Daikin EDHQ011BA6V3, EDHQ014BA6V3, EDHQ016BA6V3, EDHQ011BA6W1, EDHQ014BA6W1 Installation manual

...
INSTALLATION MANUAL
EDHQ011BA6V3 EDHQ014BA6V3 EDHQ016BA6V3
EDHQ011BA6W1 EDHQ014BA6W1 EDHQ016BA6W1
EDLQ011BA6V3 EDLQ014BA6V3 EDLQ016BA6V3
EDLQ011BA6W1 EDLQ014BA6W1 EDLQ016BA6W1
EBHQ011BA6V3 EBHQ014BA6V3 EBHQ016BA6V3
EBHQ011BA6W1 EBHQ014BA6W1 EBHQ016BA6W1
EBLQ011BA6V3 EBLQ014BA6V3 EBLQ016BA6V3
EBLQ011BA6W1 EBLQ014BA6W1 EBLQ016BA6W1
D2D2
L1
L2
B1
B2
D2D2
L1
L2
1
B2
B2
D2
D2D2
EE
L1
L1
CC
HH
B1B1B1
L2
L2
AA
D1D1D1
1
B2B2B2
D2D2
D2
EE
L1
CC
L2
L2
AA
D1D1D1
L1
HH
B1
B1
1
2
1
2
W1V3
AC
AC
DCACDCAC
2
.
07
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
.
.
.
.
*
.
. 07
*
.
.
.
.
.
.
.
i
.
.
.
*
.
.
.
.
.
*
01
02
03
04
05
06
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Direktive z vsemi spremembami.
Direktiivid koos muudatustega.
Директиви, с техните изменения.
Direktyvose su papildymais.
Direktīvās un to papildinājumos.
Smernice, v platnom znení.
Değiştirilmiş halleriyle Yönetmelikler.
ATITIKTIES-DEKLARACIJA
ATBILSTĪBAS-DEKLARĀCIJA
VYHLÁSENIE-ZHODY
CE -
CE -
CE -
CE - UYUMLULUK-BİLDİRİSİ
<A> DAIKIN.TCF.025C22/10-2009
<B> KEMA (NB0344)
<C> 2082543.0551-QUA/EMC
v
<B>
<B>
pozitīvajam
<C> Sertifikasına
<B>
a pozitívne zistené
съгласно
<B>
положително от
szerint.
<C> tanúsítvány
a(z)
sertifikātu <C>
<A>
ir kaip teigiamai nuspręsta
un atbilstoši
<A>
<A>
osvedčením <C>
Sertifikatą <C>
vērtējumam saskaņā ar
súlade s
pagal
Cертификата <C>
kaip nustatyta
kā norādīts
ako bolo uvedené v
22 Pastaba *
23 Piezīmes *
24 Poznámka *
v
<B>
, pozytywną opinią
şi apreciat pozitiv
Certificatul <C>
<A>
<A>
in odobreno s strani
<A>
certifikatom <C>
în conformitate cu
Świadectwem <C>
<B>
de
zgodnie z dokumentacją
<B>
aşa cum este stabilit în
kot je določeno v
skladu s
tarafından olumlu olarak
<B>
‘da belirtildiği gibi ve
değerlendirildiği gibi.
<A>
göre
Not
25
ja heaks
<A>
sertifikaadile <C>
järgi vastavalt
<B>
kiidetud
nagu on näidatud dokumendis
ZJAVA O SKLADNOSTI
VASTAVUSDEKLARATSIOON
ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ
CE - I
CE -
CE -
deklaruje na własną wyłączną odpowiedzialność, że urządzenia, których ta deklaracja dotyczy:
declară pe proprie răspundere că echipamentele la care se referă această declaraţie:
m
r
IZJAVA-O-USKLAĐENOSTI
DEKLARACJA-ZGODNOŚCI
DECLARAŢIE-DE-CONFORMITATE
CE - MEGFELELŐSÉGI-NYILATKOZAT
CE -
CE -
CE -
z vso odgovornostjo izjavlja, da je oprema naprav, na katero se izjava nanaša:
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluv varustus:
visiška savo atsakomybe skelbia, kad įranga, kuriai taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk aprakstītās iekārtas, uz kurām attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že zariadenie, na ktoré sa vzťahuje toto vyhlásenie:
декларира на своя отговорност, че оборудването, за което се отнася тази декларация:
o
x
b
tamamen kendi sorumluluğunda olmak üzere bu bildirinin ilgili olduğu donanımının aşağıdaki gibi olduğunu beyan eder:
t
v
k
w
25
megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
instrukcjami:
sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
conformitate cu instrucţiunile noastre
skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
инструкции:
atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade
s našim návodom:
ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
Direktiver, med senere ændringer.
Direktiv, med företagna ändringar.
Direktiver, med foretatte endringer.
Direktiivejä, sellaisina kuin ne ovat muutettuina.
v platném znění.
Directives, as amended.
Direktiven, gemäß Änderung.
Directives, telles que modifiées.
Richtlijnen, zoals geamendeerd.
Directivas, según lo enmendado.
Smjernice, kako je izmijenjeno.
irányelv(ek) és módosításaik rendelkezéseit.
и оценено
z późniejszymi poprawkami.
Directivelor, cu amendamentele respective.
<A>
както е изложено в
21 Забележка *
Direttive, come da modifica.
√‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›.
Directivas, conforme alteração em.
Директив со всеми поправками.
igazolta a megfelelést,
<B>
alapján, a(z)
<A>
a(z)
PROHLÁŠENÍ-O-SHODĚ
CE - ERKLÆRING OM-SAMSVAR
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE -
заявляет, исключительно под свою ответственность, что оборудование, к которому относится настоящее заявление:
erklærer som eneansvarlig, at udstyret, som er omfattet af denne erklæring:
deklarerar i egenskap av huvudansvarig, att utrustningen som berörs av denna deklaration innebär att:
erklærer et fullstendig ansvar for at det utstyr som berøres av denne deklarasjon, innebærer at:
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat laitteet:
prohlašuje ve své plné odpovědnosti, že zařízení, k němuž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da oprema na koju se ova izjava odnosi:
teljes felelőssége tudatában kijelenti, hogy a berendezések, melyekre e nyilatkozat vonatkozik:
u
q
s
n
j
c
y
CE - DECLARAÇÃO-DE-CONFORMIDADE СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OPFYLDELSESERKLÆRING
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - ¢H§ø™H ™YMMOPºø™H™
CE - DECLARACION-DE-CONFORMIDAD
CE - DICHIARAZIONE-DI-CONFORMITA
la declaración:
referencia
h
estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
acordo com as nossas instruções:
соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим
инструкциям:
overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore
instrukser:
respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under
förutsättning att användning sker i överensstämmelse med våra instruktioner:
respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
disse brukes i henhold til våre instrukser:
vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme
mukaisesti:
za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
29/12/2009)
Low Voltage 2006/95/EC
Machinery 98/37/EC (
Electromagnetic Compatibility 2004/108/EC *
ob upoštevanju določb:
vastavalt nõuetele:
следвайки клаузите на:
laikantis nuostatų, pateikiamų:
ievērojot prasības, kas noteiktas:
održiavajúc ustanovenia:
bunun koşullarına uygun olarak:
under iagttagelse af bestemmelserne i:
enligt villkoren i:
gitt i henhold til bestemmelsene i:
noudattaen määräyksiä:
za dodržení ustanovení předpisu:
prema odredbama:
követi a(z):
zgodnie z postanowieniami Dyrektyw:
în urma prevederilor:
Notă *
16 Megjegyzés *
17 Uwaga *
18
on
<B>
ja jotka
enligt
<B>
och godkänts av
<A>
enligt
11 Information *
e giudicato positivamente
<A>
delineato nel
mukaisesti.
<A>
Sertifikat <C>
og gjennom positiv
<A>
ifølge
<B>
Sertifikaatin <C>
hyväksynyt
Certifikatet <C>
som det fremkommer i
bedømmelse av
jotka on esitetty asiakirjassa
12 Merk *
13 Huom *
Certificado <C>
¶ИЫЩФФИЛЩИОfi <C>
e com o parecer
Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο
<A>
<A>
Certificato <C>
de acordo com o
Û‡Ìʈӷ Ì ÙÔ
<B>
<B>
secondo il
<B>
positivo de
·fi ÙÔ
tal como estabelecido em
da
* fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ
™ËÌ›ˆÛË
06 Nota *
08 Nota
<B>
positiv
<B>
<C>
<C>
et évalué positivement par
Certificat <C>
<A>
Certificate
and judged positively by
Zertifikat
aufgeführt und von
<A>
<A>
conformément au
beurteilt gemäß
according to the
as set out in
wie in der
tel que défini dans
<B>
19 Opomba *
20 Märkus
v
<B>
a pozitivně zjištěno
i pozitivno ocijenjeno od
<A>
Certifikatu <C>
<A>
prema
osvědčením <C>
<B>
strane
jak bylo uvedeno v
kako je izloženo u
souladu s
14 Poznámka *
15 Napomena *
i
<B>
согласно
<B>
и в соответствии с
og positivt vurderet af
<A>
<A>
Certifikat <C>
положительным решением
henhold til
как указано в
Свидетельству <C>
som anført i
09 Примечание *
10 Bemærk *
y es valorado
de acuerdo con el
<A>
Certificaat <C>
en positief beoordeeld door
<B>
<A>
overeenkomstig
zoals vermeld in
<B>
como se establece en
Certificado <C>
positivamente por
Jiro Tomita
Director Quality Assurance
Ostend, 2nd of November 2009
declares under its sole responsibility that the equipment to which this declaration relates:
erklärt auf seine alleinige Verantwortung, dass die Ausrüstung für die diese Erklärung bestimmt ist:
déclare sous sa seule responsabilité que l’équipement visé par la présente déclaration:
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de apparatuur waarop deze verklaring betrekking heeft:
declara bajo su única responsabilidad que el equipo al que hace
a
d
f
l
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
Daikin Europe N.V.
e
dichiara sotto la propria responsabilità che gli apparecchi a cui è riferita questa dichiarazione:
declara sob sua exclusiva responsabilidade que os equipamentos a que esta declaração se refere:
‰ЛПТУВИ МВ ·ФОПВИЫЩИО‹ ЩЛ˜ В˘ı‡УЛ fiЩИ Ф ВНФПИЫМfi˜ ЫЩФУ ФФ›Ф ·У·К¤ЪВЩ·И Л ·ЪФ‡Ы· ‰‹ПˆЫЛ:
i
p
g
EDLQ011BA6V3, EDLQ011BA6W1, EDLQ014BA6V3, EDLQ014BA6W1, EDLQ016BA6V3, EDLQ016BA6W1, EDHQ011BA6V3, EDHQ011BA6W1, EDHQ014BA6V3, EDHQ014BA6W1, EDHQ016BA6V3, EDHQ016BA6W1,
EBLQ011BA6V3, EBLQ011BA6W1, EBLQ014BA6V3, EBLQ014BA6W1, EBLQ016BA6V3, EBLQ016BA6W1, EBHQ011BA6V3, EBHQ011BA6W1, EBHQ014BA6V3, EBHQ014BA6W1, EBHQ016BA6V3, EBHQ016BA6W1,
are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
instructions:
der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung,
daß sie gemäß unseren Anweisungen eingesetzt werden:
sont conformes à la/aux norme(s) ou autre(s) document(s) nor matif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig
onze instructies:
están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) nor mativo(s), siempre que sean utilizados de acuerdo con
nuestras instrucciones:
sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle
nostre istruzioni:
В›У·И Ы‡МКˆУ· МВ ЩФ(·) ·ОfiПФ˘ıФ(·) ЪfiЩ˘Ф(·) ‹ ¿ППФ ¤ББЪ·КФ(·) О·УФУИЫМТУ, ˘fi ЩЛУ ЪФ¸fiıВЫЛ fiЩИ ¯ЪЛЫИМФФИФ‡УЩ·И
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜:
following the provisions of:
gemäß den Vorschriften der:
conformément aux stipulations des:
EN60335-2-40,
overeenkomstig de bepalingen van:
siguiendo las disposiciones de:
secondo le prescrizioni per:
Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv:
de acordo com o previsto em:
в соответствии с положениями:
01 Note *
02 Hinweis *
03 Remarque *
04 Bemerk *
05 Nota
3PW33163-5F
EDHQ011~016BA6V3 EDHQ011~016BA6W1 EDLQ011~016BA6V3 EDLQ011~016BA6W1 EBHQ011~016BA6V3 EBHQ011~016BA6W1 EBLQ011~016BA6V3 EBLQ011~016BA6W1
Unit for air to water heat pump system
Installation manual
CONTENTS Page
Introduction ....................................................................................... 1
General information ................................................................................... 1
Scope of this manual ................................................................................. 2
Model identification.................................................................................... 2
Accessories....................................................................................... 3
Accessories supplied with the unit............................................................. 3
Safety considerations........................................................................ 3
Before installation.............................................................................. 4
Important information regarding the refrigerant used........................ 4
Selecting installation site................................................................... 5
Selecting a location in cold climates.......................................................... 5
Precautions on installation ................................................................6
Installation method for prevention of falling over........................................ 6
Installation servicing space........................................................................ 6
Typical application examples............................................................. 7
Application 1 .............................................................................................. 7
Application 2 .............................................................................................. 8
Application 3 .............................................................................................. 8
Application 4 .............................................................................................. 9
Application 5 .............................................................................................. 9
Application 6 ............................................................................................ 11
Overview of the unit ........................................................................ 12
Opening the unit ...................................................................................... 12
Main components .................................................................................... 12
Water pipework........................................................................................ 14
Charging water ........................................................................................ 17
Piping insulation....................................................................................... 17
Field wiring .............................................................................................. 17
Installation of the digital controller ........................................................... 24
Start-up and configuration............................................................... 25
DIP switch settings overview ................................................................... 25
Room thermostat installation configuration ............................................. 25
Pump operation configuration.................................................................. 26
Domestic hot water tank installation configuration................................... 26
Initial start-up at low outdoor ambient temperatures ............................... 26
Pre-operation checks............................................................................... 27
Powering up the unit ................................................................................ 27
Setting the pump speed........................................................................... 27
Field settings............................................................................................ 28
Field settings table................................................................................... 37
Test run and final check .................................................................. 39
Automatic test run.................................................................................... 39
Test run operation (manual)..................................................................... 39
Maintenance and service......................................................................... 40
Maintenance and service ................................................................40
Troubleshooting............................................................................... 41
General guidelines................................................................................... 41
General symptoms................................................................................... 41
Error codes .............................................................................................. 42
Technical specifications................................................................... 43
General.................................................................................................... 43
Electrical specifications ........................................................................... 43
READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL.
ALL ACTIVITIES DESCRIBED IN THIS MANUAL SHALL BE CARRIED OUT BY A LICENSED TECHNICIAN.
BE SURE TO WEAR ADEQUATE PERSONAL PROTEC­TION EQUIPMENT (PROTECTION GLOVES, SAFETY GLASSES, ...) WHEN PERFORMING INSTALLATION, MAINTENANCE OR SERVICE TO THE UNIT.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.
THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED FOR OUTDOOR INSTALLATION.
The English text is the original instruction. Other languages are translations of the original instructions.

INTRODUCTION

General information

These units are used for both heating and cooling applications. The units can be combined with Daikin fan coil units, floor heating applications, low temperature radiators, domestic hot water tank (option) and solar kit (option).
A remote controller is standard supplied with the unit to control your installation.
Heating/cooling units and heating only units
The monoblock unit range consists of two main versions: a heating/cooling (EB) version and a heating only (ED) version.
Installation manual
1
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures. The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protection of the outside water piping during winter time. The backup heater factory set capacity is 6 kW, however, depending on the installation, the installer can limit the backup heater capacity to 3 kW/2 kW. The backup heater capacity decision is a mode based on the equilibrium temperature, see scheme below.
P
H
3
1
2
4
1 Heat pump capacity 2 Required heating capacity (site dependent) 3 Additional heating capacity provided by the backup heater 4 Equilibrium temperature (can be set through the user interface,
refer to "Field settings" on page 28)
T
Ambient (outdoor) temperature
A
P
Heating capacity
H
T
A
Domestic hot water tank (option) An optional EKHW* domestic hot water tank with integrated
3 kW electrical booster heater can be connected to the indoor unit. The domestic hot water tank is available in three sizes: 150, 200 and 300 litre. Refer to the domestic hot water tank installation manual for further details.
Solar kit for domestic hot water tank (option) For information concerning the EKSOLHW solar kit, refer to the
installation manual of that kit.
Digital I/O PCB kit (option) An optional EKRP1HB digital I/O PCB can be connected to the
indoor unit and allows:
remote alarm output
heating/cooling ON/OFF output
bivalent operation (permission signal for the auxiliary boiler)
Refer to the operation manual of the indoor unit and to the installation manual of the digital I/O PCB for more information.
Refer to the wiring diagram or connection diagram for connecting this PCB to the unit.
Bottom plate heater EKBPHTH16A (option)
Remote thermostat kit (option)
An optional room thermostat EKRTW, EKRTWA, or EKRTR can be connected to the indoor unit. Refer to the installation manual of the room thermostat for more information..
To obtain more information concerning these option kits, please refer to dedicated installation manuals of the kits.
Operation range
Heating mode Cooling mode
A
°C DB
35
0
–15 –20 –25
A Outdoor temperature B Leaving water temperature
No heat pump operation, back up heater only (V3 and W1 models) No heat pump operation, back up heater only (for V3 models only) Operation possible, but no guarantee of capacity (for W1 models only)
(*) - E(D/B)L* units include special equipment (insulation, heater
sheet, ...) to ensure good operation in areas where low ambient temperatures can occur together with high humidity conditions. In such conditions the E(D/B)H* units may experience problems with severe ice build-up on the air-cooled coil. In case such conditions are expected, the E(D/B)L* units must be installed instead.
- Both E(D/B)L* and E(D/B)H* units have a freeze prevention function using the pump and backup heater to keep the water system safe from freezing in all conditions. In case accidental or intentional power shutdown is likely to happen, we recommend to use glycol.
(**) Only for E(D/B)L* units
(*)
(**)
°C51525 40 55
A
°C DB
46
10
B
°C5 22
B
Connection to a benefit kWh rate power supply
This equipment allows for connection to benefit kWh rate power supply delivery systems. Full control of the unit will remain possible only in case the benefit kWh rate power supply is of the type that power supply is not interrupted. Refer to "Connection to a benefit
kWh rate power supply" on page 23 for more details.

Scope of this manual

This installation manual describes the procedures for installing and connecting all EDH, EBH, EDL and EBL outdoor unit models.
Model identification
ED H Q 011 BA 6 V3
Power supply: V3 = 1~, 230 V, 50 Hz W1 = 3N~, 400 V, 50 Hz
Backup heater capacity (kW)
Model changes
Indication of heating capacity (kW)
Refrigerant R410A
H = Low water temperature - ambient zone 3 L = Low water temperature - ambient zone 2
ED = Monoblock outdoor heating only EB = Monoblock outdoor heat pump
(a) For exact values, refer to "Technical specifications" on page 43.
(a)
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
2

ACCESSORIES

Accessories supplied with the unit

12 3 4
1x 1x 2x 1x
1 Installation manual 2 Operation manual 3 Wiring diagram sticker (inside unit cover doors 1 and 2) 4 User interface kit
(digital remote controller, 4 fixing screws and 2 plugs)

SAFETY CONSIDERATIONS

The precautions listed here are divided into the following four types. They all cover very important topics, so be sure to follow them carefully.
Meanings of DANGER, WARNING, CAUTION and NOTE symbols.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE
Indicates situations that may result in equipment or property-damage accidents only.
Danger
Before touching electric terminal parts, turn off power switch.
When service panels are removed, live parts can be easily
touched by accident. Never leave the unit unattended during installation or servicing
when the service panel is removed.
Do not touch water pipes during and immediately after operation as the pipes may be hot. Your hand may suffer burns. To avoid injury, give the piping time to return to normal temperature or be sure to wear proper gloves.
Do not touch any switch with wet fingers. Touching a switch with wet fingers can cause electrical shock.
Before touching electrical parts, turn off all applicable power supply.
Warning
Tear apart and throw away plastic packaging bags so that children will not play with them.
Children playing with plastic bags face danger of death by suffocation.
Safely dispose of packing materials. Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself.
Improper installation may result in water leakage, electric shocks or fire.
Perform installation work in accordance with this installation manual.
Improper installation may lead to water leakage, electric shocks or fire.
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in water leakage, electric shocks, fire, or the unit falling.
Install the unit on a foundation that can withstand its weight.
Insufficient strength may result in the fall of equipment and
causing injury.
Carry out the specified installation work in consideration of strong winds, hurricanes, or earthquakes.
Improper installation work may result in accidents due to fall of equipment.
Make certain that all electrical work is carried out by qualified personnel according to the local laws and regulations and this installation manual, using a separate circuit.
Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire.
Be sure to install a earth leak detector according to local laws and regulations.
Failure to install a earth leak detector may cause electric shocks and fire.
Make sure that all wiring is secure, using the specified wires and ensuring that external forces do not act on the terminal connections or wires.
Incomplete connection or fixing may cause a fire.
When wiring the power supply, form the wires so that the frontside panel can be securely fastened.
If the frontside panel is not in place, overheat of the terminals, electric shocks or a fire may be caused.
After completing the installation work, check to make sure that there is no leakage of refrigerant gas.
Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
Do not touch the internal parts (pump, backup heater, etc.) during and immediately after operation.
Your hands may suffer burns if you touch the internal parts. To avoid injury, give the internal parts time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
.
Installation manual
3
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Caution
For use of units in applications with temperature alarm settings it is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded. The unit may stop for several minutes during normal operation for "defrosting of the unit" or when in "thermostat-stop" operation.
Earth the unit. Earth resistance should be according to local laws and
regulations Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire. Incomplete earthing may cause electric shocks.
Gas pipe.
Ignition or explosion may occur if the gas leaks.
Water pipe.
Hard vinyl tubes are not effective earths.
Lightning conductor or telephone earth wire.
Electric potential may rise abnormally if struck by a lightning bolt.
Install the power wire at least 1 meter away from televisions or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
Do not rinse the unit. This may cause electric shocks or fire.
Do not install the unit in places such as the following:
Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall out or water to leak.
Where corrosive gas, such as sulphurous acid gas, is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
Where there is machinery which emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
Where flammable gases may leak, where carbon fibre or
ignitable dust is suspended in the air or where volatile flammables, such as thinner or gasoline, are handled. Such gases may cause a fire.
Where the air contains high levels of salt such as that near
the ocean.
Where voltage fluctuates a lot, such as that in factories.
In vehicles or vessels.
Where acidic or alkaline vapour is present.

BEFORE INSTALLATION

Installation
Be sure to confirm the model name and the serial no. of the outer (front) plates when attaching/detaching the plates to avoid mistakes.
When closing the service panels, take care that the tightening torque does not exceed 4.1 N•m.
Model
EDL and EBL units include special equipment (insulation, heater sheet,...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the EDH and EBH models may experience problems with severe ice build up on the air-cooled coil. In case such conditions are expected, the EDL or EBL must be installed instead. These models contain countermeasures (insulation, heater sheet,...) to prevent freeze up.
Possible options
Heater sheet Drain socket
EDLQ, EBLQ Standard Use prohibited EDHQ, EBHQ Optional kit
(a) Combination of both options is prohibited.
(a)
Optional kit
(a)
Handling
Due to relatively large dimensions and high weight, the handling of the unit is only to be done by means of lifting tools with slings. These slings can be fitted into specially for this purpose foreseen sleeves at the base frame.
To avoid injury, do not touch the air inlet or aluminium fins of the unit.
Do not use the grips in the fan grills to avoid damage.
Unit is top heavy! Prevent the unit from falling due to inclination during
handling. Centre of gravity is indicated on the unit.
IMPORTANT INFORMATION REGARDING THE
REFRIGERANT USED
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R410A
(1)
GWP
value: 1975
(1)
GWP = global warming potential
The refrigerant quantity is indicated on the unit name plate
Installation manual
4

SELECTING INSTALLATION SITE

Set the outlet side at a right angle to the direction of the wind.
Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
1 Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.
- Places which are well-ventilated.
- Places where the unit does not bother next-door neighbours.
- Safe places which can withstand the unit's weight and vibration and where the unit can be installed level.
- Places where there is no possibility of flammable gas or product leak.
- The equipment is not intended for use in a potentially explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the units' piping and wiring lengths come within the allowable ranges.
- Places where water leaking from the unit cannot cause damage to the location (e.g. in case of a blocked drain pipe).
- Places where the rain can be avoided as much as possible.
- Do not install the unit in places often used as workplace. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
- Do not place any objects or equipment on top of the unit (top plate)
- Do not climb, sit or stand on top of the unit.
- Be sure that sufficient precautions are taken, in accordance with relevant local laws and regulations, in case of refrigerant leakage.
2 When installing the unit in a place exposed to strong wind, pay
special attention to the following. Strong winds of 5 m/sec or more blowing against the unit's air
outlet causes short circuit (suction of discharge air), and this may have the following consequences:
- Deterioration of the operational capacity.
-Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the face of the unit, the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where the wind direction can be foreseen.
Tu rn the air outlet side toward the building's wall, fence or screen.
Strong wind
Blown air Strong wind
3 Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.
4 If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the foundation should be maximum 150 mm).
5 If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction.
6 When installing the unit in a place frequently exposed to snow,
pay special attention to elevate the foundation as high as possible.
7 If you install the unit on a building frame,
please install a waterproof plate (field supply) (within 150 mm) of the underside of the unit) in order to avoid the drainwater dripping. (See figure).

Selecting a location in cold climates

Refer to "Handling" on page 4.
NOTE
To prevent exposure to wind, install the unit with its suction side
Never install the unit at a site where the suction side may be
To prevent exposure to wind, install a baffle plate on the air
In heavy snowfall areas it is very important to select an
When operating the unit in a low outdoor ambient temperature, be sure to follow the instructions described below.
facing the wall.
exposed directly to wind.
discharge side of the unit.
installation site where the snow will not affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is not affected by the snow (if necessary construct a lateral canopy).
Make sure there is enough room to do the installation
Installation manual
5
1 Construct a large canopy. 2 Construct a pedestal.
Install the unit high enough off the ground to prevent burying in snow.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A

PRECAUTIONS ON INSTALLATION

Installation servicing space

Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after installation.
In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four sets of M12 foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are
20 mm from the foundation surface.
AC C
B
240 955 240
1435
A Discharge side B Bottom view mm C Drain hole

Drain work

Check in the combination table under "Possible options" on page 4 whether drain work is allowed. In case drain work on your unit is allowed and the installation site requires drain work, then follow the guidelines below.
Drain kits for drainage are available as option.
If drain work from the unit causes trouble (for example, if the
drain water may splash on people) provide the drain piping using a drain socket (optional).
Make sure the drain works properly.
345
380
The numerical figures used in the figures represent the dimensions in mm.
(Refer to "Precautions on installation" on page 6)
Precaution (A) In case of non-stacked installation figure 1
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
20
Top side obstacle
NOTE
Minimum distance B1 in figure 1 mentions the
Obstacle is present
In these cases, close the
1
bottom of the installation frame to prevent the discharged air from being bypassed
In these cases, only
2
2 units can be installed.
This situation is not allowed
space required for correct operation of the unit. Required space for servicing though is 300 mm.
(B) In case of stacked installation
1. In case obstacles exist in front of the outlet side.
A
100
1000
NOTE
If drain holes of the unit are covered by a mounting base or by floor surface, raise the unit in order to provide a free space of more than 100 mm under the unit.
100 mm

Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown in the figure.
prepare all 4 wires as indicated in the drawing
unscrew the top plate at the 4 locations indicated A and B
put the screws through the nooses and screw them back tight
AA
B
C
2. In case obstacles exist in front of the air inlet.
A
100
300
Do not stack more than one unit. About 100 mm is required as the dimension for laying the upper unit's
drain pipe. Get the portion A sealed so that air from the outlet does not bypass.
A Location of the 2 fixation holes on the front side of the unit B Location of the 2 fixation holes on the rear side of the unit C Wires: field supply
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
6
(C) In case of multiple-row installation (for roof top use, etc.)
1. In case of installing one unit per row.
100
2000
200
1000
2. In case of installing multiple units (2 units or more) in lateral connection per row.
L
A
3000
H
600
1500
Relation of dimensions of H, A and L are shown in the table below.
L A
LH
H<L Installation not allowed
0<L1/2H 250 1/2H<L 300

TYPICAL APPLICATION EXAMPLES

The application examples given below are for illustration purposes only.

Application 1

Space heating only application with a room thermostat connected to the unit.
I
T
4321
1 Unit FHL1..3 Floor heating loop 2 Heat exchanger 3 Pump T Room thermostat 4 Shut-off valve 5 Collector (field supply) I User interface
5
FHL1
FHL2
FHL3
(field supply)
(optional)
Unit operation and space heating
When a room thermostat (T) is connected to the unit and when there is a heating request from the room thermostat, the unit will start operating to achieve the target leaving water temperature as set on the user interface.
When the room temperature is above the thermostat set point, the unit will stop operating.
Make sure to connect the thermostat wires to the correct terminals (see "Connection of the thermostat cable" on
page 22) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
on page 25).
Installation manual
7
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A

Application 2

Space heating only application without room thermostat connected to the unit. The temperature in each room is controlled by a valve on each water circuit. Domestic hot water is provided through the domestic hot water tank which is connected to the unit.
I
Domestic water heating
When domestic water heating mode is enabled (either manually by the user, or automatically through a schedule timer) the target domestic hot water temperature will be achieved by a combination of the heat exchanger coil and the electrical booster heater.
When the domestic hot water temperature is below the user configured set point, the 3-way valve will be activated to heat the domestic water by means of the heat pump. In case of large domestic hot water demand or a high domestic hot water temperature setting, the booster heater (8) can provide auxiliary heating.
43 721
1 Unit 9 Heat exchanger coil 2 Heat exchanger 10 Domestic hot water tank 3 Pump 4 Shut-off valve FHL1..3 Floor heating loop 5 Collector (field supply) 6 Motorised 3-way valve
(optional)
7 By-pass valve
(field supply)
8 Booster heater
6
M
T1..3 Individual room
M1..3 Individual motorised
5
T1
M1
M2T2M3
98
FHL1
FHL2
10
(optional)
(field supply)
thermostat (field supply)
valve to control loop FHL1 (field supply)
I User interface
T3
FHL3
Pump operation
With no thermostat connected to the unit (1), the pump (3) can be configured to operate either as long as the unit is on, or until the required water temperature is reached.
It is possible to connect either a 2-wire or a 3-wire 3-way valve (6). Make sure to fit the 3-way valve correctly. For more details, refer to "Wiring the 3-way valve" on page 23.
NOTE
The unit can be configured so that at low outdoor temperatures the domestic water is exclusively heated by the booster heater. This assures that the full capacity of the heat pump is available for space heating.
Details on domestic hot water tank configuration for low outdoor temperatures can be found under "Field
settings" on page 28, field settings [5-02] to [5-04].

Application 3

Space cooling and heating application with a room thermostat suitable for heating/cooling changeover connected to the unit.
Heating is provided through floor heating loops and fan coil units. Cooling is provided through the fan coil units only. Domestic hot water is provided through the domestic hot water tank which is connected to the unit.
5
I
T
4321
6 11
M
FCU1
FCU2
M
FCU3
NOTE
Details on pump configuration can be found under
"Pump operation configuration" on page 26.
Space heating
The unit (1) will operate to achieve the target leaving water temperature as set on the user interface.
When circulation in each space heating loop (FHL1..3) is controlled by remotely controlled valves (M1..3), it is important to provide a by-pass valve (7) to avoid the flow switch safety device from being activated.
The by-pass valve should be selected as such that at all time the minimum water flow as mentioned under "Water
pipework" on page 14 is guaranteed.
It is recommended to select a pressure difference controlled by-pass valve.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
98
FHL1
FHL2
FHL3
10
1 Unit 10 Domestic hot water tank 2 Heat exchanger 11 Motorised 2-way valve 3 Pump 4 Shut-off valve FCU1..3 Fan coil unit (field supply) 5 Collector (field supply) FHL1..3 Floor heating loop 6 Motorised 3-way valve
(optional) T Room thermostat with 8 Booster heater 9 Heat exchanger coil
(field supply)
(field supply)
heating/cooling switch (optional)
I User interface
Installation manual
8
Pump operation and space heating and cooling
According to the season, the customer will select cooling or heating on the room thermostat (T). This selection is not possible by operating the user interface.
When space heating/cooling is requested by the room thermostat (T), the pump will start operating and the unit (1) will switch to "heating mode"/"cooling mode". The unit (1) will start operating to achieve the target leaving cold/hot water temperature.
In case of cooling mode, the motorised 2-way valve (11) will close as to prevent cold water running through the floor heating loops (FHL).
Make sure to connect the thermostat wires to the correct terminals (see "Connection of the thermostat cable" on
page 22) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
on page 25).
Wiring of the 2-way valve (11) is different for a NC (normal closed) valve and a NO (normal open) valve! Make sure to connect to the correct terminal numbers as detailed on the wiring diagram.
The ON/OFF setting of the heating/cooling operation is done by the room thermostat and cannot be done by the user interface.
Domestic water heating
Domestic water heating is as described under "Application 2" on
page 8.

Application 4

Space cooling and heating application without a room thermostat connected to the unit, but with a heating only room thermostat
controlling the floor heating and a heating/cooling thermostat controlling the fan coil units. Heating is provided through floor heating loops and fan coil units. Cooling is provided through the fan coil units only.
5
I
T4 T5 T6
4321 12
1 Unit 12 Motorised 2-way valve for 2 Heat exchanger
3 Pump FCU1..3 Fan coil unit with 4 Shut-off valve 5 Collector (field supply) FHL1..3 Floor heating loop (field 7 By-pass valve (field
supply) T Heating only room
11 Motorised 2-way valve
to shut off the floor heating loops during cooling operation (field supply)
11
FCU1
T
M
M
T4..6 Individual room
I User interface
FCU2
5
FHL1
FHL2
activation of the room thermostat (field supply)
thermostat (field supply)
supply)
thermostat (optional)
thermostat for fan coil heated/cooled room (optional)
FCU3
FHL3
Pump operation
With no thermostat connected to the unit (1), the pump (3) can be configured to operate either as long as the unit is on, or until the required water temperature is reached.
NOTE
Details on pump configuration can be found under
"Pump operation configuration" on page 26.
Space heating and cooling
According to the season, the customer will select cooling or heating through the user interface.
The unit (1) will operate in cooling mode or heating mode to achieve the target leaving water temperature.
With the unit in heating mode, the 2-way valve (11) is open. Hot water is provided to both the fan coil units and the floor heating loops.
With the unit in cooling mode, the motorised 2-way valve (11) is closed to prevent cold water running through the floor heating loops (FHL).
When closing several loops in the system by remotely controlled valves, it might be required to install a by-pass valve (7) to avoid the flow switch safety device from being activated. See also "Application 2" on page 8.
Wiring of the 2-way valve (11) is different for a NC (normal closed) valve and a NO (normal open) valve! Make sure to connect to the correct terminal numbers as detailed on the wiring diagram.
The ON/OFF setting of the heating/cooling operation is done by the user interface.

Application 5

Space heating with an auxiliary boiler (alternating operation)
7
Space heating application by either the Daikin unit or by an auxiliary boiler connected in the system. The decision whether either the E(D/B)* unit or the boiler will operate can be achieved by an auxiliary contact or an E(D/B)* indoor controlled contact.
The auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. See
"Field wiring configuration A" on page 10.
The E(D/B)* unit controlled contact (also called 'permission signal for the auxiliary boiler") is determined by the outdoor temperature (thermistor located at the outdoor unit). See "Field wiring
configuration B" on page 10.
Bivalent operation is only possible for space heating operation, not for the domestic water heating operation. Domestic hot water in such an application is always provided by the domestic hot water tank which is connected to the Daikin unit.
The auxiliary boiler must be integrated in the piping work and in the field wiring according to the illustrations below.
Installation manual
9
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
CAUTION
Be sure that the boiler and the integration of the boiler in the system is in accordance with relevant local laws and regulations.
Always install a 3-way valve, even if no domestic hot water tank is installed. This to ensure that the freeze protection function (see "[4-04] Freeze protection
function" on page 31) can operate when the boiler is
active.
I
1
M
2
FHL1 FHL2 FHL3
1 Motorised 3-way valve 2 Boiler
Daikin can not be put responsible for incorrect or unsafe situations in the boiler system.
I
6 18
4321
517
Field wiring configuration A
L
Com
H
E(D/B)*/auto
Boiler
/ Boiler
N
A
K1A
K2A
Boiler thermostat input
K1A
E(D/B)*
X2M
123 4
Boiler
thermostat input
Y
X
K2A
thermostat input A Auxiliary contact (normal closed) H Heating demand room thermostat (optional) K1A Auxiliary relay for activation of E(D/B)* unit (field
supply)
K2A Auxiliary relay for activation of boiler (field supply)
Field wiring configuration B
E(D/B)*
X2M
12
3 4
K1A
Com
H
C
EKRTW*
Boiler thermostat input
C Cooling demand room thermostat (optional) H Heating demand room thermostat (optional) Com Common room thermostat (optional) K1A Auxiliary relay for activation of boiler unit
KCR Permission signal for the auxiliary boiler
EKRP1HB
KCR
X1 X2
K1A
X Y
Boiler
thermostat input
Boiler thermostat input
(field supply)
M
15
17
16
10
11
FHL1
FHL2
12
1 Outdoor unit 12 Domestic hot water 2 Heat exchanger
tank (optional)
3 Pump 15 Boiler (field supply) 4 Shut-off valve 16 Aquastat valve 5 Collector (field supply) 6 Motorised 3-way valve
(delivered with the domestic hot water tank)
(field supply)
17 Shut-off valve
(field supply)
18 Non-return valve
(field supply)10 Booster heater
11 Heat exchanger coil FHL1...3 Floor heating loop
(field supply)
Operation
Configuration A
When the room thermostat requests heating, either the E(D/B)* unit or the boiler starts operating, depending on the position of the auxiliary contact (A).
Configuration B
When the room thermostat requests heating, either the E(D/B)* unit or the boiler starts operating, depending on the outdoor temperature (status of "permission signal for the auxiliary boiler").
When the permission is given towards the boiler, the space heating operation by the E(D/B)* unit will be automatically switched off.
For more details see field setting [C-02~C-04].
FHL3
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
10
NOTE
Configuration A
Make sure that auxiliary contact (A) has sufficient differential or time delay so as to avoid frequent changeover between the E(D/B)* unit and the boiler. If the auxiliary contact (A) is an outdoor temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun.
Configuration B
Make sure that the bivalent hysteresis [C-04] has sufficient differential to avoid frequent changeover between the E(D/B)* unit and the boiler. As the outdoor temperature is measured via the outdoor unit, air thermistor make sure to install the outdoor unit in the shade, so that it is not influenced by the sun.
Frequent switching may cause corrosion of the boiler in an early stage. Contact the manufacturer of the boiler.
During heating operation of the E(D/B)* unit, the unit will operate so as to achieve the target leaving water temperature as set on the user interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature.
During heating operation of the boiler, the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller.
Never set the target leaving water temperature set point on the boiler controller above 55°C.
Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already premounted in the Daikin unit.

Application 6

Space heating with room thermostat application through floor heating loops and fan coil units. The floor heating loops and fan coil units require different operating water temperatures.
The floor heating loops require a lower water temperature in heating mode compared to fan coil units. To achive these two set points, a mixing station is used to adapt the water temperature according to requirements of the floor heating loops. The fan coil units are directly connected to the unit water circuit and the floor heating loops after the mixing station. The control of this mixing station is not done by the unit.
The operation and configuration of the field water circuit is the responsibility of the installer.
Daikin only offers a dual set point control function. By this function two set points can be generated. Depending on the required water temperature (floor heating loops and/or fan coil units are required) first set point or second set point can be activated.
T1
T2
4321
B
A
FCU1
6
5
FCU2
FCU3
NOTE
Make sure to configure the DIP switch SS2-3 on the PCB of the E(D/B)* switch box correctly. Refer to
"Room thermostat installation configuration" on page 25.
For configuration B: Make sure to configure the field settings [C-02, C-03 and C-04] correctly. Refer to
"Bivalent operation" on page 35.
CAUTION
Make sure that return water to the E(D/B)* heat exchanger never exceeds 55°C.
For this reason, never put the target leaving water temperature set point on the boiler controller above 55°C and install an aquastat
(a)
valve in the return water flow of
the E(D/B)* unit. Make sure that the non-return valves (field supply) are
correctly installed in the system. Make sure that the room thermostat (th) is not frequently
turned ON/OFF. Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
(a) The aquastat valve must be set for 55°C and must operate to close the return
water flow to the unit when the measured temperature exceeds 55°C. When the temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)* unit again.
Manual permission towards the E(D/B)* unit on the boiler. In case only the E(D/B)* unit should operate in space
heating mode, disable the bivalent operation via setting [C-02].
In case only the boiler should operate in space heating mode, increase the bivalent ON temperature [C-03] to 25°C.
7
1 Outdoor unit 7 Mixing station (field supply) 2 Heat exchanger T1 Room thermostat for zone 3 Pump 4 Shut-off valve T2 Room thermostat for zone 5 Collector zone A
(field supply) FCU1..3 Fan coil unit (optional)
6 Collector zone B
(field supply)
FHL1...3 Floor heating loop
FHL1
FHL2
FHL3
A (optional)
B (optional)
(field supply)
The advantage of the dual set point control is that the heat pump will/can operate at the lowest required leaving water temperature when only floor heating is required. Higher leaving water temperatures are only required in case fan coil units are operating. This results in a better performance of the heat pump.
Pump operation and space heating
When the room thermostat for the floor heating loop (T1) and the fan coil units (T2) are connected to the indoor unit, the pump (4) will operate when there is a request for heating from T1 and/or T2. The outdoor unit will start operating to achieve the target leaving water temperature. The target leaving water temperature depends on which room thermostat is requesting heating.
Set point Field setting Thermo status
Zone A First UI ON OFF ON OFF Zone B Second [7-03] OFF ON ON OFF Resulting water temperature UI [7-03] [7-03] — Result pump operation ON ON ON OFF
Installation manual
11
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
When the room temperature of both zones is above the thermostat set point, the outdoor unit and pump will stop operating.

Main components

NOTE
NOTE
Make sure to connect the thermostat wires to the
correct terminals (see "Overview of the unit" on
page 12).
Make sure to configure the field settings [7-02],
[7-03] and [7-04] correctly. Refer to "Dual set point
control" on page 33.
Make sure to configure the DIP switch SS2-3 on
the PCB of the E(D/B)* switch box correctly. Refer to "Room thermostat installation configuration" on
page 25.
The request signals for space heating can be
implemented in two different ways (installer choice).
- Thermo ON/OFF signal from room thermostat
- Status signal (active/not active) from the mixing station
It is the installers responsibility to make sure no unwanted situations can occur (e.g. too high water temperatures towards floor heating loops, etc.)
Daikin does not offer any type of mixing station. Dual set point control only provides the possibility to use two set points.
When only zone A request heating, zone B will be fed with water at a temperature equal to the first set point. This can lead to unwanted heating of zone B.
When only zone B request heating, the mixing station will be fed with water at a temperature equal to the second set point. Depending on the control of the mixing station, the floor heating loop can still receive water at a temperature equal to set point of the mixing station.
Be aware that the actual water temperature through the floor heating loops depends on the control and setting of the mixing station.

OVERVIEW OF THE UNIT

Opening the unit

22
1
3
Door 1 gives access to the compressor compartment and electrical parts Door 2 gives access to the electrical parts of the hydraulic compartment Door 3 gives access to the hydraulic compartment
Switch off all power supply — i.e. unit power supply and backup heater and domestic hot water tank power supply (if applicable) — before removing doors 1 and 2.
Parts inside the unit can be hot.
Hydraulic compartment (door 3)
1
18 13
17 16
15
8
10
3
9 8
14 12
3
11
1. Air purge valve
Remaining air in the water circuit will be automatically removed via the air purge valve.
2. Backup heater The backup heater consists of an electrical heating element that
will provide additional heating capacity to the water circuit if the heating capacity of the unit is insufficient due to low outdoor temperatures, it also protects the external water piping from freezing during cold periods.
3. Temperature sensors Four temperature sensors determine the water and refrigerant
temperature at various points in the water circuit.
4. Heat exchanger
5. Expansion vessel (10 l)
6. Refrigerant liquid connection
7. Refrigerant gas connection
8. Shut-off valves
The shut-off valves on the water inlet connection and water outlet connection allow isolation of the unit water circuit side from the residential water circuit side. This facilitates draining and filter replacement of the unit.
9. Water inlet connection
10. Water outlet connection
11. Drain and fill valve
12. Water filter
The water filter removes dirt from the water to prevent damage to the pump or blockage of the evaporator. The water filter must be cleaned on a regular base. See "Maintenance and service"
on page 40.
13. Manometer The manometer allows readout of the water pressure in the
water circuit.
3PW55762-1
2
3
4
5
7 6 3
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
12
14. Flow switch
O
>
3T
>
t >
t >
The flow switch checks the flow in the water circuit and protects the heat exchanger against freezing and the pump against damage.
15. Pump The pump circulates the water in the water circuit.
16. Backup heater thermal protector The backup heater is equipped with a thermal protector. The
thermal protector is activated when the temperature becomes too high.
17. Backup heater thermal fuse The backup heater is equipped with a thermal fuse. The thermal
fuse is blown when the temperature becomes too high (higher than the backup heater thermal protector temperature).
18. Pressure relief valve The pressure relief valve prevents excessive water pressure in
the water circuit by opening at 3 bar and discharging some water.
Functional diagram of hydraulic compartment (door 3)
12 6 7
34 5
Switch box main components (door 2)
ABDC
AC
9
9 8
B
15
3 1
24
1
5 4 2
14 FU2 10 FU1
16
17 12
X13A SS2
11
13 X9A
t
R1
t
1289 1011
1 Expansion vessel 8 Heat exchanger 2 Manometer 9 Flow switch 3 Air purge valve 10 Drain/fill valve 4 Pressure relief valve 11 Filter 5 Backup heater vessel
with backup heater
6 Pump R11T 7 Shut-off valve water
outlet
12 Shut-off valve water inlet with
drain valve
R12T
Temperature sensors
R13T R14T
D
8
23
25
6 7
18 19
8
1. Backup heater contactors K1M and K5M
2. Main PCB
The main PCB (Printed Circuit Board) controls the functioning of the unit.
3. Booster heater contactor K3M (only for installations with domestic hot water tank)
4. Booster heater circuit breaker F2B (only for installations with domestic hot water tank)
The circuit breaker protects the booster heater in the domestic
hot
water tank against overload or short circuit.
5. Backup heater circuit breaker F1B The circuit breaker protects the backup heater electrical circuit
against overload or short circuit.
6. Te r minal blocks The terminal blocks allow easy connection of field wiring.
7. Te r minal block for backup heater capacity limitation.
8. Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable ties to the switch box to ensure strain relief.
9. Te r minal blocks X3M, X4M (only for installations with domestic hot water tank)
10. PCB fuse FU1
11. DIP switch SS2
The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters. See "DIP switch settings
overview" on page 25.
12. X13A socket The X13A socket receives the K3M connector (only for
installations with domestic hot water tank).
6
8 21
20 22
Installation manual
13
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
13. X9A socket The X9A socket receives the thermistor connector (only for
installations with domestic hot water tank).
14. Pump fuse FU2 (in line fuse)
15. Pump relay K4M
16. Tr ansformer TR1 for PCB power supply
17. A4P digital I/O PCB (only for installations with solar kit or digital
I/O PCB)
18. Conduit hole to pass through the booster heater power supply cable.
19. Conduit hole to pass through the booster heater power supply cable and the thermal protection cable.
20. Conduit hole to pass through the room thermostat cable and 2-way valve and 3-way valve control cables.
21. Conduit hole to pass through the thermistor cable and user interface cable (and benefit kWh rate cable).
22. Conduit hole to pass through the backup heater power supply wiring.
23. Conduit hole to pass through optional I/O PCB connection wiring.
24. K7A relay for solar pump (optional) This relay and its output on X2M can be activated when the solar
input on A4P becomes active.
25. Te r minal for expansion vessel heater and, only for EDL and EBL units, plate heat exchanger heater and switch box heater.
NOTE
The electrical wiring diagram can be found on the inside of the switch box cover.

Water pipework

All piping lengths and distances have been taken into consideration.
Requirement Value
Maximum allowable distance between the domestic hot water tank and the unit (only for installations with domestic hot water tank). The thermistor cable supplied with the domestic hot water tank is 12 m in length. In order to optimise efficiency Daikin recommends to install the 3-way valve and the domestic hot water tank as close as possible to the unit.
NOTE
If the installation is equipped with a domestic hot water tank (optional), please refer to the domestic hot water tank installation manual.
10 m
Checking the water circuit
The units are equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by a licensed technician and must comply with local laws and regulations.
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
Before continuing the installation of the unit, check the following points:
The maximum water pressure = 3 bar + static pressure of pump.
The maximum water temperature is 65°C according to safety
device setting.
Always use materials which are compatible with the water used in the system and with the materials used in the unit.
Ta ke care that the components installed in the field piping can withstand the water pressure and temperature.
Drain taps must be provided at all low points of the system to permit complete drainage of the circuit during maintenance.
A drain valve is provided in the unit to drain the water from the unit water system.
Air vents must be provided at all high points of the system. The vents should be located at points which are easily accessible for servicing. An automatic air purge is provided inside the unit. Check that this air purge valve is not tightened too much so that automatic release of air in the water circuit remains possible.
Select piping diameter in relation to required water flow and available ESP of the pump.
The minimum required water flow for the unit operation is 16 l/min. When the water flow is lower than this minimum value, flow error 7H will be displayed and the operation of the indoor unit will be stopped.
Checking the water volume and expansion vessel pre-pressure
The unit is equipped with an expansion vessel of 10 litre which has a default pre-pressure of 1 bar.
To assure proper operation of the unit, the pre-pressure of the expansion vessel might need to be adjusted and the minimum and maximum water volume must be checked.
1 Check that the total water volume in the installation, excluding
the internal water volume of the unit, is 20 l minimum. Refer to
"Technical specifications" on page 43 to know the internal water
volume of the unit.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
In most applications this minimum water volume will have a satisfying result.
In critical processes or in rooms with a high heat load though, extra water volume might be required.
Installation manual
14
NOTE
When circulation in each space heating loop is controlled by remotely controlled valves, it is important that this minimum water volume is kept even if all the valves are closed.
Example
321 5
I
4
T1
M1
T3
M2T2M3
6
Checking the maximum allowed water volume
To determine the maximum allowed water volume in the entire circuit, proceed as follows:
1 Determine for the calculated pre-pressure (Pg) the
corresponding maximum water volume using the graph below.
2 Check that the total water volume in the entire water circuit is
lower than this value.
If this is not the case, the expansion vessel inside the unit is too small for the installation.
[bar]
2.5
2
1.5
figure "Maximum allowed water volume"
FHL1
FHL2
FHL3
1 Unit FHL1..3 Floor heating loop 2 Heat exchanger 3 Pump T1..3 Individual room 4 Shut-off valve 5 Collector (field
supply)
6 By-pass valve
(field supply)
(field supply)
thermostat (optional)
M1..3 Individual motorised
valve to control loop FHL1 (field supply)
I User interface
2 Using the table below, determine if the expansion vessel pre-
pressure requires adjustment.
3 Using the table and instructions below, determine if the total
water volume in the installation is below the maximum allowed water volume.
Installation height difference
7 m
>7 m
Water volume
(a)
280 l
No pre-pressure adjustment required.
Actions required:
• pre-pressure must be increased, calculate according to "Calculating
the pre-pressure of the expansion vessel"
• check if the water volume is lower than maximum allowed water volume (use graph below)
(a) Installation height difference: height difference (ft)(m) between the highest point
of the water circuit and the unit. If the unit is located at the highest point of the installation, the installation height is considered 0 m.
>280 l
Actions required:
• pre-pressure must be decreased, calculate according to "Calculating
the pre-pressure of the expansion vessel"
• check if the water volume is lower than maximum allowed water volume (use graph below)
Expansion vessel of the unit too small for the installation.
Calculating the pre-pressure of the expansion vessel
The pre-pressure (Pg) to be set depends on the maximum installation height difference (H) and is calculated as below:
=(H
Pg
(bar)
/10+0.3) bar
(m)
1
pre-pressure
0.5
0.3
(Refer to "Caution: "Use of glycol"" on page 16)
100500 20 150 200 250 300 350 400 450
maximum water volume
A = System without glycol B = System with 25% propylene glycol
B A
[l]
= pre-pressure = maximum water volume
Example 1
The unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100 l.
In this example, no action or adjustment is required.
Example 2
The unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 350 l.
Result:
Since 350 l is higher than 280 l, the pre-pressure must be decreased (see table above).
The required pre-pressure is:
= (H
Pg
(bar)
/10+0.3) bar = (0/10+0.3) bar = 0.3 bar
(m)
The corresponding maximum water volume can be read from the graph: approximately 410 l.
Since the total water volume (350 l) is below the maximum water volume (410 l), the expansion vessel suffices for the installation.
Setting the pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of the expansion vessel (1 bar), keep in mind the following guidelines:
Use only dry nitrogen to set the expansion vessel pre-pressure.
Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Therefore, the pre-pressure should only be adjusted by a licensed installer.
Installation manual
15
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Connecting the water circuit
Water connections must be made in accordance with local regulations and the outlook diagram delivered with the unit, respecting the water in- and outlet.
Be careful not to deform the unit piping by using excessive force when connecting the piping. Deformation of the piping can cause the unit to malfunction.
If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit:
Use clean pipes only.
Hold the pipe end downwards when removing burrs.
Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.
Use a good thread sealant for the sealing of the connections. The sealing must be able to withstand the pressures and temperatures of the system.
When using non-brass metallic piping, make sure to insulate both materials from each other to prevent galvanic corrosion.
Because brass is a soft material, use appropriate tooling for connecting the water circuit. Inappropriate tooling will cause damage to the pipes.
NOTE
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
Never use Zn-coated parts in the water circuit. Excessive corrosion of these parts may occur as copper piping is used in the unit's internal water circuit.
When using a 3-way valve in the water circuit. Preferably choose a ball type 3-way valve to
guarantee full separation between domestic hot water and floor heating water circuit.
When using a 3-way valve or a 2-way valve in the water circuit.
The recommended maximum changeover time of the valve should be less than 60 seconds.
Protecting the water circuit against freezing
Frost can cause damage to the hydraulic system. As this unit is installed outdoors and thus the hydraulic system is exposed to freezing temperatures, care must be taken to prevent freezing of the system.
All hydraulic parts are insulated to reduce heat loss. Insulation must be foreseen on the field piping.
The unit is already equipped with several features to prevent freezing.
The software contains special functions using pump and back up heater to protect the complete system against freezing.
This function will only be active when the unit is off.
Only for EDL and EBL units: As extra safety, a heatertape is winded around the piping to protect vital parts of the hydraulic system inside the unit.
This heatertape will only be active in case of an abnormal situation concerning the pump and will only protect internal parts of the unit. It can not protect field installed parts outside the unit.
Field heater tape must be foreseen by the installer.
However in case of power failure, above mentioned features can not protect the unit from freezing.
If power failure can happen at times the unit is unattended, Daikin recommends adding glycol to the water system. Refer to Caution:
"Use of glycol" on page 16.
Refer to "[4-04] Freeze protection function" on page 31. Depending on the expected lowest outdoor temperature, make sure
the water system is filled with a weight concentration of glycol as mentioned in the table below.
Minimum outdoor temperature Glycol
–5°C 10% –10°C 15% –15°C 20% –20°C 25% –25°C 30%
(a)(b)(c)
WARNING
(a)
ETHYLENE GLYCOL IS TOXIC
(b)
The concentrations mentioned in the table above will not prevent the medium from freezing, but prevent the hydraulics from bursting.
(c)
The maximum allowed water volume is then reduced according to the figure "Maximum allowed water
volume" on page 15.
Caution: "Use of glycol"
Caution: Use of glycol
For installations with a domestic hot water tank, the use of propylene glycol, including necessary inhibitors, is only allowed if classified as Category 3 according to EN1717 or equivalent based on national regulations.
In case of over-pressure when using glycol, be sure to connect the safety valve to a drain pan in order to recover the glycol.
For this purpose a knock out hole is foreseen in the backplate of the unit making it possible to connect a drain pipe to the safety valve.
Connecting a drain pipe is not required if no glycol is used. The discharged water is then drained via the bottom of the unit.
Corrosion of the system due to presence of glycol
Uninhibited glycol will turn acidic under the influence of oxygen. This process is accelerated by presence of copper and at higher temperatures. The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe damage to the system.
It is therefore of extreme importance:
that the water treatment is correctly executed by a qualified water specialist;
that a glycol with corrosion inhibitors is selected to counteract acids formed by the oxidation of glycols;
that in case of an installation with a domestic hot water tank, only the use of propylene glycol, including necessary inhibitors classified as Category 3 according to EN1717 or equivalent based on national regulations is allowed. In other installations the use of ethylene glycol is permitted as well;
that no automotive glycol is used because their corrosion inhibitors have a limited lifetime and contain silicates which can foul or plug the system;
that galvanized piping is not used in glycol systems since its presence may lead to the precipitation of certain components in the glycol’s corrosion inhibitor;
that it has to be made sure the glycol is compatible with the used materials in the system.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
16
NOTE
Also refer to "Checks before initial start-up" on page 27.
Be aware of the hygroscopic property of glycol: it absorbs moisture from its environment.
Leaving the cap off the glycol container causes the concentration of water to increase. The glycol concentration is then lower than assumed. And in consequence, freezing can happen after all.
Preventive actions must be taken to ensure minimal exposure of the glycol to air.

Charging water

1 Connect the water supply to a drain and fill valve (see "Main
components" on page 12).
2 Make sure the automatic air purge valve is open (at least 2
turns).
3 Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge valves. Air present in the water circuit might cause malfunctioning of the backup heater.
4 Check that the backup heater vessel is filled with water by
opening the pressure relief valve. Water must flow out of the valve.
NOTE
During filling, it might not be possible to remove all air in the system. Remaining air will be removed through the automatic air purge valves during first operating hours of the system. Additional filling with water afterwards might be required.
The water pressure indicated on the manometer will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure should remain above 1 bar to avoid air entering the circuit.
The unit might dispose some excessive water through the pressure relief valve.
Water quality must be according to EN directive 98/83 EC.
If no glycol is in the system in case of a power supply failure or pump operating failure, drain the system (as suggested in the figure below).
A
When water is at standstill inside the system, freezing is very likely to happen and damaging the system in the process.
<A

Piping insulation

The complete water circuit, inclusive all piping, must be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity as well as prevention of freezing of the outside water piping during winter time. The thickness of the sealing materials must be at least 13 mm with 0.039 W/mK in order to prevent freezing on the outside water piping.
If the temperature is higher than 30°C and the humidity is higher than RH 80%, then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing.

Field wiring

WARNING
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with relevant local laws and regulations.
Switch off the power supply before making any connections.
Use only copper wires.
For W1
Make sure to connect power supply cables in normal phase. If connected in reverse phase, the remote controller of the indoor unit indicates " equipment cannot operate. Change any two of the three power supply cables (L1, L2, L3) to correct phase.
Never squeeze bundled cables and make sure that it does not come in contact with the piping and sharp edges.
Make sure no external pressure is applied to the terminal connections.
All field wiring and components must be installed by a licensed electrician and must comply with relevant local laws and regulations.
The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below.
Be sure to use a dedicated power supply. Never use a power supply shared by another appliance.
Be sure to establish an earth. Do not earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
Be sure to install the required fuses or circuit
DANGER
Be sure to install an earth leakage circuit breaker in accordance with relevant local and national regulations. Failure to do so may cause electrical shock.
breakers.
U1
" and the
Installation manual
17
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Precautions on electrical wiring work
Fix cables so that cables do not make contact with the pipes (especially on high pressure side).
Secure the electrical wiring with cable ties as shown in figure 2 so that it does not come in contact with the piping, particularly on the high-pressure side.
Make sure no external pressure is applied to the terminal connectors.
When installing the earth leak detector make sure that it is compatible with the inverter (resistant to high frequency electrical noise) to avoid unnecessary opening of the earth leak detector.
NOTE
The earth leak detector must be a high-speed type breaker of 30 mA (<0.1 s).
As this unit is equipped with an inverter, installing a phase advancing capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating accident due to high-frequency waves. Therefore, never install a phase advancing capacitor.
Overview
The illustration below gives an overview of the required field wiring between several parts of the installation. Refer also to "Typical
application examples" on page 7.
E
I
5
B
C D
3
1
2
A1011
A Single power supply for
unit, backup heater and booster heater
B Unit H 2-way valve for cooling C Bottom plate heater
D Backup heater J Domestic hot water tank E User interface F Room thermostat (field
(a) Bottom plate heater is only applicable in combination with ERLQ or in case of
optional EKBPHT kit.
(a)
EKBPHT
supply, optional)
4
F
T
6
G
M
7
H
M
J
K
8
9
G 3-way valve for domestic
hot water tank (field supply, optional)
mode (field supply, optional)
(optional)
K Booster heater
(optional)
Required number of
AC/
conductors
Item Description
1 Pow er supply cable for unit AC 2+GND 2 Pow er supply cable for backup
heater
3 Pow er cable for bottom plate
heater
4 Room thermostat cable AC 3 or 4 100 mA 5 User interface cable DC 2 100 mA 6 3-way valve control cable AC 2+GND 100 mA 7 2-way valve control cable AC 2+GND 100 mA 8 Booster heater power supply
and thermal protection cable
9 Thermistor cable DC 2
10 Booster heater power supply
cable
11 Benefit kWh rate power supply
cable (voltage free contact)
(a) Refer to nameplate on outdoor unit (b) See table under "Connection of the backup heater power supply" on page 21. (c) Minimum cable section 1.5 mm (d) Minimum cable section 0.75 mm (e) Cable section 0.75 mm2 till 1.25 mm2, maximum length: 500 m. (f) The thermistor and connection wire (12 m) are delivered with the domestic hot
water tank.
(g) Cable section 0.75 till 1.25 mm2, maximum length: 500 m. Voltage free contact
shall ensure the minimum applicable load of 15 V DC, 10 mA.
2
DC
AC 2+GND
AC 2
AC 4+GND
AC 2+GND 13 A
DC 2 100 mA
2
2
1 Protection cap 2 Entry for power cables 3 Entry for low voltage cables
entry (<30 V)
1 3
CAUTION
Select all cables and wire sizes in accordance with relevant local laws and regulations.
WARNING
After finishing the electric work, confirm that each electric part and terminal inside the electric parts box is connected securely.
Maximum running current
(a)
(b)
(c)
(b)
(f)
(d)
(e)
(d)
(d)
(g)
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
18
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit (on the inside of the switch box cover). The abbreviations used are listed below.
Door 1 compressor compartment and electrical parts
A1P ................. Main PCB
A2P ................. Inverter PCB
A3P ................. Noise filter PCB
A4P ................. PCB (only for V3 models)
BS1~BS4......... Push button switch
C1~C4............. Capacitor
DS1 .................DIP switch
E1H .................Bottom plate heater
E1HC............... Crankcase heater
F1U,F2U.......... Fuse (31.5 A/250 V) (only for W1 models)
F1U,F3U,F4U.. Fuse (T 6.3 A/250 V) (only for V3 models)
F3U~F6U......... Fuse (T 6.3 A/250 V) (only for W1 models)
F6U ................. Fuse (T 5.0 A/250 V) (only for V3 models)
F7U ................. Fuse (T 5.0 A/250 V) (only for W1models)
F7U,F8U.......... Fuse (F 1.0 A/250 V) (only for V3 models)
F8U,F9U.......... Fuse (F 1.0 A/250 V) (only for W1 models)
H1P~H7P ........ Orange LED service monitor
(A1P only for W1 models, A2P only for V3 models) H2P: prepare, test = flickering
H2P: malfunction detection = light up
HAP (A1P)....... Green LED service monitor
HAP (A2P)....... Green LED service monitor (only for W1 models)
K1M,K2M ........ Magnetic contactor (only for W1 models)
K1R .................Magnetic relay (Y1S) (only for V3 models)
K1R (A1P) ....... Magnetic relay (Y1S) (only for W1 models)
K1R (A2P) ....... Magnetic relay (only forW1 models)
K2R (A1P) ....... Magnetic relay (Y2S) (only for W1 models)
K3R (A1P) ....... Magnetic relay (E1HC) (only for W1 models)
K4R .................Magnetic relay (E1HC) (only for V3 models)
K10R,K11R .....Magnetic relay (only for V3 models)
L1R.................. Reactor (only for V3 models)
L1R~L3R......... Reactor (only for W1 models)
L4R.................. Reactor for (outdoor fan motor) (only for W1 models)
M1C................. Motor (compressor)
M1F ................. Motor (upper fan)
M2F ................. Motor (lower fan)
PS ................... Switching power supply
Q1DI................ Field earth fault interrupter
R1,R2 .............. Resistor (only for V3 models)
R1~R4............. Resistor (only for W1 models)
R1T ................. Thermistor (air)
R2T ................. Thermistor (discharge)
R3T ................. Thermistor (suction)
R4T ................. Thermistor (heat exchanger)
R5T ................. Thermistor (heat exchanger middle)
R6T ................. Thermistor (liquid)
R7T ................. Thermistor (fin) (only for W1 models)
R10T ............... Thermistor (fin) (only for V3 models)
RC ................... Signal receiver circuit (only for V3 models)
S1NPH ............Pressure sensor
S1PH............... High pressure switch
TC ................... Signal transmission circuit (only for V3 models)
V1R .................Power module
V2R .................Power module (only for W1 models)
V2R,V3R .........Diode module (only for V3 models)
V3R .................Diode module (only for W1 models)
V1T.................. IGBT (only for V3 models)
X1M .................Power supply terminal strip
Y1E.................. Electronic expansion valve
Y1S.................. Solenoid valve (4 way valve)
Y3S.................. Solenoid valve (only for W1 models)
Z1C~Z3C.........Noise filter (ferrite core) (only for V3 models)
Z1C~Z9C.........Noise filter (ferrite core) (only for W1 models)
Z1F~Z4F.......... Noise filter
OPTIONAL CONNECTOR
X1Y.................. Connector
X6A,X77A........ Connector (only for W1 models)
NOTES
THIS WIRING DIAGRAM ONLY APPLIES TO THE COMPRESOR
1.
MODULE SWITCH BOX L: LIVE
2.
N: : NEUTRAL
: FIELD WIRING
3.
NOT APPLICABLE
4.
DO NOT OPERATE THE UNIT BY SHORT-CIRCUITING
6.
PROTECTION DEVICE S1PH COLOURS:
7.
BLK : BLACK ORG : ORANGE BLU : BLUE RED : RED BRN : BROWN WHT : WHITE GRN : GREEN YLW : YELLOW CONFIRM THE METHOD OF SETTING THE SELECTOR
8.
SWITCHES (DS1) BY SERVICE MANUAL. FACTORY SETTING OF ALL SWITCHES: "OFF".
: TERMINAL STRIP : CONNECTOR : CONNECTION : PROTECTIVE EARTH (SCREW) : CONNECTOR : NOISELESS EARTH : TERMINAL
9. : OPTION
: WIRING DEPENDENT ON MODEL
POWER SUPPLY UNIT POWER SUPPLY UNIT TO HYDROMODULE
SWITCHBOX COMPRESSOR
MODULE SWITCHBOX COMPRESSOR
TERMINAL POSITION REACTOR BOX REACTOR BOX WIRE ENTRANCE WIRE ENTRANCE
TO HYDROMODULE SWITCHBOX
COMPRESSOR MODULE SWITCHBOX
COMPRESSOR TERMINAL POSITION
Installation manual
19
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Door 2 electrical parts of the hydraulic compartment
A11P................ Main PCB
A12P................ User interface PCB (remote controller)
A3P.................. Thermostat (EKRTW*, EKRTR*)(PC=Power Circuit)
A3P.................. Solar pump station PCB (EKSR3PA)
A4P.................. Digital I/O PCB (EKRP1HB)
A4P.................. Receiver PCB (EKRTR*)
E11H,E12H......Backup heater element 1, 2
E13H................Backup heater element 3 (only for W1 models)
E4H..................Booster heater
E5H..................Switch box heater
E6H..................Expansion vessel heater
E7H..................Plate heat exchanger heater
F1B.................. Fuse backup heater
F1T ..................Thermal fuse backup heater
F2B.................. Fuse booster heater
FU1.................. Fuse 3.15 A T 250 V for PCB
FU2.................. Fuse 5 A T 250 V
FuS,FuR ..........Fuse 5 A 250 V for digital I/O PCB
K1M .................Contactor backup heater step
K3M .................Contactor booster heater
K4M .................Pump relay
K5M .................Contactor for backup heater all pole disconnection
M1P .................Pump
M2S .................2-way valve for cooling mode
M3S .................3-way valve: floor heating/domestic hot water
PHC1............... Optocoupler input circuit
Q1DI,Q2DI....... earth leak detector
Q1L.................. Thermal protector backup heater
Q2L.................. Thermal protector 1 booster heater
Q3L.................. Thermal protector 2 booster heater
(only for W1 models)
R1H .................Humidity sensor (EKRTR*)
R1T.................. Ambient sensor (EKRTW*, EKRTR*)
R2T.................. External sensor (floor or ambient) (EKRTETS)
R5T.................. Domestic hot water thermistor (EKHW*)
R11T................ Outlet water heat exchanger thermistor
R12T................ Outlet water backup heater thermistor
R13T................ Refrigerant liquid side thermistor
R14T................ Inlet water thermistor
S1L ..................Flow switch
S1S.................. Solar pump station relay
S1T.................. Thermostat switch box heater
S2S.................. Benefit kWh rate power supply contact
S2T.................. Thermostat expansion vessel heater
S3S.................. Dual set point 2 contact
S3T.................. Thermostat plate heat exchanger
S4S.................. Dual set point 1 contact
SS1.................. DIP switch
TR1.................. Transformer 24 V for PCB, for relays and valves
V1S,V2S.......... Spark suppression 1, 2
X1M~X11M...... Terminal strips
X2Y~X5Y.........Connector
NOTES
THIS WIRING DIAGRAM ONLY APPLIES TO THE HYDROMODULE
1.
SWITCH BOX USE A DEDICATED POWER CIRCUIT FOR THE BACKUP HEATER
2.
AND BOOSTER HEATER. NEVER USE A POWER CIRCUIT SHARED BY OTHER APPLIANCE.
3.
NO/NC : NORMAL OPEN/NORMAL CLOSED SPST : SINGLE POLE SINGLE THROW
: FIELD WIRING
4.
DO NOT OPERATE THE UNIT BY SHORT-CIRCUITING ANY
5.
PROTECTION DEVICE COLOURS:
6.
BLK : BLACK PNK : PINK BLU : BLUE RED : RED BRN : BROWN VIO : VIOLET GRN : GREEN WHT : WHITE GRY : GREY YLW : YELLOW ORG : ORANGE FOR *KHWSU*V3, REFER TO OPTION MANUAL
7.
FOR *KSOLHWAV1, REFER TO OPTION MANUAL
8.
MAXIMUM LOAD: 0.3 A - 250 VAC MINIMUM LOAD: 20 mA - 5 VDC
9.
230 VAC OUTPUT MAXIMUM LOAD: 0.3 A
10.
BACKUP HEATER KW REDUCTION. REFER TO INSTALLATION
11.
MANUAL FOR BENEFIT kWh RATE POWER SUPPLY INSTALLATION, REFER
12.
TO INSTALLATION MANUAL
POWER SUPPLY POWER SUPPLY Only for benefit kWh rate
power supply installation: use normal kWh rate power supply for E5H, E6H, E7H.
FROM COMPRESSOR MODULE SWITCHBOX
To bottom plate heater To bottom plate heater E5H, E6H, E7H, internally
powered (Standard) POSITION OF PARTS POSITION OF PARTS HYDROMODULE
SWITCHBOX domestic hot water tank domestic hot water tank change-over to boiler
output Solar pump connection Solar pump connection Alarm output Alarm output cooling/heating on/off
output Solar input Solar input Standard 6 kW Standard 6 kW Reduced 3 kW Reduced 3 kW Dual setpoint application
(refer to installation manual)
3 wire type (SPST) 3 wire type (SPST) NO valve NO valve NC valve NC valve user interface user interface OUTSIDE UNIT OUTSIDE UNIT only for... option only for... option electric heater fuse electric heater fuse *KHW* kit fuse *KHW* kit fuse
: TERMINAL STRIP : CONNECTOR : TERMINAL : PROTECTIVE EARTH
Only for benefit kWh rate power supply installation: use normal kWh rate power supply for E5H, E6H, E7H.
FROM COMPRESSOR MODULE SWITCHBOX
E5H, E6H, E7H, internally powered (Standard)
HYDROMODULE SWITCHBOX
change-over to boiler output
cooling/heating on/off output
Dual setpoint application (refer to installation manual)
WIRING DEPENDENT ON MODEL FIELD WIRING OPTION FIELD WIRING PCB
WIRE COLOUR
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
20
Field wiring guidelines
Most field wiring on the unit is to be made on the terminal block inside the switch box. To gain access to the terminal block, remove the switch box service panel (door 2).
WARNING
Switch off all power supply – i.e. unit power supply and backup heater and domestic hot water tank power supply (if applicable) – before removing the switch box service panel.
Cable tie mountings are provided at the bottom of the switch box. Fix all cables using cable ties.
A dedicated power circuit is required for the backup heater.
Installations equipped with a domestic hot water tank (optional),
require a dedicated power circuit for the booster heater. Please refer to the domestic hot water tank installation manual.
Secure the wiring in the order shown below.
Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely (see
figure 2).
Follow the electric wiring diagram for electrical wiring works (the electric wiring diagrams are located on the rear side of doors 1 and 2).
Form the wires and fix the cover firmly so that the cover may be fit in properly.
Precautions on wiring of power supply
Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to unavoidable reasons, be sure to observe the following instruction.
1 Round pressure terminal 2 Cut out section 3 Cup washer
123
- Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause overheating.)
- When connecting wires of the same gauge, connect them
according to the below figure.
Specifications of standard wiring components
Door 1: compressor compartment and electrical parts: X1M
V3
1~ 50 Hz
230 V
L1 L3
3N~ 50 Hz
L2
W1
400 V
1 Earth leakage circuit
breaker
2 Fuse
1 2
L1 L3L2
X1MX1M
V3 W1
Minimum circuit amps (MCA) Recommended field fuse 32 A 20 A
(b)
Wire type Size Wiring size must comply with the
Wire type of wiring between the units H05VV-U4G2.5
(a) Stated values are maximum values (see electrical data of combination with
indoor unit for exact values).
(b) Only in protected pipes, use H07RN-F when protected pipes are not used.
NOTE
The earth leakage circuit breaker must be a
(a)
26.5 14
H05VV-U3G H05VV-U5G
applicable local and national code
high-speed type breaker of 30 mA (<0.1 s).
The wiring diagram can be found on the inside of the front plate of the unit.

Connection of the backup heater power supply

Power circuit and cable requirements
Be sure to use a dedicated power circuit for the backup heater. Never use a power circuit shared by another appliance.
Use one and same dedicated power supply for the unit, backup heater and booster heater (domestic hot water tank).
This power circuit must be protected with the required safety devices according to local laws and regulations.
Select the power cable in accordance with relevant local laws and regulations. For the maximum running current of the backup heater, refer to the table below.
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can damage the screw head and prevent appropriate tightening.
Over-tightening the terminal screws can damage the screws.
See the table below for tightening torques for the terminal
screws.
Tightening torque
(N•m)
M4 (X1M) 1.2~1.8 M5 (X1M) 2.0~3.0 M5 (EARTH) 3.0~4.0
Attach a earth leak detector and fuse to the power supply line.
In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces are not applied to the terminals.
Installation manual
21
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Door 2: electrical parts of the hydraulic compartment: X10M
V3
1~ 50 Hz
230 V
3N~ 50 Hz
L1 L3
L2
W1
400 V
1 Earth leakage circuit
breaker
2 Fuse
1 2
L1 L3L2
X10MX10M
(1)
Backup heater
Model
(a) (b)
V3 W1 6 kW 3x 400 V 8.7 A
(c)
V3 W1 2 kW 3x 400 V 5.0 A
(a) Equipment complying with EN/IEC 61000-3-12 (b) This equipment complies with EN/IEC 61000-3-11
(c) Refer to procedure how to set the backup heater to lower capacity.
NOTE
capacity
6 kW 1x 230 V 26 A 0.29
3 kW 1x 230 V 13 A
impedance Z user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a system impedance Z
sys
sys
The earth leak detector must be a high-speed type
Backup heater
nominal voltage
is less than or equal to Z
less than or equal to Z
Maximum
running current
(1)
(2)
provided that the system
at the interface point between the
max
.
max
Z
()
max
breaker of 30 mA (<0.1 s).
Procedure
1 Using the appropriate cable, connect the power circuit to the
main circuit breaker as shown on the wiring diagram and in
figure 2.
2 Connect the earth conductor (yellow/green) to the earthing
screw next to the X10M terminal.
3 Fix the cable with cable ties to the cable tie mountings to ensure
strain relief. (Positions are marked with in figure 2.)
Note: only relevant field wiring is shown.
4 If the backup heater capacity is to be set lower than the default
value (6 kW), this can be done by reconnecting wires according to following figure. The backup heater capacity is now 3 kW for V3 models or 2 kW for W1 models.
Connection of the thermostat cable
Connection of the thermostat cable depends on the application. See also "Typical application examples" on page 7 and "Room
thermostat installation configuration" on page 25 for more information
and configuration options on pump operation in combination with a room thermostat.
Thermostat requirements
Power supply: 230 V AC or battery operated
Contact voltage: 230 V.
Procedure 1 Connect the thermostat cable to the appropriate terminals as
shown on the wiring diagram and installation manual of the room thermostat kit.
2 Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
3 Set DIP switch SS2-3 on the PCB to ON. See "Room thermostat
installation configuration" on page 25 for more information.
Connection of the first set point and second set point contacts
The connection of the set point contact is only relevant in case dual set point contact is enabled.
See also "Typical application examples" on page 7 and "Dual set
point control" on page 33.
Contact requirements
The contact shall be a voltage free contact that ensure 230 V (100 mA).
Procedure 1 Connect the contact of first set point and second set point to the
appropriate terminals as shown in the figure below
X2M
123
4
SP1SP2
2 Fix the cables with cable ties to the cable tie mountings to
ensure strain relief.
3 Depending on the required pump operation set DIP switch
SS2-3 and field setting [F-00]. See "Pump operation
configuration" on page 26 and field setting [F-00] in "[F] Option setup" on page 36.
SP1 First set point contact SP2 Second set point contact
V3 W1
X5M
1
1
E12H
ON
2
2
3
4
X5M
3
E12H
OFF
4
BLK
BRN
X5M
1
1
E12H
ON
2
2
3
4
(1) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems with input current >16 A and 75 A per phase.
(2) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current 75 A.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
X5M
3
E12H
OFF
4
BLK
BRN
X5M
1 2 3 4 5 6
X5M
1 2 3 4 5 6
E11H
1
E12H E13H
2
3
E11H
4
E12H
5
E13H
6
E11H
1
E12H E13H
2
3
E11H
4
E12H
5
E13H
6
X5M
X5M
BRN BLK GRY
BRN BLK GRY
Connection of the valve control cables
Valve requirements
Power supply: 230 V AC
Maximum running current: 100 mA
Wiring the 2-way valve 1 Using the appropriate cable, connect the valve control cable to
the X2M terminal as shown on the wiring diagram.
NOTE
Wiring is different for a NC (normal closed) valve and a NO (normal open) valve. Make sure to connect to the correct terminal numbers as detailed on the wiring diagram and illustrations below.
Normal closed (NC) 2-way valve Normal open (NO) 2-way valve
5X2M 6 7
M
NC
5 6X2M 7
M
NO
2 Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
Installation manual
22
Wiring the 3-way valve 1 Using the appropriate cable, connect the valve control cable to
the appropriate terminals as shown on the wiring diagram.
Tw o types of 3-way valves can be connected. Wiring is different for each type:
"Spring return 2-wire" type 3-way valve The 3-way valve should be fitted as such that
when the 3-way valve is idle (not activated), the space heating circuit is selected.
"SPST 3-wire" type 3-way valve The 3-way valve should be fitted as such that
when terminal ports 9 and 10 are electrified, the domestic hot water circuit is selected.
"Spring return 2-wire" valve "SPST 3-wire" valve
10
9X2M 8
M
10
9X2M 8
M
2 Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
Connection to a benefit kWh rate power supply
Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates,
Wärmepumpentarif in Germany and Austria, ... .
This equipment allows for connection to such benefit rate power supply delivery systems.
Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the benefit kWh rate power supply delivery systems available, if any.
When the equipment is connected to such benefit kWh rate power supply, the electricity company is allowed to:
interrupt power supply to the equipment for certain periods of time;
demand that the equipment only consumes a limited amount of electricity during certain periods of time.
The unit is designed to receive an input signal by which the unit switches into forced off mode. At that moment, the outdoor unit compressor will not operate.
CAUTION for a benefit kWh rate power supply like illustrated
below as type 1 (allowed for all models)
If the benefit kWh rate power supply is of the type that power supply is not interrupted, then control of the heaters is still possible.
For the different possibilities of controlling heaters at moments that benefit kWh rate is active, refer to
"[D] Benefit kWh rate power supply/Local shift value weather dependent" on page 35.
If heaters must be controlled at moments that the benefit kWh rate power supply is off, then these heaters shall be connected to a separate power supply.
During the period that the benefit kWh rate is active and power supply is continuous, then stand-by power consumption is possible (PCB, controller, pump, ...).
for a benefit kWh rate power supply like illustrated below as types 2 or 3 (only allowed for EDL and EBL models)
If during benefit kWh rate power supply the power supply is shut off, then heaters can not be controlled.
This power supply interruption should not be longer than 2 hours, otherwise the real time clock of the controller will be reset.
During power supply interruption, the controller display will be blank.
If during benefit kWh rate power supply the power supply is shut off, the freeze protection function (refer to "[4-04]
Freeze protection function" on page 31) can not operate.
For this reason it is important that the power supply of the expansion vessel heater, plate heat exchanger heater and switch box heater are changed to guarantee freeze protection.
Procedure 1 Using the appropriate cable, connect the power
supply to the circuit heater as shown in the wiring diagram and in the figure below.
1 2
1234
1
1
43
2
2
L
N
1 Earth leakage
circuit breaker
2 Fuse
X11M
Installation manual
23
2 Connect the earth conductor (yellow/green) to the
earthing screw.
3 Fix the cable with cable ties to the cable tie mountings
to ensure strain relief.
4 Reconnect the wires according to the figure below.
BLK
1 L
212
N
X11M
WHT
4321
43
BLK
WHT
4321
1
43
212
L
N
X11M
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Possible types of benefit kWh rate power supply
Possible connections and requirements to connect the equipment to such power supply are illustrated in the figure below:
[D-01]=1
LN
1 2
1 2
1 2
3
3
DHQ/*DLQ/*BHQ/*BLQ
*
1 Benefit kWh rate power supply box 2 Receiver controlling the signal of the electricity company 3 Power supply to unit 4 Voltage free contact
Allowed only for EDL and EBL unit models
LN
LN
S2S
S2S
S2S
43
43
4
X2M17 18
A1P
X40A
[D-01]=2
LN
1 2
1 2
1 2
3
S2S
43
LN
S2S
43
LN
S2S
When the unit is connected to a benefit kWh rate power supply, the voltage free contact of the receiver controlling the benefit kWh rate signal of the electricity company must be connected to clamps 17 and 18 of X2M (as illustrated in the figure above). When parameter [D-01]=1 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will open and the unit will go in forced off mode
(1)
. When parameter [D-01]=2 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will close and the unit will go in forced off mode
(2)
.
Type 1
This type of benefit kWh rate power supply is not interrupted.
Type 2
This type of benefit kWh rate power supply is interrupted after elapse of time.
Type 3
This type of benefit kWh rate power supply is interrupted immediately.
When connecting the equipment to a benefit kWh rate power supply, change field settings [D-01] and both [D-01] and [D-00] in case the benefit kWh rate power supply is of the type that power supply is not interrupted (like illustrated above as type 1). Refer to "[D] Benefit kWh rate power
supply/Local shift value weather dependent" on page 35 of
chapter "Field settings".
If the benefit kWh rate power supply is of the type that power supply is not interrupted, the unit will be forced to off. Controlling the solar pump is still possible.
When the benefit kWh rate signal is sent, the centralised control indicator e will flash to indicate that the benefit kWh rate is active.

Installation of the digital controller

The unit is equipped with a digital controller offering a user-friendly way to set up, use and maintain the unit. Before operating the controller, follow this installation procedure.
Wiring specifications
Wire specification Val ue
Type 2 wire
Section
Maximum length 500 m
NOTE
The wiring for connection is not included.
0.75~1.25 mm
2
Mounting
The digital controller, delivered in a kit, has to be mounted indoors.
1 Remove the front part of the digital controller.
Insert a slotted screwdriver into the slots (1) in the rear part of the digital controller, and remove the front part of the digital controller.
2 Fasten the digital controller on a flat
surface.
NOTE
Be careful not to distort the shape of the lower part of the digital controller by over tightening the mounting screws.
1
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto restart function enabled. Refer to "[3] Auto restart" on page 29.
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto restart function enabled. Refer to "[3] Auto restart" on page 29.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
24
3 Wire the unit.

START-UP AND CONFIGURATION

6
16a
16a
16
1
16
1
2
P1P2
P1P2
3
4 5
1 Unit 2 Rear part of the digital controller 3 Front part of the digital controller 4 Wired from the rear 5 Wired from the top 6 Notch the part for the wiring to pass through with nippers, etc.
Connect the terminals on top of the front part of the digital controller and the terminals inside the unit (P1 to 16, P2 to 16a).
NOTE
When wiring, run the wiring away from the power supply wiring in order to avoid receiving electric noise (external noise).
Peel the shield for the part that has to pass through the inside of the digital controller case ( l ).
4 Reattach the upper part of the digital controller.
Be careful not to pinch the wiring when attaching.
First begin fitting from the clips at the bottom.
The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user expertise.
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as applicable.

DIP switch settings overview

DIP switch SS2 is located on the switch box PCB (see "Switch box
main components (door 2)" on page 13) and allows configuration of
domestic hot water tank installation, room thermostat connection and pump operation.
WARNING
Switch off the power supply before opening the switch box service panel and making any changes to the DIP switch settings.
ONOFF
DIP switch SS2
Description ON OFF
1 Not applicable for installer — (Default) 2 Domestic hot water tank
installation (see "Domestic hot water
tank installation configuration" on page 26)
3 Room thermostat
connection (see "Room thermostat
installation configuration" on page 25)
4 This setting
operation mode when there is a simultaneous demand for more space heating/cooling and domestic water heating.
(a) only applicable in case DIP switch 2 = ON (b) Heating/cooling or domestic water heating mode can be restricted by schedule
1
timer and/or field settings (4, 5, 8).
(a)
decides the
4321
Installed Not installed
Room thermostat connected
Heating/cooling priority
(Default)
No room thermostat connected (Default)
Priority to highest demand side
(b)
Installation manual
25
Room thermostat installation configuration
When no room thermostat is connected to the unit, toggle switch SS2-3 should be set to OFF.
When a room thermostat is connected to the unit, toggle switch SS2-3 should be set to ON.
On the room thermostat, set the hysteresis appropriately to prevent the pump from repeatedly turning on and off (i.e. chattering), and thereby impacting the lifetime of the pump.
NOTE
When a room thermostat is connected to the unit, the heating and cooling schedule timers are never available. Other schedule timers are not affected. For more information on the schedule timers, refer to the operation manual.
When a room thermostat is connected to the unit, and the = button or y button is pressed, the centralised control indicator e will flash to indicate that the room thermostat has priority and controls on/off operation and changeover operation.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
ONOFF
ONOFF
4PW57621-1A
4321
4321
The following table summarizes the required configuration and thermostat wiring at the terminal block in the switch box. Pump operation is listed in the third column. The three last columns indicate whether the following functionality is available on the user interface (UI) or handled by the thermostat (T):
• space heating or cooling on/off (y)
• heating/cooling changeover (=)
• heating and cooling schedule timers (pr)
Pump
Thermostat Configuration
No thermostat
Heating only thermostat
Thermostat with heating/cooling switch
(a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space heating/cooling turned on, the pump will then run every 5 minutes during 3 minutes to check the water temperature.
• SS2-3=OFF
•wiring: (non)
X2M
1 234
• SS2-3=ON
•wiring:
X2M
1 234
• SS2-3=ON
•wiring: (see installation manual of the room thermostat kit)
• SS2-3=ON
•wiring: (see installation manual of the room thermostat kit)
operation
determined by leaving water temperature
on when space heating or cooling is on
(a)
(y)
on when heating request by room thermostat
on when heating request or cooling request by room thermostat
yyyy==== pppprr
UI UI UI
UI UI UI
T——
TT—
rr
Pump operation configuration
NOTE
To set the pump speed, refer to "Setting the pump
speed" on page 27.
The following table summarizes the required configuration and wiring at the terminal block (X2M: 1, 2, 4) in the switch box. Pump operation is listed in the third column. The three last columns indicate whether the following functionality is available on the user interface (UI) or handled by the set point selection contacts SP1 and SP2:
• space heating or cooling on/off (y)
• heating/cooling changeover (=)
• heating and cooling schedule timers (pr)
Dual set point
Configuration Pump operation yy
•[7-02]=1
• SS2-3=OFF
•wiring:
X2M
123
4
SP1SP2
•[7-02]=1
• SS2-3=ON
•wiring:
X2M
1234
SP1SP2
(a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space heating/cooling turned on, the pump will then run every 5 minutes during 3 minutes to check the water temperature.
determined by leaving water temperature
on when main or/and sub set point is requested
SP1 =
First set point contact
SP2 =
Second set point contact
(a)
yy
UI UI UI
SP2/SP1 UI
==== pppprr
rr
Domestic hot water tank installation configuration
When no domestic hot water tank is installed, toggle switch SS2-2 should be set to OFF (default).
When a domestic hot water tank is installed, toggle switch SS2-2 should be set to ON.
ONOFF
ONOFF
4321
4321
Without room thermostat: DIP switch SS2-3=OFF
When no thermostat is connected to the unit, pump operation will be determined by the leaving water temperature.
To f orce continuous pump operation when no room thermostat is connected do the following:
- set toggle switch SS2-3 to ON,
- short-circuit the terminal numbers 1-2-4 on the terminal block in the switch box.
With room thermostat: DIP switch SS2-3=ON
When a thermostat is connected to the unit, the pump will operate continuously whenever there is heating or cooling demand requested by the thermostat.
Dual set point
When dual set point is enabled, the pump operation will be determined depending on the status of the DIP switch SS2-3 and set point selection contacts. Refer to the pump operation configurations when the thermostat is connected or not as described above.
When dual set point is enabled, the "forced continuous pump operation" is not possible. When SS2-3 is ON while SP1 and SP2 are both closed, the pump operation will be the same operation as "with room thermostat" and the second set point will be the applicable set point. Refer to
"Dual set point control" on page 33.
When SS2-3 was set to ON without all necessary and correct wiring connections between indoor unit and switch box of the domestic hot water tank, the error code AC will be displayed on the user interface.

Initial start-up at low outdoor ambient temperatures

During initial start-up and when water temperature is low, it is important that the water is heated gradually. Failure to do so may result in cracking of concrete floors due to rapid temperature change. Please contact the responsible cast concrete building contractor for further details.
To do so, the lowest leaving water set temperature can be decreased to a value between 15°C and 25°C by adjusting the field setting [9-01] (heating set point lower limit). Refer to "Field settings" on
page 28.
NOTE
Heating between 15°C and 25°C is performed by the backup heater only.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
26

Pre-operation checks

Powering up the unit

Checks before initial start-up
DANGER
Switch off the power supply before making any connections.
After the installation of the unit, check the following before switching on the circuit breaker:
1 Field wiring
Make sure that the field wiring between local supply panel and unit and valves (when applicable), unit and room thermostat (when applicable), and unit and domestic hot water tank has been carried out according to the instructions described in the chapter "Field wiring" on page 17, according to the wiring diagrams and according to local laws and regulations.
2 Fuses, circuit breakers, or protection devices
Check that the fuses or the locally installed protection devices are of the size and type specified in the chapter "Technical
specifications" on page 43. Make sure that neither a fuse nor a
protection device has been bypassed.
3 Backup heater circuit breaker F1B/F3B
Do not forget to turn on the backup heater circuit breaker F2B in the switch box (F1B/F3B depends on the backup heater type). Refer to the wiring diagram.
4 Booster heater circuit breaker F2B
Do not forget to turn on the booster heater circuit breaker F2B in the switch box (applies only to units with optional domestic hot water tank installed).
5 Earth wiring
Make sure that the earth wires have been connected properly and that the earth terminals are tightened.
6 Internal wiring
Visually check the switch box on loose connections or damaged electrical components.
7 Fixation
Check that the unit is properly fixed, to avoid abnormal noises and vibrations when starting up the unit.
8 Damaged equipment
Check the inside of the unit on damaged components or squeezed pipes.
9 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak, call your local dealer.
10 Power supply voltage
Check the power supply voltage on the local supply panel. The voltage must correspond to the voltage on the identification label of the unit.
11 Air purge valve
Make sure the air purge valve is open (at least 2 turns).
12 Pressure relief valve
Check if the backup heater vessel is completely filled with water by operating the pressure relief valve. It should purge water instead of air.
NOTE
Operating the system with the backup heater not completely filled with water will damage the backup heater!
When power supply to the unit is turned on, "88" is displayed on the user interface during its initialisation, which might take up to 30 seconds. During this process the user interface cannot be operated.

Setting the pump speed

The pump speed can be selected on the pump (see "Main
components" on page 12).
The default setting is high speed (I). If the water flow in the system is too high (e.g., noise of running water in the installation) the speed can be set to low speed (II).
NOTE
The speed dial on the pump indicates 3 speed settings. However, only 2 speed settings exist: low speed and high speed. The indicated medium speed setting on the speed dial is equal to low speed.
The available external static pressure (ESP, expressed in kPa) in function of the water flow (l/min) is shown in the graph below.
[kPa]
85
80
75
70
65
60
55
50
45
ESP
40
35
30
25
20
15
10
5
0
20 30 40 5016 60
[l/min]
Failure diagnosis at the moment of first installation
In case nothing is displayed on the remote controller (the current set temperature does not display), check for any of the following abnormalities before you can diagnose possible malfunction codes.
Disconnection or wiring error (between power supply and unit
and between unit and remote controller).
The fuse on the PCB may have run out.
If the remote controller shows "E3", "E4" or "L8" as an error code,
there is a possibility that either the stop valves are closed, or that air inlet or air outlet are blocked.
If the error code "U2" is displayed on the remote controller, check for voltage imbalance.
If the error code possible that air inlet or air outlet are blocked.
"L4"
is displayed on the remote controller, it is
13 Shut-off valves
Make sure that the shut-off valves are fully open.
Operating the system with closed valves will damage the pump!
Installation manual
27
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
The reversed phase protection detector of this product only works during the initialisation stage after a power reset.
The reversed phase protection detector is designed to stop the product in case of an abnormality when the product is started up.
When the reversed phase protection circuit forced the unit to
stop, check if all phases are existing. If this is the case, shut off the power supply to the unit and replace two of three phases. Turn on power again and start the unit.
Reversed phase detection is not performed while the product
is operating.
In case of possible reversal of phases after a momentary
black out of power and the power goes on and off while the product is operating, install a reversed phase protection circuit on site. Such situation is not unimaginable when using generators. Running the product in reversed phase can break the compressor and other parts.
E7
For a missing phase in case of W1 units, "
" or "U2" will be
displayed on the remote controller of the unit.
Operation will be impossible with either one of these phenomena. If this happens, turn off the power, re-check the wiring and switch the position of two of the three electrical wires.

Field settings

The unit shall be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user demand. Thereto, a number of so called field settings are available. These field settings are accessible and programmable through the user interface.
Each field setting is assigned a 3-digit number or code, for example [5-03], which is indicated on the user interface display. The first digit [5] indicates the 'first code' or field setting group. The second and third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under "Field
settings table" on page 37. In this same list, we provided for 2
columns to register the date and value of altered field settings at variance with the default value.
A detailed description of each field setting is given under "Detailed
description" on page 28.
Procedure
To change one or more field settings, proceed as follows.
3 Press the bgj button to select the appropriate field
setting second code.
4 Press the pfi button and pfj button to change
the set value of the select field setting.
5 Save the new value by pressing the pr button. 6 Repeat step 2 through 4 to change other field settings as
required.
7 When finished, press the z button to exit FIELD SET MODE
NOTE
Changes made to a specific field setting are only
.
stored when the pr button is pressed. Navigating to a new field setting code or pressing the z button will discard the change made.
NOTE
Before shipping, the set values have been set as shown under "Field settings table" on page 37.
When exiting FIELD SET MODE, "88" may be displayed on the user interface LCD while the unit initialises itself.
Detailed description
[0] User permission level
If required, certain user interface buttons can be made unavailable for the user.
Three permission levels are defined (see the table below). Switching between level 1 and level 2/3 is done by simultaneously pressing buttons pfi and pfj immediately followed by simultaneously pressing buttons s and ba, and keeping all 4 buttons pressed for at least 5 seconds (in normal mode). Note that no indication on the user interface is given. When level 2/3 is selected, the actual permission level — either level 2 or level 3 — is determined by the field setting [0-00].
Permission level
Button
Quiet mode button Weather dependent
set point button Schedule timer
enable/disable button Programming button
Time adjust buttons
Inspection/test operation button
s
ba
pr
<
pf
i
pf
j
z
1 2 3
operable
operable
operable operable
operable
operable
operable
3
2
1
1 Press the z button for a minimum of 5 seconds to enter FIELD
SET MODE. The $ icon (3) will be displayed. The current selected field setting code is indicated ; (2), with the set value displayed to the right - (1).
2 Press the bgi button to select the appropriate field
setting first code.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
28
[1] Weather dependent set point (heating operation only)
The weather dependent set point field settings define the parameters for the weather dependent operation of the unit. When weather dependent operation is active the water temperature is determined automatically depending on the outdoor temperature: colder outdoor temperatures will result in warmer water and vice versa. During weather dependent operation, the user has the possibility to shift up or down the target water temperature by a maximum of 5°C. See the operation manual for more details on weather dependent operation.
[1-00] Low ambient temperature (Lo_A): low outdoor temperature.
[1-01] High ambient temperature (Hi_A): high outdoor temperature.
[1-02] Set point at low ambient temperature (Lo_Ti): the target outgoing water temperature when the outdoor temperature equals or drops below the low ambient temperature (Lo_A). Note that the Lo_Ti value should be higher than Hi_Ti, as for colder outdoor temperatures (i.e. Lo_A) warmer water is required.
[1-03] Set point at high ambient temperature (Hi_Ti): the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature (Hi_A). Note that the Hi_Ti value should be lower than Lo_Ti, as for warmer outdoor temperatures (i.e. Hi_A) less warm water suffices.
T
t
[2] Disinfection function
Applies only to installations with a domestic hot water tank. The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic water to a specific temperature.
CAUTION
The disinfection function field settings must be configured by the installer according to local laws and regulations.
[2-00] Operation interval: day(s) of the week at which the domestic water should be heated.
[2-01] Status: defines whether the disinfection function is turned on (1) or off (0).
[2-02] Start time: time of the day at which the domestic water should be heated.
[2-03] Set point: high water temperature to be reached.
[2-04] Interval: time period defining how long the set point
temperature should be maintained.
T
DHW
[2-03]
T
H
T
U
[2-04]
Lo_Ti
Hi_Ti
Lo_A Hi_A T
T
Target water temperature
t
T
Ambient (outdoor) temperature
A
= Shift value
+ 05
– 05
A
00
Shift value
00.00 22.00 24.0001.00 23.00 t
[2-02]
T
Domestic hot water temperature
DHW
T
User set point temperature (as set on the user interface)
U
T
High set point temperature [2-03]
H
t Time
WARNING
Be aware that the domestic hot water temperature at the hot water tap will be equal to the value selected in field setting [2-03] after a disinfection operation.
If this high domestic hot water temperature can be a potential risk for human injuries, a mixing valve (field supply) shall be installed at the hot water outlet connection of the domestic hot water tank. This mixing valve shall secure that the hot water temperature at the hot water tap never rise above a set maximum value. This maximum allowable hot water temperature shall be selected according to local laws and regulations.
[3] Auto restart
When power returns after a power supply failure, the auto restart function reapplies the user interface settings at the time of the power supply failure.
NOTE
It is therefore recommended to leave the auto restart function enabled.
Installation manual
29
Note that with the function disabled the schedule timer will not be activated when power returns to the unit after a power supply failure. Press the pr button to enable the schedule timer again.
[3-00] Status: defines whether the auto restart function is turned ON (0) or OFF (1).
NOTE
If the benefit kWh rate power supply is of the type that power supply is interrupted, then always allow the auto restart function.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
[4] Backup heater operation and space heating off temperature
Backup heater operation
The operation of the backup heater can be enabled or disabled, or it can be disabled depending on operation of the booster heater.
[4-00] Status: defines whether backup heater operation is enabled (1) or disabled (0).
NOTE
Even in case the backup heater operation status field setting [4-00] is disabled (0), the backup heater can operate during start-up and defrost operation.
[4-01] Priority: defines whether backup heater and booster heater can operate simultaneously (0), or if the booster heater operation has priority over the backup heater operation (1), or if the backup heater operation has priority over the booster heater operation (2).
NOTE
When the priority field setting is set to ON (1), space heating performance of the system might be decreased at low outdoor temperatures, since in case of domestic water heating demand the backup heater will not be available for space heating (space heating will still be provided by the heat pump).
When the priority field setting is set to ON (2), domestic water heating performance of the system might be decreased at low outdoor temperatures, since in case of space heating demand the booster heater will not be available for domestic water heating. However domestic water heating by heat pump will still be available.
When the priority field setting is set to OFF (0), make sure that electrical power consumption does not exceed supply limits.
Space heating off temperature
[4-02] Space heating off temperature: outdoor temperature above which space heating is turned off, to avoid overheating.
Booster heater operation
Applies only to installations with a domestic hot water tank. The operation of the booster heater can be enabled or limited
depending on outdoor temperature (TA), domestic hot water temperature (T
) or operation mode of the heat pump.
DHW
[4-03] Booster heater operation: defines whether the optional booster heater operation is enabled (1) or has certain limitations (0/2/3).
Explanation of settings of [4-03]
Booster heater will/can only operate if domestic hot water mode is activated (w).
[4-03]=0, then booster heater operation is only allowed during "[2] Disinfection function" and "Powerful domestic water heating" (see operation manual). This setting is only recommended in case the capacity of the heat pump can cover the heating requirements of the house and domestic hot water over the complete heating season. The result of this setting is that the domestic hot water will never be heated by the booster heater except for "[2] Disinfection function" and "Powerful domestic water heating" (see operation manual).
If the booster heater operation is limited ([4-03]=0) and the ambient outdoor temperature TA is lower than the field setting to which parameter [5-03] is set and [5-02]=1, then the domestic hot water will not be heated.
The consequence of this setting is that the domestic hot water temperature (T heat pump OFF temperature (T
) can be maximum the
DHW
HP OFF
). Refer to
setting of [6-00] and [6-01] in "[6]" on page 32.
[4-03]=1, then booster heater heater operation is only determined by booster heater OFF temperature (T booster heater ON temperature (T
) and/or schedule
BH ON
BH OFF
timer. Refer to setting "[7-00]" on page 32 and "[7-01]" on
page 33.
[4-03]=2, then booster heater operation is only allowed if heat pump is out of "operation range" of heat pump domestic water heating mode (TA<[5-03] or TA>35°C) or domestic hot water temperature is 2°C lower than the heat pump OFF temperature (T (T
DHW>THP OFF–
) for domestic hot water mode
HP OFF
2°C). (Refer to setting [5-03] on page 31, [6-00] on page 32 and [6-01] on page 32). Results in the most optimum coverage of domestic hot water heated by the pump.
[4-03]=3, then booster heater operation is the same as setting 1, except that booster heater is OFF when the heat pump is active in domestic hot water mode. The consequence of this functionality is that setting [8-03] is not relevant. Results in optimum coverage of domestic hot water heated by heat pump in relation with [8-04].
),
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
When setting [4-03]=1/2/3, the booster heater operation can still be restricted by the schedule timer as well. I.e., when booster heater operation is preferred during certain period of the day. (See operation manual)
When setting [4-03]=2, the booster heater will be allowed to operate when TA<[5-03] independent of the status of [5-02]. If bivalent operation is enabled and permission signal for auxiliary boiler is ON, the booster heater will be restricted even when T
<[5-03]. (See "[C-02]" on page 35).
A
Booster heater is always allowed during powerful and disinfection function, except for the period that the backup heater operation is required for safety reasons and [4-02]=1.
Installation manual
30
[4-04] Freeze protection function: avoids freezing of the water piping between home and unit. In case of low ambient temperatures it will activate the pump and in case of low water temperatures it will additionally activate the backup heater. Default freeze protection function takes into account freezing of water piping which is insufficiently insulated. Basically it means that the pump is activated whenever ambient temperatures become close to freezing, independently of the working temperature.
[5] Equilibrium temperature and space heating priority temperature
Equilibrium temperature — The 'equilibrium temperature' field
settings apply to operation of the backup heater. When the equilibrium temperature function is enabled, operation of the backup heater is restricted to low outdoor temperatures, i.e. when the outdoor temperature equals or drops below the specified equilibrium temperature. When the function is disabled, operation of the backup heater is possible at all outdoor temperatures. Enabling this function reduces the working time of the backup heater.
[5-00] Equilibrium temperature status: specifies whether the equilibrium temperature function is enabled (1) or disabled (0).
[5-01] Equilibrium temperature: outdoor temperature below which operation of the backup heater is allowed.
Space heating priority temperature
Applies only to installations
with a domestic hot water tank. The 'space heating priority temperature' field settings apply to operation of the 3-way valve and the booster heater in the domestic hot water tank. When the space heating priority function is enabled, it is assured that the full capacity of the heat pump is used for space heating only when the outdoor temperature equals or drops below the specified space heating priority temperature, i.e. low outdoor temperature. In this case the domestic hot water will only be heated by the booster heater.
[5-02] Space heating priority status: specifies whether space heating priority is enabled (1) or disabled (0).
[5-03] Space heating priority temperature: outdoor temperature below which the domestic hot water will be heated by the booster heater only, i.e. low outdoor temperature.
If the booster heater operation is limited ([4-03]=0) and the ambient outdoor temperature TA is lower than the field setting to which parameter [5-03] is set and [5-02]=1, then the domestic hot water will not be heated.
[5-04] Set point correction for domestic hot water temperature: set point correction for the desired domestic hot water temperature, to be applied at low outdoor temperature when space heating priority is enabled. The corrected (higher) set point will make sure that the total heat capacity of the water in the tank remains approximately unchanged, by compensating for the colder bottom water layer of the tank (because the heat exchanger coil is not operational) with a warmer top layer.
T
set
T
U
T
Domestic hot water set point temperature
set
T
User set point (as set on the user interface)
U
T
Ambient (outdoor) temperature
A
Space heating priority
[5-04]
[5-03]
T
A
WARNING
Be aware that the domestic hot water temperature will be automatically increased with the value selected in field setting [5-04] (if the outdoor temperature drops below field setting [5-03]) compare to the user set point for domestic hot water (TU). Refer to field setting [5-03], [7-00] and the operation manual to select preferable set point.
If this high domestic hot water temperature can be a potential risk for human injuries, a mixing valve (field supply) shall be installed at the hot water outlet connection of the domestic hot water tank. This mixing valve shall secure that the hot water temperature at the hot water tap never rise above a set maximum value. This maximum allowable hot water temperature shall be selected according to local laws and regulations.
Installation manual
31
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
[6] DT for heat pump domestic water heating mode
Applies only to installations with a domestic hot water tank. The 'DT (temperature difference) for heat pump domestic water
heating mode' field settings determine the temperatures at which heating of the domestic hot water by the heat pump will be started (i.e., the heat pump ON temperature) and stopped (i.e., the heat pump OFF temperature). When the domestic hot water temperature drops below the heat pump ON temperature (T
), heating of the domestic hot water by
HP ON
the heat pump will be started. As soon as the domestic hot water temperature reaches the heat pump OFF temperature (T
HP OFF
) or the user set point temperature (TU), heating of the domestic hot water by the heat pump will be stopped (by switching the 3-way valve).
The heat pump OFF temperature, and the heat pump ON temperature, and its relation with field settings [6-00] and [6-01] are explained in the illustration below.
[6-00] Start: temperature difference determining the heat
T
pump ON temperature (
). See illustration.
HP ON
[6-01] Stop: temperature difference determining the heat pump OFF temperature (
TU > T
HP MAX
T(°C)
70
55 T
48 T
41 T
T
U
T
HP MAX
T
HP OFF
T
HP ON
(a) 50°C = T
48°C = T
TU = 70°C [6-01] = 7°C [6-00] = 7°C
T
U
HP MAX
HP OFF
HP ON
User set point temperature (as set on the user interface) Maximum heat pump temperature at sensor in domestic hot
water tank (50°C)(depending on T Heat pump OFF temperature Heat pump ON temperature
HP MAX HP MAX
[6-01]
[6-00]
at TA≤25°C. at TA>25°C.
T
). See illustration.
HP OFF
T
< T
U
T(°C)
55 T
45
38 T
HP MAX
TU = T
)
A
TU = 45°C [6-01] = 7°C [6-00] = 7°C
HP MAX
HP OFF
HP ON
(a)
[6-00]
The maximum domestic hot water temperature that can be reached with the heat pump is 50°C. It is advised to select T
not higher than 48°C in order to improve
HP OFF
performance of the heat pump during domestic water heating mode.
When setting [4-03]=0 or 2 special attention to setting [6-00] is recommended. A good balance between the required domestic hot water temperature and heat pump ON temperature (T
HP ON
) is a must.
[7] DT for booster heater and dual set point control
DT for booster heater
Applies only to installations with a domestic hot water tank. When the domestic hot water is heated and the domestic hot water
set point temperature (as set by the user) has been reached, the booster heater will continue to heat the domestic hot water to a temperature a few degrees above the set point temperature, i.e. the booster heater OFF temperature. These extra degrees are specified by the domestic hot water step length field setting. Correct setting prevents the booster heater from repeatedly turning on and off (i.e. chattering) to maintain the domestic hot water set point temperature. Note: the booster heater will turn back on when the domestic hot water temperature drops [7-01] (field setting) below the booster heater OFF temperature.
If the schedule timer for booster heater (see the operation manual) is active, the booster heater will only operate if allowed by this schedule timer.
[7-00] Domestic hot water step length: temperature difference above the domestic hot water set point temperature before the booster heater is turned off.
(°C)T
DHW
T
BH OFF
T
T
HP MAX
T
HP OFF
T
BH ON
T
HP ON
73 71
70
U
60 50
48
41 40
30
20
HP
10
5
[7-00]
[6-01]
[6-00]
BH
T [7-00] = 3°C [6-01] = 2°C [6-00] = 7°C
BH Booster heater HP Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the booster heater can take place
T
BH OFF
T
BH ON
T
HP MAX
T
HP OFF
T
HP ON
T
DHW
T
Booster heater OFF temperature (TU + [7-00]) Booster heater ON temperature (T Maximum heat pump temperature at sensor in domestic hot
water tank Heat pump OFF temperature (T Heat pump ON temperature (T
HP MAX
HP OFF
Domestic hot water temperature User set point temperature (as set on the user interface)
U
t Time
U
BH OFF
– [6-00])
[7-01]
=70°C
HP
– 2°C)
– [6-01])
t
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
WARNING
Be aware that the domestic hot water temperature will be automatically increased (always) with the value selected in field setting [7-00] compare to the user set point for domestic hot water (TU). Refer to field setting [7-00] and the operation manual to select preferable set point.
If this high water temperature can be a potential risk for human injuries, a mixing valve (field supply) shall be installed at the hot water outlet connection of the domestic hot water tank. This mixing valve shall secure that the hot water temperature at the hot water tap never rise above a set maximum value. This maximum allowable hot water temperature shall be selected according to local laws and regulations.
If the booster heater operation is limited ([4-03]=0), then set point of field setting parameter [7-00] has only meaning for powerful domestic water heating.
Installation manual
32
[7-01] Hysteresis value booster heater: temperature difference determining the booster heater ON temperature (T
BH ON
). T
BH ON
= T
BH OFF
– [7-01]
The minimum value for booster heater ON temperature (T
OFF temperature (T
) is 2°C (fixed) below heat pump
BH ON
HP OFF
).
Dual set point control
Applies only to installations with different heat emitter which require different set points.
Dual set point control makes it possible to generate 2 different set points.
NOTE
There is no indication available which set point is active!
[7-02] Dual set point control status: defines whether the dual set point control is enabled (1) or disabled (0).
[7-03] Second set point heating: specifies the second set point temperature in heating operation.
[7-04] Second set point cooling: specifies the second set point temperature in cooling operation.
NOTE
The first set point heating/cooling is the set point selected on the user interface.
- In heating mode the first set point can be a
fixed value or weather dependent.
- In cooling mode the first set point is always a
fixed value.
The second set point heating [7-03] should be linked to the heat emitters which requires the highest set point in heating mode. Example: fan coil unit.
The second set point cooling [7-04] should be linked to the heat emitters which requires the lowest set point in cooling mode. Example: fain coil unit.
The actual second set point heating value depends on the selected value of setting [7-03].
- In case [7-03]=1~24°C, the actual second set
point will be first set point heating increased with [7-03] (the maximum is 55°C). In this way the second set point heating is linked to the first set point heating.
- In case [7-03]=25~55°C, the actual second set
point heating is equal to [7-03].
The selection of second set point or first set point is determined by the terminals (X2M: 1, 2, 4). The second set point has always priority on the first set point.
[8] Domestic water heating mode timer
Applies only to installations with a domestic hot water tank. The 'domestic water heating mode timer' field settings defines the
minimum and maximum domestic water heating times, minimum time between two domestic water heating cycles by heat pump, and booster heater delay time.
[8-00] Minimum running time: specifies the minimum time period during which heat pump domestic water heating mode should be activated, even when the target domestic hot water temperature for heat pump (T
) has already been
HP OFF
reached.
[8-01] Maximum running time: specifies the maximum time period during which heat pump domestic water heating mode can be activated, even when the target domestic hot water temperature for heat pump (T
) has not yet been
HP OFF
reached. The actual maximum running time will automatically vary between [8-01] and [8-01]+[8-04] depending on the outdoor temperature. See figure in chapter "[8-04]" on page 34.
Note that when the unit is configured to work with a room thermostat (refer to "Room thermostat
installation configuration" on page 25), the
maximum running timer will only be taken into account when there is a request for space cooling or space heating. When there is no request for room cooling or room heating, domestic water heating by the heat pump will continue until the 'heat pump OFF temperature' (see field settings [6] on page 32) is reached. When no room thermostat is installed, the timer is always taken into account.
[8-02] Anti-recycling time: specifies the minimum required interval between two heat pump domestic water heating mode cycles. The actual anti-recycling time will automatically vary between [8-02] and 0 depending on the outdoor temperature. See figure in chapter "[8-04]" on page 34.
1
0
1
0
[8-00]
[8-01] [8-02]
1 Domestic water heating (1 = active, 0 = not active) 2 Hot water request (1 = request, 0 = no request)
t Time
t
When dual set point control is enabled, heating/cooling selection always has to be done on the user interface.
NOTE
It is the responsibility of the installer to make sure no unwanted situations can occur.
It is very important that the water temperature to the floor heating loops never becomes too high in heating mode or never too cold in cooling mode. Failure to observe this rule can result in construction damage or discomfort. For example in cooling mode condensation on the floor can occur when water towards the floor heating loops is too cold (dew point).
Installation manual
33
X2M
1234
SP1SP2
SP1 First set point contact SP2 Second set point
contact
If the outdoor temperature is higher than the field setting to which parameter [4-02] is set, then field settings of parameters [8-01], [8-02], and [8-04] are not considered.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
[8-03] Booster heater delay time: specifies the start-up time delay of the booster heater operation when heat pump domestic water heating mode is active.
When heat pump is active in domestic water heating mode, the delay time of booster heater is [8-03].
When heat pump is not active in domestic water heating mode, the delay time is 20 min.
The delay timer starts from booster heater ON temperature (T
BH ON
)
[8-04] Additional running time at [4-02]/[F-01]: specifies the additional running time on the maximum running time at outdoor temperature [4-02] or [F-01]. See figure below.
Heating Cooling
t
[8-01]+
[8-04]
[8-02]
[8-01]
t
[8-01]+
[8-04]
[8-02]
[8-01]
1
4
0
1
3
0
1
0
1
0
[8-03]
1 Booster heater operation (1 = active, 0 = not active) 2 Heat pump domestic water heating mode
(1 = active, 0 = not active)
3 Hot water request for booster heater
(1 = request, 0 = no request)
4 Hot water request for heat pump (1 = request, 0 = no request)
t Time
t
By adapting the booster heater delay time versus the maximum running time, an optional balance can be found between the energy efficiency and the heat up time.
However, if the booster heater delay time is set too high, it might take a long time before the domestic hot water reaches its set temperature upon domestic hot water mode request.
The purpose of [8-03] is to delay the booster heater in relation with the heat pump operation time in domestic water heating mode.
The setting [8-03] has only meaning if setting [4-03]=1. Setting [4-03]=0/2/3 limits the booster heater automatically in relation to heat pump operation time in domestic water heating mode.
Ta ke care that [8-03] is always in relation with the maximum running time [8-01].
Example: [4-03]=1
Quick heating settings
Energy saving settings
[8-01] 20~60 min 30 min [8-03] [8-01] + 20 min 20 min
(default)
0
[5-03] [4-02]
t Time
T
Ambient (outdoor) temperature
A
maximum running time anti-recycle time
0
T
A
[F-01] 35°C
The full advantage of [8-04] will be applicable if setting [4-03] is not 1.
[9] Cooling and heating set point ranges
The purpose of this field setting is to prevent the user from selecting a wrong (i.e., too hot or too cold) leaving water temperature. Thereto the heating temperature set point range and the cooling temperature set point range available to the user can be configured.
CAUTION
In case of a floor heating application, it is important to limit the maximum leaving water temperature at heating operation according to the specifications of the floor heating installation.
In case of a floor cooling application, it is important to limit the minimum leaving water temperature at cooling operation (field setting of parameter [9-03]) to 16~18°C to prevent condensation on the floor.
[9-00] Heating set point upper limit: maximum leaving water temperature for heating operation.
[9-01] Heating set point lower limit: minimum leaving water temperature for heating operation.
[9-02] Cooling set point upper limit: maximum leaving water temperature for cooling operation.
[9-03] Cooling set point lower limit: minimum leaving water temperature for cooling operation.
[9-04] Overshoot setting: defines how much the water temperature may rise above the set point before the compressor stops. This function is only applicable in heating mode.
T
A
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
34
[A] Quiet mode
This field setting allows to select the desired quiet mode. Two quiet modes are available: quiet mode A and quiet mode B.
In quiet mode A, priority is given to the unit operating quietly under all circumstances. Fan and compressor speed (and thus performance) will be limited to a certain percentage of the speed at normal operation. In certain cases, this might result in reduced performance.
In quiet mode B, quiet operation might be overridden when higher performance is required. In certain cases, this might result in less quiet operation of the unit to meet the requested performance.
[A-00] Quiet mode type: defines whether quiet mode A (0) or quiet mode B (2) is selected.
[A-01] Parameter 01: do not change this setting. Leave it set to its default value.
NOTE
Do not set other values than the ones mentioned.
[C-04] Bivalent hysteresis: defines the temperature difference between bivalent ON temperature and bivalent OFF temperature.
Permission signal X1–X2 (EKRP1HB)
closed
[C-04]
open
T
[C-03]
T
Outdoor temperature
A
A
CAUTION
Make sure to observe all rules mentioned in application 5 when bivalent operation function is enabled.
Daikin shall not be held liable for any damage resulting from failure to observe this rule.
[C] Setup on EKRP1HB digital I/O PCB
Solar priority mode
[C-00] Solar priority mode setting: for information concerning the EKSOLHW solar kit, refer to the installation manual of that kit.
Alarm output logic
[C-01] Alarm output logic: defines the logic of the alarm output on the EKRP1HB digital I/O PCB. [C-01]=0, the alarm output will be powered when an alarm occurs (default). [C-01]=1, the alarm output will not be powered when an alarm occurs. This field setting allows for distinction between detection of an alarm and detection of a power failure to the unit.
No power supply
[C-01] Alarm No alarm
0 (default)
1 Open output Closed output Open output
Closed output Open output Open output
to unit
Bivalent operation
Applies only to installations with an auxiliary boiler (alternating operation, parallel connected). The purpose of this function is to determine —based on the outdoor temperature— which heating source can/will provide the space heating, either the Daikin unit or an auxiliary boiler.
The field setting "bivalent operation" apply only the unit space heating operation and the permission signal for the auxiliary boiler.
When the "bivalent operation" function is enabled, the unit will stop automatically in space heating operation when the outdoor temperature drops below "bivalent ON temperature" and the permission signal for the auxiliary boiler becomes active.
When the bivalent operation function is disabled, the space heating by unit is possible at all outdoor temperatures (see operation ranges) and permission signal for auxiliary boiler is always disactivated.
[C-02] Bivalent operation status: defines whether bivalent operation is enabled (1) or disabled (0).
[C-03] Bivalent ON temperature: defines the outdoor temperature below which the permission signal for the auxiliary boiler will be active (closed, KCR on EKRP1HB) and space heating by indoor unit will be stopped.
In case the unit is single phase, the combination of setting [4-03]=0/2 with bivalent operation at low outdoor temperature can result in domestic hot water shortage.
The bivalent operation function has no impact on the domestic water heating mode. The domestic hot water is still and only heated by the unit.
The permission signal for the auxiliary boiler is located on the EKRP1HB (digital I/O PCB). When it is activated, the contact X1, X2 is closed and open when it is disactivated. See figure for the schematic location of this contact.
X1 X2 X3 X4
X2M
OFF ON
SS1
X1M
YC Y1 Y2 Y3 Y4
[D] Benefit kWh rate power supply/Local shift value weather dependent
Benefit kWh rate power supply
[D-00] Switching off heaters: Defines which heaters are switched off when the benefit kWh rate signal of the electricity company is received. If [D-01]=1 or 2 and the benefit kWh rate signal of the electricity company is received, following devices will be switched off:
[D-00] Compressor Back up heater Booster heater
0 (default)
1Forced off Forced off Permitted 2Forced off Permitted Forced off 3Forced off Permitted Permitted
Forced off Forced off Forced off
Installation manual
35
[D-00] settings 1, 2 and 3 are only meaningful if the benefit kWh rate power supply is of the type that power supply is not interrupted,
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
[D-01] Unit connection to benefit kWh rate power supply: Defines whether or not the outdoor unit is connected to a benefit kWh rate power supply. If [D-01]=0, the unit is connected to a normal power supply (default value). If [D-01]=1 or 2, the unit is connected to a benefit kWh rate power supply. In this case the wiring requires specific installation like explained in "Connection to a benefit kWh
rate power supply" on page 23.
When parameter [D-01]=1 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will open and the unit will go in forced off mode
(1)
. When parameter [D-01]=2 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will close and the unit will go in forced off mode
(2)
.
Local shift value weather dependent
The local shift value weather dependent field setting is only relevant in case weather dependent set point (see field setting "[1] Weather
dependent set point (heating operation only)" on page 29) is
selected.
[D-03] Local shift value weather dependent: determines the shift value of the weather dependent set point around outdoor temperature of 0°C.
T
t
[1-02]
local shift value
[1-03]
range
[F] Option setup
Pump operation
The pump operation field setting apply to the pump operation logic only when DIP switch SS2-3 is OFF.
When the pump operation function is disabled the pump will stop if the outdoor temperature is higher than the value set by [4-02] or if the outdoor temperature drops below the value set by [F-01]. When the pump operation is enabled, the pump operation is possible at all outdoor temperatures. Refer to "Pump operation configuration" on
page 26.
[F-00] Pump operation: specifies whether the pump operation function is enabled (1) or disabled (0).
Space cooling permission
[F-01] Space cooling permission temperature: defines the outdoor temperature below which space cooling is turned off.
This function is only valid for E(D/B) when space cooling is selected.
Bottom plate heater control
Applies only to installation with an outdoor unit E(D/B)LQ or in case the option bottom plate heater kit is installed.
[F-02] Bottom plate heater ON temperature: defines the outdoor temperature below which the bottom plate heater will be activated by unit in order to prevent ice build-up in the bottom plate of the outdoor unit at lower outdoor temperatures.
[F-03] Bottom plate heater hysteresis: defines the temperature difference between bottom plate heater ON temperature and the bottom plate heater OFF temperature.
[1-00] 32°F
T
t
T
A
range Range
local shift
value
[1-00], [1-01],
[1-02], [1-03]
[D-03]
0— — 1 24 3 44
Target water temperature
Outdoor temperature
Local shift value
Applicable field setting of the weather dependent set point [1]
Outdoor temperature range (TA)
[E] Unit information readout
[E-00] Readout of the software version (example: 23)
[E-01] Readout of the EEPROM version (example: 23)
[E-02] Readout of the unit model identification (example: 11)
[E-03] Readout of the liquid refrigerant temperature
0°C
–2°C~2°C
–4°C~4°C
[1-01]
T
A
Local shift value
2
2
Bottom plate heater
ON
OFF
T
Outdoor temperature
A
CAUTION
The bottom plate heater is controlled via X14A. Make sure [F-04] is correctly set.
Functionality of X14A
[F-04] Functionality of X14A: specifies if the logic of X14A follows the output signal for the solar kit model (EKSOLHW) (0) or if the logic of X14A follows the output for the bottom plate heater (1).
NOTE
Independent from field setting [F-04], the contact X3-X4 (EKRP1HB) follows the logic of the output signal for the solar kit model (EKSOLHW). See figure below for the schematic location of this contact.
X1 X2 X3 X4
[E-04] Readout of the inlet water temperature
NOTE
[E-03] and [E-04] readouts are not permanently refreshed. Temperature readouts are updated after looping through the field setting first codes again only.
X2M
[F-02]
[F-03]
T
A
OFF ON
SS1
(1) When the signal is released again, the voltage free contact will close and the unit
will restart operation. It is therefore important to leave the auto restart function enabled. Refer to "[3] Auto restart" on page 29.
(2) When the signal is released again, the voltage free contact will open and the unit
will restart operation. It is therefore important to leave the auto restart function enabled. Refer to "[3] Auto restart" on page 29.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
X1M
YC Y1 Y2 Y3 Y4
Installation manual
36

Field settings table

First
Second
code
code
Setting name
0 User permission level
00 User permission level
1 Weather dependent set point
00 Low ambient temperature (Lo_A)
01 High ambient temperature (Hi_A)
02 Set point at low ambient temperature (Lo_TI)
03 Set point at high ambient temperature (Hi_TI)
2 Disinfection function
00 Operation interval
01 Status
02 Start time
03 Set point
04 Interval
3 Auto restart
00 Status
4 Backup/booster heater operation and space heating off temperature
00 Status
01 Priority
02 Space heating off temperature
03 Booster heater operation
04 Freeze-up protection function 0
5 Equilibrium temperature and space heating priority temperature
00 Equilibrium temperature status
01 Equilibrium temperature
02 Space heating priority status
03 Space heating priority temperature
04 Set point correction for domestic hot water
temperature
6 DT for heat pump domestic water heating mode
00 Start
01 Stop
02 Not applicable
7 DT for booster heater and dual set point control
00 Domestic hot water step length
01 Hysteresis value booster heater
02 Dual set point control status
03 Second set point heating
04 Second set point cooling
8 Domestic water heating mode timer
00 Minimum running time
01 Maximum running time
02 Anti-recycling time
03 Booster heater delay time
04 Additional running time at [4-02]/[F-01]
Installer setting at variance with default value
Default
value
3 2/3 1
–10 –20~5 1 °C
15 10~20 1 °C
40 25~55 1 °C
25 25~55 1 °C
Fri
1 (ON) 0/1
23:00 0:00~23:00 1:00 hour
70 40~80 5 °C
10 5~60 5 min
0 (ON) 0/1
1 (ON) 0/1
0 (OFF) 0/1/2
35 14~35 1 °C
3 0/1/2/3
(active)
Read
only
1 (ON) 0/1
0 –15~35 1 °C
0 (OFF) 0/1
0 –15~20 1 °C
10 0~20 1 °C
2 2~20 1 °C
2 0~10 1 °C
0 Read only
0 0~4 1 °C
2 2~40 1 °C
0 0/1
10 1~24 / 25~55 1 °C
7 5~22 1 °C
5 0~20 1 min
30 5~60 5 min
3 0~10 0.5 hour
50 20~95 5 min
95 0~95 5 min
Range Step UnitDate Va lue Date Va lue
Mon~Sun,
All
———
——
Installation manual
37
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
First code
Second code
Setting name
Installer setting at variance with default value
9 Cooling and heating set point ranges
00 Heating set point upper limit
01 Heating set point lower limit
02 Cooling set point upper limit
03 Cooling set point lower limit
04 Overshoot setting
(a)
A Quiet mode
00 Quiet mode type
01 Parameter 01
02 Not applicable
03 Not applicable
04 Not applicable
b Not applicable
00 Not applicable
01 Not applicable
02 Not applicable
03 Not applicable
04 Not applicable
C Setup on EKRP1HB digital I/O PCB
00 Solar priority mode setting
01 Alarm output logic
02 Bivalent operation status
03 Bivalent ON temperature
04 Bivalent hysteresis
D Benefit kWh rate power supply/local shift value weather dependent
00 Switching off heaters
01 Unit connection to benefit kWh rate power supply
02 Not applicable. Do not change the default value.
03 Local shift value weather dependent
E Unit information readout
00 Software version Read
01 EEPROM version Read
02 Unit model identification Read
03 Liquid refrigerant temperature Read
04 Inlet water temperature Read
F Option setup
00 Pump operation
01 Space cooling permission temperature
02 Bottom plate heater ON temperature
03 Bottom plate heater hysteresis
04 Functionality of X14A
(a) Only possible to modify the first 3 minutes after power ON.
Default
value
Range Step UnitDate Va lue Date Va lue
55 37~55 1 °C
25 15~37 1 °C
22 18~22 1 °C
5 5~18 1 °C
1 1~4 1 °C
0 0/2
3———
1 Read only
0 Read only
0 Read only
0 Read only
0 Read only
0 Read only
0 Read only
0 Read only
0 0/1 1
0 0/1
0 0/1
0 –25~25 1 °C
3 2~10 1 °C
0 0/1/2/3
0 (OFF) 0/1/2
0———
0 0/1/2/3/4
only
only
only
only
only
———
———
———
——°C
——°C
0 0/1
20 10~35 1 °C
3 3~10 1 °C
5 2~5 1 °C
1 0/1
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
38

TEST RUN AND FINAL CHECK

Test run operation (manual)

The installer is obliged to verify correct operation of unit after installation.

Final check

Before switching on the unit, read following recommendations:
When the complete installation and all necessary settings have been carried out, close all front panels of the unit and refit the unit cover.
The service panel of the switch box may only be opened by a licensed electrician for maintenance purposes.
DANGER
Never leave the unit unattended during installation or servicing. When the service panel is removed live parts can be easily touched by accident..
NOTE
Note that during the first running period of the unit, required power input may be higher than stated on the nameplate of the unit. This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption.

Pre-run checks

Items to check
Electrical wiring Inter-unit wiring Earth wire
Is the wiring as mentioned on the wiring diagram? Make sure no wiring has been forgotten and that there are no missing phases or reverse phases.
Is the unit properly earthed?
Is the wiring between units connected in series
correct?
Are any of the wiring attachment screws loose?
Is the insulation resistance at least 1 M?
- Use a 500 V mega-tester when measuring
insulation.
- Do not use a mega-tester for low-voltage circuits.

Automatic test run

When the unit is put into operation (by pressing the y button) for the first time, the system will automatically perform a test run in cooling mode. The test run will take up to 3 minutes, during which no specific indication is given on the user interface.
During the automatic test run, it is important to ensure that the water temperature does not drop below 10°C, which might activate the freeze-up protection and thereby prevent the test run to finish. Should the water temperature drop below 10°C, press the h/c button so the h icon is displayed. This will activate the backup heater during the automatic test run and raise the water temperature sufficiently.
If the automatic test run has ended successfully, the system will automatically resume normal operation.
If there are misconnections or malfunctions, an error code will be displayed on the user interface. To resolve the error codes, see "Error
codes" on page 42.
If required, the installer can perform a manual test run operation at any time to check correct operation of heating, cooling and domestic water heating.
Procedure
1 Push the z button 4 times so the t icon will be displayed. 2 Depending on the unit model, heating operation, cooling
operation or both must be tested as follows (when no action is performed, the user interface will return to normal mode after 10 seconds or by pressing the z button once):
•To test the heating operation push the h/c button so the h icon is displayed. To start the test run operation press the y button.
•To test the cooling operation push the h/c button so the c icon is displayed. To start the test run operation press the y button.
•To test the domestic water heating operation push the v button. The test run operation will start without pressing the y button.
3 The test run operation will end automatically after 30 minutes or
when reaching the set temperature. The test run operation can be stopped manually by pressing the z button once. If there are misconnections or malfunctions, an error code will be displayed on the user interface. Otherwise, the user interface will return to normal operation.
4 To resolve the error codes, see "Error codes" on page 42.
To display the last resolved error code, push the z button 1 time. Push the z button again 4 times to return to normal mode.
NOTE
It is not possible to perform a test run if a forced operation from the unit is in progress. Should forced operation be started during a test run, the test run will be aborted.
Never leave the unit unattended with an open front panel during test run.
To protect the compressor, make sure to turn on the power supply 6 hours before starting operation.
NOTE
When the unit is put into pump down operation, the automatic test run flag will be cleared. The next time the system is put into operation, the automatic test run will be executed again.
After finishing automatic test run or power ON/OFF, the compressor will operate in the selected operation mode and continue for certain time (set point on the remote controller is overruled during this operation).
Installation manual
39
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A

MAINTENANCE AND SERVICE

In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals.
This maintenance has to be carried out by your local Daikin technician.
DANGER: ELECTRIC SHOCK
Before carrying out any maintenance or repair activity, always switch off the circuit breaker on the supply panel, remove the fuses (or switch off the circuit breakers) or open protection devices of the unit.
Make sure that before starting any maintenance or repair activity, also the power supply to the outdoor unit is switched off.
Do not touch live parts for 10 minutes after the power supply is turned off because of high voltage risk.
The heater of the compressor may operate even in stop mode.
Please note that some sections of the electric component box are hot.
In order to prevent damage to the PCB, first eliminate static electricity by touching a metal part (e.g. stop valve) with your hand. Then pull out the connector.
After measuring the residual voltage, pull out the outdoor fan connector.
Make sure you do not touch a conductive section.
The outdoor fan may rotate due to strong backblow
wind, causing the capacitor to charge. This may result in an electric shock.
Make sure you do not touch a conductive section.
Do not rinse the unit. This may cause electric shocks
or fire.
When service panels are removed, live parts can be easily touched by accident. Never leave the unit unattended during installation or servicing when service panel is removed.
After maintenance, make sure the outdoor fan connector is connected again. Otherwise, the unit may break down.
Play it safe!
Touch a metal part by hand (such as the stop valve) in order to eliminate static electricity and to protect the PCB before performing service.
DANGER
Do not touch water pipes during and immediately after operation as the pipes may be hot. Your hand may suffer burns. To avoid injury, give the piping time to return to normal temperature or be sure to wear proper gloves.
WARNING
Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
Do not touch the internal parts (pump, backup heater, etc.) during and immediately after operation.
Your hands may suffer burns if you touch the internal parts. To avoid injury, give the internal parts time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
The described checks must be executed at least once a year by qualified personnel.
1 Water pressure
Check if the water pressure is above 1 bar. If necessary add water.
2 Water filter
Clean the water filter.
3 Water pressure relief valve
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter-clockwise:
If you do not hear a clacking sound, contact your local dealer.
In case the water keeps running out of the unit, close both
the water inlet and outlet shut-off valves first and then contact your local dealer.
4 Pressure relief valve hose
Check that the pressure relief valve hose is positioned appropriately to drain the water.
5 Backup heater vessel insulation cover
Check that the backup heater insulation cover is fastened tightly around the backup heater vessel.
6 Domestic hot water tank pressure relief valve (field supply)
Applies only to installations with a domestic hot water tank. Check for correct operation of the pressure relief valve on the
domestic hot water tank.
7 Domestic hot water tank booster heater
Applies only to installations with a domestic hot water tank. It is advisable to remove lime buildup on the booster heater to
extend its life span, especially in regions with hard water. To do so, drain the domestic hot water tank, remove the booster heater from the domestic hot water tank and immerse in a bucket (or similar) with lime-removing product for 24 hours.
8 Unit switch box
Carry out a thorough visual inspection of the switch box and look for obvious defects such as loose connections or defective wiring.
Check for correct operation of contactors K1M, K3M, K5M (applications with domestic hot water tank only) and K4M by use of an ohm meter. All contacts of these contactors must be in open position.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
40
9 In case of use of glycol
(Refer to Caution: "Use of glycol" on page 16) Document the glycol concentration and the pH-value in the
system at least once a year.
A pH-value below 8.0 indicates that a significant portion of the inhibitor has been depleted and that more inhibitor needs to be added.
When the pH-value is below 7.0 then oxidation of the glycol occurred, the system should be drained and flushed thoroughly before severe damage occurs.
Make sure that the disposal of the glycol solution is done in accordance with relevant local laws and regulations.

TROUBLESHOOTING

This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.
This troubleshooting and related corrective actions may only be carried out by your local Daikin technician.

General guidelines

Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.

General symptoms

Symptom 1: The unit is turned on (y LED is lit) but the unit is not heating or cooling as expected
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not correct.
The water flow is too low.
The water volume in the installation is too low.
Symptom 2: The unit is turned on but the compressor is not starting (space heating or domestic water heating)
Check the controller set point.
• Check that all shut off valves of the water circuit are completely open.
• Check if the water filter needs cleaning.
• Make sure there is no air in the system (purge air).
• Check on the manometer that there is sufficient water pressure. The water pressure must be >1 bar (water is cold).
• Check that the pump speed setting is on the highest speed.
• Make sure that the expansion vessel is not broken.
• Check that the resistance in the water circuit is not too high for the pump (refer to "Setting the pump
speed" on page 27).
Make sure that the water volume in the installation is above the minimum required value (refer to "Checking
the water volume and expansion vessel pre-pressure" on page 14).
DANGER
When carrying out an inspection on the switch box of the unit, always make sure that the main switch of the unit is switched off.
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no circumstances safety devices may be bridged or changed to a value other than the factory setting. If the cause of the problem cannot be found, call your local dealer.
If the pressure relief valve is not working correctly and is to be replaced, always reconnect the flexible hose attached to the pressure relief valve, to avoid water dripping out of the unit!
NOTE
For problems related to the optional solar kit for domestic water heating, refer to the troubleshooting in the installation manual of that kit.
POSSIBLE CAUSES CORRECTIVE ACTION
The unit must start up out of its operation range (the water temperature is too low).
The benefit kWh rate power supply settings and electrical connections do not match.
The benefit kWh rate signal was sent by the electricity company.
Symptom 3: Pump is making noise (cavitation)
POSSIBLE CAUSES CORRECTIVE ACTION There is air in the system. Purge air. Water pressure at pump inlet is too
low.
In case of low water temperature, the system utilizes the backup heater to reach the minimum water temperature first (15°C).
• Check that the backup heater power supply is correct.
• Check that the backup heater thermal fuse is closed.
• Check that the backup heater thermal protector is not activated.
• Check that the backup heater contactors are not broken.
If [D-01]=1 or 2, the wiring requires specific installation like illustrated in
"Connection to a benefit kWh rate power supply" on page 23. Other
correctly installed configurations are possible, but are to be specific for the type of benefit kWh rate power supply type at this specific site.
Wait for the power to return.
• Check on the manometer that there is sufficient water pressure. The water pressure must be >1 bar (water is cold).
• Check that the manometer is not broken.
• Check that the expansion vessel is not broken.
• Check that the setting of the pre­pressure of the expansion vessel is correct (refer to "Setting the pre-
pressure of the expansion vessel" on page 15).
Installation manual
41
Symptom 4: The water pressure relief valve opens
POSSIBLE CAUSES CORRECTIVE ACTION The expansion vessel is broken. Replace the expansion vessel. The water volume in the installation
is too high.
Make sure that the water volume in the installation is under the maximum allowed value (refer to
"Checking the water volume and expansion vessel pre-pressure" on page 14).
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Symptom 5: The water pressure relief valve leaks
POSSIBLE CAUSES CORRECTIVE ACTION
Dirt is blocking the water pressure relief valve outlet.
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter clockwise:
• If you do not hear a clacking sound, contact your local dealer.
•In case the water keeps running out of the unit, close both the water inlet and outlet shut-off valves first and then contact your local dealer.
Symptom 6: The user interface displays "nn
nn
" when pressing
certain buttons
POSSIBLE CAUSES CORRECTIVE ACTION
The current permission level is set to a level that prevents using the pressed button.
Change the "user permission level" field setting ([0-00], see "Field
settings" on page 28.
Symptom 7: Space heating capacity shortage at low outdoor temperatures
POSSIBLE CAUSES CORRECTIVE ACTION
Backup heater operation is not activated.
Check that the "backup heater operation status" field setting [4-00] is turned on, see "Field settings" on
page 28.
Check whether or not the thermal protector of the backup heater has been activated (refer to Main
components, "Backup heater thermal protector" on page 13 for
location of the reset button). Check if booster heater and backup heater are configured to operate simultaneously (field setting [4-01], see "Field settings" on page 28) Check whether or not the thermal fuse of the backup heater is blown (refer to "Main components",
"Backup heater thermal fuse" on page 13 for location of the reset
button).
The backup heater equilibrium temperature has not been configured correctly.
Too much heat pump capacity is used for heating domestic hot water (applies only to installations with a domestic hot water tank).
Raise the field setting [5-01] to activate backup heater operation at a higher outdoor temperature.
Check that the temperature configured appropriately:
• Make sure that the 'space heating
• Raise the 'space heating priority
'equilibrium temperature'
'space heating priority
' field settings are
priority status' field setting [5-02] is enabled.
temperature' field setting [5-03] to activate booster heater operation at a higher outdoor temperature.

Error codes

When a safety device is activated, the user interface LED will be flashing, and an error code will be displayed.
A list of all errors and corrective actions can be found in the table below.
Reset the safety by turning the unit OFF and back ON.
Instruction to turn the unit OFF User interface mode
(heating/cooling =)
ON ON 1 time 1 time ON OFF 1 time OFF ON —1 time OFF OFF ——
In case this procedure for resetting the safety is not successful, contact your local dealer.
Error code
Failure cause Corrective action
80 Inlet water temperature
thermistor failure (inlet water thermistor broken)
81 Outlet water temperature
thermistor failure (outlet water temperature sensor broken)
89 Water heat exchanger freeze-up
failure (due to water flow too low) Water heat exchanger freeze-up
failure (due to refrigerant shortage)
7H Flow failure (water flow too low
or no water flow at all, minimum required water flow is 16 l/min.
8H Outlet water temperature of unit
too high (>65°C)
A1 Hydraulic PCB defective Contact your local dealer. A5 Too low (during cooling
operation) or too high (during heating operation) refrigerant temperature (measured by R13T)
Domestic water heating mode (w)
Push the y button
Push the v button
Contact your local dealer.
Contact your local dealer.
Refer to error code 7H.
Contact your local dealer.
• Check that all shut off valves of the water circuit are completely open.
• Check if the water filter needs cleaning.
Check that the unit is operating within its operating range (refer to
specifications" on page 43
•Also refer to "Charging water" on
page 17.
• Make sure there is no air in the system (purge air).
• Check on the manometer that there is sufficient water pressure. The water pressure must be >1 bar (water is cold).
• Check that the pump speed setting is on the highest speed.
• Make sure that the expansion vessel is not broken.
• Check that the resistance in the water circuit is not too high for the pump (refer to "Setting the
pump speed" on page 27).
• If this error occurs at defrost operation (during space heating or domestic water heating), make sure that the backup heater power supply is wired correctly and that fuses are not blown.
• Check that the pump fuse (FU2) and PCB fuse (FU1) are not blown.
• Check that the contactor of the electric backup heater is not short circuited.
• Check that the outlet water thermistor is giving the correct read out.
"Technical
).
Contact your local dealer.
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
Installation manual
42
Error code
Failure cause Corrective action
AA Booster heater thermal protector
is open (applies only to
Reset the thermal protector
installations with a domestic hot water tank)
Backup heater thermal protector is open.
Reset the thermal protector by pressing the reset button (refer to "Main components" on
page 12 for location of the reset
button)
Check the reset button of the thermal protector.
Contact your local dealer.
If both the thermal protector and the controller are reset, but the AA error code persists, the backup heater thermal fuse has blown.
C0 Flow switch failure (flow switch
remains closed while pump is stopped)
C4 Heat exchanger thermistor
failure (heat exchanger
Check that the flow switch is not clogged with dirt.
Contact your local dealer.
temperature sensor broken)
E1 Compressor PCB defective Contact your local dealer. E3 Abnormal high pressure Check that the unit is operating
within its operating range (refer to "Technical specifications" on
page 43).
Contact your local dealer.
E4 Actuation of low pressure sensor Check that the unit is operating
within its operating range (refer to "Technical specifications" on
page 43).
Contact your local dealer.
E5 Overload activation of
compressor
Check that the unit is operating within its operating range (refer to "Technical specifications" on
page 43).
Contact your local dealer.
E7 Fan lock failure (fan is locked) Check if the fan is not obstructed
by dirt. If the fan is not obstructed, contact your local dealer.
E9 Malfunction of electronic
Contact your local dealer.
expansion valve
EC Domestic hot water temperature
too high (>89°C)
F3 Too high discharge temperature
(e.g. due to outdoor coil blockage)
• Check that the contactor of the electric booster heater is not short circuited.
• Check that the domestic hot water thermistor is giving the correct read out.
Clean the outdoor coil. If the coil is clean, contact your local dealer.
H3 Malfunctioning HPS system Contact your local dealer. H9 Outdoor temperature thermistor
failure (outdoor thermistor is broken)
HC Domestic hot water tank
thermistor failure
Contact your local dealer.
Contact your local dealer.
J1 Malfunction of pressure sensor Contact your local dealer. J3 Discharge pipe thermistor failure Contact your local dealer. J5 Suction pipe unit thermistor
failure
J6 Aircoil thermistor frost detection
failure
J7 Aircoil thermistor mean
temperature failure
Contact your local dealer.
Contact your local dealer.
Contact your local dealer.
J8 Liquid pipe unit thermistor failure Contact your local dealer. L4 Electric component failure Contact your local dealer. L5 Electric component failure Contact your local dealer. L8 Electric component failure Contact your local dealer. L9 Electric component failure Contact your local dealer. LC Electric component failure Contact your local dealer. P1 PCB failure Contact your local dealer. P4 Electric component failure Contact your local dealer. PJ Failure of capacity setting Contact your local dealer. U0 Refrigerant failure (due to
refrigerant leak)
Contact your local dealer.
Error code
Failure cause Corrective action
U1 Power supply cables are
connected in the reverse phase instead of the normal phase.
Connect the power supply cables in normal phase. Change any two of the three power supply cables (L1, L2 , L3) to correct phase.
U2 Main circuit voltage failure Contact your local dealer. U4 Communication failure Contact your local dealer. U5 Communication failure Contact your local dealer. U7 Communication failure Contact your local dealer. UA Communication failure Contact your local dealer.

TECHNICAL SPECIFICATIONS

General

Nominal capacity
• heating
• cooling
Dimensions H x W x D 1418 x 1435 x 382 mm Weight
• machine weight
• operation weight
Connections
•water inlet/outlet
•water drain
Expansion vessel
•volume
• maximum working pressure (MWP)
Pump
•type
•no. of speed
Internal water volume 5.5 l Pressure relief valve
water circuit Operation range - water side
• heating
• cooling
Operation range - air side
• heating
• cooling
• domestic hot water by heat pump
(a) FBSP = Female British Standard Pipe (b) EDL and EBL models can reach –20°C / EDL_W1 and EBL_W1 models can
reach –25°C, but this is without capacity guarantee
Electrical specifications
Standard unit (power supply via unit)
•power supply
• nominal running current
Backup heater
•power supply
• maximum running current
EDLQ EDHQ EBLQ EBHQ
Refer to the Technical Data Refer to the Technical Data
180 kg 185 kg
G 5/4" FBSP
(a)
hose nipple
10 l
3 bar
water cooled
2
3 bar
+15~+55°C +15~+55°C
+5~+22°C
–15~+35°C
(b)
–15~+35°C
+10~+46°C
–15~+35°C
(b)
V3 models (1~) W1 models (3N~)
–15~+35°C
230 V 50 Hz 1P 400 V 50 Hz 3P
5.8 A
See "Connection of the backup heater power
supply" on page 21
See "Connection of the backup heater power
supply" on page 21
(b)
(b)
Installation manual
43
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
NOTES NOTES
4PW57621-1A
Copyright © Daikin
Loading...