Ω±5%
Heating1200Ω
Reduce1800Ω
Summer2700Ω
Automatic 14700Ω
Automatic 28200Ω
INFORMATION
The resistances specified in " 4‒1 Resistance values for
evaluating the EXT signal" [4 12] in a tolerance field of
5%. Resistances outside this tolerance field are interpreted
as an open input. The heat generator switches back to the
previously active operating mode.
The input is not considered for resistance values greater
than the value for "Automatic 2".
If several switching contacts are connected to the indoor
unit (e.g. smart grid, room thermostat), the associated
functions may have a higher priority than the external
mode switching. The operating mode requested by the
EXT switching contact is then possibly not activated or is
only activated later.
Besides these operating modes, different temporary time programs
(see " 4‒2 Overview of temporary time programs" [4 12]) are
available that are carried out with priority after activation.
4‒2 Overview of temporary time programs
Temporary heating
program
PartyTime program"4.3Time pro-
Absent
Public holiday
Holiday
ScreedConfiguration"4.5.7Additional
INFORMATION
If a temporary heating program (Party, Absent, Public
holiday, Holiday, Screed) is started during the selected
operating mode, control is carried out primarily according
to the settings for this time program.
Setting/activation in
the menu
Information
gram"[413]
program"[419]
4.2User
[→Main menu →User]
The most important target temperatures and functions are set for the
user in this menu.
4.2.1Room temperature target setting
[→Main menu →User →Room]
The room target temperatures for room heating in heating operation
are defined in this menu. The available setpoints (1-3) belong to the
respective cycle (1-3) of the [Heating circuit auto. 1] and [Heating
circuit auto. 2] time programs.
Further explanations and possible settings for this menu can be
found in "7.3User"[429].
4.2.2Room temperature reduced setting
[→Main menu →User →Reduce]
The room target temperatures for room heating in Reduced mode
are defined in this menu. The reduced operation is carried out by the
"Reduce" operating mode or by the "Heating circuit auto. 1" and
"Heating circuit auto. 2" time programs.
Further explanations and possible settings for this menu can be
found in "7.3User"[429].
4.2.3Room temperature absent setting
[→Main menu →User →Absent]
The room target temperature for room heating in Absence mode are
defined in this menu. The absence operation is carried out by the
"Absent" or "Holiday" time programs.
Further explanations and possible settings for this menu can be
found in "7.3User"[429].
4.2.4Hot water temperature, target setting
[→Main menu →User →Hot water]
The hot water target temperatures for domestic hot water
preparation are defined in this menu. The available setpoints (1-3)
belong to the respective cycle (1-3) of the "Hot water auto. 1" and
"Hot water auto. 2" time programs.
Further explanations and possible settings for this menu can be
found in "7.3User"[429].
Operating instructions
12
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
4 Function
4.2.5Unscheduled domestic hot water
preparation
[→Main menu →User →1x load]
By starting this function, the hot water can be heated up to the [Hot
water temperature target 1] target temperature at any time. The
heating up is carried out with priority and independent of other
heating programs. After this temporary function has elapsed, the
controller automatically jumps back to the previously active operating
mode.
Possible settings for this menu can be found in "7.3User"[429].
4.3Time program
[→Main menu →Time program]
Various freely adjustable permanent time programs are available for
convenient and individual room and hot water temperature control.
Temporary time programs are also available, which override the
permanent time programs or the currently set operating mode for the
duration of their validity.
4.3.1Temporary time programs
INFORMATION
The following temporary time programs can be cancelled
at any time due to the manual changing of the operating
mode.
Party
[→Main menu →Time program →Party]
The program runs from activation until the end of the set period.
During this time, the HC is controlled to the temperature set in the
[Room temperature target 1] parameter. If the [Automatic 1] or
[Automatic 2] time program is active, the heating cycle is extended
or started prematurely. The domestic hot water preparation is not
affected.
Absent
[→Main menu →Time program →Absent]
The program runs from activation until the end of the set period.
During this time, the HC is controlled to the room target temperature
in the [Room temperature absent] parameter. The domestic hot
water preparation is not affected.
Holiday
[→Main menu →Time program →Holiday]
A calendar function can be used to enter a time period of absence.
During this time, the HC is continuously controlled (24 h per day) to
the room target temperature set in the [Room temperature absent]
parameter. This program is not started if the Standby operating
mode is active on the set start date.
Public holiday
[→Main menu →Time program →Public holiday]
A calendar function can be used to enter a time period of presence.
During this time, regulation is carried out exclusively according to the
settings for "Sunday" in [Heating circuit auto. 1] and [Hot water auto.
1].
4.3.2Permanent time programs
For the connected HCs and the storage tank charging circuit, time
programs control the HC and hot water temperatures or the
operating times of the circulation pump according to the specified
switching cycles. The switching cycles are saved in time blocks for
which different target temperatures can be set.
The saved time program can be changed at any time. For a better
overview, it is recommended to write down and safely store the
programmed switching cycles ("11.1Timers"[452]).
Heating circuit auto. 1 and Heating circuit auto. 2
[→Main menu →Time program →HC auto 1/HC auto 2]
The time programs for the HC can be parametrised in these menus.
Three switching cycles can be set per day, to which the [Room
temperature target 1/2/3] parameters are assigned. Outside the
switching cycles, it is controlled to the [Reduce room temperature]
setpoint. The entry can be made separately for each individual
weekday or in week segments.
Hot water auto. 1 and Hot water auto. 2
[→Main menu →Time program →DHW auto 1/DHW auto 2]
The time programs for the domestic hot water preparation can be
parametrised in these menus. Three switching cycles can be set per
day, to which the [Hot water temperature, target 1/2/3] parameters
are assigned.
Outside of the switching cycles, it is controlled to the minimum
adjustable setpoint (see "7.3.4 Menu: Hot water temperature,
target"[429]).
Circulation program
[→Main menu →Time program →Circulation]
A time program for an optionally connected circulation pump can be
parametrised in this menu. 3 switching cycles per day can be set.
INFORMATION
Use of circulation lines not permitted in France!
Sound program
INFORMATION
During quiet mode, the output in room heating and room
cooling operation decreases so that it may no longer be
possible to achieve pre-set target temperature values. This
program can therefore only be set by the installer.
In this menu, a time program can be parametrised for various stages
of the heat pump quiet mode. 3 switching cycles with a resolution of
15 minutes can be set. A separate entry for each weekday is
possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and
Monday to Sunday can be parametrised.
A noise level can be assigned to each switching cycle:
▪ 0 – no noise reduction,
▪ 1 – low noise reduction,
▪ 2 – medium noise reduction,
▪ 3 – maximum noise reduction.
Factory settings
The permanent time programs are preset according to the following
factory settings.
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
13
4 Function
4‒3 Factory setting of the permanent time programs
This menu can be used to reset the time programs to factory
settings. To do this, select the respective time programs and then
confirm the selection with the Confirm button on the second menu
page.
4.4Settings
[→Main menu →Settings]
The basic settings of the controller and the system are made in this
menu. This includes the integration of optional and external
components. Depending on the access authorisation (user or
expert), different parameters are available.
4.4.1Display settings
[→Main menu →Settings →Display]
This menu can be used to set the following parameters: Language,
date, time, LCD brightness and LCD illumination time.
Further explanations and possible settings for this menu can be
found in "7.5Settings"[431].
INFORMATION
Increasing the brightness of the LCD display beyond the
factory-set value will reduce the life of the display.
4.4.2System
[→Main menu →Settings →System]
This menu combines basic parameters of the heating system.
Further explanations and possible settings for this menu can be
found in "7.5.2Menu: System"[432].
4.4.3External heat sources
[→Main menu →Settings →Ext. source]
This menu can be used to configure the integration of an optional
external heat source.
The heat supplied by an alternative heat generator (WEZ) must be
fed to the unpressurised cylinder water in the hot water tank of the
indoor unit.
▪ On use of the optional EKBUxx backup heater, this is carried out
due to the design installation situation.
▪ When using an alternative WEZ (e.g. gas- or oil-fired boiler), this
can be hydraulically integrated:
▪ unpressurised via the connections (solar feed and solar return)
of the hot water storage tank or
▪ with Daikin Altherma EHS…B… and ETS…B… device types,
via the integrated pressure solar heat exchanger
The setting of the [Config. ext. heat source] parameter determines
whether and which additional heat generator (WEZ) is available for
domestic hot water preparation (DHW) and heating support (HZU).
▪ No external heat source
▪ Optional backup heater
▪ External heat source for DHW and heating support: Alternative
WEZ provides domestic hot water preparation and heating
support. To request the WEZ, relay K3 is switched for connections
X1-L1 and XBUH1-T1 on the RTX-EHS PCB.
▪ External heat source for DHW or HZU: Alternative WEZ 1
(optional EKBUxx backup heater) provides domestic hot water
preparation and alternative WEZ 2 provides heating support. To
request the WEZ 1, relay K3 (connections X1-L1 and XBUH1-T1)
is switched on the RTX-EHS PCB and to request the WEZ 2, relay
K1 (connections X1-L3 and XBUH1-T3) is switched on the RTX-
Operating instructions
14
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
4 Function
EHS PCB. Heed warning notice! The operation of an additional
alternative WEZ is also influenced by the settings of the
[Bivalence function] and [Bivalence temperature] parameters.
Further explanations and possible settings for this menu can be
found in "7.5.3Menu: External heat source"[433].
4.4.4Inputs/Outputs
[→Main menu →Settings →Inputs/Outputs]
This menu can be used to adjust parameter for inputs and outputs of
the controller PCB to optimise the system controller individually.
Smart grid
WARNING
There is a danger of scalds at hot water target
temperatures over 65°C. This is possible because the
utility company (EVU) is entitled to control current draw
optimised according to supply and demand in the
definitions for Smart Grid.
Such forced charging can cause the hot water target
temperature in the hot water tank to exceed 65°C.
This storage tank charging is carried out even when
"Standby" operating mode is set.
▪ Install scald protection in the hot water distribution line.
To use this function, a special electricity meter with SG receiver to
which the heat pump must be connected is required.
As soon as the function is activated by the [Smart grid] parameter,
the heat pump is set to an operating mode as per the following table
depending on the utility company signal.
4‒4 Use of the SG signal
(1)
Signal
EVUSGHot waterHeating
10---No operation
00NormalNormal
01lowSwitch-on re-
11Very lowSwitch-on com-
AUX switching function
Setting the [AUX switching function] parameter determines the
switching conditions for the potential-free AUX switching contact
(toggle switch output A). This switching contact can be used to
control an external heat generator, for example.
Electricity
costs
Effect on
operation
commendation,
and storage
tank setpoint
temperature
value is in-
creased de-
pending on the
[Smart grid
mode] para-
meter.
mand and stor-
age tank set-
point temperat-
ure is set to
70°C.
installations
(2)
No operation
Normal
operation
Switch-on recommendation,
and target leav-
ing water tem-
perature is in-
creased de-
pending on the
[Smart grid
mode] para-
meter.
Switch-on com-
mand for stor-
age tank char-
ging
(2)
(3)
If one of the switching conditions is fulfilled, the potential-free
switching contact is switched after the time set in the [AUX wait time]
parameter.
AUX switching contact (toggle switch output A) is not switched if
the switch function is deactivated. [AUX switching function]
parameter = "Inactive".
AUX switch contact (toggle switch output A) is switched when one
of the following conditions is set:
▪ Storage tank temperature (T
) ≥ [Switching threshold TDHW
dhw
(AUX)] parameter value.
▪ if an error is pending.
▪ Outside temperature <[Bivalence temperature] parameter value.
▪ Heat request for domestic hot water preparation.
▪ Heat request for room heating or cooling requirement.
▪ Heat request for room heating or domestic hot water preparation.
▪ "Cooling" operating mode active.
Interlink function
Setting the [Interlink function] parameter = "On" provides the option
that the indoor unit includes two different leaving water temperature
setpoints in the controller.
This applies to both weather-compensated control and control
according to a fixed target leaving water temperature (see
"4.5Configuration"[416]).
One possible application is, for example, the additional integration of
an HP convector in a surface heating and cooling system.
Prerequisite: 2 switching contacts (e.g. room thermostats) are
connected to the plug connection J16 of the indoor unit.
▪ [Interlink function] parameter = "On": Evaluation of the heating and
cooling switching contacts at plug connection J16 on the
RoConBM2C PCB:
Activation of cooling operation only by switching the operating
mode to "Cooling" (see "4.1 Operating mode" [4 11]). [Room
thermostat] parameter must be set to "Yes".
1Open switching contacts: Only freeze-up protection active
2"Heating" or "Automatic 1" / "Automatic 2" operating mode
active during the switching cycles in day mode.
▪ Closed heating switching contact = IL1: It is controlled to the
normal target leaving water temperature according to the
parameter settings for [Heating].
▪ Closed cooling switching contact = IL2: It is controlled to the
increased target leaving water temperature (normal target
leaving water temperature + value of the [Interlink temperature
increase] parameter). Priority if both switching contacts are
closed!
3"Cooling" operating mode active.
▪ Closed heating switching contact = IL1: It is controlled to the
normal target leaving water temperature according to the
parameter settings in level [Heating circuit config.] > [Cooling].
▪ Closed cooling switching contact = IL2: It is controlled to the
reduced target leaving water temperature (normal target leaving
water temperature – value of the [Interlink temperature
increase] parameter). Priority if both switching contacts are
closed!
Further explanations and possible settings for this menu can be
found in "7.5.4Menu: Inputs/Outputs"[433].
(1)
Switching contacts at input J8 of the RoConBM2C PCB closed(1) or open(0).
(2)
No freeze-up protection function
(3)
When the charging process is completed, heating is carried out according to the settings for the respective HC. Heating support from the HC
active if [Heating support (HZU)] parameter = "On".
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
15
4 Function
4.4.5Intelligent storage tank management
[→Main menu →Settings →ISM]
If the storage temperatures are high enough, the energy in the
storage tank can be used for room heating. This can either increase
comfort ([Continuous heating] function) or make it possible to use
energy from an external heat source, e.g. solar, when heating is
required ([Heating support (HZU)] function).
Continuous heating
The activated Continuous heating function ([Continuous heating]
parameter = "On") allows uninterrupted heating even during
defrosting of the evaporator. This enables high comfort to be
guaranteed, even with rapidly reacting heating systems (e.g.
convectors).
Heating support (HZU)
If the heating support ([Heating support (HZU)] parameter = "On") is
activated, the energy in the built-in storage tank of the indoor unit is
used to perform the heating function. If the storage tank temperature
is sufficiently high, the heat generation by the heat pump remains
out of operation.
The minimum required storage tank temperature (T
calculated as follows:
T
= Currently active hot water target temperature
HZUmin
(1)
+hysteresis
a) Switch-on condition:
Tdhw>T
+4 K and Tdhw>Information parameter [Feed
HZUmin
temperature, target]+1K
If the switch-on condition is fulfilled, heat is taken from the storage
tank and this is used to supply the heating system.
b) Switch-off condition:
Tdhw<T
or Tdhw<Information parameter [Feed temperature,
HZUmin
target] (see "7.7.2Values"[444])
If the switch-off condition is met, heating support from the hot water
storage tank is ceased, and the heat pump takes over heating
operation.
The [Heating support power] parameter limits the maximum power
that can be taken. The [Heating support max. temp.] parameter limits
the maximum temperature that can enter the heating system.
Further explanations and possible settings for the parameters in this
menu can be found in "7.5.5Menu: Intelligent Storage Mgmt"[436].
HZUmin
) is
4.5Configuration
[→Main menu →Configuration]
This menu can be used to optimally adapt the operating
characteristics of the system to the system structure and the needs
of the users. Additional programs facilitate commissioning.
Depending on the access authorisation (user or expert), different
parameters are available.
4.5.1Access rights (technician code)
[→Main menu →Configuration →Access]
Certain functions and parameters in the controller are restricted by
access rights and are not visible to the user. To gain access to it, the
specialist code must be entered.
4‒1 Setting the access code
Example: Set code 3090 (example only, this is not a valid access
code) [→Main menu →Configuration →Access]:
1 Turn the rotary button clockwise until the first input field is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The first input field flashes blue.
(2)
3 Turn the rotary button clockwise until 3 is displayed.
4 Briefly press the rotary button to confirm ("OK").
Result: The second input field is displayed in blue.
5 Turn the rotary button clockwise until the third input field is
displayed in blue.
6 Briefly press the rotary button to confirm ("OK").
Result: The third input field flashes blue.
7 Turn the rotary button clockwise until 9 is displayed.
8 Briefly press the rotary button to confirm ("OK").
Result: The fourth input field is displayed in blue.
9 Turn the rotary button clockwise until the Confirm icon turns
blue.
10 Briefly press the rotary button to confirm ("OK").
Result: The code is checked and the setting level is exited.
4.5.2Sensors
[→Main menu →Configuration →Sensors]
Optional sensors are activated and configured in this menu.
Pressure setpoints for the water side can be defined.
Further explanations and possible settings for the parameters in this
menu can be found in "7.6.1Menu: Sensors"[437].
4.5.3HC config.
[→Main menu →Configuration →HC config]
This menu is used to adjust the basic functionality of the HC.
Further explanations and possible settings for the parameters in this
menu can be found in "7.6.2Menu: Heating circuit config."[438].
Weather-compensated leaving water temperature
control
If the weather-compensated leaving water temperature control is
active, the leaving water temperature ([Feed temperature, target]
parameter) is determined automatically according to the set heating/
cooling curve depending on the outside temperature.
(1)
Information parameter [Hot water temperature, target] (see "7.3.4Menu: Hot water temperature, target"[429])
(2)
[Heating support hysteresis] parameter setting (see "7.5.5Menu: Intelligent Storage Mgmt"[436])
Operating instructions
16
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
4 Function
This function is activated in the delivery condition. It can only be
deactivated (fixed value control) or reactivated with a technician
code.
If the RoConU1 (EHS157034) room station is also connected to the
RoCon+ HP1, the target temperatures are controlled according to
the weather and room temperature [Room influence]) parameter.
This function can only be configured using the technician code.
Contact your heating expert in this regard.
This function is activated or deactivated via the [Weathercompensated] parameter in the "Configuration" menu.
▪ For heating operation: [Feed temperature, heating mode]
parameter or [Feed temperature, reducing mode] parameter
▪ For cooling operation: [Feed temperature, cooling mode]
parameter
INFORMATION
The weather-compensated leaving water temperature
control has no influence on the target leaving water
temperature in the case of a hot water circuit request.
With mixer module connected
The setting of the heating/cooling curves and the activation of the
weather-compensated leaving water temperature control for the
assigned HC are carried out in the same way as described above.
The assigned HC can be operated as a:
▪ Mixer add-on
The outside temperature of the outdoor temperature sensor
connected to the indoor unit external temperature sensor is
transmitted to the mixer module via the CAN bus.
or as a
▪ Mixer add-on with zone control
A separate outdoor temperature sensor must be connected to the
mixer module. The assigned HC is controlled according to the
outside temperature relevant for this zone.
If the terminal function is activated, the mixer module can be
operated and the settings for the assigned HC undertaken via the
RoCon+B1 control panel of the indoor unit.
In conjunction with the RoCon U1 (EHS157034) room station, the
mixer module can also control the assigned HC completely
autonomously and independently of the heat generator.
Further explanations and possible settings for this menu can be
found in "7.6Configuration"[437].
Freeze-up protection function
The integrated heating circulation pump is switched on at an external
temperature below the [Frost protection temperature] parameter
value in order to prevent the heating system from freezing.
In addition, the feed, storage and connected room temperature
sensors are also constantly monitored. If the temperature measured
by one of these sensors falls below 7°C (below 5°C at room
temperature), the antifreeze function is also activated.
If the heating leaving water temperature falls below 7°C, the heat
pump heats until the heating leaving water temperature reaches at
least 12°C.
The function is ended if the external temperature rises above the set
[Frost protection temperature] parameter value+1K and also there is
no other activation condition.
INFORMATION
Operation of the heat pump can be shut off completely for
a limited period of time by the utility company if the
following low-tariff functions are activated:
[HT/NT function] parameter = "Switch all off" or [Smart grid]
parameter = "On"
These situations can be recognised if, in the [→ Main
menu → Information → Overview] menu in the operating
data field "Ext" the "High rate" or "SG1" value is displayed.
4.5.4Heating
[→Main menu →Configuration →Heating]
This menu is used to configure heating times and target leaving
water temperatures for heating operation.
Heating curve
INFORMATION: Overheating and moisture protection
In the event of malfunction, the underfloor heating system,
the screed or the floor structure could be damaged due to
overheating.
▪ Prior to initial commissioning, set the maximum
temperature limit in the RoCon+HP1 controller ([Max.
feed temperature] parameter) to the maximum
permissible system temperature before the screed
drying starts.
▪ Connect an overheating protection switch (in the
building) at the "EXT" plug connection to external mode
switch-over so that the indoor unit is switched to
"Standby" or "Summer" mode. If the [Room thermostat]
parameter = "Yes" or [Interlink function] parameter =
"On", the overheating protection switch must be
connected so that the room thermostat's switching
contact is interrupted.
▪ If the underfloor heating is also used for room cooling,
the connection notes in the above point also apply to
the connection of a moisture protection switch in the
building.
The heating curve is used to adapt the leaving water temperature to
the characteristics of the building independent of the respective
outside temperature (weather-compensated leaving water
temperature control, see "4.5 Configuration" [4 16]). Generally
speaking, the slope of the heating curve describes the ratio of the
leaving water temperature change to the external temperature
change.
The heating curve is valid within the limits of the minimum and
maximum temperatures set for the respective HC. Deviations may
occur between the room temperature measured in the occupied area
and the desired room temperature; these can be minimised by
installing a room thermostat or a RoCon U1 (EHS157034) room
station.
The controller is set at the factory in such a way that the heatingcurve does not independently adjust itself during operation.
The automatic heating curve adjustment can be activated
([Heating curve adaptation] parameter) if the outdoor temperature
sensor and the room station (RoCon U1 (EHS157034)) are
connected (see "4.5Configuration"[416]).
Start conditions for automatic heating curve adjustment:
▪ Outside temperature<8°C
▪ Operating mode is "Automatic 1" or "Automatic 2"
▪ Duration of the setback period is at least 6h
If no automatic heating curve adjustment is activated, the heating
curve can be manually adjusted by adjusting the [Heating curve]
parameter).
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.