Daikin EHSH04P30D3, EHSX04P30D3, EHSX04P50D3, EHSH08P30D3, EHSX08P30D3 Operation manuals

...
Page 1
Operating instructions
Controller RoCon+ HP1
EHSH(B)04P30D3 EHSX(B)04P30D3 EHSX(B)04P50D3 EHSH(B)08P30D3 EHSX(B)08P30D3 EHSH(B)08P50D3 EHSX(B)08P50D3 EHSH(B)04P30D2 EHSX(B)04P30D2 EHSH(B)08P30D2 EHSH(B)08P50D EHSX(B)04P50D EHSX(B)08P50D
ETSH(B)16P30D ETSX(B)16P30D ETSH(B)16P50D ETSX(B)16P50D
Operating instructions
Controller RoCon+ HP1
English
Page 2

List of contents

List of contents
1 General safety precaution 3
1.1 Particular safety instructions ..................................................... 3
1.1.1 Observing the instructions .......................................... 3
1.1.2 Meaning of warnings and symbols.............................. 4
1.2 Safety instructions for installation and operation....................... 4
1.2.1 General ....................................................................... 4
1.2.2 Intended use ............................................................... 4
2 Product description 5
2.1 Temporary shutdown................................................................. 5
3 Operation 6
3.1 General...................................................................................... 6
3.2 Display and operating elements ................................................ 6
3.2.1 Status indicator ........................................................... 6
3.2.2 Display ........................................................................ 6
3.2.3 Rotary button .............................................................. 6
3.2.4 Start screen................................................................. 6
3.3 Operating concept ..................................................................... 8
3.3.1 Navigating in the menu ............................................... 8
3.3.2 Help function ............................................................... 8
3.3.3 Navigating in lists and selecting list entries................. 8
3.3.4 Setting setpoints ......................................................... 9
3.3.5 Setting the times ......................................................... 9
3.3.6 Calendar function........................................................ 9
3.3.7 Setting the time programs........................................... 10
3.3.8 External operation....................................................... 11
4 Function 11
4.1 Operating mode......................................................................... 11
4.2 User........................................................................................... 12
4.2.1 Room temperature target setting ................................ 12
4.2.2 Room temperature reduced setting ............................ 12
4.2.3 Room temperature absent setting............................... 12
4.2.4 Hot water temperature, target setting ......................... 12
4.2.5 Unscheduled domestic hot water preparation............. 13
4.3 Time program ............................................................................ 13
4.3.1 Temporary time programs........................................... 13
4.3.2 Permanent time programs .......................................... 13
4.3.3 Time program reset..................................................... 14
4.4 Settings ..................................................................................... 14
4.4.1 Display settings........................................................... 14
4.4.2 System ........................................................................ 14
4.4.3 External heat sources ................................................. 14
4.4.4 Inputs/Outputs............................................................. 15
4.4.5 Intelligent storage tank management.......................... 16
4.5 Configuration ............................................................................. 16
4.5.1 Access rights (technician code) .................................. 16
4.5.2 Sensors....................................................................... 16
4.5.3 HC config. ................................................................... 16
4.5.4 Heating........................................................................ 17
4.5.5 Cooling........................................................................ 18
4.5.6 Hot water..................................................................... 19
4.5.7 Additional program...................................................... 19
4.5.8 Configuration Wizard .................................................. 21
4.5.9 Parameter reset .......................................................... 21
4.6 Information ................................................................................ 21
4.6.1 Current ........................................................................ 21
4.6.2 Overview ..................................................................... 22
4.6.3 Values ......................................................................... 22
4.6.4 Water pressure ........................................................... 22
4.7 Error .......................................................................................... 22
4.8 Terminal .................................................................................... 22
4.8.1 Selecting the terminal address.................................... 23
4.8.2 Bus scan for terminal function..................................... 23
4.9 Statistics ..................................................................................... 23
4.9.1 Month ........................................................................... 23
4.9.2 Total ............................................................................. 23
5 Initial commissioning 24
5.1 Configuration Wizard.................................................................. 24
5.2 Menu navigation in the Configuration Wizard............................. 24
6 Parameter overview 25
6.1 Menu: Operating mode............................................................... 25
6.2 Menu: User................................................................................. 25
6.3 Menu: Time program .................................................................. 25
6.4 Menu: Settings ........................................................................... 26
6.5 Menu: Configuration ................................................................... 26
6.6 Menu: Information ...................................................................... 27
6.7 Menu: Error ................................................................................ 27
6.8 Menu: Terminal .......................................................................... 27
6.9 Menu: Statistics .......................................................................... 27
7 Parameter settings 28
7.1 Explanation of the parameter tables........................................... 28
7.2 Operating mode.......................................................................... 28
7.3 User............................................................................................ 29
7.3.1 Menu: Room temperature target.................................. 29
7.3.2 Menu: Reduce room temperature ................................ 29
7.3.3 Menu: Room temperature absent ................................ 29
7.3.4 Menu: Hot water temperature, target ........................... 29
7.3.5 Menu: 1x Hot water...................................................... 30
7.4 Time program ............................................................................. 30
7.5 Settings ...................................................................................... 31
7.5.1 Menu: Display settings................................................. 31
7.5.2 Menu: System .............................................................. 32
7.5.3 Menu: External heat source ......................................... 33
7.5.4 Menu: Inputs/Outputs................................................... 33
7.5.5 Menu: Intelligent Storage Mgmt ................................... 36
7.6 Configuration .............................................................................. 37
7.6.1 Menu: Sensors............................................................. 37
7.6.2 Menu: Heating circuit config......................................... 38
7.6.3 Menu: Heating.............................................................. 38
7.6.4 Menu: Cooling.............................................................. 40
7.6.5 Menu: Hot water........................................................... 41
7.6.6 Menu: Additional programs .......................................... 42
7.7 Information ................................................................................. 43
7.7.1 Overview ...................................................................... 43
7.7.2 Values .......................................................................... 44
7.7.3 Water pressure ............................................................ 45
7.8 Error ........................................................................................... 45
7.9 Terminal ..................................................................................... 45
7.10 Statistics ..................................................................................... 46
7.11 Configuration Wizard .................................................................. 46
8 Errors and faults 47
8.1 Emergency operation ................................................................. 47
8.2 Manual operation........................................................................ 47
8.3 Error protocol.............................................................................. 47
8.4 Error screen................................................................................ 48
8.5 Error codes................................................................................. 48
9 Mixer module 48
9.1 Mixer module start screen (terminal function) ............................ 49
9.2 Mixer valve parameter overview................................................. 49
9.3 Mixer module parameter settings ............................................... 50
10 Glossary 51
11 User-specific settings 52
11.1 Timers ........................................................................................ 52
11.2 Parameters ................................................................................. 53
11.3 Data bus addresses ................................................................... 53
List of keywords 54
Operating instructions
2
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 3

1 General safety precaution

1 General safety precaution

1.1 Particular safety instructions

WARNING
Heating devices that are not set up and installed correctly can impair the function of the heating device and/or cause serious or fatal injury to the user.
▪ Work on the heat generator (such as
set-up, servicing, connection and initial start-up) must only be carried out by persons who are authorised and who have successfully completed qualifying technical or vocational training and who have taken part in advanced training sessions recognised by the relevant responsible authorities for the specific activity. They include, in particular, certified heating engineers, qualified electricians and HVAC specialists who, because of their professional
training and their expert knowledge, have experience in the
professional installation and maintenance of heating systems, oil and gas installations and hot water storage systems.
▪ Only operate the heat generator
when it is in perfect condition with the protective hood closed.
WARNING
Disregarding the following safety instructions may result in serious physical injury or death.
▪ This device may only be used by
children aged 8 and above and by persons with restricted physical, sensory or mental capabilities or with a lack of experience and knowledge if they are under supervision or if they have been instructed in the safe use of the equipment and understand the dangers arising from it. Children must not play with the device. Cleaning and user maintenance must not be carried out by children without supervision.
▪ Establish the power supply in
accordance with IEC60335‑1, via a separate isolator that separates all poles with a contact opening distance and that provides full disconnection in accordance with overvoltage categoryIII.
▪ All the electrical work must only be
carried out by electrically qualified experts and with consideration of the local and national regulations, and the instructions in this manual. Check that a suitable electrical circuit is being used. Insufficient load capacity of the electrical circuit or improperly executed connections can result in electric shock or fire.

1.1.1 Observing the instructions

▪ The original documentation is written in German. All other
languages are translations.
▪ Please read this manual carefully and thoroughly before
proceeding with the installation or modification of the heating system.
▪ The precautionary measures described in this document cover
very important topics. Follow them meticulously.
▪ The installation of the system, and all activities described in this
manual and the applicable documents for the installer must be carried out by an approved installer.
Documentation set
This document is part of a documentation set of other applicable documents. The complete set comprises:
▪ Installation manual for the Daikin Altherma indoor unit –
subsequently referred to as "indoor unit " (format: paper – included in the indoor unit scope of delivery)
▪ Operating manual for the indoor unit (format: paper – included in
the indoor unit scope of delivery)
▪ Operating manual for the heat pump (format: paper – included in
the indoor unit scope of delivery)
▪ Installation manual for the outdoor unit (format: paper – included
in the outdoor unit scope of delivery)
▪ Installation instructions for optional components (format: paper –
included in the scope of delivery of the respective component)
▪ Installer reference guide of the indoor unit (format: digital)
▪ Installer reference guide of the outdoor unit (format: digital)
▪ Operating instructions for controller RoCon HP, EHS157034,
EHS157068 (status 04/2017) (format: digital)
The reference guides contain the complete set of technical data, a detailed description of best practices and information on maintenance, troubleshooting and decommissioning.
The digital documents and the latest editions of the supplied documentation are available on the regional Daikin website or, on request, from your dealer. The Daikin website is easy to access using the QR code on your device.
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
3
Page 4
1 General safety precaution

1.1.2 Meaning of warnings and symbols

Warnings in this manual are classified according into their severity and probability of occurrence.
DANGER
Indicates an immediate danger.
Disregarding this warning can lead to serious injury or death.
WARNING
Indicates a potentially dangerous situation.
Disregarding this warning may result in serious physical injury or death.
CAUTION
Indicates a situation which may cause possible damage.
Disregarding this warning can cause damage to property and the environment and result in minor injuries.
This symbol identifies user tips and particularly useful information, but not warnings or hazards
Special warning signs
Some types of danger are represented by special symbols.
Electric current

1.2.2 Intended use

The RoCon+ HP1 controller may only be used in the indoor units specified on the title page that are approved for the control system. The RoCon+ HP1 controller must only be operated in accordance with the specifications in these instructions.
Any other use or use beyond the intended use is considered improper use. The operator alone bears responsibility for any resulting damage.
For any work on the equipment that extends above and beyond the operation of the regulating system, the details provided in the supplementary documents must be observed, particularly with regard to safety instructions.
Documentation
The technical documentation included in the scope of supply is a constituent part of the equipment. It must be stored in such a way that it can be consulted at any time by the operator or technicians.
Risk of burns or scalds
General description
1 Handling instructions are shown as a list. Actions where the
sequential order must be adhered to are numbered.
[Language]: Parameters are shown in square brackets.
"Operating mode", "Deutsch": Available menu names and parameter setting options are shown in quotation marks.
[→ Main menu]: The position of menus and functions is shown in square brackets with →.

1.2 Safety instructions for installation and operation

1.2.1 General

▪ For any work on the equipment that extends above and beyond
the operation of the regulating system, the details provided in the supplementary documents must be observed, particularly with regard to safety instructions.
Avoid danger
The indoor unit conforms to the state of the art and meets all recognised technical requirements. However, improper use can lead to serious injuries or death, as well as causing material damage.
To avoid hazards, only operate the indoor unit:
▪ as stipulated and in perfect condition,
▪ with an awareness of the safety and hazards involved.
This assumes knowledge and use of the contents of this manual, all applicable documents, the relevant accident prevention regulations as well as the recognised safety-related and occupational health rules.
Display representation of the RoCon+HP1 controller
Certain screen displays or menu items may deviate from those shown in these instructions depending on the national or equipment variant of the indoor unit or the user status logged onto the controller.
Operating instructions
4
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 5

2 Product description

2 Product description
INFORMATION
The RoCon+HP1 controller is part of the indoor unit.
It consists of the switching panel RoCon BM2C PCB to which the actuators and sensors as well as other components in the regulating system are connected and the RoCon+B1 control panel.
These operating instructions only explain the functions and possible settings of the controller. More information on the switch box and other equipment components can be found in the supplementary documents.
The electronic, digital controller is able to automatically control all heating and hot water functions for a direct HC, a storage loading circuit and also further HCs via optionally connectible mixer modules, depending on the heating device.
It performs all safety management for the indoor unit. This executes a safety switch-off in the event of a water shortage or undefined operating states. A corresponding error message shows the operator all the information regarding fault causes.
All function settings for the indoor unit and the optional RoCon devices that are connected via the data bus are undertaken with the control elements of the integrated RoCon+ B1 control panel and shown on the plain text display with coloured backlighting.
The following additional, optional devices can be connected to the indoor unit via the controller data bus:
▪ RoConU1 (EHS157034) room station
▪ RoConM1 (EHS157068) mixer module
In addition, the RoCon+ HP1 controller has a freeze-up protection function for the direct HC and the storage tank charging circuit as well as an automatic function for heating support (integration of an auxiliary heat source such as a wood-burning boiler or solar system).
The potential-free AUX switching contact can be used to carry out different control functions in conjunction with external devices (request from an external heat generator, changeover to bivalent operation, external status indicator, etc.).
In addition, it also has several inputs for assessing external control contacts (external operating mode switching or heat request, Smart Grid and low rate EVU functions
The optional outdoor temperature sensor installed on the north side of the building can be used to further optimise the weather­compensated leaving water temperature control.
If the optional RoCon G1 (EHS157056) gateway is installed and connected to the Internet, the indoor unit can be conveniently monitored and operated by remote control using a mobile phone (app).
Initial commissioning of the heating system is described in the installation instructions for the indoor unit.
Certain menu items of the RoCon+ HP1 controller are only accessible to the heating expert. This security measure ensures that no undesirable malfunctions arise during operation of the system through incorrect settings.
All settings for the assigned HC can be made with the RoConU1 (EHS157034) room station in the same way as on the control panel. If the terminal function is activated, all operating possibilities that are available on the integrated control panel are available with the exception of certain special functions (e.g. manual operation).
After appropriate assignment, a connected RoConM1 (EHS157068) mixer module is also operated using the RoCon+ B1 control panel and/or the RoConU1 (EHS157034) room station.
(1)
).

2.1 Temporary shutdown

CAUTION
A heating system that is shut down can freeze in the event of frost and may suffer damage.
▪ Drain the heating system that is shut down if there is
danger of frost.
▪ If the heating system is not drained, the power supply
must be ensured and the external main switch must remain switched on if there is a danger of frost.
If the heat pump is not required for a lengthy period, it can be temporarily decommissioned.
However, we recommend not to disconnect the system from the power supply but merely to switch it to "Standby mode"
The system is then protected from frost. The pumps and valve protection functions are active.
If it is not possible to guarantee the power supply when there is danger of frost,
▪ completely drain the indoor unit on the water side, or
▪ apply suitable antifreeze measures to the connected heating
system and hot water storage tank (e.g. draining).
INFORMATION
If there is only a risk of frost for a few days when the power supply is not reliable, it is not necessary to empty the indoor unit due to the very good thermal insulation, provided that the storage tank temperature is regularly monitored and does not fall below +3°C.
However, this provides no freeze-up protection for the connected heat emitter.
(1)
The energy supply company (EVU) sends signals that are used for controlling the power mains utilisation and that have an influence on the cost of the power and availability.
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
5
Page 6

3 Operation

3 Operation

3.1 General

DANGER: RISK OF ELECTROCUTION
If electrical components come into contact with water, this can cause an electric shock as well as cause potentially fatal burns or injuries.
▪ The displays and keys of the controller must be
protected against the effects of moisture.
▪ To clean the controller, use a dry cotton cloth. The use
of aggressive cleaning agents and other fluids can cause damage to devices or lead to electric shock.
INFORMATION
The heat pump makes the most effective use of energy at the lowest possible return and hot water target temperatures.
If an external heat generator (e.g. the optional backup heater) is activated at target leaving water temperatures above 50°C, the efficiency (COP) of the heat pump can deteriorate (depending on the outside temperature).

3.2 Display and operating elements

3.2.1 Status indicator

The LEDs of the status indicator light up or flash to indicate the operating mode of the device.
 3‒1 Status indicator
LED Mode Description
Flashes blue Standby The device is not in operation.
Lights up blue Operation The device is in operation.
Flashes red Error An error has occurred. For further
details, see "8Errors and
faults"[447].

3.2.2 Display

During normal operation the display is deactivated (completely dark). The activity of the system is indicated by the status indicator. Each press of the rotary button (turn, press or hold) activates the display with the start screen.
If the start screen is active and no user input is made for 60 seconds, the display is deactivated. If no input is made by the user at any other point in the menu for 120seconds, the system returns to the start screen.

3.2.3 Rotary button

CAUTION
Never operate the operating elements of the controller with a hard, pointed object. This can cause damage and can cause the controller to malfunction.
The rotary button can be used to navigate in the respective level, to select or change the setting value and to accept this change with a short key press.
 3‒1 RoCon+B1 display and operating elements
1 Status indicator 2 Display 3 Rotary button
 3‒2 Function of the rotary button
Action Result
Turning Select menu, select setting, make setting
Press Confirm selection, accept setting, execute
function.
Press for 2sec. Exit menu

3.2.4 Start screen

The start screen provides an overview of the current operating status of the system. From the start screen, any operation of the rotary switch (turn, press or hold down) leads to the Main menu.
Operating instructions
6
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 7
 3‒2 Display position on the start screen
 3‒3 Display icons on the start screen
Item Icon Explanation
1 Date and time
2 Error message
3 Operation
Item Icon Explanation
10 Operating mode: Standby
Operating mode: Reduce
Operating mode: Heating
Operating mode: Cooling
Operating mode: Summer
Operating mode: Automatic 1
Operating mode: Automatic 2
Operating mode: Emergency
11 Special program: Party
Special program: Absent
Special program: Holiday
Special program: Public holiday
3 Only with connected room unit: Room
temperature
4 Hot water temperature
5 Underfloor heating leaving water temperature
Convector heating leaving water temperature
Radiator heating leaving water temperature
6 Outside temperature
7 Pressure in the HC
8 Storage tank without heating rod
Storage tank with connected heating rod (off)
Storage tank with connected heating rod (on)
9 No outdoor unit detected
Outdoor unit present, compressor off
Outdoor unit present, compressor on
Special program: 1 x hot water
Special program: Screed
Special program: Ventilation
12 Quiet mode On
13 Operating mode: Heating
Operating mode: Cooling
Operating mode: Hot water
Operating mode: Defrost
Operating mode: No request
14 Ext External operating mode switched (Burner
blocking contact or Room thermostat)
INFORMATION
If the local control panel is used as a remote controller for a mixer module, both the standard screen and the menu structure are changed (see "9Mixer module"[448]).
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
7
Page 8
3 Operation

3.3 Operating concept

The operating concept of the controller allows quick navigation in the menu:
▪ Clear display of information
▪ Straightforward selection of parameters
▪ Setting of setpoints and programs.
The basics of the operating concept are described in detail below using a few examples. The operation of special functions follows the same principle and is described in the corresponding sections if required in "4Function"[411].

3.3.1 Navigating in the menu

From the start screen, any operation of the rotary switch (turn, press or hold down) leads to the main menu. The menu view consists of an upper area for the menu icons of the various submenus and the lower menu bar. The Back and Help icons are displayed in the menu bar. Use the rotary button to switch between the icons (including the icons in the menu bar). Multi-page menus are indicated by the page break arrow. Use the rotary button to switch between the menu icons on the different menu pages.
 3‒3 Example: Elements in a two-page menu
1 Back icon 2 Menu bar 3 Menu icon 4 Page change arrow (for multi-page menus) 5 Help icon
Example: In the "Statistics" menu, change [→Main menu]:
1 Turn the rotary button clockwise until the "Statistics" icon (on
the second menu page) turns blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The "Statistics" submenu is called up

3.3.2 Help function

A help text is available for each menu icon.
 3‒4 Help function
Example: Calling up the help text for the "Hot water" menu and stopping the help function again [→Main menu →User]:
1 Turn the rotary button clockwise until the help icon in the menu
bar turns blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The help function becomes active, the "?" symbol is
displayed on the last menu icon.
3 Turn the rotary button anticlockwise until the "?" symbol
appears on the "Hot water" icon.
4 Briefly press the rotary button to confirm ("OK").
Result: The help text for the "Hot water" is displayed.
5 Briefly press the rotary button to confirm ("OK").
Result: Exits the help text level.
6 Turn the rotary button clockwise until the help icon in the menu
bar turns blue.
7 Briefly press the rotary button to confirm ("OK").
Result: The help function is terminated.

3.3.3 Navigating in lists and selecting list entries

Lists exist as pure information lists or can be used to select a list entry. Turning the rotary button switches between the list entries. Multi-page lists are indicated by the page break arrow. Turn the rotary button to switch between the list entries of the different pages.
In the case of selection lists, the currently selected list entry is indicated by a tick. Click "OK" to select another list entry. The corresponding setting is then accepted and the list is exited.
Operating instructions
8
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 9
 3‒5 List with selected list entry
Example: Switch the operating mode to "Summer" [→Main menu →Operating mode]
1 Turn the rotary button clockwise until the "Summer" list entry is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The box is ticked in the "Summer" list entry.
3 Turn the rotary button anticlockwise until the Back icon turns
blue.
4 Briefly press the rotary button to confirm ("OK").
Result: The setting is saved and the setting level is exited.

3.3.4 Setting setpoints

The setpoint of a parameter can be changed within the displayed scale. Click "OK" to save the new value. Press and hold the rotary button to exit the setting level without saving. For some parameters there is an "Off" setting in addition to values on the scale. This setting can be selected by turning the rotary button anticlockwise after the minimum value of the scale has been reached.
3 Operation
2 Briefly press the rotary button to confirm ("OK").
Result: The setting is saved and the setting level is exited.

3.3.5 Setting the times

The clock function is used to set the current time.
 3‒7 Setting the times
Example: Set the time to 16:04 [→ Main menu → Settings →Display →Time]:
1 Turn the rotary button clockwise until the circle is displayed in
blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The hour hand is displayed in blue.
3 Turn the rotary button clockwise until 16:00 is displayed.
4 Briefly press the rotary button to confirm ("OK").
Result: The minute hand is displayed in blue.
5 Turn the rotary button clockwise until 16:04 is displayed.
6 Briefly press the rotary button to confirm ("OK").
Result: The Confirm icon in the menu bar is displayed in blue.
7 Briefly press the rotary button to confirm ("OK").
Result: The setting is saved and the setting level is exited.
 3‒6 Display of the parameter setting
1 Minimum value 2 Default value 3 Currently selected value 4 Maximum value
Example: Set [Room temperature target 1] to 22°C [→ Main menu
→User →Room →Room temperature target 1]:
1 Turn the rotary button clockwise until 22°C is displayed.
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020

3.3.6 Calendar function

The calendar function is used to set the current date or the "Holiday" and "Public holiday" time programs. The calendar function allows the selection of a time period for the time programs.
 3‒8 Setting the period with the calendar function
Operating instructions
9
Page 10
3 Operation
Example: Set [Holiday] from 16 July2020 – 20July 2020 [→Main
menu →Time program →Holiday]:
1 Turn the rotary button clockwise until the month selection is
Jul2020.
2 Briefly press the rotary button to confirm ("OK").
Result: 1July is shown with a blue border.
3 Turn the rotary button clockwise until 16July is highlighted in
blue.
4 Briefly press the rotary button to confirm ("OK").
Result: 16July is shown on a grey background.
5 Turn the rotary button clockwise until 20July is highlighted in
blue.
6 Briefly press the rotary button to confirm ("OK").
Result: The setting is saved and the setting level is exited.
When a new holiday period is set, the previously set holiday period is automatically deleted. Alternatively, the holiday setting can also be reset.
Example: Reset the holiday setting [→Main menu →Time program →Holiday]:
1 Turn the rotary button clockwise until the month selection is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The last selected day of the holiday is displayed with a
blue border.
3 Turn the rotary button anticlockwise until all days are shown in
white.
4 Briefly press the rotary button to confirm ("OK").
Result: The holiday setting is reset and the setting level is
exited.

3.3.7 Setting the time programs

The time program function is used to set permanent time programs (see "4.3.2Permanent time programs"[413]). This allows the daily setting of 3switching cycles. The times can be entered separately for each individual weekday or in blocks of "Monday to Friday", "Saturday to Sunday" and "Monday to Sunday". The selected switching cycles are highlighted in grey ("  3‒9 Time program
function with overview level (left) and setting level (right)" [410]) in
the overview level of the respective program.
 3‒4 Structure of the permanent time programs
Time period Switching cycle
Single day of the week (Monday, Tuesday ...)
Working week (Monday to Friday)
Weekend (Saturday to Sunday) 1. 06:00 to 22:00
Entire week (Monday to Sunday) 1. 06:00 to 22:00
1. 06:00 to 22:00
2. xx:xx to xx:xx
3. xx:xx to xx:xx
1. 06:00 to 22:00
2. xx:xx to xx:xx
3. xx:xx to xx:xx
2. xx:xx to xx:xx
3. xx:xx to xx:xx
2. xx:xx to xx:xx
3. xx:xx to xx:xx
INFORMATION
Time settings for a switching cycle in a weekday or block program will also be accepted for other time periods as long as they are for the same weekdays.
▪ The starting time in the first switching cycle is changed
from 06:00 am to 05:00 am for the individual weekday "Monday". In the period "Monday to Friday" and "Monday to Sunday", the first switching cycle is automatically changed from 06:00 to 05:00.
 3‒9 Time program function with overview level (left) and setting
level (right)
Example: For the [Heating circuit auto. 1] program, set switch cycles 1 and 2 for Monday to Friday [→Main menu →Time program →HC auto 1]:
1 Turn the rotary button clockwise until the "Settings" icon is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: Display changes to setting level with blue flashing
period selection.
3 Turn the rotary switch clockwise until the required time period is
displayed.
4 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the start
time of the first switching cycle.
5 Briefly press the rotary button to confirm ("OK").
Result: Input window for start time of the first switching cycle
flashes blue.
6 Turn the rotary button clockwise until the required start time is
displayed.
7 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the end
time of the first switching cycle.
8 Turn the rotary button clockwise until the required end time is
displayed.
9 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the start
time of the second switching cycle.
10 Briefly press the rotary button to confirm ("OK").
Result: Input window for the start time of the second switching
cycle flashes blue.
11 Turn the rotary button clockwise until the required start time is
displayed.
12 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the end
time of the second switching cycle.
13 Turn the rotary button clockwise until the required end time is
displayed.
14 Briefly press the rotary button to confirm ("OK").
Result: The display changes to the input window for the start
time of the third switching cycle.
Operating instructions
10
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 11

4 Function

15 Turn the rotary button clockwise until the Confirm icon turns
blue.
Result: The display changes to the Confirm icon.
16 Briefly press the rotary button to confirm ("OK").
Result: The programming is saved.
Result: The setting level is exited.
Result: Selected switching cycles are highlighted in grey.
17 Turn the rotary button anticlockwise until the Back icon turns
blue.
18 Briefly press the rotary button to confirm ("OK").
Result: The menu is exited

3.3.8 External operation

In addition to operation via the integrated RoCon+ HP1 controller, the system can also be adjusted and operated via external devices.
Operation via the Internet
An optional (RoCon G1 (EHS157056)) gateway can be used to connect the RoCon+ HP1 controller to the Internet. This enables remote control of the RoCon+HP1 by mobile phone (using an app).
Operation via the room station
It can also be operated via the optional RoCon U1 (EHS157034) room station. The operating elements and instructions for use are described in the "Daikin RoCon HP, EHS157034, EHS157068 Operating Instructions " (available in digital form). All application instructions are also valid for the indoor unit.
4 Function
The system fully automatically controls the operation of the room heating, room cooling and domestic hot water preparation on the sanitary side on the basis of the specifications set in the RoCon +HP1 controller. The functions that can influence system operation are described below.
Some of the functions and parameters described are restricted by access rights and can only be set by a heating specialist (see
"4.5.1Access rights (technician code)"[416]).

4.1 Operating mode

[→Main menu →Operating mode]
This menu is used to select the operating mode for operating the device. The current operating mode is indicated by a corresponding symbol on the start screen.
Standby operating mode (Standby)
NOTICE
A heating system that is not protected against frost can freeze in the event of frost and thus be damaged.
▪ Drain the heating system on the water side if there is a
danger of frost.
▪ If the heating system is not drained, the power supply
must be ensured and the mains switch must remain switched on if there is a risk of frost.
In this operating mode, the indoor unit is switched to standby mode. The freeze-up protection function remains unchanged. In order to maintain this function, the system must not be disconnected from the mains.
All controllers integrated in the RoCon system via the CAN bus are primarily also switched to the "Standby" operating mode.
INFORMATION
In the "Standby" operating mode, the heat pump and the optionally connected backup heater are disconnected from the power supply (energy-saving mode) if the following conditions are met:
▪ the outdoor temperature sensor is connected and
correctly parametrised in the system configuration
▪ the outside temperature is more than 8°C
▪ there is no heating request
▪ the freeze-up protection function is not active in any
connected HC and
▪ the indoor unit has been switched on for at least
5minutes.
Reduce operating mode
Reduced heating operation (lower room target temperature) according to the set reduction temperature in the [Reduce room temperature] parameter (see "4.2User"[412]).
Domestic hot water preparation according to the target leaving water temperatures and switching cycles in the [Hot water auto. 1] hot water time program (see "4.2User"[412]).
Heating operating mode
Heating, cooling operation according to the room target temperature set in the [Room temperature target 1] parameter (see
"4.2User"[412]).
A connected outdoor temperature sensor (weather-compensated leaving water temperature control), a connected RoCon U1 (EHS157034) room station or a connected room thermostat also influence the target leaving water temperature.
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
11
Page 12
4 Function
Domestic hot water preparation according to the target leaving water temperatures and switching cycles in the [Hot water auto. 1] hot water time program (see "4.2User"[412]).
Summer operating mode
Only domestic hot water preparation according to the set target temperatures and switching cycles is carried out in the [Hot water auto. 1] hot water time program (see "4.2User"[412]).
All controllers integrated in the RoCon system via the CAN bus are primarily also switched to the "Summer" operating mode.
Automatic 1 operating mode (time program)
Automatic heating and setback mode according to the permanent time programs (see "4.3Time program"[413]):
▪ [Heating circuit auto. 1]
▪ [Hot water auto. 1]
Automatic 2 operating mode (time program)
Automatic heating and setback mode according to the permanent time programs (see "4.3Time program"[413]):
▪ [Heating circuit auto. 2]
▪ [Hot water auto. 2]
INFORMATION: Switching contact for external operating mode changeover
A potential-free switching contact connected to the "Ext" terminals on connection J8 of the indoor unit and wired with a resistor can also be used to change over from an external device (e.g. modem, ...). See "  4‒1 Resistance
values for evaluating the EXT signal"[412].
In this case, the switching contact functionality is dependent on the parameter [Func. burner blocking contact]:
▪ [Func. burner blocking contact] = "Resistance
values" (default setting): Evaluation of the resistance values.
▪ [Func. burner blocking contact] = "Burner blocking
contact": Evaluation as a burner blocking contact. If the switching contact is closed, the external heat generator has priority.
 4‒1 Resistance values for evaluating the EXT signal
Operating mode Resistance Tolerance
Standby <680Ω ±5%
Heating 1200Ω
Reduce 1800Ω
Summer 2700Ω
Automatic 1 4700Ω
Automatic 2 8200Ω
INFORMATION
The resistances specified in "  4‒1 Resistance values for
evaluating the EXT signal" [4 12] in a tolerance field of
5%. Resistances outside this tolerance field are interpreted as an open input. The heat generator switches back to the previously active operating mode.
The input is not considered for resistance values greater than the value for "Automatic 2".
If several switching contacts are connected to the indoor unit (e.g. smart grid, room thermostat), the associated functions may have a higher priority than the external mode switching. The operating mode requested by the EXT switching contact is then possibly not activated or is only activated later.
Besides these operating modes, different temporary time programs (see "  4‒2 Overview of temporary time programs" [4 12]) are available that are carried out with priority after activation.
 4‒2 Overview of temporary time programs
Temporary heating
program
Party Time program "4.3Time pro-
Absent
Public holiday
Holiday
Screed Configuration "4.5.7Additional
INFORMATION
If a temporary heating program (Party, Absent, Public holiday, Holiday, Screed) is started during the selected operating mode, control is carried out primarily according to the settings for this time program.
Setting/activation in
the menu
Information
gram"[413]
program"[419]

4.2 User

[→Main menu →User]
The most important target temperatures and functions are set for the user in this menu.

4.2.1 Room temperature target setting

[→Main menu →User →Room]
The room target temperatures for room heating in heating operation are defined in this menu. The available setpoints (1-3) belong to the respective cycle (1-3) of the [Heating circuit auto. 1] and [Heating circuit auto. 2] time programs.
Further explanations and possible settings for this menu can be found in "7.3User"[429].

4.2.2 Room temperature reduced setting

[→Main menu →User →Reduce]
The room target temperatures for room heating in Reduced mode are defined in this menu. The reduced operation is carried out by the "Reduce" operating mode or by the "Heating circuit auto. 1" and "Heating circuit auto. 2" time programs.
Further explanations and possible settings for this menu can be found in "7.3User"[429].

4.2.3 Room temperature absent setting

[→Main menu →User →Absent]
The room target temperature for room heating in Absence mode are defined in this menu. The absence operation is carried out by the "Absent" or "Holiday" time programs.
Further explanations and possible settings for this menu can be found in "7.3User"[429].

4.2.4 Hot water temperature, target setting

[→Main menu →User →Hot water]
The hot water target temperatures for domestic hot water preparation are defined in this menu. The available setpoints (1-3) belong to the respective cycle (1-3) of the "Hot water auto. 1" and "Hot water auto. 2" time programs.
Further explanations and possible settings for this menu can be found in "7.3User"[429].
Operating instructions
12
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 13
4 Function

4.2.5 Unscheduled domestic hot water preparation

[→Main menu →User →1x load]
By starting this function, the hot water can be heated up to the [Hot water temperature target 1] target temperature at any time. The heating up is carried out with priority and independent of other heating programs. After this temporary function has elapsed, the controller automatically jumps back to the previously active operating mode.
Possible settings for this menu can be found in "7.3User"[429].

4.3 Time program

[→Main menu →Time program]
Various freely adjustable permanent time programs are available for convenient and individual room and hot water temperature control. Temporary time programs are also available, which override the permanent time programs or the currently set operating mode for the duration of their validity.

4.3.1 Temporary time programs

INFORMATION
The following temporary time programs can be cancelled at any time due to the manual changing of the operating mode.
Party
[→Main menu →Time program →Party]
The program runs from activation until the end of the set period. During this time, the HC is controlled to the temperature set in the [Room temperature target 1] parameter. If the [Automatic 1] or [Automatic 2] time program is active, the heating cycle is extended or started prematurely. The domestic hot water preparation is not affected.
Absent
[→Main menu →Time program →Absent]
The program runs from activation until the end of the set period. During this time, the HC is controlled to the room target temperature in the [Room temperature absent] parameter. The domestic hot water preparation is not affected.
Holiday
[→Main menu →Time program →Holiday]
A calendar function can be used to enter a time period of absence. During this time, the HC is continuously controlled (24 h per day) to the room target temperature set in the [Room temperature absent] parameter. This program is not started if the Standby operating mode is active on the set start date.
Public holiday
[→Main menu →Time program →Public holiday]
A calendar function can be used to enter a time period of presence. During this time, regulation is carried out exclusively according to the settings for "Sunday" in [Heating circuit auto. 1] and [Hot water auto. 1].

4.3.2 Permanent time programs

For the connected HCs and the storage tank charging circuit, time programs control the HC and hot water temperatures or the operating times of the circulation pump according to the specified switching cycles. The switching cycles are saved in time blocks for which different target temperatures can be set.
The saved time program can be changed at any time. For a better overview, it is recommended to write down and safely store the programmed switching cycles ("11.1Timers"[452]).
Heating circuit auto. 1 and Heating circuit auto. 2
[→Main menu →Time program →HC auto 1/HC auto 2]
The time programs for the HC can be parametrised in these menus. Three switching cycles can be set per day, to which the [Room temperature target 1/2/3] parameters are assigned. Outside the switching cycles, it is controlled to the [Reduce room temperature] setpoint. The entry can be made separately for each individual weekday or in week segments.
Hot water auto. 1 and Hot water auto. 2
[→Main menu →Time program →DHW auto 1/DHW auto 2]
The time programs for the domestic hot water preparation can be parametrised in these menus. Three switching cycles can be set per day, to which the [Hot water temperature, target 1/2/3] parameters are assigned.
Outside of the switching cycles, it is controlled to the minimum adjustable setpoint (see "7.3.4 Menu: Hot water temperature,
target"[429]).
Circulation program
[→Main menu →Time program →Circulation]
A time program for an optionally connected circulation pump can be parametrised in this menu. 3 switching cycles per day can be set.
INFORMATION
Use of circulation lines not permitted in France!
Sound program
INFORMATION
During quiet mode, the output in room heating and room cooling operation decreases so that it may no longer be possible to achieve pre-set target temperature values. This program can therefore only be set by the installer.
In this menu, a time program can be parametrised for various stages of the heat pump quiet mode. 3 switching cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
A noise level can be assigned to each switching cycle:
▪ 0 – no noise reduction,
▪ 1 – low noise reduction,
▪ 2 – medium noise reduction,
▪ 3 – maximum noise reduction.
Factory settings
The permanent time programs are preset according to the following factory settings.
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
13
Page 14
4 Function
 4‒3 Factory setting of the permanent time programs
Switching cycle 1 Switching cycle 2 Switching cycle 3
Time period On Off On Off On Off
Room heating
Temperature setting [Room temperature target 1]: 20°C [Room temperature target 2]: 20°C [Room temperature target 3]: 20°C
[Reduce room temperature]: 10°C
"Heating circuit auto. 1"
Monday – Friday 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
Saturday, Sunday 07:00 23:00 - - : - - - - : - - - - : - - - - : - -
"Heating circuit auto. 2"
Monday – Friday 06:00 08:00 16:00 22:00 - - : - - - - : - -
Saturday, Sunday 07:00 23:00 - - : - - - - : - - - - : - - - - : - -
Domestic hot water preparation
Temperature setting [Hot water temperature target 1]:
48°C
"Hot water auto. 1"
Monday – Sunday 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
"Hot water auto. 2"
Monday – Friday 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
Saturday, Sunday 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
"Circulation program"
Monday – Friday 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
Saturday, Sunday 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
Monday – Sunday - - : - - - - : - - - - : - - - - : - - - - : - - - - : - -
[Hot water temperature target 2]:
"Sound program"
48°C
[Hot water temperature target 3]:
48°C

4.3.3 Time program reset

[→Main menu →Time program →TP reset]
This menu can be used to reset the time programs to factory settings. To do this, select the respective time programs and then confirm the selection with the Confirm button on the second menu page.

4.4 Settings

[→Main menu →Settings]
The basic settings of the controller and the system are made in this menu. This includes the integration of optional and external components. Depending on the access authorisation (user or expert), different parameters are available.

4.4.1 Display settings

[→Main menu →Settings →Display]
This menu can be used to set the following parameters: Language, date, time, LCD brightness and LCD illumination time.
Further explanations and possible settings for this menu can be found in "7.5Settings"[431].
INFORMATION
Increasing the brightness of the LCD display beyond the factory-set value will reduce the life of the display.

4.4.2 System

[→Main menu →Settings →System]
This menu combines basic parameters of the heating system.
Further explanations and possible settings for this menu can be found in "7.5.2Menu: System"[432].

4.4.3 External heat sources

[→Main menu →Settings →Ext. source]
This menu can be used to configure the integration of an optional external heat source.
The heat supplied by an alternative heat generator (WEZ) must be fed to the unpressurised cylinder water in the hot water tank of the indoor unit.
▪ On use of the optional EKBUxx backup heater, this is carried out
due to the design installation situation.
▪ When using an alternative WEZ (e.g. gas- or oil-fired boiler), this
can be hydraulically integrated:
▪ unpressurised via the connections (solar feed and solar return)
of the hot water storage tank or
▪ with Daikin Altherma EHS…B… and ETS…B… device types,
via the integrated pressure solar heat exchanger
The setting of the [Config. ext. heat source] parameter determines whether and which additional heat generator (WEZ) is available for domestic hot water preparation (DHW) and heating support (HZU).
▪ No external heat source
▪ Optional backup heater
▪ External heat source for DHW and heating support: Alternative
WEZ provides domestic hot water preparation and heating support. To request the WEZ, relay K3 is switched for connections X1-L1 and XBUH1-T1 on the RTX-EHS PCB.
▪ External heat source for DHW or HZU: Alternative WEZ 1
(optional EKBUxx backup heater) provides domestic hot water preparation and alternative WEZ 2 provides heating support. To request the WEZ 1, relay K3 (connections X1-L1 and XBUH1-T1) is switched on the RTX-EHS PCB and to request the WEZ 2, relay K1 (connections X1-L3 and XBUH1-T3) is switched on the RTX-
Operating instructions
14
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 15
4 Function
EHS PCB. Heed warning notice! The operation of an additional alternative WEZ is also influenced by the settings of the [Bivalence function] and [Bivalence temperature] parameters.
Further explanations and possible settings for this menu can be found in "7.5.3Menu: External heat source"[433].

4.4.4 Inputs/Outputs

[→Main menu →Settings →Inputs/Outputs]
This menu can be used to adjust parameter for inputs and outputs of the controller PCB to optimise the system controller individually.
Smart grid
WARNING
There is a danger of scalds at hot water target temperatures over 65°C. This is possible because the utility company (EVU) is entitled to control current draw optimised according to supply and demand in the definitions for Smart Grid.
Such forced charging can cause the hot water target temperature in the hot water tank to exceed 65°C.
This storage tank charging is carried out even when "Standby" operating mode is set.
▪ Install scald protection in the hot water distribution line.
To use this function, a special electricity meter with SG receiver to which the heat pump must be connected is required.
As soon as the function is activated by the [Smart grid] parameter, the heat pump is set to an operating mode as per the following table depending on the utility company signal.
 4‒4 Use of the SG signal
(1)
Signal
EVU SG Hot water Heating
1 0 --- No operation
0 0 Normal Normal
0 1 low Switch-on re-
1 1 Very low Switch-on com-
AUX switching function
Setting the [AUX switching function] parameter determines the switching conditions for the potential-free AUX switching contact (toggle switch output A). This switching contact can be used to control an external heat generator, for example.
Electricity
costs
Effect on
operation
commendation,
and storage
tank setpoint
temperature
value is in-
creased de-
pending on the
[Smart grid
mode] para-
meter.
mand and stor-
age tank set-
point temperat-
ure is set to
70°C.
installations
(2)
No operation
Normal
operation
Switch-on re­commendation, and target leav-
ing water tem-
perature is in-
creased de-
pending on the
[Smart grid
mode] para-
meter.
Switch-on com-
mand for stor-
age tank char-
ging
(2)
(3)
If one of the switching conditions is fulfilled, the potential-free switching contact is switched after the time set in the [AUX wait time] parameter.
AUX switching contact (toggle switch output A) is not switched if the switch function is deactivated. [AUX switching function] parameter = "Inactive".
AUX switch contact (toggle switch output A) is switched when one of the following conditions is set:
▪ Storage tank temperature (T
) ≥ [Switching threshold TDHW
dhw
(AUX)] parameter value.
▪ if an error is pending.
▪ Outside temperature <[Bivalence temperature] parameter value.
▪ Heat request for domestic hot water preparation.
▪ Heat request for room heating or cooling requirement.
▪ Heat request for room heating or domestic hot water preparation.
▪ "Cooling" operating mode active.
Interlink function
Setting the [Interlink function] parameter = "On" provides the option that the indoor unit includes two different leaving water temperature setpoints in the controller.
This applies to both weather-compensated control and control according to a fixed target leaving water temperature (see
"4.5Configuration"[416]).
One possible application is, for example, the additional integration of an HP convector in a surface heating and cooling system.
Prerequisite: 2 switching contacts (e.g. room thermostats) are connected to the plug connection J16 of the indoor unit.
▪ [Interlink function] parameter = "Off": Deactivated
▪ [Interlink function] parameter = "On": Evaluation of the heating and
cooling switching contacts at plug connection J16 on the RoConBM2C PCB: Activation of cooling operation only by switching the operating mode to "Cooling" (see "4.1 Operating mode" [4 11]). [Room thermostat] parameter must be set to "Yes".
1 Open switching contacts: Only freeze-up protection active
2 "Heating" or "Automatic 1" / "Automatic 2" operating mode
active during the switching cycles in day mode.
▪ Closed heating switching contact = IL1: It is controlled to the
normal target leaving water temperature according to the parameter settings for [Heating].
▪ Closed cooling switching contact = IL2: It is controlled to the
increased target leaving water temperature (normal target leaving water temperature + value of the [Interlink temperature increase] parameter). Priority if both switching contacts are closed!
3 "Cooling" operating mode active.
▪ Closed heating switching contact = IL1: It is controlled to the
normal target leaving water temperature according to the parameter settings in level [Heating circuit config.] > [Cooling].
▪ Closed cooling switching contact = IL2: It is controlled to the
reduced target leaving water temperature (normal target leaving water temperature – value of the [Interlink temperature increase] parameter). Priority if both switching contacts are closed!
Further explanations and possible settings for this menu can be found in "7.5.4Menu: Inputs/Outputs"[433].
(1)
Switching contacts at input J8 of the RoConBM2C PCB closed(1) or open(0).
(2)
No freeze-up protection function
(3)
When the charging process is completed, heating is carried out according to the settings for the respective HC. Heating support from the HC active if [Heating support (HZU)] parameter = "On".
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
15
Page 16
4 Function

4.4.5 Intelligent storage tank management

[→Main menu →Settings →ISM]
If the storage temperatures are high enough, the energy in the storage tank can be used for room heating. This can either increase comfort ([Continuous heating] function) or make it possible to use energy from an external heat source, e.g. solar, when heating is required ([Heating support (HZU)] function).
Continuous heating
The activated Continuous heating function ([Continuous heating] parameter = "On") allows uninterrupted heating even during defrosting of the evaporator. This enables high comfort to be guaranteed, even with rapidly reacting heating systems (e.g. convectors).
Heating support (HZU)
If the heating support ([Heating support (HZU)] parameter = "On") is activated, the energy in the built-in storage tank of the indoor unit is used to perform the heating function. If the storage tank temperature is sufficiently high, the heat generation by the heat pump remains out of operation.
The minimum required storage tank temperature (T calculated as follows:
T
= Currently active hot water target temperature
HZUmin
(1)
+hysteresis
a) Switch-on condition:
Tdhw>T
+4 K and Tdhw>Information parameter [Feed
HZUmin
temperature, target]+1K
If the switch-on condition is fulfilled, heat is taken from the storage tank and this is used to supply the heating system.
b) Switch-off condition:
Tdhw<T
or Tdhw<Information parameter [Feed temperature,
HZUmin
target] (see "7.7.2Values"[444])
If the switch-off condition is met, heating support from the hot water storage tank is ceased, and the heat pump takes over heating operation.
The [Heating support power] parameter limits the maximum power that can be taken. The [Heating support max. temp.] parameter limits the maximum temperature that can enter the heating system.
Further explanations and possible settings for the parameters in this menu can be found in "7.5.5Menu: Intelligent Storage Mgmt"[436].
HZUmin
) is

4.5 Configuration

[→Main menu →Configuration]
This menu can be used to optimally adapt the operating characteristics of the system to the system structure and the needs of the users. Additional programs facilitate commissioning. Depending on the access authorisation (user or expert), different parameters are available.

4.5.1 Access rights (technician code)

[→Main menu →Configuration →Access]
Certain functions and parameters in the controller are restricted by access rights and are not visible to the user. To gain access to it, the specialist code must be entered.
 4‒1 Setting the access code
Example: Set code 3090 (example only, this is not a valid access code) [→Main menu →Configuration →Access]:
1 Turn the rotary button clockwise until the first input field is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The first input field flashes blue.
(2)
3 Turn the rotary button clockwise until 3 is displayed.
4 Briefly press the rotary button to confirm ("OK").
Result: The second input field is displayed in blue.
5 Turn the rotary button clockwise until the third input field is
displayed in blue.
6 Briefly press the rotary button to confirm ("OK").
Result: The third input field flashes blue.
7 Turn the rotary button clockwise until 9 is displayed.
8 Briefly press the rotary button to confirm ("OK").
Result: The fourth input field is displayed in blue.
9 Turn the rotary button clockwise until the Confirm icon turns
blue.
10 Briefly press the rotary button to confirm ("OK").
Result: The code is checked and the setting level is exited.

4.5.2 Sensors

[→Main menu →Configuration →Sensors]
Optional sensors are activated and configured in this menu. Pressure setpoints for the water side can be defined.
Further explanations and possible settings for the parameters in this menu can be found in "7.6.1Menu: Sensors"[437].

4.5.3 HC config.

[→Main menu →Configuration →HC config]
This menu is used to adjust the basic functionality of the HC.
Further explanations and possible settings for the parameters in this menu can be found in "7.6.2Menu: Heating circuit config."[438].
Weather-compensated leaving water temperature control
If the weather-compensated leaving water temperature control is active, the leaving water temperature ([Feed temperature, target] parameter) is determined automatically according to the set heating/ cooling curve depending on the outside temperature.
(1)
Information parameter [Hot water temperature, target] (see "7.3.4Menu: Hot water temperature, target"[429])
(2)
[Heating support hysteresis] parameter setting (see "7.5.5Menu: Intelligent Storage Mgmt"[436])
Operating instructions
16
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 17
4 Function
This function is activated in the delivery condition. It can only be deactivated (fixed value control) or reactivated with a technician code.
If the RoConU1 (EHS157034) room station is also connected to the RoCon+ HP1, the target temperatures are controlled according to the weather and room temperature [Room influence]) parameter.
This function can only be configured using the technician code. Contact your heating expert in this regard.
This function is activated or deactivated via the [Weather­compensated] parameter in the "Configuration" menu.
▪ [Weather-compensated] parameter = "Weather-compensated":
Weather-compensated leaving water temperature control according to the settings made in the [Heating] and [Cooling] menus.
▪ [Weather-compensated] parameter = "Feed temperature, fixed":
Control based on fixed target temperature
▪ For heating operation: [Feed temperature, heating mode]
parameter or [Feed temperature, reducing mode] parameter
▪ For cooling operation: [Feed temperature, cooling mode]
parameter
INFORMATION
The weather-compensated leaving water temperature control has no influence on the target leaving water temperature in the case of a hot water circuit request.
With mixer module connected
The setting of the heating/cooling curves and the activation of the weather-compensated leaving water temperature control for the assigned HC are carried out in the same way as described above.
The assigned HC can be operated as a:
▪ Mixer add-on
The outside temperature of the outdoor temperature sensor connected to the indoor unit external temperature sensor is transmitted to the mixer module via the CAN bus.
or as a
▪ Mixer add-on with zone control
A separate outdoor temperature sensor must be connected to the mixer module. The assigned HC is controlled according to the outside temperature relevant for this zone.
If the terminal function is activated, the mixer module can be operated and the settings for the assigned HC undertaken via the RoCon+B1 control panel of the indoor unit.
In conjunction with the RoCon U1 (EHS157034) room station, the mixer module can also control the assigned HC completely autonomously and independently of the heat generator.
Further explanations and possible settings for this menu can be found in "7.6Configuration"[437].
Freeze-up protection function
The integrated heating circulation pump is switched on at an external temperature below the [Frost protection temperature] parameter value in order to prevent the heating system from freezing.
In addition, the feed, storage and connected room temperature sensors are also constantly monitored. If the temperature measured by one of these sensors falls below 7°C (below 5°C at room temperature), the antifreeze function is also activated.
If the heating leaving water temperature falls below 7°C, the heat pump heats until the heating leaving water temperature reaches at least 12°C.
The function is ended if the external temperature rises above the set [Frost protection temperature] parameter value+1K and also there is no other activation condition.
INFORMATION
Operation of the heat pump can be shut off completely for a limited period of time by the utility company if the following low-tariff functions are activated:
[HT/NT function] parameter = "Switch all off" or [Smart grid] parameter = "On"
These situations can be recognised if, in the [→ Main menu → Information → Overview] menu in the operating data field "Ext" the "High rate" or "SG1" value is displayed.

4.5.4 Heating

[→Main menu →Configuration →Heating]
This menu is used to configure heating times and target leaving water temperatures for heating operation.
Heating curve
INFORMATION: Overheating and moisture protection
In the event of malfunction, the underfloor heating system, the screed or the floor structure could be damaged due to overheating.
▪ Prior to initial commissioning, set the maximum
temperature limit in the RoCon+HP1 controller ([Max. feed temperature] parameter) to the maximum permissible system temperature before the screed drying starts.
▪ Connect an overheating protection switch (in the
building) at the "EXT" plug connection to external mode switch-over so that the indoor unit is switched to "Standby" or "Summer" mode. If the [Room thermostat] parameter = "Yes" or [Interlink function] parameter = "On", the overheating protection switch must be connected so that the room thermostat's switching contact is interrupted.
▪ If the underfloor heating is also used for room cooling,
the connection notes in the above point also apply to the connection of a moisture protection switch in the building.
The heating curve is used to adapt the leaving water temperature to the characteristics of the building independent of the respective outside temperature (weather-compensated leaving water temperature control, see "4.5 Configuration" [4 16]). Generally speaking, the slope of the heating curve describes the ratio of the leaving water temperature change to the external temperature change.
The heating curve is valid within the limits of the minimum and maximum temperatures set for the respective HC. Deviations may occur between the room temperature measured in the occupied area and the desired room temperature; these can be minimised by installing a room thermostat or a RoCon U1 (EHS157034) room station.
The controller is set at the factory in such a way that the heating curve does not independently adjust itself during operation.
The automatic heating curve adjustment can be activated ([Heating curve adaptation] parameter) if the outdoor temperature
sensor and the room station (RoCon U1 (EHS157034)) are connected (see "4.5Configuration"[416]).
Start conditions for automatic heating curve adjustment:
▪ Outside temperature<8°C
▪ Operating mode is "Automatic 1" or "Automatic 2"
▪ Duration of the setback period is at least 6h
If no automatic heating curve adjustment is activated, the heating curve can be manually adjusted by adjusting the [Heating curve] parameter).
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
17
Page 18
4 Function
INFORMATION: Manually adjusting the heating curve
Do not make any corrections to the set values for 1 – 2 days, and then only make them in small increments.
▪ Deactivate the external heat sources (e.g. stoves,
direct sunlight, open windows).
▪ Fully open any radiator thermostat valves or actuators.
▪ Activate "Heating" operating mode. Approximate setting
values:
Radiator: 1.4 to 1.6.
Underfloor heating: 0.5 to 0.9.
 4‒2 Heating curves
TAOutside temperature TRRoom temperature setpoint TVLeaving water temperature
Comfort heating
If the heat pump cannot cover the heating demand when outside temperatures are very low, heat is extracted from the storage tank and used for room heating. In rare cases (in systems with high required leaving water temperatures and low required hot water temperatures), the required leaving water temperature can be higher than the storage tank setpoint temperature. In order to avoid short­term loss of comfort in heating operation for these systems, the [Comfort heating] parameter can be set to "On". At corresponding outside temperatures, the storage tank temperature is raised above the storage tank temperature set for the hot water requirement.
INFORMATION
If [Comfort heating] is set to "On", the power consumption of the heat pump may increase. In the default setting, [Comfort heating] is set to "Off".
Detailed explanations and possible setting values of this function can be found in "7.6Configuration"[437].

4.5.5 Cooling

[→Main menu →Configuration →Cooling]
This menu is used to make settings for cooling operation.
INFORMATION: Danger of condensation
In the event of malfunction or incorrect parameter settings, the underfloor heating, the screed or the floor structure could be damaged due to condensation.
▪ Prior to initial commissioning and activation of cooling
operation, set the minimum temperature limit to the minimum permissible system temperature in the RoCon + HP1 controller ([Feed temperature lower limit] parameter).
To protect against moisture damage caused by cooling, a moisture protection switch can be connected to the plug connection J8 "EXT" (see "4.5.4Heating"[417]).
Prerequisites for cooling operation:
▪ Outside temperature > set value of room target temperature
Outside temperature > set value of the [Start cooling outside temp.] parameter
▪ "Cooling" operating mode activated.
▪ via menu "Operating mode" or
▪ via room thermostat function (cooling switching contact closed)
▪ No heat request active in the heating system's RoCon system.
INFORMATION
If the mean outside temperature falls below 4°C when "Cooling" operating mode is active, the operating mode automatically switches to "Heating".
Renewed automatic operating mode changeover to "Cooling" only takes place:
▪ if a room thermostat is connected to plug connection
J16 (cooling) and
▪ the room thermostat's switching contact is closed and
▪ the mean outside temperature increases to over 10°C
again.
Cooling curve
[→Main menu →Configuration →Cooling →Cooling curve]
The cooling curve determines the target leaving water temperature in cooling operation depending on the respective outside temperature. (for weather-compensated leaving water temperature control, see "4.5.3HC config." [416]). Warmer outside temperatures result in a colder target leaving water temperature and vice versa. The cooling curve can be adapted to the condition of the building by four parameters (see "  4‒3 Cooling curve parameter
dependency"[419]).
1 [Start cooling outside temp.]
2 [Max. cooling outside temp.]
3 [Target flow cooling, start]
4 [Target flow cooling, max.]
Cooling parameters
[→Main menu →Configuration →Cooling →Parameters]
This menu combines further parameters to determine target leaving water temperatures in cooling operation.
During weather-dependent leaving water temperature control, the user can increase or decrease the target leaving water temperature by a maximum of 5 K with the parameter [Cooling setpoint correction]. A temperature reduction is limited by the [Feed temperature lower limit] parameter.
Operating instructions
18
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 19
 4‒3 Cooling curve parameter dependency
1 [Start cooling outside temp.] parameter 2 [Max. cooling outside temp.] parameter 3 [Target flow cooling, start] parameter 4 [Target flow cooling, max.] parameter 5 [Feed temperature lower limit] parameter 6 Room target temperature 7 Cooling operation possible
TAOutside temperature TVLeaving water temperature
------- Cooling curve
- - - - Possible parallel cooling curve shift
Further explanations and possible settings for the parameters in this menu can be found in "7.6.4Menu: Cooling"[440].

4.5.6 Hot water

[→Main menu →Configuration →DHW]
The domestic hot water preparation can be individually adapted to the behaviour and requirements of the users in this menu. This minimises energy consumption and increases comfort.
Solar function
The [Solar function] parameter is used to reduce the target temperature of the hot water storage tank in order to increase the yield of a connected solar system. The setpoint of the hot water temperature is set as a function of the outside temperature and in compliance with the safety functions. In addition, the following parameters are defined: [Hot water hysteresis] = 5 K; [Building insulation] = "Normal"
To activate the solar function, it must be set in the menu [→Main menu → Configuration →DHW → Solar function] to "On" and the switching contact connected to the plug connection J8 (EXT) must be closed..
Settings for optional circulation pump
Depending on the [Circulation pump control] parameter, an optional circulation pump can be controlled synchronously with the selected time program for domestic hot water preparation or with the time program for the circulation pump (see "4.3 Time program" [4 13]). During the release times of the selected time program, the circulation pump can be operated either continuously or cycled. This is defined with the [Circulation pump interval] parameter.
Anti-legionella protection
This function is used to prevent bacterial contamination in the hot water tank by thermal disinfection. To do so, the hot water tank is heated 1× daily or 1× weekly to the disinfection temperature [Anti­legionella temperature] depending on the [Anti-legionella day] parameter. Disinfection starts at the specified start time [Anti­legionella start time] and is active for one hour. An optionally connected circulation pump is automatically switched on during this time.
Detailed explanations and possible setting values of this function can be found in "7.6.5Menu: Hot water"[441].
4 Function

4.5.7 Additional program

[→Main menu →Configuration →Addition]
This menu combines programs which simplify initial commissioning of the system.
Ventilation function
[→Main menu →Configuration →Addition →Ventilation]
By activating the air purge function, the controller starts a fixed defined sequence program with start/stop operation of the integrated heating circulation pump and various positions of the integrated 3­way changeover valves. Existing air can escape during operation via the automatic air purge valve.
INFORMATION
The activation of this function does not replace correct venting of the HC.
The HC must be completely full before activating this function.
Relay test
[→Main menu →Configuration →Addition →Relay test]
This program allows testing of internal switching relays. This may be necessary in the event of malfunctions, error messages or as part of annual maintenance. When the menu is opened, all relays are deactivated. Selecting one or more relays activates them. When the menu is exited, all relay tests are terminated.
The relay test menu is operated in the same way as list entries (see
"3.3.3 Navigating in lists and selecting list entries"[48]). However,
several relays can be activated in parallel in the relay list for testing. To do this, select the corresponding relay with "OK". Activated relays are indicated by a tick.
Screed drying
[→Main menu →Configuration →Addition →Screed]
The screed drying is started in the menu according to the settings in [Screed program]. The program is used exclusively for the prescribed drying of newly created screed for underfloor heating systems. The first day of the screed program begins after activation of the program at the change of day at 00:00.
Screed drying is a special function and is not interrupted by any other operating mode. It can only be activated by the heating expert for the direct HC and/or optionally connected mixed HCs. It must be activated separately for each HC.
INFORMATION
Before starting the screed drying, the [Room thermostat] and [Interlink function] parameters must be deactivated. During a short-term power failure, a previously activated screed drying is continued at the point of the interruption.
After activation of the screed drying, all weather-compensated control functions of the respective HC are switched off. The respective HC works as a constant temperature control regardless of the operating mode and switching times.
Already activated screed drying can be deactivated at any time. After ending the screed drying, the parameter is automatically set to "Off" and the HC works according to the currently set operating mode again.
Screed program
[→Main menu →Configuration →Addition →Program]
This menu allows the individual adjustment of the factory settings for the duration and target leaving water temperatures of the screed drying. Changes can only be made after entering the specialist code.
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
19
Page 20
4 Function
Changing the screed program
A separate target leaving water temperature can be set for each day for a maximum duration of 28 days. The end of the screed program is defined by the first day without a preset target leaving water temperature.
 4‒5 Default settings of the screed program
Day Factory setting Day Factory setting
1 – 3 25°C 10 – 19 55°C
4 – 7 55°C 20 40°C
8 25°C 21 25°C
9 40°C 22 – 26 -
 4‒4 Changing the screed program
Example: Increase the leaving water temperature of the 3rd day to 40°C and stop the program on the 8th day [→ Main menu →Configuration →Addition →Program]:
1 Turn the rotary button clockwise until the day selection is set to
3.
2 Briefly press the rotary button to confirm ("OK").
Result: The temperature field is displayed in blue.
3 Turn the rotary button clockwise until the temperature selection
is 40°C.
4 Briefly press the rotary button to confirm ("OK").
Result: Temperature selection of the next day is shown in blue
5 Briefly press the rotary button several times until the day
selection is set to 8.
6 Turn the rotary button anticlockwise until the temperature
selection is set to "Off".
7 Briefly press the rotary button to confirm ("OK").
Result: Day 8 to day 28 are set to "Off", the Confirm icon is
shown in blue
8 Briefly press the rotary button to confirm ("OK").
Result: The programming is saved and the menu is exited.
Typical screed programs
Function heating
The function heating serves as proof of the production of defect free work for the heating engineer. A prefabricated heating protocol related to underfloor heating can be found in the Internet portal of the manufacturer.
In this sense, the function heating (identical with "Heating" in EN 1264, section 5.2) is not considered as a heating process to achieve workability of the screed. Generally, a special screed curing heating and/or mechanical drying is required for this.
The heating of cement screeds should be carried out at the earliest after 21days and of anhydrite screeds after 7 days at the earliest in accordance with the specifications of the manufacturer. The first heating begins with a leaving water temperature of 25°C that must
be maintained for 3days. Afterwards, the heating is carried out with the maximum set leaving water temperature for the HC (limited to max. 55°C), which must be maintained for a further 4days.
Due to the insulating effect of the DUO heating pipe for System 70, the screed function must be carried out at higher temperatures. The temperature profile must be adapted in the [Screed program] parameter for this use case. For System70, the heating begins at a temperature of 38°C that is maintained for 3days. The set maximum HC temperature (limited to 70°C) is then maintained for 4 days.
After the described heating process, it is not yet assured that the screed has reached the required moisture content for workability of the screed.
The moisture content in the screed must be checked by measurement prior to laying the surface covering.
INFORMATION
Procedure in accordance with EN1264 Part 4:
For anhydrite and cement screeds, the HCs must be leak tested by a water pressure test after completion. The leaktightness must be ensured immediately before and during the laying of the screed. The height of the test pressure is at least 1.3x the maximum permitted operating pressure.
Suitable measures must be taken if there is a risk of freezing, e.g. use of antifreeze agents or heating the building. If antifreeze agents are no longer necessary for the intended operation of the system, the antifreeze agent must be removed by draining and rinsing the system with at least 3 changes of the water.
 4‒5 Chronological sequence of the screed program during the
function heating
t1Start temperature 25°C t2Maximum HC temperature
tVLeaving water temperature
Z Duration of the screed function in days after starting the
function
Screed curing heating
The drying process for the screed cannot be exactly predicted. If there is a high degree of humidity, sometimes it can stop completely. The drying process can be speeded up by activating the underfloor heating (screed curing heating) or measures such as mechanical drying.
Each screed curing heating must be ordered separately by the client as an extra service in accordance with German construction contract procedures (VOB). The workability of the screed is a prerequisite for the top floor installer to start work so that he can produce defect free work.
With standard settings, the combined function and screed curing heating program can be activated to achieve the required residual moisture in the screed for workability of the screed (see "  4‒6
Chronological sequence of the screed program during the combined function and screed curing heating" [4 21]). However, the residual
moisture of the screed must basically be checked metrologically before the flooring can be laid.
Operating instructions
20
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 21
 4‒6 Chronological sequence of the screed program during the
combined function and screed curing heating
t1Start temperature 25°C t2Maximum HC temperature tVLeaving water temperature Z Duration of the screed function in days after starting the
function
Detailed explanations and possible setting values of this function can be found in "7.6Configuration"[437].

4.5.8 Configuration Wizard

[→Main menu →Configuration →Wizard]
This menu summarises the parameters queried in the Configuration Wizard. This allows a quick adjustment of the system settings. See
"5.1Configuration Wizard"[424].
4 Function
 4‒7 Hydraulic circuit diagram – first page
t-AU Outdoor temperature sensor
P Pressure VVolume flow
t-R Heating return flow temperature t-V leaving water temperature after the plate heat exchanger
t-V,BH Heating leaving water temperature; if necessary, after
heating support heat exchanger
t-liq Refrigerant temperature
T-DHW Temperature in the hot water storage tank

4.5.9 Parameter reset

[→Main menu →Configuration →Parameter reset]
All customer-specific parameter settings can be reset to factory settings in this menu. This can be useful if the indoor unit no longer functions properly and no other causes of malfunction can be identified.

4.6 Information

[→Main menu →Information]
This menu displays all system temperatures, the heat generator type, various software information and the operating states of all system components. The number of displayed parameters depends on which components are connected. No adjustments can be made to these values.

4.6.1 Current

[→Main menu →Information →Current]
This menu shows the hydraulic diagram of the system. The first and second pages show sensors and the assigned, current values. The third page shows the compressor, pump and heating rod in white if they are inactive and blue if they are active. The current valve position is shown for both 3-way valves.
 4‒8 Hydraulic circuit diagram - second page
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
 4‒9 Hydraulic circuit diagram – third page
B1 Current position of the 3-way mixing valve 3UVB1
(0%:heating network; 100%:internal bypass)
DHW Current position of the 3-way distributor valve 3UV DHW
(0%:heating network; 100% hot water storage tank)
Operating instructions
21
Page 22
4 Function

4.6.2 Overview

[→Main menu →Information →Overview]
This menu lists the current operating states of the heat pump and its components.
Further explanations of the parameters in this menu can be found in
"7.7Information"[443].

4.6.3 Values

[→Main menu →Information →Values]
In this menu, the current setpoint and actual values are listed.
Further explanations of the parameters in this menu can be found in
"7.7Information"[443].

4.6.4 Water pressure

[→Main menu →Information →Water pressure]
The current water pressure is displayed in large font in this menu. This makes it easier to read during the installation of the system.

4.7 Error

[→Main menu →Error]
The error handling of the heat pump takes place in this menu. See
"8Errors and faults"[447].

4.8 Terminal

[→Main menu →Terminal]
This menu can also be used to operate and parametrise other devices integrated in the RoCon system via the CAN bus (control components mixer module or heat generator), provided the respective control panel has the required authorisation.
Functional IDs
The RoCon system offers a very wide range of application and extension options. The individual RoCon system components communicate via the CAN data bus. To do this, the RoConBM2C PCBs and the RoCon+B1 control panels of the indoor unit and, if necessary, the optional RoCon U1 (EHS157034) room station system components and RoConM1 (EHS157068) mixer module are connected to each other via data bus cables. These system components must be allocated unique functional IDs, so that the data exchange and the assignment within the RoCon system functions without any problems.
The easiest way to assign the functional identifiers is to use the Configuration Wizard. This is carried out automatically during the first commissioning or can be started manually in case of extensions in the heating system in [→Main menu →Configuration →Wizard]. In addition, most identifiers can also be adapted to the RoCon system by parameter settings in this menu.
 4‒6 Functional IDs in the RoCon system
ID/Function System components Parameters Comments
HC ID
Unique numbering of a HC in the heating system in the RoCon system. A maximum of 16 HCs can be controlled.
Heat generator ID
Unique numbering of a heat generator in the RoCon system.
(1)
Indoor unit (RoConBM2C) [Direct circuit
configuration]
See "7.11Configuration
Wizard"[446]
RoConU1 (EHS157034)
room station
RoConM1 (EHS157068)
mixer module
[Heating circuit
assignment]
see RoCon U1/M1
instructions
(2)
[Heating circuit
assignment]
see RoCon U1/M1
instructions
(2)
Indoor unit (RoConBM2C) [Bus ID heat generator]
See "7.11Configuration
Wizard"[446]
RoConM1 (EHS157068)
mixer module
[Boiler Assignment]
see RoCon U1/M1
instructions
(2)
Factory setting = 0
Should not normally be changed.
Factory setting = "Off"
Adaptation required if there are different HCs in the system and/or the [Master-RoCon] parameter = "On"
Factory setting = "Off"
Must always be adapted to the setting of the address switch.
Factory setting = 0
Should not normally be changed.
Factory setting = 0
Should not normally be changed.
Defines the heat generator that supplies the assigned HC with heat.
(1)
(1)
(1)
(1)
A maximum of 8 heat generators can be connected in the RoCon system via the CAN data bus. Several heat generators integrated in the heating system must be regarded as a special application. If necessary, contact a service technician.
(2)
"Operating instructions for Daikin RoConHP, EHS157034, EHS157068", status 04/2017, available in digital form: www.daikin.eu, search for "EHS157034"
Operating instructions
22
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 23
ID/Function System components Parameters Comments
Terminal ID
Unique numbering of a RoCon+B1 or EHS157034 control panel from which a heat generator and/or mixer module can be remotely controlled in the RoCon system.
The authorisation for remote control can be allocated to up to 10 control panels in the RoCon system. If remote control is to be possible in the RoCon system, the control panel must be allocated the ID "0".
Device ID
Unique numbering of a heat generator or mixer module in the RoCon system.
Up to 16 device numbers can be allocated.
These device numbers are detected during a [Bus scan] and are displayed for identification of a remotely controlled device.
Indoor unit (RoConBM2C) [Terminal address]
See
"7.9Terminal"[445]
RoConU1 (EHS157034)
room station
Indoor unit (RoConBM2C) [Bus ID heat generator]
RoConM1 (EHS157068)
mixer module
[Terminal address]
See
"7.9Terminal"[445]
See "7.11Configuration
Wizard"[446]
[Heating circuit
assignment]
See "9Mixer
module"[448]
Factory setting = "Off"
The value should be set to "0" if at least 1 mixer module is connected in the RoCon system and the mixer circuit is to be operated from the heat generator.
Factory setting = "Off"
The value must be set to a unique numerical value in the RoCon system if the room station system components are to be remotely controlled using a valid device ID.
Identical to heat generator detection.
The value must not be the same as the HC ID of a mixer module in the RoCon system.
Identical to the HC ID.
The value must not be the same as the heat generator ID of the heat generator in the RoCon system.
The value must be the same as the setting of the address switch.
4 Function

4.8.1 Selecting the terminal address

[→Main menu →Terminal →Address]
Setting of the terminal ID of the control panel for system access. The set value must be unique throughout the entire system. Confirmation of this parameter with the rotary button effects a new initialisation of the controller.
All settings except "Off" authorise the user of the control panel to activate the terminal function and thus to operate all RoCon system components with a valid device ID.

4.8.2 Bus scan for terminal function

[→Main menu →Terminal →Bus scan]
After activating the "Bus scan", a list of detected devices (with assigned terminal address) is displayed in the menu [→ Main menu →Terminal] for selection. After selecting and confirming an external device, the terminal function for this device is activated. The control panel is then in terminal operation.
The local control panel acts as a remote controller for the external device and the corresponding start screen is shown on the display. In this case, all the control functions are performed and saved 1:1 in the same way as on the external device. The displayed values and symbols are always taken over by the selected device.
To operate the local device, switch to the start screen of the external device. Press and hold the rotary switch to return to the menu of the local device.
INFORMATION
To perform the bus scan, a valid terminal address must be assigned to the RoCon+B1 control panel of the indoor unit or the RoConU1 (EHS157034) room station. This can only be done with a specialist code. Contact your heating expert in this regard.
If the terminal function is to be used in the heating system, the terminal ID = 0 ([Terminal address] parameter = "0") must be assigned to a control panel.
Example: Activate terminal operation for the heat generator with bus identification 2 [→Main menu →Terminal →Bus scan]:
The bus scan is carried out. An overview of all devices that are found is displayed.
1 Turn the rotary switch clockwise until the BM1/BE1 #2 controller
is displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
Result: The local control panel acts as a remote controller for
the heat generator with bus ID 2.
To end terminal operation and switch the control panel back to the operation of the assigned device, switch to the start screen of the external device. Press and hold the rotary switch to return to the menu of the local device.
INFORMATION
If the local control panel is used as a remote controller for a mixer module, both the standard screen and the menu structure are changed (see "9Mixer module"[448]).

4.9 Statistics

INFORMATION
The values listed in this menu are approximate values. In particular if glycol is present in the system, there may be greater deviations from real performance data.
[→Main menu →Statistics]
This menu can be used to access the values for the power output and run times of the heat pump and its components. The [Electr. energy total] parameter describes the total electrical power input of the heat pump and its components. All other values refer to the energy provided by the heat pump or the run time of various components.

4.9.1 Month

[→Main menu →Statistics →Month]
This menu can be used to call up summed values for the power output and power input over the month. The displayed value is assigned to the month shown in blue on the diagram. The various values can be displayed by turning the rotary switch.

4.9.2 Total

[→Main menu →Statistics →Total]
This menu can be used to call up summed values for the power output and power input of the heat pump since commissioning (or since the last reset by a specialist).
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
23
Page 24

5 Initial commissioning

5 Initial commissioning
INFORMATION
In addition to the commissioning instructions listed in this chapter, the specific commissioning instructions listed in the respective installation instructions for the heat pump must be observed.

5.1 Configuration Wizard

The Configuration Wizard simplifies system configuration during installation. It appears automatically during initial commissioning and guides the user through defined selection pages. As long as the entire system setting is not confirmed, the Configuration Wizard is called up again each time it is switched on. Only after confirmation of the system setting can the heat generator switch to normal operation. In normal operation, the parameters of the Configuration Wizard can be called up and set in the menu [→ Main menu →Configuration →Wizard].
The different selection pages of the Configuration Wizard are operated according to the screens described in "3.3 Operating
concept"[48]. Confirming a selection with "OK" or the confirm icon
leads directly to the next selection page. The modified parameter is applied directly.

5.2 Menu navigation in the Configuration Wizard

→Language
1 Select the desired language.
2 Confirm the selection with the Confirm icon.
→Standard configuration
If no optional RoCon system components are connected:
1 Briefly press the rotary button to confirm ("Yes").
When optional RoCon system components such as RoCon U1 (EHS157034) and/or RoConM1 (EHS157068) are connected:
1 Turn the rotary button clockwise until "No" is displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
3 Select and set the following list elements as required:
▪ Direct circuit configuration (see "4.8Terminal"[422])
▪ Bus ID heat generator (see "4.8Terminal"[422])
▪ Time master (see "7.11Configuration Wizard"[446])
4 If all settings have been made as required, confirm by clicking
on the Confirm icon.
→Time
1 Setting the current time (see "3.3.5Setting the times"[49]).
→Date
1 Setting the current date (see "3.3.6Calendar function"[49]).
→System parameters
The following parameters can be set:
▪ [Room thermostat] present? (see "7.5.4 Menu: Inputs/
Outputs"[433])
▪ [Heating support (HZU)] required? (see "7.5.5Menu: Intelligent
Storage Mgmt"[436])
▪ [Continuous heating] required? (see "7.5.5 Menu: Intelligent
Storage Mgmt"[436])
→Heating limit
The following parameters can be set:
▪ [Heat limit, heating mode] (see "7.5.3 Menu: External heat
source"[433])
▪ [Heat limit, reducing mode] (see "7.5.3 Menu: External heat
source"[433])
→Weather-compensated
Weather-compensated control is required:
1 Confirm the "Weather-compensated" selection with the Confirm
icon.
The following parameters can be set:
▪ [Room temperature target 1] setting (see "7.5.1Menu: Display
settings"[431])
▪ [Heating curve] setting (see "4.5.4Heating"[417])
▪ Only with reversible device type: Setting of the cooling curve
(see "4.5.5Cooling"[418])
Weather-compensated control is not required:
1 Select the "Feed temperature, fixed" setting.
2 Confirm the selection with the Confirm icon.
The following parameters can be set:
▪ [Feed temperature, heating mode] setting (see "7.6.3 Menu:
Heating"[438])
▪ Only with reversible device type: Setting [Feed temperature,
cooling mode] (see "7.6.4Menu: Cooling"[440])
→Hot water
The following parameters can be set:
▪ [Hot water temperature target 1] (see "7.3.4 Menu: Hot water
temperature, target"[429])
▪ [Hot water hysteresis] (see "7.6.5Menu: Hot water"[441])
→Device selection
The following parameters can be set:
▪ [Outdoor unit]
▪ [Indoor unit]
→External heat generator
No external heat generator available:
1 Select the "No external heat generator" setting.
2 Confirm the selection with the Confirm icon.
Optional backup heater available:
1 Confirm the "Backup heater BUH" selection with the Confirm
icon.
2 Select and set the following list elements as required:
▪ [External power hot water] (see "7.5.3 Menu: External heat
source"[433])
▪ [External power stage 1] (see "7.5.3 Menu: External heat
source"[433])
▪ [External power stage 2] (see "7.5.3 Menu: External heat
source"[433])
▪ Emergency (see "8.1Emergency operation"[447])
3 If all settings have been made as required, confirm by clicking
on the Confirm icon.
Alternative external heat generator available:
1 Select the "DHW + heating support" or "Two external heat
generators" setting (see "7.5.3 Menu: External heat
source"[433]).
2 Confirm the selection with the Confirm icon.
Operating instructions
24
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 25

6 Parameter overview

Standby
Reduce
Heating
Automatic 2
Automatic 1
Summer
Cooling
Room temperature target 1
Room temperature target 2
Room temperature target 3
Hot water temperature target 1
Hot water temperature target 2
Hot water temperature target 3
Room
Reduce
Absent
Hot water
1x load
Reduce room temperature
Room temperature absent
1 x hot water
Party
Absent
Holiday
Public holiday
HC auto 1
Heating circuit auto. 1
HC auto 2
Heating circuit auto. 2
TP reset
Time program reset
DHW auto 1
Hot water auto. 1
DHW auto 2
Hot water auto. 2
Circulation
Circulation program
Sound program
3 Select and set the following list elements as required:
▪ [External power hot water] (see "7.5.3 Menu: External heat
source"[433])
▪ [External power stage 1] (see "7.5.3 Menu: External heat
source"[433])
▪ [Emergency] (see "8.1Emergency operation"[447])
4 If all settings have been made as required, confirm by clicking
on the Confirm icon.
→Heating system
1 The [Heating system] parameter can be set (see "7.5.2Menu:
System"[432]).
6 Parameter overview
Parameters that are only available for certain device types are marked as follows:
(a) ETS only…
(b) EHS only…
(c) EHS only…D3

6.1 Menu: Operating mode

 6‒1 Parameter in menu: "Operating mode"

6.2 Menu: User

 6‒2 Parameter in menu: "User"

6.3 Menu: Time program

 6‒3 Parameter in menu: "Time program"
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
25
Page 26
6 Parameter overview
Display
System
Ext. source
Inputs/Outputs
ISM
Glycol
Language
Time
Date
LCD brightness
LCD illumination duration
Outdoor unit
Indoor unit
Heating system
Pump dT heating
Pump dT cooling
Config. ext. heat source
External power hot water
External power stage 1
External power stage 2
Bivalence function
Bivalence temperature
Smart grid
Smart grid mode
HT/NT function
HT/NT contact
Room thermostat
Interlink function
Programmable output (230V)
Func. burner blocking contact
AUX switching function
AUX wait time
Switching threshold TDHW (AUX)
Continuous heating
Heating support (HZU)
Heating support power
Heating support hysteresis
Heating support max. temp.
Min. pump power
Max. pump power
HP Power limitation
Pump limit
(a)
(a)
Hot water sensor
Water pressure sensor
Heat limit, reducing mode
Heating curve
Feed temperature, heating mode
Feed temperature, reducing mode
Min. feed temperature
Room sensor adaptation
Feed temperature lower limit
Cooling setpoint correction
Interlink temperature reduction
Max. hot water loading time
Hot water blocking time
Outside temperature correction
Water pressure, min.
Water pressure, max.
Water pressure, target
Maximum pressure loss
Weather-compensated
Frost protection temperature
Building insulation
Heat limit, heating mode
Max. feed temperature
Room influence
Heating curve adaptation
Interlink temperature increase
Feed temperature, cooling mode
Circulation pump control
Circulation pump interval
Anti-legionella day
Anti-legionella start time
Anti-legionella temperature
Addition
Sensors
Access
DHW
HC config
Heating
Cooling curve
Cooling
Parameters
Wizard
Reset
Feed temperature, overshoot
Comfort heating
Outside temperature sensor
Switch temp. heating circuit
Hot water hysteresis
Wait time ext. heat generator
Target flow cooling, start
Start cooling outside temp.
Max. cooling outside temp.
Target flow cooling, max.
Relay test
Ventilation
Ventilation function
Screed
Screed drying
Program
Screed program
Parameter reset
Solar function
DHW Mode
Par.Download
Par.Upload
Pump down
(b)
(c)

6.4 Menu: Settings

6.5 Menu: Configuration

 6‒4 Parameter in menu: "Settings"
Operating instructions
26
 6‒5 Parameter in menu: "Configuration"
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 27
6 Parameter overview
Hot water temperature, current
Hot water temperature, target
Return flow temperature
Feed temperature HC target
Feed temperature BUH
Outdoor temperature (optional)
Refrigerant temperature
Volume flow
Feed temperature, current
Feed temperature, target
Feed temperature PHX
Average outside temperature
Feed temperature HC current
Current
Overview
Values
Pressure
Mode
External request
Room thermostat/Interlink
Quiet mode
Status heat circulation pump
PWM pump
BUH current output
3UVB1 position
3UVDHW position
Heat generator type
Software no. B1/U1
Software no. controller
Glycol
Water pressure
Heating support
Water pressure
(a)
Emergency
Manual operation
Protocol
Screen
Manual operation status
Temperature, manual operation
Error screen
Mixer #X
Address
Bus scan
Controller BM1/BE1 #X
Terminal address
Month
Total
Energy HP, cooling
Energy HP, heating
Energy, hot water
Energy HP total
Electr. energy total
Reset
Ext. energy source, hot water
Ext. energy source, heating
Energy HP, cooling
Energy HP, heating
Energy, hot water
Energy HP total
Electr. energy total
Runtime, compressor
Runtime, pump

6.6 Menu: Information

INFORMATION
If the local control panel is used as a remote controller for a mixer module, both the standard screen and the menu structure are changed (see "9Mixer module"[448]).

6.9 Menu: Statistics

 6‒6 Parameter in menu: "Information"

6.7 Menu: Error

 6‒7 Parameter in menu: "Error"
 6‒9 Parameter in menu: "Statistics"

6.8 Menu: Terminal

 6‒8 Parameter in menu: "Terminal"
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
27
Page 28

7 Parameter settings

7 Parameter settings

7.1 Explanation of the parameter tables

The parameter tables listed in "7.2 Operating mode" [4 28] to
"7.10 Statistics" [4 46] contain compact information on all
parameters that are available in the respective menus and submenus of the controller (1st menu level, 2nd menu level).
In addition to the parameter designations, the tables contain information on setting ranges, factory settings, setting options or adjustment steps and brief explanations of the function.
In addition, they provide an explanation of the access rights for operation of the controller. The following abbreviations are used for corresponding labelling:

7.2 Operating mode

[→Main menu →Operating mode]
BE Access right for the operator
HF Access authorisation with technician code
If different entries are made in the BE and HF columns, the technician must be logged in before selecting the parameter level in order to obtain the status entered in the HF column (see "4.5.1Access rights (technician code)"[416])
Status:
N Not visible
E Visible and configurable
S Visible
INFORMATION
Changing some parameters requires a restart of the device. This takes a few minutes. No further settings can be made during this time. The restart can be delayed by 5 minutes in response to the prompt "Restart required. Perform now?" by selecting "later".
Parameters that require a restart are marked with (*) in the following tables
 7‒1 Parameter in the "Operating mode" menu
Parameters Setting range
Min/Max
Standby In this operating mode all internal functions are switched off. Freeze-up
protection remains active and a blocking protection for the pump is guaranteed.
All controllers integrated in the RoCon system via the CAN bus are primarily also switched to the operating mode if this setting is selected.
Outputs are not always completely free of voltage.
Reduce The internal HC continuously regulates to the required reduced leaving
water temperature according to the [Heating curve] or [Feed temperature, reducing mode] parameters or to the room temperature [Reduce room temperature] if the room thermostat is connected. Domestic hot water preparation is carried out according to [Hot water auto. 1].
Heating The internal HC continuously regulates to the required leaving water
temperature according to the [Heating curve] or [Feed temperature, heating mode] parameters or to the room temperature [Room temperature target 1] if the room thermostat is connected. Domestic hot water preparation is carried out according to [Hot water auto. 1].
Summer The internal HC is switched off. Freeze-up protection remains active and a
blocking protection for the pump is guaranteed. Domestic hot water preparation is carried out according to [Hot water auto. 1].
All controllers integrated in the RoCon system via the CAN bus are primarily also switched to the operating mode if this setting is selected.
Automatic 1 The internal HCs are controlled according to the set [Heating circuit auto.
1] time program with the respective room target temperatures. Domestic hot water preparation is carried out according to [Hot water auto. 1].
Automatic 2 The internal HCs are controlled according to the set [Heating circuit auto.
2] time program with the respective room target temperatures. Domestic hot water preparation is carried out according to [Hot water auto. 2].
Cooling The internal HC continuously regulates to the required leaving water
temperature according to the parameters in the menu [→Main menu →Configuration →Cooling] or to the [Room temperature target 1] room temperature if the room thermostat is connected. Domestic hot water preparation is carried out according to [Hot water auto. 1]. Freeze-up protection remains active and a blocking protection for the pump is guaranteed.
Description Factory
setting
Incre-
ment
BE HF
- E E
- E E
- E E
- E E
- E E
- E E
- E E
Access
Operating instructions
28
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 29

7.3 User

[→Main menu →User]

7.3.1 Menu: Room temperature target

[→Main menu →User →Room]
 7‒2 Parameter in the "Room temperature target" menu
Parameters Setting range
Min/Max
Room temperature target 1
Room temperature target 2
Room temperature target 3

7.3.2 Menu: Reduce room temperature

[→Main menu →User →Reduce]
 7‒3 Parameter in the "Reduce room temperature" menu
Parameters Setting range
Reduce room temperature
5 – 40°C Setpoint of the room temperature in °C, which is valid for the 1st switching
time cycle of the [Automatic 1] and [Automatic 2] time programs.
5 – 40°C Setpoint of the room temperature in °C, which is valid for the 2nd switching
time cycle of the [Automatic 1] and [Automatic 2] time programs.
5 – 40°C Setpoint of the room temperature in °C, which is valid for the 3rd switching
time cycle of the [Automatic 1] and [Automatic 2] time programs.
Min/Max
5 – 40°C Setpoint of the reduced room temperature in °C, which is valid for the
[Automatic 1] and [Automatic 2] time programs.
7 Parameter settings
Description Factory
setting
20°C 0.5°C E E
20°C 0.5°C E E
20°C 0.5°C E E
Description Factory
setting
15°C 0.5°C E E
Incre-
ment
Incre-
ment
Access
BE HF
Access
BE HF

7.3.3 Menu: Room temperature absent

[→Main menu →User →Absent]
 7‒4 Parameter in the "Room temperature absent" menu
Parameters Setting range
Min/Max
Room temperature absent
5 – 40°C Setpoint of the reduced room temperature in °C, which is valid for the
[Absent] and [Holiday] time programs.

7.3.4 Menu: Hot water temperature, target

[→Main menu →User →Hot water]
 7‒5 Parameter in the "Hot water temperature, target" menu
Parameters Setting range
Min/Max
Hot water temperature target 1
Hot water temperature target 2
Hot water temperature target 3
35 – 70°C Setpoint of the hot water temperature in °C, which is valid for the 1st
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Outside of the switching cycles, control is performed at the lowest temperature of the setting range.
35 – 70°C Setpoint of the hot water temperature in °C, which is valid for the 2nd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
35 – 70°C Setpoint of the hot water temperature in °C, which is valid for the 3rd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Description Factory
setting
15°C 0.5°C E E
Description Factory
setting
48°C 0.5°C E E
48°C 0.5°C E E
48°C 0.5°C E E
Incre-
ment
Incre-
ment
Access
BE HF
Access
BE HF
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
29
Page 30
7 Parameter settings

7.3.5 Menu: 1x Hot water

[→Main menu →User →1x load]
 7‒6 Parameter in the "1 x hot water" menu
Parameters Setting range
Min/Max
1 x hot water Off Start of one-time domestic hot water preparation to the set setpoint [Hot
On
water temperature target 1] without time limit, independent of the heating programs.
Description Factory

7.4 Time program

[→Main menu →Time program]
 7‒7 Parameter in the "Time program" menu
Parameters Setting range
Min/Max
Party 0 – 360min This operating mode can be used to set a unique time for temporarily
extending the heating time of the internal HC.
Absent 0 – 360min This operating mode can be used to set a one-off time for temporary
control to the parametrised absence temperature.
Holiday Date 1st day
-
Date last day
Public holiday Date 1st day
-
Date last day
Heating circuit auto. 1
Heating circuit auto. 2
Hot water auto. 1
Hot water auto. 2
Circulation program
See "4.3Time
program"[413]
See "4.3Time
program"[413]
See "4.3Time
program"[413]
See "4.3Time
program"[413]
See "4.3Time
program"[413]
The internal HC provides continuous (24h per day) regulation to the parametrised absence temperature ([Reduce room temperature] parameter).
A calendar function can be used to enter a time period of absence.
A calendar function can be used to enter a time period of presence.
During this period of time, regulation is carried out exclusively according to the settings for "Sunday" in the [Heating circuit auto. 1] and [Hot water auto. 1] time programs.
In this menu, the 1st time program can be parametrised for the internal HC. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
In this menu, the 2nd time program for the internal HC can be parametrised. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
This menu can be used to parametrise the 1st time program for domestic hot water preparation. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
This menu can be used to parametrise the 2nd time program for domestic hot water preparation. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
This menu can be used to parametrise a timer program for the circulation pump. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
Description Factory
Incre-
setting
setting
0min 15min E E
0min 15min E E
- 1 day E E
- 1 day E E
See "  4‒3
Factory set-
ting of the
permanent
time pro-
grams"[414]
See "  4‒3
Factory set-
ting of the
permanent
time pro-
grams"[414]
See "  4‒3
Factory set-
ting of the
permanent
time pro-
grams"[414]
See "  4‒3
Factory set-
ting of the
permanent
time pro-
grams"[414]
See "  4‒3
Factory set-
ting of the
permanent
time pro-
grams"[414]
ment
- E E
Incre-
ment
15min E E
15min E E
15min E E
15min E E
15min E E
Access
BE HF
Access
BE HF
Operating instructions
30
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 31
7 Parameter settings
Parameters Setting range
Min/Max
Sound program
Time program reset
See "4.3Time
program"[413]
0 – 3
Party This menu can be used to reset the time programs to factory settings. To
Absent
Holiday
Public holiday
Heating circuit
auto. 1
Heating circuit
auto. 2
Hot water auto.
1
Hot water auto.
2
Circulation
program
Sound program
Description Factory
In this menu, a time program can be parametrised for various stages of the heat pump quiet mode. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
A noise level can be assigned to each switching cycle:
0: no noise reduction,
1: low noise reduction,
2: medium noise reduction,
3: maximum noise reduction.
do this, select the respective time programs and then confirm the selection with the Confirm icon.
Incre-
setting
0 15min N E
- - E E
ment
Access
BE HF

7.5 Settings

[→Main menu →Settings]

7.5.1 Menu: Display settings

[→Main menu →Settings →Display]
 7‒8 Parameter in the "Display settings" menu
Parameters Setting range
Min/Max
Language Deutsch National language of the display texts on the control panel - E E
English
Français
Nederlands
Español
Italiano
Português
Lietuvos
Time Time in hours/minutes format. E E
Date Current date in day/month/year format. The current day of the week is
calculated automatically from the date.
LCD brightness
LCD illumination duration
10 – 100% Brightness of the display 80% 10% E E
1 – 60s Lighting duration of the display 30s 1s E E
Description Factory
setting
Incre-
ment
Access
BE HF
E E
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
31
Page 32
7 Parameter settings

7.5.2 Menu: System

[→Main menu →Settings →System]
 7‒9 Parameter in the "System" menu
Parameters Setting range
Min/Max
Outdoor unit No selection - - N E
4kW For outdoor units of the type ERGA... series and indoor units EHS...
6kW
8kW
11kW
14kW
16kW
EPRA14 For outdoor units of the type EPRA... series and indoor units ETS...
EPRA16
EPRA18
Indoor unit No selection Heat pump interior unit type
EHSX/H(B)
04/08P30D
EHSX/H(B)
04/08P50D
EHSX/H(B)
08P50D
EHSX/H(B)
16P50D
ETSH/X(B)
16P30D
ETSH/X(B)
16P50D
Heating system (*)
Pump dT heating (*)
Pump dT cooling (*)
Glycol (*) No glycol added For ETS… indoor units only
HP Power limitation
Pump limit This parameter defines the maximum pump speed. Under normal
Floor heating Heat exchanger type in the heating system
Convector
Radiator
3 – 10 Required temperature difference between return and leaving water
3 – 10 Required temperature difference between return and leaving water
Glycol added
20 – 50A For ETS… indoor units only
0 No limit
1 – 4 Limitation of pump speed independent of the operating status. This setting
5 – 8 Limitation of the pump speed if there is no heating or cooling requirement.
Adaptation of the set value important, as the device types have different defrosting logics.
If "Radiator" is selected and high leaving water temperatures are desired, it may make sense to increase the [Max. feed temperature] parameter to 65°C ([→Main menu →Configuration →Heating]).
temperature. If a minimum temperature difference is required for proper operation of the heat emitters in heating operation.
temperature. If a minimum temperature difference is required for proper operation of the heat emitters in cooling operation.
Adding glycol to the water circuit is recommended to guarantee freeze-up protection in the event of a power failure. If glycol has been added to the system, the RoCon+HP1 controller setting must be adapted accordingly.
The permanent power limitation is useful to ensure maximum power consumption of the system. In some countries, legislation limits the maximum power consumption for room heating and domestic hot water preparation.
conditions, the default setting should NOT be changed. The limitation of the pump speed is skipped if the flow rate is in the range of the minimum flow rate. The water flow resulting at limited pump speed can be taken from the pump characteristic curve (see installation instructions for the indoor unit)
cannot guarantee heating comfort. The maximum pump speed depends on the setting as follows: 1:90%, 2:75%, 3:65%,4:55%
The maximum pump speed depends on the setting as follows: 5:90%, 6:75%, 7:65%, 8:55%
Description Factory
setting
- - N E
5 1 N E
5 1 N E
50A N E
6 1 N E
Incre-
ment
BE HF
- N E
- N E
Access
Operating instructions
32
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 33

7.5.3 Menu: External heat source

[→Main menu →Settings →Ext. source]
 7‒10 Parameter in the "External heat source" menu
Parameters Setting range
Min/Max
Config. ext. heat source
External power hot water
External power stage 1 (*)
External power stage 2 (*)
Bivalence function (*)
Bivalence temperature
No external heat
generator
Backup heater
BUH
DHW + heating
support
Two external
heat generators
1 – 40kW Heat output of the electric heater booster for domestic hot water
1 – 40kW Heat output of the electric heater booster for heating support stage 1
1 – 40kW Heat output of the electric heater booster for heating support stage 2
Aux. heating
always possible
Aux. heating T-
biv. dependent
-15°C – +35°C Setting influences the effect of the potential-free AUX switching contact
Setting of whether there is an additional external heat generator for domestic hot water preparation (DHW) and/or heating support (HZU) (see
"4.4.3External heat sources"[414]).
The heat pump is the only heat source
Optional heating rod (3N~) installed in the storage tank
An alternative heat generator (e.g. backup heater 1N~) provides domestic hot water preparation and backup heating
Two external heat generators: Alternative WEZ 1 (e.g. backup heater 1N~) takes over domestic hot water preparation and alternative WEZ 2 takes over heating support
preparation
See operating instructions for heating element EKBUxx.
See operating instructions for heating element EKBUxx.
The bivalence function is only relevant to operation of the optional heater booster due to a backup request (room heating operation).
Operation of the backup heater is always possible.
Backup heater is only released if the temperature set in the [Bivalence temperature] parameter is undercut.
(toggle switch output A) defined in the [AUX switching function] parameter.
Only if [Bivalence function] parameter = "Aux. heating T-biv. dependent":
Outside temperature as of which the optional heater booster is activated to support room heating. The bivalence temperature is relevant to operation of the optional heater booster due to a backup request (room heating operation). The temperature of the temperature sensor integrated in the heat pump outdoor unit (info value "Average outside temperature") is used for this.
7 Parameter settings
Description Factory
setting
3kW 1kW N E
3kW 1kW N E
3kW 1kW N E
0°C 1°C N E
Incre-
ment
- N E
- N E
Access
BE HF

7.5.4 Menu: Inputs/Outputs

[→Main menu →Settings →Inputs/Outputs]
 7‒11 Parameter in the "Inputs/Outputs" menu
Parameters Setting range
Min/Max
Smart grid Evaluation of the SG signal (see "4.4.4Inputs/Outputs"[415]). - N E
Off Smart Grid function not active, SG signal is not evaluated.
On Depending on the utility company signal, the heat pump is shut off (no
freeze-up protection function) or operated at higher temperatures.
Smart grid mode
Comfort Increase of the hot water target temperature by 5K
Standard Increase of the target leaving water temperature by 2K and increase of the
Eco Increase of the target leaving water temperature by 5K and increase of the
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Only if [Smart grid] parameter = "On":
Is used for a possible target temperature increase with a Smart Grid switch-on command.
hot water target temperature by 5K
hot water target temperature by 7K
Description Factory
setting
Incre-
ment
Operating instructions
Access
BE HF
- N E
33
Page 34
7 Parameter settings
Parameters Setting range
Min/Max
HT/NT function
Inactive Deactivated (no effect)
Switch off
compressor
Switch off
compressor +
BUH
Switch all off Everything is switched off (no freeze-up protection function, see "4.5.3HC
HT/NT contact Definition of whether the HT/NT input is evaluated as a normally closed
Normally open
contact
Normally closed
contact
Room thermostat
No Deactivated
Yes 1 Open contacts: Only freeze-up protection active.
Setting of which heat sources are switched off if the high rate signal output by the utility company (EVU) is received in the case of a low rate mains connection.
Refrigerant compressor is switched off
Refrigerant compressor and backup heater are switched off
config."[416])
contact or a normally open contact.
Switching contact closed during high rate.
Switching contact closed during low rate.
Configuration of a room thermostat with floating contacts connected to connection J16 of the indoor unit.
2 If [Interlink function] parameter = "On": see description [Interlink
function]
3 If [Interlink function] parameter = "Off": Evaluation of the heating and
cooling switching contacts at connector J16 on the RoConBM2C PCB (only if none of the "Standby", "Reduce", "Summer", "Holiday", "Public holiday" or "Screed" operating modes are active):
▪ Closed heating switching contact: Operating mode is switched to
"Heating". Priority if both switching contacts are closed.
▪ Closed cooling switching contact: Operating mode is switched to
"Cooling".
Description Factory
setting
Incre-
ment
BE HF
- N E
- N E
- N E
Access
Operating instructions
34
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 35
7 Parameter settings
Parameters Setting range
Min/Max
Interlink function
Off Deactivated
On
Programmable output (230V)
Func. burner blocking contact
Inactive The output has no function.
Heating circuit
request
Circulation
request
Direct heating circuit request
Resistance
values
Burner blocking
contact
Description Factory
setting
Configuration for systems that are operated with 2 different target leaving water temperatures (see "4.4.4Inputs/Outputs"[415]).
One possible application is, for example, the additional integration of an HP convector in a surface heating and cooling system.
Prerequisite: 2 room thermostats are connected to plug connection J16 of the indoor unit.
Evaluation of the heating and cooling switching contacts at plug connection J16 on the RoConBM2C PCB.
Activation of cooling operation only by switching the operating mode to "Cooling" (see "4.1Operating mode"[411]).
[Room thermostat] parameter must be set to "Yes". (If [Room thermostat] parameter = "No" is set, the heating circulation pump runs in continuous operation!)
1 Open switching contacts: Only freeze-up protection active
2 "Heating" and "Automatic 1"/"Automatic 2" operating modes active
during the switching cycles in day mode:
▪ Closed heating switching contact = IL1: It is controlled to the normal
target leaving water temperature according to the parameter settings in [→Main menu →Configuration →Heating].
▪ Closed cooling switching contact = IL2: It is controlled to the increased
target leaving water temperature (normal target leaving water temperature + value of the [Interlink temperature increase] parameter. Priority if both switching contacts are closed!
3 "Cooling" operating mode active.
▪ Closed heating switching contact = IL1: It is controlled to the normal
target leaving water temperature according to the parameter settings in [→Main menu →Configuration →Cooling].
▪ Closed cooling switching contact = IL2: It is controlled to the reduced
target leaving water temperature (normal target leaving water temperature – value of the [Interlink temperature reduction] parameter). Priority if both switching contacts are closed!
Configuration of the multi-function output (230V, J14 connection): - N E
Header pump – The output becomes active as soon as any HC (e.g. mixer circuit) of the system reports a heat request to the heat generator.
Circulation pump – The output is activated either after the time program of the circulation pump or after the time program of the domestic hot water preparation, depending on the parametrisation (see "4.3Time
program"[413]).
Feeder pump – The output becomes active as soon as a heat requirement is pending for the direct HC of the heat generator.
Selection of the functionality of the EXT switching contact (J8) (see
"4.1Operating mode"[411])
Incre-
ment
BE HF
- N E
- N E
Access
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
35
Page 36
7 Parameter settings
Parameters Setting range
Min/Max
AUX switching function
Inactive Function deactivated.
Switching
threshold TDHW
(AUX)
Heating/cooling
request
BUH request If a hot water request to the backup heater (EKBUxx) is present or the
Error If an error is pending
TVBH >60°C If the sensor value (TVBH) is >60°C.
Outside
temperature
Outside temp. +
DHW/heating
DHW request If a hot water request is present.
Outside
temperature +
heating
Multi-oil If the outside temperature is <[Bivalence temperature] parameter value +
Cooling mode If the heat pump is in the "Cooling" operating mode.
AUX wait time 0 – 600s AUX switching contact(A) only switches after a delay if the switching
Switching threshold TDHW (AUX)
20 – 85°C Storage tank temperature (Tdhw) switching threshold for AUX switching
Setting assigns the switching conditions for the potential-free AUX switching contact (toggle switch output A, see "4.4.4Inputs/
Outputs"[415]).
AUX switching contact switches:
If storage tank temperature (Tdhw) ≥ value of [Switching threshold TDHW (AUX)] parameter.
If a cooling request or heating request is present.
configured backup heater is requested for heating support.
If the outside temperature is <[Bivalence temperature] parameter value. (heat pump continues to operate = parallel equilibrium mode)
If the outside temperature is <[Bivalence temperature] parameter value + a heating request or a hot water request is present. (heat pump does not continue to operate = alternative equilibrium mode)
If the outside temperature is <[Bivalence temperature] parameter value + "room heating" heat request (not for hot water request). Heat pump no longer operates in room heating operation below the value set in the [Bivalence temperature] parameter – only in hot water mode.
Application: Alternative room heating bi-valence mode if the boiler is hydraulically integrated so that it directly heats the unpressurised storage tank water of the indoor unit (connection via solar connections).
"room heating" heat request (not for hot water request). Heat pump no longer operates in room heating operation below the value set in the [Bivalence temperature] parameter – only in hot water mode.
Application: Alternative room heating equilibrium mode if the boiler is hydraulically integrated in the heat pump feed. For this application type, the freeze-up protection function must be deactivated on the indoor unit ([Frost protection temperature] parameter = "Off").
condition (see [AUX switching function] parameter) is present for longer than the set time.
contact (see [AUX switching function] parameter).
Description Factory
Incre-
setting
120s 5s N E
50°C 1°C N E
ment
Access
BE HF
- N E

7.5.5 Menu: Intelligent Storage Mgmt

[→Main menu →Settings →ISM]
 7‒12 Parameter in the "Intelligent Storage Mgmt" menu
Parameters Setting range
Min/Max
Continuous heating
Off No uninterrupted heating
On Uninterrupted heating. When the evaporator is being defrosted, heat for
Operating instructions
This function enables uninterrupted heating, even when the evaporator is being defrosted. This enables high comfort to be guaranteed, even with rapidly reacting heating systems (e.g. convectors).
heating is taken from the storage tank.
36
Description Factory
setting
Incre-
ment
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Access
BE HF
- N E
Daikin RoCon+ HP1
Page 37
7 Parameter settings
Parameters Setting range
Min/Max
Heating support (HZU)
Off No heating support
On Heating support function active
Heating support power
Heating support hysteresis
Heating support max. temp.
Min. pump power
Max. pump power
3 – 40kW The setting limits the heating support output. 15kW 1kW N E
2 – 15 Only if [Heating support (HZU)] parameter = "On":
5 – 85°C The setting limits the target leaving water temperature (measured against
40 – 80% Lower limit for pump operation. Only used when heating support is active
60 – 80% Upper limit for pump operation. Only used when heating support is active
Description Factory
Heating support from hot water storage tank if minimum temperature is exceeded (see "4.4Settings"[414] and [Heating support hysteresis] parameter).
Heating support is activated if
Tdhw>THZUmin+4K and Tdhw>[Feed temperature, target]+1K.
Heating support is deactivated if
Tdhw<THZUmin or Tdhw<[Feed temperature, target].
THZUmin = currently active hot water target temperature [Hot water temperature, target] (see "7.3.4Menu: Hot water temperature,
target"[429]) + set [Heating support hysteresis] parameter value.
Tdhw = current hot water storage tank temperature
[Feed temperature, target] = currently active target leaving water temperature (see "4.5Configuration"[416])
t
) when the heating support function is active.
V, BH
or heat is generated by an external heat source. During normal operation, the pump is controlled according to the [Pump limit] parameter, see
"7.5.2Menu: System"[432].
or heat is generated by an external heat source. During normal operation, the pump is controlled according to the [Pump limit] parameter, see
"7.5.2Menu: System"[432].
Incre-
setting
5 1 N E
60°C 1°C N E
50% 1% N E
80% 1% N E
ment
Access
BE HF
- N E

7.6 Configuration

[→Main menu →Configuration]

7.6.1 Menu: Sensors

[→Main menu →Configuration →Sensors]
 7‒13 Parameter in the "Sensors" menu
Parameters Setting range
Min/Max
Outside temperature sensor (*)
Hot water sensor
Water pressure sensor
Outside temperature correction
Integrated
sensor
Optional sensor
Inactive No function for domestic hot water preparation.
Sensor Function for domestic hot water preparation is activated. A storage
Thermostat Function for domestic hot water preparation is activated. A thermostatic
Off No sensor evaluation
On Sensor evaluation activated (if no pressure sensor is connected, an error
-5.0 – +5.0K Individual adjustment for the measured value of the outside temperature
Selection of whether the sensor integrated in the outdoor unit or an optional outdoor temperature sensor is used to determine the target leaving water temperatures
Configuration of the domestic hot water preparation: - N E
temperature sensor is evaluated for domestic hot water preparation (if no storage temperature sensor is connected, an error message is generated).
switch (ON/OFF) is evaluated for domestic hot water preparation where an "open terminal" is evaluated as "not required".
Configuration of the sensor for detecting the water pressure of the system. - N E
message is generated.)
relevant for the controller.
Description Factory
setting
0.0K 0.1K N E
Incre-
ment
- N E
Access
BE HF
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
37
Page 38
7 Parameter settings
Parameters Setting range
Min/Max
Water pressure, min.
Water pressure, max.
Water pressure, target
Maximum pressure loss
0.1 – 5.0bar Defines the minimum water pressure.
Pressure monitoring function (only with activated pressure sensor [Water pressure sensor] = "On"): If the measured value falls below the set value, an error message is generated.
0.1 – 5.0bar Defines the maximum water pressure.
Pressure monitoring function (only with activated pressure sensor, [Water pressure sensor] = "On"): If the measured value exceeds the set value, a warning message is generated.
0.1 – 5.0bar Defines the target water pressure.
Pressure monitoring function (only with activated pressure sensor, [Water pressure sensor] = "On"): If the measured value falls below the set value by more than the value set in the [Maximum pressure loss] parameter, a warning message is generated.
0.1 – 5.0bar Defines the maximum acceptable pressure loss in the heating system.
Pressure monitoring function (only with activated pressure sensor, [Water pressure sensor] = "On"): If the measured value falls below the set value by more than the value set in the [Water pressure, target] parameter, a warning message is generated.

7.6.2 Menu: Heating circuit config.

[→Main menu →Configuration →HC config]
 7‒14 Parameter in the "Heating circuit config." menu
Parameters Setting range
Min/Max
Weather­compensated
Frost protection temperature
Building insulation
Switch temp. heating circuit
Feed temperat-
ure, fixed
Weather-com-
pensated
Off No freeze-up protection of the HC 0°C 1°C E E
-15 – 5°C If the outside temperature drops below the set value, the system switches
Off Setting the building insulation standard. This influences the averaged
low
Normal
Good
Very good
Off Deactivated
10 – 40°C If the outside temperature exceeds the set value, the system is switched to
Selection of the method for determining the target leaving water temperature.
Control to a fixed target leaving water temperature (depending on operating mode)
Weather-compensated control based on the heating curve.
to freeze-up protection operation (the pumps are switched on). The function is ended if the outside temperature rises above the set value +1K.
outside temperature and the automatic adaptations of the heating curve and the heating times.
Automatic activation of cooling operation. Off 1°C N E
the "Cooling" operating mode. If the outside temperature falls 2K below the set value, the system automatically switches back to the previously activated operating mode
Description Factory
setting
0.5bar 0.1bar N E
3.0bar 0.1bar N E
0.9bar 0.1bar N E
0.5bar 0.1bar N E
Description Factory
setting
Incre-
ment
Incre-
ment
BE HF
BE HF
- N E
- E E
Access
Access

7.6.3 Menu: Heating

[→Main menu →Configuration →Heating]
 7‒15 Parameter in the "Heating" menu
Parameters Setting range
Min/Max
Heat limit, heating mode
Operating instructions
Off Setting of the automatic summer switch-off of the heating operation. If the
10 – 40°C
outside temperature measured and averaged by the controller exceeds the set value by 1K, the HC is switched off. The heating is released again if the outside temperature undercuts the set heating limit.
38
Description Factory
setting
19°C 1K E E
Incre-
ment
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Access
BE HF
Daikin RoCon+ HP1
Page 39
7 Parameter settings
Parameters Setting range
Min/Max
Heat limit, reducing mode
Heating curve 0.0 – 3.0 Only if [Weather-compensated] parameter = "Weather-compensated":
Feed temperature, overshoot (*)
Feed temperature, heating mode
Feed temperature, reducing mode
Max. feed temperature
Min. feed temperature
Room influence
Room sensor adaptation
Off Setting the heating limit for the "switch-off" of the HC during the setback
10 – 40°C
0 – 4 This function defines how far the water temperature may exceed the target
20 – 90°C Only if [Weather-compensated] parameter = "Feed temperature, fixed":
10 – 90°C Only if [Weather-compensated] parameter = "Feed temperature, fixed":
20 – 90°C The setting limits the leaving water temperature (measured on t
10 – 90°C The determined HC target leaving water temperature is limited to the
Off Purely weather-compensated leaving water temperature control
0K Purely weather-compensated leaving water temperature control, but
1 – 20K Causes a correction of the target leaving water temperature (parallel shift
-5 – +5K Only when a room station is connected and assigned to the HC:
time (functioning as in [Heat limit, heating mode] parameter).
Setting of the heating curve. The heating curve reflects the dependency of the HC's target leaving water temperature on the outside temperature (see
"4.5Configuration"[416]).
leaving water temperature before the compressor is stopped. The compressor resumes operation when the leaving water temperature falls below the target leaving water temperature. This function ONLY applies to heating operation.
Setting of the target leaving water temperature for the HC during the heating time in operating mode: "Automatic 1", "Automatic 2", "Heating".
Setting of the target leaving water temperature for the HC during the reduction time in operating mode: "Automatic 1", "Automatic 2", "Heating".
the heating support function is active.
The determined HC target leaving water temperature is limited to the maximum value set here.
If an optionally connected mixed HC requests a higher temperature of the heat generator, this is taken into account. This means the internal circulation pump of the heat generator always runs if the generator is switched on. If the direct HC supplies the underfloor heating, a mechanical temperature limiter must be installed to prevent any overheating of the screed.
minimum value set here.
Only when a room station is connected and assigned to the HC:
The setting of what influence the deviation of the room temperature measured by the RoConU1 (EHS157034) room station from the current setpoint (see "4.2User"[412]) has on the leaving water temperature.
internal circulation pump continues running until the next heating cycle after a heat requirement during the setback cycle.
of the heating curve) by the set factor. If the measured temperature lies 2K below the setpoint, the target leaving water temperature is increased by 2x the set value.
Individual adjustment of the room temperature relevant to the controller.
If a systematic deviation of the room temperature measured by the RoConU1 (EHS157034) room station to the actual temperature in the occupied area of this room is determined, the measured value can be corrected by the set value.
Description Factory
) when
V, BH
Incre-
setting
10°C 1K E E
0.5 0.1 E E
3 1 N E
40°C 1°C E E
10°C 1°C E E
80°C 1°C N E
10°C 1°C N E
Off 1K E E
0.0K 1K E E
ment
Access
BE HF
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
39
Page 40
7 Parameter settings
Parameters Setting range
Min/Max
Heating curve adaptation
Off Deactivated
On Activated = start of a one-time automatic heating curve adaptation.
Interlink temperature increase
Comfort heating
1 – 50K Only if [Interlink function] parameter = "On":
Off Only if the heating demand is not covered is the storage tank temperature
On At corresponding outside temperatures, the storage tank temperature is
Description Factory
Function can only be executed when the room station is connected and assigned to the HC:
Prerequisites:
▪ Outside temperature <8°C
▪ Setting of the operating mode: "Automatic 1" or "Automatic 2"
▪ Duration of the setback period is at least 6hours
Function: At the start of the setback time, the current room temperature is set as the setpoint for the following 4hours. The heating curve is determined by the controller from the target leaving water temperatures that are required to maintain this room temperature.
If the automatic heating curve adaptation is interrupted, the function pauses until the adaptation is successfully carried out or ended the next day (setting the parameter to "Off" or changing the current operating mode).
Domestic hot water preparation and heating optimisation is locked during the automatic heating curve adaptation.
The target leaving water temperature is increased by the set value when the cooling RT switching contact is closed. Request, e.g. by HP convector.
If the heat pump cannot cover the heating demand when outside temperatures are very low, heat is extracted from the storage tank and used for room heating if the storage tank temperature is [Hot water temperature, current]>[Feed temperature, target]. (See
"4.5.4Heating"[417])
raised. During the time it takes to raise the temperature, there may be a slight loss of comfort.
always raised above the storage tank temperature set for the hot water requirement. The power consumption of the heat pump may increase.
Incre-
setting
5K 1K N E
ment
Access
BE HF
- N E
N E

7.6.4 Menu: Cooling

[→Main menu →Configuration →Cooling]
 7‒16 Parameter in the "Cooling" menu
Parameters Setting range
Min/Max
Target flow cooling, start
Target flow cooling, max.
Start cooling outside temp.
Max. cooling outside temp.
5 – 25°C Only if [Weather-compensated] parameter = "Weather-compensated":
Setting of the cooling target leaving water temperature at the start of cooling operation (outside temperature = [Start cooling outside temp.] parameter)
5 – 25°C Only if [Weather-compensated] parameter = "Weather-compensated":
Setting of the minimum cooling target leaving water temperature. This is held constant as of the outside temperature ([Max. cooling outside temp.] parameter).
15 – 45°C Only if [Weather-compensated] parameter = "Weather-compensated":
Setting as of which outside temperature cooling operation starts with the highest cooling target leaving water temperature [Target flow cooling, start] (setting condition: "Cooling" operating mode).
20 – 45°C Only if [Weather-compensated] parameter = "Weather-compensated":
Setting of the outside temperature at which the lowest cooling target leaving water temperature [Target flow cooling, max.] is specified (setting condition: "Cooling" operating mode).
Description Factory
setting
18°C 1°C E E
8°C 1°C E E
24°C 1°C E E
35°C 1°C E E
Incre-
ment
Access
BE HF
Operating instructions
40
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 41
7 Parameter settings
Parameters Setting range
Min/Max
Feed temperature lower limit
Feed temperature, cooling mode
Cooling setpoint correction
Interlink temperature reduction
5 – 25°C Setting of the absolute lower limit of the cooling target leaving water
8 – 30°C Only if [Weather-compensated] parameter = "Feed temperature, fixed":
-5.0 – +5.0K Parallel shift of the cooling characteristic curve by the set value. 0.0K 1K N E
1 – 50K Only if [Interlink function] parameter = "On":
temperature. Limitation acts if a lower cooling target leaving water temperature is determined from other parameter settings.
If optional freeze-up protection valves are installed in the system, the [Feed temperature lower limit] parameter must not be set below 7°C.
Setting of the cooling target leaving water temperature (fixed value) for active cooling operation.
When the RT switching contact cooling is closed, the cooling target leaving water temperature is reduced by the set value (see [Interlink function] parameter). Request, e.g. by HP convector.
Description Factory

7.6.5 Menu: Hot water

[→Main menu →Configuration →DHW]
 7‒17 Parameter in the "Hot water" menu
Parameters Setting range
Min/Max
Max. hot water loading time
Hot water blocking time
Hot water hysteresis
Wait time ext. heat generator
Solar function Used to reduce the target temperature of the hot water storage tank in
Circulation pump control
Circulation pump interval
10 – 240min Setting of the maximum duration of a domestic hot water preparation cycle.
Then cancellation of domestic hot water preparation if the current hot water temperature does not reach the set setpoint in the [Hot water temperature target 1] parameter.
0 – 180min Setting of the blocking time after completion or cancellation of a domestic
hot water preparation cycle. The repeat request for domestic hot water preparation is operated after this blocking time has elapsed at the earliest.
2 – 20K Hot water charging switching threshold
Setting of the temperature difference by which the temperature in the hot water storage tank may fall in comparison with the currently valid hot water target temperature [Hot water temperature, target] (see "7.3.4Menu: Hot
water temperature, target"[429]) before the heat pump for hot water
charging is to be activated.
20 – 95min Delay time as of which the additional heat generator may support the heat
pump in hot water charging (see "4.5Configuration"[416]).
order to increase the yield of a connected solar system.
Off No function
On The setpoint of the hot water temperature is set as a function of the outside
temperature and in compliance with the safety functions. The setpoint reduction has priority over the settings for the time programs. In addition, the following parameters are defined:
[Hot water hysteresis] = 5K; [Building insulation] = "Normal"
Activated if the switching contact connected to the plug connection J8 (EXT) on the control panel RoConBM2C PCB is also closed
Setting for the control of a circulation pump. Use in France not permitted! - E E
Off Optional circulation pump is synchronously controlled to the active
switching time program for domestic hot water preparation.
On Optional circulation pump is controlled according to the [Circulation
program] switching time program.
Setting of the interval control for an optional circulation pump. Use in France not permitted!
Off Deactivated. The circulation pump runs permanently during the release
times of the assigned switching time program ([Circulation pump control] parameter).
1 – 15min The circulation pump runs clocked (clock cycle ratio: pump runtime =
setting value each 15min).
Description Factory
Incre-
setting
18°C 1°C N E
18°C 1°C E E
5K 1K N E
setting
60min 10min N E
30min 10min N E
7K 1K E E
50min 1min E E
Off 1min E E
ment
Incre-
ment
Access
BE HF
Access
BE HF
- E E
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
41
Page 42
7 Parameter settings
Parameters Setting range
Min/Max
Anti-legionella day
Anti-legionella start time
Anti-legionella temperature
DHW Mode For EHS… indoor units only:
Off No thermal disinfection
Monday
...
Sunday
Daily Daily thermal disinfection
00:00 – 23:45 Setting of the start time for thermal disinfection of the hot water storage
60 – 70°C Setting of the hot water target temperature during thermal disinfection of
On Domestic hot water preparation at low output and higher efficiency
Off Domestic hot water preparation at higher output for greater comfort
Setting of the day for thermal disinfection of the hot water storage tank. Off - E E
Day of thermal disinfection
tank (format hh:mm).
the hot water storage tank.
This function is used for optimum adaptation of the domestic hot water preparation to demand.
Description Factory

7.6.6 Menu: Additional programs

[→Main menu →Configuration →Addition]
 7‒18 Parameter in the "Additional programs" menu
Parameters Setting range
Min/Max
Relay test Manual control of individual relays for test purposes. After confirmation of
this parameter with the rotary button, the list of switchable relays is displayed with a checkbox on the display. For selection and confirmation of a relay with the rotary button, a tick is placed in the checkbox and the respective relay is activated. Multiple selection is possible.
Output J1 Output J1: No function
Output J14 Output J14: Circulation pump power supply
Output J2 contact A
Output J2 contact B
Output J12 3UV
DHW open
Output J12 3UV
DHW closed
Connection J3
N/O contact B
Connec. J3
changeover
contact A
Output J10 Output J10: A1P power supply
Output J17 relayK2Output J17 (pin 3): Relay K2 (RTX-EHS) Output XBUH1 T2
Contact A at output J2: 3UVB1 mixing valve "closed"
Contact B on output J2: 3UVB1 mixing valve "open"
Output J12: 3UV DHW distribution valve "closed"
Output J12: 3UV DHW distribution valve "open"
Connection J3: Potential-free relay: normally open contact B-B1
Connection J3: Potential-free relay: Changer A-A1/A-A2 - AUX
Description Factory
Incre-
setting
03:30 15min N E
65°C 1°C N E
setting
- - N E
ment
Incre-
ment
Access
BE HF
- E E
Access
BE HF
Output J17 relayK1Output J17 (Pin 2): Relay K1 (RTX-EHS) Output XBUH1 T3
Output J17 relayK3Output J17 (Pin 4): Relay K3 (RTX-EHS) Output XBUH1 T1
Ventilation function
Operating instructions
42
Activation of the automatic air purge of the indoor unit and the connected HC.
Off Deactivated
On Start of the air purge function
- N E
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 43
7 Parameter settings
Parameters Setting range
Min/Max
Screed Function for screed drying - N E
Off Deactivated
On The target leaving water temperature is regulated according to the [Screed
program]. The day on which the screed function is activated is not included in the running time of the screed program. The first day starts when the day changes at 00:00 am. On the day of activation, heating is carried out for the remaining time with the target leaving water temperature of the first day's program (see "4.5.7Additional program"[419]).
Screed program
Pump down Only for EHS...D3 indoor units in combination with ERGA...EV3 outdoor
Off, 10 – 70°C
per heating day
Setting of the sequence program of the screed heating. A separate target leaving water temperature can be set for each day for a maximum duration of 28 days. The end of the screed program is defined by the 1st day with the setpoint setting "Off" (see "4.5.7Additional program"[419]).
units:
By activating this function, the refrigerant is sucked back into the refrigerant compressor.
Description Factory
setting
See
"4.5.7Addi-
tional pro-
gram"[419]
Incre-
ment
Access
BE HF
1°C N E
- N E

7.7 Information

[→Main menu →Information]

7.7.1 Overview

[→Main menu →Information →Overview]
 7‒19 Parameter in the "Overview" menu
Parameters Setting range
Min/Max
Mode No request Current mode of the heating pump. - - S S
Heating
Cooling
Domestic hot
water prepara-
tion
Defrost
External request
Room thermostat/ Interlink
Quiet mode 0 – 3 Status of the Quiet mode - - S S
Heating support
No external
mode
Low rate EVU function HT/NT active and low rate.
High rate EVU function HT/NT active and high rate.
SGN EVU function Smart grid active, normal operation.
SG1 EVU function Smart grid active, discharge: No heat pump operation, no
SG2 EVU function Smart grid active, switch-on recommendation, operation at
SG3 EVU function Smart grid active, switch-on command and storage tank
Off If [Interlink function] = "On": Freeze-up protection only; otherwise: "Off"
Request If [Room thermostat] = "Yes"
No heat request If [Room thermostat] = "Yes"
IL1 If [Interlink function] = "On": Normal target leaving water temperature
IL2 If [Interlink function] = "On": In heating operation, increased target leaving
Off Status of the heating support - - S S
On
External request: - - S S
Heat pump operates in normal operation.
freeze-up protection function.
higher target temperatures, inexpensive electricity.
charging to 70°C, inexpensive electricity
Room thermostat/Interlink: - - S S
water temperature, in cooling operation reduced target leaving water temperature
Description Factory
setting
Incre-
ment
Access
BE HF
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
43
Page 44
7 Parameter settings
Parameters Setting range
Min/Max
Status heat circulation pump
PWM pump 25 – 100% Output of the internal heating circulation pump - - S S
BUH current output
3UVB1 position
3UVDHW position
Heat generator type
Software no. B1/U1
Software no. controller
Glycol For ETS... indoor unit only: - N E
Off Status of the internal heating circulation pump - - S S
On
- Current output of the optional backup heater in kW - - S S
- The current position of the 3-way 3UVB1 mixing valve is displayed in % - 1% S S
- The current position of the 3-way 3UV DHW distributor valve is displayed in %.
- The configured type of the heat generator is displayed. - - S S
- The software and the version of the RoCon+B1 control panel are displayed on the indoor unit:
ETS: 427.001.AR
EHS…D2: 427.001.AT, EHS…D3: 427.001.AV
- The software number and version of the RoConBM2C controller PCB are displayed on the indoor unit:
ETS: 425.001.Y
EHS…D2: 425.002.D, EHS…D3: 425.002.F
No glycol added No glycol present in the HC
Glycol added Glycol present in the HC
Description Factory
setting
- 1% S S
- - S S
- - S S
Incre-
ment
Access
BE HF

7.7.2 Values

[→Main menu →Information →Values]
 7‒20 Parameter in the "Values" menu
Parameters Unit Description Factory
setting
Feed temperature, current
Feed temperature, target
Average outside temperature
Hot water temperature, current
Hot water temperature, target
Return flow temperature
Feed temperature HC current
Feed temperature HC target
Feed temperature PHX
°C The current leaving water temperature of the heat generator is displayed
(tV).
°C The current target leaving water temperature of the heat generator is
displayed.
°C The current outside temperature is displayed. 0.1°C S S
°C The current temperature of the hot water storage tank is displayed. If no
hot water function is activated, "----" is displayed.
°C The current target temperature for domestic hot water preparation is
displayed. If no hot water function is activated, "----" is displayed. Here, the current setpoint is always the maximum value of all requests relevant for this hot water circuit.
°C The current return flow temperature of the heat generator is displayed. If
no respective sensor is connected to the heat generator, "----" is displayed.
°C The temperature of the direct HC is displayed (t
support, otherwise tV).
°C The target leaving water temperature of the direct HC is displayed. - 0.1°C S S
°C The current leaving water temperature of the heat generator in the outdoor
unit is displayed.
with active heating
V,BH
Incre-
ment
- 1°C S S
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
Access
BE HF
Operating instructions
44
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 45
7 Parameter settings
Parameters Unit Description Factory
setting
Feed temperature BUH
Outdoor temperature (optional)
Refrigerant temperature
Volume flow l/h The filtered value of the current water-side volume flow is displayed.
Water pressure
INFORMATION
Depending on the device type, the system configuration and the status of the device software, individual listed information parameters cannot be displayed or can be displayed at a different parameter level.
°C The current leaving water temperature t
optional backup heater is displayed.
°C The current outdoor temperature measured by the optional outdoor
temperature sensor is displayed.
°C The current refrigerant temperature of the outdoor unit (liquid) is displayed. - 0.1°C S S
If glycol is added and the internal flow switch is active, 0l/h is displayed.
bar The current water pressure is displayed. - 0.1bar S S
of the heat generator after the
V,BH

7.7.3 Water pressure

[→Main menu →Information →Pressure]
 7‒21 Parameter in the "Water pressure" menu
Parameters Unit Description Factory
setting
Water pressure
bar The current water pressure is displayed. - 0.1bar S S
Incre-
ment
- 0.1°C S S
- 0.1°C S S
- 1l/h S S
Incre-
ment
Access
BE HF
Access
BE HF

7.8 Error

[→Main menu →Error]
 7‒22 Parameter in the "Error" menu
Parameters Setting range
Min/Max
Emergency Emergency heating by backup heater or another external heat generator. - E E
Yes In the event of an error, emergency operation is automatically activated.
No In the event of an error, emergency operation by manual activation only.
Manual operation status
Temperature, manual operation
Inactive Activation of the fixed leaving water temperature control (for diagnostic
purposes).
Active
20 – 80°C Required leaving water temperature for manual operation. 50°C - E E
Description Factory
setting
Incre-
ment
- E E
Access
BE HF

7.9 Terminal

[→Main menu →Terminal]
 7‒23 Parameter in the "Terminal" menu
Parameters Setting range
Min/Max
Terminal address
Off Setting of the terminal ID of the control panel for system access. The set
0 – 9
value must be unique throughout the entire system. Confirmation of this parameter with the rotary button effects a new initialisation of the controller.
All settings except "Off" authorise the user of the control panel to activate the terminal function and thus to operate all RoCon system components with a valid device ID.
Description Factory
setting
Off 1 N E
Incre-
ment
Access
BE HF
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
45
Page 46
7 Parameter settings
Parameters Setting range
Min/Max
Bus scan Off No function Off - E E
On Controller checks which RoCon devices are connected in the system via
CAN bus lines. Detected devices are displayed in the menu [→Main menu →Terminal] with type and data bus ID (e.g. MM#8 = mixer module with bus ID8).
Controller BM1/BE1 #X
Mixer #X With a detected device only: Activation switches to the mixer module with
With a detected device only: Activation switches to the heat generator with the bus ID X (see "4.8Terminal"[422], [Bus ID heat generator] parameter).
the bus ID X (see "4.8Terminal"[422], [Heating circuit assignment] parameter).
Description Factory
setting
Incre-
ment
BE HF
-
- E E
Access

7.10 Statistics

[→Main menu →Statistics →Month/Total]
 7‒24 Parameter in the "Statistics" menu
Parameters Unit Description Factory
setting
Energy HP, cooling
Energy HP, heating
Energy, hot water
Energy HP total
Electr. energy total
Ext. energy source, hot water
Ext. energy source, heating
Runtime, compressor
Runtime, pump
Reset - All parameters listed in the Statistics menu are reset to "0". (Specialist
kWh The amount of heat given off by the heat pump for cooling operation is
displayed.
kWh The amount of heat given off by the heat pump for heating operation is
displayed.
kWh The amount of heat given off by the heat pump for domestic hot water
preparation is displayed.
kWh The total volume of heat given off by the heat pump is displayed. - 1kWh S S
kWh The total electrical power consumed is displayed. - 1kWh S S
kWh The amount of heat of the additional heat generator for domestic hot water
preparation is displayed.
kWh The amount of heat of the additional heat generator for heating operation is
displayed.
h The running time of the refrigerant compressor is displayed. - 1h S S
h The runtime of the internal heating circulation pump is displayed. - 1h S S
code required).
- 1kWh S S
- 1kWh S S
- 1kWh S S
- 1kWh S S
- 1kWh S S
- - S E
Incre-
ment
Access
BE HF
INFORMATION
Depending on the device type, the system configuration and the status of the device software, individual listed information parameters cannot be displayed or can be displayed at a different parameter level.

7.11 Configuration Wizard

Only after hardware reset.
 7‒25 Parameter in the "Configuration Wizard" menu
Parameters Setting range
Min/Max
Direct circuit configuration
Bus ID heat generator
Operating instructions
0 – 15 Setting of the HC ID for the direct HC of the indoor unit. The HC ID must
be unique throughout the entire RoCon system. There must be no overlap with the HC IDs of optional mixer circuits.
0 – 7 The setting must not be changed if more than 1 heat generator is
integrated in the RoCon system. Several heat generators integrated in the heating system must be regarded as a special application. If necessary, contact a service technician.
46
Description Factory
setting
0 1 N E
0 1 N E
Incre-
ment
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Access
BE HF
Daikin RoCon+ HP1
Page 47

8 Errors and faults

Parameters Setting range
Min/Max
Time master No Activation of a system-wide time master. The time master synchronises all
Yes
controllers in the RoCon system with the time and date set on the time master. For all other control panels in the system, it is no longer possible to enter the time and date. There must only be one time master in the entire system. The parameter is not available if the time master parameter is activated on another controller in the RoCon system.
8 Errors and faults
DANGER: RISK OF ELECTROCUTION
Electrostatic charges can lead to voltage arcing that can destroy the electronic components.
▪ Ensure potential equalisation prior to touching the
switching panel PCB (e.g. by touching the switching panel holder).
The electronics of the indoor unit indicate an error by red illumination of the status indicator, the appearance of the error screen on the display (see "8.4 Error screen" [4 48]) and the appearance of the error symbol on the start screen. An integrated error memory stores up to 15 error messages (see "8.3Error protocol"[447]).
INFORMATION
A list of all error codes can be found in the reference guide for the installer, chapter "Errors and faults".
Troubleshooting: Error code E90XX
An error reset can be performed. This can be started from the currently displayed error screen. If the error screen has been exited, it can be recalled via [→Main menu →Error →Screen].
If the same error is displayed again shortly, the cause of the error must be found and rectified by a specialist. In the meantime, emergency operation may be maintained. Emergency operation can be permitted via [→ Main menu → Error → Emergency], see
"8.1 Emergency operation" [4 47]. If emergency operation has not
been permitted ([Emergency] parameter = "No"), it can be started from the current error screen.
Troubleshooting: Other error codes
The cause of the error must be found and rectified by a specialist. In the meantime, emergency operation may be maintained. Emergency operation can be permitted via [→ Main menu → Error →Emergency], see "8.1 Emergency operation" [447]. If emergency operation has not been permitted ([Emergency] parameter = "No"), it can be started from the current error screen.
INFORMATION
To ensure that the error has not been caused by incorrect settings, set all the parameters back to the factory settings before possible replacement of components (see
"4.5.9Parameter reset"[421]).
If it is not possible to determine the cause of the fault, please consult a service technician.
Please have the essential device data ready for this:
Type and manufacturer number of the indoor unit (see heat pump nameplate) as well as the software versions of:
a: Control panel RoCon+B1 [→Main menu →Information →Values →Software no. B1/U1]
b: PCB RoCon BM2C [→ Main menu → Information →Values →Software no. controller]
On optional RoCon system components:
RoConU1 (EHS157034) [Software no. B1/U1]
RoConM1 (EHS157068) [Mixer software number]
Description Factory

8.1 Emergency operation

[→Main menu →Error →Emergency]
If the heat pump fails, the backup heater or another external heat generator can be used as an emergency heater. If [Emergency] is set to "Yes", emergency operation is automatically activated in the event of an error. Otherwise, emergency operation can only be started in the event of an error via the error screen.
If emergency operation is started via the error screen, the [Emergency] parameter remains set to "Yes", i.e. emergency operation is also started automatically in the event of future errors. If this is not desired, the [Emergency] parameter must be reset to "No" after the error has been corrected.

8.2 Manual operation

[→Main menu →Error →Manual operation]
In manual operation, the heat pump is controlled to a fixed leaving water temperature. Manual operation should only be used for diagnostic purposes. Manual operation is started by setting the [Manual operation status] parameter to "Active". The desired leaving water temperature is set by [Temperature, manual operation] parameter.
With hydraulically controlled priority operation for domestic hot water preparation, it must be ensured that the target leaving water temperature set in manual operation is sufficient to achieve the stored hot water target temperature ([Hot water temperature target 1] parameter).

8.3 Error protocol

[→Main menu →Error →Protocol]
The error protocol can be read in this menu. The most recent error message comes first. All previous messages are moved backwards with each new entry in the position. The 16th error message is deleted if a new error message arrives. The error protocol can only be deleted by a service specialist.
The protocol lists
▪ the error code,
▪ the PCB associated with the error (A1P or BM2, see installation
instructions for indoor unit)
▪ Date and time when the error occurred.
setting
Incre-
ment
- N E
Access
BE HF
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
47
Page 48

9 Mixer module

8.4 Error screen

[→Main menu →Error →Screen]
 8‒1 Error screen
If an error occurs, the error screen is displayed. This displays the error code, an explanatory text and the date and time when the error occurred. Depending on the type of error, a reset can be carried out in the error screen by selecting the corresponding icons and/or emergency operation can be started (see "8.1 Emergency
operation" [4 47]). Selecting the Back icon closes the error screen
and the display returns to the start screen.
If an error has occurred, the error screen can be called up manually via [→Main menu →Error →Screen].

8.5 Error codes

See reference guide for the installer, chapter "Errors, faults, messages".
9 Mixer module
In addition to the direct HC, the heating system can be extended by additional HCs using RoCon M1 (EHS157068) mixer modules. These additional HCs can be configured independently of the direct HC. The configuration is similar to the configuration of the direct HC (see "4 Function"[4 11]). Only a limited selection of parameters and functions is available (see "9.2 Mixer valve parameter
overview"[449]).
The optional RoConM1 (EHS157068) mixer module does not have its own control unit. For configuration and operation, it must be connected via a CAN bus line to the RoCon+ HP1+ controller installed in the heat generator or a RoConU1 (EHS157034) room station. The mixer module can be operated in terminal mode from both operating units (see "4.8Terminal"[422]).
A unique device ID (≥1) must be set on the address switch of the mixer module (see "  9‒1 Setting the device ID for the RoConM1
(EHS157068) mixer module" [4 48]) for the HC to be controlled by
this mixer module, which must be synchronised with the [Heating circuit assignment] parameter of the mixer module (see "  4‒6
Functional IDs in the RoCon system"[422]]).
 9‒1 Setting the device ID for the RoConM1 (EHS157068) mixer
module
The current operating status can be determined directly on the RoCon M1 (EHS157068) mixer module (see "  9‒2 Status
indicator on the mixer module"[448]).
Operating instructions
48
 9‒2 Status indicator on the mixer module
 9‒1 Explanation of symbols for RoConM1 (EHS157068) status
indicators
Item LED Description
1 Red Flashing: Internal error
(The error code is communicated to the relevant control unit via the CAN bus)
On: Undervoltage of the internal clock after a power failure (>10h)
2 Green On: Display during operation, mixer module switched
on
3 Green On: CAN communication
4 Green On: Mixer circuit pump switched on
5 Green On: Mixer valve "Open" is activated
6 Green On: Mixer valve "Closed" is activated
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 49
9 Mixer module
Room temperature target 1
Room temperature target 2
Room temperature target 3
Room
Reduce
Absent
Reduce room temperature
Room temperature absent
Party
Absent
Holiday
Public holiday
HC auto 1
Heating circuit auto. 1
HC auto 2
Heating circuit auto. 2
SystemMin. mixer valve pump
Max. mixer valve pump
Outside temperature sensor
Outside temperature correction
Weather-compensated
Frost protection temperature
Building insulation
Heat limit, heating mode
Heat limit, reducing mode
Heating curve
Feed temperature, heating mode
Feed temperature, reducing mode
Max. feed temperature
Min. feed temperature
Room influence
Room sensor adaptation
Heating curve adaptation
SlopeOffset
Cooling curve
Target flow cooling, start
Target flow cooling, max.
Start cooling outside temp.
Max. cooling outside temp.
Cooling parameters
Feed temperature lower limit
Feed temperature, cooling mode
Cooling setpoint correction

9.1 Mixer module start screen (terminal function)

 9‒3 Mixer module start screen
1 Mixer circuit leaving water temperature
The start screen for the mixer module ("  9‒3 Mixer module start
screen"[449]) is a reduced version of the RoCon+B1 start screen.
The meaning of the icons corresponds to "  3‒3 Display icons on
the start screen"[47], but the mixer circuit leaving water temperature
is the only system temperature displayed.
The start screen for the mixer module is displayed in the menu [→Main menu → Terminal → Mixer #X]. Briefly pressing the rotary switch switches to the mixer menu. A long press of the rotary switch switches to the menu of the local control panel.
Menu: Access
Menu: System
 9‒6 Parameters in menu: "System"
Menu: Sensors
 9‒7 Parameters in menu: "Sensors"
Menu: HC config
 9‒8 Parameters in menu: "HC config"
Menu: Heating

9.2 Mixer valve parameter overview

Menu: Operating mode
See "6.1Menu: Operating mode"[425].
Menu: User
 9‒4 Parameters in menu: "User"
Menu: Time program
 9‒9 Parameters in menu: "Heating"
Menu: Cooling
 9‒10 Parameters in menu: "Cooling"
 9‒5 Parameters in menu: "Time program"
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
49
Page 50
9 Mixer module
Relay test
Screed
Program
Screed drying
Screed program
Software no. B1/U1
Average outside temperature
Values
Mixer temperature current
Mixer software number
Mixer temperature target
Mixer pump status
PWM mixer pump
Mixer valve status
Menu: Special
 9‒11 Parameters in menu: "Special"
Menu: Information

9.3 Mixer module parameter settings

The parameters available for the mixer module are largely identical to the parameter described in "7Parameter settings" [428]. "  9‒2
Parameters of the mixer module" [4 50] lists the additional
parameters available for the mixer module.
 9‒2 Parameters of the mixer module
Parameters Setting range
Min/Max
Min. mixer valve pump
Max. mixer valve pump
10 – 100% [→Main menu →System]
Minimum power of the pump in the mixer circuit.
20 – 100% [→Main menu →System]
Maximum power of the pump in the mixer circuit.
SlopeOffset 0 – 50K [→Main menu →Heating]
Setting of the slope offset of the target leaving water temperature on the indoor unit in comparison with the target leaving water temperature determined for the mixer circuit.
Mixer temperature current
Mixer temperature target
Mixer pump status
PWM mixer pump
Mixer valve status
[→Main menu →Information →Values]
Current leaving water temperature in the mixer circuit in °C
[→Main menu →Information →Values]
Current target leaving water temperature in the mixer circuit in °C
On [→Main menu →Information →Values]
Off
Current status of the mixer pump
0 – 100% [→Main menu →Information →Values]
Current modulation of the mixer pump
Neutral [→Main menu →Information →Values]
Close
Current status of the mixer valve
Open
Description Factory
 9‒12 Parameters in menu: "Information"
setting
30% 1% N E
100% 1% N E
5K 1K N E
- - S S
- - S S
- - S S
- - S S
- - S S
Incre-
ment
Access
BE HF
Operating instructions
50
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 51

10 Glossary

10 Glossary
Operating mode Request by the user or controller for the function of the heat generator (e.g. room heating, domestic hot water
preparation, standby, etc.)
Backup request Operating situation in which the required leaving water temperature cannot be reached efficiently or at all
using the heat pump process. A heater booster (e.g. a backup heater) is therefore integrated to support the heat pump in generating heat.
Backup heater Optional electric heater booster for general support of the heat pump during heat generation.
Heating curve Mathematical relationship between the outside temperature and the target leaving water temperature in order
to achieve the required room temperature at all outside temperatures.
Refrigerant A substance used for heat transfer in the heat pump process. At low temperature and low pressure, heat is
absorbed (refrigerant evaporates) and at higher temperature and pressure, heat is released (refrigerant condenses).
Anti-legionella protection Periodic heating of the storage water to >60°C for the preventative elimination of pathogenic bacteria (so-
called legionella) in the hot water circuit.
Low rate mains connection (HT/NT)
Parameters A value that influences the execution of programs or processes or defines specific states.
Controller Device electronics that are used to control the processes for the heat generation and heat distribution of the
Return flow Part of the hydraulic HC that directs the cooled water from the heating surfaces in the rooms back to the heat
Switching time program Program for setting the times on the controller in order to determine the regular heating, reducing and hot
Smart Grid (SG) Intelligent use of energy for inexpensive heating. By using a special electricity meter, it is possible to receive a
Feed Part of the hydraulic HC that diverts the heated water from the heat generator to the heating surfaces.
Domestic hot water circuit This is the water circuit in which domestic cold water is heated and diverted to the hot water tap.
Domestic hot water preparation Operating status of the heat generator in which heat with elevated temperatures is generated and fed to the
Heat pump process In a closed-loop refrigerant circuit, the refrigerant absorbs the heat from the ambient air. By means of
Heat exchanger A component that transfers thermal energy from one circuit to another. The two circuits are hydraulically
Weather-compensated leaving water temperature control
Circulation pump The circulation pump is an additional electrical circulation pump that permanently circulates the hot water in
Heater booster Additional heat generator (e.g. backup heater or external boiler) integrated in the heating system to achieve
A special mains connection to the energy supplier that offers various cheaper rates during so-called low-load periods for electrical current (day-, night-, heat pump current, etc.).
heating system. The controller consists of a number of electronic components. The most important component for the operator is the control panel in the front area of the heat generator, which includes rotary buttons and display.
generator via the piping system.
water cycles.
"Smart Grid signal" from the utility company.
Depending on the signal, the heat pump is shut off or operated as normal or at higher temperatures.
hot water circuit, e.g. loading of the hot water storage tank.
compression, the refrigerant achieves a higher temperature that is transferred to the heating system (thermodynamic cycle).
separated from one another by a wall in the heat exchanger.
A suitable leaving water temperature is determined from the measured value for the outside temperature and a defined heating curve; this temperature is used as the setpoint for temperature control in the heating unit.
the hot water lines, thus providing it immediately at every tap. This circulation is especially useful in extensive pipeline networks. In systems without a circulation line, first the water cooled in the sampling line escapes during the sampling process until the sampling line has been sufficiently heated by the inflowing hot water.
the required target leaving water temperature in the case of an inadequate or inefficient heat pump process.
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
51
Page 52

11 User-specific settings

11 User-specific settings

11.1 Timers

 11‒1 Individual settings in the heating timer programs
Switching cycle 1 Switching cycle 2 Switching cycle 3
Heating circuit auto. 1
Heating circuit auto. 2
Temperature setting
Time period On Off On Off On Off
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
[Room temperature target 1]:
____ °C
The factory settings of the timers are indicated in "4.3 Time
program"[413].
Enter your timer settings in the table below.
[Room temperature target 2]:
____ °C
[Room temperature target 3]:
____ °C
 11‒2 Individual settings in the hot water switching timer programs
Switching cycle 1 Switching cycle 2 Switching cycle 3
Temperature setting
Time period On Off On Off On Off
Hot water auto.1Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Hot water auto.2Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
 11‒3 Individual settings of the switching time program of the circulation pump
Time period On Off On Off On Off
Circulation program
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
[Hot water temperature target 1]:
____ °C
Switching cycle 1 Switching cycle 2 Switching cycle 3
[Hot water temperature target 2]:
____ °C
[Hot water temperature target 3]:
____ °C
Operating instructions
52
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 53
11 User-specific settings
 11‒4 Individual settings of the sound program
Switching cycle 1 Switching cycle 2 Switching cycle 3
Time period On Off Stage On Off Stage On Off Stage
Sound program Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday

11.2 Parameters

Enter the parameter changes that were made in the table below and in the operating manual of the heat generator.
 11‒5 Individual parameter changes
Menu path Parameters Old value New value Date Comments

11.3 Data bus addresses

 11‒6 Data bus addresses in the RoCon system
RoCon Device Terminal address Comments
Daikin RoCon+ HP1 Controller RoCon+ HP1
008.1447899_01 – 08/2020
Operating instructions
53
Page 54
11 List of keywords

List of keywords

A
Anti-legionella protection...............................................................................19, 51
C
Calendar ..........................................................................................................................9
Circulation pump .......................................................................................................19
Comfort heating.........................................................................................................18
Configuration...............................................................................................................16
Configuration Wizard ..............................................................................................24
D
Device ID ......................................................................................................................23
Display..............................................................................................................................6
Documentation set......................................................................................................3
E
External operation ....................................................................................................11
F
Factory setting............................................................................................................28
G
Glossary ........................................................................................................................51
H
HC ID..............................................................................................................................22
Heat generator ID.....................................................................................................22
Heating curve .............................................................................................................17
Heating support function.......................................................................................16
Help function..................................................................................................................8
I
Intended use..................................................................................................................4
M
Mixer module ......................................................................................................17, 48
R
Relevant documents..................................................................................................3
S
Safety switch-off...........................................................................................................5
Screed program
Function heating ...............................................................................................20
Screed curing heating....................................................................................20
Sensor test...................................................................................................................19
Setting setpoints ..........................................................................................................9
Setting the times..........................................................................................................9
Settings..........................................................................................................................14
Smart Grid....................................................................................................................15
Start screen....................................................................................................................6
Mixer module......................................................................................................49
Status indicator.............................................................................................................6
Mixer module......................................................................................................48
Switching function ....................................................................................................15
T
Technician code ........................................................................................................28
Temperature setting
Hot water operation.........................................................................................12
Reduced ...............................................................................................................12
Room temperature absent...........................................................................12
Room temperature target.............................................................................12
Terminal function ......................................................................................................22
Terminal ID ..................................................................................................................23
Time program .....................................................................................................10, 13
Permanent programs .....................................................................................13
Temporary programs......................................................................................13
U
Unscheduled domestic hot water preparation............................................13
V
Ventilation function...................................................................................................19
Z
Zone control ................................................................................................................17
N
Navigating
In lists........................................................................................................................8
Navigating ???
In the menu............................................................................................................8
O
Operating elements....................................................................................................5
Rotary button ........................................................................................................6
Operating mode.........................................................................................................11
Operating modes
Automatic 1 .........................................................................................................12
Automatic 2 .........................................................................................................12
Heating, Cooling ...............................................................................................11
Reduce..................................................................................................................11
Standby.................................................................................................................11
Summer ................................................................................................................12
Operation via the Internet.....................................................................................11
Operation via the room station...........................................................................11
P
Parameter reset.........................................................................................................21
Parameter table.........................................................................................................28
Parameters ..................................................................................................................51
Operating instructions
54
Daikin RoCon+ HP1
Controller RoCon+ HP1
008.1447899_01 – 08/2020
Page 55
Page 56
Verantwortung für Energie und Umwelt
Copyright Daikin
008.1447899_01 08/2020