Daikin EHFH03S18DJ3V Installer reference guide

Installer reference guide
Daikin Altherma 3 R F
EHFH03S18DJ3V ERLA03DAV3

Table of contents

Table of contents
1 General safety precautions 6
1.1 About the documentation .............................................................................................................................................. 6
1.1.1 Meaning of warnings and symbols ................................................................................................................ 6
1.2 For the installer............................................................................................................................................................... 7
1.2.1 General ........................................................................................................................................................... 7
1.2.2 Installation site ............................................................................................................................................... 8
1.2.3 Refrigerant ...................................................................................................................................................... 9
1.2.4 Brine................................................................................................................................................................ 10
1.2.5 Water .............................................................................................................................................................. 11
1.2.6 Electrical ......................................................................................................................................................... 11
2 About the documentation 14
2.1 About this document ...................................................................................................................................................... 14
2.2 Installer reference guide at a glance .............................................................................................................................. 15
3 About the box 17
3.1 Overview: About the box ................................................................................................................................................ 17
3.2 Outdoor unit ................................................................................................................................................................... 17
3.2.1 To unpack the outdoor unit ........................................................................................................................... 17
3.2.2 To handle the outdoor unit ............................................................................................................................ 18
3.2.3 To remove the accessories from the outdoor unit........................................................................................ 18
3.3 Indoor unit ...................................................................................................................................................................... 18
3.3.1 To unpack the indoor unit .............................................................................................................................. 18
3.3.2 To remove the accessories from the indoor unit .......................................................................................... 19
3.3.3 To handle the indoor unit............................................................................................................................... 19
4 About the units and options 20
4.1 Overview: About the units and options.......................................................................................................................... 20
4.2 Identification ................................................................................................................................................................... 20
4.2.1 Identification label: Outdoor unit .................................................................................................................. 20
4.2.2 Identification label: Indoor unit ..................................................................................................................... 21
4.3 Combining units and options.......................................................................................................................................... 21
4.3.1 Possible combinations of indoor unit and outdoor unit................................................................................ 21
4.3.2 Possible options for the outdoor unit ............................................................................................................ 21
4.3.3 Possible options for the indoor unit............................................................................................................... 22
5 Application guidelines 24
5.1 Overview: Application guidelines ................................................................................................................................... 24
5.2 Setting up the space heating/cooling system ................................................................................................................ 24
5.2.1 Single room ..................................................................................................................................................... 25
5.2.2 Multiple rooms – OneLWT zone ................................................................................................................... 29
5.2.3 Multiple rooms – TwoLWT zones.................................................................................................................. 33
5.3 Setting up an auxiliary heat source for space heating ................................................................................................... 35
5.4 Setting up the domestic hot water tank......................................................................................................................... 38
5.4.1 System layout – Integrated DHW tank........................................................................................................... 38
5.4.2 Selecting the desired temperature for the DHW tank .................................................................................. 38
5.4.3 Setup and configuration – DHW tank ............................................................................................................ 39
5.4.4 DHW pump for instant hot water .................................................................................................................. 40
5.4.5 DHW pump for disinfection ........................................................................................................................... 40
5.5 Setting up the energy metering...................................................................................................................................... 41
5.5.1 Produced heat ................................................................................................................................................ 41
5.5.2 Consumed energy........................................................................................................................................... 41
5.5.3 Normal kWh rate power supply ..................................................................................................................... 42
5.5.4 Preferential kWh rate power supply .............................................................................................................. 43
5.6 Setting up the power consumption control ................................................................................................................... 44
5.6.1 Permanent power limitation .......................................................................................................................... 44
5.6.2 Power limitation activated by digital inputs .................................................................................................. 45
5.6.3 Power limitation process................................................................................................................................ 46
5.7 Setting up an external temperature sensor ................................................................................................................... 46
Installer reference guide
2
6 Unit installation 48
6.1 Preparing the installation site......................................................................................................................................... 48
6.1.1 Installation site requirements of the outdoor unit........................................................................................ 48
6.1.2 Additional installation site requirements of the outdoor unit in cold climates............................................ 51
6.1.3 Installation site requirements of the indoor unit .......................................................................................... 52
6.2 Opening and closing the units ........................................................................................................................................ 53
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
Table of contents
6.2.1 About opening the units................................................................................................................................. 53
6.2.2 To open the outdoor unit ............................................................................................................................... 53
6.2.3 To close the outdoor unit ............................................................................................................................... 54
6.2.4 To open the indoor unit ................................................................................................................................. 54
6.2.5 To lower the switch box on the indoor unit .................................................................................................. 56
6.2.6 To close the indoor unit ................................................................................................................................. 57
6.3 Mounting the outdoor unit............................................................................................................................................. 57
6.3.1 About mounting the outdoor unit ................................................................................................................. 57
6.3.2 Precautions when mounting the outdoor unit .............................................................................................. 58
6.3.3 To provide the installation structure ............................................................................................................. 58
6.3.4 To install the outdoor unit ............................................................................................................................. 59
6.3.5 To provide drainage........................................................................................................................................ 59
6.3.6 To prevent the outdoor unit from falling over .............................................................................................. 60
6.4 Mounting the indoor unit ............................................................................................................................................... 60
6.4.1 About mounting the indoor unit .................................................................................................................... 60
6.4.2 Precautions when mounting the indoor unit................................................................................................. 60
6.4.3 To install the indoor unit ................................................................................................................................ 60
6.4.4 To connect the drain hose to the drain ......................................................................................................... 61
6.5 Finishing the outdoor unit installation ........................................................................................................................... 62
6.5.1 To finish the outdoor unit installation ........................................................................................................... 62
7 Piping installation 64
7.1 Preparing refrigerant piping ........................................................................................................................................... 64
7.1.1 Refrigerant piping requirements.................................................................................................................... 64
7.1.2 Refrigerant piping insulation .......................................................................................................................... 65
7.2 Preparing water piping ................................................................................................................................................... 65
7.2.1 Water circuit requirements............................................................................................................................ 65
7.2.2 Formula to calculate the expansion vessel pre-pressure .............................................................................. 68
7.2.3 To check the water volume and flow rate ..................................................................................................... 68
7.2.4 Changing the pre-pressure of the expansion vessel...................................................................................... 70
7.2.5 To check the water volume: Examples .......................................................................................................... 71
7.3 Connecting the refrigerant piping .................................................................................................................................. 71
7.3.1 About connecting the refrigerant piping ....................................................................................................... 71
7.3.2 Precautions when connecting the refrigerant piping .................................................................................... 72
7.3.3 Guidelines when connecting the refrigerant piping ...................................................................................... 73
7.3.4 Pipe bending guidelines ................................................................................................................................. 73
7.3.5 To flare the pipe end ...................................................................................................................................... 73
7.3.6 To braze the pipe end..................................................................................................................................... 74
7.3.7 Using the stop valve and service port ............................................................................................................ 75
7.3.8 To connect the refrigerant piping to the outdoor unit ................................................................................. 76
7.3.9 To connect the refrigerant piping to the indoor unit .................................................................................... 77
7.4 Checking the refrigerant piping...................................................................................................................................... 77
7.4.1 About checking the refrigerant piping ........................................................................................................... 77
7.4.2 Precautions when checking the refrigerant piping........................................................................................ 78
7.4.3 To check for leaks ........................................................................................................................................... 78
7.4.4 To perform vacuum drying............................................................................................................................. 79
7.5 Charging refrigerant........................................................................................................................................................ 80
7.5.1 About charging refrigerant............................................................................................................................. 80
7.5.2 About the refrigerant ..................................................................................................................................... 80
7.5.3 Precautions when charging refrigerant ......................................................................................................... 81
7.5.4 To determine the complete recharge amount .............................................................................................. 81
7.5.5 To fix the fluorinated greenhouse gases label ............................................................................................... 81
7.6 Connecting water piping................................................................................................................................................. 82
7.6.1 About connecting the water piping ............................................................................................................... 82
7.6.2 Precautions when connecting the water piping ............................................................................................ 82
7.6.3 To connect the water piping .......................................................................................................................... 82
7.6.4 To connect the recirculation piping ............................................................................................................... 84
7.6.5 To fill the water circuit ................................................................................................................................... 84
7.6.6 To fill the domestic hot water tank ................................................................................................................ 84
7.6.7 To insulate the water piping .......................................................................................................................... 85
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
8 Electrical installation 86
8.1 About connecting the electrical wiring .......................................................................................................................... 86
8.1.1 Precautions when connecting the electrical wiring....................................................................................... 86
8.1.2 Guidelines when connecting the electrical wiring......................................................................................... 87
8.1.3 Specifications of standard wiring components.............................................................................................. 88
8.1.4 About electrical compliance........................................................................................................................... 89
8.1.5 About preferential kWh rate power supply ................................................................................................... 89
8.1.6 Overview of electrical connections except external actuators ..................................................................... 90
8.2 Connections to the outdoor unit.................................................................................................................................... 90
Installer reference guide
3
Table of contents
8.2.1 To connect the electrical wiring to the outdoor unit .................................................................................... 90
8.3 Connections to the indoor unit ...................................................................................................................................... 91
8.3.1 To connect the main power supply................................................................................................................ 93
8.3.2 To connect the backup heater power supply ................................................................................................ 95
8.3.3 To connect the user interface ........................................................................................................................ 97
8.3.4 To connect the shut-off valve ........................................................................................................................ 99
8.3.5 To connect the electricity meters .................................................................................................................. 100
8.3.6 To connect the domestic hot water pump .................................................................................................... 101
8.3.7 To connect the alarm output ......................................................................................................................... 101
8.3.8 To connect the space cooling/heating ON/OFF output................................................................................. 102
8.3.9 To connect the changeover to external heat source..................................................................................... 104
8.3.10 To connect the power consumption digital inputs........................................................................................ 104
8.3.11 To connect the safety thermostat (normally closed contact)....................................................................... 105
8.4 After connecting the electrical wiring to the indoor unit .............................................................................................. 107
9 Configuration 108
9.1 Overview: Configuration................................................................................................................................................. 108
9.1.1 To change the user permission level ............................................................................................................. 109
9.1.2 To access the most used commands ............................................................................................................. 110
9.1.3 To copy the system settings from the first to the second user interface ..................................................... 111
9.1.4 Quick wizard: Set the system layout after first power ON ............................................................................ 112
9.2 Basic configuration.......................................................................................................................................................... 113
9.2.1 Quick wizard: Language / time and date ....................................................................................................... 113
9.2.2 Quick wizard: Standard .................................................................................................................................. 113
9.2.3 Quick wizard: Options .................................................................................................................................... 116
9.2.4 Space heating/cooling control ....................................................................................................................... 120
9.2.5 Domestic hot water control ........................................................................................................................... 123
9.2.6 Contact/helpdesk number ............................................................................................................................. 124
9.3 Weather-dependent curve ............................................................................................................................................. 124
9.3.1 What is a weather-dependent curve? ........................................................................................................... 124
9.3.2 2-points curve ................................................................................................................................................. 125
9.3.3 Using weather-dependent curves.................................................................................................................. 125
9.4 Advanced configuration/optimisation............................................................................................................................ 127
9.4.1 Space heating/cooling operation: advanced ................................................................................................. 127
9.4.2 Domestic hot water control: advanced ......................................................................................................... 136
9.4.3 Heat source settings ....................................................................................................................................... 141
9.4.4 System settings ............................................................................................................................................... 144
9.5 Menu structure: Overview user settings........................................................................................................................ 151
9.6 Menu structure: Overview installer settings.................................................................................................................. 152
10 Commissioning 154
10.1 Overview: Commissioning .............................................................................................................................................. 154
10.2 Precautions when commissioning .................................................................................................................................. 154
10.3 Checklist before commissioning ..................................................................................................................................... 155
10.4 Checklist during commissioning ..................................................................................................................................... 156
10.4.1 To check the minimum flow rate ................................................................................................................... 156
10.4.2 Air purge function........................................................................................................................................... 156
10.4.3 To perform a test run ..................................................................................................................................... 158
10.4.4 To perform an actuator test run .................................................................................................................... 158
10.4.5 Underfloor heating screed dryout ................................................................................................................. 158
11 Hand-over to the user 162
12 Maintenance and service 163
12.1 Overview: Maintenance and service .............................................................................................................................. 163
12.2 Maintenance safety precautions .................................................................................................................................... 163
12.3 Checklist for yearly maintenance of the outdoor unit ................................................................................................... 164
12.4 Checklist for yearly maintenance of the indoor unit ..................................................................................................... 164
12.4.1 To drain the domestic hot water tank ........................................................................................................... 166
12.5 About cleaning the water filter in case of trouble ......................................................................................................... 167
12.5.1 To remove the water filter ............................................................................................................................. 167
12.5.2 To clean the water filter in case of trouble.................................................................................................... 168
12.5.3 To install the water filter................................................................................................................................ 169
13 Troubleshooting 170
13.1 Overview: Troubleshooting ............................................................................................................................................ 170
13.2 Precautions when troubleshooting ................................................................................................................................ 170
13.3 Solving problems based on symptoms ........................................................................................................................... 171
13.3.1 Symptom: The unit is NOT heating or cooling as expected........................................................................... 171
13.3.2 Symptom: The compressor does NOT start (space heating or domestic water heating) ............................ 172
13.3.3 Symptom: The system is making gurgling noises after commissioning ........................................................ 172
Installer reference guide
4
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
Table of contents
13.3.4 Symptom: The pump is blocked..................................................................................................................... 173
13.3.5 Symptom: The pump is making noise (cavitation)......................................................................................... 173
13.3.6 Symptom: The pressure relief valve opens.................................................................................................... 173
13.3.7 Symptom: The water pressure relief valve leaks........................................................................................... 174
13.3.8 Symptom: The space is NOT sufficiently heated at low outdoor temperatures........................................... 175
13.3.9 Symptom: The pressure at the tapping point is temporarily unusually high................................................ 176
13.3.10 Symptom: Decoration panels are pushed away due to a swollen tank ........................................................ 176
13.3.11 Symptom: Tank disinfection function is NOT completed correctly (AH-error) ............................................. 176
13.4 Solving problems based on error codes ......................................................................................................................... 176
13.4.1 Error codes: Overview.................................................................................................................................... 177
14 Disposal 184
14.1 Overview: Disposal.......................................................................................................................................................... 184
14.2 To pump down ................................................................................................................................................................ 184
15 Technical data 186
15.1 Piping diagram: Outdoor unit ......................................................................................................................................... 186
15.2 Piping diagram: Indoor unit ............................................................................................................................................ 187
15.3 Wiring diagram: Outdoor unit ........................................................................................................................................ 188
15.4 Wiring diagram: Indoor unit ........................................................................................................................................... 190
16 Glossary 196
17 Field settings table 197
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
Installer reference guide
5
1 | General safety precautions

1 General safety precautions

In this chapter

1.1 About the documentation...................................................................................................................................................... 6
1.2 For the installer....................................................................................................................................................................... 7

1.1 About the documentation

The original documentation is written in English. All other languages are
translations.
The precautions described in this document cover very important topics, follow
them carefully.
1.1.1 Meaning of warnings and symbols ........................................................................................................................ 6
1.2.1 General ................................................................................................................................................................... 7
1.2.2 Installation site ....................................................................................................................................................... 8
1.2.3 Refrigerant.............................................................................................................................................................. 9
1.2.4 Brine ....................................................................................................................................................................... 10
1.2.5 Water ...................................................................................................................................................................... 11
1.2.6 Electrical ................................................................................................................................................................. 11
The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised installer.

1.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
Installer reference guide
6
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
1 | General safety precautions
Symbols used in the documentation:

1.2 For the installer

1.2.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
DANGER: RISK OF BURNING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
WARNING
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Installer reference guide
7
1 | General safety precautions
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.Do NOT sit, climb or stand on the unit.

1.2.2 Installation site

NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Installer reference guide
8
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F

1.2.3 Refrigerant

1 | General safety precautions
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
In case of R410A or R32 refrigerant: Toxic gas might be produced if refrigerant
gas comes into contact with fire.
In case of CO
refrigerant: Refrigerant gas is toxic in high concentrations.
2
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self­combustion and explosion of the compressor because of air going into the operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
Installer reference guide
9
1 | General safety precautions
In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the system.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of oxygen going into the operating compressor.
Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside down.
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.

1.2.4 Brine

Installer reference guide
10
If applicable. See the installation manual or installer reference guide of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F

1.2.5 Water

1 | General safety precautions
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.
WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.
If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.

1.2.6 Electrical

DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 1minute, and measure the voltage at
the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage categoryIII condition, MUST be installed in the fixed wiring.
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
Installer reference guide
11
1 | General safety precautions
WARNING
ONLY use copper wires.Make sure the field wiring complies with the applicable legislation.All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.Make sure to install an earth leakage protector. Failure to do so may cause
electric shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
Installer reference guide
12
Install power cables at least 1 m away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 m may not be sufficient.
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
1 | General safety precautions
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/ OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
Installer reference guide
13
2 | About the documentation

2 About the documentation

In this chapter

2.1 About this document.............................................................................................................................................................. 14
2.2 Installer reference guide at a glance...................................................................................................................................... 15

2.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the indoor unit)
Operation manual:
- Quick guide for basic usage
- Format: Paper (in the box of the indoor unit)
User reference guide:
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Installation manual – Outdoor unit:
- Installation instructions
- Format: Paper (in the box of the outdoor unit)
Installation manual – Indoor unit:
- Installation instructions
- Format: Paper (in the box of the indoor unit)
Installer reference guide:
- Preparation of the installation, good practices, reference data,…
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Addendum book for optional equipment:
Installer reference guide
14
- Additional info about how to install optional equipment
- Format: Paper (in the box of the indoor unit) + Digital files on http://
www.daikineurope.com/support-and-manuals/product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
2 | About the documentation
Technical engineering data
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
Online tools
In addition to the documentation set, some online tools are available for installers:
Heating Solutions Navigator
- Digital toolbox that offers a variety of tools to facilitate the installation and
configuration of heating systems.
- To access Heating Solutions Navigator, registration to the Stand By Me
platform is required. For more information, see https://
professional.standbyme.daikin.eu.
Daikin e-Care
- Mobile app for installers and service technicians that allows you to register,
configure and troubleshoot heating systems.
- The mobile app can be downloaded for iOS and Android devices using the QR
codes below. Registration to the Stand By Me platform is required to access the app.
App Store Google Play

2.2 Installer reference guide at a glance

Chapter Description
General safety precautions Safety instructions that you must read before
installing
About the documentation What documentation exists for the installer
About the box How to unpack the units and remove their
accessories
About the units and options How to identify the units
Possible combinations of units and options
Application guidelines Various installation setups of the system
Unit installation What to do and know to install the system,
including information on how to prepare for an installation
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
Piping installation What to do and know to install the piping of the
system, including information on how to prepare for an installation
Electrical installation What to do and know to install the electrical
components of the system, including information on how to prepare for an installation
Installer reference guide
15
2 | About the documentation
Configuration What to do and know to configure the system
Commissioning What to do and know to commission the system
Hand‑over to the user What to give and explain to the user
Maintenance and service How to maintain and service the units
Troubleshooting What to do in case of problems
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
Field settings table Table to be filled in by the installer, and kept for
Chapter Description
after it is installed
after it is configured
future reference
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user.
Installer reference guide
16
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F

3 About the box

2
3
1

In this chapter

3.1 Overview: About the box........................................................................................................................................................ 17
3.2 Outdoor unit ........................................................................................................................................................................... 17
3.2.1 To unpack the outdoor unit ................................................................................................................................... 17
3.2.2 To handle the outdoor unit.................................................................................................................................... 18
3.2.3 To remove the accessories from the outdoor unit ............................................................................................... 18
3.3 Indoor unit .............................................................................................................................................................................. 18
3.3.1 To unpack the indoor unit...................................................................................................................................... 18
3.3.2 To remove the accessories from the indoor unit .................................................................................................. 19
3.3.3 To handle the indoor unit ...................................................................................................................................... 19

3.1 Overview: About the box

This chapter describes what you have to do after the boxes with the outdoor and indoor unit are delivered on-site.
Keep the following in mind:
At delivery, the unit MUST be checked for damage. Any damage MUST be
reported immediately to the claims agent of the carrier.
3 | About the box
Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
When handling the unit, take into account the following:
Prepare the path along which you want to bring the unit inside in advance.

3.2 Outdoor unit

3.2.1 To unpack the outdoor unit

Fragile, handle the unit with care.
Keep the unit upright in order to avoid damage.
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
Installer reference guide
17
3 | About the box
a b c d e
1 2

3.2.2 To handle the outdoor unit

CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.

3.2.3 To remove the accessories from the outdoor unit

a Outdoor unit installation manual b Multilingual fluorinated greenhouse gases label
c Drain plug (located on the bottom of the packing case) d Energy label e Fluorinated greenhouse gases label

3.3 Indoor unit

3.3.1 To unpack the indoor unit

Installer reference guide
18
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F

3.3.2 To remove the accessories from the indoor unit

4×1×4×
a b
g h ic d e f
j
b
a a
b
a Shut-off valves for water circuit b Overpressure bypass valve c General safety precautions d Addendum book for optional equipment e Indoor unit installation manual
f Operation manual g Sealing rings for shut-off valves (space heating water circuit) h Sealing rings for field-supplied shut-off valves (domestic hot water circuit)
i Sealing tape for low voltage wiring intake j Remote user interface
3 | About the box

3.3.3 To handle the indoor unit

Use the handles at the back and at the bottom to carry the unit.
a Handles at the back of the unit b Handles at the bottom of the unit. Carefully tilt the unit to the back so that the handles become visible.
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
Installer reference guide
19
4 | About the units and options

4 About the units and options

In this chapter

4.1 Overview: About the units and options ................................................................................................................................. 20
4.2 Identification........................................................................................................................................................................... 20
4.2.1 Identification label: Outdoor unit .......................................................................................................................... 20
4.2.2 Identification label: Indoor unit ............................................................................................................................. 21
4.3 Combining units and options.................................................................................................................................................. 21
4.3.1 Possible combinations of indoor unit and outdoor unit ....................................................................................... 21
4.3.2 Possible options for the outdoor unit.................................................................................................................... 21
4.3.3 Possible options for the indoor unit ...................................................................................................................... 22

4.1 Overview: About the units and options

This chapter contains information about:
Identifying the outdoor unit
Identifying the indoor unit
Combining the outdoor unit with options
Combining the indoor unit with options

4.2 Identification

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.

4.2.1 Identification label: Outdoor unit

Location
Model identification
Example: ERLA03DAV3
Installer reference guide
20
Code Explanation
ER European split outdoor pair heat pump
L Low water temperature – ambient zone: −10~−20°C
A Refrigerant R32
03 Capacity class
DA Model series
V3 Power supply
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F

4.2.2 Identification label: Indoor unit

Location
Model identification
Example: EHFH03S18DJ3V
Code Description
E European model
HF Floor-standing indoor unit with integrated tank
H H=Heating only
03 Capacity class
S Integrated tank material: Stainless steel
18 Integrated tank volume
4 | About the units and options
DJ Model series
3V Backup heater model

4.3 Combining units and options

INFORMATION
Certain options might not be available in your country.

4.3.1 Possible combinations of indoor unit and outdoor unit

Outdoor unit Indoor unit
ERLA03DAV3 O

4.3.2 Possible options for the outdoor unit

Bottom plate heater (EKBPHT03D)
Prevents freeze-up of the bottom plate.
EHFH03S18DJ3V
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
Recommended in areas with low ambient temperature and high humidity.
Required in areas with ambient temperatures between –7°C and –15°C when the
outdoor unit is installed between 1000 m and 2000 m altitude. See
"6.1.2 Additional installation site requirements of the outdoor unit in cold climates"[451] for more information.
For installation instructions, see the installation manual of the bottom plate
heater.
Installer reference guide
21
4 | About the units and options

4.3.3 Possible options for the indoor unit

User interface used as room thermostat (BRC1HHDA)
The user interface used as room thermostat can only be used in combination
with the user interface connected to the indoor unit.
The user interface used as room thermostat needs to be installed in the room
that you want to control.
For installation instructions, see the installation and operation manual of the user interface used as room thermostat.
Room thermostat (EKRTWA, EKRTR1)
You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (EKRTWA) or wireless (EKRTR1).
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (EKRTR1).
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HBAA)
The digital I/O PCB is required to provide following signals:
Alarm output
Space heating/cooling On/OFF output
Changeover to external heat source
For installation instructions, see the installation manual of the digital I/O PCB and addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room temperature sensor.
As an option the remote indoor sensor can be installed to measure the room temperature on another location.
Installer reference guide
22
For installation instructions, see the installation manual of the remote indoor sensor and addendum book for optional equipment.
INFORMATION
The remote indoor sensor can only be used in case the user interface is
configured with room thermostat functionality.
You can only connect either the remote indoor sensor or the remote outdoor
sensor.
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4 | About the units and options
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor temperature on another location (e.g. to avoid direct sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor sensor and the addendum book for optional equipment.
INFORMATION
You can only connect either the remote indoor sensor or the remote outdoor sensor.
PC cable (EKPCCAB4)
The PC cable makes a connection between the switch box of the indoor unit and a PC. It gives the possibility to update the software of the indoor unit.
For installation instructions, see the installation manual of the PC cable.
Pipe bend kit (EKHVTC)
When the indoor unit is installed in a place with limited space, a pipe bend kit can be installed to facilitate the connection to the refrigerant liquid and gas connections of the indoor unit.
For installation instructions, see the instruction sheet of the pipe bend kit.
Heat pump convector (FWXV)
For providing space heating/cooling, it is possible to use heat pump convectors (FWXV).
For installation instructions, see the installation manual of the heat pump convectors, and the addendum book for optional equipment.
LAN adapter for smartphone control + Smart Grid applications (BRP069A61)
You can install this LAN adapter to:
Control the system via a smartphone app.
Use the system in various Smart Grid applications.
For installation instructions, see the installation manual of the LAN adapter.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a smartphone app.
For installation instructions, see the installation manual of the LAN adapter.
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
Installer reference guide
23
5 | Application guidelines

5 Application guidelines

In this chapter

5.1 Overview: Application guidelines........................................................................................................................................... 24
5.2 Setting up the space heating/cooling system ........................................................................................................................ 24
5.2.1 Single room............................................................................................................................................................. 25
5.2.2 Multiple rooms – OneLWT zone ........................................................................................................................... 29
5.2.3 Multiple rooms – TwoLWT zones ......................................................................................................................... 33
5.3 Setting up an auxiliary heat source for space heating........................................................................................................... 35
5.4 Setting up the domestic hot water tank ................................................................................................................................ 38
5.4.1 System layout – Integrated DHW tank .................................................................................................................. 38
5.4.2 Selecting the desired temperature for the DHW tank .......................................................................................... 38
5.4.3 Setup and configuration – DHW tank .................................................................................................................... 39
5.4.4 DHW pump for instant hot water .......................................................................................................................... 40
5.4.5 DHW pump for disinfection ................................................................................................................................... 40
5.5 Setting up the energy metering ............................................................................................................................................. 41
5.5.1 Produced heat ........................................................................................................................................................ 41
5.5.2 Consumed energy .................................................................................................................................................. 41
5.5.3 Normal kWh rate power supply............................................................................................................................. 42
5.5.4 Preferential kWh rate power supply...................................................................................................................... 43
5.6 Setting up the power consumption control........................................................................................................................... 44
5.6.1 Permanent power limitation.................................................................................................................................. 44
5.6.2 Power limitation activated by digital inputs .......................................................................................................... 45
5.6.3 Power limitation process ....................................................................................................................................... 46
5.7 Setting up an external temperature sensor........................................................................................................................... 46

5.1 Overview: Application guidelines

The purpose of the application guidelines is to give a glance of the possibilities of the heatpump system.
NOTICE
The illustrations in the application guidelines are meant for reference only, and
are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic
dimensioning and balancing are NOT shown, and are the responsibility of the
installer.
For more information about the configuration settings to optimize heat pump
operation, see "9Configuration"[4108].
This chapter contains application guidelines for:
Setting up the space heating/cooling system
Setting up an auxiliary heat source for space heating
Setting up the domestic hot water tank
Setting up the energy metering
Setting up the power consumption control
Setting up an external temperature sensor

5.2 Setting up the space heating/cooling system

Installer reference guide
24
The heat pump system supplies leaving water to heat emitters in one or more rooms.
Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
5 | Application guidelines
A
B
a
How many rooms are heated or cooled by the heatpump system?
Which heat emitter types are used in each room and what is their design leaving
water temperature?
Once the space heating/cooling requirements are clear, we recommend to follow the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if the leaving water temperature control on user interface of the unit is turned ON.
INFORMATION
In case an external room thermostat is used and room frost protection needs to be guaranteed in all conditions, then you have to set auto emergency [A.6.C] to 1.
NOTICE
An overpressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations.

5.2.1 Single room

Underfloor heating or radiators – Wired room thermostat
Setup
A Main leaving water temperature zone B One single room
a User interface used as room thermostat
For more information about connecting the electrical wiring to the unit, see:
- "8.2Connections to the outdoor unit"[490]
- "8.3Connections to the indoor unit"[491]
The underfloor heating or radiators are directly connected to the indoor unit.
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
The room temperature is controlled by the user interface used as room
thermostat (EKRUDAL1).
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
Code: [C-07]
Installer reference guide
25
5 | Application guidelines
A
B
b
a
Underfloor heating or radiators – Wireless room thermostat
Benefits
Highest comfort and efficiency. The smart room thermostat functionality can
decrease or increase the desired leaving water temperature based on the actual room temperature (modulation). This results in:
- Stable room temperature matching the desired temperature (higher comfort)
- Less ON/OFF cycles (more quiet, higher comfort and higher efficiency)
- Lowest possible leaving water temperature (higher efficiency)
Easy. You can easily set the desired room temperature via the user interface:
- For your daily needs, you can use preset values and schedules.
- To deviate from your daily needs, you can temporarily overrule the preset
values and schedules, or use the holiday mode.
Setup
A Main leaving water temperature zone B One single room a Receiver for wireless external room thermostat b Wireless external room thermostat
For more information about connecting the electrical wiring to the unit, see:
- "8.2Connections to the outdoor unit"[490]
- "8.3Connections to the indoor unit"[491]
The underfloor heating or radiators are directly connected to the indoor unit.
The room temperature is controlled by the wireless external room thermostat
(optional equipment EKRTR1).
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
1 (Ext RT control): Unit operation is decided by the external thermostat.
Code: [C-07]
External room thermostat for the main zone:
#: [A.2.2.4]
1 (Thermo ON/OFF): When the used external room thermostat or heatpump convector can only send a thermo ON/ OFF condition.
Code: [C-05]
Installer reference guide
26
Benefits
Wireless. The Daikin external room thermostat is available in a wireless version.
Efficiency. Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heatpump system.
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
Comfort. In case of underfloor heating, the wireless external room thermostat
a
A
B
prevents condensation on the floor during cooling operation by measuring the room humidity.
Heatpump convectors
Setup
For more information about connecting the electrical wiring to the unit, see:
5 | Application guidelines
A Main leaving water temperature zone B One single room
a Remote controller of the heat pump convectors
- "8.2Connections to the outdoor unit"[490]
- "8.3Connections to the indoor unit"[491]
The heatpump convectors are directly connected to the indoor unit.
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump convectors. For more information, see:
- The installation manual of the heat pump convectors
- The installation manual of the heat pump convector options
- The addendum book for optional equipment
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
The space operation mode is sent to the heat pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
1 (Ext RT control): Unit operation is decided by the external thermostat.
Code: [C-07]
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
External room thermostat for the main zone:
#: [A.2.2.4]
1 (Thermo ON/OFF): When the used external room thermostat or heatpump convector can only send a thermo ON/ OFF condition.
Code: [C-05]
Benefits
Cooling. The heat pump convector offers, besides heating capacity, also excellent
cooling capacity.
Efficiency. Optimal energy efficiency because of the interlink function.
Installer reference guide
27
5 | Application guidelines
M1
a
A
B
Combination: Underfloor heating + Heatpump convectors
Stylish.
Space heating is provided by:
- The underfloor heating
- The heatpump convectors
Space cooling is provided by the heat pump convectors only. The underfloor
heating is shut off by the shut-off valve.
Setup
A Main leaving water temperature zone B One single room a Remote controller of the heat pump convectors
For more information about connecting the electrical wiring to the unit, see:
- "8.2Connections to the outdoor unit"[490]
- "8.3Connections to the indoor unit"[491]
The heatpump convectors are directly connected to the indoor unit.
A shut-off valve (field supply) is installed before the underfloor heating to
prevent condensation on the floor during cooling operation.
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump convectors. For more information, see:
- The installation manual of the heat pump convectors
- The installation manual of the heat pump convector options
- The addendum book for optional equipment
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
The space operation mode is sent by one digital output (X2M/4 and X2M/3) on
the indoor unit to:
- The heatpump convectors
Installer reference guide
28
- The shut-off valve
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
1 (Ext RT control): Unit operation is decided by the external thermostat.
Code: [C-07]
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
5 | Application guidelines
C
T
A
B
a
Setting Value
External room thermostat for the main zone:
#: [A.2.2.4]
Code: [C-05]
Benefits
Cooling. Heat pump convectors provide, besides heating capacity, also excellent
cooling capacity.
Efficiency. Underfloor heating has the best performance with the heat pump
system.
Comfort. The combination of the two heat emitter types provides:
- The excellent heating comfort of the underfloor heating
- The excellent cooling comfort of the heatpump convectors
5.2.2 Multiple rooms – OneLWT zone
If only one leaving water temperature zone is needed because the design leaving water temperature of all heat emitters is the same, you do NOT need a mixing valve station (cost effective).
Example: If the heatpump system is used to heat up one floor where all the rooms have the same heat emitters.
1 (Thermo ON/OFF): When the used external room thermostat or heatpump convector can only send a thermo ON/ OFF condition.
Underfloor heating or radiators – Thermostatic valves
If you are heating up rooms with underfloor heating or radiators, a very common way is to control the temperature of the main room by using a thermostat (this can either be the user interface or an external room thermostat), while the other rooms are controlled by so-called thermostatic valves, which open or close depending on the room temperature.
Setup
A Main leaving water temperature zone B Room 1 C Room 2
a User interface used as room thermostat
For more information about connecting the electrical wiring to the unit, see:
ERLA03DAV3 + EHFH03S18DJ3V Daikin Altherma 3 R F 4P596806-1 – 2019.10
- "8.2Connections to the outdoor unit"[490]
- "8.3Connections to the indoor unit"[491]
The underfloor heating of the main room is directly connected to the indoor unit.
The room temperature is controlled by the user interface used as room
thermostat (EKRUDAL1).
Installer reference guide
29
5 | Application guidelines
A
B C
b
a
M1
a
M2
A thermostatic valve is installed before the underfloor heating in each of the
other rooms.
INFORMATION
Mind situations where the main room can be heated by another heating source. Example: Fireplaces.
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
Code: [C-07]
Benefits
Easy. Same installation as for one room, but with thermostatic valves.
Underfloor heating or radiators – Multiple external room thermostats
Setup
A Main leaving water temperature zone B Room 1 C Room 2 a External room thermostat b Bypass valve
For more information about connecting the electrical wiring to the unit, see:
- "8.2Connections to the outdoor unit"[490]
- "8.3Connections to the indoor unit"[491]
For each room, a shut-off valve (field supplied) is installed to avoid leaving water
supply when there is no heating or cooling demand.
A bypass valve must be installed to make water recirculation possible when all
shut-off valves are closed. To guarantee reliable operation, provide a minimum water flow as described in table "To check the water volume and flow rate" in
"7.2Preparing water piping"[465].
The user interface connected to the indoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to match the indoor unit.
The room thermostats are connected to the shut-off valves, but do NOT have to
be connected to the indoor unit. The indoor unit will supply leaving water all the time, with the possibility to program a leaving water schedule.
Installer reference guide
30
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
Loading...
+ 174 hidden pages